Transcript
© Siemens AG 2008
LOGO!Power LOGO!Power 15 V
■ Overview
■ Application
■ Technical specifications Power supply, type
15 V/1.9 A
15 V/4 A
Order No.
6EP1 351-1SH02
6EP1 352-1SH02
Input Rated voltage Vin rated
Single-phase AC 100 - 240 V AC Wide-range input 85 ... 264 V AC
Single-phase AC 100 - 240 V AC Wide-range input 85 ... 264 V AC
Overvoltage strength
2.3 x Vin rated/1.3 ms
2.3 x Vin rated/1.3 ms
Mains buffering at Iout rated Rated line frequency, rated line-frequency range Rated current Iin rated Switch-on current limit (+25 °C)
> 40 ms at Vin = 187 V 50/60 Hz, 47 ... 63 Hz
> 40 ms at Vin = 187 V 50/60 Hz, 47 ... 63 Hz
0.63 ... 0.33 A < 15 A
1.24 ... 0.68 A < 30 A
I 2t Built-in line-side fuse Recommended miniature circuit breaker (IEC 898) in the mains power input
< 0.8 A2s Internal From 16 A, Characteristic B or from 10 A, Characteristic C
< 3 A2s Internal From 16 A, Characteristic B or from 10 A, Characteristic C
Output Rated voltage Vout rated Total tolerance, static • Static mains compensation • Static load smoothing
Controlled, isolated DC voltage 15 V DC ±3 % Approx. 0.1 % Approx. 1.5 %
Controlled, isolated DC voltage 15 V DC ±3 % Approx. 0.1 % Approx. 1.5 %
Residual ripple Spikes (bandwidth approx. 20 MHz) Adjustment range Status display Response on activation/deactivation
< 200 mVpp (typ. 10 mVpp) < 300 mVpp (typ. 30 mVpp) 10.5 ... 16.1 V Green LED for output voltage OK No overshoot of Vout (soft start)
< 200 mVpp (typ. 10 mVpp) < 300 mVpp (typ. 40 mVpp) 10,5 ... 16,1 V Green LED for output voltage OK No overshoot of Vout (soft start)
Startup delay/ voltage rise Rated current Iout rated Current range to +55 °C Parallel switching for enhanced performance
< 0.5 s/typ. 15 ms
< 0.5 s/typ. 10 ms
1.9 A 0 ... 1.9 A Yes
4A 0 ... 4 A Yes
Voltage range
12
The power supplies of the LOGO!Power range are primary switched-mode devices that are optimally matched to the LOGO! logic modules in their functionality and design. With the wide-range input 85 V to 264 V AC, radio interference level B and option for installing in built-in miniature distribution boards, they can be used universally in a diverse range of applications in the low-end performance range.
Continued on page 12/7.
12/6
Siemens KT 10.1 · 2008
© Siemens AG 2008
LOGO!Power LOGO!Power 15 V Power supply, type
15 V/1.9 A
15 V/4 A
Order No.
6EP1 351-1SH02
6EP1 352-1SH02
Efficiency Efficiency at Vout rated, Iout rated Power losses at Vout rated, Iout rated
Approx. 80 % Approx. 7 W
Approx. 85 % Approx. 11 W
<0.2 % Vout
<0.2 % Vout
Typ. ± 2.8 %Vout
Typ. ± 3.3 %Vout
Typ. 20 ms Typ. 20 ms
Typ. 20 ms Typ. 20 ms
Typ. 2.7 A Constant current characteristic <4A
Typ. 5.0 A Constant current characteristic <8A
–
–
Yes, safety extra-low output voltage Vout to EN 60950 and EN 50178 Class II (without protective conductor) Yes; CB scheme
Yes, safety extra-low output voltage Vout to EN 60950 and EN 50178 Class II (without protective conductor) Yes; CB scheme
Yes cULus-listed (UL 508, CSA C22.2 No. 14), File E197259; cURus-recognized (UL 60950, CSA C22.2 No. 60950), File E151273
Yes cULus-listed (UL 508, CSA C22.2 No. 14), File E197259; cURus-recognized (UL 60950, CSA C22.2 No. 60950), File E151273
FM approval Marine approval Degree of protection (EN 60529)
Class I Div. 2, Group A, B, C, D T4 GL IP20
Class I Div. 2, Group A, B, C, D T4 GL IP20
EMC Emitted interference Supply-harmonics limitation Noise immunity
EN 55022 Class B Not applicable EN 61000-6-2
EN 55022 Class B Not applicable EN 61000-6-2
Closed-loop control Dyn. mains compensation (Vin rated ± 15 %) Dynamic load smoothing (Iout: 10/90/10 %) Load step settling time • 10 to 90 % • 90 to 10 % Protection and monitoring Current limit Short-circuit protection Sustained short-circuit current rms value Overload/short-circuit indicator Safety Primary/secondary electrical isolation Protection class German Technical Inspectorate approval CE mark UL/cUL (CSA) approval
Operating data Ambient temperature range
– 20 ... +55 °C with natural convection Transport/storage temperature range – 40 ... +70 °C Humidity class Climate class 3K3 to EN 60721, no condensation Mechanics Supply-input connections L1, N Connections • Output + • Output – Dimensions (W x H x D) in mm Weight, approx. Installation
– 20 ... +55 °C with natural convection – 40 ... +70 °C Climate class 3K3 to EN 60721, no condensation
One screw terminal each for 0.5 ... 2.5 mm2 single-core/finely stranded
One screw terminal each for 0.5 ... 2.5 mm2 single-core/finely stranded
2 screw terminals for 0.5 ... 2.5 mm2
2 screw terminals for 0.5 ... 2.5 mm2
54 x 90 x 55 0.17 kg Snaps onto DIN rail EN 60715 35x7.5/15
72 x 90 x 55 0.25 kg Snaps onto DIN rail EN 60715 35x7.5/15
12
Siemens KT 10.1 · 2008
12/7