Marvair Dc Free Air Hvac Unit Free Cooling And Coollinks™ Controller

   EMBED


Share

Transcript

Marvair DC Free Air HVAC Unit with 48 VDC Evaporator Fan Motor, 100% Free Cooling and CoolLinks™ Controller 8.8 to 17.7 kW (30,200 to 60,350 BTUH) Models ASDCA36-42-48-60-72 General Description The Marvair® DC Free Air HVAC units are designed to cool telecommunications shelters where the high internal heat load requires year round cooling-even when ambient temperatures are below 60°F (15°C). To provide cooling during a wide range of ambient conditions, the ASDCA air conditioners have the necessary controls and components for year round cooling. The units use the non-ozone depleting R-410A refrigerant. DC power provides emergency cooling/ventilation Should there be loss of power to the site, the Marvair DC Free Air unit will continue to cool/ventilate the site by utilizing the shelter’s DC power to introduce outside air into the shelter for free cooling. The DC Free Air unit will continue to ventilate the site and extend the run time of the equipment until battery power is exhausted or, at the minimum, owner specified pull down of battery drain. ASDCA36 The ASDCA models operate on both AC and DC power. The compressor, condenser fan motor and electric heat operate on AC power, but the evaporator motors, the 100% free cooling economizer damper and the internal control board operate on DC power – an inverter is not required. Since these key components are all powered by 48 VDC – the same 48 VDC power used by the shelter’s radios- they are always operational. The 48 VDC power supply connects to an internal DC breaker. From this breaker, power is supplied to the DC indoor blower and control board. Free Cooling with the Marvair 100% Full Flow Economizer When the outside air is cool and dry, the economizer damper opens and draws in filtered, outside air to cool the shelter. The Marvair 100% full flow economizer means the same CFM of outside air is brought into the shelter as the rated air flow of the unit. The innovative design of the full flow economizer assembly also allows outside air to exit the building – pressure relief- when the full flow economizer is operating. This design eliminates the need for additional, costly penetrations in the shelter. Free cooling provides temperature control, energy savings, and increased reliability by decreasing the operating hours of the compressor and the condenser fan. To insure proper operation and optimum performance, all economizers are non-removable, factory installed and tested. Safety Listed The ASDCA air conditioners are built to UL standard 1995, 3rd edition and CAN/CSA C.22.2, No. 236, 3rd edition. For energy efficiency and performance, the units are tested and rated in accordance to the ANSI/AHRI (Air-Conditioning Heating and Refrigeration Institute Standard 390-2003 (Single Package Vertical Units). All units meet or exceed the efficiency requirements of ANSI/ASHRAE/IESNA 90.1.2007. The ASDCA units are commercial units and not intended for residential use. 50Hz. units are for export only. 1 ComPac ASDCA 50 Hz PDS 2/2014 New PLC controller The Siemens PLC-based CoolLinks controller sequences the operation of the two Marvair ComPac II units to ensure the most energy-efficient conditioning of the shelter space and the most balanced use of the conditioning equipment. The CoolLinks system determines the need to cool or heat the shelter based on an indoor temperature sensor and outside temperature/humidity sensor connected directly to the controller. When cooling or heating is