LSE 2-300
2V300AH 2V1000AH
LSE Series SLA Battery Range Summary By combining the service life reliability of a flooded battery with the performance energy density of a valve-regulated battery, BSB created a true long service life VRLA battery - the LSE range. The range offers 20 years design life with very good cycling capabilities. This range is highly suited to telecom, UPS, renewable energy system, power station and similar applications.
Application · Control Equipment · Medical Equipment · Emergency Power System · Power Plant
· Cable Television · Communication Equipment · Security System · UPS
General Features · Extra long life service design. · Non-Spillable construction design. · ABS containers and covers(UL94 V0, optional). · Safety valve installation for explosion proof. · Higher safety & reliable construction. · Exceptional deep discharge recovery performance. · Low self discharge characteristic. · Flexible design for multiple installation positions.
7mm (0.28inch)
20mm (0.79inch)
M8mm (0.31inch)
Construction Positive ...... Negative ...... Container ...... ...... Cover Sealant ......
Safety valve Terminal Separator Electrolyte
Lead dioxide Lead ABS ABS Epoxy Resin
...... ...... ...... ......
Terminal Dimensions
184.5mm(7.26inch)
102mm(4.02inch)
372mm(14.6inch)
123mm(4.84inch)
360.5mm(14.2inch)
EPDR Copper AGM Sulfuric acid
Battery Model
LSE2-300
Designed Floating Life Capacity(20oC)
20 Years 10HR(30.0A,1.80V)
20HR(15.8A,1.80V) 316AH Length
Dimensions
123mm(4.84inch)
5HR(51.5A,1.75V)
300AH
257AH
188AH
Width
Height
Total Height
184.5mm(7.26inch)
Approx. Weight
360.5mm(14.2inch)
Internal Resistance Self Discharge
< 3% of capacity declined per month at (20oC)
Charge Voltage(20oC)
372mm(14.6inch)
19 Kg (41.9 lbs) Full charged at 20oC :0.00047 Ohm
Capacity Affected by Temp.(10HR)
1HR(188A,1.60V)
40oC
20oC
0oC
-15oC
109%
100%
85%
65%
Cycle use
Float use
o
2.35V-2.40V(-5mV/ C), max. Current: 75A
Page 1 of 2
2.25-2.29V(-3mV/ oC)
LSE 2-300
2V300AH 2V1000AH
Charge Voltage
Current
o
Constant Charge at 0.25CA-2.35V (20oC)
(CA) (V/Cell)
100 0.25
Charge Capacity
Charge Voltage
2.35 80
2.17 100%Discharge
0.20
60
2.00
50%Discharge
0.15
40
0.10 20
1.83
0.05
0
Discharge Characteristic (20 C)
Charge Characteristic
Charge Current
0
0
2
4
6
8
10
Discharge Voltage (V/Cell)
(%) 120
Charge
Charge Capacity
LSE Series SLA Battery
2.17 2.00 1.83 0.05CA 0.25CA 0.1CA
1.67 1.60
0.6CA
30
60
1.33 0
12
2
6
12
3
Min
Time(hour)
10 Hour
20
Self Discharge Characteristics
Relationship of OCV and state of charge 110 105
2.25
2.17
Capacity (%)
Battery Voltage (V/Cell)
1CA
2.08
2.00
100 95 90 85 80 75 70 65 60 55 50
1.92
40oC
45
1.83
0
10
20
30
40
50
60
70
80
90
100
40 0
1
2
o
20 C
o
30 C 3 4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20
Storage time:months
Remained Capacity(%)
Constant current discharge ratings-amperes at 20oC F .V /T im e
5 M IN
1 0 M IN
1 5 M IN
3 0 M IN
1HR
3HR
5HR
10 H R
20HR
1 .6 0V
1172
729
550
335
188
9 3.6
5 4 .9
3 2 .0
1 7 .5
1 .6 7V
1100
692
529
321
185
9 0.0
5 3 .8
3 1 .7
1 6 .9
1 .7 0V
1008
667
517
292
180
8 4.0
5 2 .6
3 1 .6
1 6 .6
1 .7 5V
988
646
500
277
171
8 1.2
5 1 .5
3 1 .1
1 6 .2
1 .8 0V
884
617
454
257
160
7 8.0
4 8 .4
3 0 .0
1 5 .8
1 .8 5V
780
588
408
236
149
7 5.2
4 5 .3
3 0 .3
1 5 .3
Constant power discharge ratings-watts at 20oC F .V /T im e
5 M IN
10 M IN
1 5M IN
3 0 M IN
1H R
3HR
5HR
1 0H R
20HR
1. 6 0 V 1. 6 7 V 1. 7 0 V
2056 1984 1868
1317 1283 1271
1004 992 983
604 592 554
339 337 330
166 161 154
9 1 .8 9 1 .4 9 0 .3
64 . 0 63 . 6 63 . 2
3 4 .9 3 3 .7 3 3 .3
1. 7 5 V 1. 8 0 V 1. 8 5 V
1800 1720 1560
1267 1248 1184
975 904 820
538 513 480
325 306 288
150 146 141
8 9 .5 8 6 .7 8 3 .9
62 . 4 61 . 6 60 . 8
3 2 .4 3 1 .6 3 0 .4
ISO9001
COPYRIGHT BSB POWER COMPANY LIMITED Page 2 of 2