ProMinent
Operating Instructions DULCOMETER® D1C Part 2: Adjustment and Operation, Measured Variable Standard Signal
D1C2-mA-001-GB
mA
12.3 % DULCOMETER STOP START
mA
12.3 % DULCOMETER STOP START
Type D
D1C A
Type W
___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ Please enter the identity code of your device here!
Please completely read through operating instructions! · Do not discard! The warranty shall be invalidated by damage caused by operating errors!
Part no. 987528
ProMinent Dosiertechnik GmbH · D-69123 Heidelberg · Germany
BA_DM_147_04_07_GB.p65
1
BA DM 147 04/07 GB
11.04.2007, 11:02 Uhr
1 D1C A
Device Identification / Identity Code DULCOMETER® Controller Series D1C / Version A D W
Type of mounting Control panel installation 96 x 96 mm Wall mounting Operating voltage 0 230 V 50/60 Hz 1 115 V 50/60 Hz 2 200 V 50/60 Hz (only with panel installation) 3 100 V 50/60 Hz (only with panel installation) 4 24 V AC/DC Measured variable S Standard signal 0/4-20 mA Connection of measured variable 1 Terminal standard signal 0/4-20 mA Correction variable 0 None Feed forward control 0 None 1 As standard signal 0/4-20 mA 2 As frequency 0-500 Hz 3 As frequency 0-10 Hz Control input 0 None 1 Pause Signal output 0 None 1 Standard signal 0/4-20 mA measured value 2 Standard signal 0/4-20 mA control variable 4 2 standard signal 0/4-20 mA outputs, free programmable Power control G Alarm and 2 limit value/timer relays M Alarm and 2 solenoid valve relays R Alarm relay and servomotor with feedback Pump control 0 None 2 Two pumps Control characteristics 0 None 1 Proportional control 2 PID control Log output 0 None Language D German E English F French I Italian N Dutch S Spanish P Polish A Swedish B Portuguese U Hungarian G Czech
D1C A
Please enter the identity code of your device here!
2 BA_DM_147_04_07_GB.p65
2
11.04.2007, 11:02 Uhr
2
General User Information Page
1
Device Identification / Identity Code ..................................................................................................... 2
2
General User Information ...................................................................................................................... 3
3
Device Overview / Controls ................................................................................................................... 4
4
Functional Description .......................................................................................................................... 5
5
Display Symbols .................................................................................................................................... 6
6
Operation diagram ................................................................................................................................. 7
7
Restricted Operating Menu ................................................................................................................... 8 Layout .............................................................................................................................................. 8 Description ...................................................................................................................................... 9
8
Complete Operating Menu .................................................................................................................. 12 Overview ........................................................................................................................................ 12 Description .................................................................................................................................... 13
9
Faults/Notes/Troubleshooting ............................................................................................................. 24
General User Information These operating instruction describe the technical data and function of the series DULCOMETER® D1C controller, provide detailed safety information and are divided into clear steps.
IMPORTANT • Please observe the parts of these operating instructions applicable to your particular version! This is indicated in the Section “Device Identification / Identity Code”! • Correct measuring and metering is only possible in the case of impeccable operation of the sensor. The sensor has to be calibrated / checked regularly!
NOTE A form “Documentation of controller settings type D1C” is available under www.prominent.com/documentation_D1C for the purpose of documenting the controller settings.
3 BA_DM_147_04_07_GB.p65
3
11.04.2007, 11:02 Uhr
3
Device Overview / Controls
Display field Measured variable Standard signal (0/4–20 mA) Graphic display
®
mA "Start/stop" button
"Change" button
"Enter" button
"Branch back" button
DULCOMETER®
"Down" button
"Up" button
STOP START
D1C2-mA-002-GB
STOP START
CHANGE button
UP button
To change over within a menu level and to change from one variable to another within a menu point.
To increase a displayed numerical value and to change variables (flashing display)
START/STOP button
BRANCH BACK button
Start/stop of control and metering function.
Back to permanent display or start of relevant setting menu.
ENTER button
DOWN button
To accept, confirm or save a displayed value or status. For alarm acknowledgement.
To decrease a displayed numerical value and to change variables (flashing display).
4 BA_DM_147_04_07_GB.p65
4
11.04.2007, 11:02 Uhr
4
Functional Description NOTE Please refer to the description of the complete operating menu in Section 8 for a detailed description of the individual characteristics of the D1C controller!
