MegaLine®, GigaLine® and VarioLine® Copper and Fiber Optic Cabling Systems for DataCenter · Office · Industry
The Quality Connection
2
Portfolio Strong brands, strong service Datacom system families: a sound, future-proof investment
MegaLine®
VarioLine®
GigaLine®
Copper cabling systems
Modular system peripherals*
FO cabling systems
MegaLine®
Cu data cables
* VarioLine® can be used for both system families
GigaLine®
FO data cables
MegaLine®
GigaLine®
FO connectivity
Connect Cu connectivity
GigaLine®
VarioKeystone®
FO patch cords/ trunk cables
Cu connectivity
MegaLine®
Cu patch cords/ trunk cables
LEONI organises its range of data communications products for the passive cabling infrastructure in buildings and local networks into three main groups: n Copper cabling systems
MegaLine®
n Fiber optic cabling systems
GigaLine®
n Modular system peripherals
VarioLine®
MegaLine® from LEONI is a copper system family for all classes and categories that delivers a sound, future-proof investment. It incorporates MegaLine® Copper data cables, patch cords and trunk cables as well as MegaLine® Connect and VarioKeystone® Connectivity. GigaLine® allows extremely high bandwidths and long transmission distances thanks to its fiber optic technology. GigaLine® Fiber optic data cables, patch cords and trunk cables as well as GigaLine® Connectivity combine to produce an extremely efficient system. VarioLine® is a modular consolidation point and underfloor range. All connection components can be easily and quickly integrated into different areas of application and adapted to local conditions. LEONI also offers a comprehensive service package comprising data sheets, announcement texts, seminars and certification
Issue: November 2012 © LEONI Kerpen GmbH The contents of this catalogue are protected by copyright. All rights reserved. All necessary planning documents can be found on the Internet: www.leoni-infrastructure-datacom.com We reserve the right to make technical modifications; typographical errors and mistakes excepted.
programmes. www.leoni-infrastructure-datacom.com
3
Contents
Page
n MegaLine®
Copper (Cu)
10
Cu data cables
n VarioKeystone®
72
Cu connectivity
Cabling systems
n MegaLine® Connect45 92
Cable and connectivity
Cu connectivity
n ELine 1200® EC7
104
Cu connectivity
n MegaLine®
116
Cu patch cords/trunk cables
n GigaLine®
Fiber optic (FO)
n GigaLine®
n GigaLine®
Cable and connectivity
for copper and FO
210
FO patch cords/trunk cables
n GigaLine®
182
FO connectivity
Cabling systems
System peripherals
152
FO data cables
228
DataCenter links
n VarioLine®
236
Modular
system peripherals
• Consolidation points (CP)
• Underfloor solutions (UF)
n Office 264
Fields of application
www.leoni-infrastructure-datacom.com
n Industry
266
n DataCenter
272
4
Welcome to the datacom mega store for cable and system solutions
LEONI is a leading supplier in the market for structured cabling systems. In addition to cabling for offices (LAN Office), the range also includes cabling for industrial complexes (LAN Industry) and DataCenter infrastructure (DataCenter).
LEONI's services range from producing our own fibers, manufacturing data cables in copper and fiber optic technology, pre-assembled patch cords and trunk cables as well as connection components through to complete cabling systems. Everything from a single source LEONI's range of copper cable and connectivity offers futureproof cabling systems for building, floor and workstation cabling.
Fiber optic cable and connectivity is the first choice wherever broadband data transmission in combination with long transmission distances in a LAN or MAN are required. LEONI's GigaLine® fiber optic cables and GigaLine® fiber optic connectivity offer high-speed data highways for backbone networks. LEONI products and solutions are ideal for applications which demand maximum reliability, quality and durability, even under harsh and adverse conditions.
www.leoni-infrastructure-datacom.com
5
Application
Office
Industry
DataCenter
European standards
EN 50173-2
EN 50173-3
EN 50173-5
International standards
ISO/IEC 11801
ISO/IEC 24702
ISO/IEC 24764
The cabling systems exceed all relevant European (EN 50173) and international standards (ISO/IEC 11801) and are designed for key applications (Office · DataCenter · Industry).
www.leoni-infrastructure-datacom.com
6
The LEONI Group Cable expertise for the most varied industrial markets
LEONI is a leading supplier of cable systems and related
Your markets – our strength
services for the automotive industry and various other
As diverse as our product and service range are the markets and
industrial sectors.
sectors LEONI is supplying. We focus our activities on customers in the fields of Automotive & Commercial Vehicles, Industry
Our group of companies employs more than 63,000 people in
& Healthcare, Communication & Infrastructure, Electrical
31 countries. Corporate vision, highest quality and innovative
Appliances and Conductors & Copper Solutions.
power have made us one of the leading cable manufacturers in Europe. LEONI develops and produces technically sophisticated
We are among the leading European suppliers in the Communi-
products ranging from wire and optical fibers to cables
cation & Infrastructure market to which at LEONI as a cable
through to complete cable systems and also offers the related
manufacturer also belong activities in the fields of infrastructure
services. Moreover, the product portfolio comprises strands,
& data communications, industrial plant projects, solar- and
standardised cables, hybrid cables, glass fiber as well as special
wind power, energy & telecommunications, irradiation cross-
cables, cable harnesses, wiring systems components and
linking and transportation engineering. Our customers benefit
fully assembled systems for applications in various industrial
world-wide from innovative as well as reliable and long-lasting
markets.
products of high quality. LEONI – we create the best connection for your future.
