4.LED indicators, Wires, Auxiliary Input and Output Four-door Installation Guide Vision: 1 . 0 . 1
Notes:
Date: Oct. 2010
1.Cautions Please note the following cautions.Mis-operation may lead to personal injury or equipment failure: 1) Do not energize the system before installation is complete; never carry out installation activities when the system is energized.
1)Meaning of LED indicators: LINK indicator(green): always(green) indicates TCP/IP communication is proper; ACT indicator(yellow):its flashing indicates data is in transmitting through TCP/IP communication. TX indicator(yellow):its flashing indicates it is sending data through RS485 communication. RX indicator(green):its flashing indicates it is receiving data through RS485 communication. Auxiliary output indicator(green):always(green) indicates it is in use. Lock indicator(green):always(green) indicates lock is open. POWER indicator(red):always(red) indicates control panel is power on. RUN indicator(green):its flashing indicates the system works normally. CARD indicator(yellow):its flashing indicates card is punched on reader.
2)Recommended use of wires: A Use 2-conducotor power cord B Use 6-conductor wire between wiegand reader and control panal (RVVP 6*0.5mm) (To choose the proper cord according to the interface you connect, such as 6,8,10 cord.) C Use 4-conducotor lock power cord (RVV 4*0.75mm) D Use 2-conducotor switch power cord(RVV 2*0.5mm) 3)The auxiliary input may be connnected to infrared body detectors, alam switches,etc. 4)The auxiliary output may be connected to door bells,alarms,etc.
2) All peripheral devices must be grounded.
SD Card
Ethernet interface
GND 485485+
IN
BUTTON1
TX RX
+12V EXT
PC
PC RS485 interface
(green) flashes.
485+ 485GND
IN GND
AUX4
Advanced Access Control
Connect the system to the power supply.If the system works properly,the POWER indicator(red) is lit constantly and the RUN indicator
GND
AUX3
Description of normal working state:
IN
ACT
5 6 7 8
Dip switch
ON
6) It is recommended to use the power supply in case for control panel, and external power supply for each lock.
1 2 3 4
5) It is recommended that card readers and buttons should be installed at height of 1.4m-1.5m above ground.
AUX2
IN GND
D Auxiliary input1
D Auxiliary input2
D Auxiliary input3
D
Auxiliary input4
{
LAN
clamping tools may be used to avoid unintentional contact of exposed wires to avoid short-circuit or communication failure.
AUX1
IN GND
4) It is strongly recommended that the length of exposed part of any connection cable should not be longer than 4 mm. Professional
{ { { {
LINK
3) It is preferred that all wires run through PVC or galvanized pipes.
Extended RS485 output
TX RX
GND
RUN CARD
D
2# Door Button
B
2# Door wiegand reader
D
3# Door Button
B
3# Door wiegand reader
{
+12V
B
1# Door wiegand reader
{
POWER
+12V
D 1# Door Button
{
Power of control panel
WD1 WD0 GND
READER4
Fixed case
A
IN GND
BUTTON4
Get through the thread hole
2
V+ V-
READER3
1
LOCK POWER
A
Power of lock
BEEP GLED WD1 WD0 GND +12V
BEEP GLED
1
C
Door4
SEN GND NO COM NC
1
C
Door3
SEN GND NO COM NC
LOCK4
Thread hole
IN GND
BUTTON3
3.Get through the thread hole
GND +12V 1
C
Door2
SEN GND NO COM NC
LOCK3
{ { { {
BEEP GLED WD1 WD0
READER2
C
Door1
SEN GND NO COM NC
1
Appearance of case
IN GND
{ { { {
Thread hole
NO COM NC
BUTTON2
Auxiliary output4
BEEP GLED WD1 WD0 GND +12V
{
D
Heat dissipation hole
GND
READER1
Auxiliary output3
NO COM NC
LOCK2
D
LOCK1
Auxiliary output2 Key hole
NO COM NC
AUXOUT4
D
AUXOUT3
Auxiliary output1 Backup battery Power supply Control panel
NO COM NC
AUXOUT2
{ { { {
D
AUXOUT1
2.Components
D
4# Door Button
B
4# Door wiegand reader
5.RS485 address setting, Restore factory setting, Terminal resistance setting
7.Equipment communication
Set RS485 address through DIP switch: The background PC software is able to communicate with the system according to two protocols(RS485 and TCP/IP) for data exchange and remote management. The communication cable should be away from high-voltage lines as far as possible. Do not keep the communication cable in parallel with power cords or bind them together.