required, the controller selects the unit that was not running in the previous cooling/heating cycle. This lead/lag operation ensures that each unit receives equal runtime and therefore extends the operating life of the units. In the event that one of the units is unavailable, for example, scheduled maintenance, the system will automatically select the active unit. Similarly, if the internal shelter temperature continues to rise/fall, the system will run both units. For cooling requests, the CoolLinks controller first examines the external shelter conditions to establish whether DC Free Cooling is possible. If acceptable, the 100% full flow economizer damper on the lead unit is opened to 100%. The damper then modulates its position, regulated by the controller, to cool the shelter to the target set point. During extreme cold outdoor temperatures this prevents “shocking” the equipment in the shelter. For units installed in corrosive environments, e.g., near the ocean, the economizer cooling function can be disabled to prevent the entry of corrosive air into the shelter. If DC Free Cooling is active on one unit and the internal temperature continues to rise, DC Free Cooling will then be activated on the second unit. Should the temperature continue to rise, the DC Free Cooling will be disabled on both units, both economizer dampers will be closed, and mechanical cooling activated on the lead unit. The control scheme allows the CoolLinks controller to make as efficient use of the external air as possible to minimize HVAC power consumption. The CoolLinks controller communicates with the Marvair air conditioners over Ethernet. Should communications between the controller and one of the units fail, the unit will continue to run in stand-alone mode and cool to a mixed-air set point of 55°F (12.8°C). Whenever communications are restored, the CoolLinks controller will assume control of the air conditioner. An Ethernet connection is also provided for a SNMP interface through which the Network Operations Center can receive traps (alarms), monitor/change cooling and heating set points, and monitor HVAC unit and system operational parameters. Air Conditioner Alarms and Lockouts Each air conditioner is monitored over Ethernet and if a problem is detected, an alarm is generated. The alarm is displayed on the CoolLinks PLC in the shelter and sent via SNMP trap to the network operations center. • High Pressure Alarm – the refrigerant pressure has exceeded the set point pressure once in a cooling cycle. The air conditioner will continue to operate, but notification is sent that there is a high pressure fault. • High Pressure Lockout Alarm - the refrigerant pressure has exceeded the set point pressure twice in a cooling cycle. The air conditioner will shut down and notification will be sent that there is a high pressure lockout. • Low Pressure Alarm – the refrigerant pressure has dropped below the set point pressure once in a cooling cycle. The air conditioner will continue to operate, but notification is sent that there is a low pressure fault. • Low Pressure Lockout Alarm - the refrigerant pressure has dropped below the set point pressure twice in a cooling cycle. The air conditioner will shut down and notification will be sent that there is a low pressure lockout. • Damper Alarm – if the 100% full flow damper does not open when required, an alarm notification is sent that the damper is not open. The damper is exercised every 24 hours to verify proper operation. • Dirty Filter Alarm – a switch monitors the pressure on either