Page 1
32 Digital Outputs HE450DQM701 / HE459DQM701 24VDC Out, Negative Logic HE459DQM706 24VDC Out , Positive Logic
SmartStix
For electronic information including the GSD File, see www.SmartStix.com. This product has a Programming Reference (SUP0552). HE450 denotes a non-removable terminal strip; HE459 denotes a removable terminal strip.
1
SPECIFICATIONS
DQM701 / 706 Outputs Number of output points Commons per Module Operating Voltage Rated Load Voltage Maximum Load Current per channel
Max. DQM Inrush 701 Current DQM per 706 channel OFF Leakage Current Maximum Voltage Drop during ON circuit Internal power Consumption (mA) General Storage Temperature Operating Temperature Atmosphere Operating and Storage Humidity
32 2 24VDC 24VDC 0.1A Max. per output; 2A per common 0.4A, 10ms.
External Power Supply
Voltage Current
OFF to ON Response ON to OFF Response DQM Output 701 Type DQM 706 Operating Indicator
24VDC ± 10%(ripple voltage: 4Vp-p or less) 30mA (TYP, All points ON) 0-3ms. or less 0-3ms. or less Sinking Sourcing LED turns on during ON state of output
External connections
Terminal block connector (M3 x 6 screws)
0.1mA or less
Common Method
16 points / COM
1.5VDC(0.5A)
Isolation methods
Photo Coupler
1A, 10ms
380mA -25° to 70° C 0° to 55° C Free from corrosive gases and excessive dust
5 to 95% Noncondensing
Weight
DQM701 DQM706
Pollution degree Internal power Consumption (mA) Cooling method Weight
8.9oz. (255g) 10.0oz. (285g) 2 or lower 380mA Self-cooling 8.4 (239G)
MAN0532-04
Information is subject to change without notice.
Page 2
12 NOV 2003
DQM701 / 706
Vibration Occasional Vibration Frequency 10 ≤ f < 57 Hz 57 ≤ f ≤ 150 Hz
Acceleration
Amplitude
-
0.075 mm
9.8 m/s 2 {1G}
-
Sweep Count 10 times in each direction for X,Y,Z
Continuous Vibration Frequency
Acceleration
Amplitude
10 ≤ f < 57 Hz
-
0.035 mm
57≤ f ≤ 150 Hz
4.9 m/s 2 {0.5G}
-
10 times in each direction for X,Y,Z
Shocks Maximum shock acceleration
147 m/s 2 {15G}
Duration Time Pulse Wave
Sweep Count
11 ms. Half sine wave pulse (3 times in each of X, Y, Z directions)
Noise Immunity AC: ± 1,500VDC DC: ± 900VDC Voltage: 4kV (contact discharge)
Square wave impulse noise Electrostatic Discharge Radiated electromagnetic field Fast Transient Burst Noise
27 – 500MHz, 10V/m Severity level Voltage
2
All power modules 2 kV
Digital I/Os (Ue ≥24V) 1 kV
Digital I/Os (Ue < 24 V) Analog I/Os Communication I/Os 0.25 kV
DIMENSIONS 0.18 [4.6mm]
0.31 [7.9mm]
0.31 [7.9mm]
1.62 [41.1mm]
6.61 [167.9mm] 6.95 [176.5mm]
Information is subject to change without notice.
1.53 [38.9mm]
HExx0- Without Removable Terminal
1.87 [47.5mm]
HExx9-With Removable Terminal
DQM701 / 706
3
12 NOV 2003
Page 3
WIRING
24+
Pin
24C
24+
Q2
FG
Q4
24C
Q6
Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8 Q9 Q10 Q11 Q12 Q13 Q14 Q15 Q16
FG LOAD
Q1
LOAD LOAD
Q3
LOAD
Q5
LOAD
Q7
LOAD
Q9
LOAD
Q11
LOAD
Q13
LOAD
Q15
LOAD
LOAD
Q8
LOAD
Q10
LOAD
24VDC
Q12
LOAD
Q14
LOAD
Q16
LOAD
C1 Q17
LOAD
Q18
LOAD
Q19
LOAD
Q20
LOAD
Q21
LOAD
Q22
LOAD
Q23
LOAD
Q24
LOAD
Q25
LOAD
Q26
LOAD LOAD
24VDC
LOAD
C1
Q29
Q17 Q18 Q19 Q20 Q21 Q22 Q23 Q24 Q25 Q26 Q27 Q28 Q29 Q30 Q31 Q32
Q30
LOAD
Q31
LOAD LOAD
Q27 Q28
LOAD
Q32
C2 V+ 006DQM006
C2 V+
Information is subject to change without notice.
