Transcript
SPLIT SYSTEM 21 - 121
MCN 21-121 AIR COOLED CONDENSING UNIT HEAT PUMP FOR INDOOR INSTALLATION
Cooling
Heating
[kW]
[kW]
21
6.45
7.20
25
7.91
8.60
31
8.84
9.82
41
12.0
12.8
51
14.1
15.1
71
20.5
20.5
91
26.6
27.2
101
31.9
32.4
121
37.8
38.5
Size
These units allow the creation of air-conditioning systems in two sections, combined with our CN, CN-V, CNI series units, or alternatively with the air handling unit exchanger. The MCN series condensing units are designed for indoor installation, and can operate both in cooling and heat pump mode. They feature very silent operation, thanks to the thermal and acoustic insulation on all the panelling, the use of low-speed centrifugal fans and the adoption of the new silenced hermetic compressors. The high pressure gain values available allow the use of extensive ducting for the intake and discharge of the cooling air.
CERTIFIED QUALITY SYSTEM ISO 9001 : 2008
BT05B024GB-02
MCN 21 - 121 (R-407C)
SPLIT SYSTEM 21 - 121
STANDARD UNIT SPECIFICATIONS COMPRESSOR hermetic orbiting scroll compressor complete with motor over-temperature and over-current devices and protection against excessive gas discharge temperature. Fitted on rubber antivibration mounts and complete with oil charge STRUCTURE the units are assembled on a solid "ALUZINK" channel base PANELLING The casing is made of prepainted steel sheet panels, completely lined with foam thermo-acoustic insulation with a class 1 fire resistance. The side panels are easily removable for total accessibility to the inside of the unit. EXTERNAL EXCHANGER finned exchanger, made from copper pipes arranged in staggered rows and mechanically expanded for better adherence to the collar of the fins. The fins are made from aluminium with a special corrugated surface, set a suitable distance apart to ensure maximum heat exchange efficiency. FAN Dual intake centrifugal fan directly coupled to the single-phase electric motor, fitted for speed control. (sizes 21÷51) Dual intake centrifugal fans, statically- and dynamically-balanced, fitted on antivibration supports. Coupled via belt and pulley system to three-phase electric motors on belt tightener slides. (gsizes 71÷121)
REFRIGERANT CIRCUIT each circuit features: - filter dryer, supplied separately (inside the unit) (sizes 21÷71) - high pressure switch - low pressure switch - liquid and gas shut-off valves with service fitting - high compressor discharge temperature safety thermostat - 4-way reverse cycle valve - expansion device
ELECTRICAL PANEL - auxiliary circuit fuse - compressor power supply remote control switch connection terminal block for: - remote ON/OFF control - remote shut-down - cooling / ventilation / heating switching - microprocessor control - variable fan speed control for operation at low ambient temperatures (sizes 21÷51) - compressor overload protection and timer - centralised alarms with remote signalling - RS485 remote communication serial port - Separate alarms visualization (high pressure, low pressure, overload compressor, probe breakdown). - main door lock isolator switch (gsizes 71÷121)
ACCESSORIES POFX - air outlet plenum (gsizes 71÷121) supplied separately MMF - uprated motor for high static pressures (for motor coupled to belt/pulley system). (gsizes 71÷121) optional accessory PMX - phase monitor supplied separately MHPX - high and low pressure gauges supplied separately LTF - variable fan speed control for operation at low ambient temperatures (condensation control in cooling) (Supplied as standard for sizes 21÷51. Optional for sizes 71÷121) AMRX - rubber antivibration mounts supplied separately KCX - connecting set: thermal expansion valve, filter dryer, sight glass, check valve. (gsizes 71÷121) supplied separately TCDC - auxiliary condensate collection tray (gsizes 71÷121) optional accessory
CONFIGURATION CODE (1)
-
BT05B024GB-00
MCN-2 -
(Standard 71-121)
LT
(Standard 21-51)
LTFI2
(71-121)
LTFI4
(71-121)
