Transcript
BA 242F/00/en/02.03 Nr. 52011930 Valid as of software version: V 01.02.00 (amplifier) V 01.02.00 (communication)
levelflex M FMP 40 HART/4...20 mA Guided Level-Radar
Operating Instructions
HART
R
FIELD COMMUNICATION PROTOCOL
Brief operating instructions
Levelflex M FMP 40 with HART/4...20 mA
Brief operating instructions KA 189F/00/a2/03.02 52012501 000 measured value -
+
Contrast:
+
or
+
E
E
Group selection
-
E
+
002 tank properties
003 medium property
004 process cond.
01 safety settings
- standard - aluminium tank - plastic tank - bypass/pipe - coax-probe - concrete wall
- unknown - 1.4 … 1.6 - 1.6 … 1.9 - 1.9 … 2.5 - 2.5 … 4 -4…7 ->7
input E input F D and L are - standard (see sketch) (see sketch) displayed - fast change - slow change - test: no filter
03 length adjustment
05 extended calibr.
030 end of probe - free - tie down isolated - tie down gnd.
09 display
092 language
0E envelope curve
09B recording curve - envel. curve - substracted signal - single curve - cyclic - mapping 0A3 0A1 0A0 reset previous present error error
04 linearisation
0A diagnostics 0C system parameters
008 dist./ meas value
E
00 basic setup +
-
Levelflex M - Brief operating instructions
031 probe length
… …
005 empty calibr.
006 full calibr.
008 dist./ meas value
051 check distance
052 range of mapping
053 start mapping
confirm suggestion or specify range
reference point of 033 034 measurement probe determine length length UB If shortened threaded please enter probe length here. connection ¾ or 1 ½ BSP (G ¾ or G 1½) ¾ or 1½ NPT: reference point of measurement LB
032 probe
09A plot settings
E F
LN
min.level
0A4 unlock parameter
… …
UB = upper blocking distance LB = lower bllocking distance LN = probe lenght
(333 = reset customer parameters) = 100: unlocked ≠ 100: locked
52012501
Note! This operating manual explains the installation and initial start-up for the level transmitter measuring device. All functions that are required for a typical measuring task are taken into account here. In addition, the Levelflex M provides many other functions that are not included in this operating manual, such as optimising the measuring point and converting the measured values. An overview of all device functions can be found on Page 84. The operating manual BA 245F/00/en provides an extensive description of all device functions – Description of the device functions for Levelflex M, which can also be found on the enclosed CD-ROM.
2
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
Table of contents
Table of contents 1
Safety instructions . . . . . . . . . . . . . . . . . 4
6
Commissioning . . . . . . . . . . . . . . . . . . . 46
1.1 1.2 1.3 1.4
Designated use . . . . . . . . . . . . . . . . . . . . . . . . Installation, commissioning and operation . . . Operational safety . . . . . . . . . . . . . . . . . . . . . . Notes on safety conventions and symbols . . .
2
Identification . . . . . . . . . . . . . . . . . . . . . . 6
6.1 6.2 6.3 6.4 6.5 6.6 6.7
Function check . . . . . . . . . . . . . . . . . . . . . . . . 46 Switching on the measuring device . . . . . . . . 46 Basic Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Basic Setup with the VU 331 . . . . . . . . . . . . . 49 Blocking distnace . . . . . . . . . . . . . . . . . . . . . . 57 Function "envelope curve display" (0E3) . . . . 59 Basic Setup with the ToF Tool . . . . . . . . . . . . 61
2.1 2.2 2.3 2.4
Device designation . . . . . . . . . . . . . . . . . . . . . Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . Certificates and approvals . . . . . . . . . . . . . . . . Registered trademarks . . . . . . . . . . . . . . . . . .
7
Maintenance . . . . . . . . . . . . . . . . . . . . . . 66
8
Accessories . . . . . . . . . . . . . . . . . . . . . . . 67
9
Trouble-shooting . . . . . . . . . . . . . . . . . 71
9.1 9.2 9.3 9.4 9.5 9.6 9.7 9.8
Trouble-shooting instructions . . . . . . . . . . . . . 71 System error messages . . . . . . . . . . . . . . . . . 72 Application errors . . . . . . . . . . . . . . . . . . . . . . 74 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 Software history . . . . . . . . . . . . . . . . . . . . . . . 79 Contact addresses of Endress+Hauser . . . . . 79
10
Technical data . . . . . . . . . . . . . . . . . . . . 80
4 4 4 5
6 9 9 9
3
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.1 3.2 3.3 3.4 3.5
Quick installation guide . . . . . . . . . . . . . . . . . Incoming acceptance, transport, storage . . . Installation Conditions . . . . . . . . . . . . . . . . . . Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . Post-installation check . . . . . . . . . . . . . . . . . .
4
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.1 4.2 4.3 4.4 4.5
Quick wiring guide . . . . . . . . . . . . . . . . . . . . . Connecting the measuring unit . . . . . . . . . . . Equipotential bonding . . . . . . . . . . . . . . . . . . Degree of protection . . . . . . . . . . . . . . . . . . . Post-connection check . . . . . . . . . . . . . . . . .
5
Operation . . . . . . . . . . . . . . . . . . . . . . . . . 35
11
5.1 5.2 5.3 5.4 5.5
Quick operation guide . . . . . . . . . . . . . . . . . . Display and operating elements . . . . . . . . . . Local operation . . . . . . . . . . . . . . . . . . . . . . . Display and acknowledging error messages HART communication . . . . . . . . . . . . . . . . . .
11.1 Operating menu HART (Display modul), ToF Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 11.2 Operating matrix HART / Commuwin II . . . . . . 86 11.3 Description of functions . . . . . . . . . . . . . . . . . 87 11.4 Function and system design . . . . . . . . . . . . . . 88
10 11 12 13 28
29 31 34 34 34
35 37 39 42 43
10.1 Technical data at a glance . . . . . . . . . . . . . . . 80
Appendix . . . . . . . . . . . . . . . . . . . . . . . . . 84
Index
Endress+Hauser
93
3
1 Safety instructions
Levelflex M FMP 40 with HART/4...20 mA
1
Safety instructions
1.1
Designated use
The Levelflex M FMP 40 is a compact level transmitter for the continuous measurement of solids and liquids, measuring prinziple: Guided Level Radar / TDR: Time Domain Reflectometry).
1.2
Installation, commissioning and operation
The Levelflex M has been designed to operate safely in accordance with current technical, safety and EU standards. If installed incorrectly or used for applications for which it is not intended, however, it is possible that application-related dangers may arise, e.g. product overflow due to incorrect installation or calibration. For this reason, the instrument must be installed, connected, operated and maintained according to the instructions in this manual: personnel must be authorised and suitably qualified. The manual must have been read and understood, and the instructions followed. Modifications and repairs to the device are permissible only when they are expressly approved in the manual.
1.3
Operational safety
Hazardous areas Measuring systems for use in hazardous environments are accompanied by separate "Ex documentation", which is an integral part of this Operating Manual. Strict compliance with the installation instructions and ratings as stated in this supplementary documentation is mandatory. • Ensure that all personnel are suitably qualified. • Observe the specifications in the certificate as well as national and local regulations.
4
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
1.4
1 Safety instructions
Notes on safety conventions and symbols
In order to highlight safety-relevant or alternative operating procedures in the manual, the following conventions have been used, each indicated by a corresponding symbol in the margin. Safety conventions
Explosion protection
Electrical symbols
Endress+Hauser
Symbol
Meaning
#
Warning! A warning highlights actions or procedures which, if not performed correctly, will lead to personal injury, a safety hazard or destruction of the instrument
"
Caution! Caution highlights actions or procedures which, if not performed correctly, may lead to personal injury or incorrect functioning of the instrument
!
Note! A note highlights actions or procedures which, if not performed correctly, may indirectly affect operation or may lead to an instrument response which is not planned
0
Device certified for use in explosion hazardous area If the Levelflex has this symbol embossed on its name plate it can be installed in an explosion hazardous area
-
Explosion hazardous area Symbol used in drawings to indicate explosion hazardous areas. – Devices located in and wiring entering areas with the designation “explosion hazardous areas” must conform with the stated type of protection
.
Safe area (non-explosion hazardous area) Symbol used in drawings to indicate, if necessary, non-explosion hazardous areas. – Devices located in safe areas still require a certificate if their outputs run into explosion hazardous areas.
%
Direct voltage A terminal to which or from which a direct current or voltage may be applied or supplied
&
Alternating voltage A terminal to which or from which an alternating (sine-wave) current or voltage may be applied or supplied
)
Grounded terminal A grounded terminal, which as far as the operator is concerned, is already grounded by means of an earth grounding system
*
Protective grounding (earth) terminal A terminal which must be connected to earth ground prior to making any other connection to the equipment
+
Equipotential connection (earth bonding) A connection made to the plant grounding system which may be of type e.g. neutral star or equipotential line according to national or company practice
5
2 Identification
Levelflex M FMP 40 with HART/4...20 mA
2
Identification
2.1
Device designation
2.1.1
Nameplate
The following technical data are given on the instrument nameplate: Designation according to Directive 94/9/EC and designation of protection
Order No (see Order Information)
ENDRESS+HAUSER LEVELFLEX-M
Serial number
Made in Germany D-79689 Maulburg
Order Code: Ser.-No.:
LN=
Communication variant and supply voltage
IP68 / NEMA 6P PN=
Profibus PA Foundation Fieldbus 90 … 253 V AC 3,5VA 10,5 … 32 V DC 1W 16 … 3 V DC 0,8W 4 … 20 mA HART
TA > 70°C : t >85°C
2-wire 4-wire
if modification X = see sep. label Dat./Insp.:
Patents D01301-A
Reference to additional safety-relevant documentation
Fig. 1
2.1.2
Information on the nameplate of the Levelflex M FMP 40 (example)
Ordering structure
Ordering structure Levelflex M FMP 40 10
20
FMP 40-
Certificates A For non-hazardous areas M FM DIP, Class II, Division 1, Group E-G N.I. N CSA General Purpose P CSA DIP, Class II, Division 1, Group G+coal dust, N.I. S FM IS - Class I/II/III, Division 1, Group A-G N.I. T FM XP - Class I/II/III, Division 1, Group A-G U CSA IS - Class I/II/III, Division 1, Group A-D, G+coal dust, N.I. V CSA XP - Class I/II/III, Division 1, Group A-D, G+coal dust, N.I. 1 ATEX II 1/2 G EEx ia IIC T6 2 ATEX II 1/2 D Alu cover, dust Ex 3 ATEX II 2 G EEx em [ia] IIC T6 4 ATEX II 1/3 D transp. cover, dust Ex 5 ATEX II 1/2 G, II 1/3 D EEx ia IIC T6 Y Special version Probe version, material 1) Type / application A 4 mm rope probe, predominantly bulk solids B 6 mm rope probe, solids K One rod probe 16 mm, predominantly liquids L Coax probe, liquids N Rod probe 6 mm, liquids Y Special version
Material 316 316 316L 316L 316L
Product designation (part 1)
1) Rod and coaxial probes are also available in Alloy C22. In this case the probe rod is fixed to the instrument and can not be dismantled. 6
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
30
2 Identification
Probe length Rope probes: 1000 mm...35000 mm / 40 in...1378 in A mm, 4 mm rope, 316 B mm, 6 mm rope, 316 C in, 1/6" rope, 316 D in, 1/4" rope, 316
K L M N
Rod probes: min. 300 mm...4000 mm / 12 in...157 in mm, rod 16 mm, 316L mm, coax probe, 316L in (0,1 in), rod 16 mm, 316L in (0,1 in), coax probe, 316L
Rod probes: min. 300 mm...2000 mm / 12 in...80 in P mm, rod 6 mm, 316L R in (0,1 in), rod 6 mm, 316L Y Special version 40
50
Sealing 2 FKM O-ring (e.g. Viton) 3 EPDM O-ring 4 FFKM O-ring (e.g. Kalrez) 9 Special version
Process connection, material Threaded connection Material CNJ ¾" NPT 316L CRJ G ¾", ISO 228 1.4435 GNJ 1½" NPT 316L GRJ G 1½", ISO 228 1.4435
CFJ CGJ CMJ CQJ CTJ CWJ CXJ ACJ ADJ AEJ AFJ ALJ AMJ APJ AQJ AWJ A3J KDJ KEJ KLJ KPJ YY9 60
FMP 40-
Endress+Hauser
temperature -30° C...+150° C temperature -40° C...+120° C temperature -5° C...+150° C
Flange Dia/Pressure DN40 PN40 DN50 PN40 DN80 PN16 DN100 PN16 DN100 PN40 DN150 PN16 DN200 PN16 1½"/150 lbs 1½"/300 lbs 2"/150 lbs 2"/300 lbs 3"/150 lbs 3"/300 lbs 4"/150 lbs 4"/300 lbs 6"/150 lbs 8"/150 lbs 10 K 40A 10 K 50A 10 K 80A 10 K 100A Special version
Standard DIN 2526 Form C DIN 2526 Form C DIN 2526 Form C DIN 2526 Form C DIN 2526 Form C DIN 2526 Form C DIN 2526 Form C ANSI B16.5 ANSI B16.5 ANSI B16.5 ANSI B16.5 ANSI B16.5 ANSI B16.5 ANSI B16.5 ANSI B16.5 ANSI B16.5 ANSI B16.5 JIS B2210 JIS B2210 JIS B2210 JIS B2210
Material 316L 316L 316L 316L 316L 316L 316L 316L 316L 316L 316L 316L 316L 316L 316L 316L 316L 316L 316L 316L 316L
Electronic insert / Communication B 2-wire, 4…20 mA HART D 2-wire, PROFIBUS-PA F 2-wire, Foundation Fieldbus G 4-wire, 90...250 VAC, 4...20 mA HART H 4-wire, 10,5...32 VDC, 4...20 mA HART Y Special version
Product designation (part 2)
7
2 Identification
Levelflex M FMP 40 with HART/4...20 mA
70
Display 1 without display 2 with display VU 331 incl. on-side operation 9 Special version
80
Remote electronic 1 Standard compact device 2 distance sleeve 400 mm for electronic 3 remote electronic, 3 m cable 9 Special version
90
Housing and cable gland / entry housing A aluminium F12-housing, coated, IP68 B aluminium F12-housing, coated, IP68 C aluminium F12-housing, coated, IP68 D aluminium F12-housing, coated, IP68 E aluminium F12-housing, coated, IP68 G aluminium T12-housing, coated, IP68 H aluminium T12-housing, coated, IP68 J aluminium T12-housing, coated, IP68 K aluminium T12-housing, coated, IP68 L aluminium T12-housing, coated, IP68 9 Special version
100
FMP 40-
cable gland/-entry cable gland M20x1,5 cable entry G ½ cable entry ½ NPT M12 PROFIBUS-PA plug 7/8" FF-plug cable gland M20x1,5 cable entry G ½ cable entry ½ NPT M12 PROFIBUS-PA plug 7/8" FF-plug
Additional options A Additional options not selected B 3.1.B material, wetted parts SS316Ti, Inspection Certificate EN 10204, acc. specification 52005759 Y Special version
Complete product designation
⇓
Please enter probe length in mm or inch / 0.1 inch mm inch / 0.1 inch probe length LN see page 12
8
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
2.2
"
2 Identification
Scope of delivery
Caution! It is essential to follow the instructions concerning the unpacking, transport and storage of measuring instruments given in the chapter »Incoming acceptance, transport, storage« on page 11 The scope of delivery consists of: • Assembled instrument • 2 ToF Tool CD-ROMs – CD 1: ToF Tool Program – CD 2: Device descriptions (device drivers) and documentation for all Endress+Hauser devices which are operable using ToF Tool • Accessories (s. Chapter 8) Accompanying documentation: • Short manual (basic equalisation/troubleshooting): housed in the instrument • Operating manual (this manual) • Operating manual: Description of the instrument functions • Approval documentation: if this is not included in the operating manual.