1) Place 1-6 on DIP switch are for setting the number of control panel when communicating through RS485, it is adopted for binary coding, and little endian, the address represented by place 1-6 are shown as figurue(5-1). 2) Before setting the address, please keep the system is power off, Jump place 1-6 to desired status, and the address number shall not be the same as another one in the network. For example: to set the device number as 39 (39=1+2+4+32), the corresponding RS485 code is 111001, then Jump place 1,2,3 and 6 at “ON” status. ON
1
2
3
4
5
6
7
1.TCP/IP Communication
8
PC
3) Place 7 is for restoring factory default settings, Jump it for three times within 10 seconds and restart the system, then all information in RAM of control panel will be cleared and the system restores factory default settings.
Switch
4) Place 8 is for setting terminal resistance when communicating through RS485. Jump it at “ON” status, then it is equivalent to have a terminal resistance of 120 ohm between 485+ and 485-. 1# control panel Diagram of places of DIP switch.
LINK
AUX3 AUX4
+12V GND 485485+
EXT
IN
BUTTON1
BUTTON2
READER2
IN GND
BUTTON3
BEEP GLED WD1 WD0 GND +12V
READER3
IN GND
BUTTON4
WD1 WD0 GND
V+ V-
POWER
READER4
BEEP GLED
1
LOCK POWER
+12V
GND +12V
1
LOCK4
SEN GND NO COM NC
BEEP GLED WD1 WD0
1
SEN GND NO COM NC
IN GND
1
SEN GND NO COM NC
LOCK3
READER4
LOCK2
BUTTON4
LOCK1
READER3
NO COM NC SEN GND NO COM NC
GND BEEP GLED WD1 WD0 GND +12V
READER1
NO COM NC
AUXOUT4
BUTTON3
+12V
POWER
NO COM NC
AUXOUT3
READER2
WD1 WD0 GND
V+ V-
NO COM NC
AUXOUT2
BUTTON2
IN GND
AUXOUT1
READER1
BEEP GLED WD1 WD0 GND +12V
BEEP GLED
AUX2
PC
BUTTON1
IN GND
TX RX
GND IN GND
TX RX
GND +12V
1
LOCK POWER
RUN CARD
BEEP GLED WD1 WD0
1
LOCK4
SEN GND NO COM NC
IN GND
1
SEN GND NO COM NC
IN GND
485+ 485GND
AUX1
LAN
5 6 7 8
EXT
GND 485485+
IN
ACT
Advanced Access Control
+12V
BEEP GLED WD1 WD0 GND +12V
1
SEN GND NO COM NC
LOCK3
+12V GND
SEN GND NO COM NC
LOCK2
+12V
NO COM NC
LOCK1
READER4
POWER
NO COM NC
AUXOUT4
BUTTON4
LOCK POWER
BUTTON4
WD1 WD0 GND
NO COM NC
AUXOUT3
READER3
BEEP GLED
V+ V-
BUTTON3
IN GND
AUXOUT2
READER2
BEEP GLED WD1 WD0 GND +12V
AUXOUT1
BUTTON2
IN GND
NO COM NC
ON
1 2 3 4
AUX4
TX RX
AUX3
PC
READER1
GND +12V
1
LOCK4
SEN GND NO COM NC
BEEP GLED WD1 WD0
1
LOCK3
SEN GND NO COM NC
IN GND
BUTTON1
LOCK2
SEN GND NO COM NC
IN GND BEEP GLED WD1 WD0 GND +12V
1
SEN GND NO COM NC
485+ 485GND
GND IN GND
IN GND
AUX2
ON
5 6 7 8
Advanced Access Control
EXT
GND 485485+
IN GND
AUX1
LAN
1 2 3 4
AUX4
+12V
IN
ACT
TX RX
1
NO COM NC
LOCK1
READER3
IN GND
READER4
LOCK POWER
WD1 WD0 GND
POWER
AUXOUT4
BEEP GLED WD1 WD0 GND +12V
BEEP GLED
V+ V-
NO COM NC
BUTTON3
IN GND
NO COM NC
AUXOUT3
READER2
GND +12V
1
LOCK4
SEN GND NO COM NC
BEEP GLED WD1 WD0
1
LOCK3
figure(5-1)
SEN GND NO COM NC
GND
BUTTON2
LOCK2
SEN GND NO COM NC
IN
READER1
LOCK1
SEN GND NO COM NC
GND BEEP GLED WD1 WD0 GND +12V
BUTTON1
AUXOUT4
NO COM NC
1
NO COM NC
NO COM NC
AUXOUT2
GND 485485+
IN
1
NO COM NC
AUXOUT3
Restore factory setting
AUXOUT2
RS485 terminal resistance
NO COM NC
AUXOUT1