4.1
Operating Menu
The DULCOMETER® D1C controller permits settings to be made in two different menus – a “complete” and a “restricted” menu. All values are preset and can be changed in the complete operating menu. The controller is delivered with a restricted operating menu so that the D1C controller can be used effectively in many applications from the very onset. If adaptations prove to be necessary, all relevant parameters can then be accessed by switching over to the complete operating menu (see “General settings”). 4.2
Access Code
Access to the setting menu can be prevented by setting up an access code. The D1C controller is supplied with the access code 5000 which permits free access to the setting menu. The calibration menu remains freely accessible even if access to the setting menu is blocked by the code. 4.3
Control
The D1C can operate as a proportional controller or as a PID controller - depending on the device version (see identity code) and the setting. The controlled variable is recalculated once a second. Control procedures which require rapid correction of setpoint deviations (less than approx. 30 seconds) cannot be processed with this controller. The cycle times must be taken into consideration when activating solenoid valves (pulse length) in the same way as their running times when activating servomotors (3-point). Via the control input pause, the control function (selection of controlled variable) can be switched off. The calculation of the controlled variable starts again after cessation of "pause". 4.4
Feed Forward Control
The D1C controller can process a signal of a feed forward control. Depending on the device version (see identity code) and the setting, this signal can be obtained in any form of a 0–20 mA or 4–20 mA signal or as a digital contact signal with the maximum frequencies 10 Hz or 500 Hz. This signal can be used, for example, for flow-proportional metering (multiplicative effect) or feedforwarddependent basic load metering (additive effect). The result of control variable calculation from the proportional or PID control is multiplied by or added to the feedforward signal. A multiplicative feedforward variable at the level of the set rated value carries over the calculated control variable unchanged into the controlled variable: Controlled variable = Feedforward variable/rated value x calculated control variable During start-up, the zero point has to be checked. The multiplicative feed forward control is not designed for switching off permanently the actuating variable (signal ≈ 0). An additive feedforward variable at the level of the rated value results in maximum controlled variable: Controlled variable (max. 100 %) = Feedforward variable/rated value x max. controlled variable + calculated control variable 4.5
Error Messages
Error messages and information are indicated on the bottom line in the permanent display 1. Errors to be acknowledged (acknowledgement switches off the alarm relay) are indicated by the " ". Errors/notes which still apply after acknowledgement are indicated alternately. Faults which are rectified of their own accord due to changed operating situations are removed from the permanent display without the need for acknowledgement.
5 BA_DM_147_04_07_GB.p65
5
11.04.2007, 11:02 Uhr
5
Display Symbols
The display of the DULCOMETER® D1C controller uses the following symbols: Description
Comment
Limit value transgression Relay 1, upper
Symbol
Symbol left Symbol
Relay 1, lower
left Symbol
Relay 2, upper
right Symbol
Relay 2, lower
right
Metering pump 1 Control off
left
Symbol
Control on
left
Symbol Metering pump 2 Control off
Symbol right Symbol
Control on
right
Solenoid valve 1 Control off
Symbol left
Control on
left
Symbol Solenoid valve 2 Control off
Symbol right Symbol
Control on
right
Servomotor Control, open relay Control, close relay Without control The bar increases from left to right during opening
Position feedback Stop button pressed Manual metering Fault
6 BA_DM_147_04_07_GB.p65
6
11.04.2007, 11:02 Uhr
6
Operation diagram
Permanent display 1
The various menus are selected with the CHANGE button The menu is started with the ENTER button
Permanent display 2
BRANCH BACK to permanent display or to relevant setting menu
Calibration menu
Calibration notes
Various
Access code, correct
Setting menus Access code
Parameter setting D1C2-mA-007-GB
NOTE Access to the setting menus can be barred with the access code! The number and scope of setting menus depends on the device version! If the access code is selected correctly in a setting menu, the following setting menus are also accessible! If within a period of 10 minutes no button is pushed, the unit automatically branches back from the calibrating menu or a setting menu to the permanent display 1.
BRANCH BACK without saving setting
CHANGE from selection to selection Text 1 Selection 1 Text 2 Selection 2
BRANCH BACK to start of setting
Change numbers or settings of selection
Variables flash Text 1 Selection 1 Text 2 Selection 2
ENTER and save setting, continue to next menu D1C2-mA-008-GB
7 BA_DM_147_04_07_GB.p65
7
11.04.2007, 11:02 Uhr
7
Restricted Operating Menu / Layout
The restricted operating menu permits simple operation of the most important parameters. The following overview shows the settings which can be selected:
12.3 % mea val. fd. fwd.: reg. val.: w:
12.3 % 70 % 59 % 50 %
Permanent display 1
Permanent display 2 only with control (w = setpoint)
calibration zero-p.: 4.00 mA slope: 100 %
calibration meas. value 14.5 %
limits setting ?
limit 2 30.0 % limit 1 26.0 %
Positive values of setting variable: Negative values of setting variable:
calibration zero-p.: 4.00 mA slope: 100 %
Number and scope of setting menus depends on the device. Access to setting menus con be blocked with access code.
upper lower
Only with control control regulated value: positive negative
control settings ?