2.3
Certificates and approvals
CE mark, declaration of conformity The instrument is designed to meet state-of-the-art safety requirements, has been tested and left the factory in a condition in which it is safe to operate. The instrument complies with the applicable standards and regulations in accordance with EN 61010 "Protection Measures for Electrical Equipment for Measurement, Control, Regulation and Laboratory Procedures". The instrument described in this manual thus complies with the statutory requirements of the EG directives. Endress+Hauser confirms the successful testing of the instrument by affixing to it the CE mark.
2.4
Registered trademarks
KALREZ ®, VITON ®, TEFLON ® Registered trademark of the company E.I. Du Pont de Nemours & Co., Wilmington, USA TRI-CLAMP ® Registered trademark of the company Ladish & Co., Inc., Kenosha, USA HART ® Registered trademark of HART Communication Foundation, Austin, USA ToF ® Registered trademark of the company Endress+Hauser GmbH+Co. KG, Maulburg, Germany PulseMaster ® Registered trademark of the company Endress+Hauser GmbH+Co. KG, Maulburg, Germany
Endress+Hauser
9
3 Mounting
Levelflex M FMP 40 with HART/4...20 mA
3
Mounting
3.1
Quick installation guide
F12 or T12 housing
Turn housing The housing can be turned 350° in order to simplify access to the display and the terminal compartment
1½" Caution! Use only the threaded boss ???
F12 housing 2
AF 60
60
3
max. torque 20 Nm
1
F12 or T12 housing
T12 housing 2
¾" 3
1
50
AF 50 Allen key 4 mm / 0.1"
max. torque 5 Nm
10
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
3.2
Incoming acceptance, transport, storage
3.2.1
Incoming acceptance
3 Mounting
Check the packing and contents for any signs of damage. Check the shipment, make sure nothing is missing and that the scope of supply matches your order.
3.2.2
"
Transport
Caution! Follow the safety instructions and transport conditions for instruments of more than 18 kg. Do not lift the measuring instrument by its probe rod in order to transport it.
3.2.3
Storage
Pack the measuring instrument so that is protected against impacts for storage and transport. The original packing material provides the optimum protection for this. The permissible storage temperature is -40 °C…+80 °C.
Endress+Hauser
11
3 Mounting
Levelflex M FMP 40 with HART/4...20 mA
3.3
Installation Conditions
3.3.1
Dimensions T12 housing
Ø 129
68
ENDRESS+HAUSER Levelflex-M
94
65
78
ENDRESS+HAUSER Levelflex-M
85
162
78
150
65
Ø 129
F12 housing ca. 86
85
option: remote electronic
123
88
option: distance sleeve
88
112
Ø 60,3
270...310
2765
400
4 x Ø 8,5
Ø 76
Threaded connection G 1 ½ (1 ½BSP) or 1 ½ NPT SW 60
110
68
Flange DN 40…200 or equivalent Ø 60
110
Threaded connection G ¾ (¾ BSP) or ¾ NPT SW 50
Ø 76
Ø 67,8
25
measurement
25
reference point of
Probe rods in Alloy C22 consist of 1 piece (can not be dismantled)
rod probe
rope: Ø 4 mm/0.16” or Ø 6 mm/0.24”
150
coax probe
probe length LN
rope probe
internal thread: M14 on 4 mm/0.16” rope M20 on 6 mm/0.24” rope
Ø 6/0.24” (on ¾” thread) Ø 16/0.63” (on 1½” thread or flange)
Ø 21,3/0.84” (on ¾” thread) Ø 42,4/1.67” (on 1½” thread or flange)
Ø 22/0.87” (on 4 mm/0.16” rope) Ø 30/1.18” (on 6 mm/0.24” rope)
Fig. 2
12
Dimensions Levelflex M FMP 40
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
3.4
Installation
3.4.1
Mounting kit
3 Mounting
In addition to the tool needed for flange mounting, you will require the following tool: • 4 mm Allen wrench for turning the housing. Shortening probes Rod and rope probes can be easily shortened. This is necessary if the distance to the container floor or outlet cone is less than 150 mm in the case of a rope probe, or less than 100 mm in the case of a rod probe or less than 50 mm in the case of a coax probe. Shortening rod probes The rods of a rod probe are shortened by sawing or separating at the bottom end.
M4 secured with Loctite 243 torque 4 mm cable = 5 Nm 6 mm cable =15 Nm
60 / 80 mm
Shortening rope probes • Remove ballast weight: – The weight is fixed to the probe rope with 3 Allen setscrews (M4, Allen key AF3). The screws are secured with Loctite. This may first have to be made plastic with a hot air apparatus. • Remove released rope from the weight • Measure off new rope length • Wrap adhesive tape around the rope at the point to be shortened to prevent it from fanning out. • Saw off the rope at a right angle or cut it off with a bolt cutter. • Insert the rope completely into the weight, – thin rope (4 mm) 60 mm deep, – thick rope(6 mm) 80 mm deep The weight is then refixed to the rope: • Reapply screw locking fluid (we recommend Loctite type 243) to the setscrews and screw into place. • When doing so, observe the following torques: – For 6 mm rope: 15 Nm – For 4 mm rope: 5 Nm
Shortening coax probes Coax probes can be shortened max. 80 mm from the end. They have centering units inside which fix the rod centrally in the pipe. The centerings are held with borders on the rod. Shortening is possible up to approx. 10 mm below the centering.
Endress+Hauser
13
3 Mounting
Levelflex M FMP 40 with HART/4...20 mA
3.4.2
Engineering hints for level measurement in bulk solids and fluids
The following installation instructions apply for rope and rod probes for measurement in bulk solids and fluids. Coax probes are suitable purely for measurement in fluids. They function practically independent of all installation conditions and can, therefore, be installed as desired. • Temperature conditions must be met (see page 81). • It is recommended that a protective cover (1) is used, in order to protect the transmitter against direct sunlight or rain (see »Accessories« on page 67.). Mounting location • Do not mount rod or rope probes in the filling curtain (3) • Mount rod and rope probes away from the wall (B) at such a distance that, in the event of build-up on the wall, there is still a minimum distance of 100 mm between the probe and the build-up. • Mount rod and rope probes as far away as possible from installed fittings. "Mapping " must be carried out during commissioning in the event of distances < 300 mm. • When installing rod and rope probes in plastic containers, the minimum distance of 300 mm also applies to metallic parts outside the container. • Rod and rope probes may not, at times, contact metallic container walls or floors. • In metal containers, do not install rod and rope probes exactly in the centre (2). • Minimum distance of probe end to the container floor (C): – Rope probe: 150 mm – Rod probe: 100 mm – Coax probe: 50 mm • When installing outdoors, it is recommended that you use a protective cover (1) see »Accessories« on page 67..
14
1
2
3
B
C
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
3 Mounting
Other installations • Select the mounting location such that the distance to internals (5) (e.g. limit switch, struts) > is 300 mm over the entire length of the probe, also during operation. • Probe must within the measuring span not touch any internals during operation. If necessary: when using rope probes the probe end (4) may be fixed to ensure that (see page 23)!.
5
Optimization options • Interference echo suppression: Measurement can be optimised by electronically tuning out interference echoes. 4
Minimum distance B of the probe to the container wall: Wall
min. distance B
Metal
100 mm for smooth walls
Plastic
100 mm, min. 300 mm to metallic components outside of the tank
Concrete
0.5 m/20", otherwise the max. possible measuring range is reduced
Distance to protruding internals min. 300 mm.
Endress+Hauser
15
3 Mounting
Levelflex M FMP 40 with HART/4...20 mA
Standard installation • Probes are mounted to the process connection with threaded connections or flanges and are usually also secured with these. If during this installation there is the danger that the probe end moves so much that it touches the tank floor or cone at times, the probe must, if necessary, be shortened and fixed down. The easiest way to fix the rope probes is to screw them to the internal thread on the lower end of the weight. Thread size, see page 23. • The ideal installation is mounting in a screwed joint / screw-in sleeve which is internally flush with the container ceiling. • If installation takes place in a nozzle, the nozzle should be 50 ... 150 mm in diameter and should not be more than 150 mm high. Installation adapters are available for other dimensions, see »Accessories« on page 67. installation with welding boss 1½" or ¾"
installation in nozzle
≤ 150 mm (≤ 4")
diameter nozzle: ≤ DN150 (≤ 6”)
Probe length
• The measuring range is directly dependent on the probe length. If the probe is not fixed at the bottom end, the following distances to the container floor must be observed: – Rope probe: 150 mm – Rod probe: 100 mm – Coax probe: 30 mm It is better to order probes too long than too short since it is possible to shorten the probe if necessary.
16
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
3.4.3
3 Mounting
Special notes for bulk solids
• In the case of bulk solids, as great a distance as possible from the filling curtain is especially important to avoid wear. • In concrete silos, a large distance (B) should be observed between the probe and the concrete wall, if possible >= 1m, but at least 0.5m
B
Installation in concrete silos Installation, for example, into a thick concrete ceiling should be made flush with the lower edge. Alternatively, the probe can also be installed into a pipe that must not protrude over the lower edge of the silo ceiling. Installation suggestions see diagram. ≥ 100 mm
≥ 100 mm
metal
Ø 80...150 mm Extension rod / Centering (see accessories)
Endress+Hauser
17
3 Mounting
Levelflex M FMP 40 with HART/4...20 mA
3.4.4
Installation in bulk solid silos
Tensile load Bulk solids exert tensile forces on rope probes whose height increases with:: • the length of the probe, i.e. max. cover, • the bulk density of the product, • the silo diameter and • the diameter of the probe rope The following diagrams show typical loads for frequently occurring bulk solids as reference values. The calculation is performed for the following conditions: • Suspended probe (probe end not fixed at the bottom) • Free-flowing bulk solid, i.e. mass flow. A calculation for core flow is not possible. In the event of collapsing cornices, considerably higher loads can occur. • The specification for tensile forces contains the safety factor 2, which compensates for the normal fluctuation range in pourable bulk solids.
18
35
16
30
40 25 20
30
15 20 10
12
polyethylene pellets smooth metallic walls silo diameter 12 m silo diameter 9 m silo diameter 6 m silo diameter 3 m
14 pulling force, 6 mm rope [kN]
11 10 9 8
12
7
10
6 8
5 4
6
3
4
10
2 5
0 0
5
10
15
20
25
30
2
0 35
1
0 0
5
10
level [m]
60
24
25
30
0 35
50
20
16 14
20
12 15
10 8
10
6 4
5
pulling force, 6 mm rope [kN]
18
25
40
cement smooth metallic walls silo diameter 12 m silo diameter 9 m silo diameter 6 m silo diameter 3 m
22
pulling force, 4 mm rope [kN]
pulling force, 6 mm rope [kN]
30
20
level [m]
wheat smooth metallic walls silo diameter 12 m silo diameter 9 m silo diameter 6 m silo diameter 3 m
35
15
35 30
40 25 20
30
15 20 10
pulling force, 4 mm rope [kN]
pulling force, 6 mm rope [kN]
50
40
pulling force, 4 mm rope [kN]
silica sand smooth metallic walls silo diameter 12 m silo diameter 9 m silo diameter 6 m silo diameter 3 m
pulling force, 4 mm rope [kN]
60
10 5
2 0 0
5
10
15
20
level [m]
18
25
30
0 35
0 0
5
10
15
20
25
30
0 35
level [m]
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
3 Mounting
Since the tensile forces are also heavily dependent on the viscosity of the product, a higher safety factor is necessary for highly viscous products and if there is a risk of cornice build-up. In critical cases it is better to use a 6 mm rope instead of a 4 mm one. The same forces also act on the silo cover. On a fixed rope, the tensile forces are definitely greater, but this can not be calculated. Observe the tensile strength of the probes or ensure that the tensile strength of the probes is not exceeded. Options for reducing the tensile forces: • Shorten the probe • If the maximum tensile load is exceeded, check whether it would be possible to use a non-contact ultrasonic device.
Endress+Hauser
19
3 Mounting
Levelflex M FMP 40 with HART/4...20 mA
3.4.5
Installation in liquids tanks
• When installing in agitation units, check whether a no-contact process (ultrasonic or radar) would be better suited, especially if the agitator generates large mechanical loads on the probe. • If Levelflex is, nevertheless, installed in tanks with agitators, it is better to use coax probes which have a greater lateral loading capacity. Standard installation Using a coax probe offers great advantages when the viscosity of the product is < 500 cst and it is certain that the product does not accumulate build-up: • Greater reliability: As of dielectric constant=1.4, measurement functions independently of all electrical properties in all liquids. • Internals in the tank and nozzle dimensions do not have any influence on measurement. • Higher lateral load-bearing capacity than rod probes. • For higher viscosity a rod probe is recommended, or using a non-contact measuring principle. Installation in horizontal cylindrical and standing tanks • Use a coax or rod probe for measuring ranges up to 4 m. For anything over this or if there is too free cover space use a 4 mm rope probe. • Installation and possible fixing as with bulk solids. • Any distance from wall, as long as occasional contact is prevented. • Do not mount a rod or rope probe (1) exactly central when using metallic containers. Central mounting doesn‘t impair coax probe (2) performance. • When installing in tanks with a lot of internals or internals situated close to the probe: Use a coax probe.
20
1
2
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
3 Mounting
Installation in underground tanks • Use coax probe for nozzles with large diameters in order to avoid reflections at the nozzle wall.
Measurement in corrosive fluids For measurement in corrosive liquids, it is possible to install a rod probe in a closed plastic pipe with a diameter of up to approx. 50 mm. When using plastic tanks it is also possible to mount the probe on the outside of the tank (see Installation instructions on page 24). Levelflex measures the level through the plastic in both cases. Installation in stilling well or bypass • A rod probe can be used for pipe diameters up to 150 mm, for diameters above that the flange with horn adapter recommended. • When installing a rod probe into a metallic pipe with internal diameter of up to 150 mm, you have all the advantages of a coax probe. • Welded joints that protrude up to approx. 5 mm/0.2" inwards do not influence measurement.
Endress+Hauser
21
3 Mounting
Levelflex M FMP 40 with HART/4...20 mA
Mounting Location • Recommended distance B wallmounted rope probe: ~1/6...1/4 of the container diameter (min. 100 mm/4", concrete silos: min. 500 mm). • Not central (2) in metallic tanks. • Not in the filling curtain (3). • Please order the probe length such that it ends approx 30 mm above the floor of the tank. • Temperature conditions must be met. • It is recommended that a protective cover (1) be used, in order to protect the transmitter against direct sunlight or rain. Mounting and demounting are carried out simply with a clamp (see »Accessories« on page 67.).
1
2
3
B
Tank installations • Select the mounting location such that the distance to internals (4) (e.g. limit switch, struts) is > 300 mm. Optimization options • Interference echo suppression: Measurement can be optimised by electronically tuning out interference echoes. • Bypass pipe and stilling well (only for liquids): for viscosities of up to 500 cst, a bypass pipe, stilling well or a coax probe can be used to prevent interference.