side of the filter. If the differential pressure exceeds the set point pressure, an alarm notification is sent that there is not sufficient air flow through the filter. • Communications Alarm – a signal is sent if there is a loss of communication between the air conditioner and the CoolLinks controller. • Landline Power Alarm - If either air conditioner loses landline power, an alarm notification is sent. ComPac ASDCA 50 Hz PDS 2/2014 New 2 Shelter & System Alarms In addition to the HVAC alarms, the CooLinks controller also provides Shelter and System alarms. The alarm is displayed on the CoolLinks PLC in the shelter and also sent via SNMP trap to the network operations center. • First Stage High Temperature Alarm – Inside temperature above 85°F (29.4°C). • Second Stage High Temperature Alarm – Inside temperature above 90°F (32.2°C). • Low Temperature Alarm - Inside temperature is below 45°F (7.2°C). • Smoke Alarm - If the smoke sensor input to the CoolLinks system is active, the Compressor, Heater, and Indoor Blower Motor on both HVAC units will be shut down and the damper will closed completely. This will stop air flow within the shelter. • Hydrogen Detector Alarm- If the hydrogen sensor input to the CoolLinks system is active, the damper(s) on units that are not currently in mechanically cooling will be fully opened and the Indoor Blower Motor(s) will be turned on. This will expel noxious gases and introduce outside air into the shelter. If one unit is in mechanical cooling, it will continue to run. The other air conditioner will turn on and operate in the emergency ventilation mode. • Generator Operation Alarm - If the generator running input to the CoolLinks system is active, only one HVAC unit will be permitted to run in mechanical cooling. As the generator is typically sized to run only one HVAC unit, this ensures that the generator load is not exceeded. Remote Access Data Points Through the Ethernet connection, the network operations center can monitor and change various data points in the HVAC system and the shelter. Data Points which can be monitored and changed: • First Stage Cooling Set Point Temperature • Second Stage Cooling Set Point Differential Temperature • First Stage Heating Set Point Temperature • Second Stage Heating Set Point Differential Temperature Data points which can only be monitored: • Inside Temperature - Current • Outside Temperature - Current • Outside Humidity - Current • Dew point - Current • Inside Temperature - Average Last Hour • Outside Temperature - Average Last Hour • Outside Humidity - Average Last Hour • Dew point - Average Last Hour • Unit 1 & Unit 2 Mechanical Cooling Time - Last Hour • Unit 1 & Unit 2 Mechanical Cooling Requests - Last Hour • Unit 1 & Unit 2 DC Free Air Cooling Time - Last Hour • Unit 1 & Unit 2 DC Free Air Cooling Requests - Last Hour • Unit 1 & Unit 2 Heating Time - Last Hour • Unit 1 & Unit 2 Heating Requests - Last Hour Dry Contact Alarm Outputs A dry contact is provided for each HVAC unit to indicate HVAC unit failure to the shelter alarm block. Unit failure is defined as 1) a high pressure lockout or 2) a low pressure lockout or 3) a loss of landline power.This dry contact is a normally open contact. 