Preview only show first 10 pages with watermark. For full document please download

Manual 13794919

   EMBED


Share

Transcript

DUAL-TEC™ WALL-MOUNT™ Air Conditioners with -48VDC Blower Motor DC Voltage 100% Free Cooling Unit D28A/L to D60A/L 1-Stage Right & Left-Hand Control Panel The Bard DUAL-TEC™ Wall Mount™ Air Conditioners with -48VDC Blower Motor and DC Voltage Free Cooling Economizer are designed for maximum indoor cooling at the most efficient operating cost for year-round operation in the demanding equipment shelter environment. The DUAL-TEC™ units operate on both AC and -48VDC positive ground power under normal power supply conditions. If there is loss of AC power supply (shore and/ or back-up generator) the DUAL-TEC™ will continue to operate as free-cooling or ventilation system using the shelter’s DC power. The DUAL-TEC™ indoor blower and economizer operate from -48VDC and no inverter is required. The DUAL-TEC™ units will supply up to 100% of rated cooling airflow in free cooling mode with the ability to exhaust the same amount through the unit itself without any additional relief openings in the shelter. Green Refrigerant R-410A Standard Engineered Features — All Models Copper Tube / Aluminum Fin Coils: Galvanized 20 Gauge Zinc Coated Grooved copper tubing and enhanced Steel Cabinet: Dirty Filter Switch: With alarm relay with gold-plated contacts. aluminum fins provide maximum heat transfer and high energy efficiency. Evaporator coil constructed with hydrophilic fin stock that seals fin surface against aluminum oxide formation, is resistant to mold and mildew growth (tested to ASTM D3273, no growth) and reduces beading of condensate on the fin surface. Optional phenolic-coated coils are also available. Cleaned, rinsed, sealed and dried before the polyurethane primer is applied. The cabinet is handsomely finished with a baked on textured enamel, which allows it to withstand 1000 hours of salt spray tests per ASTM B117-03. Extreme Outdoor Temperature Rating: Slope Top: Unit operation tested at 131°F outdoor ambient temperature. Built into cabinet for improved appearance and easy installation. NOTE: Bottom mounting bracket included to assist in installation. Twin Blower Wheels: Liquid Line Filter Drier: High & Low Pressure Switches are Move air quietly with standard dual blower configuration on slide tracks for service. Brushless -48VDC Indoor Blower Motor: Features low sound levels and softstart capabilities. Soft start function helps to ensure DC power levels will not decrease on start up, and brushless design ensures low DC power noise. The motor is self-adjusting to provide the proper airflow rate without user adjustment or wiring changes. Foil Faced Insulation: Standard on all units. Full Length Mounting Brackets: Slides out for easy access. Built-In Circuit Breakers: HACR-type circuit breakers are standard for AC power supply, and DC rated circuit breaker used for -48VDC power circuit. Standard feature for water run-off. Top Rain Flashing: delay if power interrupt. 120-second bypass for low pressure control, and both soft and manual lockouts for high and low pressure controls. Alarm output for alarm relay. Low Ambient Control: Electrical Components: Standard on all units. 