Signal DQM701 24V Power Supply Frame Ground Power Supply Return Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7 Output 8 Output 9 Output 10 Output 11 Output 12 Output 13 Output 14 Output 15 Output 16 Isolated Common 1 Output 17 Output 18 Output 19 Output 20 Output 21 Output 22 Output 23 Output 24 Output 25 Output 26 Output 27 Output 28 Output 29 Output 30 Output 31 Output 32 Isolated Common 2 Isolator Power
Page 4
12 NOV 2003
DQM701 / 706
Pin 24+
FG LOAD
Q1
LOAD
Q3
LOAD
LOAD
24VDC
LOAD
Q5
LOAD
Q7
LOAD
Q9
LOAD
Q11
LOAD
Q13
LOAD
Q15
LOAD
LOAD
24C
24 FG
Q2
24C*
Q4 Q6 Q8 Q10
LOAD
Q12
LOAD
Q14
LOAD
Q16
LOAD
C1 Q17
LOAD
Q18
LOAD
Q19
LOAD
Q20
LOAD
24VDC
Q21
LOAD
Q22
LOAD
Q23
LOAD
Q24
LOAD
Q25
LOAD
Q26
LOAD
Q27
LOAD
Q28
LOAD
Q29
LOAD
Q30
LOAD
Q31
LOAD LOAD
Q32
C2 0V 006DQM008-R1
Note: If desired, C1 and C2 can use a single supply.
Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8 Q9 Q10 Q11 Q12 Q13 Q14 Q15 Q16 C1 Q17 Q18 Q19 Q20 Q21 Q22 Q23 Q24 Q25 Q26 Q27 Q28 Q29 Q30 Q31 Q32 C2 0V
Information is subject to change without notice.
Signal DQM706 24V + Frame Ground 24V Common (*Do not Connect) Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7 Output 8 Output 9 Output 10 Output 11 Output 12 Output 13 Output 14 Output 15 Output 16 Isolated Common 1 Output 17 Output 18 Output 19 Output 20 Output 21 Output 22 Output 23 Output 24 Output 25 Output 26 Output 27 Output 28 Output 29 Output 30 Output 31 Output 32 Isolated Common 2 Isolated Power Negative
DQM701 / 706
12 NOV 2003
4
INTERNAL WIRING
a.
DQM701
I/O Connector
Page 5
SmartStix
V+
Field Side
Q32
From Controller
Q17
From Controller
Isolated C2 Q16
From Controller
Q1
From Controller
Isolated C1
Information is subject to change without notice.
Page 6
b.
12 NOV 2003
DQM701 / 706
DQM706
I/O Connector
SmartStix
C1 From Controller
Field Side Q17 – Q32 Typical
C2 From Controller
Q1 – Q16 Typical
0V
Information is subject to change without notice.
DQM701 / 706
5
12 NOV 2003
Page 7
SWITCHES
Setting Address Switches: Profibus addresses are set using the decimal number system from 1 to 99. Set a unique Network ID by inserting a small Phillips screwdriver into the two identical switches as shown in the example. Use this switch to set the Low Digit – has an x1 multiplier.
Use this switch to set the High Digit –has an x10 multiplier.
Power and Diagnostic LEDs
SmartStix I/O HI (x10)
7 5 6 6
7
8
9
10
I/O Status LEDs
9
12
13
14
15
006DIM001
1
2 3
8
2 3
8 7
0 7
9
1
4
4
5 6
0
11
4
5
2 3
4
4
3
0 1
8
2 3
2
9
0 1
8
1
LO (x1)
7
ERR
9
RDY
5 6
RUN
5 6
Close-up of Switches
6
LEDs Communication LED
MEANING
RUN
Displays the status of the power
RDY
Displays the communication status of the communication module
ERR
Displays abnormal condition of communication module
Information is subject to change without notice.
16
Page 8
7
12 NOV 2003
DQM701 / 706
NETWORK CABLE
For detailed network information, refer to www.profibus.org.
a.
A SmartStix module uses a 9-pin D-sub plug connector for its DP port. The pin assignment of the plug connector and the wiring are shown below. Station 1 Rx/TxD-P V+ DGND Rx/TxD-N
3 6 5 8
Station 2
Line B
3 6 5 8
Line A Shielding
Protective Ground
b.
It is necessary to terminate both ends of the network. Both terminations must have power to them to insure proper operation of the network. The following diagram illustrates the correct connection for the termination resistors. The diagram is for illustrative purposes only. Note: Cabling and connectors need to be PTO-approved to achieve the desired performance results. VP(6) Line Termination
390 Ohm
B-Line (3) 220 Ohm
Internal
A-Line (8) 390 Ohm GND(5)
c.
The shield braiding (and if present, the shield foil) must be connected to protective ground on both sides and must have good conductivity via shield clamps that cover as large an area as possible. In addition, it is recommended that the data lines be kept separate from all high-voltage cables.
8
INSTALLATION / SAFETY
a. b.
All applicable codes and standards need to be followed in the installation of this product. For I/O wiring (discrete), use the following wire type or equivalent: Belden 9918, 18 AWG or larger.
c.
For detailed installation information, refer to www.profibus.org.
Warning: Consult user documentation.
Information is subject to change without notice.
Warning: Electrical Shock Hazard.
DQM701 / 706
9
12 NOV 2003
TECHNICAL ASSISTANCE
For assistance, contact Technical Support at the following locations: North America: (317) 916-4274 www.heapg.com Europe: (+) 353-21-4321-266 www.horner-apg.com
Information is subject to change without notice.
Page 9
Page 10
12 NOV 2003
NOTES
Information is subject to change without notice.
DQM701 / 706