3 ComPac ASDCA 50 Hz PDS 2/2014 New Standard Features Designed for Operation in Low Ambient Conditions • Low ambient control cycles condenser fan to maintain proper refrigerant pressures. Allows operation in mechanical cooling (compressor) down to 0ºF (-18ºC). Note: low temperature operation is affected by ambient conditions, e.g. wind and humidity. • Three minute by-pass of the low pressure switch for startup of compressor when outdoor temperatures are below 55°F (13°C). • Factory built-in economizer. High Efficiency • High efficiency compressor. • Lanced fins standard on all evaporator and condenser coils. Built-in Reliability • High pressure switch and low pressure switch with lockout protects refrigerant circuit. Ease of Installation Ease of Service • Sloped top with flashing eliminates • Service access valves are need of rain hood. standard. • Built-in mounting flanges facilitate • Standard 2” (50 mm) pleated installation and minimize chance filter with a MERV rating of 8 of water leaks. changeable from outside. • Supply and return openings exactly match previous models. • All major components are readily accessible. • Factory installed disconnect on all units. • Front Control Panel allows easy access and complies with NEC clearance codes on redundant • Single Point Power Entry complies side-by-side systems. with latest edition of U.L. Standard 1995. • LEDs indicate operational status and fault conditions. Rugged Construction • Copper tube, aluminum fin evaporator & condenser coils. • Foiled backed insulation on the indoor air path. • Field or factory installed heaters on discharge side of evaporator coil (optional) • Baked on neutral beige finish over galvanneal steel for maximum cabinet life. (Other finishes are available.) • Adjustable .03 to ten minute delay on make for short cycle protection. Grilles For ASDCA36 Supply Grille: 28” x 8” (711mm x 203mm)................. P/N 80675 Return Grille: 20” x 12” (508mm x 356mm)................ P/N 80678 For ASDCA42-48-60-72 Supply Grille: 30” x 10” (762mm x 254mm)................ P/N 80676 Return Grille: 30” x 16” (762mm x 406mm)................ P/N 80679 Factory Installed Accessories Phase Monitor - Monitors 3Ø power supply and will turn the air conditioner off if power supply is not phased properly. Not required on 1Ø units. Compressor Sound Jacket - To reduce sound of compressor. Right & Left Side Compressor Configuration – The air conditioners can be built with the compressor on the opposite side to facilitate service access when two units are installed side by side. In the 36, the standard location for the compressor is on the right hand side. In the 42-48-60, the standard location for the compressor is on the left hand side. In the 72, the compressor is accessed from the front of the unit and an opposing configuration is not required. Hard Start Kit - Used on single phase equipment to give the compressor higher starting torque under low voltage conditions. (Field installed only) (Note: Not recommended for use on scroll compressors.) Options Extreme Duty Package - Allows Marvair® air conditioners to operate in extremely cold and hot ambient conditions. The Extreme Duty Kit is always factory installed and is available on all air conditioners. The units will operate from -20°F to 130°F (-29° to 54°C). The Extreme Duty Package includes a suction line accumulator, thermal expansion valve (TXV), crankcase heater, hard start kit, an auto reset high pressure switch and an outdoor thermostat and fan cycle switch. The fan cycle control is standard on all ComPac air conditioners and operates based upon the liquid line pressure. The outside thermostat opens whenever the outside temperature is below 50°F (10°C) and closes when the outside temperature is 50°F (10°C) or higher. Whenever the temperature is below 50°F (10°C), the fan cycle switch is in the circuit; when temperatures are 50°F (10°C) or higher, the