24V Transformer: 75VA with circuit breaker Designed with R-410A (HFC) non-ozone depleting refrigerant in Electric Heat Strips: compliance with the Montreal protocol Features an automatic limit and and 2010 EPA requirements. thermal cut-off safety control. Heater packages are factory installed PTCR Motor Starting Device: for all 2½ through 5 ton models. Standard on 1-phase models, increases compressor motor starting Two-Inch, MERV 8 Air Filters: torque 2-3 times. Optional factory or Are standard equipment. All models field installed hard start kit available, include tight-sealing U-channel filter replaces PTCR device. bracket to minimize air bypass around the filter. DC Polarity Monitor: Includes diagnostics and protects critical DC components against reverse polarity and out-of-range DC power. Range is 40-60 VDC. Modulating Economizer Motor: For precision control. Standard feature on all models. Standard on all units. Protects system Auto-Reset: against moisture. Standard on all units. Built-in lockout circuit resets from the shelter Compressor Control Module: Bard-Link™ Controller. Provides Standard on all units. Built-in commercial quality protection to the off-delay timer adjustable from 30 seconds to 5 minutes. 2-minute on- compressor. Are easily accessible for routine inspection and maintenance through Air Conditioner Compressor: side service panel opening. Features Scroll compressors are designed for a lockable, hinged access cover to increased efficiency, quieter operation the circuit breaker. and improved reliability for longer life. R-410A Refrigerant: Condenser Fan and Motor Shroud Assembly: LC2000 Series Modulating LAC standard on all models. Screw-on fitting design for ease of service. Refrigerant Sight Glass: Refrigerant Pressure Alarm Contacts: Standard on all units. Free Cooling Unit: All units come equipped with a full-flow dry bulb Free Cooling Unit as standard equipment. Free Cooling Units are also equipped with alarm outputs. Phase Rotation Monitor (3-Phase Units Only): Protects against reverse rotation if AC power supply is not properly connected. Form No. S3521-116 Supersedes S3521-1015 Page 1 of 6 Capacity and Efficiency Ratings — 1-Stage Compressors MODELS Cooling Capacity BTUH  EER    D28A D28L D36A D36L D42A D42L D48A D48L D60A D60L 28,600 36,000 41,500 47,000 57,000 11.5 11.5 11.0 10.5 10.0 Capacity is certified in accordance with ANSI/ARI Standard 390-2003. Rating conditions are 95°F (35°C) outdoor and 80°F DB/67°F WB (26.5°C / 19.5°C WB) return air. EER = Energy Efficiency Ratio (BTU / Watt Efficiency) is certified in accordance with ANSI/ARI Standard 390-2003. Includes DC watts for blower motor. Ratings are with no outside air. Performance will be affected by altitude. Electrical Ratings — 1-Stage Compressor Models D28A2PA D28L2PA MODELS Electrical Rating – 60 Hz D28A2PB D28L2PB D36A2PA D36L2PA D36A2PB D36L2PB D42A2PA D42L2PA D42A2PB D42L2PB D48A2PA D48L2PA D48A2PB D48L2PB D60A2PA D60L2PA D60A2PB D60L2PB 230/208-1 230/208-3 230/208-1 230/208-3 230/208-1 230/208-3 230/208-1 230/208-3 230/208-1 230/208-3 253-197 253-197 253-197 253-197 253-197 -48VDC -48VDC -48VDC -48VDC -48VDC 40 - 60 VDC 40 - 60 VDC 40 - 60 VDC 40 - 60 VDC 40 - 60 VDC Operating Voltage Range DC Electrical Rating  Operating Voltage Range Compressor Voltage Rated Load Amps Branch Circuit Selection Current Lock Rotor Amps 230/208-1 230/208-3 230/208-1 230/208-3 230/208-1 230/208-3 230/208-1 230/208-3 230/208-1 230/208-3 8.3 / 9.3 