for further informations www.leoni.com
Engineering
Products and services portfolio at a glance
Services Cable systems/Wiring systems Cable harnesses Copper cables Wires and strands
Sensors Hybrid cables Optical fibers
Relay and safety systems Optical cables Connectors
LEONI's core markets
Automotive & Commercial Vehicles
Industry & Healthcare
Communication & Infrastructure
Electrical Appliances
Conductors & Copper Solutions
www.leoni-infrastructure-datacom.com
7
Infrastructure & Datacom Business Unit
Trust the best partner for your requirements. Infrastructure & Datacom Business Unit
Datacom
LEONI brings together the expertise for power and
The extensive know-how of all companies belonging to the
communications networks in public buildings, in structural
LEONI Group and the unique range of products and services they
and civil engineering, in offices, in DataCenters and in industry.
offer are concentrated in the Datacom business unit. Some of the companies involved have been working successfully in the field
Investors, integrators, planners, installers and businesses can
of cable-bound networks for decades now - particularly LEONI.
obtain cables, connectivity and complete cabling solutions from a single source. The range includes system solutions based
The origins
on copper and fiber optic technology as well as halogen-free
LEONI has been working successfully in the field of cable-bound
power cables with and without total system integrity. Constant
networks for many years. As one of the leading manufacturers
innovations in the areas of safety, environmental compatibility
in the cable industry, the company has been successfully
and energy efficiency offer enhanced customer benefits. Thanks
meeting the complex needs of international markets for more
to on-site consulting services and extensive experience, LEONI is
than 90 years. The quest for constant improvement is a central
an internationally recognised partner for your projects.
element of the company philosophy and will continue under the new name of LEONI Infrastructure & Datacom Business Unit. And it is to the future that we look, producing high-quality, innovative cable and cabling products which are always well ahead of the standards of the time.
www.leoni-infrastructure-datacom.com
8
Quality and environmental management The Quality Connection
LEONI quality management
LEONI environmental management
One of the most important factors in the success of LEONI
New environmental directives have been in force in the European
was and remains the uniformly high quality of its products over
Union (EU) since July 2006. EU Directive 2002/96/EC WEEE
the decades.
(Waste Electrical and Electronic Equipment) regulates the
We pay particularly close attention to this through precise
disposal of electrical and electronic equipment and components.
planning, testing and documentation. Quality management for LEONI's wire and cable production facilities is certified
EU Directive 2002/95/EC RoHS (Restriction of the use of certain
worldwide in accordance with ISO 9001:2000.
Hazardous Substances in electrical and electronic equipment ) restricts the use of certain hazardous substances in electrical and electronic equipment and components.
As part of the production process, we use the latest systems
Cables and wires and the associated connectivity are only
to measure, monitor and regulate the diameter and insulating
affected by the aforementioned directives insofar as they are
capabilities of our cables and wires. The production control group
an internal component of the listed devices and components.
performs regular spot checks to ensure compliance with the
Cables and wires and the associated connectivity therefore do
required limit values. These tests are performed directly in the
not fall under the aforementioned directives if they are located
production area and guarantee a speedy response to interference.
outside of electrical and electronic devices. This also applies
By combining these quality assurance measures, we are able
to connection cables, connection sockets and other peripheral
to continuously optimise our ambitious quality targets.
products as these are disconnected when a device is to be disposed of.
www.leoni-infrastructure-datacom.com
9
All MegaLine® and GigaLine® brand data cables produced after January 1, 2006 are free from hazardous substances
EU Directive 2002/96/EC
as per RoHS. The associated connectivity is also free from
on waste electrical and electronic equipment.
hazardous substances. This is ensured in close cooperation with suppliers.
EU Directive 2002/95/EC on the restriction of the use of certain
This means avoiding the following substances, among others: ■■
Polybrominated diphenyl ether (PBDE)
■■
Decabromodiphenyl ether (DecaBDE)
■■
Perfluorooctane sulfonate (PFOS)
■■
Pentabromodiphenyl ether (PentaBDE)
■■
Octabromodiphenyl ether (OctaBDE)
■■
Lead (Pb)
■■
Mercury (Hg)
■■
Cadmium (Cd)
■■
Hexavalent chromium (Cr VI)
■■
Polybrominated biphenyls (PBB)
hazardous substances in electrical and electronic equipment.
LEONI has been operating a certified and practised environmental management system according to DIN EN ISO 14001 for the development and manufacture of cables and wires from as far back as 1989. The TÜV certification given by the German Technical Certification Association is proof of the company's environmentally friendly product design credentials. By ensuring the RoHS conformity of the data and communication cables as well as the associated connectivity, LEONI Kerpen GmbH is making a further commitment to environmental responsibility.
Even though data and communication cables as well
What does RoHS mean?
as the associated connectivity do not fall under the
RoHS stands for Restriction of the use of certain
new directives, LEONI has opted to use RoHS-compliant
Hazardous Substances in electrical and electronic
materials.
equipment.
