Transcript
Power analyzers
M-CVM-AB
Expansion modules M-CVM-AB-8I-8OTR
Description Expansion module with 8 digital inputs and 8 transistor outputs.
Applications Digital inputs Reports via communications: ——Logic states of non-unit external systems ——Metering of the impulses generated by other units (water and gas meters, etc.) Digital outputs ——Activation / deactivation by maximum or minimum instantaneous parameter values measured by the unit ——Generation of impulses by incremental parameters measured by the unit
Technical features Maximum power consumed
3W
Mechanical
Terminal protection
IP 20
Logical inputs
Type of input
Voltage-free / NPN
Type of coupling
Optoisolated input
Maximum voltage
12 Vdc
ION
4 mA
Input consumption
< 0.25 W
Minimum times
tON 40 ms tOFF 40 ms
Static outputs
Digital outputs Code
Number of inputs
8
Connection
0.05-1.5 (AWG 30-14) mm2
Terminal tightening torque
0.3 Nm
Rated voltage
250/150 Vac / Vdc
Nominal current
< 100 mA
Maximum current
< 150 mA
Maximum dissipation power
0.5 W
Maximum R ON
80
No. of outputs
8
Connection
0.05-2.5 (AWG 30-12) mm2
Terminal tightening torque
0.6 Nm
M56E01
17
Power analyzers
Expansion modules M-CVM-AB-8I-8OTR
M-CVM-AB Connections 1
2
3
4
5
6
7
8
9 10
Terminals on the upper face List of terminals on the upper face, transistor digital inputs/outputs module Unit terminals
Terminals of transistor digital inputs/ outputs, upper face
11 12 13 14 15 16 17 18 19
1
T1
Digital output of transistor 1
6
T5
Digital output of transistor 5
2
T2
Digital output of transistor 2
7
T6
Digital output of transistor 6
3
T3
Digital output of transistor 3
8
T7
Digital output of transistor 7
4
T4
Digital output of transistor 4
9
T8
Digital output of transistor 8
5
CT
Shared by the transistor's digital outputs
10
CT
Shared by the transistor's digital outputs
Terminals on the lower face List of terminals on the lower face, transistor digital inputs/outputs module Unit terminals
Terminals of transistor digital inputs/ outputs, lower face
11
GND
For digital inputs:
16
I5
Digital input 5
12
I1
Digital input 1
17
I6
Digital input 6
13
I2
Digital input 2
18
I7
Digital Input 7
14
I3
Digital input 3
19
I8
Digital input 8
15
I4
Digital input 4
Transistor digital outputs
Digital inputs
12 V DC
Optoacoplador
10k
10k
1 2 3 4 5 6 7 8 9 10
COMM
11
3k
3k
NPN
Tensión Externa
Connection diagram, transistor digital outputs
18
Connection diagram, digital inputs
19
Libre potencial
Power analyzers
M-CVM-AB
Expansion modules M-CVM-AB-8I-8OR
Description Expansion module with 8 digital inputs and 8 relay outputs.