(1) LOW AMBIENT CONTROL Pressure switch device for operation at low outside temperatures: not required(-) standard (gsizes 71÷121) Device for operation at low temperature of outdoor air(LT) Standard (sizes 21÷51) device with variable fan speed with INVERTER for motors from 1.1 to 2.2kW(LTFI2) optional accessori (gsizes 71÷121) device with variable fan speed with INVERTER for motors from 3 to 4kW (LTFI4) optional accessori (gsizes 71÷121)
(2) ACOUSTIC CONFIGURATION Standard acoustic configuration(ST)
(3) ENERGY EFFICIENCY Energy efficiency for temperate climate(T) standard
2
21
(2)
(3)
ST
T
ST (Standard)
T (Standard)
SPLIT SYSTEM 21 - 121
GENERAL TECHNICAL SPECIFICATIONS COOLING Cooling capacity Compressor power input Total power input HEATING
1 1 1
kW kW kW
6.45 2.27 2.55
7.91 2.68 3.21
8.84 3.51 4
12 3.46 4.5
14.1 4.64 5.7
20.5 5.55 6.6
26.6 7.96 9
31.9 8.8 10.3
37.8 11.6 13
Heat output Compressor power input Total power input COMPRESSOR
2 2 2
kW kW kW
7.2 1.6 1.9
8.6 1.8 2.3
9.82 2.1 2.7
12.8 2.6 3.7
15.1 3.2 4.3
20.5 4.1 5.2
27.2 5.9 7
32.4 6.8 8.3
38.5 8.3 9.8
Type of compressors No. of Compressors Std Capacity control steps Oil charge (C1) Refrigerant charge (C1) Refrigerant circuits AIR HANDLING SECTION FANS (OUTLET) Type of fans Number of fans Standard air flow Installed unit power Max outside static pressure Max outside static pressure CONNECTIONS Gas connection Liquid connection POWER SUPPLY Standard power supply DIMENSIONS Length Depth Height STANDARD UNIT WEIGHTS Shipping weight
3
4 5
Nr Nr l kg Nr
SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1.1 1.1 1.9 1.6 1.7 4.1 4.1 4.1 2.3 2.5 2.6 3.8 4.5 5 5.8 7 7 1 1 1 1 1 1 1 1 1 CFG 1 720 0.3 60
CFG 1 1020 0.5 65
CFG 1 1020 0.5 65
CFG 1 1600 1.1 90
CFG 1 1600 1.1 90
CFG 1 2770 1.1 90 450
CFG 1 2770 1.1 90 450
CFG 1 3880 1.5 90 410
CFG 1 3880 1.5 90 410
mm mm
16 10
16 10
18 12
18 12
22 12
28 16
28 18
35 22
35 22
V
230/1/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
mm mm mm
790 538 648
935 630 648
935 630 648
1165 703 723
1165 703 723
1517 758 1130
1517 758 1130
1780 846 1205
1780 846 1205
kg
92
112
114
157
160
318
336
385
392
Nr l/s kW Pa Pa
(1) saturated suction temperature (SST) = 9.5 °C (Dew Point) room temperature = 35°C (2) condensing temperature = 40°C external exchanger air intake = 6.1 °C W.B. (3) charge to be completed during start-up (4) Standard motor
(5) uprated motor
Voltage: 230/1/50
ELECTRICAL DATA Size
21
25
31
41
A
17.2
20.2
23
30.7
kW
3.4
3.9
4.5
5.6
A
63.6
4
5
120.7
F.L.A. - Total F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION F.L.I. - Total M.I.C. MAXIMUM INRUSH CURRENT M.I.C. - Value power supply 230/1/50 Hz +/-6% voltage unbalance: max 2 %
BT05B024GB-00
F.L.A. - FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS
Voltage: 400/3/50+N
ELECTRICAL DATA Size
21
25
31
41
51
71
91
101
121
F.L.A. - Total A 7.3 F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION
10.2
11
15.3
17.5
16.5
20.3
23.7
28.3
F.L.I. - Total M.I.C. MAXIMUM INRUSH CURRENT
F.L.A. - FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS
M.I.C. - Value
kW
3
3.8
4.3
5.4
6.4
8.7
11.4
13.4
16.9
A
34.6
44.5
50.5
57.7
73.7
103.9
125.9
130.7
170.7
power supply 400/3/50 (+ NEUTRAL) +/- 6%
3
SPLIT SYSTEM 21 - 121
OPERATING LIMITS (COOLING) Size
21
25
31
41
51
71
91
101
121
°C °C °C
47
48
46
48
47
-6
-6
-6
-6
-6
48 12 -7
47 11 -8
48 12 -7
47 12 -8
°C
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
°C °C °C °C
17.5 -5 64 30
17 -6 64 30
16.5 -5 64 30
17 -6 64 30
17.5 -6 64 30
18 -6 64 30
17.5 -5 64 30
16.5 -6 64 30
17.5 -5 64 30
EXTERNAL EXCHANGER Max air intake temperature Min. air intake temperature Min. air intake temperature COMPRESSOR
1 2 3
Max saturated suction temperature (SST)
OPERATING LIMITS (HEATING) EXTERNAL EXCHANGER Max air temperature inlet (WB) Min air inlet temperature (W.B.) Max condensing temperature Min. condensing temperature
4 4 5
DB = dry bulb WB = wet bulb In case of below zero air ambient temperature with a long period of heat pump operating mode it is necessary to help the evacuation of the water produced during the defrost cycle; this to avoid the formation of ice in the unit basement. Pay attention that the evacuation will not create inconveniences to things or persons.