www.leoni-infrastructure-datacom.com
10 10
MegaLine® copper data cables
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter
MegaLine® copper data cables
Page
SPACE concept
12
SPACE – Security
13
SPACE – Performance
14
SPACE – Application
16
SPACE – Construction
17
SPACE – EMC
18
Type codes
19
Cable types
20
MegaLine® copper data cables
Copper data cables at a glance
o o o o o o o o o o o o o o o i i i i i i i i i i o dc i
www.leoni-infrastructure-datacom.com
Page
dc dc dc dc dc
dc dc
22
MegaLine® G12-150 S/F
Category "8"
Class "G"
22
MegaLine® F10-130 S/F
Category 7A
Class FA
24
MegaLine® F10-125 S/F
Category 7A
Class FA
26
MegaLine® F10-115 S/F
Category 7A
Class FA
28
MegaLine® F6-90 S/F
Category 7
Class F
30
MegaLine® E5-70 S/F
Category 6A
Class E A
32
MegaLine® E5-70 F/F
Category 6A
Class E A
34
MegaLine® E5-60 U/F
Category 6A
Class E A
36
MegaLine® E2-45 U/F
Category 6
Class E
38
MegaLine® E2-30 F/U
Category 6
Class E
40
MegaLine® E2-30 U/U
Category 6
Class E
42
MegaLine® D1-20 SF/U
Category 5
Class D
44
MegaLine® F10-120 S/F flex
Category 7
Class FA
46
MegaLine® F6-90 S/F flex
Category 7
Class F
48
MegaLine® D1-20 SF/U flex
Category 5
Class D
50
MegaLine® F10-130 S/F (L)2Y
Category "7A"
Class FA
52
MegaLine® F10-130 S/F QH
Category "7A"
Class FA
54
MegaLine® F10-130 S/F Vö
Category "7A"
Class FA
56
MegaLine® F10-115 S/F V
Category "7A"
Class FA
58
MegaLine® F6-90 S/F 2Y
Category 7
Class F
60
MegaLine® D1-20 SF/U 2Y
Category 5
Class D
62
MegaLine® D1-20 SF/U HQH
Category 5
Class D
64
MegaLine® F10-120 S/F 11Y flex
Category "7A"
Class FA
66
MegaLine® F6-70 S/F 11Y flex
Category 7
Class F
68
MegaLine® D1-20 S/U 11Y superflex
Category 5
Class D
70
Office cables DataCenter cables Industrial cables
MegaLine® Cu data cables
11
12
SPACE concept Finding the right data cable
S P A C E
Security Performance Application Construction EMC
LEONI's SPACE concept is based on a pragmatic and clearly
SPACE matrix:
structured matrix. This decision-making aid will help you to find the right data cable for your application faster. The concept is based on the classification of the five main selection criteria for determining the potential overall performance of a data cable:
Security (fire behaviour)
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Security · Performance · Application · Construction · EMC It also allows the value for money to be assessed and makes room for alternative technical and economic scenarios. The demands made on the segment in question rise in step
Performance (cabling class, bandwidth)
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
with the increase in the SPACE index. Example of a data cable with the code S3 P4 A4 C5 E5 :
S3 It passes the fire test according to IEC 60332-3-24 (Security Level 3)
P4
It meets the minimum requirements of the new Class FA
(Performance Level 4)
Application (Ethernet, TV)
A
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
A4 It is dimensioned for applications with more than 10 GbE
Construction (conductor dimensions, tensile strength)
C
(Application Level 4)
C5 It consists of a conductor with AWG 22 (Construction Level 5) _
and thus has low attenuation values and an increased
current rating
E5
The coupling attenuation is >80 dB (EMC Level 5)
With the VDE kitemark (an independent hallmark of quality including production monitoring), LEONI documents that
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation)
E
1 > 40 dB
2 > 50 dB
it guarantees the SPACE quality features at all times. www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter SPACE concept
13
SPACE – Security
As a result of the constant increase in the installed basis and
MegaLine® data cables have improved fire protection
the installation density, the fire behaviour of data cables
characteristics:
is an important safety criterion. When manufactured according
■■
➔ Makes rescue and salvage operations easier
to the legal regulations and installed correctly, data cables cannot cause a fire. If they do catch fire, however, they can
Extremely low smoke development according to IEC 61034
■■
Low toxicity (dioxins are not produced) ➔ Reduces the risk of poisoning
inflame and spread the fire. ■■
Free from halogens according to IEC 60754-2 ➔N o consequential damage to material assets as a result
One of the aims here is to prevent the propagation of fire and
of corrosion
the resulting damage by using flame-retardant, halogen-free cable designs.
■■
Low fire load values ➔ Limits the exacerbating effects on the source of the fire
■■
High oxygen index (OI up to 45) ➔ Reduces the flammability
Security (fire behaviour)
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
The five security levels with regard to fire propagation/flame retardance:
S
1 IEC 60332-2-2
S
4 EFP (Enhanced Fire Performance) Grade 1
Testing of the vertical propagation in a core or individual cable.
In this cable bundle test, a flame is applied to the lower part
Test method: incandescent flame.
of the test samples on a vertical ladder with a length of
S
360 cm using a high-performance burner. During and after
Testing of the vertical propagation in a core or individual cable.
20 minutes, only about 1 m of the section to which the flame
Test method: 1 KW flame. A flame is applied to the lower end
is applied may burn. Immediately after removal of the flame,
of a vertical sample of the cable with a length of approx. 60 cm
the self‑extinguishing process must start. Only specially
for about 60 seconds using a type of Bunsen burner. After
designed data cables can stand up to this exacting fire test.
2 IEC 60332-1-2
removal of the burner, the flames must go out by themselves. The parts of the cable damaged by the flames must not reach
intensive application of the flame for a test period of
S
5 EFP (Enhanced Fire Performance) Grade 2
its upper end (distance: 50 mm).
This stricter security level is application-specific.
S
Security levels
Testing of the flame propagation in an arrangement of several
where high and very high security measures are required
cables, a so-called cable bundle, is carried out according
for the protection of persons or material assets. For example
to IEC 60332-3-24. In this cable bundle test, a flame is applied
in hospitals, schools, hotels, airports, train stations, department
to the lower part of the test samples on a vertical ladder with
stores or in power stations, DataCenters, banks and insurance
a length of 360 cm using a high-performance burner. During
companies, alarm systems.
3 IEC 60332-3-24
and after intensive application of the flame for a test period of 20 minutes, the cables must not burn higher than 250 cm.
www.leoni-infrastructure-datacom.com
SS S 3,
4 and
5 are used in particular
MegaLine® Cu data cables
Fire behaviour
14
SPACE concept
SPACE – Performance Cabling class/bandwidth
Indoor cabling is expected to have a service life of 10 to 15 years. This requires far-sighted planning of the necessary performance of cabling systems and their components. The international standards have often not gone far enough
Performance (cabling class, bandwidth)
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
due to the compromises struggled for and in view of the swiftly increasing transmission rates. Since the development
The five classes for performance (cabling class, bandwidth)
of 10 Gigabit Ethernet, none of the cabling classes below
have very high reserves with regard to the standard involved.