Applications Digital inputs ——Reports via communications: ——Logic states of non-unit external systems ——Metering of the impulses generated by other units (water and gas meters, etc.) Digital outputs ——Activation / deactivation by maximum or minimum instantaneous parameter values measured by the unit
Technical features Maximum power consumed
3W
Mechanical
Terminal protection
IP 20
Logical inputs
Type of input
Voltage-free / NPN
Type of coupling
Optoisolated input
Maximum voltage
12 Vdc
I ON
4 mA
Input consumption
< 0.25 W
Minimum times
tON 40 ms tOFF 40 ms
Relay outputs
Number of inputs
8
Connection
0.05-1.5 (AWG 30-14) mm2
Terminal tightening torque
0.3 Nm
Rated voltage
12 V
Nominal current
10 mA
Maximum load Vac
250/5 Vac / A
Maximum load Vdc
30/5 Vdc / A
Minimum relay load
100 mV dc 100 μA
Digital outputs Code
Mechanical working life
2 x 107 cycles
Electrical working life at rated load
5 x 104 cycles
Number of outputs
8
Connection
0.05-2.5 (AWG 30-12) mm2
Terminal tightening torque
0.6 Nm
M56E02
19
Power analyzers
Expansion modules M-CVM-AB-8I-8OR
M-CVM-AB Connections 1
2
3
4
5
6
7
8
9 10
Terminals on the upper face List of terminals on the upper face, relay digital inputs/outputs module Unit terminals
Terminals of relay digital inputs/outputs, upper face
11 12 13 14 15 16 17 18 19
1
R1
Relay digital output 1
6
R5
Relay digital output 5
2
R2
Relay digital output 2
7
R6
Relay digital output 6
3
R3
Relay digital output 3
8
R7
Relay digital output 7
4
R4
Relay digital output 4
9
R8
Relay digital output 8
5
Rc
Shared by all relay digital outputs
10
Rc
Shared by all relay digital outputs
Terminals on the lower face List of terminals on the lower face, relay digital inputs/outputs module Unit terminals
Terminals of relay digital inputs/outputs, lower face
Transistor digital outputs
11
GND
For digital inputs:
16
I5
Digital input 5
12
I1
Digital input 1
17
I6
Digital input 6
13
I2
Digital input 2
18
I7
Digital Input 7
14
I3
Digital input 3
19
I8
Digital input 8
15
I4
Digital input 4
Digital inputs
12 V DC
Relé
10k
10k
1 2 3 4 5 6 7 8 9 10
COMM
11
3k
NPN
3k
19
Libre potencial
Tensión externa
Connection diagram, relay digital outputs
20
Connection diagram, digital inputs
Power analyzers
M-CVM-AB
Expansion modules M-CVM-AB-4AI-8AO
Description Expansion module with 4 analogue inputs and 8 analogue outputs.
Applications Analogue inputs ——Measuring signal parameters for non-unit external processes. ——Viewing the signals on screen and reporting them via communications Analogue outputs ——Generating process signals for the instantaneous electrical parameters measured by the unit
Technical features Maximum power consumed
3W
Mechanical
Terminal protection
IP 20
Analogue inputs
Type of measurement
Current
Nominal input range
0-20 / 4-20 mA dc
Metering accuracy
< 1%
Input impedance
150 Ω
Maximum acceptable input current
22 mA dc
Number of inputs
4
Connection
0.05-1.5 (AWG 30-14) mm2
Terminal tightening torque
0.25 Nm
Maximum internal voltage
12 V
Nominal output range
0-20 / 4-20 mA
Linearity
<1%
Maximum load resistor
300 Ω
DAC resolution
4096 dots
No. of configurable outputs in current mode
8
Maximum internal voltage
12 V
Nominal output range
0-10 V
Linearity
<1%
Minimum load resistor
5000 Ω
DAC resolution
4096 dots
No. of configurable outputs in current mode
8
Analogue outputs in current mode
Analogue outputs in voltage mode
Code
M56E03
21
Power analyzers
Expansion modules M-CVM-AB-4AI-8AO
M-CVM-AB Connections 1
2
3
4
5
6
7
8
Terminals on the upper face
9
List of terminals on the upper face, analogue inputs/outputs module Unit terminals
Analogue input/output terminals, upper face
1
O1
Analogue output 1
6
O5
Analogue output 6
2
O2
Analogue output 2
7
O6
Analogue output 7
3
O3
Analogue output 3
8
O7
Analogue output 8
4
O4
Analogue output 4
9
COM
Shared by the analogue outputs
5
Oc
Analogue output 5
Terminals on the lower face
10 11 12 13 14 15 16 17
List of terminals on the upper face, analogue inputs/outputs module Unit terminals 10
I1+
Analogue input 1
14
I3+
Analogue input 3
11
I1-
Analogue input 1
15
I3-
Analogue input 3
12
I2+
Analogue input 2
16
I4+
Analogue input 4
13
I2-
Analogue input 2
17
I4-
Analogue input 4
Analogue input/output terminals, lower face
Analogue outputs
D
A
Analogue inputs
D
D
A
1
9
Connection diagram, analogue outputs
22
A
10 +
Carga externa
D
A
17 Sensor 0/4 ...20 mA
Connection diagram, analogue inputs
+
Sensor 0/4 ...20 mA
Power analyzers
M-CVM-AB
Expansion modules M-CVM-AB-Modbus TCP-bridge
Description Expansion module with Modbus/TCP communications (Ethernet).
Applications Enables communications with SCADA systems, or similar, over TCP/IP computer networks using the Modbus/TCP protocol.
