Transcript
Liebert GXT is featured in these Scenarios:
Liebert GXT UPS
Scenario B 1-2 Racks Single Phase page 10
Scenario C 3-6 Racks Single Phase page 12
Liebert GXT UPS leads the industry in combining the best total cost of ownership with small size, high capacity and function-rich features. This true online UPS offers internal batteries, unlimited extended external batteries, and internal bypass capability, resulting in continuous uptime for the connected equipment. Designed for rack-mount or tower modes, the Liebert GXT is available in 500, 700, 1,000, 1,500, 2,000, 3,000, 6,000, and 10,000 VA ratings, in both 120V and 230V models.
Features & Benefits Flexibility:
Higher Availability:
Lowest Total Cost Of Ownership:
n
Unit can be installed in either rack or tower configuration.
n
Protection and conditioning against all forms of power anomalies.
n
n
The Liebert GXT automatically detects and matches line input frequencies of either 60 or 50 Hz.
n
Internal automatic and manual bypass assure continuity of power to critical loads during system maintenance or in case of internal fault.
Corrects for frequency variations without switching to battery, resulting in longer battery life.
n
Two-year, no-hassle replacement warranty with paid shipping both ways.
n
Compatible with backup generator — handles frequency variations and other power fluctuations that occur during generator operation.
n
Configuration program allows selection of UPS features including output voltage, auto-restart enable/disable, and other features.
n
Wide input voltage window allows the UPS to support the critical load without having to transfer to battery, extending system availability for when battery backup is truly needed.
n
User-replaceable hot-swappable internal batteries.
n
Advanced early warning of UPS status via automatic and manual battery test feature.
Frequently Asked Questions Question
Resolution
Why should I consider using online, double-conversion UPS technology?
While line interactive UPS technology is appropriate for many situations, there may be times when you need greater power capacity or higher levels of availability offered by online double-conversion technology. With zero transfer time when switching to battery, online technology’s clean power (through 100% power conditioning) causes less stress on power supplies, creating the highest level of equipment protection. Over time, the online, double-conversion Liebert GXT also offers an attractive total cost of ownership. Because an online system corrects for frequency variations without switching to battery, it can greatly extend the lifetime of the UPS battery.
Is the Liebert GXT compatible with a backup generator?
Generators do not provide computer grade AC power required by today’s sensitive electronics. A true online UPS such as the Liebert GXT will work with a generator and provide tight voltage and frequency regulation. The UPS will bridge the gap between loss of AC power and the time it takes your generator to come up to speed and your loads to be switched to generator power — can your business-critical applications be without power for even a few minutes?
How fast can I get a Liebert GXT shipped to my customer?
Liebert maintains a warehouse of products for quick distribution. Ingram Micro and Tech Data also stock many standard Liebert UPS products for next day shipment.
38
Competitive Comparison The Liebert GXT offers a number of advantages over the competition, which you can use to generate new high-margin sales. Feature
Liebert GXT
APC SmartUPS-RT
Powerware 9125
Tripplite Smart Online
Capacity range down to 500VA.
Yes
No
No
No
Widest input frequency window (40-70Hz).
Yes
No
No
No
Delivered fully assembled — batteries connected and activated at the factory.
Yes
No
No
Yes
Standard rack ears and tower pedestal.
Yes
No
No
Yes
Two-year, no hassle replacement warranty.
Yes
No
No
No
Liebert GXT Product Ancillary Guide Liebert GXT UPS
GXT2-500RT120
GXT2-700RT120
GXT2-1000RT120
GXT2-1500RT120
GXT2-2000RT120
VA/Watts
500/350W
700/490W
1000/700W
1500/1050W
2000/1400W
UPS Battery Kit
internal
internal
internal
internal
internal
External Battery Cabinet
GXT2-48VBATT
GXT2-48VBATT
GXT2-48VBATT
GXT2-48VBATT
GXT2-48VBATT
4-Post Rack Mounting Kit
RMKIT18-32
RMKIT18-32
RMKIT18-32
RMKIT18-32
RMKIT18-32
Web/SNMP Card
IS-WEBCARD
IS-WEBCARD
IS-WEBCARD
IS-WEBCARD
IS-WEBCARD
MicroPOD
MP2-115A
MP2-115A
MP2-115A
MP2-115A
MP2-120C
Liebert GXT UPS
GXT2-3000RT120
GXT2-2700RT208
GXT2-6000RTL630
GXT2-6000RT208
VA/Watts
3000/2100W
2700/890W
6000/4200W
6000/4200W
10000/8000W
UPS Battery
internal
internal
GXT2-240BATKIT [1] √
GXT2-144BATKIT [1] √
GXT2-288RTBKIT [2] √
External Battery Cabinet
GXT2-72VBATT
GXT2-72VBATT
GXT2-240VBATTUL
GXT2-144VBATT
GXT2-288RTVBATT
4-Post Rack Mounting Kit
RMKIT18-32
RMKIT18-32
RMKIT18-32
RMKIT18-32
RMKIT18-32
Web/SNMP Card
IS-WEBCARD
IS-WEBCARD
IS-WEBCARD
IS-WEBCARD
IS-WEBCARD
MicroPOD
MP2-130C
MP2-220N
PD-L630 √
PD-002
PD-101
GXT2-10000RT208
√ Required UPS Components
39
Liebert GXT UPS
Specifications Model Number
GXT2-500RT120
GXT2-700RT120
GXT2-1000RT120
Model Rating VA/W
500VA/350W
700VA/ 490W
1000VA / 700W
1500VA / 1050W
Dimensions: in (mm)
3.5 x 21.5 x 17 in.