5.4 / 6.1 11.6 / 12.9 7.4 / 8.2 15.1 / 16.7 11.5 / 12.6 16.3 / 18.2 10.1 / 11.5 21.0 / 23.8 13.9 / 15.8 12.9 8.4 16.7 10.5 18 13.5 21.8 13.8 26.3 15.8 64 58 79 73 112 88 117 83.1 134 110 Fan Motor Fan Motor – HP Volts Full Load Amps Fan – CFM 1/3 230/208-60-1 2.5 2400 1/3 230/208-60-1 2.5 2900 1/3 230/208-60-1 2.5 3300 1/3 230/208-60-1 2.5 3400 1/3 230/208-60-1 2.5 3400 3/4 -48VDC 14.0 3/4 -48VDC 14.0 3/4 -48VDC 14.0 3/4 -48VDC 14.0 3/4 -48VDC 14.0 550 565 565 630 635 DC Blower Motor Blower Motor – HP Volts  Blower Motor – Full Load Amps Shipping Weight (Lbs.)  Neg. 48VDC positive ground. Outdoor Sound Ratings — Cooling Mode DISTANCE FROM HVAC UNIT dBA 10 Feet 63.5 20 Feet 57.6 30 Feet 56.1 1. Values recorded in Bard Manufacturing Company, Inc. Sound Lab Facility. 2. Actual field results may vary with local conditions that can affect ambient background levels. • • • • Complies with efficiency requirements of ASHRAE/IESNA 90.1-2013. Certified to ANSI/ARI Standard 390-2003 for SPVU (Single Package Vertical Units). Intertek ETL Listed to Standard for Safety Heating and Cooling Equipment ANSI/UL 1995/CSA 22.2 No. 236-05, Fourth Edition. Commercial Product - Not intended for Residential application. Form No. S3521-116 Supersedes S3521-1015 Page 2 of 6 SUMMARY ELECTRICAL RATINGS 1-Stage Compressor Models AC Power Circuit DC Positive Ground Power Circuit Rated Volts, Hertz & Phase Minimum Circuit Ampacity Maximum External Fuse or Ckt. Brkr. D28A2PA05 / D28L2PA05 208/230-60-1 26 30 10 15.6 20 12 D28A2PB06 / D28L2PB06 208/230-60-3 18 20 12 15.6 20 12 D36A2PA05 / D36L2PA05 208/230-60-1 26 40 8 15.6 20 12 D36A2PB06 / D36L2PB06 208/230-60-3 18 25 10 15.6 20 12 D42A2PA05 / D42L2PA05 208/230-60-1 26 40 8 15.6 20 12 D42A2PB06 / D42L2PB06 208/230-60-3 20 25 10 15.6 20 12 D48A2PA05 / D48L2PA05 208/230-60-1 30 50 8 15.6 20 12 D48A2PB06 / D48L2PB06 208/230-60-3 20 30 10 15.6 20 12 D60A2PA05 / D60L2PA05 208/230-60-1 36 60 6 15.6 20 12 D60A2PB06 / D60L2PB06 208/230-60-3 23 35 8 15.6 20 12 MODEL Field Power Wire Size Minimum Circuit Ampacity Maximum External Fuse or Ckt. Breaker Field Power Wire Size These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing. Caution: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a raceway. Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes. IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses & conductor wires in accordance with the National Electrical Code & all local codes. Cooling Application Data - Outdoor Temperature  Model D28A/L D36A/L D42A/L D48A/L D60A/L Return Air (DB/WB) Cooling Capacity  Total Cooling 75/62 Sensible Cooling Total Cooling 80/67 Sensible Cooling Total Cooling 85/72 Sensible Cooling Total Cooling 75/62 Sensible Cooling Total Cooling 80/67 Sensible Cooling Total Cooling 85/72 Sensible Cooling Total Cooling 75/62 Sensible Cooling Total Cooling 80/67 Sensible Cooling Total Cooling 85/72 Sensible Cooling Total Cooling 75/62 Sensible Cooling Total Cooling 80/67 Sensible Cooling Total Cooling 85/72 Sensible Cooling Total Cooling 75/62 Sensible Cooling Total Cooling 80/67 Sensible Cooling Total Cooling 85/72 Sensible Cooling 75°F 80°F 85°F 90°F 95°F 100°F 32,600 26,100 34,800 25,300 41,500 25,900 37,500 27,200 40,000 26,400 47,700 27,100 45,900 33,700 49,000 32,700 58,400 33,500 54,400 42,100 58,100 40,800 69,200 41,800 63,000 47,400 67,200 46,000 80,100 