Class F can be said to meet the demands of the future. MegaLine® data cables have excellent transmission performance. They offer high security reserves and are always one step ahead of the standard. MegaLine® – an investment with a future!
P
3 better than Class F (600 MHz) n Class F
MHz
n MegaLine®
1200 1000 800
F6-90 S/F
F6-80 S/F
600 400 200 0
Example: MegaLine® F6-90 S/F better than Category 7 according to EN 50288 and IEC 61156 excellent NEXT, excellent shielding characteristics (shielding of pairs and overall shielding), low skew
www.leoni-infrastructure-datacom.com
Industry
DataCenter SPACE concept
P
P
1 better than Class E (250 MHz)
2 better than Class EA (500 MHz)
n Class E
MHz
n MegaLine®
500
800
E2-45 U/F
450
700
400 350 300
n Class E A
MHz
n MegaLine® E5-70 S/F
E5-70 F/F
600 E2-30 U/U
E2-30 F/U
500
250
400
200
300
150
200
100
100
50
0
0
Example: MegaLine® E2-45 U/F
Example: MegaLine® E5-70 S/F
better than Category 6 according to EN 50288
better than Category 6A according to EN 50288 and IEC 61156
and IEC 61156, very good NEXT, low skew
very good NEXT, very good shielding characteristics (shielding of pairs and overall shielding), low skew
P
P
4 better than Class FA (1000 MHz) MHz
n MegaLine®
1400
F10-130 S/F
1300 1200
5 better than Class "G" (1200 MHz)
n Class FA
F10-115 S/F
1100
n Class "G"
MHz 1600
n MegaLine® G12-150 S/F
1400 1200 1000 800
1000 900
600 400
800
200
700
0
Example: MegaLine® G12-150 S/F
Example: MegaLine® G12-150 S/F
better than Category 7A and "8" according to EN 50288 and
better than Category 7A and "8" according to EN 50288 and IEC
IEC 61156, excellent NEXT, low attenuation, excellent shielding
61156, excellent NEXT, very low attenuation, excellent shielding
characteristics (shielding of pairs and overall shielding), low skew
characteristics (shielding of pairs and overall shielding), low skew
www.leoni-infrastructure-datacom.com
15
MegaLine® Cu data cables
Office
16
SPACE concept
SPACE – Application Ethernet/TV
Cables and connectors form a perfect symbiosis: 4 pairs,
Video/audio/TV/radio
4 connecting clips: each with GHz performance. This allows the parallel, simultaneous use of different applications via Telephone
one cable and one connector:
PC
data, voice and images. Multimedia systems do not need to cost more than conventional systems, in which an individual cable and an individual connector is usually required for each service. This allows savings of up to 50 % of the necessary cables, connectors, wall outlets and patch panels. The large security reserves mean that multimedia applications
Multiple use reduces the system costs by 15 – 30 % (depending
like TV or transmission protocols with high bandwidth
on the services used). The reduction in the number of cables
requirements such as 10 Gigabit Ethernet and 8 Gigabit
and wall outlets actually required usually also allows reductions
Fiberchannel can be transmitted over 100 m. Experts have
in the costs for cable ducts, switching cabinets, etc.
calculated that, as far as we know today, MegaLine® Category 7A data cables allow transmission rates of as much as 100 Gbit/s.
But MegaLine® data cables are capable of more The supply of current (up to 350/600 mA) and voltage (up to 48 V)
The use of low-loss broadband S/FTP cables with individual
can be provided via PoE/PoE+ (according to IEEE 802.3a/at).
or overall shielding in conjunction with multimedia cabling
The current is fed in centrally via the floor distributor or switch.
systems such as ELine 1200® EC7 allows so-called cable
Devices such as IP telephones, Web cameras, WLAN access points,
or service sharing.
etc. are supplied via the telecommunications outlet. The voltage is tapped via a phantom circuit or two unassigned pairs.
Application (Ethernet, TV)
A
1 > 100 MbE
2 > 1 GbE
A A A A A
1 >100 Mbit/s (Fast Ethernet) IEEE 802.3 u
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
The SPACE concept provides five different application levels.
2 >1,000 Mbit/s (Gigabit Ethernet) IEEE 802.3 ab 3 ≤10,000 Mbit/s (10 Gigabit Ethernet) IEEE 802.3 an 4 >10,000 Mbit/s (10 Gigabit Ethernet) IEEE 802.3 an 5 >10,000 Mbit/s (10 Gigabit Ethernet) and TV IEEE 802.3 an and Multimedia
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter SPACE concept
17
SPACE – Construction
High-precision conductor and core geometries, optimally
The designs have low overall diameters, thus allowing high
matched lay lengths in the pairs and the use of very high-
packing densities and small bending radii. The weight
quality insulation and sheath materials are the characteristic
reductions and the robust cable construction offer advantages
features of our range of cables.
for assembly and installation, even under difficult conditions.
Our cables are produced on ultra-modern equipment which
The five different conductor classes describe the permitted
corresponds with the "state of the art" as a result of procedural
tensile stress during installation and the conductor
innovations. The use of physical foaming in the manufacture
resistance.
of high-frequency cores allows excellent, uniform electrical and geometrical characteristics to be achieved. Double skin layers ensure excellent mechanical stability while patented stranding techniques demonstrate technical leadership.
C
Construction (conductor dimensions, tensile strength)
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
1 AWG 27 (7x0.14 mm/0.112 mm2)
5 AWG 22
The current-handling capacity for a maximum ambient
Tensile stress: max. 40/20 N (4 p/2 p) Conductor resistance: max. 170 Ω/km
C
2 AWG 26/AWG 25 ➔ C21 AWG 26 (7x0.16 mm/0.14 mm2)
temperature of 60 °C and the maximum installation
Tensile stress: max. 60/30 N (4 p/2 p)
lengths in the transmission channel can be derived from
Conductor resistance: max. 145 Ω/km
this on request.
