Transcript
LSG2-300
2V300Ah
Gel SLA Battery Range Summary By combining the newly developed nano gel electrolyte with up-to-date AGM structures, BSB created the innovative LSG range of batteries. The range offers 20 years design life with very high deep cycling capabilities. This range is highy suited to telecom outdoor applications, renewable energy system and other harsh environment applications.
Application Emergency power system UPS Other spare, circulatory system
Correspondence exchange and transmission system Mobile communication system Power plant and power transformer system Radio and broadcasting station Navigation and signaling system
General Features Sealed and maintenance free operation. Non-Spillable construction design. ABS containers and covers (UL94 V0, optional). Safety valve installation for explosion proof. High quality and high reliability. Exceptional deep discharge recovery performance. Low self discharge characteristic. Flexible design for multiple installation positions.
7mm (0.28inch)
20mm (0.79inch)
M8mm (0.31inch)
Construction Positive ...... Negative ...... Container ...... ...... Cover Sealant ......
Safety valve Terminal Separator Electrolyte
Lead dioxide Lead ABS ABS Epoxy Resin
...... ...... ...... ......
Terminal Dimensions
184.5mm(7.26inch)
102mm(4.02inch)
372mm(14.6inch)
123mm(4.84inch)
360.5mm(14.2inch)
EPDR Copper AGM Acid with gel
Battery Model
LSG2-300
Designed Floating Life Capacity(20oC)
Dimensions
20 Years 10HR(30.0A,1.80V)
20HR(15.8A,1.80V)
5HR(51.5A,1.75V)
316Ah
300Ah
257Ah
188Ah
Length
Width
Height
Total Height
123mm(4.84inch)
184.5mm(7.26inch)
360.5mm(14.2inch)
Approx. Weight
19.4Kg (42.8 lbs)
Internal Resistance
Full charged at 20oC :0.00047 Ohm
Self Discharge
< 3% of capacity declined per month at (20oC)
Capacity Affected by Temp.(10HR) Charge Voltage(20oC)
1HR(188A,1.60V)
372mm(14.6inch)
40oC
20oC
0oC
-15oC
109%
100%
85%
65%
Cycle use
Float use
o
2.35V-2.40V(-5mV/ C), max. Current: 75A
Page 1 of 2
2.25-2.29V(-3mV/ oC)
LSG2-300
2V300Ah
Charge Voltage
(CA) (V/Cell)
(%) 120
2.35 100 80
0.25
o
Constant Charge at 0.25CA-2.35V (20 C) Charge Capacity
Charge Voltage
2.17 100%Discharge
0.20
60
2.00
50%Discharge
0.15
40
0.10 20
1.83
0.05
0
0
Discharge Characteristic (20oC)
Charge Characteristic
Charge Current
0
2
4
6
8
10
Discharge Voltage (V/Cell)
Current
Charge
Charge Capacity
Gel SLA Battery
2.17 2.00 1.83 0.25CA 0.1CA 0.05CA
1.67 1.60
3CA
2CA
1CA
6
12
30
1.33 0
12
2
60
3
Min
Time(hour)
10 Hour
20
Self Discharge Characteristics
Relationship of OCV and state of charge 2.25
110 105
2.17
100 95 90
Capacity (%)
Battery Voltage (V/Cell)
0.6CA
2.08
2.00
85 80 75 70 65 60 55 50
1.92
1.83
o
0
10
20
30
40
50
60
70
80
90
100
40 0
1
2
20oC
o
40 C
45
30 C 3 4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20
Storage time:months
Remained Capacity(%)
Constant current discharge ratings-amperes at 20oC F .V /T im e
5 M IN
1 0 M IN
1 5 M IN
3 0 M IN
1HR
3HR
5HR
10 H R
20HR
1 .6 0V
1172
729
550
335
188
9 3.6
5 4 .9
3 2 .0
1 7 .5
1 .6 7V
1100
692
529
321
185
9 0.0
5 3 .8
3 1 .7
1 6 .9
1 .7 0V
1008
667
517
292
180
8 4.0
5 2 .6
3 1 .6
1 6 .6
1 .7 5V
988
646
500
277
171
8 1.2
5 1 .5
3 1 .1
1 6 .2
1 .8 0V
884
617
454
257
160
7 8.0
4 8 .4
3 0 .0
1 5 .8
1 .8 5V
780
588
408
236
149
7 5.2
4 5 .3
3 0 .3
1 5 .3
Constant power discharge ratings-watts at 20oC F .V /T im e
5 M IN
1 0 M IN
1 5 M IN
3 0 M IN
1HR
3HR
5HR
10 H R
20HR
1 .6 0V
2056
1317
1004
604
339
1 66
9 1 .8
6 4 .0
3 4 .9
1 .6 7V
1984
1283
992
592
337
1 61
9 1 .4
6 3 .6
3 3 .7
1 .7 0V
1868
1271
983
554
330
1 54
9 0 .3
6 3 .2
3 3 .3
1 .7 5V
1880
1267
975
538
325
1 50
8 9 .5
6 2 .4
3 2 .4
1 .8 0V
1720
1248
904
513
306
1 46
8 6 .7
6 1 .6
3 1 .6
1 .8 5V
1560
1184
820
480
288
1 41
8 3 .9
6 0 .8
3 0 .4
ISO9001
COPYRIGHT BSB POWER COMPANY LIMITED Page 2 of 2