variable fan speed control for operation at low ambient temperatures (Supplied as standard for sizes 21÷51. Optional for sizes 71÷121) (4) condensing temperature = 45°C (5) air 10°C DB / 8.3 °C WB
(1) conditions referred to a saturated suction temperature (SST) of 7°C (Dew Point) (2) external exchanger air in quiet (3) external exchanger air in quiet
SOUND LEVELS Sound Power Level (dB) Size
Octave band (Hz)
Sound pressure level
Sound power level
63
125
250
500 1000 2000 4000 8000
dB(A)
dB(A)
21
80
72
66
68
67
63
59
50
57
71
25
83
78
72
70
68
65
59
52
59
73
31
83
79
73
70
69
65
60
52
60
74
41
80
80
79
75
73
70
66
59
64
78
51
81
81
80
76
74
71
67
60
65
79
71
83
82
80
81
78
73
69
62
67
83
91
85
84
82
83
79
75
70
63
69
84
101
84
77
70
73
65
61
52
44
57
73
121
85
79
72
73
66
64
54
49
58
74
Measures according to ISO 3744 regulations, with respect to the EUROVENT 8/1 certification. The sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refers to a distance of 1m from the external surface of the units, excepted ducted ones.
BT05B024GB-00
CONVERSION TABLE : DEW / MID POINT
4
DP (°C)
3
5
7
8
9.5
12
MP (°C)
1
3
5
6
7.5
10
THE FOLLOWING VALUES ARE REFERRED TO DEW POINT. AN INDICATION OF THE CORRESPONDING MEDIUM EVAPORATING TEMPERATURE (MID POINT) IS GIVEN IN THE TABLE.
SPLIT SYSTEM 21 - 121
COOLING PERFORMANCE EXTERNAL EXCHANGER AIR INTAKE TEMPERATURE (ºC)
21
25
31
41
51
71
25
30
32
35
40
43
46
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
3
6.00
1.85
5.62
2.05
5.47
2.14
5.23
2.27
4.83
2.50
4.58
2.64
4.33
2.79
5
6.42
1.87
6.02
2.07
5.85
2.15
5.60
2.28
5.17
2.51
4.91
2.65
4.64
2.79
7
6.85
1.88
6.42
2.07
6.24
2.16
5.97
2.28
5.52
2.50
5.24
2.64
4.95
2.78
8
7.07
1.88
6.62
2.07
6.44
2.16
6.16
2.28
5.69
2.50
5.40
2.63
5.11
2.77
9.5
7.40
1.88
6.93
2.07
6.74
2.15
6.45
2.27
5.96
2.48
5.66
2.61
5.35
2.74
12
7.97
1.87
7.46
2.06
7.25
2.13
6.94
2.25
6.41
2.45
6.08
2.57
5.75
2.69
3
7.23
2.06
6.79
2.32
6.61
2.42
6.32
2.59
5.82
2.88
5.51
3.06
5.18
3.25
5
7.76
2.10
7.29
2.35
7.10
2.46
6.79
2.62
6.26
2.91
5.93
3.09
5.58
3.28
7
8.31
2.13
7.81
2.38
7.60
2.49
7.28
2.65
6.72
2.94
6.36
3.12
6.00
3.30
8
8.59
2.14
8.08
2.39
7.86
2.50
7.53
2.66
6.95
2.95
6.59
3.13
6.21
3.31
9.5
9.02
2.16
8.48
2.41
8.26
2.52
7.91
2.68
7.31
2.96
6.93
3.14
6.54
3.32
12
9.76
2.20
9.18
2.45
8.94
2.55
8.56
2.71
7.92
2.99
7.51
3.16
7.09
3.34
3
8.24
2.57
7.71
2.87
7.49
3.00
7.15
3.19
6.56
3.53
6.19
3.75
5.80
3.97
5
8.83
2.64
8.28
2.94
8.04
3.07
7.68
3.26