3.5 x 21.5 x 17 in.
3.5 x 21.5 x 17 in.
3.5 x 21.5 x 17 in.
(89 x 546 x 432 mm)
(89 x 546 x 432 mm)
(89 x 546 x 432 mm)
(89 x 546 x 432 mm)
49 lbs. (22 kg)
49 lbs. (22 kg)
50 lbs. (23 kg)
51 lbs. (23 kg)
WxDxH Weight: lbs. (kg)
GXT2-1500RT120
Input AC Parameters Voltage Range
120 VAC nominal, (60 to 140VAC Variable based upon output load)
Frequency
40 - 70 Hz; Auto Sensing
Input Power Cord
6 ft. attached, w/ NEMA
6 ft. attached, w/ NEMA
10 ft. attached, w/ NEMA
10 ft. attached, w/ NEMA
5-15 plug
5-15 plug
5-15 plug
5-15 plug
(6) NEMA 5-15R
(6) NEMA 5-15R
(6) NEMA 5-15R
(6) NEMA 5-15R
Output AC Parameters Output Receptacles
Voltage
100/110/115/120/127 (user configurable) VAC; ±3%
Frequency
50 Hz or 60 Hz
Waveform
Sinewave
Typical Battery Backup Time Full Load
28 minutes
17 minutes
11 minutes
7 minutes
Half Load
66 minutes
44 minutes
25 minutes
20 minutes
Recharge Time
5 Hours to 95% capacity after full discharge into 100% load
Agency Safety
UL 1778; c-UL Listed
RFI/EMI
FCC Part 15, Subpart B, Class A
Surge Immunity
IEEE 587 Category A & B
Transportation
ISTA Procedure 1A
Model Number
GXT2-2000RT120
GXT2-2700RT208
Model Rating VA/W
2000VA / 1400W
2700VA/1890W
3000VA / 2100W
Dimensions: in (mm)
3.5 x 21.5 x 17 in.
3.5 x 24.2 x 17 in.
3.5 x 24.2 x 17 in.
(89 x 546 x 432 mm)
(89 x 615 x 432 mm)
(89 x 615 x 432 mm)
54 lbs. (24kg)
75.2 (34.1)
69 lbs. (31kg)
WxDxH Weight: lbs. (kg)
GXT2-3000RT120
Input AC Parameters Voltage Range
120 VAC nominal,
208 VAC nominal,
120 VAC nominal,
(60 to 140VAC Variable based upon output load)
(119 to 280VAC Variable based upon output load)
(60 to 140VAC Variable based upon output load)
Frequency
40 - 70 Hz; Auto Sensing
40 - 70 Hz; Auto Sensing
40 - 70 Hz; Auto Sensing
Input Power Cord
10 ft. attached, w/ NEMA
10 ft. attached w/ NEMA L6-20 plug
10 ft. attached, w/ NEMA
5-20 plug
5-15 plug
L5-30 plug
(6) 5-20 T-Slot
(2) NEMA L6-15R
(6) NEMA 5-15R
receptacles
(1) NEMA L6-20R
(1) NEMA L5-30R on 12” cord
Output AC Parameters Output Receptacles
100/110/115/120/127 (user configurable) VAC; ±3%
200/208/220/230/240 (user configurable) VAC; ±3%
100/110/115/120/127 (user configurable) VAC; ±3%
Frequency
50 Hz or 60 Hz
50 Hz or 60 Hz
50 Hz or 60 Hz
Waveform
Sinewave
Sinewave
Sinewave
Voltage
Typical Battery Backup Time Full Load
6 minutes
5 minutes
5 minutes
Half Load
14 minutes
16 minutes
16 minutes
Recharge Time
5 Hours to 95% capacity after full discharge into 100% load
Agency Safety
UL 1778; c-UL Listed
RFI/EMI
FCC Part 15, Subpart B, Class A
Surge Immunity
IEEE 587 Category A & B
Transportation
ISTA Procedure 1A
40
Specifications Model Number Model Rating DIMENSIONS Unit W x D x H in. (mm) WEIGHT lbs (kg) Unit
GXT2-6000RT208
GXT2-10000RT208
4200W/5200VA at 120/208 (120 or 240 degrees)
8000W/8660VA at 120/208 (120 or 240 degrees)
4200W/6000VA at 120/240 (180 degrees)
8000W/10000VA at 120/240 (180 degrees)
6.9 x 24.2 x 16.9 (176 x 615 x 430)
10.5 x 26.0 x 16.9 (267 x 660 x 430)
67 (30.3)
109 (49.3)
