LIEBERT® PSI-XR High Performance Rack-Mount UPS for Network Power Protection
OVERVIEW Liebert PSI-XR allows you to get more from your UPS and your protected equipment, with features normally found only on more expensive systems: yy Greater than five minutes of internal battery backup time at full load provides ample time for an orderly shutdown of connected equipment. yy Optional matching external battery cabinets offer more backup time - add up to 6 additional cabinets to extend battery runtime to meet equipment needs. yy Liebert PSI-XR operates at a higher output power factor - meaning less power consumption. This results in your network running at lower power levels and lower heat levels, and ultimately provides a longer network service life.
Liebert® PSI-XR is a compact, line-interactive UPS system designed especially for IT applications such as network closets and small data centers. It provides reliable power protection for servers, critical nodes, network workstations, large network peripherals, network routers, bridges, hubs and other electronic equipment. Matching battery cabinets are available to extend the on-battery operating time. Ideally suited for: yyPCs yyNetwork workstations yyServers yyNetwork closets yyLarge network peripherals yyVoIP
yy Remote communications and shutdown options provide remote monitoring and power management - serial and contact closure, USB, SNMP
1
LIEBERT® PSI-XR
Reliable UPS Protection And Extended Battery Time To Keep Your Network Up And Running
Liebert PSI-XR Features
The flexible design of Liebert® PSI-XR allows the unit to be configured as a self-standing tower or to be rack-mounted within a 2U space. It is available in four capacities, and both 120V or 230V models.
Flexibility
The UPS features an innovative line-interactive design incorporating buck/boost automatic voltage regulation technology. This protects against utility voltage fluctuation by raising and lowering utility power to the level needed by the connected equipment. It also allows the UPS to prolong battery life by maximizing its time on utility power before going to battery.
Battery Runtime Chart (Runtimes are in minutes, assuming fully charged batteries at 25°C) NUMBER OF BATTERIES
LOAD %
1000VA
1500VA
2200VA
3000VA
Internal Battery
50
15
13
14
13
100
6
5
5
5
Internal Battery +1 External Battery Cabinet
50
73
55
45
31
100
31
18
15
12
Internal Battery +2 External Battery Cabinet
50
129
95
67
56
100
65
46
29
18
Internal Battery +3 External Battery Cabinet
50
181
131
95
73
100
96
64
48
31
Internal Battery +4 External Battery Cabinet
50
233
167
143
95
100
124
82
72
47
Internal Battery +5 External Battery Cabinet
50
285
203
167
113
100
151
106
84
56
Internal Battery +6 External Battery Cabinet
50
336
239
191
131
100
179
124
102
65
Rack Rail Kit These telescoping rails mount to the sides of the UPS to facilitate installation into a rackmount enclosure.
Output Circuit Breakers
Receptacles
Higher Availability:
UPS with internal battery
Data line surge protection Network surge protection for equipment connected to the UPS via the RJ-45.
Optional external battery cabinets
Advance early warning of UPS system status The Liebert PSI-XR offers multiple audible and visual alarms to immediately alert you to an input voltage fluctuation (buck/ boost), output overload, low battery or replace battery condition.
Add up to 6 cabinets for additional runtime
2
Input Circuit Breakers
Configurable input voltage window Allows the UPS to be properly matched to the incoming utility power and adjusts its input window and transfer points to supply precisely regulated power to connected loads within the selected range. Also enables the UPS to meet the required input voltage when transferring to battery.
Automatic Frequency Sensing The UPS automatically adjusts to the input frequency, 50Hz or 60Hz.
Provide extended runtime for applications that require longer backup time. Liebert Intellislot® Port
Six to seven battery-backed outlets Allows the Liebert PSI-XR to be more flexible in accommodating additional equipment to be connected to the UPS via the 15, 20 or 30 Amp receptacles.
Rotatable Display Panel 90 degrees rotatable LED display panel rotates 90° to make the readout of the LED display easy to see in rack or tower position.
