Transcript
“Mega”Series Emergency LED Luminaires & Energy Saving Lamp
Description
Connection Diagram
LED Luminaires & Energy Saving Lamp can be used with emergency Kit. The Kits contain battery packs that can light up the lamp for 2 or 3 hours duration.
ORANGE ORANGE BLACK
16 15 14 13 12 BATTERY 11 10 9
Standards Fluorescent Tube
TRANSFORMER
TEST BUTTON INDICATOR
• BS EN 60598-2-22 • BS EN 61347-2-7 • BS 5266-1 • FSD PPA 104(A) 4th Revision
LED Luminaires
CRYSTALITE INVERTER
YELLOW GREEN
220V 50Hz LED LUMINAIRES or ENERGY SAVING LAMP
N/o
1 2 3 4 5 6 7 8
L/o A L NEUTRAL
N
Energy Saving Lamp
Compact Fluorescent
Tungsten Halogen
LED & ESL
Technical Data Model Suitable Lamps ATS
CC-M-LED-15-K2
CC-M-LED-19-K2
CC-M-LED-25-K2
CC-M-LED-30-K2
8W Max.
16W Max.
20W Max.
26W Max.
30W Max.
Emergency Output
70%
Discharge Duration
2 Hours
Battery Line Voltage Exit Sign
CC-M-LED-7-K2
Low Voltage Discharge Protection
Sealed Ni-cad / Ni-mh High Temperature Rechargeable Battery 10 x 2.2Ah, 12V
10 x 4.0Ah, 12V
10 x 7.0Ah, 12V
0°C - 50°C
Transfer Time
< 0.3 Second
Recharge Period
Metal Case (L x W x H)
10 x 7.0Ah, 12V
Electronic Protection for approximate 1V per cell
Operating Temperature
Compliance
10 x 5.0Ah, 12V
A/C 220V~230V +6%, -10% 50Hz
12 Hours BS EN 60598-2-22, BS EN 61347-2-7, BS 5266-1, FSD PPA 104A (4th Revision) MB-818 390 x 160 x 50 mm
MB-812 340 x 155 x 70 mm
Option: This Series could support both Normal & Dimmable Energy Saving Lamp
53
Self-Contained Emergency Lighting System
Technical Data Model Suitable Lamps
CC-M-LED-7-K3
CC-M-LED-15-K3
CC-M-LED-19-K3
8W Max.
16W Max.
20W Max.
Emergency Output
70%
Discharge Duration
3 Hours
Battery
Sealed Ni-cad / Ni-mh High Temperature Rechargeable Battery 10 x 4.0Ah, 12V
10 x 5.0Ah, 12V
Line Voltage Low Voltage Discharge Protection
Electronic Protection for approximate 1V per cell
Operating Temperature
0°C - 50°C
Transfer Time Recharge Period Compliance Metal Case (L x W x H)
10 x 7.0Ah, 12V
A/C 220V~230V +6%, -10% 50Hz
< 0.3 Second 12 Hours for 2 Hours discharge / 24 Hours for 3 Hours discharge
Fluorescent Tube
BS EN 60598-2-22, BS EN 61347-2-7, BS 5266-1, FSD PPA 104A (4th Revision) MB-818 390 x 160 x 50 mm
MB-812 340 x 155 x 70 mm
Option: This Series could support both Normal & Dimmable Energy Saving Lamp Compact Fluorescent
Additional Function for Mega Series Description
Connection Diagram
Some of the LED Luminaires have high Wattage consumption that is difficult to support by emergency kit. If the LED Luminaire with a build-in 1-10V Dimmer, it can be used with Crystalite emergency Kit. The Kits contain battery packs that can light up the lamp for 2 or 3 hours duration.
Maintained Type 長明式 D+ DDo+ ORANGE ORANGE TRANSFORMER BLACK
Standards
TEST BUTTON INDICATOR
• BS EN 60598-2-22 • BS EN 61347-2-7 • BS 5266-1 • FSD PPA 104A (4th Revision)
Technical Data Model Suitable Lamps
Tungsten Halogen
BATTERY
20 19 18 17 16 15 14 13 12 11 10 9
YELLOW GREEN
CRYSTALITE INVERTER + DIMMER _ IN + DIMMER _ OUT
1 2 3 4 5 6 7 8
CC-M-LED-15-DK2
Compliance Metal Case (L x W x H)
L N
NEUTRAL
CC-M-LED-15-DK3
High Wattage LED Luminaire with build-in 1-10V Dimmer (~15W / AC Power) %
Recharge Period
LED & ESL
A
ATS
2 Hours 3 Hours Sealed Ni-cad / Ni-mh High Temperature Rechargeable Battery 10 x 4.0Ah, 12V 10 x 5.0Ah, 12V
Transfer Time
220V 50Hz LUMINAIRES with 1-10V Dimmer
LED Luminaires with 1-10V dimmer
Discharge Duration
Line Voltage Low Voltage Discharge Protection Operating Temperature
N/o L/o
Emergency Output
Battery
Do-
Dimmer Input Dimmer Output
Exit Sign
A/C 220V~230V +6%, -10% 50Hz Electronic Protection for approximate 1V per cell 0°C - 50°C < 0.3 Second 12 Hours for 2 Hours discharge / 24 Hours for 3 Hours discharge BS EN 60598-2-22, BS EN 61347-2-7, BS 5266-1, FSD PPA 104A (4th Revision) MB-808 440 x 160 x 50 mm
Self-Contained Emergency Lighting System
54