Transcript
SKUKUZA SAFARI LODGE - ELECTRICAL INSTALLATION SECTION E1: LIGHT FITTINGS SCHEDULE OF LIGHT FITTINGS NOTE 1 2 3 4 5 6 7 Fitting L01-A
All control gear and drivers shall be power factor corrected to better than 0.9 All fittings, control gear and drivers shall have verifiable SABS or equivalent IEC certification. All light fittings shall have their own, unique, certified photometrics available in hard copy and electronic eulum data files. Each fitting shall an energy rating certificate. The lamp life, lamp guarantee and control gear guarantee shall be submitted for each fitting at tender stage. Fittings shall be priced and supplied complete with all lamps, control gear, accessories and mounting/fixing accessories. Lighting Innovations contact details: Craig Lane - 083 254 2733 /
[email protected], Greg Bower - 082 902 0383 /
[email protected] Description
Lamps No Large diameter down lighter with opal 1 lens
W 12
Type LED
Colour Temp warm white
CRI >=80
Small diameter down lighter with opal lens
1
8
LED
warm white
>=80
1
20
LED
warm white
>=80
L03
Vanity fitting for toilet/bathroom mirrors. Decorative 'star light'
1
1
14
1.2
T5 FLR
warm white
>=90
L04 L05
Bedside lamp Splash proof down lighter
1 1
14 14
L01-B L01-C L02 L03-driver
L06 L06-driver L07-A L07-B L07-C L08 L09 L10
L11-A
Large diameter down lighter with opal lens
Driver for star light - 4 lights per driver.
1m LED strip light Driver for LED strip - 3 lengths per driver Eyelid fitting with 100% downward light. Up/down lighter Eyelid fitting with 100% downward light.
LED
warm white
>=80
CFL CFL
warm white warm white
>=80 >=80
Accessories
Supplier
Staggered wiring for 50/100% switching | LCS | occupancy sensor | local light switch
Suspended ceiling, skimmed ceiling
3m cordset, 5A plug top
LEDWISE LEDWISE
Next to/above mirror.
Recessed into bulkhead 3m cordset, 5A plug top above each hand wash basin. Recessed into bulkhead 3m cordset, 5A plug top above each hand wash basin. Surface Mounting brackets
Staggered wiring for 50/100% switching | LCS | occupancy sensor | local light switch
Skimmed bulkhead
Light switch
Skimmed bulkhead
Recessed
-
Light switch Occupancy sensor
Above bedside table Skimmed ceiling
Surface Recessed
3m cordset, 5A plug top Remote drivers
LEDS-C4 LIGHTING INNOVATIONS LEDWISE
BRISTOL AQUALUCE
Light switch
Against wall.
Surface
-
REGENT
Surface
tbc
TBC
LCS | dimmable
Against exposed timber roof structure under thatch Against exposed timber roof structure under thatch Against exposed timber roof structure under thatch Concrete/brick columns
SERENGETI SINGLE SERENGETI SERENGETI MINI SINGLE
Surface
tbc
TBC
On permanently | LCS | occupancy sensor | dimmable
Occupancy sensor | local light switch -
Light switch -
3.2
LED
1
4
LED
warm white
>=80
Large, decorative pendant/chandelier
tbc
tbc
tbc
tbc
-
LCS
Large, decorative pendant/chandelier
tbc
tbc
tbc
tbc
-
LCS
Large, decorative pendant/chandelier Large, square brick light
tbc 1
8 4
tbc
LED LED
tbc
warm white warm white
tbc
>=80
Mounting
1
1 1
warm white
Control
>=80 >=80
-
22
LED
warm white
>=80
Occupancy sensor | LCS Occupancy sensor | LCS
LCS
Skimmed bulkhead
Bar counters
Against wall. Against wall.
L11-B
Small, square brick light
1
14
LED
warm white
>=80
LCS | dimmable
Concrete/brick columns
L12-A
Spot light, one direction
1
35
CMH
warm white
>=90
LCS | dimmable
L12-B
Spot light up/down lighter
2
70
CMH
warm white
>=90
LCS | dimmable
Against exposed timber roof structure under thatch
L13
Small, square brick light with opal lens
1
4
LED
warm white
>=80
On permanently
Brick/concrete wall.