47,100 30,300 25,300 33,000 24,800 38,600 25,200 35,800 27,100 39,000 26,500 45,600 26,900 43,200 33,000 47,000 32,300 55,000 32,800 50,500 40,700 55,000 39,900 64,300 40,500 59,200 45,600 64,500 44,700 75,400 45,400 28,400 24,500 31,500 24,200 36,200 24,300 34,300 26,700 38,100 26,400 43,800 26,500 40,700 32,300 45,200 32,000 51,900 32,200 47,000 39,400 52,200 39,000 60,000 39,200 55,800 43,900 62,000 43,500 71,200 43,700 26,600 23,700 30,000 23,700 33,900 23,600 32,800 26,300 37,100 26,300 41,900 26,100 38,300 31,500 43,300 31,500 48,900 31,300 43,800 38,200 49,500 38,200 55,900 38,000 52,700 42,400 59,500 42,400 67,200 42,100 24,900 23,000 28,600 23,200 31,800 22,800 31,400 25,900 36,000 26,100 40,000 25,600 36,200 30,700 41,500 31,000 46,100 30,400 40,900 37,100 47,000 37,400 52,200 36,700 49,600 40,900 57,000 41,300 63,300 40,500 23,500 22,400 27,400 22,800 30,000 22,100 30,100 25,400 35,000 25,800 38,300 25,000 34,200 30,000 39,800 30,500 43,600 29,500 38,400 36,000 44,700 36,600 48,900 35,400 47,000 39,500 54,700 40,200 59,800 38,900  Below 65°F (18.3C), unit requires a factory or field installed low ambient control.  Return air temperature. 105°F 110°F 115°F 120°F 125°F 22,300 21,300 20,500 19,700 21,900 21,200 20,800 20,300 26,300 25,400 24,600 23,800 22,400 21,900 21,600 21,200 28,400 27,100 25,900 24,800 21,400 20,600 19,900 19,200 28,700 27,400 26,100 24,900 24,800 24,100 23,400 22,600 33,800 32,600 31,400 30,100 25,400 24,900 24,300 23,600 36,500 34,700 33,000 31,300 24,200 23,400 22,400 21,300 32,300 30,500 28,900 27,300 29,200 28,300 27,400 26,500 38,100 36,400 34,700 33,100 29,900 29,200 28,500 27,700 41,100 38,700 36,500 34,400 28,500 27,400 26,300 25,000 36,100 34,100 32,200 30,600 34,900 34,000 33,000 32,100 42,600 40,600 38,700 37,100 35,800 35,100 34,300 33,600 45,900 43,200 40,700 38,600 34,100 32,900 31,600 30,400 44,400 42,000 39,900 37,900 38,100 36,900 35,700 34,600 52,400 50,100 48,000 45,900 39,100 38,100 37,100 36,200 56,500 53,300 50,400 47,700 37,300 35,700 34,200 32,700 Capacity Multiplier Factors % of Rated Airflow -10 Rated Total BTUH 0.975 1.0 Sensible BTUH 0.950 1.0 19,200 19,900 23,300 20,900 24,000 18,500 23,600 21,700 28,700 22,800 29,500 20,200 25,900 25,500 31,500 26,800 32,400 23,700 29,200 31,400 35,600 33,000 36,600 29,200 36,000 33,500 43,800 35,300 45,100 31,200 +10 1.02 1.05 Form No. S3521-116 Supersedes S3521-1015 Page 3 of 6 Indoor Blower Performance MODEL Rated ESP MAX ESP Free Cooling CFM above 40° Free Cooling CFM below 40°  Rated Full Load Cooling CFM  Electric Heat Airflow D28A/D28L 0.15 0.50 1800 800 1050 1800 D36A/D36L 0.15 0.50 1800 800 1100 1800 D42A/D42L 0.20 0.50 1800 950 1250 1800 D48A/D48L 0.20 0.50 1800 1100 1600 1800 D60A/D60L 0.20 0.50 1800 1100 1600 1800  Free Cooling Logic Control derives at this decision point, and switches the indoor motor speed. The damper actuator will then adjust to still yield a 55°F supply air temperature.  