Optional external battery cabinets RS232 (DB-9) Port
Standard
Voltage Configuration DIP Switch
EPO USB Port
RJ-45 Data Line Connectors
External Battery Connector
Power Cord
Greater than five minutes of battery backup time at full load when utility fails Provides ample time for an orderly shutdown of connected equipment. Optional matching external battery cabinets offer more backup time. Full sequenced battery testing The Liebert PSI-XR provides a manual self-diagnostic test feature. This provides a comprehensive analysis of the condition of the batteries within the UPS and will notify you when the internal batteries need to be replaced. The battery test feature can also be programmed for automatic operation using Liebert shutdown software. Lightning and surge protection The transient voltage surge suppression (TVSS) circuitry inside the Liebert PSI-XR provides protection for the connected equipment from incoming spikes, surges, and other power anomalies present on the incoming utility power source. Remote emergency power off Allows the UPS to be remotely shut down during an emergency. User replaceable hot swappable batteries Increase product life and provide prolonged UPS reliability. Batteries are conveniently located behind the front bezel of the unit.
Lowest Total Cost Of Ownership:
Reduced installation time and costs UPS is shipped with batteries connected and charged. Warranty Protection Standard two-year warranty ensures UPS replacement if problems occur during the warranty period. Optional one-year and three-year extensions also available.
Multiple Choices For Communication, Shutdown And Reporting: Serial and Contact Closure Communication Option Automated shutdown software allows you to monitor communication between the UPS and a server. It also ensures a graceful unattended shutdown in the event of an extended power failure. USB Communications Windows (98 and later) built-in power management functions provide monitoring of UPS status and manage the automatic orderly shutdown of the computer if a power outage ever exceeds the battery capacity of the UPS. Liebert USB shutdown and monitoring software is provided. SNMP Communication Option Liebert IntelliSlot® Web Card provides SNMP and web-based management to your Liebert PSI-XR. Provides SNMP MIB to monitor and control your UPS from your network management station or any PC running Microsoft Internet Explorer.
0.9 Output Power Factor Liebert PSI operates at a higher output power factor - meaning less power consumption. This results in your network running at lower power levels and lower heat levels, and ultimately provides a longer network service life.
yyNetwork shutdown
Wider input voltage window Prolongs battery life by allowing the UPS to maximize the use of utility power before transferring to battery when input voltage exceeds specified limits.
yyCompatible with shutdown software to ensure graceful computer shutdown
yySends both SNMP traps and emails for event notification, and automatically emails a daily UPS history. yyAuto-senses 10M/100M Ethernet
Optional Liebert IntelliSlot Web Card provides SNMP and web-based management
Liebert PSI-XRW Network Solution Package With Built-In Communications Liebert PSI-XRW is the standard Liebert PSI-XR made network–ready with a factory-installed Liebert IntelliSlot Web Card for SNMP communications. This totally integrated, cost-efficient solution allows remote monitoring, start-up or restart for connected equipment.
