Transcript
220-240V ~ 50Hz 1Ph 380-420V ~ 50Hz 3Ph
Slim Line Ceiling Concealed Ducted Split Systems
Green
Medium Static Pressure
Ducted Split System Heat Pump 12 - 18 - 24 - 30 - 36 - 48 - 60
DC Inverter
R-410A
Inverter Technology
$
Refrigerant Leak Detection
Anti Freezing
Anti-Freezing Protection
Easy Flexible Installation
High Temp. Protect
High Temp. Protection
Easy Fast Service & Maintenance
Auto Restart Function
Cold Draft Protection
Washable Air Filter
3 Minutes Time Delay
Defrost Protection
Durability
Self diagnostic function
Hydrophilic Aluminum Fins
Independent Dehumidification
Inverter Compressor
Super Quiet
ECO Function
Medium Static Pressures
Wired Control
Timer Functions
Fresh Air
Efficient Fans
Wireless Control
Slim Design
Efficient Coils
Display Panel
Inner Groove Copper Tubing
Refrigerant
HFC R410A IAQ
Optional Drain Pump
Efficient Operation
Efficient Anti-dust Filters
40~100 Pa
Auto
Auto Fan Speed Auto Mode
3 Min.
Ducted Split Systems Green
Medium Static Pressure
Key Features
Heat Pump
medium static pressure, slim line, ceiling concealed ducted split is the optimum air conditioning solution for places which require ceiling installation above false ceiling and minimum sound levels. Its slim profile and flexible installation make this system the best choice for residential and light commercial applications where the units are practically hidden from view. Healthy & Clean Indoor Air Quality (IAQ) IAQ
The indoor unit is fitted with a fresh air knock out panel that can be utilized to introduce fresh air into the room. This helps prevent the build of stale air and enhances air quality in working environments and enclosed applications without natural fresh air supply.
SMART CONTROLS
Modern Slim Design Compact invisible indoor unit with ultra slim profile and low height is just 21 cm for sizes 12K-18K, 24.9 cm for sizes 30K-36K and 30 cm for sizes 42K-48K-60K suitable for low false ceiling applications. Wired room controller
( option ) Wireless Remote control
Smart LED display panel shows control functions and also shows error code in case of a malfunction.
EFFICIENT, TROPICAL & QUIET Efficient Tropical Operation with Minimum Electrical Consumption works with the new R-410A refrigerant which increases its energy efficiency and does not degrade the ozone layer.
$
Patented heat transfer and aerodynamics technologies to ensure prefect operation up to 52°C outdoor ambient temperature for energy saving and low operating cost.
OUTDOOR UNIT
2
Sizes : 30 - 36
Sizes : 48-60
Patented centrifugal blower, elephant ear propeller, new heat exchangers, improved Air Management System (AMS), and quiet compressor. Statically and dynamically balanced fans for quiet operation. Minimum vibrations with strengthened sheet metal parts by finite element analysis.
R-410A
HFC
Standard Smart Wired Controller with complete control functions built in the control system. Wired Controller can be fixed on the wall and avoid mislaying. It’s mainly used for commercial zone and makes the control more convenient. Standard Smart LCD infrared wireless remote control with complete control functions built in the control system to ensure efficiency at all operating conditions. Optional Smart Link central Control to monitor from a center point, the operation of number of ducted indoor units in the same project site. This feature is particularly helpful in large office applications and hotels. Auto fan speed which changes automatically the fan speed to high or medium or low fan speed by sensing the temperature difference between the room temperature and setting temperature. Auto mode which changes automatically the operation mode and capacity output according to temperature difference between room temperature and setting temperature. Independent Dehumidification mode which dehumidifies the room efficiently, but not lower the temperature so obviously as cooling operation. ECO function for energy saving and comfortable healthy sleep which automatically changes fan speed to low speed and controls both setting and room temperatures.
$
Programmable timer for easy on and off selection with energy savings including off timer, on timer, off/on timer and on/off timer functions.
Superior air distribution performance : Three fan speeds with external static pressure up to 40 ~ 100 Pa as per the model to satisfy air flow and static pressure requirements to suit various applications.
40~100 Pa
Efficient Air Management System (AMS) leading to maximum air flow with minimum turbulence for minimum air resistance, smooth airflow and efficient operation.
AMS
Follow Me function for smart wired control of comfortable temperature. With this technology, an efficient temperature sensor is built in the wired control just like the air conditioner is following wired control.