Proportional control
For normal control
Setting in complete operating menu
control normal current regulat. 30 % value:
Control with dead zone
or control with dead zone current regulat. value: 30 %
or
general setting information
ctrl. parameter 10 % xp =
setpoint 50 %
setpoint 2 upper 30 % setpoint 1 lower 28 %
PID control ctrl. parameter 10 % xp = 0s Ti = Td = 0s
Manual control
control manual current regulat. value: 30 %
manual dosing 15 % regulated range
ident-code: D1CA DxSxxxxxxxxxx software version D1C-B1 FW-5.00
alarm relay active
access c.: 5000 operating menu: = english = restricted
D1C2-mA-010-GB
8 BA_DM_147_04_07_GB.p65
8
11.04.2007, 11:02 Uhr
Restricted Operating Menu / Description Permanent display 1
12.3 % mea val. fd. fwd.: reg. val.: w:
12.3 % 70 % 59 % 50 %
Permanent display 2 only with control (w = setpoint)
Positive values of setting variable: Negative values of setting variable:
D1C2-mA-011-GB
Calibration of the standard signal (zero-point calibration) The D1C sets the control output to “0” during the calibration procedure. Exception: When a basic load or a manual control variable is set the corresponding parameter is retained during calibration. The standard signals outputs mA (measured value) are frozen. The measured value frozen at the start of calibration is the proposed value. This value is adjustable (arrow buttons!). Calibration is possible only when the value is ≥2 % of the measuring range. Following successful calibration, all troubleshooting procedures relating to the measured value are restarted. IMPORTANT The measuring range of the sensor must agree with the set measuring range. The unit of measure must be set prior to calibration (see Page 14)!
Access to all setting menus can be blocked with an access code ! calibration zero-p.: 4.00 mA slope: 100 %
calibration meas. value 14.5 %
calibration zero-p.: 4.00 mA slope: 100 %
Permanent display 1
D1C2-mA-029-GB
Possible values Initial value
Increment
Lower value
Upper value
Remarks
Measured value
0.1 % 0.01 mA 0.01 m 0.1 % 0.001 bar 0.001 bar 0.01 bar 0.1 bar 0.1 psi 1 psi 0.001 m3/h 0.1 m3/h 1 m3/h 0.1 gal/h 1 gal/h 1 ppm 0.1 %RH 0.01 mA 0.1 %
-5 % -1.00 mA 0m 0% 0 bar 0 bar 0 bar 0 bar 0 psi 0 psi 0 m3/h 0 m3/h 0 m3/h 0 gal/h 0 gal/h 0 ppm 0 %RH 0/4 mA 0%
105 % 21.00 mA 31.50 m 105 % 1.050 bar 5.250 bar 10.50 bar 105 bar 105 psi 1050 psi 9.999 m3/h 105 m3/h 1050 m3/h 105 gal/h 1050 gal/h 1050 ppm 105 %RH 21 mA 105 %
30.00 m 100 % 1.000 bar 5.000 bar 10.00 bar 100.0 bar 100 psi 1000 psi 9.999 m3/h 100 m3/h 1000 m3/h 100 gal/h 1000 gal/h 1000 ppm 100 %RH 20 mA 100 % 9
BA_DM_147_04_07_GB.p65
9
11.04.2007, 11:02 Uhr
Restricted Operating Menu / Description Limit values
Access to all setting menus can be blocked with an access code !
limit 2 30.0 % limit 1 26.0 %
limits setting ?
upper lower
D1C2-mA-014-GB
Possible values Initial value
Increment
Type of limit transgression Limit 1: Limit 2:
lower upper
upper lower off*
Limit value Limit 1: Limit 2: Limit 1: Limit 2:
0% 100 % 0.00 mA 20.00 mA
0.1 % 0.1 % 0.01 mA 0.01 mA
Lower value
Upper value
Remarks Limit transgression when exceeding or dropping below value *only with limit value relay
-5 % -5 % -1.00 mA -1.00 mA
105 % 105 % 21 mA 21 mA
Measuring unit % Measuring unit mA
Control
Access to all setting menus can be blocked with an access code ! Note:
The controlled variable is recalculated every second. Only suitable for processes with time constants greater than 30 s ! Only with control control regulated value: positive negative
control settings ?