Input AC Parameters Nominal Operating Frequency
50 or 60 Hz (Factory Default = 60)
Factory Default VAC
120/208 VAC at 120 degrees
L1-L2 Factory Default Input Phase Angle Allowable Input Phase Angle
120 degrees 120, 180, 240 degrees, Auto-sensing on application of AC (Restrictions for L-N voltages other than 120 VAC)
Factory Default L1-N, L2-N VAC
120 VAC nominal
Input Frequency w/o Battery Operation
40 - 70 Hz
Output AC Parameters Factory Default VAC
120/208 VAC @ 120 degrees
L1-L2 Factory Default Output Phase Angle Allowable Output Phase Angle
120 degrees 120, 180, 240 degrees Auto-sensing on initial application of input AC
Factory Default L1-N, L2-N VAC
120 VAC nominal
User Configurable L1-N, L2-N VAC
100/110/115/120/127 VAC, ±3%
Frequency
50 Hz or 60 Hz, Nominal
Waveform Overload Rating
Sinewave 200% for 8 cycles; 130% for 10 seconds
200% for 8 cycles then shutdown; 130% for 60 seconds
with transfer to bypass
with transfer to bypass
Environmental Operating Temp
+32°F to +104°F (0°C to +40°C)
Storage Temp
+5°F to +122°F (-15°C to +50°C)
Relative Humidity Operating Elevation
0% to 95%, non-condensing Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
Storage Elevation Audible Noise
50,000 ft. (15,000 m) maximum <55 dBA, at 1 meter from the rear; <50 dBA, at 1 meter from the front or sides
Agency Safety
UL 1778, c-UL Listed (Suitable for computer room applications)
RFI/EMI
FCC Part 15, Subpart B, Class A
Surge Immunity
IEEE/ANSI C62.41 Category A & B
Transportation
ISTA Procedure 1A
Internal Battery Model Number
GXT2-144BATKIT (one required)
GXT2-288RTBKIT (two required)
WEIGHT lbs (kg)
79 (35.8) (one required)
78.1 (35.5) (two required)
Type Quantity x V x Rating
Valve-regulated, non-spillable, flame retardant, lead acid 12 x 12V x 9.0 AH (one required)
Battery Mfg / Part # Recharge Time
12 x 12V x 9.0 AH (two required) Yuasa / REW 45-12 FR
6 Hours to 90% capacity after full discharge into 100% load
Optional Extended Battery Cabinet Model Number DIMENSIONS W x D x H in.(mm) WEIGHT lbs (kg) Unit
GXT2-144VBATT
GXT2-288RTVBATT (requires two GXT2-288RTBKIT)
3.5 x 24.2 x 16.9 (87 x 618 x 430)
7.0 x 26.0 x 16.9 (178 x 660 x 430)
93.6 (42.5)
41.6 (18.9) (two required)
BATTERY PARAMETERS Type Qty x V x Rating Battery Mfg / Part #
Valve-regulated, non-spillable, flame retardant, lead acid 12 x 12V x 9.0 AH per kit
12 x 12V x 9.0 AH per kit (two required) Yuasa / REW 45-12 FR
ENVIRONMENTAL Operating Temp
+32°F to +104°F (0°C to +40°C)
Storage Temp
+5°F to +122°F (-15°C to +50°C)
Relative Humidity Operating Elevation Storage Elevation
0% to 95%, non-condensing Up to 10,000 ft. (3000m) at 104°F (40°C) without derating 50,000 ft. (15,000m) maximum
AGENCY Safety
UL 1778, c-UL Listed (Suitable for computer room applications)
RFI/EMI
FCC Part 15, Subpart B, Class A
Transportation
ISTA Procedure 1A
Note: Part Numbers GXT2-6000RT208 and GXT2-10000RT208 do not include internal battery kits. When calculating total unit weight, add weight of internal batteries.