Durability
Carrier innovative outdoor axial fan technology for efficient operation with minimum air resistance and maximum air flow.
Anti-rust, weather proof and long life indoor unit sheet metal parts made of chemically treated and zinc coated ( galvanized ) sheet metal.
Carrier innovative double inlet, double width forward curved centrifugal blower technology driven by 3 speeds high efficiency motor of low power consumption .
Drain pan is designed to protect against rust, to minimize wet surface and residual water during off cycles and to inhibit bacteria growth that may cause smells.
Efficient indoor and outdoor coils with large heat transfer surfaces for minimum electrical consumption. Efficient trapeziform Inner groove copper tubing compared with traditional copper tubing, it allows more refrigerant flow, improvs heat exchange efficiency and lowers power consumption while keeping the same capacity output level. Precoated Hydrophilic Aluminum Fins of indoor coil to protect the coil against corrosion and to allow easy and quick removal of unrestricted condensate water between the coil fins to increase airflow, improve heat exchange efficiency and accelerate cooling process.
Auto restart function with backup memory. When the power failure happenes during the operation of air conditioner, the microprocessor of the Printed Circuit Board will memorize the operation setting. After the power is recovered, the air conditioner operates automatically ( without remote control but after elapse of compressor safety time delay ), according to the previous operation settings.
Anti-rust, weather proof and long life outdoor unit sheet metal parts made of chemically treated and zinc coated ( galvanized ) sheet metal. Powder painted casing of outdoor unit with prefect adhesion of highly resistant ployester paint 60-80 microns thick, which is electro-statically applied and baked at a temperature of 220°C. Optional coated aluminum fins of outdoor coil for coastal applications to protect against corrosion.
Smart Link
Auto
3 (three) minutes safety time delay between compressor turning off and turning on for compressor protection against cycling.
3 Min.
Anti-freezing protection of indoor coil when the air conditioner is operating in cool mode with excessive dirt on the indoor coil and / or clogged air filters and / or low ambient temperature operation of cool mode.
Anti Freezing
High temperature protection of outdoor coil when Hi Temp. Protect the air conditioner is operating in cool mode. This protection is only available for heat pump system. Cool Cold draft protection when the air conditioner is operating in heat mode to prevent cold air blowing out at the beginning of heat mode which avoids the discomfort to the user. High temperature protection of indoor coil when the air conditioner is operating in heat mode.
Hi Temp. Protect Heat
Defrost protection of outdoor coil when the air conditioner is operating in heat mode at very low ambient temperature. Smart self-diagnostic function for malfunctions detection for easy fast service and maintenance. Smart Refrigerant leak detection by sensitive sensors mounted on both indoor and outdoor coils for easy fast service and maintenance. Auto reset – internal thermal protector of indoor and outdoor fan motors to protect motor windings against excessive current.
Motors
The components of both indoor and outdoor units comply with international standards of performance and safety.
Rev. (0) - 2017
www.carrierafrica.com
Sizes : 12-18-24
Complete Safety & Reliability Functions
Comfort with Complete Control Functions
KEY FEATURES Efficient anti dust washable aluminim air filters for clean and healthy air.
Quiet with Minimum Sound Level
Ducted Split Systems Green
Medium Static Pressure
Key Features
Key Features
Easy Installation, Service and Maintenance (Cont.)
Easy Installation, Service and Maintenance Due to compact dimensions, low height and low weight, the installation of ducted indoor unit on the ceiling is faster and extremely easy.
The display panel can be installed on the false ceiling to show unit operation and error code.
Easy removal of washable air filters for cleaning.
Slim Low Height Compact Dimensions & Light Weight Size
W
12K
70
18K
88
24K
111
30K 36K 48K 60K
Net Weight
Dimensions (cm)
136
H
D
21
67.4
18.5 23 30.2
24.9
120
30
77.4
Min. 5mm
Kg
21 cm or 24.9 cm or 30 cm
Remote ON / OFF
Drop - Ceiling
40.5
87.4
Remote ON / OFF function provides more easy central control of ducted split system.
Easy accessibility to motors and fans of indoor unit for easy fast service and maintenance.
46
Flexible two directions of air return : Back air return ( factory standard ) Bottom air return ( can be done at field ).