22
4
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
3.4.6
3 Mounting
Notes on special installation situations
Fixing rope probe • The end of the probe needs to be secured if the probe would otherwise touch the silo wall, the cone or another part, or the probe comes closer than 0.5 m to a concrete wall. This is what the internal thread in the probe weight is intended for: – for 4 mm rope:M14 – for 6 mm rope:M20 • Preferably use the 6 mm rope probe due to the higher tensile strength when fixing a rope probe • The fixing must be either reliably grounded or reliably insulated (see accessories). If it is not possible to mount the probe weight with a safe earthed connection, it can be secured using an isolated eyelet, which is available as an accessory (see page 69). • In order to prevent an extremely high tensile load and the risk of rope crack, the rope has to be slack. Make the rope longer than the required measuring range such that there is a sag in the middle of the rope that is ≥ 1cm/m (1"/ 100") of the rope length.
Reliable, earthed mounting
sag of the rope: ≥1cm/m of the rope length
Reliable, isolated mounting
Mounting-kit isolated (see accessories)
Mounting and contact with a bolt 4mm-rope: M14 6mm-rope: M20
Endress+Hauser
23
3 Mounting
Levelflex M FMP 40 with HART/4...20 mA
Installation from the side • If installation from above is not possible, the Levelflex can also be mounted from the side. • In this case, always fix the rope probe (see »Fixing rope probe« ). • Support coax probe if the lateral loadbearing capacity is exceeded. Only fix rod probes at the probe end. • Connect rod probe metallically with the container wall.
Installation in plastic containers Please note that for rod and rope probes only with a metallic surface at the process connection an optimal performance can be guaranteed. When installing the probe in plastic silos, whose silo cover is also made of plastic or silos with wood cover, the probes must either be mounted in a ≥ DN50 / 2" metallic flange, or a metal sheet with diameter of ≥ 200 mm must be mounted under the screw-in piece. metal sheet or metal flange
silo roof of plastic or wood
metal sheet or metal flange
max. 20 mm
Wall thickness for GFK/PP < 15 mm
• It is also possible to mount the probe externally on the tank wall for measuring in Aqueous solutions. Measurement then takes place through the tank wall without contacting the medium. If people are in the vicinity of the probe mounting location, a plastic half pipe with a diameter of approx. 200 mm, or some other protective unit, must be affixed externally to the probe to prevent any influences on the measurement. • There must not be any metallic reinforcement rings secured to the tank. • The wall thickness should be at Fibre-Glass Reinforced Plastic/PP < 15 mm. • There must be no open space between the tank wall and the probe. 24
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
3 Mounting
• If measuring externally, an automatic probe length determination and a two point linearisation must be performed in order to compensate for the time-of-flight change caused by the plastic wall.
Installation in nozzles > 150 mm high If, when installing probes in nozzles DN 40...250/1 ½"...10" with nozzle height (HS) of > 150 mm/6", the probe could touch the lower edge of the nozzle due to moving materials in the container, we recommend using an extension rod with or without centering disk. This accessory consists of the extension rod corresponding to the nozzle height, on which a centering disk is also mounted if the nozzles are narrow or when working in bulk solids. This component is delivered separately from the device. Please order the probe length correspondingly shorter. For the exact length of the rod see page 68. Order codes for specific nozzle nominal diameters and heights can be found on page 68. Only use centering disks with small diameters (DN 40 and DN 50) if there is no significant build-up in the nozzle above the disk.
DN50 (2") DN80 (3") DN150 (6") DN200 (8") DN250 (10")
HS centering disk at PPS - GF40
#
Not for ¾". For rod probe on request.
Installation in DN 200/DN 8" and DN 250/DN 10"nozzles When installing the Levelflex in nozzles of > 210 mm / 8", signals are generated by reflections on the nozzle wall, which can sometimes lead to faulty measurements in the case of products with small dielectric constants With nozzle diameters of 200 mm / 8" or 250 mm / 10", therefore, a special flange with a “horn adaptor” must be fitted. Nozzles with nominal diameters greater than DN 250 / 10" should be avoided.
204 mm
DN200 (8") DN250 (10")
Endress+Hauser
25
3 Mounting
Levelflex M FMP 40 with HART/4...20 mA
Installation in > DN 300/DN 12" nozzles If installation in > 300mm/12" nozzles is unavoidable, installation must be carried out in accordance with the sketch on the right.
pipe Ø 150 … 180
Approx. flush with the lower edge of the nozzle (± 50 mm).
3.4.7
plate
nozzle diameter
plate diameter
DN 300
280
> DN 400
> 350
Installation for difficult to access process connections
For tight spaces or temperatures above that in the graphic, the electronics housing can be ordered with distance pipe or connecting cable (seperate housing).
400
Installation with distance pipe • Follow installation instructions on Page 14 ff.. • After mounting, the housing can be turned 350°, in order make access to the display and the connection compartment easier. • The max. measuring range is reduced to 34 m/1338".
Ø 60,3
Ø 67
26
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
3 Mounting
Installation with separate housing • Follow installation instructions on Page 14 ff.. • Mount housing on a wall or pipe as shown in the diagram. 65
78
150
ENDRESS+HAUSER Levelflex M
150
Ø 129
wall
88
85
123
52
88 4 x Ø 8,5
ENDRESS+HAUSER Levelflex M
pipe
150
78
Ø 129
65
2765
94
85
112
96
max. 80 min. 30
1)
52
Ø 76 94
The separate housing is designed for use at high environmental temperatures at the mounting location of the sensor. The max. measuring range is reduced to 30 m/1181". The version with separate housing consists of the probe, a connecting cable and the housing. If they are ordered as a set, they are assembled on delivery. 1) The protective hose can not be dismantled at this point.
Endress+Hauser
27
3 Mounting
Levelflex M FMP 40 with HART/4...20 mA
3.4.8
Turn housing
After mounting, the housing can be turned 350° in order to simplify access to the display and the terminal compartment. Proceed as follows to turn the housing to the required position: • Undo the fixing screws (1) • Turn the housing (2) in the required direction • Tighten up the fixing screws (1).
F12 housing
T12 housing
2
2
1
1
allen key 4 mm/0.1”
3.5
Post-installation check
After the measuring instrument has been installed, perform the following checks: • Is the measuring instrument damaged (visual check)? • Does the measuring instrument correspond to the measuring point specifications such as process temperature/pressure, ambient temperature, measuring range, etc.? • Are the measuring point number and labeling correct (visual check)? • Is the measuring instrument adequately protected against rain and direct sunlight (see Page 67 ff.)?
28
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
4 Wiring
4
Wiring
4.1
Quick wiring guide
Wiring in F12 housing
"
Before connection please note the following: ●
The power supply must be identical to the data on the nameplate (1).
●
Switch off power supply before connecting up the device.
Caution!
ENDRESS+HAUSER LEVELFLEX-M
LN=
●
Connect Equipotential bonding to transmitter ground terminal (7) before connecting up the device.
●
Tighten the locking screw (8): It forms the connection between the probe and the housing ground potential.
Made in Germany D-79689 Maulburg
Order Code: Ser.-No.:
1
IP68 / NEMA 6P
PN= Profibus PA Foundation Fieldbus 90 … 253 V AC 1VA 10,5 … 32 V DC 1W 16 … 3 V DC 0,8W 4 … 20 mA HART
TA > 70°C : t >85°C
2-wire 4-wire if modification X = see sep. label Dat./Insp.:
Patents D01301-A
2 When you use the measuring system in hazardous areas, make sure you comply with national standards and the specifications in the safety instructions (XA’s). Make sure you use the specific cable gland.
-
7
On devices supplied with a certificate, the explosion protection is designed as follows: ●
Housing F12 - EEx ia: Power supply must be intrinsically safe.
●
The electronics and the current output are galvanically separated from the probe circuit.
8
#
Unplug display connector!
Connect up the Levelflex M as follows: ●
Unscrew housing cover (2).
●
Remove any display (3) if fitted.
●
Remove cover plate from terminal compartment (4).
●
Pull out terminal module slightly using "pulling loop" (only 2-wire).
●
Insert cable (5) through gland (6). Use screened, twisted wire pair.
3
EN
-
DR
ES
S+
US HA
ER
Only ground screening of the line (7) on sensor side. ●
Make connection (see pin assignment).
●
Re-insert terminal module.
●
Tighten cable gland (6). Max. torque 10...12 Nm!
●
Tighten screws on cover plate (4).
●
Insert display if fitted.
●
Screw on housing cover (2). (on dust-Ex torque ≈ 40 Nm).
●
Switch on power supply.
power
6
4
5
DC
AC / DC
display unit, recorder, PCS
power
7 0...20mA 1 2 3 4
Sealed terminal compartment 7 test sockets (output current)
1 2 3 4 L- L+ I+
I-
2-wire-version
Endress+Hauser
plant ground
5 6 I+
I-
1 2 L1/L+ N/L-
plant ground
Note! If 4-wire for dust-Ex-applications is used, the current output is intrinsically save.
4-wire-version
29
4 Wiring
Levelflex M FMP 40 with HART/4...20 mA
Wiring in T12 housing
"
Before connection please note the following: ●
The power supply must be identical to the data on the nameplate (1).
●
Switch off power supply before connecting up the device.
Caution! ●
Connect Equipotential bonding to transmitter ground terminal (7) before connecting up the device.
●
Tighten the locking screw (8): It forms the connection between the probe and the housing ground potential.
ENDRESS+HAUSER LEVELFLEX-M
1
Made in Germany D-79689 Maulburg
Order Code: Ser.-No.:
LN=
IP68 / NEMA 6P
PN= Profibus PA Foundation Fieldbus 90 … 253 V AC 1VA 10,5 … 32 V DC 1W 16 … 3 V DC 0,8W 4 … 20 mA HART
TA > 70°C : t >85°C
2-wire 4-wire if modification X = see sep. label Dat./Insp.:
When you use the measuring system in hazardous areas, make sure you comply with national standards and the specifications in the safety instructions (XA’s). Make sure you use the specific cable gland.
Patents D01301-A
2
Connect up the Levelflex M as follows:
-
Before unscrew housing cover (2) at seperate connection room turn off the power supply! ●
Insert cable (3) through gland (4). Use screened, twisted wire pair.
7 8
Only ground screening of the line (5) on sensor side. ●
Make connection (see pin assignment).
●
Tighten cable gland (4). Max. torque 10...12 Nm!
●
Screw on housing cover (2) (on dust-Ex torque ≈ 40 Nm).
●
Switch on power supply. 4
3 power 5
1 2 3 4
test sockets (output current)
1 2 3 4 L- L+ I+
plant ground
I-
2-wire-version
30
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
4.2
4 Wiring
Connecting the measuring unit
Terminal compartment Two housings are available: • Housing F 12 with additionally sealed terminal compartment for standard or EEx ia • Housing T 12 with separate terminal compartment for standard, EEx e or EEx d. T12 housing
F12 housing
sealed terminal compartment
The instrument data are given on the nameplate together with important information regarding the analog output and voltage supply. Housing orientation regarding the wiring, see »Turn housing« on page 28. Load HART Minimum load for Hart communication: 250 Ω Cable entry Cable gland: M20x1.5 Cable entry: G ½ or ½ NPT Supply voltage HART, 2-wire The following values are the voltages across the terminals directly at the instrument:
Communication HART
Terminal voltage
Current consumption
minimal
maximal
4 mA
16 V
36 V
20 mA
7,5 V
36 V
4 mA
16 V
30 V
20 mA
7,5 V
30 V
standard
EEx ia
Fixed current (HART multidropoperation)
Endress+Hauser
EEx em EEx d
4 mA
16 V
30 V
20 mA
11 V
30 V
standard
11 mA
10 V
36 V
EEx ia
11 mA
10 V
30 V
31
4 Wiring
Levelflex M FMP 40 with HART/4...20 mA
HART, 4-wire active Version
Voltage
Max. load
DC
10,5...32 V
600 Ω
AC
85...250 V
600 Ω
Power consumption min. 60 mW, max. 900 mW Current consumption Current consumption
Current consumption Power consumption
HART, 2-wire
3,6…22 mA
—
HART, 4-wire (90...250 VAC)
2,4...22 mA
~ 3...6 mA / ~ 3.5 VA
HART, 4-wire (10,5...32 VDC)
2,4...22 mA
~ 100 mA / ~ 1 W
PROFIBUS-PA
max. 11 mA
—
Foundation Fieldbus (FF)
max. 15 mA
—
Communication
32
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
4 Wiring
4.2.1
HART connection with E+H RMA 422 / RN 221 N
4.2.2
HART connection with other supplies
- ToF Tool DC power supply unit or FXA 193
PLC
4...20 mA ≥ 250 Ω
1 2 3 4
- COMMUWIN II - ToF Tool
HART DXR 275
"
Endress+Hauser
Commubox FXA 191
Caution! If the HART communication resistor is not built into the supply unit and the HART interface is to be used, it is necessary to insert a communication resistor of 250 Ω into the 2-wire line.
33
4 Wiring
Levelflex M FMP 40 with HART/4...20 mA
4.3
Equipotential bonding
Connect the Equipotential bonding to the external ground terminal (1) of the transmitter.
F12 housing
1
"
T12 housing
1
Caution! In Ex applications, the instrument must only be grounded on the sensor side. Further safety instructions are given in the separate documentation for applications in explosion hazardous areas.
4.4
Degree of protection
• housing: IP 68, NEMA 4X (open housing: IP20, NEMA 1) • probe: IP 68 (NEMA 6P)
4.5
Post-connection check
After wiring the measuring instrument, perform the following checks: • Is the terminal allocation correct (see Page 29 ff. and Page 30)? • Is the cable gland tight? • Is the housing cover screwed tight? • If auxiliary power is available: Is the instrument ready for operation and is the liquid crystal display visible.
34
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
5 Operation
5
Operation
5.1
Quick operation guide
ENDRESS + HAUSER
–
+
X
E
F 2x
X O
basic setup safety settings
F
X
X
tank shape
O
Standard
F
aluminium tank
>3 s
medium property
...
Return to Group Selection
O
plastic tank
linearisation
bypass / pipe extended calibr. ...
S
S
coax probe concrete wall
S
...
Selection and configuration in Operation menu: 1.) Change from Measured Value Display to Group Selection by pressing F 2.) Press S or O to select the required Function Group (e.g.. "basic setup (00)") and confirm by pressing F ➜ First function (e.g. "tank shape (002)") is selected. Note! The active selection is marked by a ✔ in front of the menu text. 3.) Activate Edit mode with O or S. Selection menus: a) Select the required Parameter in selected function (e.g. "tank shape (002)") with S or O. b) F confirms selection ➜ ✔ appears in front of the selected parameter c) F confirms the edited value ➜ system quits Edit mode d) O / S (= X) interrupts selection ➜ system quits Edit mode Typing in numerals and text: a) Press O or S to edit the first character of the numeral / text (e.g. "empty calibr. (005)") b) F positions the cursor at the next character ➜ continue with (a) until you have completed your input c) if a symbol appears at the cursor, press F to accept the value entered ➜ system quits Edit mode d) O / S (= X) interrupts the input, system quits Edit mode 4) Press F to select the next function (e.g. "medium property (003)") 5) Press O / S (= X) once ➜ return to previous function (e.g. "tank shape (002)") Press O / S (= X) twice ➜ return to Group selection 6) Press O / S (= X) to return to Measured value display
Endress+Hauser
35
5 Operation
Levelflex M FMP 40 with HART/4...20 mA
5.1.1
General structure of the operating menu
The operating menu is made up of two levels: • Function groups (00, 01, 03, …, 0C, 0D): The individual operating options of the instrument are split up roughly into different function groups. The function groups that are available include, e.g.: "basic setup", "safety settings", "output", "display", etc. • Functions (001, 002, 003, …, 0D8, 0D9): Each function group consists of one or more functions. The functions perform the actual operation or parameterisation of the instrument. Numerical values can be entered here and parameters can be selected and saved. The available functions of the “basic setup (00)” function group include, e.g.: "tank properties" (002), "medium property (003)", "process cond. (004)", "empty calibr. (005)", etc. If, for example, the application of the instrument is to be changed, carry out the following procedure: 1. Select the “basic setup (00)” function group. 2. Select the "tank properties" (002) function (where the existing tank shape is selected).