TX RX
TX RX AUXOUT1
32 16 8 4 2 1
485+ 485GND
AUX3
PC
8
+12V EXT
7
IN GND
AUX4
6
PC
5
GND
AUX3
5 6 7 8
4
Advanced Access Control
TX RX
IN GND
IN GND
TX RX
AUX2
ON
1 2 3 4
3
IN
ACT
485+ 485GND
GND
SD Card
SD Card IN GND
AUX2
5 6 7 8
LAN
IN GND
2
Advanced Access Control
AUX1
IN GND
1
ON
1 2 3 4
SD Card
IN
ACT
LINK AUX1
LAN
IN GND
LINK
n# control panel LINK
IN GND
ON
2# control panel
SD Card
+12V
+12V
RUN CARD
GND
RUN CARD
GND
2.RS485 Communication
+12V
+12V
RUN CARD
GND
GND 485-
6.Connection of lock 5、门锁连接
485+
485
serial line
Converter
1) Control panel provides lock control output interfaces. For NO lock ,it is open when power is on, and closed when power is off, so COM and
NO interfaces should be used; For NC lock, it is open when power is off, and closed when power is on, so COM and NC interfaces should be
485+
485+
485+
used.
485-
485-
485-
GND
GND
GND
PC
2 3 4 5
1
2) Control panel supports “dry mode” and “wet mode” by setting the jumper, it is “wet mode” when connecting “V+ V-” Input interfaces to supply power for locks, please shorten 2-3 and 4-5
+12V GND 485485+
EXT
IN
BUTTON1
AUXOUT3
NO COM NC
IN GND
BUTTON4
WD1 WD0 GND
POWER
DIP switch
READER4
BEEP GLED
7 8
BEEP GLED WD1 WD0 GND +12V
READER3
LOCK POWER
V+ V-
BUTTON3
READER4
+12V
RUN CARD
READER2
BUTTON4
WD1 WD0 GND
POWER
BUTTON2
LOCK4
SEN GND NO COM NC
IN GND
1
LOCK3
READER3
IN GND
GND +12V
1
LOCK2
SEN GND NO COM NC
BEEP GLED WD1 WD0
1
LOCK1
SEN GND NO COM NC
IN GND
1
AUXOUT4
NO COM NC SEN GND NO COM NC
GND BEEP GLED WD1 WD0 GND +12V
READER1
NO COM NC
ON
AUX4
AUXOUT2
BUTTON3
BEEP GLED WD1 WD0 GND +12V
+12V GND
AUXOUT1
READER2
LOCK POWER
V+ V-
IN GND
BEEP GLED
1
LOCK4
+12V
RUN CARD
NO COM NC
GND +12V
1
LOCK3
READER4
SEN GND NO COM NC
BUTTON2
LOCK2
BUTTON4
1
WD1 WD0 GND
SEN GND NO COM NC
BEEP GLED WD1 WD0
1
LOCK1
SEN GND NO COM NC
IN GND
1
AUXOUT4
READER3
IN GND BEEP GLED
POWER
BUTTON3
BEEP GLED WD1 WD0 GND +12V
TX RX
AUX3
PC
AUXOUT3
READER2
NO COM NC SEN GND NO COM NC
IN GND BEEP GLED WD1 WD0 GND +12V
READER1
AUXOUT2
NO COM NC
485+ 485GND
AUX2
5 6 7 8
Advanced Access Control
GND IN GND
TX RX
BUTTON1
AUXOUT1
NO COM NC
IN
ACT
AUX1
ON
GND 485485+
IN GND
1 2 3 4
TX RX
+12V EXT
PC
BUTTON2
IN GND
+12V
+12V GND
RUN CARD
LED 1
2 3 4 5 Jumper terminal
Notes: 1) Internationally accepted RVSP(shielded twisted-pair) wires should be used for communication to effectively avoid interference. RS485 communication wires should be connected by means of bus cascade connection. 2)Considering stability of communication, it is recommended the length of RS485 bus is less than 600m 3) One RS485 BUS may hold 63 units of control panel, but it is not recommended to connect with more than 32 units access control panels.. 4)When the bus is longer than 300m, to enhance the stability of communication, it is necessary to keep place 8 of DIP switches of the first and the last control panel at “ON” status. As shown in the figure above, place 8 of the DIP switches of units 1# and 8#
+
-
ON
is placed at "ON
“Wet mode” wiring diagram of lock connecting with external power supply.