Setting in complete operating menu
control normal current regulat. -30 % value:
or
Positive values of setting variable: Negative values of setting variable: Proportional control
For normal control
ctrl. parameter 10 % xp =
setpoint 50 %
Control with dead zone
control with dead zone current regulat. value: -30 %
setpoint 2 upper 30 % setpoint 1 lower 28 %
or
Control manual
control manual current regulat. value: -30 %
manual dosing 15 % regulated range
PID control ctrl. parameter 10 % xp = 0s Ti = Td = 0s
D1C2-mA-015-GB
10 BA_DM_147_04_07_GB.p65
10
11.04.2007, 11:02 Uhr
Restricted Operating Menu / Description Possible values Initial value Setpoint
Control parameter xp Control parameter Ti Control parameter Td Manual metering
Increment
Lower value
Upper value
Remarks
50 % 10.00 mA
0.1 % 0.01 mA
-5.0 % -1.00 mA
105 % 21 mA
Measuring unit: % Measuring unit: mA 2 setpoints necessary for control with dead zone. Setpoint 1 ≤ setpoint 2
10 % off off 0%
1% 1s 1s 1%
1% 1s 1s -100 %
500 % 9999 s 2500 s +100 %
xp referred to measuring range Function off = 0 s Function off = 0 s
Abbreviation for control variables: xp = 100 %/Kp (inverse proportional coefficient) Ti = I controller integration time [s] Td = D controller differential time [s] General settings
Access to all setting menus can be blocked with an access code ! ident-code: D1CA DxSxxxxxxxxxx software version D1C-B1 FW-5.00
general setting information
access c.: 5000 operating menu: = english = restricted
alarm relay active
D1C2-mA-016-GB
Possible values
Alarm relay Access code Language Operating menu
Initial value
Increment
active
active not active
5000
1
as per identity code
as per identity code
restricted
restricted complete
Lower value
Upper value
1
9999
Remarks
Access Code Access to the setting menu can be prevented by setting up an access code. The DULCOMETER® D1C controller is supplied with the access code 5000 which permits free access to the setting menu. The calibration menu remains freely accessible even when access to the setting menu is blocked by the code.
11 BA_DM_147_04_07_GB.p65
11
11.04.2007, 11:02 Uhr
8
Complete Operating Menu / Overview
All parameters of the controller can be set in the complete operating menu (access see previous page). The following overview shows the settings which can be selected:
12.3 % mea val. fd. fwd.: reg. val.: w:
12.3 % 70 % 59 % 50 %
Permanent display 1
Permanent display 2 only with control (w = setpoint)
calibration zero-p.: 4.00 mA slope: 100 %
Number and scope of setting menus depends on the device. Access to setting menus can be blocked with access code.
measuring unit setting ?
measured value setting ?
pumps setting ?
Only with pumps
relays setting ?
Only with limit relay, solenoid valve relay or servomotor
limits setting ?
feed forward ctrl. setting ?
Only with feed forward control
signal output 1 mA setting ?
Only with standard signal output
Only with 2 standard signal outputs
servomotor setting ?
Only with servomotor
signal output 2 mA setting ?
control setting ?
Only with control
general setting information
D1C2-mA-017-GB
12 BA_DM_147_04_07_GB.p65
12
11.04.2007, 11:02 Uhr
Complete Operating Menu / Description Permanent display 1
12.3 % mea val. fd. fwd.: reg. val.: w:
Permanent display 2 only with control (w = setpoint)
12.3 % 70 % 59 % 50 %
Positive values of setting variable: Negative values of setting variable:
D1C2-mA-018-GB
Calibration of the standard signal (two-point calibration) The D1C sets the control output to “0” during the calibration procedure. Exception: When a basic load or a manual control variable is set the corresponding parameter is retained during calibration. The standard signals outputs mA (measured value) are frozen. The measured value frozen at the start of calibration is the proposed value. This value is adjustable (arrow buttons!). Calibration is possible only when the value is ≥2 % of the measuring range. Following successful calibration, all troubleshooting procedures relating to the measured value are restarted. IMPORTANT The measuring range of the sensor must agree with the set measuring range. The unit of measure must be set prior to calibration (see Page 14)!
calibration zero-pt.: 4.00 mA slope: 100 %
calibration meas. value 1 value accept ? 14.5 %
calibration value1: 14.5 % value2:
calibration meas. value 2 value accept ? 76.6 %
calibration value1: 14.5 % value2: 76.6 %
calibration zero-pt.: 4.00 mA slope: 100 %
Permanent display 1
D1C2-mA-030-GB
Possible values Initial value Measured value*
Increment
Lower value
Upper value
Remarks
0.1 % 0.01 mA
-5 % -1.00 mA
105 % 21.00 mA
*for possible measuring values see page 9
Error message
Condition
Effect
Value distance too small
∆ value > 5.0 % ∆ value > 1.00 mA
Measured value deleted Repeat calibration of measuring point 13
BA_DM_147_04_07_GB.p65
13
11.04.2007, 11:02 Uhr
Complete Operating Menu / Description Measuring variable
Access to all setting menus can be blocked with an access code ! measuring unit setting ?