Optional Liebert MicroPOD Output Distribution And Maintenance Bypass Module
When your computer system can’t be without power, even for scheduled UPS maintenance, the Liebert MicroPOD Maintenance Bypass and Output Distribution Unit ensures continuous uptime. It allows you to manually transfer connected equipment to utility power via a maintenance bypass switch, permitting scheduled service or UPS replacement without the need to shut down connected equipment. Features include: yy 2U height minimizes rack space requirements yy Installs with plug-and-play ease yy Two-year, no-hassle replacement warranty
3
LIEBERT® PSI-XR
Liebert® PSI-XR Specifications Model Number
PS1000RT3-120XR
PS1500RT3-120XR
PS2200RT3-120XR
PS3000RT3-120XR
AGENCY
Network Solutions Package Number
PS1000RT3-120XRW
PS1500RT3-120XRW
PS2200RT3-120XRW
PS3000RT3-120XRW
Safety
UL 1778, c-UL Listed FCC Part 15, Class A
Power Rating, VA/W
1000VW/900W
Emissions
1500VW/1350W
1920VW/1920W
3000VW/2700W
DIMENSIONS, W X D X H IN (MM) Unit
17.3 x 19.3 x 3.5 (440 x 490.5 x 88)
17.3 x 19.3 x 3.5 (440 x 490.5 x 88)
17.3 x 27.6 x 3.5 (440 x 700.5 x 88)
17.3 x 27.6 x 3.5 (440 x 700.5 x 88)
Shipping
22 x 24.1 x 9 (560 x 612 x 228)
22 x 24.1 x 9 (560 x 612 x 228)
22 x 34.8 x 9 (560 x 884 x 228)
22 x 34.8 x 9 (560 x 884 x 228)
Unit
56 (25)
62 (28)
92 (42)
105 (48)
Shipping
64 (29)
70 (32)
101 (46)
115 (52)
WEIGHT, LB (KG)
INPUT AC PARAMETERS Surge Protection
570J
Voltage Range Without Battery Operation
83 to 159 VAC (configurable)
Frequency Range
45~65Hz, (0.5Hz)
Input Power Cord, 10ft (3m) attached
NEMA 5-15P plug
NEMA 5-15P plug
NEMA 5-20P plug
NEMA L5-30P plug
Output Receptacles
(6) NEMA 5-15R
(6) NEMA 5-15R
(4) NEMA 5-15R (2) NEMA 5-20R T-Slot, accepts 15A plug
(4) NEMA 5-15R (2) NEMA 5-20R T-Slot, accepts 15A plug (1) NEMA L5-30R
Network Surge
UL 497 B
Transportation
ISTA Procedure 1A Certification
RAIL KIT (INCLUDED) Rail Kit
RAILKITPS3G-AEC
NEC limits the input current rating of the 2200VA model to 80% of the input plug's rating. If 1920 or more is required, contact a certified electrician to change the input plug to 30A plug. Vertiv™ assumes no liability for damage caused by miswiring or misapplication of the input plug.
Battery cabinet specifications Model Number
PSRT3-24VBXR
PSRT348VBXR
Used w/UPS Model
PS1000RT3120XR, PS1500RT3120XR
PS2200RT3120XR, PS3000RT3120XR
DIMENSIONS, W X D X H, IN (MM)
Voltage (Normal Mode)
110/120/127 VAC (configurable)
Voltage (Battery Mode)
110/120/127 VAC; 5% before low-battery warning
Transfer Time Battery Waveform
Shipping
17.3 x 19.3 x 3.5 (440 x 490.5 x 88) 22 x 26.6 x 9 (560 x 675 x 228)
WEIGHT, LB (KG) Unit
64 (29)
Shipping
73 (33)
BATTERIES 4-6 ms typical
Type
Sinewave Manufacturer
BATTERY PARAMETERS Type
Unit
Valve-regulated, non-spillable, lead acid
Valve-regulated, nonspillable, lead acid CSB, YUASA or Equivalent
ENVIRONMENTAL
5 hours to 90% of rated capacity, after full discharge into resistive load
Operating Temperature, ˚F (˚C)
32 to 104 (0 to 40)
Full Load
5 minutes > 10 minutes. 13-14 minutes typical
Storage Temperature, ˚F (˚C)
5 to 104 (-15 to 40)
Half Load
Recharge Time BATTERY BACKUP TIME
ENVIRONMENTAL 32 to 104 (0 to 40)
Relative Humidity
0% to 90%, non-condensing
Operating Temperature, °F (°C)
10,000 ft. (3000m) at 95˚F (35˚C) without derating
Storage Temperature, °F (°C)
5 to 104 (-15 to 40)
Maximum Operating Altitude
Relative Humidity
AGENCY 0% to 90%, non-condensing
Safety
UL 1778, c-UL Listed FCC Part 15, Class A ISTA Procedure 1A Certification
Operating Altitude
Up to 3000m (10,000ft) at 35°C (95°F) without derating
Emissions
Audible Noise
<40 dBA, internal fan(s) Off, <45 dBA, internal fan(s) On
Transportation
VertivCo.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA © 2016 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.