On single-stage models, this only occurs if you have a thermostat/controller with "Y2" cooling stage connected. Factory Built-In Electric Heat Tables Model Voltage Phase -A05 240/208 -B06 240/208 KW Amps BTUH 240 208 240 208 240 208 1 5.00 3.75 20.8 18.0 17,065 12,799 3 6.00 4.50 14.4 12.5 20,478 15,359 Bard-Link™ LC2000 Dimensions and Weight 3/4" K.O. TYP. 1 1/2" K.O. TYP. 16 1/8" 6 1/16" 12" Form No. S3521-116 Supersedes S3521-1015 Page 4 of 6 MIS-3650 MODEL SHIPPING WEIGHT (LBS.) LC2000-100 28 Dimensions of Basic Unit for Architectural and Installation Requirements (Nominal) Model Width Depth Height (W) (D) (H) Supply A B Return C B E F G I J K L M N O P Q R S T D28A/L D36A/L 42.075 22.432 84.875 9.88 29.88 15.88 29.88 43.88 13.56 31.66 30.00 32.68 26.94 34.69 32.43 3.37 43.00 23.88 10.00 1.44 16.00 1.88 D42A/L D48A/L 42.075 22.432 93.000 9.88 29.88 15.88 29.88 43.88 13.56 37.00 30.00 40.81 35.06 42.81 40.56 3.37 43.00 31.00 10.00 1.44 16.00 10.00 D60A/L All dimensions are in inches. Dimensional drawings are not to scale. D**A RIGHT HAND UNIT DT HEATER ACCESS PANEL W BUILT IN RAIN HOOD 4° PITCH 2.13 ELECTRIC HEAT A C. BREAKER/ DISCONNECT ACCESS PANEL (LOCKABLE) VENT HOOD DOOR VENTILIATION AIR F E O Side Wall Mounting Brackets (Built In) D SUPPLY AIR OPENING Top Rain Flashing Shipping Location I 7" Condenser Air Outlet S B S H Optional Electrical Entrances C LOW VOLTAGE ELECTRICAL ENTRANCE K J Cond. Air Inlet HIGH VOLTAGE ELECTRICAL ENTRANCE L S RETURN AIR OPENING  VENT HOOD G R M S S P T FRONT VIEW SIDE VIEW DRAIN N Q BACK VIEW BOTTOM INSTALLATION BRACKET BUILT IN RAIN HOOD 4° PITCH W D**L LEFT HAND UNIT DT 2.13 D VENT HOOD DOOR H G Condenser Air Outlet BACK VIEW I C. BREAKER/ DISCONNECT ACCESS PANEL (LOCKABLE) Top Rain Flashing Shipping Location 7" Optional Electrical Entrances J K Cond. Air Inlet SIDE VIEW  Units ship fully assembled with Economizer Vent Hood installed. S B S S RETURN AIR OPENING VENT HOOD  LOW VOLTAGE ELECTRICAL ENTRANCE R SUPPLY AIR OPENING ELECTRIC HEAT C DRAIN E O Side Wall Mounting Brackets (Built In) A VENTILIATION AIR F HEATER ACCESS PANEL S L M HIGH VOLTAGE ELECTRICAL ENTRANCE S P T N Q BACK VIEW BOTTOM INSTALLATION BRACKET MIS-3618 A Form No. S3521-116 Supersedes S3521-1015 Page 5 of 6 Air Conditioning Wall-Mount Model Nomenclature 1-Stage Compressor Models D 36 A 2 P MODEL SERIES CAPACITY | 28 - 2.3 Ton 36 - 3 Ton 42 - 3½ Ton 48 - 4 Ton 60 - 5 Ton A 05 4 X X X KW 05 - 5KW (1 Phase) 06 - 6KW (3 Phase) REVISIONS VOLTS & PHASE A - 230/208-60-1 B - 230/208-60-3 J CONTROL MODULES J = HPS, LPS, CCM, LAC, Alarm Contacts, Start Assist (1-Phase only) COLOR OPTIONS X - Beige 1 - White 4 - Buckeye Gray A - Right Hand L - Left Hand PLC CONTROLLER P C = "J" Module plus Comp. CCH SPECIAL FEATURES FILTER OPTIONS P - 2" Pleated (MERV 8) M - 2" Pleated (MERV 11) -48VDC Free Cooling Unit COIL OPTIONS X - Standard 3 - Phenolic Coated Evaporator and Condenser for coastal or other severe duty environments. Bard-Link™ Controller Systems LC2000-200 Series Lead/Lag Unit Controller TEC-EYE™ Hand-Held Diagnostic Tool Bard P/N 8301-059 LC2000-200 Programmable Logic Controller Communication EMI Filters Bard P/N 8301-055 Remote Temperature/Humidity Sensor with 35' Cable Bard P/N 8403-079 OPTIONAL: Optional VDC Hydrogen Detector Bard P/N 8301-061 Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com Form No. S3521-116 Supersedes S3521-1015 Page 6 of 6 VDC Smoke Detector Bard P/N 8301-060 Remote Temperature Sensor with 35' Cable Bard P/N 8301-058 Due to our continuous product improvement policy, all specifications subject to change without notice. Before purchasing this appliance, read important energy cost and efficiency information available from your retailer. Form No. S3521 January, 2016 Supersedes: S3521-1015