measuring value measuring signal measuring unit: 0...100 %
Permanent display 1
D1C2-mA-019-GB
IMPORTANT The sensor must be recalibrated and the settings in all the menus checked after changing the assigned range! Possible values Initial value Measuring variable
Measuring unit
Increment
Measurement signal
Level Pressure Water flow rate Turbidity Humidity Measurement signal
0 - 100 %
0 - 30 m 0 - 100 % 0 - 1.000 bar 0 - 5.000 bar 0 - 10.00 bar 0 - 100.0 bar 0 - 100.0 psi 0 - 1000 psi 0 - 9.999 m3/h 0 - 100.0 m3/h 0 - 1000 m3/h 0 - 100.0 gal/h 0 - 1000 gal/h 0 - 1000 ppm 0 - 100.0 %RH 0/4 - 20 mA 0 - 100 %
Lower value
Upper value
Remarks
Level Pressure
Water flow rate
Turbidity Humidity Measurement signal
IMPORTANT The setpoint and limit values are changed over to the corresponding initial values when the measuring range is changed! Check the settings in all menus!
14 BA_DM_147_04_07_GB.p65
14
11.04.2007, 11:02 Uhr
Complete Operating Menu / Description Measured value
Access to all setting menus can be blocked with an access code ! Standard signal input mA measured value range adjustment 4 mA = 0.0 %
measured value setting ?
measured value range adjustment 20 mA = 100.0 %
measured value checkout time measured value off D1C2-mA-020-GB
IMPORTANT When changing the range adjustment, the sensor must be newly calibrated and the adjustments in all menus have to be checked! Possible values Increment
Initial value Standard signal input lower signal limit Allocated measuring range*
Checkout time
Lower value
Upper value
Remarks
0.1 % 0.01 mA
-5 % -1.00 mA
105 % 21.00 mA
1s
1s
9999 s
Measurement signal *for other measuring ranges see page 9 Constant measurement signal results in message and alarm. Function off = 0 s
4 mA
0 mA 4 mA
0-100.0 % 0-20.00 mA off
Measured value checkout time IMPORTANT This function may not be activated for applications in which it can be assumed that the measured value will not change. This function tests whether the measured value changes from that of the sensor (at the measured value input) within the “Measured value checkout time”. It is assumed that it will do so for an intact sensor. If the measuring value does not change during this checkout time, the DULCOMETER® D1C sets the control variable to “0” and the alarm relay drops out. The LCD display shows e.g. the message “limit 1/2”. Pumps
Access to all setting menus can be blocked with an access code ! Only with pumps for control pumps setting ?
control
dosing pump max. pump1: 180 pump2: 180 pulse/minute
pump1 pump2
D1C2-mA-022-GB
Possible values
Max. stroke/minute of pumps 1 and 2
Initial value
Increment
Lower value
Upper value
Remarks
180
1
1
500
off = 0 strokes/min
15 BA_DM_147_04_07_GB.p65
15
11.04.2007, 11:02 Uhr
Complete Operating Menu / Description Relay for power control
Access to all setting menus can be blocked with an access code ! Only with limit relay, solenoid valve relay or servomotor relay adjustment SV1 relay1: relay2: SV2
relays setting ?
solenoid valve 1
solenoid valve 2
10 s period min. time 1 s
10 s period min. time 1 s
D1C2-mA-023-GB
with timer relay adjustment relay 1: timer relay 2: timer
relays setting ?
timing 1 relay 1 period t on:
timing 2 relay 2 period t on:
1h 1 min
1h 1 min
D1C2-mA-033-GB
Possible values Initial value Relay adjustment Relay 1
Increment
as per identity code
Period min. time
10 s 1s
Solenoid valve 1 Limit value 1* Actuator 1 Timer 1 Servomotor off Solenoid valve 2 Limit value 2* Actuator 2 Timer 2 off 1s 1s
Period t on
off 1 min
1h 1 min
Relay 2
Lower value
Upper value
Remarks * At “limit value”, the relays remain active even in the case of fault.
Only with servomotor
10 s 1s
9999 s period/2
for solenoid valve for solenoid valve Set here the smallest permitted operating factor of the connected device.