➔ C22 AWG 25 (7x0.18 mm/0.175 mm2) Tensile stress: max. 70/35 N (4 p/2 p) Conductor resistance: max. 120 Ω/km
C
3 AWG 24 (0.51 mm/0.205 mm2)
Tensile stress: max. 90/45 N (4 p/2 p) Conductor resistance: max. 95 Ω/km
C
4 AWG 23 (0.57 mm/0.258 mm2)
Tensile stress: max. 110/55 N (4 p/2 p) Conductor resistance: max. 75 Ω/km
C
5 AWG 22 (0.64 mm/0.325 mm2)
Tensile stress: max. 130/65 N (4 p/2 p) Conductor resistance: max. 57 Ω/km
www.leoni-infrastructure-datacom.com
MegaLine® Cu data cables
Conductor dimensions
18
SPACE concept
SPACE – EMC Coupling attenuation
Electromagnetic compatibility (EMC)
The main danger is increasingly a result of the alien
This refers to the ability of devices, systems and plants
crosstalk between adjacent data cables. Depending on their
to function satisfactorily in an electromagnetic environment
construction, data cables have different capabilities with regard
without negative effects on other devices, systems or plants.
to the prevention or reduction of interference.
EMC legislation prescribes the electromagnetic compatibility of devices, systems and plants. The limits for the emission
■■
Unshielded data cables have very good symmetry
of interference and the immunity to interference which
characteristics but are not shielded against internal, external
must be observed are regulated in EN 55022 (Class B) and
or adjacent sources of interference. They are endangered to
EN 50082-1/2 / EN 55024.
a high degree by the environment in which they are installed.
A data cable must resist electromagnetic influences coming
■■
Data cables with individual or overall shielding have very
from the outside to the inside (immunity to interference)
good symmetry characteristics and good or even very good
and from the inside to the outside (emission of interference).
shield characteristics. The EMC is very good or even excellent.
The susceptibility of data cable systems to interference
Interference coming from the installation environment
increases in step with the transmission frequency
(adjacent data cables) can be ruled out completely.
and the data rates (currently 10 Gigabit Ethernet). MegaLine® data cables with a dual shielding reach values
Electromagnetic compatibility
of >80 dB up to 1,000 MHz, thus suppressing incoming
Construction
U/UTP
F/UTP
S/FTP
Symmetry characteristics
+++
++
++
or outgoing potential interference by a factor of >10,000.
Shielding characteristics
low
+
+++
Cables with individual and overall shielding (S/FTP)
Influence of the installation environment
high
medium
low
have excellent EMC, making them an obvious choice for the fail-safe transmission of high data rates such as those offered by 10 Gigabit Ethernet.
E
EMC (coupling attenuation)
E
1 > 40 dB
2 > 50 dB
1 Coupling attenuation >40 dB
3 > 60 dB
4 > 70 dB
5 > 80 dB
Interference suppression exceeding a factor of 100
E
2 Coupling attenuation >50 dB
E
3 Coupling attenuation >60 dB
E
4 Coupling attenuation >70 dB
E
5 Coupling attenuation >80 dB
Interference suppression exceeding a factor of 300
With the MegaLine® SPACE concept, LEONI provides five different EMC levels to choose from.
Interference suppression exceeding a factor of 1,000 The evaluation criterion is the coupling attenuation (interference power suppression). As the sum of the shielding attenuation and the symmetry attenuation, the coupling attenuation is the "be-all and end-all" for the assessment and comparison of the overall EMC behaviour of data cables with various different constructions.
Interference suppression exceeding a factor of 3,000
Interference suppression exceeding a factor of 10,000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 19
Type codes
MegaLine® F10-130 S/F H Cabling class Class "G" Class F Class E Class D
"G" F E D
Bandwidth acc. to standard (factor 100) 1,200 MHz 1,000 MHz 600 MHz 500 MHz 250 MHz 100 MHz
12 10 6 5 2 1
MegaLine® bandwidth (factor 10) 1,500 MHz 1,300 MHz 1,150 MHz 900 MHz 800 MHz 700 MHz 450 MHz 300 MHz 200 MHz
150 130 115 90 80 70 45 30 20
TP (twisted pair) design Overall shielding (copper braiding)/individual shield (foil) Overall shielding (foil)/individual shielding (foil) Unshielded/individual shielding (foil) Overall shielding (copper braiding & foil)/unshielded Overall shielding (foil)/unshielded Unshielded/unshielded
S/F F/F U/F SF/U F/U U/U
Sheath/armouring Halogen-free, flame-retardant PVC PE PUR Sheath Reinforced sheath for industrial applications Oil-resistant Steel wire braiding
H Y 2Y 11Y (L)2Y V Ö Q
The type codes for the MegaLine® copper data cables are compatible in structure with the SPACE concept. This makes it easier to assign cables to the old and new cabling classes and the corresponding categories.
www.leoni-infrastructure-datacom.com
The type codes also include: ■■
Information about the bandwidth in comparison to the standard
■■
Information about the design according to the international standard
■■
Information about the material used for the sheath
Cu data cable: MegaLine® F10-130 S/F H F Acc. to new cabling class FA (1,000 MHz) 10 Bandwidth acc. to standard: 1,000 MHz 130 MegaLine® bandwidth: 1,300 MHz S/F S/FTP design H With halogen-free outer sheath
MegaLine® Cu data cables
MegaLine® Cu data cables
20
Cable types MegaLine® Cu data cables
Cable type x x / x x x Overall shielding
F S SF
Foil shielding Braided shielding Braided and foil shielding Individual shielding Foil shielding
U F
Symmetrical element
P
Unshielded
S/FTP (PiMF with overall shielding)
F/FTP
U/FTP Outer sheath
Outer sheath
Outer sheath
Braided shielding
Foil shielding
Cable pair
Cable pair
Cable pair
Foil shielding
Foil shielding
Foil shielding
Conductor
Conductor
Conductor
SF/UTP
F/UTP
U/UTP
Outer sheath
Outer sheath
Outer sheath
Foil shielding Braided and foil shielding Cable pair
Cable pair
Cable pairs separated by a cross element
Conductor
Conductor
Conductor
Cable type
SF/UTP Cable with overall braided and foil shielding/
There are a large number of different type designations.
with unshielded individual elements
The standardisation defined in ISO/IEC 11801 2nd Edition determines the elements of the design in an unambiguous way.