7.04
3.61
6.64
3.83
6.22
4.05
7
9.43
2.72
8.83
3.03
8.58
3.16
8.20
3.36
7.53
3.71
7.11
3.92
6.68
4.15
8
9.74
2.76
9.11
3.08
8.85
3.21
8.46
3.41
7.78
3.76
7.36
3.98
9.5
10.2
2.83
9.53
3.17
9.26
3.30
8.84
3.51
8.15
3.85
7.73
4.06
12
11.0
2.97
10.2
3.34
9.92
3.49
9.49
3.70
8.79
4.03
8.39
4.23
3
10.9
2.79
10.3
3.10
10.0
3.23
9.61
3.42
8.91
3.76
8.46
3.97
8.00
4.18
5
11.6
2.81
11.0
3.12
10.7
3.25
10.3
3.44
9.57
3.78
9.10
3.98
8.61
4.19
7
12.5
2.82
11.8
3.13
11.5
3.26
11.0
3.45
10.3
3.78
9.76
3.99
9.24
4.19
8
12.9
2.83
12.2
3.14
11.9
3.27
11.4
3.46
10.6
3.79
10.1
3.99
9.57
4.19
9.5
13.5
2.84
12.8
3.14
12.5
3.27
12.0
3.46
11.1
3.78
10.6
3.98
10.1
4.18
12
14.6
2.84
13.8
3.14
13.5
3.27
13.0
3.45
12.1
3.76
11.5
3.95
10.9
4.14
3
12.8
3.60
12.0
3.98
11.7
4.15
11.2
4.40
10.3
4.85
9.80
5.13
9.24
5.43
5
13.8
3.67
12.9
4.06
12.6
4.22
12.1
4.48
11.1
4.94
10.6
5.22
9.96
5.53
7
14.8
3.74
13.9
4.13
13.5
4.30
12.9
4.56
11.9
5.02
11.3
5.31
10.7
5.61
8
15.3
3.77
14.3
4.16
14.0
4.33
13.4
4.59
12.4
5.05
11.7
5.35
11.1
5.66
9.5
16.0
3.82
15.1
4.21
14.7
4.38
14.1
4.64
13.0
5.11
12.4
5.40
11.7
5.71
12
17.3
3.90
16.3
4.29
15.9
4.46
15.2
4.72
14.1
5.19
13.4
5.49
12.7
5.80
3
18.4
4.19
17.4
4.68
16.9
4.89
16.3
5.22
15.2
5.81
14.4
6.19
13.7
6.59
5
19.7
4.28
18.7
4.77
18.2
4.98
17.6
5.31
16.3
5.90
15.6
6.28
14.8
6.67
7
21.2
4.38
20.0
4.87
19.6
5.08
18.9
5.41
17.6
6.00
16.8
6.37
15.9
6.76
8
21.9
4.43
20.7
4.93
20.3
5.14
19.5
5.47
18.2
6.05
17.4
6.42
16.5
6.81
9.5
23.0
4.52
21.8
5.02
21.3
5.23
20.5
5.55
19.2
6.14
18.3
6.50
17.5
6.89
12
25.0
4.67
23.7
5.17
23.2
5.38
22.3
5.71
20.9
6.29
20.0
6.66
19.0
7.03
3
24.1
6.23
22.8
6.92
22.2
7.21
21.4
7.67
19.9
8.48
19.1
8.99
18.2
9.52
5
25.9
6.31
24.4
7.01
23.8
7.30
22.9
7.76
21.4
8.58
20.5
9.10
19.5
9.64
7
27.7
6.39
26.1
7.09
25.5
7.39
24.5
7.86
22.9
8.68
21.9
9.20
20.9
9.74
8
28.6
6.43
27.0
7.14
26.3
7.43
25.3
7.90
23.7
8.72
22.7
9.25
21.6
9.79
9.5
30.0
6.49
28.3
7.20
27.6
7.49
26.6
7.96
24.9
8.79
23.8
9.31
22.7
9.86
12
32.4
6.58
30.6
7.29
29.9
7.59
28.7
8.06
26.9
8.89
25.7
9.42
24.6
9.96
91
BT05B024GB-00
Size
SST (°C)
SST = satured suction temperature corresponds to the pressure at the compressor (°C) (dew point) suction gas superheating +5° K kWe = Compressor power input in kW kWf = Cooling capacity in kW
5
SPLIT SYSTEM 21 - 121
COOLING PERFORMANCE EXTERNAL EXCHANGER AIR INTAKE TEMPERATURE (ºC) Size
101
121
SST (°C)
25
30
32
35
BT05B024GB-00
43
46
kWe
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
