Transcript
Mains Isolation Relays K-RY General • 2 NO-contact*, 1 NO/NC-contact*, 2 NC-contact * Mains isolation - relay with 3mm contact gap for full switching off • Upright version • 35 mm version for standard rail mounting • Ambient temperature – 25 … + 55 °C • Soldering heat resistance 260 °C/5s • RoHS compliance
Connections • Soldering pins for PCB • 6.3 mm Faston plug Drive • Direct current, monostable • AC-current, monostable Approvals • cULus (Version with 2 NO-contact) Standards • IEC 61810-1
Technical Data mechanical
Technical Data electrical
Dimensions L x W x H (in mm)
50,2 x 31,2 x 28,7
Shock resistance Vibration resistance
5 g, 11 ms Half sinus 5 g, 10 – 55 Hz
Operating time Releasing time
typical 15 ms typical 3 ms
Mechanical service life (without load) Weight
>10 7 cycles 55 g
Max. switching capacity Max. switching current
Version with 2 NO-contact AC 3.680 VA, DC *W 16 A
Max. switching capacity Max. switching current
version with contactset 110 or 020 AC 2.300 VA, DC *W 10 A
Max. switching voltage Electrical service life (with nominal load) * see DC-switching capacity
Insulation
Over voltage category (Ü) III Degree of pollution (V) 2 Insulating material group II Insulation between Contact – Contact Contactset – Drive
106
Relay catalogue
AC 230/240, DC *V >100.000 cycles
B-I = Basic insulation V-I = Reinforced (double) insulation
Nominal voltage network system AC 120/240 V AC 230/400 V V-I B-I V-I V-I
Air-/ creeping distance > 3 mm > 8 mm
Test voltage 50Hz/60s AC 2.500 V AC 4.000 V
Mains Isolation Relays K-RY Dimensions
K-RY (for PCB)
K-RY (with 6,3 mm Faston plug)
KOO-_3RY/11
KOO-_4RY/11
K-RY (6,3 mm and tab screen mounting)
K-RY (6,3 mm for standard rail mounting)
KOO-_4RY/12
KOO-_4RY/13
Standard rail
Type key
Special Features O Standard
Drive 0 DC, neutral, monostable 1 AC, monostable
Special version 1 Standard 2 tab screen mounting on housing 3 for standard rail mounting 35 mm
Version 00 Standard 01 Special version
K O O - 0 3 R Y _ / 1 1 - 0 0 1 0 1 4 - 2 0 0 / 0 0 1 . 0 0 Housing 0 dustproof (RTII)
Contactset table
Connections 3 Soldering pins for PCB 4 Faston plug 6,3 mm
Number of contacts NO/NC/CO-contacts 200 (16 A) 110 (10 A) 020 (10 A)
Coils See coil table
NC-contact
Size 1 Standard
CO-contact
AgCdO
AgCdO
AgCdO
AgCdO
Soldering pin
Faston plug
Soldering pin
Faston plug
DC-Coil 001 003 002
DC-Coil 007 009 008
Contactset-number See contactset table
NO-contact
AC-Coil 004 006 possible
AC-Coil 010 012 011
AgCdO + 10 µm A Soldering pin
DC-Coil 014 possible possible
Relay catalogue
W
Soldering pin Contact
DC-Coil
material
013 015 possible
contact set number
107
Mains Isolation Relays K-RY All values at ambient temperature Tu = 20 °C
Coil table Number of contacts 200
Coil-No. 001028 001026 001021 001014 001068 001009 001006
DC-Drive
Coil-No.
Number of contacts 110 und 020
001031 001028 001022 001016 001012 001011 001006
DC-Drive
Coil-No.
Number of contacts 200, 110 und 020
001136 001128 001121 001116 001114 001111 001106
AC-Drive
Resistance R/Ω 17 28 80 440 1.380 2.780 6.700
Resistancetolerance ± 15% 15% 15% 15% 15% 23% 23%
U1/V
Resistance R/Ω 12 17 63 260 1.050 1.730 6.700
Resistancetolerance ± 15% 15% 15% 15% 15% 15% 23%
U1/V
Resistance R/Ω 5 17 80 260 445 1.730 6.700
3,9 4,9 8,7 19,3 35,2 51,3 81,7
U2/V
Urück/V
7,4 9,6 16,2 38,3 67,5 93,0 144,4
U2/V
3,5 4,4 8,5 17,7 34,4 43,4 92,6
0,8 1,0 1,7 3,8 6,8 9,0 14,2
Urück/V
6,2 7,4 14,4 29,3 58,8 75,5 144,4
Umin/V
Umax/V
4,8 9,6 19,2 33,6 48,0 88,0 184,0
6,6 13,2 26,4 45,0 66,0 121,0 253,0
0,2 0,3 0,6 1,2 2,4 3,0 5,7
Printing Unom/V 5 6 12 24 48 70 110
Printing Unom/V 5 6 12 24 48 60 115
Printing Unom/V 6 12 24 42 60 110/115 220/230
Coil designed for 50 Hz, 100% ED at Tu +20 °C U 1: U 2: U rück:
Minimum operating voltage with consideration of coil self heating Thermal restricted maximum coil voltage Releasing voltage
Further coils are possible and available
Running types
Article-No. RY_-4407 RY_-4412 RY_-4417 RY_-4800 RY_-4801 RY_-4802 RY_-4806 RY_-4808 RY_-4820 RY_-4824 RY_-4839 RY_-5664
108
Relay catalogue
Type key KOO-04RY_/12-001014-200/001.00 KOO-03RY_/11-001014-200/001.00 KOO-14RY_/12-001106-200/010.01 KOO-14RY_/11-001106-200/010.00 KOO-03RY_/11-001014-200/001.00 KOO-13RY_/11-001106-200/004.00 KOO-04RY_/11-001014-200/007.00 KOO-03RY_/11-001021-200/001.00 KOO-04RY_/12-001014-200/007.00 KOO-04RY_/13-001014-200/007.00 KOO-03RY_/11-001026-200/014.00 KOO-14RY_/12-001106-200/010.00
Printing Unom DC 24 V DC 24 V AC 230 V AC 230 V DC 24 V AC 230 V DC 24 V DC 12 V DC 24 V DC 24 V DC 6 V AC 230 V
U1/V 19,3 19,3 184,0 184,0 19,3 184,0 19,3 8,7 19,3 19,3 4,9 184,0
U2/V 38,3 38,3 253,0 253,0 38,3 253,0 38,3 16,2 38,3 38,3 9,6 253,0
Urück/V 3,8 3,8
3,8 3,8 1,7 3,8 3,8 1,0
Mains Isolation Relay K-RY 2 NO (200), 16 A
Connection grid View on soldering side
2 NC (020), 10 A
1 NO / 1 NC (110), 10 A
current (A)
Contactgap: Arc duration
0
Switching voltage
DC-switching capacity
current (A)
Diagrams
0
Switching cycles
Electrical service life
Relay catalogue
109