S/FTP Cable with overall braided shielding/
with individual elements with foil shielding
PiMF Pair in metal foil (xx/FTP)
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter
MegaLine® Cu data cables
21
www.leoni-infrastructure-datacom.com
22
MegaLine® G12-150 S/F
Type
KS-02YSCH 4x2xAWG 22/1 PIMF
Category "8"
S3 P5 A5 C5 E5
Construction
Conductor
Bare copper wire, AWG 22/1
Insulation Twisting element
Cellular-PE, core-diameter: nominal value 1.6 mm Pair
Individual shielding Twisting
Aluminium-bonded polyester foil, metal side outside (PiMF) 4 pairs
Overall shielding
Tinned copper braiding
Outer sheath
Halogen-free, flame-retardant compound
Security (fire behaviour) Fire behaviour Flame retardancy Halogen free Smoke density Calorific value (approx.)
acc. to IEC 60332-3-24 acc. to IEC 60754-1/2 acc. to IEC 61034-1/2 0.74 MJ/m
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Performance Better than Category 7 ("8") acc. to EN 50288 and IEC 61156, excellent NEXT, very low attenuation, excellent shielding characteristics (shielding of pairs and overall shielding), low skew, bandwidth 1,500 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Application (Ethernet, TV) Applications Installation cable for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition) and for home cabling systems acc. to ISO/IEC 15018 and EN 50173-4. Ideal for all applications from Classes D to FA Multimedia (TV, video, data, voice) >10 GbE acc. to IEEE 802.3 an, cable sharing, VoIP, PoE.
A
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during installation after installation Tensile strength (max.) Crush strength Impact strength (number of shocks)
8 x overall diameter (min.) 4 x overall diameter (min.) 130 N 1,000 N/100 mm 10
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Transfer impedance at 10 MHz (nominal value) 2 mΩ/m Shielding attenuation up to 1,200 MHz (nominal value) 80 dB Coupling attenuation up to 1,200 MHz (nominal value) 90 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office
DataCenter
Industry
23
Electrical characteristics (HF) at 20 °C Attenuation dB/100 m typ.
NEXT dB
Cat. "8" max.*
PSNEXT dB
typ.
Cat. "8" min.*
typ.
Cat. "8" min.*
ACR dB at 100 m
PSACR dB at 100 m
ELFEXT dB at 100 m
PSELFEXT dB at 100 m
typ.
Cat. "8" min.*
typ.
typ.
Cat. "8" min.*
typ.
Cat. "8" min.*
Cat. "8" min.*
RL dB typ.
Cat. "8" min.*
1
1.6
1.9
110
80
107
77
108
78
105
75
109
80
106
77
26.1
23
10
4.2
5.4
110
78
107
75
106
72
103
69
109
74
106
71
32.3
25 20.1
100
14.4
17.5
110
76
107
73
96
58
93
55
93
54
90
51
36.2
200
21.5
25.3
110
72
107
69
88
47
85
46
86
48
83
45
35.5
18
250
24.5
28.5
105
70
102
67
81
42
78
39
83
46
80
43
34.8
17.3 17.3
500
34
41.8
105
65.5
102
62.5
71
24
68
21
70
40
67
37
31.8
600
37.7
46.3
100
64.3
97
61.3
62
18
59
15
64
38.4
61
35.4
28.5
17.3
800
44.5
54.5
95
62.5
92
59.5
50
8
47
5
58
35.9
55
32.9
25.3
16.1 15.5
900
48.1
58.4
95
61.7
92
58.7
47
3
44
0
54
34.9
51
31.9
23.8
1000
49
62
92
61
89
58
43
–1.1
40
–4
49
34
46
31
22.2
15.1
1200
54.9
69
88
59.8
85
56.8
34
–9
31
–12
40
32.4
37
29.4
20.2
14.3
1300
57
–
81
–
78
–
24
–
21
–
35
–
32
–
18.3
–
1400
58.1
–
74
–
71
–
16
–
13
–
30
–
27
–
16.3
–
1500
62
–
73
–
70
–
11
–
8
–
25
–
22
–
12.3
–
* EN 50288-4-1(2004)/IEC 61156-5(2002)/IEC 61156-7(2003)
Printing on outer sheath
Electrical characteristics (LF) at 20 °C DC resistance
max.
57.1 Ω/km
LEONI MegaLine G12-150 S/F 4P H SPACE Code 35555
Insulation resistance
min.
5 GΩ x km
"VDE approval mark" "production lot code" "meter marking"
Mutual capacitance
approx.
42 pF/m
Capacitive coupling (e)
approx.
1,000 pF/km
Colour code
Signal velocity (c)
approx.
0.80
wh/bu, wh/or, wh/gn, wh/bn
Propagation delay
approx.
420 ns/100 m
Skew at 100 MHz
approx.
3 ns/100 m
Characteristic impedance
at 100 MHz
100 ± 5 Ω
Testing voltage Ueff Operating voltage
1,000 V max.
125 V
Certificates and approvals Quality mark with production control: Link performance: LEONI MegaLine® systems and further commercial connector systems Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204
Thermal characteristics
Conforms to LVD (73/23/EEC):
For fixed installation
–20 °C up to +60 °C
For mobile operation
0 °C up to +50 °C
Chemical characteristics Free from hazardous substances acc. to RoHS 2002/95/EC
Dimensions
Outer diam. approx.