5.1.2
Identifying the functions
For simple orientation within the function menus, for each function a position is shown on the display.
The first two digits identify the function group: • basic setup
00
• safety settings
01
• linearisation
04
… The third digit numbers the individual functions within the function group: • basic setup
00
→
• tank properties
002
• medium property
003
• process cond.
004
… Here after the position is always given in brackets (e.g. "tank properties" (002)) after the described function.
36
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
5.2
5 Operation
Display and operating elements
END RES
Order MICR S+HA OPIL Ser.-NoCode: OT USE .:
Maulburg
R
IP T
65
A >70°C
: t >85°C
Made in Germany
II
Messbe Measur reich ing range U 16...36 max. 4...20 20 m V mA DC
LCD (liquid crystal display) ENDRESS + HAUSER
–
+
E
Symbols
Fig. 3
3 keys
Layout of the display and operating elements
5.2.1
Display
Liquid crystal display (LCD): Four lines with 20 characters each. Display contrast adjustable through key combination.
Headline
Position indicator
ENDRESS + HAUSER
Symbol –
+
Main value
Unit
E
Selection list
Function groups -> Functions HOME
X
F O S
Fig. 4
Endress+Hauser
FG00 FG01 FG02 FG03 FG04 FG05 FG06 FG07 ...
X F
F F000 F001 F002 F003 F004 ...
F
O S
X
X
Help text
+21mV Envelope curve
0.00
2.305m
09C 10.00
Display
37
5 Operation
Levelflex M FMP 40 with HART/4...20 mA
5.2.2
Display symbols
The following table describes the symbols that appear on the liquid crystal display: Symbols
Meaning ALARM_SYMBOL This alarm symbol appears when the instrument is in an alarm state. If the symbol flashes, this indicates a warning. LOCK_SYMBOL This lock symbol appears when the instrument is locked,i.e. if no input is possible.
COM_SYMBOL This communication symbol appears when a data transmission via e.g. HART, PFOFIBUS-PA or Foundation Fieldbus is in progress.
Tab. 1
Meaning of Symbols
5.2.3
Key assignment
The operating elements are located inside the housing and are accessible for operation by opening the lid of the housing. Function of the keys
Key(s)
Meaning
O or V
Navigate upwards in the selection list Edit numeric value within a function
S or W
Navigate downwards in the selection list Edit numeric value within a function
X or Z F or M O and F or S and F O and S and F
Tab. 2
38
Navigate to the left within a function group
Navigate to the right within a function group, confirmation.
Contrast settings of the LCD
Hardware lock / unlock After a hardware lock, an operation of the instrument via display or communication is not possible! The hardware can only be unlocked via the display. An unlock parameter must be entered to do so.
Function of the keys
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
5 Operation
5.3
Local operation
5.3.1
Locking of the configuration mode
The Levelflex can be protected in two ways against unauthorised changing of instrument data, numerical values or factory settings: "unlock parameter" (0A4): A value <> 100 (e.g. 99) must be entered in "unlock parameter" (0A4) in the "diagnostics" (0A) function group. The lock is shown on the display by the symbol and can be released again either via the display or by communication. Hardware lock: The instrument is locked by pressing the O and S and F keys at the same time. The lock is shown on the display by the symbol and can only be unlocked again via the display by pressing the O and S and F keys at the same time again. It is not possible to unlock the hardware by communication. All parameters can de displayed even if the instrument is locked.
⇒ ⇓
O and S and F press simultaneous
⇓ The LOCK_SYMBOL appears on the LCD.
Endress+Hauser
39
5 Operation
Levelflex M FMP 40 with HART/4...20 mA
5.3.2
Unlocking of configuration mode
If an attempt is made to change parameters when the instrument is locked, the user is automatically requested to unlock the instrument: "unlock parameter" (0A4): By entering the unlock parameter (on the display or via communication) 100 = for HART devices the Levelflex is released for operation. Hardware unlock: After pressing the O and S and F keys at the same time, the user is asked to enter the unlock parameter 100 = for HART devices.
⇒
O and S and F press simultaneous
⇓ Please enter unlock code and confirm with F.
⇓ "
40
Caution! Changing certain parameters such as all sensor characteristics, for example, influences numerous functions of the entire measuring system, particularly measuring accuracy. There is no need to change these parameters under normal circumstances and consequently, they are protected by a special code known only to the E+H service organization. Please contact Endress+Hauser if you have any questions.
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
5.3.3
"
5 Operation
Factory settings (Reset)
Caution! A reset sets the instrument back to the factory settings. This can lead to an impairment of the measurement. Generally, you should perform a basic setup again following a reset. A reset is only necessary: • if the instrument no longer functions • if the instrument must be moved from one measuring point to another • if the instrument is being de-installed /put into storage/installed
⇒ User input ("reset" (0A3)): • 333 = customer parameters 333 = reset customer parameters This reset is recommended whenever an instrument with an unknown 'history' is to be used in an application: • The Levelflex is reset to the default values. • The customer specific tank map is not deleted. • The mapping can also be deleted in the "cust. tank map" (055) function of the "extended calibr." (05) function group. • A linearisation is switched to "linear" although the table values are retained. The table can be reactivated in the "linearisation" (04) function group. List of functions that are affected by a reset: • • • • • • • • • • • • • • • • •
tank properties (002) medium cond. (003) process proper. (004) empty calibr. (005) full calibr. (006) output on alarm (010) output on alarm (011) outp. echo loss (012) ramp %span/min (013) delay time (014) safety distance (015) in safety dist. (016) overspill protection (018) end of probe (030) level/ullage (040) linearisation (041) customer unit (042)
• • • • • • • • • • • • • • • • •
max. scale (046) diameter vessel (047) check distance (051) range of mapping (052) start mapping (053) offset (057) output damping (058) low output limit (062) curr. output mode (063) fixed cur. value (064) 4mA value (068) language (092) back to home (093) format display (094) no of decimals (095) sep. character (096) unlock parameter (0A4)
A complete “basic setup" (00) must be activated.
Endress+Hauser
41
5 Operation
Levelflex M FMP 40 with HART/4...20 mA
5.4
Display and acknowledging error messages
Type of error Errors that occur during commissioning or measuring are displayed immediately on the local display. If two or more system or process errors occur, the error with the highest priority is the one shown on the display. The measuring system distinguishes between two types of error: • A (Alarm): Instrument goes into a defined state (e.g. MAX 22 mA) Indicated by a constant symbol. (For a description of the codes, see Table 9.2 on Page 72) • W (Warning): Instrument continue measuring, error message is displayed. Indicated by a flashing symbol. (For a description of the codes, see Table 9.2 on Page 72) • E (Alarm / Warning): Configurable (e.g. loss of echo, level within the safety distance) Indicated by a constant/flashing symbol. (For a description of the codes, see Table 9.2 on Page 72)
⇒ Error messages Error messages appear as four lines of plain text on the display. In addition, a unique error code is also output. A description of the error codes is given on Page 72. • The "diagnostics (0A)" function group can display current errors as well as the last errors that occurred. • If several current errors occur, use O or S to page through the error messages. • The last occurring error can be deleted in the "diagnostics (0A)" function group with the function"clear last error" (0A2).
42
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
5.5
5 Operation
HART communication
Apart from local operation, you can also parameterise the measuring instrument and view measured values by means of a HART protocol. There are two options available for operation: • Operation via the universal handheld operating unit, the HART Communicator DXR 275. • Operation via the Personal Computer (PC) using the operating program (e.g. ToF Tool or Commuwin II) (For connections, see Page 33 ff.).
5.5.1
Handheld unit DXR 275
All device functions can be adjusted via menu operation with the handheld unit DXR 275.
FMP 40:LIC0001 Online 1 >Group Select 2 PV
8.7 m
FMP 40: LIC0001 Online 1->Group Select 2 PV
8.7m
HELP
HELP F1
I
O
F2
FMP 40 : LIC0001 F3 F4 Group Select 1->Calibration 2 Linearisation 3 Ext. Calibration 4 Service 5 Operating mode HOME FMP 40: LIC0001 F1 F2 F3 F4 Calibration 1 Measured Value 2->Empty Calibration 3 Full Calibration 4 Application Parameter 5 Output Damping HOME F1
Fig. 5
!
F2
F3
F4
Menu operation with the DXR 275 handheld instrument
Note! • Further information on the HART handheld unit is given in the respective operating manual included in the transport bag of the instrument.
5.5.2
ToF Tool operating program
The ToF Tool is a graphical operating software for instruments from Endress+Hauser that operate based on the time-of-flight principle. It is used to support commissioning, securing of data, signal analysis and documentation of the instruments. It is compatible with the following operating systems: Win95, Win98, WinNT4.0, Win2000 and Windows XP. The ToF Tool supports the following functions: • Online configuration of transmitters • Signal analysis via envelope curve • Loading and saving of instrument data (Upload/Download) • Documentation of measuring point
! Endress+Hauser
Note! Further information you may find on the CD-ROM, which is enclosed to the instrument.
43
5 Operation
Levelflex M FMP 40 with HART/4...20 mA
Menu-guided commissioning
Signal analysis via envelope curve:
Connection options: • Service-interface with adapter FXA 193 (see Page 33 ff.) • HART with Commubox FXA 191 (see Page 33 ff.)
44
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
5.5.3
5 Operation
Commuwin II-Operating Programm
Commuwin II is an operating software with graphical support for intelligent transmitters with the communication protocols Rackbus, Rackbus RS 485, INTENSOR, HART or PROFIBUS-PA. It is compatible with the operating systems Win 3.1/3.11, Win95, Win98 and WinNT4.0. All functions of Commuwin II are supported. The configuration is made via operating matrix or graphic surface. The envelope curve can be displayed in ToF Tool and display.
!
Note! Further information on Commuwin II is given in the following E+H documentation: • System Information: SI 018F/00/en “Commuwin II” • Operating Manual: BA 124F/00/en “Commuwin II” operating program Connection The table provides an overview of the Commuwin connections.
!
Endress+Hauser
Interface
Hardware
Server
Device list
HART
Commubox FXA 191 to HART Computer with RS-232C interface
HART
Connected instrument
Interface FXN 672 Gateway for MODBUS, PROFIBUS, FIP, INTERBUS, etc.
ZA 673 for PROFIBUS
List of all rack bus modules: the required FXN 672 must be selected
Computer with RS-232C interface or PROFIBUS card
ZA 672 for other
Note! The Levelflex M can also be operated locally using the keys. If operation is prevented by the keys being locked locally, parameter entry via communication is not possible either.
45
6 Commissioning
Levelflex M FMP 40 with HART/4...20 mA
6
Commissioning
6.1
Function check
Make sure that all final checks have been completed before you start up your measuring point: • Checklist “Post installation check” (see Page 28 ff.). • Checklist “Post connection check” (see Page 34 ff.).
6.2
Switching on the measuring device
When the instrument is switched on for the first time, the following messages appear on the display:
⇒ ⇓
After 5 s, the following message appears
⇓
After 5 s, the following message appears (e.g. on HART devices)
⇓
After 5 s or after you have pressed F the following message appears Select the language (this message appears the first time the instrument is switched on)
⇓ Select the basic unit (this message appears the first time the instrument is switched on)
⇓ The current measured value is displayed
⇓
After F is pressed, you reach the group selection. This selection enables you to perform the basic setup
46
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
6.3
6 Commissioning
Basic Setup
tank shape flange: reference point of measurement
Standard
UB
measuring cond. Unknown
basic setup (standard)
SD D
measuring cond. Standard
E LN
F L
empty calibr.
LB full calibr.
mapping
E = empty calibr. (= zero) setting in 005 F = full calibr. (= span) setting in 006 D = distance (distance flange / product) display in 0A5 L = level display in 0A6
safety settings
extended calibr.
...
Endress+Hauser
(description see BA 245F)
option
linearisation
LN = probe length setting in 033 UB = upper blocking distance setting in 059 SD = safety distance setting in 015 LB = lower blocking distance
47
6 Commissioning
Levelflex M FMP 40 with HART/4...20 mA
The basic setup is sufficient for successful commissioning in most applications.
!
Note! The Levelflex M allows to check for broken probe. On delivery, this function is switched off, because otherwise shortening of the probe would be mistaken for a broken probe. If you want to check the probe for a crack select the "broken probe det" (019) function in the "safety settings" (01) function group. Complex measuring operations necessitate additional functions that the user can use to customise the Levelflex as necessary to suit his specific requirements. The functions available to do this are described in detail in the BA 245F. Comply with the following instructions when configuring the functions in the "basic setup" (00): • Select the functions as described on Page 35. • Certain functions (e.g. starting an interference echo mapping (053)) prompt you to confirm your data entries. Press O or S to select "YES" and press F to confirm. The function is now started. • If you do not press a key during a configurable time period (→ function group "display (09)"), an automatic return is made to the home position (measured value display).
48
!
Note! • The instrument continues to measure while data entry is in progress, i.e. the current measured values are output via the signal outputs in the normal way. • If the envelope curve mode is active on the display, the measured values are updated in a slower cycle time. Thus, it is advisable to leave the envelope curve mode after the measuring point has been optimised. • If the power supply fails, all preset and parameterised values remain safely stored in the EEPROM.
"
Caution! All functions are described in detail, as is the overview of the operating menu itself, in the manual “Description of the instrument functions – BA 245F”, which is a separate part of this operating manual.
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
6.4
6 Commissioning
Basic Setup with the VU 331
Function "measured value" (000)
⇒ This function displays the current measured value in the selected unit (see "customer unit" (042) function). The number of digits after decimal point can be selected in the "no.of decimals" (095) function.
6.4.1
Function group "basic setup" (00)
⇒ Function "tank properties" (002)
⇒ This function is used to select the tank properties. Selection: • standard • aluminium tank • plastic tank • bypass / pipe • coax probe • concrete wall standard The "standard" option is recommended for normal containers for rod and rope probes. aluminium tank The "aluminium tank" option is designed especially for high aluminium silos that cause an increased level of noise when empty. This option is only useful for probes longer than (< 4 m). For short probes (< 4 m) select the "standard" option.
!
Note! If "aluminium tank" is selected, the device calibrates of its own accord when first filled, depending on the medium's properties. Slope errors can, therefore, occur when beginning the first filling procedure. plastic tank Select the "plastic tank" option when installing probes in wood or plastic containers without metallic surfaces at the process connection (see installation in plastic containers). When using a metallic surface at the process connection, the "standard" option is sufficient.
!
Endress+Hauser
Note! In principle the employment of a metallic surface area should be preferred at the process connection!