1 h/off 1 min
240 h 60 min
for timer for timer
NOTE The limit value relay can be defined in such a way as to respond as a control element, i.e. if a limit value relay closes a circuit, it opens when a pause contact is activated and/or for a subsequent delay period td (if td is set to > 0 min in “General settings”). Cycle Timer relay
t on
on off t
16 BA_DM_147_04_07_GB.p65
16
11.04.2007, 11:02 Uhr
Complete Operating Menu / Description IMPORTANT The timer will reset in the event of a power failure. At the end of the (timer) cycle time the DULCOMETER® D1C closes the assigned relay for the duration of “t on” (timer). “Pause” interrupts the timer. When the clock is shown in the LC display the timer can be reset to the start of the cycle at precisely this point using the enter button. The % figure in the LC display indicates the progress of the current cycle. Timer relays may be used, e.g. for shock metering or sensor cleaning. Cycle ton
Solenoid valve on
min. time
t
Control variable: 80 % ton = 0.80 Cycle
t
Control variable: 50 % ton = 0.50 Cycle
off
Cycle ton on off
The switching time of the DULCOMETER® D1C (solenoid valve) depends on the actuating variable and the “min. time” (smallest permitted operating factor of the connected device).The actuating variable determines the ratio ton/cycle and thus the switching times (see fig. above). The “min. time” influences the switching times in two situations: a) theoretical switching time < min. time: Cycle
Cycle
Cycle
min. time on
theoretical
off
Cycle
Cycle
t
Cycle min. time
on
actual
off t ®
The DULCOMETER D1C does not switch for a certain number of cycles until the sum of the theoretical switching times exceeds the “min. time”. Then the DULCOMETER® D1C switches for the duration of this total time. b) theoretical switching time > (cycle - min. time) Cycle
Cycle
and
calculated switching time < cycle
Cycle
min. time on
theoretical
off
Cycle
Cycle
Cycle
t
min. time on
actual
off t
The DULCOMETER® D1C does not deactivate for a certain number of cycles until the differences between cycle and theoretical switching time exceed the “min. time”. 17 BA_DM_147_04_07_GB.p65
17
11.04.2007, 11:02 Uhr
Complete Operating Menu / Description Limit values
Access to all setting menus can be blocked with an access code ! limit 2 30 % limit 1 28 %
limits setting?
upper lower
relay 1: LV1 - active closed ∆t on: 0s ∆t off: 0s
limits fault hyst.: 0.2 % ∆t on: off control: on relay 2: LV2 - active closed ∆t on: 0s ∆t off: 0s D1C2-mA-034-GB
Possible values Initial value
Increment
lower upper
upper lower off*
Limit 1: Limit 2:
0% 100 %
0.1 % 0.1 %
-5 % -5 %
105 % 105 %
Measuring unit percent
Limit 1: Limit 2:
0 mA 20 mA
0.01 mA 0.01 mA
-1.00 mA -1.00 mA
21 mA 21 mA
Measuring unit milliampere
0.2 % 0.04 mA
0.1 % 0.01 mA
0.1 % 0.02 mA
105 % 21.00 mA
Active in “cancellation of limit transgression” direction
Checkout time limits
off
1s
1s
9999 s
Results in message and alarm. Off = 0 s: Function switched off, no message, no alarm
Control
on
on off
active closed
active closed active open
Type of limit transgression Limit 1: Limit 2: Limit value
Hysteresis limits
Switching direction Limit value 1 Limit value 2
Lower value
Upper value
Remarks Limit transgression when exceeding or dropping below value *only with limit value relay
Acts as N/O Acts as N/C
Switch-on delay ∆t on
0s
1s
0s
9999 s
Switch-off delay ∆t off
0s
1s
0s
9999 s
If the limit transgression is applied longer than the “delay time limit values”, an error message is triggered and the alarm relay drops out; the control procedure stops if “control” is additionally set to “off”.
18 BA_DM_147_04_07_GB.p65
18
11.04.2007, 11:02 Uhr
Complete Operating Menu / Description Servomotor The operating range is defined by the total resistance range of the feedback potentiometer. The maximum limit of the range actually used is set by defining the control range. IMPORTANT • Activation of the servomotor must be carried out with the same meticulous care as taken when calibrating a measuring sensor. • To ensure correct operation, the activation time of the actuator used should not be less than 25 seconds for the control range from 0…100 %!
Access to all setting menus can be blocked with an access code ! Only with servomotor servomotor setting current position:
servomotor setting ?
servomotor open ?
servomotor open please wait ! servomotor opened ! value take over ?
servomotor close ?
servomotor close please wait ! servomotor closed ! value take over ?
servomotor OK current position:
dosing: control range: 100 % 0 % to operating range
= automatic timing D1C2-mA-025-GB
Possible values
Servomotor
Initial value
Increment
Setting
Setting ok off
100 %
1%
Lower value
Upper value
Remarks
10 %
100 %
in % of operating range
Control direction Control range
NOTE • When the wide bar is as right as it will go, the stroke adjustment motor is fully open. • The permanent display shows to what degree the motor has opened in % (the greater the percentage, the more open the servomotor.) 19 BA_DM_147_04_07_GB.p65
19
11.04.2007, 11:02 Uhr
Complete Operating Menu / Description Control
Access to all setting menus can be blocked with an access code ! Note:
The controlled variable is recalculated every second. Only suitable for processes with time constants greater than 30 s ! Only with control control regulated value: positive negative
control settings ?