fan cycle switch is not in the circuit. The outdoor thermostat is used with a TXV to prevent excessive cycling or “hunting” of the TXV. Desert Duty package - The Desert Duty package is designed for operation in hot climates including the ComPac ASDCA 50 Hz PDS 2/2014 New 4 American southwest and the Middle East in ambient temperatures from -20°F to 130°F (-29°C to 54°C). Standard features of the Desert Duty package include a thermal expansion valve and a sealed condenser fan motor. Low temperature cooling is with the use of outside air via the economizer. and metal in the in the condenser section and an impregnated polyurethane on the condenser coil and fan blades. See Coastal Environmental Technical Bulletin for more details. Protective Coil Coatings - Either the condenser or evaporator coil can be coated, however, coating of the evaporator coil is not common. For harsh conditions, e.g., power plants, paper mills or sites were the unit will be exposed to salt water, the coil should be coated. Note: Cooling capacity may be reduced by up to 5% on units with coated coils. Dirty Filter Indicator - A factory installed option that measures the difference in pressure across the internal filter and illuminates a LED when the pressure exceeds the desired difference. An illuminated LED indicates that the air flow may be obstructed and the filter should be inspected. Wall mount adapter for AVP36 & AVPA36 air conditioners - P/N K/03955-XXX - Facilitates replacement of 44-5/8” (1133 mm) wide AVP36 & AVPA36 air conditioners with the 40” (1,016 mm) wide ASDCA36 air conditioners. XXX is color designator. See model ID. Coastal Environment Package – Recommended for units to be installed near an ocean or on seacoast. Includes corrosion resistant fasteners, sealed or partially sealed condenser fan motor, protective coating applied to all exposed internal copper Model Identification ASDC A •• Refrigerant A = R410A AC •• ••• Electric Heat – kW 000 = No Heat 050 = 5 kW 060 = 6 kW AC = Air Conditioner Nominal Cooling @ 50 Hz 36 = 8.8 kW (30,175 BTUH) 42 =10.6 kW (36,125 BTUH) 48 =11.7 kW (39,950 BTUH) 60 =14.1 kW (48,025 BTUH) 72 (1ø)= 15.7 kW (53,550 BTUH) 72 (3ø)=17.7 kW (60,350 BTUH) Air Source Direct Current Power Supply F = 200-220v. 1ø, 50 Hz. W = 220-240v. 1ø, 50 Hz. G = 200-220v. 3ø, 50 Hz. E = 380v. 3ø, 50 Hz. C • A2 ••• Special Option Code U = Scroll Compressor K = Coastal Package O = Opposite side compressor E = Extreme Duty D = Desert Duty C = ComPac® II Cabinet Color 100 = Beige 200 = Gray 400 = White A2 = Internal Disconnect Efficiency and Capacity Ratings at ANSI/AHRI Standard 390 Model Number ACF Cooling in kW (BTUH) ASDCA36 ACG ACE ACF 8.8 (30,175) ASDCA42 ACG ACE ACF 10.6 (36,125) ASDCA48 ACG ACE 11.7 (39,950) ACF ASDCA60 ACG ACE ASDCA72 ACF 14.1 (48,025) ASDCA72 ACG / ACE 15.7 (53,550) 17.7 (60,350) COP (EER2) 2.62 (8.93) 2.53 (8.65) 2.53 (8.65) 2.51 (8.55) 2.87 (9.79) 2.78 (9.50) Rated Air Flow3 1,765 (1040) 2,200 (1290) 2,545 (1500) 2,675 (1575) 2,960 (1745) 2,960 (1745) 1 Cooling rated at 95°F (35°C) outdoor and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air 2 3 EER=Energy Efficiency Ratio Rated Air Flow in M3/Hr (Cubic Feet/Minute) Ratings are with no outside air. Performance will be affected by altitude. Ratings are at 220 volts for “W or G” models and 380 volts for “E” models. Operation of units at a different voltage from that of the rating point will affect performance and air flow. Sensible Total Heat Ratio @ 35ºC (95ºF) Outside Air Dry Bulb Model Number Total Capacity in kW (BTUH) Sensible Heat