49
6 Commissioning
Levelflex M FMP 40 with HART/4...20 mA
bypass / pipe The "bypass / pipe" option is designed especially for the installation of probes in a bypass or a stilling well. coax probe Select the "coax probe" option when using a coaxial probe. When this setting is made, the evaluation is adapted to the high sensitivity of the coax probe. This option should, therefore, not be selected when using rope or rod probes. concrete wall The "concrete wall" option takes into account the signal-damping property of concrete walls when mounting with < 1 m distance to the wall. Function "medium property" (003)
⇒ This function is used to select the dielectric constant. Selection: • unknown • 1.4 ... 1.6 (for coaxial probe only) • 1.6 ... 1.9 • 1.9 ... 2.5 • 2.5 ... 4.0 • 4.0 ... 7.0 • > 7.0 Media group
DK (εr)
0
unknown
1
1,4 … 1,6
2
1,6 … 1,9
– Plastic granules – White lime, special cement – Sugar
– – – –
3
1,9 … 2,5
– Portland cement, plasters
– Mineral oils, fuels
30 m
4
2,5 … 4
– Cereals, seeds – Ground stone – Sand
– Benzene, styrene, toluene – Furan – Naphthalene
35 m
5
4…7
– Naturally-moist (ground) stone, ores – Salt
– Chlorobenzene, chloroform – Cellulose spray – Isocyanate, aniline
35 m
6
>7
– Metal powder
– Aqueous solutions – Alcohols – Ammoniac
35 m
Typical bulk solids
Typical liquids
– Liquefied gases, e.g. N2, CO2 Liquefied gas, e.g. propane Solvents Frigen / freon Palm oil
Typical measuring range
4 m, coax probe only 25 m
The lower group applies to very loose or loosened bulk solids. Reduction of the max. possible measuring range by means of: • extremely loose surfaces of bulk solids, e.g. bulk solids with low piled density when filled pneumatically. • Build-up, primarily of moist products.
50
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
6 Commissioning
Function "process propert." (004)
⇒ Use this function to adapt the device reaction to the filling speed in the tank. The setting impacts on an intelligent filter. Selection: • standard • fast change • slow change • test:no filter Selection:
standard
fast change
slow change
test:no filter
Application:
For all normal applications, bulk solids and fluids at low to medium filling speed and sufficiently large tanks.
Small tanks, primarily with fluids, at high filling speeds.
Applications with strong surface movement, e.g. caused by stirrer, primarily large tanks with slow to medium filling speed.
Shortest reaction time: • For test purposes • Measurement in small tanks at high filling speeds, if "rapid change" setting is too slow.
2-wire electronics:
Dead time: 4 s Rise time: 18 s
Dead time: 2 s Rise time: 5 s
Dead time: 6 s Rise time: 40 s
Dead time: 1 s Rise time: 0 s
4-wire electronics:
Dead time: 2 s Rise time: 11 s
Dead time: 1 s Rise time: 3 s
Dead time: 3 s Rise time: 25 s
Dead time: 0,7 s Rise time: 0 s
Function "end of probe" (030)
⇒ Use this function to select the polarity of the probe end signal. If the probe end is uncovered or in an insulated attachment, there is a negative probe end signal. The signal from the probe end is positive if the attachment is grounded. Selection: • free • tie down isol. • tie down gnd.
Endress+Hauser
51
6 Commissioning
Levelflex M FMP 40 with HART/4...20 mA
Function "probe length" (031)
⇒ Use this function to select whether the probe length was changed after factory calibration. Only then is it necessary to enter or correct the probe length. Selection: • not modified • modified
!
Note! If "modified" was selected in the "probe length" (031) function, the probe length is defined in the next step. Function "probe" (032)
⇒ Use this function to select whether the probe is at the time of the commisioning uncovered or covered. If the probe is uncovered, the Levelflex can determine the probe length automatically "determine length" (034). function. If the probe is covered, a correct entry is required in the "probe length" (033) function Selection: • free • covered Function "probe length" (033)
⇒ Use this function, the probe length can be entered manually. Function "determine length" (034)
⇒ Use this function, the probe length can be determined automatically. Selection: • length ok • too short • too long After selection "length too short" or "length too long", the calculation of the new value need approx. 10 s.
52
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
6 Commissioning
Function "empty calibr." (005)
⇒ This function is used to enter the distance from the flange (reference point of the measurement) to the minimum level (=zero).
E = empty calibration (= zero)
E
Emax = probe length – lower blocking distance
0%
Function "full calibr." (006)
⇒ This function is used to enter the distance from the minimum level to the maximum level (=span).
100%
F = full calibration (= span)
F
Fmax = E – upper blocking distance
0%
Endress+Hauser
53
6 Commissioning
!
Levelflex M FMP 40 with HART/4...20 mA
Note! The usable measuring range lies between the lower and the upper blocking distance. The values for empty distance (E) and span (F) can be set independently of this. Blocking distance and measuring range for Dk ≥ 1.6 (1.4 for coax probes): FMP 40
LN [m]/"
UB [m]/"
LB [m]/"
min
max
min
min
1/40
35/1378
0,2/8 1)
0,25/10
6 mm rod probe
0,3/12
2/80
0,2/8 1)
0,05/2
16 mm rod probe
0,3/12
4/178
0,2/8 1)
0,05/2
Coax probe
0,3/12
4/178
0/0
0,05/2
Rope probe
1) The indicated blocking distances are prearised. At media with DK >7, the upper blocking distance UB can be reduced for rod- and rope probes on 0.1m. The upper blocking distance UB can be entered manually.
!
54
Note! Within the upper and lower blocking distance, a reliable measurement can not be guaranteed.
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
6 Commissioning
Display (008)
⇒ The distance measured from the reference point to the product surface and the meas. value calculated with the aid of the empty adjustment are displayed. Check whether the values correspond to the actual meas. value or the actual distance. The following cases can occur: • Distance correct – meas. value correct -> continue with the next function, "check distance" (051) • Distance correct – meas. value incorrect -> Check "empty calibr." (005) • Distance incorrect – meas. value incorrect -> continue with the next function, "check distance" (051) Function "check distance" (051)
⇒ This function triggers the mapping of interference echoes. To do so, the measured distance must be compared with the actual distance to the product surface. The following options are available for selection: Selection: • distance = ok • dist. too small • dist. too big • dist. unknown • manual • probe free
distance too small
distance = ok
+ + distance = ok Use this function at part-covered probe. Choosing function "manual" or "probe free" at free probe. • mapping is carried out up to the currently measured echo • The range to be suppressed is suggested in the "range of mapping (052)" function Anyway, it is wise to carry out a mapping even in this case.
! Endress+Hauser
Note! At free probe, the mapping should be confirmed with the choice "probe free".
55
6 Commissioning
Levelflex M FMP 40 with HART/4...20 mA
dist. too small • At the moment, an interference is being evaluated • Therefore, a mapping is carried out including the presently measured echoes • The range to be suppressed is suggested in the "range of mapping (052)" function dist. too big • This error cannot be remedied by interference echo mapping • Check the application parameters (002), (003), (004) and "probe length." (031) dist. unknown If the actual distance is not known, no mapping can be carried out. manual A mapping is also possible by manual entry of the range to be suppressed. This entry is made in the "range of mapping (052)" function.
"
Caution! The range of mapping must end 0.3 m (20") before the echo of the actual level. In case of empty vessel it is possible to make a map over the whole probe length. probe free If the probe is uncovered, mapping is carried out along the whole probe length.
"
Caution! Only begin mapping in this function if the probe is safely uncovered. Otherwise, the device will not make correct measurements. Function "range of mapping" (052)
⇒ This function displays the suggested range of mapping. The reference point is always the reference point of the measurement (see Page 47 ff.). This value can be edited by the operator. For manual mapping, the default value is 0,3 m. Function "start mapping" (053)
⇒ This function is used to start the interference echo mapping up to the distance given in "range of mapping" (052). Selection: • off: no mapping is carried out • on: mapping is started
56
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
6 Commissioning
Display (008)
⇒ The distance measured from the reference point to the product surface and the meas. value calculated with the aid of the empty alignment are displayed again. Check whether the values correspond to the actual meas. value or the actual distance. The following cases can occur: • Distance correct – meas. value correct -> basic setup completed • Distance incorrect – meas. value incorrect -> a further interference echo mapping must be carried out "check distance" (051). • Distance correct – meas. value incorrect -> check "empty calibr." (005)
⇒ ⇓ !
Note! After the basic setup, an evaluation of the measurement with the aid of the envelope curve ("envelope curve" (0E)" function group) is recommended (see page 89).
6.5
!
After 3 s, the following message appears
Blocking distnace
Note! At installation in high nozzles, please the blocking distance in the function "upper block.dist" (059) newly enter!
⇒
Endress+Hauser
57
6 Commissioning
Levelflex M FMP 40 with HART/4...20 mA
6.5.1
Envelope curve with VU 331
After the basic setup, an evaluation of the measurement with the aid of the envelope curve ("envelope curve" (0E) function group) is recommended.).
6.5.2
Function "plot settings" (0E1)
⇒ Here you can select which information is shown on the display: • envelope curve • substracted signal • mapping
6.5.3
Function "recording curve" (0E2)
Function "recording curve" (09B) This function determines whether the envelope curve is read as: • single curve or • cyclic.
⇒ !
58
Note! If the envelope curve mode is active on the display, the measured values are updated in a slower cycle time. Thus, it is advisable to leave the envelope curve mode after the measuring point has been optimised.
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
6.6
6 Commissioning
Function "envelope curve display" (0E3)
You can obtain the following information from the envelope curve display in this function:
full calibr.
quality of evaluated echo
empty calibr.
evaluated echo is marked
envelope curve
minimum distance of the plot
full calibr.
distance of evaluated echo
probe length
empty calibr.
maximum distance of the plot
level echo
mapping
empty calibr.
level echo
substracted signal
probe length
Navigation in the envelope curve display Using navigation, the envelope curve can be scaled horizontally and vertically and shifted to the left or the right. The active navigation mode is indicated by a symbol in the top left hand corner of the display. Horizontal Zoom mode: - horizontal zoom in - horizontal zoom out Move mode: - moved to the left - moved to the right Vertical Zoom mode:
…
Endress+Hauser
- vertical zoom (4 steps)
59
6 Commissioning
Levelflex M FMP 40 with HART/4...20 mA
Horizontal-Zoom-Modus Press O or S, to switch to the envelope curve navigation. You are then in Horizontal Zoom mode. Either or is displayed. You now have the following options: • O increases the horizontal scale. • S decreases the horizontal scale.
S
O
Move-Modus Then press F, to switch to Move mode. Either You now have the following options: • O shifts the curve to the right. • S shifts the curve to the left.
S
or
O
Vertical-Zoom-Modus Press F, once more to switch to Vertical Zoom mode You now have the following options: • O increases the vertical scale. • S decreases the vertical scale. The display icon shows the current zoom factor ( to
S
is displayed.
is displayed.
).
O
Exiting the navigation • Press F again to run through the different modes of the envelope curve navigation. • Press O and S to exit the navigation. The set increases and shifts are retained. Only when you reactivate the "recording curve" (0E2) function does the Levelflex use the standard display again.
⇒ ⇓
60
After 3 s, the following message appears
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
6.7
6 Commissioning
Basic Setup with the ToF Tool
To carry out the basic setup with the ToF Tool operating program, proceed as follows: • Start the ToF Tool operating program and establish a connection • Select the "basic setup" function group in the navigation bar The following display appears on the screen: Basic Setup step 1/6: • Status image • Enter the measuring point description (TAG number).
Change to the next page
!
Endress+Hauser
Note! • Each parameter that is changed must be confirmed with the RETURN key! • The "Next" button moves you to the next screen display:
61
6 Commissioning
Levelflex M FMP 40 with HART/4...20 mA
Basic Setup step 2/5: • Enter the application parameters: – tank properties (for a description, see page 49) – medium properties (for a description, see page 50) – process properties(for a description, see page 51)
Basic Setup step 3/6: • Enter the application parameters: – end of probe (for a description, see page 51) – probe length (for a description, see page 52)
62
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
6 Commissioning
Basic Setup step 4/6: • Enter the application parameters: – probe (for a description, see page 52) – probe length (for a description, see page 52) – determine length (for a description, see page 52)
Basic Setup step 5/6: • Enter the application parameters: – empty calibration (for a description, see page 53) – full calibration (for a description, see page 53)
Endress+Hauser
63
6 Commissioning
Levelflex M FMP 40 with HART/4...20 mA
Basic Setup step 6/6: • This step starts the tank mapping • The measured distance and the current measured value are always displayed in the header • for a description, see page 55 measured value
distance
6.7.1
!
64
Blocking distance
Note! At installation in high nozzles, please the blocking distance in the function "upper block.dist" (059) newly enter!
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
6.7.2
6 Commissioning
Envelope curve with the ToF Tool
After the basic setup, an evaluation of the measurement using the envelope curve is recommended (see page 89).
!
Note! For the optimization of the measurement the installation of the Levelflex in another place can be executed when enterference echoes.
6.7.3
User-specific applications (operation)
For details of setting the parameters of user-specific applications, see separate documentation BA 245F/00/en - description of the instrument functions of the Levelflex M.
Endress+Hauser
65
7 Maintenance
Levelflex M FMP 40 with HART/4...20 mA
7
Maintenance
The Levelflex M measuring instrument requires no special maintenance. Exterior cleaning When cleaning the Levelflex M , always use cleaning agents that do not attack the surface of the housing and the seals. Repairs The Endress+Hauser repair concept assumes that the measuring devices have a modular design and that customers are able to undertake repairs themselves. Spare parts are contained in suitable kits. They contain the related replacement instructions. All the spare parts kits which you can order from Endress+Hauser for repairs to the Levelflex M are listed with their order numbers on pages 76 and 77. Please contact Endress+Hauser Service for further information on service and spare parts. Repairs to Ex-approved devices When carrying out repairs to Ex-approved devices, please note the following: • Repairs to Ex-approved devices may only be carried out by trained personnel or by Endress+Hauser Service. • Comply with the prevailing standards, national Ex-area regulations, safety instructions (XA) and certificates. • Only use original spare parts from Endress+Hauser. • When ordering a spare part, please note the device designation on the nameplate. Only replace parts with identical parts. • Carry out repairs according to the instructions. On completion of repairs, carry our the specified routine test on the device. • Only Endress+Hauser Service may convert a certified device into a different certified variant. • Document all repair work and conversions. Replacement After a complete Levelflex M or electronic module has been replaced, the parameters can be downloaded into the instrument again via the communication interface. Prerequisite to this is that the data were uploaded to the PC beforehand using the ToF Tool / Commuwin II. Measurement can continue without having to carry out a new setup. • You may have to activate linearisation (see BA 221F) • You may need to record the tank map again (see Basic Setup) After an probe or electronic has been replaced, a new calibration must be carried out. This is described in the repair instructions.
66
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
8
8 Accessories
Accessories
Various accessories, which can be ordered separately from Endress+Hauser, are available for the Levelflex M. Weather protection cover A Weather protection cover made of stainless steel is available for outdoor mounting (order code: 543199-0001). The shipment includes the protective cover and tension clamp.