L14
Submersible pool light
1
20
LED
cool white
n/a
Astronomical timer
Pool
SiVEST Electrical Division
Against exposed timber roof structure under thatch
Recessed
Recessed
Surface Surface
Surface Recessed on each column, pointing inwards. Recessed on each OUTSIDE column (pointing towards game drive vehicles). Surface mounted at top of each column, lighting thatch roof. Surface mounted on each column at the top of the column to light floor and thatch. Recessed mid point of stair riser or following incline of ramp. Submerged
-
tbc Wall box
LEDWISE OSRAM
LEDWISE
REGENT REGENT
CL12DISH160
CL6H-DIFF CL19DISH200
LINESTRA
CL1STARLIGHT
LL-A-24-25-
TBC LIGHTING INNOVATIONS
SOCCER CITY BL
Bracket for mounting on timber structure
LIGHTING INNOVATIONS
MINI CONOS DUO
Wall box
REGENT
TULA II
Remote drivers
LIGHTING INNOVATIONS
Wall box
Bracket for mounting on timber structure
LIGHTING INNOVATIONS
LIGHTING INNOVATIONS
SOCCER CITY MINI
GALILEO UP/DOWN
Page E1-SCH-1 of 3
SECTION E1: LIGHT FITTINGS SCHEDULE OF LIGHT FITTINGS NOTE 1 2 3 4 5 6 7
All control gear and drivers shall be power factor corrected to better than 0.9 All fittings, control gear and drivers shall have verifiable SABS or equivalent IEC certification. All light fittings shall have their own, unique, certified photometrics available in hard copy and electronic eulum data files. Each fitting shall an energy rating certificate. The lamp life, lamp guarantee and control gear guarantee shall be submitted for each fitting at tender stage. Fittings shall be priced and supplied complete with all lamps, control gear, accessories and mounting/fixing accessories. Lighting Innovations contact details: Craig Lane - 083 254 2733 /
[email protected], Greg Bower - 082 902 0383 /
[email protected]
Fitting
Description
L15
Flood light with opal lens
L16-A
Lamps No 1
W 32
Type LED
Colour Temp warm white
CRI >=90
Control
Mounting
Pathway light
1
3.6
LED
LED
warm white
LCS
Gardens
warm white
>=80
>=80
LCS
Ground mounted
Ground mounted accent lighting for selected trees. Recessed into pathway. Gound mounting box Recessed
Gound mounting box
L17-A
900mm aluminium bollard
1
14 35
LED
COB
warm white warm white
>=80
>=80
LCS
Ground mounted
Surface
-
L18-B
4 lamp adjustable down lighter with decorative box
4
35
COB
warm white
>=80
Light switch
Suspended from exposed timber roof structure
MULTIGIMBALO
2 lamp adjustable down lighter
2
35
COB
warm white
>=80
Light switch
L18-D
1 lamp adjustable down lighter
1
35
COB
warm white
>=80
Light switch
Recessed into skimmed or suspended ceiling
Suspended from timber COB 35 lamp, decorative LIGHTING structure, above waiter box, suspension accessories INNOVATIONS stations.
L18-C
Recessed
L19-A L19-B L20
NOT USED NOT USED 1200x600mm fluorescent with LBR difusser 1 lamp dust proof (IP66) linear fluorescent. 2 lamp dust proof (IP66) linear fluorescent. 2 lamp IP65 surface fluorescent to 25⁰C
Recessed into skimmed or suspended ceiling
MULTIGIMBALO
2
28
T5 FLR
cool white
>=80
Occupancy sensor
Suspended ceiling
2
28
T5 FLR
cool white
>=80
Occupancy sensor
Concrete roof, skimmed ceiling, 1200x600mm tiles Refrigeration panels
L16-B
L18-A
L21-A L21-B L21-C
L22-A L22-B L23
L24-A L25 L26 L27 L28-A L28-B
Heavy-duty pathway light
2 lamp adjustable down lighter with decorative box
1200x600mm fluorescent with opal diffuser 600x600mm fluorescent with opal diffuser Fluorescent with decorative trim and LBR diffuser Bulkhead with red opal lens. Zone I fluorescent NOT USED Decorative type pendant Single post top fitting on 3.5m (mounting height) pole
Double post top fitting on 3.5m (mounting height) pole
SiVEST Electrical Division
1
2
1 2
6
28 36
T5 FLR T8 FLR
cool white cool white
>=80 >=80
LCS
Dimmable
Occupancy sensor Local light switch
Ground mounted
Suspended from exposed timber roof structure
Plastered wall
2
28
T5 FLR
cool white
>=80
LCS | occupancy sensor | light switch
1
28
T5 FLR
warm white warm white cool white
>=80
>=80 >=80
Bi-level ballasts with occupancy sensors
Suspended ceiling, 1200x600mm tiles Suspended ceiling, 600x600mm tiles Concrete roof, brick walls
3
14
T5 FLR LED T8 FLR
cool white
>=80
Occupancy sensor Light switch IP65 light switch
Concrete roof Concrete roof
Accessories
Supplier REGENT
SPUTNIK
LEDS-C4
REXEL
LEDS-C4
LIGHTING INNOVATIONS Suspended from timber COB 35 lamp, decorative LIGHTING structure, aimed at art box, suspension accessories INNOVATIONS or architectural feature.