Ratio Sensible Capacity in kW (BTUH) ASDCA36 ACF ACG ACE 8.8 (30,175) 0.69 6.07 (20,820) ASDCA42 ACF ACG ACE 10.6 (36,125) 0.75 7.95 (27,095) ASDCA48 ACF ACG ACE 11.7 (39,950) 0.75 8.78 (29,960) ASDCA60 ACF ACG ACE 14.1 (48,025) 0.69 9.45 (33,135) ASDCA72 ASDCA72 ACG / ACE (3ø) ACF (1ø) 15.7 (53,550) 17.7 (60,350) 0.70 0.66 11.00 (37,485) 11.68 (39,830) Sensible heat ratios based upon ANSI/AHRI std. 390 outdoor air of 95°F (35°C) and return air of 80°F DB/67° WB (26.5°C DB/19.5°C WB). Cooling Performance in kW (BTUH) at Various Outdoor Temperatures Model Number Outdoor Temperature 29.5ºC / (85ºF) 32ºC / (90ºF) 35ºC / (95ºF) 38ºC / (100ºF) 40.5ºC / (105ºF) 43.5ºC / (110ºF) 46ºC / (115ºF) 48.9ºC / (120ºF) 51.7ºC / (125ºF) 54.4ºC / (130ºF) ASDCA36AC 9.55 (32,589) 9.19 (31,382) 8.84 (30,175) 8.49 (28,968) 8.13 (27,761) 7.78 (26,554) 7.60 (25,951) 7.07 (24,133) 6.72 (22,927) 6.36 (21,720) ASDCA42AC 11.44 (39,015) 11.01 (37,570) 10.58 (36,125) 10.16 (34,680) 9.74 (33,235) 9.31 (31,790) 9.10 (31,068) 8.46 (28,883) 8.04 (27,439) 7.62 (25,995) ASDCA48AC 12.64 (43,146) 12.17 (41,548) 11.71 (39,950) 11.24 (38,352) 10.77 (36,754) 10.30 (35,156) 10.02 (34,204) 9.36 (31,941) 8.90 (30,370) 8.43 (28,771) ASDCA60AC 15.20 (51,867) 14.63 (49,946) 14.07 (48,025) 13.51 (46,104) 12.95 (44,183) 12.38 (42,262) 12.10 (41,302) 11.26 (38,411) 10.69 (36,491) 10.13 (34,570) ASDCA72ACF 16.95 (57,834) 16.32 (55,692) 15.69 (53,550) 15.06 (51,408) 14.43 (49,266) 13.81 (47,124) 13.49 (46,053) 12.55 (42,833) 11.92 (40,692) 11.30 (38,550) ASDCA72ACG, ACE 19.10 (65,178) 18.39 (62,764) 17.68 (60,350) 16.98 (57,936) 16.27 (55,522) 15.56 (53,108) 15.21 (51,901) 14.14 (48,266) 13.44 (45,853) 12.73 (43,440) Based upon ANSI/AHRI std. 390 return air conditions of 80°F DB/67° WB (26.5°C DB/19.5°C WB) at various outdoor temperatures. 5 ComPac ASDCA 50 Hz PDS 2/2014 New Electrical Characteristics - Compressor & Motors BASIC MODEL ASDCA36ACW ASDCA42ACW ASDCA48ACW ASDCA60ACW ASDCA72ACW ASDCA36ACG ASDCA42ACG ASDCA48ACG ASDCA60ACG ASDCA72ACG ASDCA36ACE ASDCA42ACE ASDCA48ACE ASDCA60ACE ASDCA72ACE 1 COMPRESSOR VOLTS / HZ / PH RLA1 220/240-50-1 13.5 220/240-50-1 16.0 220/240-50-1 15.9 220/240-50-1 20.2 220/240-50-1 24.5 200/220-50-3 13.2 200/220-50-3 13.6 200/220-50-3 13.7 200/220-50-3 15.6 200/220-50-3 22.4 380/420-50-3 6.0 380/420-50-3 6.1 380/420-50-3 6.2 380/420-50-3 7.1 380/420-50-3 10.6 RLA = Rated Load Amps 2 LRA2 72.0 87.0 98.0 128.0 153.0 88.0 83.1 83.1 110.0 149.0 44.0 41.0 41.0 52.0 75.0 LRA = Locked Rotor Amps 3 OUTDOOR FAN MOTOR VOLTS / HZ / PH RPM3 FLA4 220/240-50-1 900 2.1 220/240-50-1 825 2.4 220/240-50-1 825 2.4 220/240-50-1 825 2.4 220/240-50-1 825 2.4 220/240-50-1 900 2.1 220/240-50-1 825 2.4 220/240-50-1 825 2.4 220/240-50-1 825 2.4 220/240-50-1 825 2.4 220/240-50-1 900 2.1 220/240-50-1 825 2.4 220/240-50-1 825 2.4 220/240-50-1 825 2.4 220/240-50-1 825 2.4 RPM = Revolutions per Minute 4 HP5 1/4 1/2 1/2 1/2 1/2 1/4 1/2 1/2 1/2 1/2 1/4 1/2 1/2 1/2 1/2 QTY 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 FLA = Full Load Amps 5 INDOOR BLOWER MOTORS VDC6 RPM3 FLA4 48 2070 4.0 48 1930 4.4 48 1930 4.4 48 1930 4.4 48 1930 4.4 48 2070 4.0 48 1930 4.4 48 1930 4.4 48 1930 4.4 48 1930 4.4 48 2070 4.0 48 1930 4.4 48 1930 4.4 48 1930 4.4 48 1930 4.4 HP = Horsepower 6 HP5 1/6 1/5 1/5 1/5 1/5 1/6 1/5 1/5 1/5 1/5 1/6 1/5 1/5 1/5 1/5 VDC = Volts Direct Current Summary Electrical Ratings (Wire and Circuit Breaker Sizing) ELECTRIC HEAT BASIC MODEL VOLTAGE PHASE / HZ 000 = None 050 = 5 kw SPPE3 SPPE3 060 = 6 kw SPPE3 MCA MFS MCA MFS MCA MFS2 ASDCA36ACW 220/240-50-1 