Adapter flange FAU 70 E/FAU 70 A
adapter flange
probe
FAU 70 E -
Endress+Hauser
nozzle
Version
Version
12 DN 50 PN 16 14 DN 80 PN 16 15 DN 100 PN 16
12 ANSI 2“ 150 psi 14 ANSI 3“ 150 psi 15 ANSI 4“ 150 psi
Thread 3 G 1½, ISO 228
thread 3 NPT 1½ - 11,5
Material 2 1.4435
Material 2 1.4435
Complete product designation
FAU 70 A -
Complete product designation
67
8 Accessories
Levelflex M FMP 40 with HART/4...20 mA
Flange with horn adapter to adapt on the following nozzles
G 1 1/2" at DN 200 / PN 16 G 1 1/2" at DN 250 / PN 16 NPT 1 1/2" at 8" / 150 psi NPT 1 1/2" at 10" / 150 psi
Order - No. 52014251 52014252 52014253 52014254
204 mm
DN200 (8") DN250 (10")
Extension rod / Centering
DN50 (2") DN80 (3") DN150 (6") DN200 (8") DN250 (10")
HS centering disk at PPS - GF40
#
Not for ¾". For rod probe on request.
Certificate A For non-hazardous areas 2 ATEX II 1D Extension rod 1 115mm-rod for nozzle height 150...250mm / 6...10" 2 215mm-rod for nozzle height 250...350mm / 10...14" 3 315mm-rod for nozzle height 350...450mm / 14...18" 4 415mm-rod for nozzle height 450...550mm / 14...22" 9 Special version Centre disk A without centre disk B DN40 / 1 1/2", inside diam. 40-45mm C DN50 / 2", inside diam. 50...57mm D DN80, inside diam. 80...85mm E 3", inside diam. 76...78mm G DN100 / 4", inside diam. 100...110mm H DN150 / 6", inside diam. 152...164mm J DN200 / 8", inside diam. 201...215mm K DN250 / 10", inside diam. 253...269mm Y Special version HMP40-
68
complete product designation
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
8 Accessories
Isolated tie down
for 4mm rope probe for 6mm rope probe
Order - No. 52014249 52014250
If a rope probe has to be fixed and a secure grounded mounting is not possible, we recommend using the insulating sleeve made of PEEK-GF30 with accompanying DIN 580 eye-bolt made of stainless steel. Max. process temp. 150 °C.
Reliable, isolated mounting
Insulating sleeve
D
eye-bolt D = 20 mm at M8 DIN 580 for 4 mm rope D = 25 mm at M10 DIN 580 for 6 mm rope
Due to the risk of electrostatic charge, the insulating sleeve is not suitable for use in hazardous areas. In these cases the fixing must be reliably grounded (see page 23).
Commubox FXA 191 HART For intrinsically safe communication with ToF Tool or Commuwin II via the RS 232Cinterface. Service adapter FXA 193 For communication with ToF Tool via the display connector. (Bestell-Nr.: 50095566). Commuwin II Operating software for intelligent instruments.
Endress+Hauser
69
8 Accessories
Levelflex M FMP 40 with HART/4...20 mA
Remote display FHX 40 Dimensions
F12 housing (IP 68) Separate housing FHX 40 (IP 65)
W
EN
DR
ES
S+
HA US ER
H IP
T
Maulburg
Mes Measber surineich g ra nge U 16 max . 20 4...2 ...36 m 0 m V DC A
65
A >7
0°C :
t >8
5°C
Made in Germany
Orde r Se Code r.-No : .:
D Cable
Technical data: Max. cable length:
20 m (67 ft)
Temperature range:
-30 °C...+70 °C (-22 °F...158 °F)
Separate housing: Degree of protection:
IP65 acc. to EN 60529 (NEMA 4)
Material for housing:
Alloy of Aluminium AL Si 12
Dimensions [mm] / [inch]: 122x150x80 (HxBxT) / 4.8x5.9x3.2 EMC version with conductive sealing Also suitable for use in zone 1, in combination with a Levelflex M with ATEX II 1/2 G EEx ia IIC T6 approval.
70
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
9 Trouble-shooting
9
Trouble-shooting
9.1
Trouble-shooting instructions Levelflex M FMP 40 -Trouble Shooting Check voltage and compare it with the specifications on the nameplate.
Instrument does not respond
Not ok
Connect the correct voltage
Instrument works?
Yes
Ready
No
ok Check the polarity of the voltage.
Not ok
Correct the polarity
Check power connection to electronic board
Not ok
Connect plug
Contrast:
Ready
Instrument works?
Yes
Ready
No
ok
Yes
Yes
No
ok
Values on display invissible
Instrument works?
F+ O
ok
Ready
Not ok
No
Check plug contact of the display.
Not ok
Connect the plug correctly
Yes
Display works?
Ready
No
ok Output current between 3.6 …22mA ?
Yes
The display is possibly defective. Contact E+H Service
No Output current < 3.6 mA ? (2 wire) < 2.4 mA ? (4 wire)
Yes
Check cabling
Not ok
Yes
Correct the cabling
Current is ok?
Install the fuse (see the OM)
Communication ok?
ok
Ready
No
Possibly defective electronics Contact E+H Service HART communication does not function
Yes
Is the communication resistor installed according to the OM?
Not ok
Yes
Ready
No
ok Is the Commubox connected according to the OM?
Not ok
Connect the Commubox (see the OM)
Communication ok?
Not ok
Set the switch correctly
Communication ok?
Yes
Check cabling + terminator
Ready
Contact E+H Service
Not ok
Correct cabling + terminator
Communication ok?
Yes
Ready
No
ok
EMC interference?
Yes
No
ok
Communication PA does not function
Ready
No
ok Is the switch on the Commubox for selecting HART/Intensor in the correct position?
Yes
Yes
Check screening (see BA Section 'Connection’)
Communication ok?
Yes
Ready
No
No
Contact E+H Service Communication via Service adapter FXA 193 does not function
Yes
Check configuration of COM port on PC
Not ok
Correct configuration
Communication ok? No
Instrument measures incorrectly
Yes
Check basic setup ok
Not ok
Repeat basic setup
Yes
Ready
Contact E+H Service
Measurement ok?
Yes
Ready
No
Proceed according to section 'Trouble shooting’ in OM
Endress+Hauser
71
9 Trouble-shooting
Levelflex M FMP 40 with HART/4...20 mA
9.2 Code
Description
Possible cause
Remedy
A102
checksum error general reset & new calibr.required
device has been powered off before data could be stored; emc problem; E²PROM defect
reset; avoid emc problem; if alarm prevails after reset, exchange electronics
W103
initialising - please wait
E²PROM storage not yet finished
wait some seconds; if warning prevails, exchange electronics
A106
downloading please wait
processing data download
wait until warning disappears
A110
checksum error general reset & new calibr.required
device has been powered off before data could be stored; emc problem; E²PROM defect
reset; avoid emc problem; if alarm prevails after reset, exchange electronics
A111
electronics defect
RAM defective
reset; if alarm prevails after reset, exchange electronics
A113
electronics defect
ROM defective
reset; if alarm prevails after reset, exchange electronics
A114
electronics defect
E2PROM defective
reset; if alarm prevails after reset, exchange electronics
A115
electronics defect
general hardware problem
reset; if alarm prevails after reset, exchange electronics
A116
download error repeat download
checksum of stored data not correct
restart download of data
A121
electronics defect
no factory calibration existant; E²PROM defective
contact service
W153
initialising - please wait
initialisation of electronics
wait some seconds; if warning prevails, power off device and power on again
A160
checksum error general reset & new calibr.required
device has been powered off before data could be stored; emc problem; E²PROM defect
reset; avoid emc problem; if alarm prevails after reset, exchange electronics
A164
electronics defect
hardware problem
reset; if alarm prevails after reset, exchange electronics
A171
electronics defect
hardware problem
reset; if alarm prevails after reset, exchange electronics
A221
Probe pulse deviation from average values
HF module or cable between HF module and electronics defective
Check contacts on HF module If fault cannot be eliminated: Replace HF module
Tab. 3
72
System error messages
System error messages
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
Code
Description
Possible cause
Remedy
A241
Broken probe
Broken probe or value for probe length is too short
Check the probe length in 033, Check the probe itself, if the probe is broken, change the probe, or change to a non contact system
A251
Feedthrough
Lost contact in the process feedthrough
Replace process feedtrough
A261
HF cable defective
HF cable defective or HF connector removed
Check HF connector, replace cable if defective
A275
Offset too high
Temperature at the electronics too high or HF module defective
Check temperature, replace HF module if defective
A512
recording of mapping please wait
mapping active
wait some seconds until alarm disappears
W601
linearisation ch1 curve not monotone
linearization not monotonously increasing
correct linearisation table
W611
less than 2 linearisation points for channel 1
number of entered linearization points < 2
correct linearisation table
W621
simulation ch. 1 on
simulation mode is active
switch off simulation mode
E641
no usable echo channel 1 check calibr.
echo lost due to application conditions of built up on antenna
check installation; clean antenna (cf. Operating Instructions)
W650
Signal/noise ratio too low or no echo
noise on signal to high
eliminate electromagnetic interference
E651
level in safety distance - risk of overspill
level in safety distance
alarm will disappear as soon as level leaves safety distance;
A671
linearisation ch1 not complete, not usable
linearisation table is in edit mode
activate linearisation table
W681
current ch1 out of range
current out of range (3,8 mA ... 21,5 mA)
check calibration and linearisation
Tab. 3
Endress+Hauser
9 Trouble-shooting
System error messages
73
9 Trouble-shooting
Levelflex M FMP 40 with HART/4...20 mA
9.3
Application errors
Error
Output
Possible cause
Remedy
A warning or alarm has occurred.
Depending on the configuration
See table of error messages (see page 72)
1. See table of error messages (see page 72)
Measured distance (008) OK? D m/ft (008)
Measured value (00) is incorrect F m/ft
yes → 1. Check empty calibr. (005) and full calibr. (006). 2. Check linearisation: → level/ullage (040) → max. scale (046) → diameter vessel (047) → Check table
20 mA/100%
expected
no ↓ actual E m/ft t→
4 mA/0%
No change off measured value on filling/emptying
20 mA/100%
An interference echo may have been evaluated.
yes → 1. Carry out tank mapping → basic setup
Interference echo from installations, nozzle or extension on the antenna
1. Carry out tank mapping → basic setup
noise level during the initialisation phase to high.
Repeat once more empty calibr. (005). Caution! Before conformation change with O or S to the edit mode.
2. If necessary, clean probe. 3. If necessary, select better mounting position
actual
expected 4 mA/0%
E 641 (loss of echo) after turn on the power supply
74
t→
If the instrument is configured to Hold by loss of echo the output is set to any value/current.
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
9 Trouble-shooting
Device displays a level when the tank is empty.
Incorrect probe length
1. Carry out automatic probe length detection when the tank is empty. 2. Carry out mapping over entire probe when the tank is empty (probe free).
Tank properties incorrect.
LN < 4 m and "Aluminium tank" tank properties selected → Calibration not possible. → Selection → Select standard → Thresholds too high
Medium properties incorrect.
Select lower medium properties.
20 mA/100%
actual expected t→
4 mA/0%
Measured value incorrect (slope error in the entire measuring range)
20 mA/100% expected
2.) actual 1.) actual 4 mA/0%
Endress+Hauser
t→
75
9 Trouble-shooting
Levelflex M FMP 40 with HART/4...20 mA
9.4
!
Spare parts
Note! You can order spare parts directly from your E+H service organization by giving the serial number which is printed on the measuring transducer nameplate (see Page 6 ff.). The corresponding spare part number also appears on each spare part. Installation instructions are given on the instruction card that is also delivered. Spare parts Levelflex M FMP 40 with housing F12
Only identical, original E+H spare parts may be used. The instrument may only be maintained and repaired by qualified personnel. The device documentation, applicable standards and legal requirements as well as any certificates have to be observed!
021
Housing F12: standard, complete pre-mounted, incl. nameplate, cable gland and Teflon filter 543 120 - 0022 G ½" cable gland 543 120 - 0023 NPT ½" cable gland 543 120 - 0024 M20 x 1.5 PA cable gland 5201 3409 M20 x 1.5 metal cable gland (not for lid with sight glas) 5200 1992 M12 PROFIBUS PA plug 5200 8556 7/8 UNC Fieldbus Foundation plug 5201 3348 G ½" cable gland, 4 wire 5201 3349 NPT ½" cable gland, 4 wire 5201 3350 4 wire, M20 x 1.5 PA cable gland 5201 3351 4 wire, M20 x 1.5 metal cable gland (not for lid with sight glas)
O-ring
O-ring
C
C
The spare parts listed are generally suitable for use in Ex-devices
Terminal module with connection cable • Version HART (4 pole) 5200 6197 • Version PROFIBUS PA and Foundation Fieldbus 5201 2156
or
Power supply for 4wire electronics 10.5... 32 V DC 5201 3304 90 ...250 V AC 5201 3305
Hood for terminal compartment F12 cpl. 5200 6026
EN D MIC RES Ord er RO S+H Ser Cod PIL AU e: .-N o.: OT SE R II Mes Measber surineich g ra nge U 16 max . 20 4...2 ...36 m 0m VD A C
5°C
Made in Germany
A >7
t >8
l
65
T
0°C :
ina
Maulburg
rm Te
IP
1
2
Electronic module, Ex version * HART (2pole) 5201 3244 HART (4pole) 5201 3245 PROFIBUS PA 5201 3242 Foundation Fieldbus 5201 3243
4
3
A
Cover with O-ring for housing F12/T12 • with sight glas (not for ATEX II 1/2D) 5200 5936 • without sight glas 517 391-0011
retaining screw Stop screw
B kers -Stec h: nKoax Ex-Bereicgezogehe des hen el) im ss bei ab tatisc Sonde en). i Abzie Wechs n, da elektros der tleer ng be odul stelle ine pazität) er En fort rs Achtu B. HF-Msicherzu tecker keerte Ka füllen odtecker so tecke h: (z. ist ax-S (isoli rch Be ax-S ax-S eic genEs Ko ng du s Ko -Ber zo em fladu (z.B. turen Koken! n de im Ex i abge ische e Au folgt para fstec ziehe hsel) ss be ostat r Sond eren). er i Re au Be eder ng bei Abodul Wec llen, daine elektrzität) de er Entlefort ste wi pa Achtu B. HF-Msicherzu tecker keerte Ka füllen odtecker so (z. ist ax-S (isoli rch Be ax-S Es Ko ng du em fladu (z.B. turen Koken! Au folgt para fstec er i Re au Be eder wi
O-ring O-ring
coa
D
xia
l pl
ug EN
HF module * 5201 3378
* Ex-protection: threaded boss thread ¾" thread 1½"
E
Attention! When taking the coax-plug (e.g. HF module off change) within the ex area: It is to be guaranteed that with taken off coax-plug no electrostatic loading (capacity isolated) of the probe takes place (e.g. by filling or emptying). Attach coaxial plugs immediately with repairs again!
Type of probes and spare parts for probes see other drawing
DR
ES
S+
US HA
ER
Control and display module VU 331 5200 5585 (cover with sight glas required)
Screw set 535 720 - 9020 consist of: 1 stop screw M5x10; 1 retaining screw M8x10; Note the mounting instructions !
Pos. A Pos. B
NordLock washers Gasket set 5201 0526 consist of: 2 gaskets 25 x 20.5 x 2 FA; 1 O-ring 49.21 x 3.53 EPDM; 1 O-ring 113.9 x 3.63 EPDM; 1 O-ring 72.0 x 3.0 EPDM
Pos. C Pos. D Pos. E
probe rope probe rod
76
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
9 Trouble-shooting
Spare parts Levelflex M FMP 40 with housing T12 Only identical, original E+H spare parts may be used. The instrument may only be maintained and repaired by qualified personnel. The device documentation, applicable standards and legal requirements as well as any certificates have to be observed!