Weight approx.
Cu content
mm
kg/km
kg/km
8.6
80
48
4p Package: Drum 1,000 m
www.leoni-infrastructure-datacom.com
Colour of sheath
Order no.
● Rape yellow RAL 1021
LKD 7KS8 0001 0000
MegaLine® Cu data cables
Frequency MHz
24
MegaLine® F10-130 S/F
Types KS-02YSCH 4x2xAWG 22/1 PIMF KS-02YSCH 2x(4x2xAWG 22/1 PIMF) Category 7A
S3 P4 A4 C5 E5
Construction 4 p
Conductor
Bare copper wire, AWG 22/1
Insulation Twisting element
Cellular-PE, core-diameter: nominal value 1.6 mm Pair
Individual shielding Twisting
Aluminium-bonded polyester foil, metal side outside (PiMF) 4 pairs
Overall shielding
Tinned copper braiding
Outer sheath
Halogen-free, flame-retardant compound
Security (fire behaviour) Fire behaviour Flame retardancy Halogen free Smoke density Calorific value (approx.)
acc. to IEC 60332-3-24 acc. to IEC 60754-1/2 acc. to IEC 61034-1/2 0.70 MJ/m (Sx), 1.4 MJ/m (Dx)
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Performance Better than Category 7A acc. to EN 50288 and IEC 61156, excellent NEXT, very low attenuation, excellent shielding characteristics (shielding of pairs and overall shielding), low skew, bandwidth 1,300 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Application (Ethernet, TV) Applications Installation cable for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition). Ideal for all applications from Classes D to FA Multimedia (video, data, voice) >10 GbE acc. to IEEE 802.3 an, cable sharing, VoIP, PoE.
A
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during installation after installation Tensile strength (max.) Crush strength Impact strength (number of shocks)
8 x overall diameter (min.) 4 x overall diameter (min.) 130 N (Sx), 260 N (Dx) 1,000 N/100 mm 10
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Transfer impedance at 10 MHz (nominal value) 5 mΩ/m Shielding attenuation up to 1,000 MHz (nominal value) 70 dB Coupling attenuation up to 1,000 MHz (nominal value) 85 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office
DataCenter
Industry
25
Electrical characteristics (HF) at 20 °C Attenuation dB/100 m typ.
NEXT dB typ.
Cat. 7A max.*
PSNEXT dB
Cat. 7A min.*
typ.
ACR dB at 100 m
PSACR dB at 100 m
ACRF dB at 100 m
PSACRF dB at 100 m
Cat. 7A min.*
typ.
Cat. 7A min.*
typ.
typ.
typ.
Cat. 7A min.*
Cat. 7A min.*
Cat. 7A min.*
RL dB typ.
Cat. 7A min.*
1
1.7
2.1
105
78
102
75
104
75.9
101
72.9
105
78
102
75
27.1
20
10
4.5
5.8
105
78
102
75
101
72.2
98
69.2
108
75.3
105
72.3
35.2
25 20.1
100
15.4
18.5
105
75.4
102
72.4
90
56.9
87
53.9
93
55.3
90
52.3
38.9
200
22.9
26.5
105
70.9
102
67.9
83
44.4
80
41.4
85
49.3
82
46.3
36.6
18
250
26
29.7
105
69.4
102
66.4
79
39.7
76
36.7
82
47.3
79
44.3
35.3
17.3
500
35.9
42.8
100
64.9
97
61.9
64
22.2
61
19.2
70
41.3
67
38.3
29.4
17.3
600
40.4
47.1
95
63.7
92
60.7
55
16.6
52
13.6
63
39.7
60
36.7
26.6
17.3 16.6
700
44.6
51.1
95
62.7
92
59.7
50
11.6
47
8.6
60
38.4
57
35.4
25.8
800
47.7
54.9
93
61.9
90
58.9
45
6.9
42
3.9
57
37.2
54
34.2
25
16.1
900
51.6
58.5
90
61.1
87
58.1
38
2.6
35
–0.4
53
36.2
50
33.2
23.6
15.5
1000
54.8
61.9
88
60.4
85
57.4
33
–1.5
30
–4.5
48
35.3
45
32.3
22.3
15.1
1100
56.9
–
87
–
84
–
30
–
27
–
44
–
41
–
21.4
–
1300
61.4
–
80
–
77
–
21
–
18
–
39
–
36
–
18.3
–
* EN 50288-4-1 (2004)/IEC 61156-5 (2002) Configuring multiple single elements can result in attenuation values that are up to 3 % higher and frequency-selective reflections in the case of multi-types.
Printing on outer sheath 4 p
Electrical characteristics (LF) at 20 °C DC resistance
max.
57.1 Ω/km
LEONI MegaLine F10-130 S/F 4P H SPACE Code 34455
Insulation resistance
min.
5 GΩ x km
"VDE approval mark" "production lot code" "meter marking"
Mutual capacitance
approx.
40 pF/m
Capacitive coupling (e)
approx.
1,500 pF/km
Colour code
Signal velocity (c)
approx.
0.80
wh/bu, wh/or, wh/gn, wh/bn
Propagation delay
approx.
420 ns/100 m
Skew at 100 MHz
approx.
5 ns/100 m
Characteristic impedance
at 100 MHz
100 ± 5 Ω
Testing voltage Ueff Operating voltage
1,000 V max.
125 V
Certificates and approvals Quality mark with production control: Link performance: LEONI MegaLine® systems and further commercial connector systems Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204
Thermal characteristics
Conforms to LVD (73/23/EEC):
For fixed installation
–20 °C up to +60 °C
For mobile operation
0 °C up to +50 °C
Chemical characteristics Free from hazardous substances acc. to RoHS 2002/95/EC
Dimensions
Outer diam. approx.