3
28.6
6.86
27.0
7.63
26.4
7.96
25.4
8.48
23.7
9.40
22.7
9.99
21.7
10.6
5
30.7
6.94
29.0
7.72
28.3
8.06
27.3
8.58
25.5
9.51
24.5
10.1
23.4
10.7
7
32.9
7.03
31.1
7.82
30.4
8.15
29.3
8.68
27.4
9.62
26.3
10.2
25.1
10.8
8
34.0
7.07
32.2
7.86
31.4
8.20
30.3
8.73
28.4
9.67
27.2
10.3
26.1
10.9
9.5
35.8
7.14
33.8
7.93
33.1
8.27
31.9
8.80
29.9
9.75
28.7
10.4
27.5
11.0
12
38.8
7.26
36.7
8.06
35.9
8.40
34.6
8.93
32.5
9.88
31.2
10.5
29.9
11.1
3
34.5
8.89
32.5
9.83
31.7
10.2
30.4
10.9
28.3
12.0
27.0
12.8
25.6
13.5
5
36.9
9.08
34.8
10.0
33.9
10.4
32.6
11.1
30.4
12.3
29.0
13.0
27.6
13.8
7
39.5
9.26
37.2
10.2
36.3
10.6
34.9
11.3
32.5
12.5
31.0
13.3
29.6
14.1
8
40.8
9.36
38.4
10.3
37.5
10.7
36.0
11.4
33.6
12.6
32.1
13.4
30.6
14.2
9.5
42.8
9.50
40.3
10.5
39.3
10.9
37.8
11.6
35.3
12.8
33.7
13.6
32.1
14.4
12
46.2
9.75
43.5
10.7
42.5
11.2
40.9
11.9
38.1
13.1
36.5
13.9
34.8
14.8
SST = satured suction temperature corresponds to the pressure at the compressor (°C) (dew point) suction gas superheating +5° K kWe = Compressor power input in kW kWf = Cooling capacity in kW
6
40
kWf
SPLIT SYSTEM 21 - 121
HEATING PERFORMANCE
21
25
31
41
51
71
Ta (°C) DB/WB
CONDENSING TEMPERATURE (°C) 40
45
50
55
60
kWt
kWe
kWt
kWe
kWt
kWe
kWt
kWe
kWt
kWe
-5 / -5.4
5.22
1.57
5.16
1.76
5.11
1.98
5.07
2.23
0 / -0.6
5.95
1.60
5.90
1.80
5.85
2.02
5.80
2.27
5.76
2.54
5 / 3.9
6.76
1.61
6.69
1.81
6.62
2.04
7 / 6.1
7.20
1.60
7.12
1.81
7.03
2.03
6.55
2.28
6.48
2.55
6.94
2.27
6.85
2.54
10 / 8.2
7.65
1.59
7.55
1.80
7.44
2.02
7.33
2.26
7.20
2.52
8.05
2.45
15 / 13
8.79
1.56
8.62
1.76
8.44
1.97
8.25
2.20
-5 / -5.4
6.13
1.83
6.09
2.08
6.07
2.36
6.06
2.67
0 / -0.6
7.04
1.83
6.99
2.08
6.94
2.36
6.89
2.67
6.85
3.01
5 / 3.9
8.05
1.83
7.97
2.08
7.89
2.36
7.80
2.66
7.70
3.00
7 / 6.1
8.60
1.82
8.51
2.07
8.40
2.35
8.28
2.65
8.16
2.98
10 / 8.2
9.16
1.81
9.04
2.06
8.92
2.34
8.78
2.64
8.62
2.97
9.78
2.92
15 / 13
10.6
1.79
10.4
2.03
10.2
2.30
10.00
2.60
-5 / -5.4
7.20
2.24
7.20
2.55
7.20
2.89
7.21
3.27
0 / -0.6
8.13
2.19
8.09
2.49
8.05
2.81
8.01
3.17
7.97
3.56
5 / 3.9
9.21
2.15
9.14
2.45
9.06
2.77
8.97
3.12
8.86
3.49
7 / 6.1
9.82
2.14
9.73
2.43
9.63
2.75
9.50
3.10
9.37
3.48
10 / 8.2
10.5
2.14
10.3
2.43
10.2
2.74
10.1
3.09
9.90
3.47
15 / 13
12.1
2.13
11.9
2.42
11.7
2.75
11.5
3.11
11.3
3.50
-5 / -5.4
9.17
2.63
9.10
2.93
8.98
3.26
8.81
3.60
0 / -0.6
10.5
2.66
10.4
2.97
10.2
3.31
10.0
3.67
9.81
4.05
5 / 3.9
12.0
2.65
11.8
2.97
11.6
3.31
11.4
3.68
11.1
4.07
7 / 6.1
12.8