021
Housing T12, complete pre-mounted with lid for terminal compartment cable gland/ entry order No.
0 2 1
only certificates A; F; N plug plug PROFIBUS Fieldbus FF 5200 6204 543180-1023 5200 6205 5201 3411 5201 3410 G½
NPT½
The spare parts listed are generally suitable for use in Ex-devices
M20 x 1.5
Cable glands for Ex-devices may only be replaced with the same type (observe marking on packaging and permissible temp. range, T>75° C).
Cover 518 710 - 0020 (the cover is already included when ordering a housing) Terminal module T12 HART 5201 3302 PA/FF 5201 3303
F O-ring
Electronic module, Ex version* HART ( 2 wire) 5201 3244 PROFIBUS PA 5201 3242 Foundation Fieldbus 5201 3243
Cover plate T12 5200 5643 EN
D
MIC RES Ord er RO S+H Se Cod PIL AU r.-N e o.: : OT SE
FM R R
Maulburg
C
IP T
65
A >7
0°C
: t >8
5°C
Made in Germany
O-rings
Me Messbere asu ic ring h ran ge U1 ma x. 2 4...26...36 0m 0m VD A C
A
retaining screw stop screw
s tecker h: ax-S eic gens Ko -Ber zo n de im Ex i abge tische e ziehe echsel) dass be osta r Sond eren). bei Abodul W tellen, ine elektrzität) de er Entlefort ung pa us s Acht .B. HF-Msicherz tecker keerte Ka füllen odtecker so tecker h: (z ist ax-S (isoli rch Be ax-S ax-S eic genEs Ko ng . du n Ko s Ko -Ber zo em fladu (z.B ture ken! n de im Ex i abge tische e Au folgt para fstec ziehe hsel) ss be osta r Sond eren). er i Re au Be eder g bei Abodul Wectellen, daine elektrzität) de er Entlefort wi un pa us Acht .B. HF-Msicherz tecker keerte Ka füllen odtecker so (z ist ax-S (isoli rch Be ax-S Es Ko ng . du n Ko em fladu (z.B ture ken! Au folgt para fstec er i Re au Be eder wi
ER US HA S+ ES DR EN
B coa
xia
O-ring
Control and display module VU 331 5200 5585 (requires lid with sight glass)
l pl
ug
D HF module * 5201 3378
O-ring
E
* Ex-protection:
threaded boss thread ¾" thread 1½"
Attention! When taking the coax-plug (e.g. HF module off change) within the ex area: It is to be guaranteed that with taken off coax-plug no electrostatic loading (capacity isolated) of the probe takes place (e.g. by filling or emptying). Attach coaxial plugs immediately with repairs again!
Type of probes and spare parts for probes see other drawing
NordLock washers
Cover with O-ring for housing F12/T12 • with sight glas (not for ATEX II 1/2D) 5200 5936 • without sight glas 517 391-0011
Screw set 535 720 - 9020 consist of: 1 stop screw M5x10; 1 retaining screw M8x10; Note the mounting instructions ! Gasket set 5201 0526 consist of: 2 gaskets 25 x 20.5 x 2 FA; 1 O-ring 49.21 x 3.53 EPDM; 1 O-ring 113.9 x 3.63 EPDM; 1 O-ring 72.0 x 3.0 EPDM;
pos. A pos. B
pos. C pos. D pos. E pos. F
probe rope probe rod
Endress+Hauser
77
9 Trouble-shooting
Levelflex M FMP 40 with HART/4...20 mA
Spare parts Levelflex M FMP 40 - probes and accessories
EN DR MIC ES RO S+HA PILO US T II ER
Ord
er Co r.-N de: o.:
Se
T
A >7
0°C
IP
65
: t >85
°C
T
A >7
0°C
Maulburg
IP
Housing F12
EN DR MIC ES RO S+HA PILO US T II ER
er Co r.-N de: o.:
Me Messbere asu ich ring ran U 16. ge ma x. 20 4... ..36 20 m mAV DC
Maulburg
Me Messbere asu ich ring ran U 16. ge ma x. 20 4... ..36 20 m mAV DC
Made in Germany
Se
65
: t >85
°C
Housing T12
Made in Germany
Ord
O-ring 49.21 x 3.53 (see set of gaskets)
Distance pipe 400 mm with HF cable 5201 3413
remote electronic length 3m 52013414
If changing parts of probe, note hints of the assembly please !
O-ring 49.21 x 3.53 (see set of gaskets)
Flange connection standard flange ≥ DN40
Process connection
thread ¾" or 1½" pipe diameter 21 mm or 42 mm max. length 4 m
thread ¾" or 1½"
NordLock washers
Probe rod 6 mm for process connection ¾" max. length 2 m Probe rod 16 mm for process connection 1½" max. length 4 m
78
Coaxial probe Process connection
NordLock washers
Weight for rope 6 mm 5201 3352
Weight for rope 4 mm 5201 3353
Probe rod 6 mm for process connection ¾" max. length 2 m Probe rod 16 mm for process connection 1½" max. length 4 m
Find out the order code FMP 40X _ _ _ _ _ _ for complete probes with variants from the product structure list
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
9.5
9 Trouble-shooting
Return
The following procedures must be carried out before a transmitter is sent to Endress+Hauser e.g. for repair or calibration: • Remove all residue which may be present. Pay special attention to the gasket grooves and crevices where fluid may be present. This is especially important if the fluid is dangerous to health, e.g. corrosive, poisonous, carcinogenic, radioactive, etc. • Always enclose a duly completed "Declaration of contamination" form (a copy of the “Declaration of contamination” is included at the end of this operating manual). Only then can Endress +Hauser transport, examine and repair a returned device. • Enclose special handling instructions if necessary, for example a safety data sheet as per EN 91/155/EEC. Additionally specify: • An exact description of the application. • The chemical and physical characteristics of the product. • A short description of the error that occurred (specify error code if possible) • If necessary, give the error code.
9.6
Disposal
In case of disposal please seperate the different components according to their material consistence.
9.7
Software history
Software version / Date
Software changes
V 01.02.00 / 04.2002
Original software. Operated via: – ToF Tool – Commuwin II (from version 2.05.03) – HART communicator DXR 275 (from OS 4.6) with Rev. 1, DD 1.
9.8
Documentation changes
Contact addresses of Endress+Hauser
The addresses of Endress+Hauser are given on the back cover of this operating manual. If you have any questions, please do not hesitate to contact your E+H representative.
Endress+Hauser
79
10 Technical data
Levelflex M FMP 40 with HART/4...20 mA
10
Technical data
10.1 Technical data at a glance Application Application
The Levelflex M performs continuous level measurement of powdery to granular bulk solids and liquids e.g. plastic granulate. Probes are available with threaded process connections from ¾" and flanges from DN40 / 1½": • Rope probes, above all for measurement in bulk solids, measuring range up to 35 m/1378" • Rod probes, above all for liquids • Coax probes, for liquids
Function and system design Measuring principle
The Levelflex is a "downward-looking" measuring system that functions according to the ToF method (ToF = Time of Flight). The distance from the reference point (process connection of the measuring device see page 12) to the product surface is measured. High-frequency pulses are injected to a probe and led along the probe. The pulses are reflected by the product surface, received by the electronic evaluation unit and converted into level information. This method is also known as TDR (Time Domain Reflectometry).
Equipment architecture
see Page 91 ff.
Input Measured variable
The measured variable is the distance between the reference point and the product surface. Subject to the input zero point empty distance the level is calculated. Alternatively, the level can be converted by means of linearisation into other variables (volume, mass).
Measuring range
see Technical Information TI 358F
Output Output signal
• 4…20 mA with HART protocol
Signal on alarm
Error information can be accessed via the following interfaces: • Local display: – Error symbol (see page 38) – Plain text display • Current output • Digital interface
Auxiliary energy
80
Electrical connection
Two housings are available: • Housing F 12 with additionally sealed terminal compartment for standard or EEx ia • Housing T 12 with separate terminal compartment for standard, EEx e or EEx d..
Load HART
Minimum load for HART communication: 250 Ω
Cable entry
see Page 31 ff.
Supply voltage
see Page 31 ff.
Power consumption
min. 60 mW, max. 900 mW
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
10 Technical data
Performance characteristics Reference operating conditions
• • • •
temperature = +20 °C (68 °F) ±5 °C (9 °F) pressure = 1013 mbar abs. (14.7 psia) ±20 mbar (0.3 psi) relative humidity (air) = 65 % ± 20% Reflection factor 0.8 (surface of water for coax probe, metal plate for rod and rope probe with min. 1 m ∅) • Flange for rod or rope probe ≥ 30 cm ∅ • Distance to obstructions ≥ 1 m
Maximum measured error
Typical statements for reference conditions, include linearity, repeatability, and hysteresis: • Linearity: – up to 10 m/400" measuring range: ±3 mm – 10 m/400" to 35 m/1378" measuring range: ± 0,03 % According to IEC 60770-1
Operating conditions Operating conditions Installation instructions
see Page 13 ff.
Environment
Endress+Hauser
Ambient temperature range
The measurements are carried out in accordance with EN 61298-3: • digital output (HART, PROFIBUS PA, Foundation Fieldbus): – FMP 40 average TK: 0.6 mm/10 K, max. ± 3.5 mm over the entire temperature range -40 °C...+80 °C 2-wire: • Current output (additional error, in reference to the span of 16 mA): – Zero point (4 mA) average TK: 0.032 %/10 K, max. 0.35 % over the entire temperature range -40 °C...+80 °C – Span (20 mA) average TK: 0.05 %/10 K, max. 0.5 % over the entire temperature range 40 °C...+80 °C 4-wire: • Current output (additional error, in reference to the span of 16 mA): – Zero point (4 mA) average TK: 0.02 %/10 K, max. 0.29 % over the entire temperature range -40 °C...+80 °C – Span (20 mA) average TK: 0.06 %/10 K, max. 0.89 % over the entire temperature range -40 °C...+80 °C
Storage temperature
-40 °C ... +80 °C
Climate class
DIN EN 60068-2-38 (test Z/AD)
Degree of protection
• housing: IP 68, NEMA 4X (open housing: IP20, NEMA 1) • probe: IP 68 (NEMA 6P)
Vibration resistance
DIN EN 60068-2-64 / IEC 68-2-64: 20…2000 Hz, 1 (m/s²)²/Hz
Cleaning of the probe
see Technical Information TI 358F
81
10 Technical data
Levelflex M FMP 40 with HART/4...20 mA
Electromagnetic compatibility
When installing the probes in metal and concrete tanks and when using a coax probe: • Interference Emission to EN 61326, Electrical Equipment Class B • Interference Immunity to EN 61326, Annex A (Industrial) When rod and rope probes are installed in plastic and wood silos, the influence of strong electromagnetic fields can have an effect on the measured value. Interference Emission to EN 61326 is in this case: Class A.
Process conditions Process temperature range
see Technical Information TI 358F
Process temperature limits
see Technical Information TI 358F
Process pressure limits
see Technical Information TI 358F
Dielectric constant
• with coax probe: εr ≥ 1,4 • Rod and rope probe: εr ≥ 1,6
Mechanical construction Design, dimensions
see page 12
Weight
see Technical Information TI 358F
Material
see Technical Information TI 358F
Process connection
see Technical Information TI 358F
Human interface Operation concept
see page 35
Display
see page 35
Certificates and approvals CE approval
The measuring system meets the legal requirements of the EC-guidelines. Endress+Hauser confirms the instrument passing the required tests by attaching the CE-mark.
External standards and guidelines
EN 60529 Protection class of housing (IP-code) EN 61010 Safety regulations for electrical devices for measurement, control, regulation and laboratory use. EN 61326 Emissions (equipment class B), compatibility (appendix A – industrial area) NAMUR Standards committee for measurement and control in the chemical industry
Ex approval
see »Ordering structure Levelflex M FMP 40« on page 6
Ordering Information The E+H service organisation can provide detailed ordering information an information on the order codes on request.
Accessories see page 67
82
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
10 Technical data
Supplementary Documentation Supplementary Documentation
Endress+Hauser
• System Information Levelflex (SI 030F/00/en) • Technical Information (TI 358F/00/en) • Operating Instructions "Description of instrument functions" (BA 245F/00/en)
83
11 Appendix
Levelflex M FMP 40 with HART/4...20 mA
11
Appendix
11.1 Operating menu HART (Display modul), ToF Tool basic setup
00
tank properties
002
standard aluminium tank plastic tank bypass / pipe coax probe concrete wall
safety settings
01
output on alarm
medium cond.
003
unknown DK: 1.4 … 1.6 DK: 1.6 … 1.9 DK: 1.9 … 2.5 DK: 2.5 … 4 DK: 4 … 7 DK: > 7
process proper.
004
outp. echo loss
010
MIN -10% 3.6mA MAX 110% 22mA hold output on alarm
011
030
probe length
04
level/ullage.
040
level CU ullage CU
linearisation
005
enter value
014
ramp %span/min
ramp %MB/min
013
031 probe covered
modified
linearisation
empty calibr.
enter value
not modified
free tie down isolated tie down gnd.
034
in case of echo loss max. 4000 sec. default: 30 s
enter value
end of probe
delay time
012
alarm hold
user specific
length adjustment 03
determine length
end of probe 030
see Function group “leghth adjustment 03”
standard fast change slow change test: no filter
032
033
determine length
034
length OK
free
041
probe length
customer unit
042
linear
customer unit
042
horizontal cyl manual semi-automatic table on
customer unit
042
probe length
033
too short too long
linearisation
043
next point
table no. input level input volume
043 044 045
no
range of mapping
052
start mapping
clear table
045
yes
level DU ullage DU
extended calibr.
05
Selection
050
mapping
dist./meas.value
008
D and L is displayed
check distance
051
input of mapping range
distance = ok manual probe free dist. too small dist. unknown dist. too big
common
pres. Map dist.
delete map.
053
off on
054
is displayed
delete map.
055
no yes
output
06
commun.address
060
no. of preambels
061
low output limit
062
off on envelope curve
display
0E
0E1 plot settings envelope curve substracted signal mapping
09
recording curve single curve cyclic
0E2
language
092
English Deutsch Francais Espanol Italiano Nederlands Katakana (japanese) diagnostics
0A
present error
0A0
previous error
fixed current
tag no.
0C0
fixed cur. value
064
4 mA value
068
no.of decimals
095
current turn down
back to home
093
clear last error
format display
protocol + sw-no.
094
decimal
0A2
reset
0C2
20 mA value
x x.x x.xx x.xxx
1/16”
for reset code see manual system parameter 0C
063
standard
enter time Default: 900 s
0A1
curr. output mode
0A3
unlock parameter
0A4
for enter code see manual serial no.
0C4
Note! The default values of the parameters are typed in boldface. 84
Endress+Hauser
069
Levelflex M FMP 40 with HART/4...20 mA
full calibr.
006
dist./meas.value
008
enter value
check distance
051
range of mapping
052
input of mapping range
distance = ok dist. too small manual probe free
D and L are displayed
11 Appendix
start mapping
053
dist./meas.value
008
D and L are displayed
off on
015
safety distance
from blocking distance default: 0.1m
max. scale
046
max. scale
046
dist./meas.value
008
in safety dist.