Technical features Maximum power consumed
3W
Mechanical
Connections
RJ-45 connector
Protocol
Ethernet
Communications
Bridge TCP to RS-485, Modbus TCP to Modbus/RTU
Code
M56E05
Connections C B(-) A(+)
PC
RS-485
Ethernet
M-CVM-AB
Expansion modules M-CVM-AB-Modbus TCP-switch
Description Expansion module with Modbus/TCP communications (Ethernet).
Applications It allows the Modbus TCP communication with SCADA systems in addition to Ethernet connectivity with other devices in cascade, avoiding long distances Ethernet cabling from centralized router or switch.
Technical features Maximum power consumed
3W
Mechanical
Connections
RJ-45 connector
Protocol
Ethernet
Communications
Bridge TCP to RS-485, Modbus TCP to Modbus/RTU
Code
M56E0A
Connections C B(-) A(+)
PC
Ethernet
M-CVM-AB-Modbus TCP-switch
RS-485
M-CVM-AB-Modbus TCP-bridge
M-CVM-AB-Modbus TCP-bridge
23
Power analyzers
M-CVM-AB
Expansion modules M-CVM-AB-MBus
Description Expansion module with MBUS communications.
Applications Enables the integration of units in MBUS communications networks (METER BUS).
Technical features Maximum power consumed
3W
Mechanical
Input connection
A+ / B-
Output connection
A+ / B-
Bus
Wired M-Bus
M-Bus regulations
EN 13757-2:2004, EN 13757-3:2004, EN 1434-3:2008
Protocol
Slave M-BUS
Baud Rate
300, 600, 1200, 2400, 4800, 9600 (configurable from the unit menu)
Stop bits
1
Parity
even
Primary address
1 to 250 (configurable from the unit menu)
Features
Code
M-CVM-AB
M56E07
Expansion modules M-CVM-AB-LonWorks
Description Expansion module with LonWorks communications.
Applications Enables communication with SCADA systems, or similar, through the LonWorks protocol.
Technical features Maximum power consumed
1,2 W
Mechanical
Connections
RJ-45 connector
Protocol
LonWorks
Communications
Lon Talk ISO/IEC 14908 ANSI/EIA 7091
Code
M56E08
Connections Red LonWorks
AB
24
AB
A B A B
Power analyzers
M-CVM-AB
Expansion modules M-CVM-AB-Profibus
Description Expansion module with Profibus communications.
Applications Enables communication with SCADA systems, or similar, through the Profibus/DP protocol.
Technical features Maximum power consumed
2W
Mechanical
Connections
DB-9
Communications
Profibus/DP
Code
M56E09
Master Profibus
Connections
Red Profibus / Network Profibus
25
Power analyzers
M-CVM-B
Expansion modules M-CVM-AB-Datalogger
Description Expansion module for CVM-B that enables historical records. The data base is accessible using a WEB browser supporting HTML5 or PowerStudio Client (JAVA).
Applications ——Data storage on the CVM-B itself ——200MB ring buffer. Up to 1 year averaged data every 15 minutes (average, maximum and minimum value in each record) ——Integrations with other SCADA systems through XML requests (Service integrated in the module ) ——Automatic synchronization with the PowerStudio data base in all versions ——Module Configuration throught the Editor of PowerStudio (free tool software) ——All the benefits of embedded PowerStudio. (Programming calculations, time discrimincación, events, user access profiles, etc.) ——Integrated HTML5 Web Server, visible using Smarthphones, tablets and PC directly ——E-mails sending from the own equipment, reporting any variable measured or calculated in the CVM-B.
Technical features Maximum power consumed
3W
Mechanical
Terminal protection
IP 30
Communications
Connections
RJ-45
Protocol
Ethernet
Communications Speed (Baudrate)
Modbus / TCP
Data storage
Internal memory
200 MB Cyclic memory
Code
M56E06
Ethernet 10BT / 100BT
Connections
Con navegador Web compatible con Java With a browser compatible with Java
Servidor PowerStudio (Opcional)
Con navegador Web compatible con Java
PowerStudio Server (Optional)
With a browser compatible with Java
Internet router Ethernet
CVM-B M-CVM-AB-Datalogger Server / Servidor Web Server / Servidor XML PowerStudio DDBB
26