2.64
12.6
2.96
12.4
3.31
12.1
3.67
11.8
4.06
10 / 8.2
13.6
2.62
13.4
2.94
13.1
3.29
12.8
3.66
12.5
4.04
15 / 13
15.6
2.55
15.4
2.87
15.0
3.22
14.6
3.58
14.2
3.96
-5 / -5.4
10.6
3.11
10.5
3.47
10.4
3.85
10.3
4.26
0 / -0.6
12.3
3.15
12.1
3.53
12.0
3.94
11.8
4.38
11.6
4.86
5 / 3.9
14.1
3.18
13.9
3.56
13.7
3.99
13.4
4.45
13.2
4.96
7 / 6.1
15.1
3.19
14.8
3.57
14.6
4.00
14.3
4.47
14.0
4.99
10 / 8.2
16.1
3.20
15.8
3.58
15.5
4.01
15.2
4.48
14.9
5.01
17.0
5.01
15 / 13
18.7
3.20
18.3
3.57
17.9
4.00
17.5
4.48
-5 / -5.4
14.6
4.12
14.6
4.68
14.5
5.32
14.4
6.04
0 / -0.6
16.7
4.10
16.6
4.65
16.4
5.27
16.2
5.96
15.9
6.72
5 / 3.9
19.2
4.11
18.9
4.64
18.6
5.25
18.2
5.92
17.9
6.66
7 / 6.1
20.5
4.12
20.1
4.65
19.8
5.25
19.4
5.91
19.0
6.64
10 / 8.2
21.9
4.14
21.5
4.67
21.1
5.26
20.6
5.92
20.2
6.64
23.1
6.66
15 / 13
25.4
4.20
24.9
4.73
24.3
5.31
23.8
5.96
-5 / -5.4
20.1
5.90
19.9
6.57
19.7
7.30
19.6
8.07
0 / -0.6
22.6
5.94
22.4
6.63
22.2
7.39
22.0
8.20
21.8
9.09
5 / 3.9
25.5
5.95
25.2
6.65
24.9
7.43
24.7
8.28
24.4
9.19
7 / 6.1
27.2
5.94
26.8
6.66
26.4
7.44
26.1
8.30
25.8
9.22
10 / 8.2
28.9
5.93
28.4
6.65
28.0
7.44
27.6
8.30
27.3
9.24
15 / 13
33.3
5.90
32.6
6.61
32.0
7.40
31.4
8.28
30.8
9.23
91
BT05B024GB-00
Size
kWt = heating capacity (kW) kWe = Compressor power input in kW Ta = external exchanger air intake temperature Performances in function of the inlet/outlet water temperature differential = 5°C WB = wet bulb DB = dry bulb
7
SPLIT SYSTEM 21 - 121
HEATING PERFORMANCE Size
101
121
CONDENSING TEMPERATURE (°C)
Ta (°C) DB/WB
40
45
50
55
kWt
kWe
kWt
kWe
kWt
kWe
-5 / -5.4
23.2
6.85
23.1
7.62
22.9
8.46
0 / -0.6
26.6
6.85
26.3
7.65
26.1
5 / 3.9
30.3
6.83
29.9
7.65
7 / 6.1
32.4
6.82
31.8
7.64
10 / 8.2
34.5
6.81
33.8
60
kWt
kWe
kWt
kWe
8.52
26.0
9.46
29.5
8.55
29.3
31.4
8.55
31.0
9.52
29.3
10.6
9.54
30.9
10.6
7.63
33.2
8.55
32.7
9.55
32.3
10.6
36.8
9.53
35.7
10.6
15 / 13
39.9
6.77
38.9
7.60
37.8
8.52
-5 / -5.4
28.4
8.16
28.1
9.08
27.4
10.1
0 / -0.6
32.0
8.22
31.6
9.17
31.1
10.2
30.4
11.3
5 / 3.9
36.1
8.28
35.6
9.25
35.1
10.3
34.6
11.5
34.1
12.8
7 / 6.1
38.5
8.32
37.9
9.29
37.3
10.4
36.8
11.6
36.3
12.9
10 / 8.2
40.9
8.35
40.2
9.32
39.6
10.4
39.0
11.6
38.5
13.0
15 / 13
47.1
8.44
46.2
9.40
45.3
10.5
44.4
11.8
43.6
13.2
kWt = heating capacity (kW) kWe = Compressor power input in kW Ta = external exchanger air intake temperature Performances in function of the inlet/outlet water temperature differential = 5°C WB = wet bulb DB = dry bulb