41
Liebert GXT UPS
Specifications POWER DISTRIBUTION GXT 2-6000RT208 Model Number PD-HDWR PD-HDWR-MBS PD-001
Amp Rating 30 No Bypass 30 With Bypass 30 With Bypass
Input Power Connection Hardwire Terminals Hardwire Terminals L14-30P
PD-002 PD-003
30 With Bypass 30 With Bypass
L14-30P L14-30P
PD-004 PD-005
30 With Bypass 30 With Bypass
L14-30P L14-30P
PD-006 PD-007 GXT 2-6000RTL630 Model Number PD-L630 GXT 2-10000RT208 Model Number PD-101 PD-102 PD-103 PD-104 PD-105
30 With Bypass 30 With Bypass
L14-30P L14-30P
Output Power Connection Hardwire Terminals Hardwire Terminals (1) L6-30R,(1) L14-30R, (4) 5-15/20R T-slot (2) L6-20R, (2) 5-15/20R T-slot (2) L6-30R, (4) 5-15/20R T-slot (4) EN60320 / C19 (4) L5-20R, (2) L5-30R (4) L5-20R, (2) L6-30R (4) L6-20R
Amp Rating 30
Input Power Connection L6-30P
Output Power Connection (2) L6-30R, (2) L6-20R
Amp Rating 50 50 50 50 50
Input Power Connection Hard Wired Hard Wired Hard Wired Hard Wired Hard Wired
Output Power Connection (8) 5-15/20R T-slot, (2) L6-30R (4) 5-15/20R T-slot, (4) L6-20R (4) 5-15/20R T-slot, (4) L6-30R (4) 5-20R T-slot, (2) L6-30R, (2) L6-20R (4) 5-20R T-slot, (2) L6-30R, (2) L5-20R
BATTERY CABINETS UPS Model GXT2-500RT120 GXT2-700RT120 GXT2-1000RT120 GXT2-1500RT120 GXT2-2000RT120 GXT2-3000RT120 GXT2-2700RT208 GXT2-6000RTL630 GXT2-6000RT208 GXT2-10000RT208
Total Runtime with Internal and Extended Battery Cabinets/Full Load Runtime with Internal Extended Battery Batteries @ Full Load Cabinet P/N 28 minutes GXT2-48VBATT 17 minutes GXT2-48VBATT 11 minutes GXT2-48VBATT 7 minutes GXT2-48VBATT 6 minutes GXT2-48VBATT 5 minutes GXT2-72VBATT 5 minutes GXT2-72VBATT 7 minutes GXT2-240VBATTUL 5 minutes GXT2-144VBATT GXT2-288VBATT 6 minutes
PARALLEL CAPABILITY GXT2-10000RT208 Model GXT2-PP20KRT208
Voltage 48 VDC 48 VDC 48 VDC 48 VDC 48 VDC 72 VDC 72 VDC 240 VDC 144 VDC 288 VDC
One Cabinet 115 min. 68 min. 44 min. 28 min. 18 min. 20 min. 20 min. 21 min. 14 min. 17 min.
Two Cabinets 231 min. 136 min. 88 min. 56 min. 42 min. 40 min. 40 min. 38 min. 25 min. 28 min.
Description Paralleling POD maximum (3) GXT2-10000RT208 connection for 20kVA capacity plus 10kVA redundancy (requires (1) paralleling cable p/n GXT2-20KPC-6 for connection to each GXT2-10000RT208) GXT2-20KPC-6 Paralleling cable, approximately 6 feet long SYSTEM CONFIGURATION Capacity / Redundancy GXT2-10000RT208 GXT2-288RTBKIT GXT2-PP20KRT208 GXT2-20KPC-6 PD-201 10kVA / 10kVA 2* 4* 1* 2* 1 20kVA / 2* 4* 1* 2* 1 3* 6* 1* 3* 1 20kVA / 10kVA * Required Paralleling Components
42
Liebert GXT Related Products
Rack-Mounting Kits These kits are required to mount a Liebert GXT and external battery cabinets within equipment racks.
Liebert MicroPOD™ A maintenance bypass switch that permits scheduled maintenance or UPS replacement without discontinuing power to critical equipment.
Liebert Nform A simple to use monitoring and communications softwaresolution that combines network monitoring of power and cooling equipment.
Liebert MultiLink Shutdown Software Monitors battery status and warns users of impending power loss and automatically shuts down systems in a safe and orderly manner.
Extended Warranties One-year and three-year warranty extensions are available at the time of the UPS sale to cost-effectively extend the life of the UPS.
5-Year Power Assurance Package For UPSs 1000VA and larger, 5-year warranty, onsite service, and equipment disposal. For UPSs 6kVA and larger, also includes startup and preventive maintenance.
Liebert IntelliSlot Web Card The Liebert IntelliSlot Web Card delivers SNMP and web management communications capability to a Liebert GXT unit.
TM
43