control normal current regulat. value: 30 %
Positive values of setting variable: Negative values of setting variable: Proportional control
For normal control
ctrl. parameter 10 % xp =
setpoint 50 %
Control with dead zone
PID control
setpoint 2 upper 30 % Setpoint 1 lower 28 %
ctrl. parameter 10 % xp = 0s Ti = Td = 0s
Control manual
add. basic load 10 % regulated range
manual dosing 15 % regulated range
D1C2-mA-026-GB
Possible values Initial value
Increment
Control
normal
normal with dead zone manual
Setpoint
50 % 10.00 mA
0.1 % 0.01 mA
-5.0 % -1.00 mA
105 % 21 mA
10 % off off 0% 0%
1% 1s 1s 1% 1%
1% 1s 1s -100 % -100 %
500 % 9999 s 2500 s +100 % +100 %
Control parameter xp Control parameter Ti Control parameter Td Additional load Manual metering
Lower value
Upper value
Remarks When controlling with dead zone, the feed forward control is not used for measured values within the dead zone. Measuring unit: % Measuring unit: mA 2 setpoints necessary for control with dead zone. Setpoint 1 ≤ setpoint 2 xp referred to measuring range Function off = 0 s Function off = 0 s
Abbreviation for control variables: xp = 100 %/Kp (inverse proportional coefficient) Ti = I controller integration time [s] Td = D controller differential time [s]
20 BA_DM_147_04_07_GB.p65
20
11.04.2007, 11:02 Uhr
Complete Operating Menu / Description Feed forward control feed forward ctrl.
feed forward ctrl. setting ?
Hz/mA 10 Hz
feed forward ctrl. disturb. variable additive
feed forward ctrl. rated value 10.00 Hz
feed forward ctrl. max. additive regulated value 100 % D1C2-mA-031-GB
Possible values
Feed forward control (Flow)
Initial value
Increment
as per identity code Standard signal 4–20 mA
None 10 Hz 500 Hz 0…20 mA 4…20 mA
10 Hz 500 Hz 20 mA
0.01 Hz 1 Hz 0.1 mA
multiplicative
multiplicative additive
100 %
1%
Feed forward control rated value Feed forward control feed forward control effect Feed forward control additive regulated value
Lower value
Upper value
Remarks Signal processing: Signal <0.02 Hz = No flow Signal <0.2 Hz = No flow Signal <0.2 mA = No flow Signal <4.2 mA = No flow
0.1 Hz 5 Hz 0.4 mA
10 Hz 500 Hz 20 mA
Depended on signal type. Maximum limitation of range used.
-500%
+500%
only with additive feed forward control
Standard signal output 1
Access to all setting menus can be blocked with an access code ! Control with standard signal Only with standard signal output signal output 1 mA setting ?
signal output 1 mA measured value 0…20 mA
control regulated value: positive negative
signal output 1 regulated value 0% 0 mA = 20 mA = 100%
signal output 1 measured value 0% 0 mA = 20 mA = 100 % D1C2-mA-027-GB
21 BA_DM_147_04_07_GB.p65
21
11.04.2007, 11:02 Uhr
Complete Operating Menu / Description Standard signal output 2
Access to all setting menus can be blocked with an access code ! Control with standard signal Only with 2 standard signal outputs signal output 2 mA setting ?