AIR FLOW: STANDARD
PERFORMANCES OF SUPPLY AIR FANS EXTERNAL STATIC PRESSURE (Pa) Standard air flow
l/s
30
60
90
120
150
180
210
240
270
300
330
360
390
420
450
2770
2770
2770
2770
2770
2770
2770
2770
2770
2770
2770
2770
2770
2770
2770
71
Fan RPM
rpm
552
608
665
722
777
832
885
936
986
1034
1081
1127
1171
1214
1256
Total input
kW
0.83
0.95
1.08
1.21
1.35
1.49
1.63
1.77
1.92
2.07
2.23
2.38
2.55
2.71
2.87
Sound pressure level
dB
69
70
71
72
72
73
74
75
76
76
77
8
78
79
79
Motor input
kW
1.1
1.1
1.1
1.5
1.5
1.5
2.2
2.2
2.2
2.2
3
3
3
3
3
Transmission code (fan) Standard air flow
T224.1.2.32
T170.1.2.32
91
l/s
2770
2770
2770
2770
2770
2770
2770
2770
2770
2770
2770
2770
2770
2770
2770
rpm
552
608
665
722
777
832
885
936
986
1034
1081
1127
1171
1214
1256
Total input
kW
0.83
0.95
1.08
1.21
1.35
1.49
1.63
1.77
1.92
2.07
2.23
2.38
2.55
2.71
2.87
Sound pressure level
dB
69
70
71
72
72
73
74
75
76
76
77
8
78
79
79
Motor input
kW
1.1
1.1
1.1
1.5
1.5
1.5
2.2
2.2
2.2
2.2
3
3
3
3
3
Standard air flow
T224.1.2.32
T244.1.2.33
T200.1.2.33
T170.1.2.32
101
l/s
3880
3880
3880
3880
3880
3880
3880
3880
3880
3880
3880
3880
3880
-
-
Fan RPM
rpm
460
510
559
607
653
697
741
783
823
863
902
940
976
-
-
Total input
kW
1.1
1.26
1.44
1.63
1.83
2.04
2.27
2.5
2.74
2.99
3.24
3.5
3.76
-
-
Sound pressure level
dB
70
69
69
70
71
72
73
74
74
75
76
76
77
-
-
Motor input
kW
1.5
1.5
1.5
2.2
2.2
2.2
3
3
3
3
4
4
4
-
-
Transmission code (fan) Standard air flow
121
BT05B024GB-00
T200.1.2.33
Fan RPM
Transmission code (fan)
T315.1.2.43 3880
T300.1.2.43
l/s
3880
Fan RPM
rpm
460
510
559
607
653
Total input
kW
1.1
1.26
1.44
1.63
1.83
Sound pressure level
dB
70
69
69
70
71
Motor input
kW
1.5
1.5
1.5
2.2
2.2
Transmission code (fan)
8
T244.1.2.33
T315.1.2.43
3880
3880
3880
T300.1.2.43
T250.1.2.40 3880
3880
3880
3880
697
741
783
823
2.04
2.27
2.5
2.74
72
73
74
74
2.2
3
3
3
T250.1.2.40
T224.1.2.40 3880
-
-
3880
-
-
3880
3880
863
902
940
976
-
2.99
3.24
3.5
3.76
-
-
75
76
76
77
-
-
3
4
4
4
-
-
-
-
T224.1.2.40
SPLIT SYSTEM 21 - 121
DIMENSIONAL DRAWING A B I
4
25
L
7 C
1
D
E
H
25
46,5
F
G
2
S
3
6
8 5 R 25
48
B G
W2
21.5
W1
32
25
25
4
W4
M
25
W3
46,5
N
P
S
7
6
Size A B C D E F G H I L M N P R S Length Depth Height W1 W2 W3 W4 Shipping weight
mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm kg kg kg kg kg
21
25
31
41
51
790 538 648 95 75 120 262 50 107 298 816 110 290 595 575 790 538 648 21 17.5 31 23.5 92
935 630 648 95 75 120 289 50 152 331 965 130 340 783 575 935 630 648 24.5 23 35.5 29 112