Pre-Punched Fresh air intake built in the indoor unit from both sides to make air quality more healthy and more comfortable. motor Blower housing
Remote system alarm function which required for some applications such as computer rooms for fast and easy service and maintenance.
Bottom Panel
Remote Alarm
Smart self-diagnostic function for malfunctions detection through the leds of display panel for easy fast service and maintenance.
Back Return Air
Bottom Return Air
Optional drain pump which can lift the condensate water up to 75 cm upmost. Optional drain pump is factory installed.
Smart Refrigerant leak detection by sensitive sensors mounted on both indoor and outdoor coils for easy fast service and maintenance.
75 cm ceiling
Rev. (0) - 2017
www.carrierafrica.com
Indoor unit equipped with flange connections for both supply and return air ducts.
Fresh air intake
3
Ducted Split Systems Green
Wired Room Controller
Medium Static Pressure 1
POWER Button
2
MODE Selection Button
3
Temperature Selection Button
4
FAN SPEED Selection Button
5
FOLLOW ME Button TIMER Button
7
DELAY / DAY OFF Button
8
CONFIRM Button
9
BACK Button
Auto Cool
2
Heat Fan SU MO TU WE TH FR SA
Week
Day On Off
3 2
4 MODE
FAN SPEED
6
5 SWING
SWING
FOLLOW ME
7
10 DELAY/DAY OFF
CONFIRM
BACK
Dry
Fan 2
Fan speed Indicator Low Fan Speed Indicator Medium Fan Speed Indicator
1
3
Faceplate function indicator
4
Follow me function indicator
5
C° / F° indicator
6
Temperature display
10 14 13
MED
5 6 7 8
Heat Fan SU MO TU WE TH FR SA
11
TIMER
DELAY/DAY OFF
9
Day On Off
1 2 3 4
MODE
Week
10 FAN SPEED
7
Lock indicator
8
Room temperature indicator
9 SWING Clock display SWING
FOLLOW ME
1
Signal transmission indicator
2
MODE indicator
AUTO Automatic COOL Cooling DRY Dehumidification only HEAT Heating 3
ON / OFF indicator
4
SET TEMP. indicator
5
FAN SPEED indicator
LOW FAN SPEED indicator LOW
2
Decrease temperature button The set temperature is decreased down to 17°C.
HIGH FAN SPEED indicator HIGH
3
Increase temperature button The set temperature is increased up to 30°C.
4
FAN selection button Low - Medium - High - Auto fan speed
5
ON/OFF button
6
Air Direction function button *
7
Vertical Air Flow Auto Swing *
8
Sleep function button
9
TIMER ON function button
10
TIMER OFF function button
11
My Mode function button to memorize the preferred settings
12
Follow Me function button *
11
Timer display
13
LED Display function button
14
TURBO function button *
COPY
67 8
MODE selection button AUTO - COOL - DRY - HEAT - FAN
On/Off timer BACK
4
LOW
1
10
CONFIRM
TIMER ON OFF
5
FAN Ventilation (fan only)
Control Buttons
4
Auto Cool Dry Auto
Auto
3
DRY
2
Note : * This function does not work with this product but works with other products
MED FAN SPEED indicator MED AUTO FAN SPEED indicator AUTO 6
TIMER ON function indicator
7
TIMER OFF function indicator
8
FOLLOW ME function indicator
Rev. (0) - 2017
www.carrierafrica.com
2
POWER
High Fan Speed Indicator Auto Fan Speed Indicator
7 11 12
4 8 9
9
DRY Mode Indicator
FAN Mode Indicator
3
FAN HIGH
COPY
8
AUTO Mode Indicator
Heating Mode Indicator
2 5 1 6
SET TEMP.
COOL HEAT
Operation Mode Indicator
COOL Mode Indicator
3 AUTO
Auto Cool Dry Auto
Display of Wired Room Controller 1
1
1
POWER
TIMER
10 COPY Button
Display Of Remote Control
Display of Wired Room Controller
1 2 3 4
6
Wireless Remote Control ( option )
Ducted Split Systems Green
Medium Static Pressure
Smart Self Diagnostic Function For Malfunction Detection
Smart Self Diagnostic Function For Malfunction Detection
Display of the indoor unit size 12
1
2
3
4
5
6
7
1
2
3
4
5
6
7
1
Touche d’urgence Lorsqu’on a perdu la télécommande, que celle-ci est endommagée ou que la batterie est à plat, la touche d’urgence permet de faire fonctionner l’unité.