19.0 30 26.0 30 ASDCA42ACW 220/240-50-1 22.4 35 26.0 35 ASDCA48ACW 220/240-50-1 22.3 35 26.0 35 ASDCA60ACW 220/240-50-1 27.7 45 27.7 45 ASDCA72ACW 220/240-50-1 33.0 50 33.0 30 ASDCA36ACG 200/220-50-3 18.6 30 18.6 30 ASDCA42ACG 200/220-50-3 19.4 30 19.4 30 ASDCA48ACG 200/220-50-3 19.5 30 19.5 30 ASDCA60ACG 200/220-50-3 21.9 35 21.9 35 ASDCA72ACG 200/220-50-3 30.4 50 30.4 50 ASDCA36ACE 380/420-50-3 8.6 15 8.6 15 ASDCA42ACE 380/420-50-3 8.8 15 8.8 15 ASDCA48ACE 380/420-50-3 9.0 15 9.0 15 ASDCA60ACE 380/420-50-3 10.1 15 10.1 15 ASDCA72ACE 380/420-50-3 14.5 25 14.5 25 1 MCA = Minimum Circuit Ampacity (Wiring Size Amps) 2MFS = Maximum Fuse Size 3SPPE= Single Point Power Entry MCA & MFS are calculated at compressor RLA for breaker and wire sizing. This chart should only be used as a guideline for estimating conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit. 1 2 1 2 1 Unit Load Amps CURRENT LOAD LOAD OF RESISTIVE HEATING - ELEMENTS ONLY (AMPS) (MOTORS) TOTAL MAXIMUM HEATING AMPS (VAC) VOLTAGE Compressor & Indoor ALL HEATING ELEMENTS ARE ON A SEPARATE CIRCUIT PHASE / HZ Outdoor Fan Blowers VAC Amps DC Amps 05 kW 06 kW ASDCA36ACW 220/240-50-1 15.6 8.0 20.8 ASDCA42ACW 220/240-50-1 18.4 8.8 20.8 ASDCA48ACW 220/240-50-1 18.3 8.8 20.8 ASDCA60ACW 220/240-50-1 22.6 8.8 20.8 ASDCA72ACW 220/240-50-1 26.9 8.8 20.8 ASDCA36ACG 200/220-50-3 15.3 8.0 13.2 ASDCA42ACG 200/220-50-3 16.0 8.8 13.2 ASDCA48ACG 200/220-50-3 16.1 8.8 13.2 ASDCA60ACG 200/220-50-3 18.0 8.8 13.2 ASDCA72ACG 200/220-50-3 24.8 8.8 13.2 ASDCA36ACE 380/420-50-3 7.1 8.0 6.3 ASDCA42ACE 380/420-50-3 7.3 8.8 6.3 ASDCA48ACE 380/420-50-3 7.4 8.8 6.3 ASDCA60ACE 380/420-50-3 8.3 8.8 6.3 ASDCA72ACE 380/420-50-3 11.8 8.8 6.3 Heating kW is rated at 240 volts on the ACF models, 220 volts on the ACG models and 420 volts on the ACE models. Total heating and cooling amps includes all VAC motors. Loads are not equally balanced on each phase and values shown are maximum phase loads. Three phase models contain single phase motor loads. BASIC MODEL NUMBER ComPac ASDCA 50 Hz PDS 2/2014 New 6 7 ASDCA36 RETURN AIR FILTER ASDCA36 Filter Size COMPAC II 30 x 16 x 2 INCHES 762 x 406 x 51 MILLIMETERS 400/182 LBS/KGS 92486 PART NUMBER 1 FILTERS PER UNIT Shipping Weight (pounds/kilograms) 8 MERV RATING Dimensional Data - ASDCA36 ComPac ASDCA 50 Hz PDS 2/2014 New ComPac ASDCA 50 Hz PDS 2/2014 New 8 RETURN AIR FILTER ASDCA42-48-60 Filter Size COMPAC II 36½ x 22 x 2 INCHES ASDCA42-48-60 927 x 559 x 51 MILLIMETERS 80162 PART NUMBER 1 FILTERS PER UNIT 532/242 LBS/KGS Shipping Weight (pounds/kilograms) 8 MERV RATING Dimensional Data - ASDCA42-48-60 9 INCHES 18 x 24 x 2 ASDCA72 RETURN AIR FILTER ASDCA72 Filter Size COMPAC II 457 x 610 x 51 MILLIMETERS 92491 PART NUMBER 640/291 LBS/KGS Shipping Weight (pounds/kilograms) 2 FILTERS PER UNIT 8 MERV RATING Dimensional Data - ASDCA72 ComPac ASDCA 50 Hz PDS 2/2014 New Notes ComPac ASDCA 50 Hz PDS 2/2014 New 10 Notes 11 ComPac ASDCA 50 Hz PDS 2/2014 New Notes Please consult the Marvair® website at www.marvair.com for the latest product literature. Detailed dimensional data is available upon request. A complete warranty statement can be found in each product’s Installation/Operation Manual, on our website or by contacting Marvair at 229-273-3636. As part of the Marvair continuous improvement program, specifications are subject to change without notice. P.O. Box 400 • Cordele, GA 31010 156 Seedling Drive • Cordele, GA 31015 Ph: 229-273-3636 • Fax: 229-273-5154 Email: [email protected] • Internet: www.marvair.com ComPac ASDCA 50 Hz PDS 2/2014 New 12