Recessed
REXEL HEAVY DUTY FERRARA
MULTIGIMBALO
COB 35 lamp, decorative LIGHTING box, suspension accessories INNOVATIONS
MULTIGIMBALO
Recessed
3m cordset, 5A plug top
Surface
3m cordset, 5A plug top
COMMODO RE DAMPA
Surface
COB 35 lamp, decorative LIGHTING box, suspension accessories INNOVATIONS
3m cordset, 5A plug top
Surface with 20mm Mounting brackets conduit from top, sealed with marine silicone. Recessed Recessed Surface Surface Surface
1 2
14 36
1 1
23 54
T5 FLR LED
warm white cool white
>=80 >=80
Light switch LCS
Suspended ceiling, skimmed Ground mounted
Surface Surface
1
108
LED
cool white
>=80
LCS
Ground mounted
Surface
LIGHTING INNOVATIONS LIGHTING INNOVATIONS LIGHTING INNOVATIONS LIGHTING INNOVATIONS
3m cordset, 5A plug top
DAMPA
DAMPA LT
LIGHTING INNOVATIONS 3m cordset, 5A plug top LIGHTING INNOVATIONS 3m cordset, 5A plug top LIGHTING INNOVATIONS GEWISS Mounting brackets and two LIGHTING Zone I glands INNOVATIONS
LOGUS ML
Galvanised steel pole, access LIGHTING door, gland plate, mcbs. INNOVATIONS
PIAZZA
tbc LEDS-C4 Galvanised steel pole, access LIGHTING door, gland plate, mcbs. INNOVATIONS
LOGUS ML REMO
SAFE LIGHT ORLANDO NEO PIAZZA
Page E1-SCH-2 of 3
SECTION E1: LIGHT FITTINGS SCHEDULE OF LIGHT FITTINGS NOTE 1 2 3 4 5 6 7
All control gear and drivers shall be power factor corrected to better than 0.9 All fittings, control gear and drivers shall have verifiable SABS or equivalent IEC certification. All light fittings shall have their own, unique, certified photometrics available in hard copy and electronic eulum data files. Each fitting shall an energy rating certificate. The lamp life, lamp guarantee and control gear guarantee shall be submitted for each fitting at tender stage. Fittings shall be priced and supplied complete with all lamps, control gear, accessories and mounting/fixing accessories. Lighting Innovations contact details: Craig Lane - 083 254 2733 /
[email protected], Greg Bower - 082 902 0383 /
[email protected]
Fitting
Description
L29-A
Recessed emergency escape route fittings
L29-B L29-C
Surface emergency escape route fittings Emergency exit sign
SiVEST Electrical Division
Lamps No 1
W 3
Type LED
Colour Temp cool white
CRI >=80
Control
Mounting
1
3
LED
cool white
1
10
LED
cool white
Accessories
Supplier
LCS
Wall, ceiling
Recessed
-
ETAP
>=80
LCS
Wall, ceiling
Surface
-
ETAP
>=80
LCS
Wall, ceiling
Surface
-
ETAP
K714/3P ESM-RF RECESSED K714/3P ESM-RF SURFACE K734/3P ESM-RF SURFACE
Page E1-SCH-3 of 3