NO COM NC
GND +12V
+12V GND
485+ 485GND
IN GND LAN
Advanced Access Control
AUX4
IN GND
AUX3
GND
5 6 7 8
READER1
BEEP GLED WD1 WD0
1
LOCK POWER
+12V
RUN CARD
LOCK4
READER4
WD1 WD0 GND
LOCK3
BUTTON4
BEEP GLED
V+ V-
IN GND
BUTTON1
LOCK2
READER3
IN GND
SEN GND NO COM NC
IN GND BEEP GLED WD1 WD0 GND +12V
1
LOCK1
BUTTON3
BEEP GLED WD1 WD0 GND +12V
SEN GND NO COM NC
ACT
SD Card
AUX2
ON
1 2 3 4
GND 485485+
IN
TX RX
1
AUXOUT4
AUXOUT3
READER2
IN GND
+12V GND
AUXOUT2
BUTTON2
GND +12V
POWER
AUXOUT1
READER1
BEEP GLED WD1 WD0
BUTTON1
V+ V-
TX RX
+12V EXT
PC
EXT
+
-
LOCK POWER
Lock power input
IN GND
1
SEN GND NO COM NC
GND
1
NC Lock
GND 485485+
BEEP GLED WD1 WD0 GND +12V
1
SEN GND NO COM NC
LOCK4
FR107
SEN GND NO COM NC
+12V
IN
1
SEN GND NO COM NC
LOCK3
NC
SEN GND NO COM NC
LOCK2
+
Diode
NO COM NC
LOCK1
-
NO COM NC
AUXOUT4
COM
AUXOUT3
GND
AUXOUT2
+
NO COM NC
NO COM NC NO COM NC
TX RX AUXOUT1
SEN
NO COM NC
SEN GND NO COM NC
AUX4
PC
-
-
TX RX
NO COM NC
AUX3
Advanced Access Control 485+ 485GND
NO COM NC
485+ 485GND
AUX4
Advanced Access Control
AUX3
5 6 7 8
IN GND
AUX2
ON
1 2 3 4
GND
AUX2
GND IN GND
5 6 7 8
+
Diode
NO
LOCK
ON
1 2 3 4
LOCK
Enlarged diagram of lock ports
IN
ACT
AUX1
LAN
IN GND
FR107
ACT
IN GND
TX RX
SD Card IN GND
NO Lock
IN
IN GND LAN
LAN
LINK
IN GND
8# control panel LINK
SD Card AUX1
IN GND
AUX1
“wet mode”, please refer to <>.
LINK
SD Card
1 2 3 4 5 6
LINK
3) When the Electrical Lock is connected to the Access Control System, you need to parallel one FR107 diode (equipped in the package) to prevent the self-inductance EMF affecting the system, do not reverse the polarities.
2# control panel
1# control panel
. Equipment factory default setting is dry mode. For setting “dry mode” and
1 2 3 4 5 6 7 8
" status.