signal output 2 mA measured value 0…20 mA
signal output 2 regulated value 0% 0 mA = 20 mA = 100%
control regulated value: positive negative signal output 2 measured value 0% 0 mA = 20 mA = 100 %
D1C2-mA-032-GB
Possible values
Variable allocation Output range
Initial value
Increment
as per identity code
Measured value Controlled variable
0…20 mA
0…20 mA 4…20 mA 3.6/4-20 mA
Lower value
Upper value
Remarks If control applicable
Reduction to 3.6 mA when alarm relay switches (not limit value violation)
Range measured value
0-100 % 0-20.00 mA
0,1 % 0,01 mA
-5 % -1,00 mA
105 % 21,00 mA
Minimum range 1 % of measured value
Range controlled variable
0 %…+100 %
1%
-100 %
+100 %
Minimum range 1 %
General setting
Access to all setting menus can be blocked with an access code ! general setting information
ident-code: D1CA DxSxxxxxxxxxx software version D1C-B1 FW-5.00
alarm relay active
pause normal - active closed - alarm off - td: 0 min access c.: 5000 operating menu: - english - complete D1C2-mA-028-GB
22 BA_DM_147_04_07_GB.p65
22
11.04.2007, 11:02 Uhr
Complete Operating Menu / Description Possible values Initial value
Increment
Alarm relay
active
active not active
Pause
normal
normal hold
active closed
active closed active open
Reacts as a make contact Reacts as a break contact
off
off on
Alarm relay can be triggered by pause contact
td
0 min
1 min
0 min
60 min
Access code
5000
1
1
9999
as per identity code
as per identity code
complete
restricted complete
Control input pause Alarm pause
Language Operating menu
Lower value
Upper value
Remarks
Normal pause If the pause switch is off, the DULCOMETER® D1C sets the operating outputs to “0” for as long as the pause switch is off or for a set time delay td (if td is set to > 0 min). While the pause switch is off, the D1C establishes the P-proportion in the background. With PID-control (identity code characteristics “control characteristic” = 2): the I-proportion is stored when the pause is switched off (I-proportion then usually only present if Ti > 0 has been selected in the “Control setting?” setting menu). Exception: the standard signal outputs mA for the measured value or correction value are not affected by the pause. After pause is activated, the operating outputs remain at “0” for the length of the time delay td. The time delay td must be set up in such a way that in this time e.g. sample water (process-specific current concentration) flows to the sensor. With PID-control (identity code characteristics “control characteristic” = 2): The control variable output resulting from the pause and the expiry of the time delay td is reconciled jointly with the current P-component and (if Ti is set > 0) with the stored I-component. Pause hold If the pause switch is off, the DULCOMETER® D1C freezes the operating output at the most recent value for as long as the pause switch is off or for a set time delay td (if td is set to > 0 min). Whilst the pause switch is off, the D1C establishes the P-proportion in the background. With PID-control (identity code characteristics “control characteristic” = 2): Even the mA standard signal outputs for measured value or correction value are frozen. After pause is activated, the operating outputs remain frozen for the length of the time delay td. The time delay td must be set up in such a way that in this time e.g. sample water (process-specific current concentration) flows to the sensor. With PID-control (identity code characteristics “control characteristic” = 2): The control variable output resulting from the pause and the expiry of the time delay td is reconciled jointly with the current P-proportion and (if Ti is set > 0) with the newly established I-proportion. Access Code Access to the setting menu can be prevented by setting up an access code. The DULCOMETER® D1C controller is supplied with the access code 5000 which permits free access to the setting menu. The calibration menu remains freely accessible even when access to the setting menu is blocked by the code. 23 BA_DM_147_04_07_GB.p65
23
11.04.2007, 11:02 Uhr
Faults / Notes / Troubleshooting 9
Stop
Yes
Alarm with acknowledgement
Function detachable
Remarks
Check function of sensor, exceed checkout time
Remedy
Yes Yes
–
24
Effect on metering on control
Fault text
Basic load
Symbol
Fault
Check probe
Check sensor, transducer and cable connection
Measured value Checkout time measured value exceeded
Signal < 3.8 ±0.2 mA or >23 ±0.2 mA Value last valid is used
Define cause, reset values if necessary
Check sensor, transducer and cable connection
Function detachable
Call in service
Check servomotor
Signal <3.0 ±0.2 mA or >23 ±0.2 mA
Servomotor closes
Yes
Yes
Electronic data defective
Yes
Yes
Stop
continue continue continue
Stop
Stop
Relay drops out
–
Remedy
Yes
Basic load
stops continue continue
Stop or Basic load
Stop
No/Yes*
No
Check connection of relay, potentiometer Adjust the operation region of the servomotor correctly
No further fault check
Remarks
input 3 mA input > 23 mA
Symbol
Stop
PI-part frozen
Stop
Effect on metering on control Stop
Stop
Alarm with acknowledgement
Signal exceeded/drops below value
System defect.
Servomot. defect.
Feed forward control feedfwd input <4 mA Signal drops below value multiplicative additive feedfwd input >23 mA Signal exceeded Limit 1 Limit transgression Limit 2 after checkout time limits Control “on” Control “off” Servomotor Position not reached
Stop
Pause Pause/Hold
Note text
Electronics error
Operation Pause contact
Stop button
Without correct adjustment the last valid values are still used
11.04.2007, 11:02 Uhr
24
BA_DM_147_04_07_GB.p65
During servomotor setting Direction check Position feed back wrong Upper position <40 % max. value Final value too small Final value too big Lower position >30 % range *depending on whether "Alarm on" or "Alarm off" set in "General settings"
©1996 ProMinent Dosiertechnik GmbH · D-69123 Heidelberg Operating Instructions DULCOMETER® D1C, Part 2/Standard Signal Subject to modifications · Printed in the F.R.Germany ProMinent Dosiertechnik GmbH · Im Schuhmachergewann 5-11 · D-69123 Heidelberg Phone +49 6221 842-0 · Fax +49 6221 842-419
[email protected] · www.prominent.com