1
Touche d’urgence Lorsqu’on a perdu la télécommande, que celle-ci est endommagée ou que la batterie est à plat, la touche d’urgence permet de faire fonctionner l’unité.
2
Led OPERATION ( fonctionnement ) * allumeé lorsque l’unité fonctionne.
2
Led OPERATION ( fonctionnement ) * allumeé lorsque l’unité fonctionne.
3
Led TIMER ( temporisateur ) * allumeé en fonction temporisateur.
3
Led TIMER ( temporisateur ) * allumeé en fonction temporisateur.
4
Led DEFROST / FAN ( dégivrage / ventilation ) Led DEFROST ( dégivrage ) : pour l’unit à pompe à chaleur. Led FAN ( ventilation ) pour l’unité à refroidissement seul.
4
Led DEFROST / FAN ( dégivrage / ventilation ) Led DEFROST ( dégivrage ) : pour l’unit à pompe à chaleur. Led FAN ( ventilation ) pour l’unité à refroidissement seul.
5
Led ALARM clignote lorsque le code défaut de l’unit extérieure est identifiable.
5
Led ALARM clignote lorsque le code défaut de l’unit extérieure est identifiable.
6
Récepteur des signaux envoyés par la télécommande
6
Récepteur des signaux envoyés par la télécommande
7
Affichage Le code de défaut est identifiable par l’affichage
7
Affichage Le code de défaut est identifiable par l’affichage
Self diagnostics sizes 18-24-30-36-48-60
Self-diagnosis function of the indoor unit size 12
The fault code is identifiable by the LEDs and the fault code
The fault code is identifiable by the LEDs and the fault code Malfunction Reason
LED OPERATION
LED TIMER
LED DEF.FAN
LED ALARM
Malfunction Code
Temperature sensor air from the indoor unit
E0
Indoor coil temperature sensor of the indoor unit
E1
Malfunction Reason
LED OPERATION
LED TIMER
LED DEF.FAN
LED ALARM
Malfunction Code
Model channel is abnormal
E0
The indoor / outdoor unit communication unit
E1
Temperature sensor air from the indoor unit
E2
Indoor coil temperature sensor of the indoor unit
E3
Outdoor unit coil temperature sensor
E4
Outdoor unit coil temperature sensor
E
Outdoor malfunction
E
EEPROM malfunction
E
Water-level alarm malfunction
E
Protection against over current outdoor unit
P0
EEPROM malfunction
E7
Protection against high temperature compressor
P1
Water-level alarm malfunction
EE
Outdoor unit low pressure malfunction
Ed
Protection against over current outdoor unit The unit is switched off by remote control Defrost heater is active = Flash 5Hz = Flash 1Hz * = LED DEFROST (defrost) for the heat pump unit Led FAN ( FAN ) for cooling only unit.
The unit is switched off by remote control Defrost heater is active = Flash 5Hz = Flash 1Hz * = LED DEFROST (defrost) for the heat pump unit Led FAN ( FAN ) for cooling only unit.
Rev. (0) - 2017
www.carrierafrica.com
Display of the indoor unit sizes 18-24-30-36-48-60
Technical Specifications System type
Heat Pump
System size
12K
18K
24K
30K
36K
36K
48K
60K
Indoor unit model
42QSS012NS
42QSS018NS
42QSS024NS
42QSS030NS
42QSS036NS
42QSS036NT
42QSS048NT
42QSS060NT
Outdoor unit model
38QUS012NS
38QUS018NS
38QUS024NS
38QUS030NS
38QUS036NS
38QUS036NT
38QUS048NT
38QUS060NT
kW
3.66
5.27
7.62
8.79
10.55
10.55
14.07
16.12
Btu/hr
12500
18000
26000
30000
36000
36000
48000
55000
Input power - Cooling
W
1370
1900
2800
3300
3800
3800
5200
6200
Input current - Cooling
A
6.1
9.7
13.5
16.5
18.5
6.1
9.1
10.9
W/W
2.67
2.77
2.72
2.66