935 630 648 95 75 120 289 50 152 331 965 130 340 783 575 935 630 648 24.5 23 36.5 30 114
1165 703 723 95 75 120 341 50 298 309 1195 130 425 1032 650 1165 703 723 36.5 31 49.5 40 157
1165 703 723 95 75 120 341 50 298 309 1195 130 425 1032 650 1165 703 723 37 32 50 41 160
BT05B024GB-00
(1) COMPRESSOR (2) GAS FITTINGS (3) LIQUID FITTINGS (4) ELECTRICAL PANEL (5) EXTERNAL EXCHANGER (6) POWER INPUT (7) OUTLET CENTRIFUGAL FAN (8) TOP OUTLET (M5) VARIATION FEASIBLE DURING INSTALLATION
9
SPLIT SYSTEM 21 - 121
DIMENSIONAL DRAWING
B
W
120
150
Y
X
Y
A
I
L
G
M
21
25
F
25
24 H
9
11
10
3 C
D
6
2 4 1
11
149
124
5
9
S
Z
7
138
NPR
285 K
T
E
21
U
8
W1
21
W2
B
Size
W3
W4
BT05B024GB-00
A
10
42.5
(1) COMPRESSOR (2) SUCTION LINE CONNECTION C1 (3) LIQUID LINE CONNECTION C1 (4) LIQUID LINE CONNECTION C2 (5) SUCTION LINE CONNECTION C2 (6) ELECTRICAL PANEL (7) POWER INPUT (8) EXTERNAL EXCHANGER (9) ACCESS TO THE COMPONENTS (10) OUTLET CENTRIFUGAL FAN (11) AIR OUTLET PLENUM (OPTIONAL)
A B C D E F G H I K L M N P R S T U W X Y Z Length Depth Height W1 W2 W3 W4 Shipping weight
mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm kg kg kg kg kg
71
91
101
121
1517 758 1130 1025 1253 1174 383 188 155 596 337 38 75 75 75 69 209 55 650 495 250 1241 1517 758 1130 87 82 76 73 318
1517 758 1130 1025 1253 1174 383 188 155 596 337 38 75 75 75 69 209 55 650 495 250 1241 1517 758 1130 90.5 85 82.5 78 336
1780 846 1205 1100 1508 1383 446 198 199 684 362 38 75 75 75 69 217 55 780 625 315 1504 1780 846 1205 104.5 97 94.5 89 385
1780 846 1205 1100 1508 1383 446 198 199 684 362 38 75 75 75 69 217 55 780 625 315 1504 1780 846 1205 106 98 96 92 392
SPLIT SYSTEM 21 - 121
FUNCTIONAL CLEARANCES
MCN 21-51
MCN 71-101
CLIVET SPA Feltre (BL) ITALY Tel. + 39 0439 3131 Fax + 39 0439 313300
[email protected]
CLIVET ESPAÑA S.A. (Madrid) SPAIN Tel. + 34 91 6658280 Fax + 34 91 6657806
[email protected]
CLIVET UK LTD Fareham (Hampshire) U.K. Tel. + 44 (0) 1489 572238 Fax + 44 (0) 1489 573033
[email protected]
CLIVET NEDERLAND B.V. Amersfoort - Netherlands Tel. + 31 (0) 33 7503420 Fax + 31 (0) 33 7503424
[email protected]
CLIVET TFA (PVT) LTD Bangalore - INDIA Tel. + 91 80 25351617 Fax + 91 80 25351392
[email protected]
The data contained in this bulletin is not binding and may be changed by the manufacturer without prior notice. All reproduction, even partial, is prohibited. © Copyright - CLIVET S.p.A. - Feltre (BL) - Italy