016
alarm warning self holding
ackn. alarm
017
no yes
diameter vessel
047
echo quality
056
overspill protection 018 standard german WHG
brocken probe det off on
019
upper block.dist
059
D und L is displayed
is displayed
simulation
offset
057
output damping
058
application par.
0A8
will be added to the measured level
output current
065
Return to Group Selection
dist. unknown dist. too big
067
sim. off sim. level sim. volume sim. current
sep. character
096
066
display test
097
off on
. point , comma
measured dist.
simulation value
0A5
measured level
0A6
not modified modified distance unit
0C5
download mode
Endress+Hauser
0C8
85
86
!
V\VWHPSDUDPHWHU
GLDJQRVWLFV
VHOIFKHFN
VHUYLFH
GLVSOD\
RXWSXW
H[WHQGHGFDOLEU
OLQHDULVDWLRQ
OHQJWK DGMXVWPHQW
VDIHW\VHWWLQJV
EDVLFVHWXS
0DWUL[0DSSLQJ )XQFWLRQ*URXS
9
9 9
*
*'
*%
9$
9
*
*&
9
*
9
9
*
*$
9
9
*
*
WDJQR
SUHVHQWHUURU
FRPPXQ$GGUHVV & **" &**"
SURWRFROVZQR jj ^]*} ]*} jj]*}
FOHDUODVWHUURU NHHS
ODQJXDJH (QJOLVK _ ~ J K\\
SUHYLRXVHUURU
ORZRXWSXWOLPLW ## RQ
QRRISUHDPEHOV & **" &**"
UHVHW & **" &**"
EDFNWRKRPH & **" &**"
FXUURXWSXWPRGH VWDQGDUG \ # \
UDQJHRIPDSSLQJ VWDUWPDSSLQJ & **" ; ;# ; ; RII &**" ;# ; ; PIW LQPP
FKHFNGLVWDQFH \ | \ \ % \ PDQXDO #
OLQHDULVDWLRQ OLQHDU $ j *
OHYHOXOODJH OHYHO&8 `@ % %@
SUREH `\ IUHH
SUREHOHQJWK & **" ; ;# ; ; &**" ;# ; ; @ # \ FXVWRPHUXQLW WDEOHQR & **" ; ;$; q;\ q &**" q;# q;!z% { z%; %; ; ; # ; ; $
+ PHGLXPFRQG XQNQRZQ ! "! UDPSVSDQPLQ & **"* &**" Z
SUREHOHQJWK QRWPRGLILHG \ # \
RXWSHFKRORVV KROG Z
+ WDQNSURSHUWLHV VWDQGDUG
HQGRISUREH IUHH \ \ \%\
+
RXWSXWRQDODUP & **"; &**" [
RXWSXWRQDODUP &JKQ Z [ 0$;P$ $\ #
IRU )03[+$57 *(3 9&:,, + * 9 PHDVXUHGYDOXH
XQORFNSDUDPHWHU & **" &**"! +$57 3$)) VHULDOQR
IRUPDWGLVSOD\ GHFLPDO
IL[HGFXU9DOXH P$ & **";{ [ &**" [ [
SUHV0DSGLVW & **"* &**"* @
LQSXWOHYHO & **" ; ;# ; ; &**" ;# ; ; @ PIWLQPP
GHWHUPLQHOHQJWK OHQJWKRN $ %
GHOD\WLPH & **" &**"
+ SURFHVVSURSHU VWDQGDUG # $% $% #
GLVWDQFHXQLW P # $
PHDVXUHGGLVW @
QRRIGHFLPDOV [[[
VLPXODWLRQ VLPRII ` `
GHOHWHPDS QR
LQSXWYROXPH & **"* &**"
PHDVXUHGOHYHO @
;
GRZQORDGPRGH SDUDPHWHURQO\ %
DSSOLFDWLRQSDU \ # \ \ # \
RYHUVSLOOSURWHFWLRQ VWDQGDUG % ]^_
+
GLDPHWHUYHVVHO & **" ; ;# ; ; &**" ;# ; ; @ PIW LQPP HFKRTXDOLW\ RIIVHW RXWSXWGDPSLQJ & **" & **"* & **"% ; &**" &**"* %# ;% ; } % &**" ;# ; ; V @ P VLPXODWLRQYDOXH RXWSXWFXUUHQW P$YDOXH & **" [ [ & **"* &**" [ &**" & **"*; ;*;# ;* !{;! ;* &**" ;# ; ; # VHSFKDUDFWHU
PD[VFDOH & **"* &**"
+
DFNQ$ODUP QR
+ IXOOFDOLEU & **" ; ;# ; ; &**" ;# ; ; @ PIWLQPP
VDIHW\GLVWDQFH LQVDIHW\GLVW & **"% ;% # ;%J;% ZDUQLQJ &**" ;# ; ; #$\ % @ P
+ HPSW\FDOLEU & **" ; ;# ; ; &**" # ; ; @ PIWLQPP
P$YDOXH & **"* &**"
XSSHUEORFNGLVW & **" ; ;# ; ; &**" ;# ; ; @ SUREHVSHFLILF
EURNHQSUREHGHW RII
+
11 Appendix Levelflex M FMP 40 with HART/4...20 mA
11.2 Operating matrix HART / Commuwin II
Note! In brackets ( ) you can see the maximum value, which can be edit.
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
11 Appendix
11.3 Description of functions
!
Endress+Hauser
Note! A detailed description of the function groups, functions and parameters is given in the documentation BA 245F/00/en - a description of the instrument functions of the Levelflex M.
87
11 Appendix
Levelflex M FMP 40 with HART/4...20 mA
11.4 Function and system design 11.4.1 Measuring principle The Levelflex is a "downward-looking" measuring system that functions according to the ToF method (ToF = Time of Flight). The distance from the reference point (process connection of the measuring device see page 12) to the product surface is measured. High-frequency pulses are injected to a probe and led along the probe. The pulses are reflected by the product surface, received by the electronic evaluation unit and converted into level information. This method is also known as TDR (Time Domain Reflectometry). flange: reference point of measurement
20 mA 100%
D E
probe length LN F
L 4 mA 0%
Input The reflected pulses are transmitted from the probe to the electronics. There, a microprocessor analyses the signals and identifies the level echo, which was generated by the reflection of the high-frequency pulses at the product surface. This clear signal finding benefits from the many years experience with pulse time-of-flight procedures that have been integrated into the development of the PulseMaster® Software. The distance D to the product surface is proportional to the time of flight t of the impulse:
D = c · t/2, with c being the speed of light. Based on the known empty distance E, the level L is calculated: L=E–D Reference point for "E" see above diagram, Details see page 47. The Levelflex possesses functions for the interference echo suppression that can be activated by the user. They guarantee that interference echoes from e.g. internals and struts are not interpreted as level echoes.
88
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
11 Appendix
Output The Levelflex is initially adjusted at the factory to the probe length ordered, so that in most cases only the application parameters, that automatically adapt the device to the measuring conditions, need to be entered. For models with current output, the factory adjustment for zero point and span is F 4 mA and 20 mA, for digital outputs and the display module 0 % and 100 %. A linearisation function with max. 32 points, that is based on a manually or semiautomatically input table, can be activated on-site or via remote operation. This function enables, for example, the conversion of the level into units of volume or weight. An evaluation of the measurement with the aid of the envelope curve Typical curve shape The following examples display typical curve shapes for a rope or rod probe in an empty tank. For all probe types, a negative probe end signal is shown. For rope probes, the end weight causes an additional preliminary positive echo (see rope probe diagram).
Probe end signal Launch pulse
Probe end signal Launch pulse
Rod probe
Rope probe
Level echoes are detected as positive signals in the envelope curve. Interference echoes can be both positive (e.g. reflections from internals) and negative (e.g. nozzles). The envelope curve, the map and the differential curve are used for the evaluation. Level echoes are searched for in the differential curve.
Endress+Hauser
89
11 Appendix
Levelflex M FMP 40 with HART/4...20 mA
Evaluation of the measurement: • The map must correspond to the course of the envelope curve (for rod probes up to approx. 5 cm and for rope probes up to approx. 25 cm before the end of the probe) when the tank is empty. • Amplitudes in the differential curve should be at a level of 0 mV when the tank is empty and lie within the span that is specified by the probe-specific blocking distances. In order to not detect any interference echoes, there must be no signals that exceed the echo threshold when the tank is empty. • For partially-filled tanks, the map may only differ from the envelope curve at the position of the level echo. The level signal is then detected unequivocally as a positive signal in the differential curve. For detecting the level echo, the amplitude must lie above the echo threshold.
Negative probe end signal
Launch pulse
Envelope curve
Mapping
Differential curve = Envelope curve Mapping
90
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
11 Appendix
11.4.2 Equipment architecture Stand-alone • Power supply directly from power line (4-wire) or from transmitter power supply unit (2-wire). • Operation by on-site display or remote operation via HART protocol. PLC - ToF Tool
- COMMUWIN II - ToF Tool
Commubox FXA 191
transmitter power supply unit RMA 422 or RN 221 N (communication resistor included)
service adapter FXA 193
Netz (for 4-wire)
operating and display module VU 331
ENDRESS + HAUSER
%
–
+
E
ENDRESS + HAUSER RMA 422
FXA 191 or DXR 275
HART handheld DXR 275
If the HART communication resistor is not installed in the supply device and HART protocol communication is to be carried out, it is necessary to insert a > 250 Ω communication resistor into the 2-wire line.
Endress+Hauser
91
11 Appendix
Levelflex M FMP 40 with HART/4...20 mA
This product may be protected by at least one of the following patents. Further patents are pending. • • • • • •
92
US 5,345,471 i EP 0 694 235 (under Licence) US 5,517,198 (under Licence) US 5,661,251 i EP 0 780 664 US 5,827,985 i EP 0 780 664 US 5,884,231 i EP 0 780 665 US 5,973,637 i EP 0 928 974
Endress+Hauser
Levelflex M FMP 40 with HART/4...20 mA
Index
Index A Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 Alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Application errors . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
B Basic Setup. . . . . . . . . . . . . . . . . . . . . . . . . . 47, 49, 61
Maximum measured error . . . . . . . . . . . . . . . . . . . . . 81 Measuring principle . . . . . . . . . . . . . . . . . . . . . . . 80, 88 Medium properties. . . . . . . . . . . . . . . . . . . . . . . . 50, 62 Menue structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
N Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
C CE approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Commubox . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Commubox FXA 191 HART. . . . . . . . . . . . . . . . . . . . 69 Commuwin II . . . . . . . . . . . . . . . . . . . . . . . . . 33, 45, 69 Connecting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
D Declaration of conformity . . . . . . . . . . . . . . . . . . . . . . 9 Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . 34 Designated use. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Determine length. . . . . . . . . . . . . . . . . . . . . . . . . 52, 63 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 DXR 275 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
E Empty calibration . . . . . . . . . . . . . . . . . . . . . . . . 53, 63 End of probe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 Engineering hints . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Envelope curve . . . . . . . . . . . . . . . . . . . . . . . . . . 58, 65 Equipotential bonding. . . . . . . . . . . . . . . . . . . . . . . . 34 Error messages. . . . . . . . . . . . . . . . . . . . . . . . . . 42, 72 Ex approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 9, 82 Exterior cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
F F12 housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29, 31 Full calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . 53, 63 FXA 191 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 FXA 193 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
H Handheld unit DXR 275 . . . . . . . . . . . . . . . . . . . . . . 43 HART. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31, 33, 43
I Interference echo mapping . . . . . . . . . . . . . . . . . . . 64
O Operating menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35, 39 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Ordering structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
P Probe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Probe length. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62–63 Process properties. . . . . . . . . . . . . . . . . . . . . . . . 51, 62
R Repairs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Repairs to Ex-approved devices . . . . . . . . . . . . . . . . 66 Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Return. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 RMA 422 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 RN 221 N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
S Safety conventions. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Safety conventions and symbols . . . . . . . . . . . . . . . . . 5 Service adapter FXA 193 . . . . . . . . . . . . . . . . . . . . . . 69 Software history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76–78 System error messages . . . . . . . . . . . . . . . . . . . . . . . 72
T T12 housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30–31 Tank properties . . . . . . . . . . . . . . . . . . . . . . . . . . 49, 62 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 Terminal compartment . . . . . . . . . . . . . . . . . . . . . . . . 31 ToF Tool . . . . . . . . . . . . . . . . . . . . . . . 33, 43, 61, 65, 84 Trouble-shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 Trouble-shooting instructions. . . . . . . . . . . . . . . . . . . 71 Turn housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10, 28
U Unlock parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
K Key assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
V VU 331 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
L Lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
W
M
Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Weather protection cover. . . . . . . . . . . . . . . . . . . . . . 67 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Endress+Hauser
93
Index
94
Levelflex M FMP 40 with HART/4...20 mA
Endress+Hauser
IMPORTANT NOTICE RETURN AUTHORIZATION POLICY Endress+Hauser must pre-approve and assign a Return Authorization number to any instrument you plan to return. Please identify the Return Authorization number clearly on all shipping cartons and paperwork. Please note that the issuance of a Return Authorization number does not automatically mean that credit will be issued, or that the return is covered by our warranty. An Endress+Hauser associate will contact you regarding the disposition of your returned equipment. In order to serve you better, and to protect our employees from any potentially hazardous contaminants, Endress+Hauser must return unopened, at the sender’s expense, all items that do not have a Return Authorization number. To get a Return Authorization number for credit, call 888-ENDRESS To get a Return Authorization number for calibration or repair, call 800-642-8737 To get a Return Authorization number in Canada, call 800-668-3199 Please be sure to include the following information when requesting a Return Authorization number. This information will help us speed up the repair and return process. Customer name: Customer address: Customer phone number: Customer contact: Equipment type: Original sales order or purchase order number: Reason for return: Failure description, if applicable: Process material(s) to which the equipment has been exposed: OSHA Hazard Communication Standard 29CFR 1910.1200 mandates that we take specific steps to protect our employees from exposure to potentially hazardous materials. Therefore, all equipment so exposed must be accompanied by a letter certifying that the equipment has been decontaminated prior to its acceptance by Endress+Hauser. The employees of Endress+Hauser sincerely appreciate your cooperation in following this policy. Address your equipment to:
In Canada:
Endress+Hauser L+P, Dock B 2340 Endress Place Greenwood, IN 46143 Return Authorization number:
Endress+Hauser 1440 Graham’s Lane, #1, Burlington Ont. Canada L7S 1W3 Return Authorization number:
Effective November 1987
For application and selection assistance, in the U.S. call 888-ENDRESS For total support of your installed base, 24 hours a day, in the U.S. call 800-642-8737 Visit us on our web site, www.us.endress.com United States
Canada
Mexico
Endress+Hauser, Inc. 2350 Endress Place Greenwood, IN 46143 Phone: (317) 535-7138 888-ENDRESS FAX: (317) 535-8498
Endress+Hauser Canada Ltd. 1440 Graham’s Lane Unit 1, Burlington ON, L7S 1W3 Phone: (905) 681-9292 800-668-3199 FAX: (905) 681-9444
Endress+Hauser Paseo del Pedregal No. 610 Col. Jardines del Pedregal 01900, Mexico D.F. MEXICO Phone: (525) 568-2405 FAX: (525) 568-7459
Endress+Hauser The Power of Know How
BA242F/00/en/02.03
© 2003 Endress+Hauser, Inc.