2.78
2.78
2.71
2.60
Btu/wh
9.12
9.47
9.28
9.09
9.47
9.47
9.23
8.87
kW
3.81
5.57
7.91
9.67
11.14
11.14
15.53
17.58
Btu/hr
13000
19000
27000
33000
38000
38000
53000
60000
Input power - Heating
W
1310
1850
2300
2900
3500
3400
4400
5200
Input current - Heating
A
5.8
7.9
11.3
15.0
17.3
5.6
7.7
9.1
W/W
2.91
3.01
3.44
3.33
3.18
3.27
3.53
3.38
42QSS012NS
42QSS018NS
42QSS024NS
42QSS030NS
42QSS036NS
42QSS036NT
42QSS048NT
42QSS060NT
m3/hr
625/485/400
950/770/670
cfm
369/287/236
561/455/396
773/661/546
885/767/590
1062/826/620
1062/826/620
Indoor maximum external static pressure
Pa
25
25
25
37
37
37
50
50
Range external static pressure
Pa
0-60
0-60
0-80
0-100
0-100
0-100
0-160
0-160
Sound Pressure (high/med/low)
dB(A)
40/36/32
40/37/35
42/39/37
44/40/37
48/43/39
48/43/39
52/48/43
52/48/43
Net Dimensions (W×H×D)
mm
700x210x635
880x210x674
1100x249x774
1100x249x774
1100x249x774
1100x249x774
1200x300x865
1200x300x865
Weight Net
Kg
19.2
23.7
30.8
32.2
32.2
32.2
44.5
47
38QUS012NS
38QUS018NS
38QUS024NS
38QUS030NS
38QUS036NS
38QUS036NT
38QUS048NT
38QUS060NT
Rotary
Rotary
Rotary
Rotary
Scroll
Scroll
Scroll
Scroll
Cooling capacity
E.E.R. - Cooling
Heating capacity
C.O.P - Heating Indoor unit model Nominal air flow (high/med/low) ( @ rated external static pressure )
Outdoor unit model Compressor type
1310/1120/925 1500/1300/1000 1800/1400/1050 1800/1400/1050 2300/1850/1400 2300/1850/1400
Refrigerant type / Coupler
1357/1092/826 1357/1092/826
R410A / Flare
Sound pressure
dB(A)
59
61
61
62
63
63
64
65
Net Dimensions (W×H×D)
mm
770x555x300
770x555x300
845x702x363
946x810x410
946x810x410
946x810x410
900x1170x350
900x1170x350
Weight Net
kg
34
36.5
52.7
65
79.5
74.5
93.2
97
Liquid
Φ6.35 ( 1/4” )
Φ6.35 ( 1/4" )
Φ9.52 ( 3/8" )
Φ9.52 ( 3/8" )
Φ9.52 ( 3/8" )
Φ9.52 ( 3/8" )
Φ9.52 ( 3/8" )
Φ9.52 ( 3/8" )
Gas
Φ12.7 ( 1/2” )
Φ12.7 ( 1/2" )
Φ15.9 ( 5/8" )
Φ19.0 ( 3/4" )
Φ19.0 ( 3/4" )
Φ19.0 ( 3/4" )
Φ19.0 ( 3/4" )
Φ19.0 ( 3/4" )
Maximum pipe length
m
15
25
25
30
30
30
50
50
Maximum height difference
m
8
15
15
20
20
20
30
30
V/ph/Hz
220-240/1/50
220-240/1/50
220-240/1/50
220-240/1/50
220-240/1/50
380-415/3/50
380-415/3/50
380-415/3/50
Installation Data Pipe connection sizes ( inch )
Rev. (0) - 2017
Power supply
* Cooling Capacity and Energy Efficiency Ratio (EER) based on ISO 13253 Standard at conditions : 35/24ºC db/wb ambient Temperature. 27/19ºC db/wb Indoor Temperature. 220 volts power supply (for sizes 12-18-24-30-36) Single Phase. 380 volts power supply (for sizes 36-48-60) Three Phase. * Heating Capacity and Coefficient Of Performance (COP) are based on ISO 13253 Standard at operating conditions : 20/15ºC db/wb Indoor Temperature 7/6ºC db/wb Outdoor Temperature. 220 volts power supply (for sizes 12-18-24-30-36) Single Phase. 380 volts power supply (for sizes 36-48-60) Three Phase. * Sound pressure is measured in anechoic chamber based on GB/T7725 Standard * Carrier is committed to continuously improving its products according to national and international standards to ensure the highest quality and reliability standards, and to meet market regulations and requirements. All specifications subject to change without prior notice according to Carrier policy of continuous development.
High Air Flow High Air Flow