Weight approx.
Cu content
Colour of sheath
Order no.
mm
kg/km
kg/km
4p
8.6
80
45
● Rape yellow RAL 1021
LKD 7KS7 0001 0000
2x4p
8.6 x 17.5
162
90
● Rape yellow RAL 1021
LKD 7KS7 0002 0000
Package: Drum 1,000 m
www.leoni-infrastructure-datacom.com
MegaLine® Cu data cables
Frequency MHz
26
MegaLine® F10-125 S/F
Types KS-02YSCH 4x2x0,62 mm/~AWG 22/1 PIMF
Category 7A
S3 P4 A4 C5 E5
Construction 4 p
Conductor
Bare copper wire, 0.62 mm/~AWG 22/1
Insulation Twisting element
Cellular-PE, core-diameter: nominal value 1.5 mm Pair
Individual shielding Twisting
Aluminium-bonded polyester foil, metal side outside (PiMF) 4 pairs
Overall shielding
Tinned copper braiding
Outer sheath
Halogen-free, flame-retardant compound
Security (fire behaviour) Fire behaviour Flame retardancy Halogen free Smoke density Calorific value
acc. to IEC 60332-3-24 acc. to IEC 60754-1/2 acc. to IEC 61034-1/2 0.65 (approx. value)
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Leistungsmerkmale Better than Category 7A acc. to EN 50288 and IEC 61156, excellent NEXT, very low attenuation, excellent shielding characteristics (shielding of pairs and overall shielding), low skew, bandwidth 1,300 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Application (Ethernet, TV) Applications Installation cable for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition). Ideal for all applications from Classes D to FA Multimedia (video, data, voice) >10 GbE acc. to IEEE 802.3 an, cable sharing, VoIP, PoE.
A
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during installation after installation Tensile strength (max.) Crush strength Impact strength (number of shocks)
8 x overall diameter (min.) 4 x overall diameter (min.) 110 N 1,000 N/100 mm 10
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Transfer impedance at 10 MHz (nominal value) 5 mΩ/m Shielding attenuation up to 1,000 MHz (nominal value) 70 dB Coupling attenuation up to 1,000 MHz (nominal value) 85 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office
DataCenter
Industry
27
Electrical characteristics (HF) at 20 °C Attenuation dB/100 m typ.
NEXT dB typ.
Cat. 7A max.*
PSNEXT dB
Cat. 7A min.*
typ.
ACR dB at 100 m
PSACR dB at 100 m
ACRF dB at 100 m
PSACRF dB at 100 m
Cat. 7A min.*
typ.
Cat. 7A min.*
typ.
typ.
typ.
Cat. 7A min.*
Cat. 7A min.*
Cat. 7A min.*
RL dB typ.
Cat. 7A min.*
1
1.8
2.1
105
78
102
75
104
75.9
101
72.9
105
78
102
75
27.1
20
10
4.7
5.8
105
78
102
75
101
72.2
98
69.2
108
75.3
105
72.3
35.2
25 20.1
100
15.9
18.5
105
75.4
102
72.4
89
56.9
86
53.9
93
55.3
90
52.3
38.9
200
23.5
26.5
105
70.9
102
67.9
81
44.4
78
41.4
85
49.3
82
46.3
36.6
18
250
26.6
29.7
105
69.4
102
66.4
79
39.7
76
36.7
82
47.3
79
44.3
35.3
17.3
500
37
42.8
100
64.9
97
61.9
63
22.2
60
19.2
70
41.3
67
38.3
29.4
17.3
600
41.8
47.1
95
63.7
92
60.7
53
16.6
50
13.6
63
39.7
60
36.7
26.6
17.3 16.6
700
45.2
51.1
95
62.7
92
59.7
50
11.6
47
8.6
60
38.4
57
35.4
25.8
800
48
54.9
93
61.9
90
58.9
45
6.9
42
3.9
57
37.2
54
34.2
25
16.1
900
52.3
58.5
90
61.1
87
58.1
38
2.6
35
–0.4
53
36.2
50
33.2
23.6
15.5
1000
55.2
61.9
88
60.4
85
57.4
33
–1.5
30
–4.5
48
35.3
45
32.3
22.3
15.1
1100
57.6
–
87
–
84
–
29
–
26
–
44
–
41
–
21.4
–
1300
64.9
–
80
–
77
–
15
–
13
–
39
–
36
–
18.3
–
* EN 50288-9 (draft)/EN 50288-4-1 (2004) / IEC 61156-5 (2009)
Printing on outer sheath 4 p
Electrical characteristics at 20 °C DC resistance
max.
65 Ω/km
LEONI MegaLine F10-125 S/F 4P H SPACE Code 34455
Insulation resistance
min.
5 GΩ x km
"VDE approval mark" "production lot code" "meter marking"
Mutual capacitance
approx.
42 pF/m
Capacitive coupling (e)
approx.
1,500 pF/km
Colour code
Signal velocity (c)
approx.
0.80
wh/bu, wh/or, wh/gn, wh/bn
Propagation delay
approx.
420 ns/100 m
Skew at 100 MHz
approx.
5 ns/100 m
Characteristic impedance
at 100 MHz
100 ± 5 Ω
Testing voltage Ueff Operating voltage
1000 V max.
125 V
Certificates and approvals Quality mark with production control: Link performance: LEONI MegaLine® systems and further commercial connector systems Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204
Thermal characteristics
Conforms to LVD (73/23/EEC):
For fixed installation
–20 °C up to +60 °C
For mobile operation
0 °C up to +50 °C
Chemical characteristics Free from hazardous substances acc. to RoHS 2002/95/EC
Dimensions
Outer diam. approx.
Weight approx.
Cu content
mm
kg/km
kg/km
8.1
68
38
4P Package: Drum 1,000 m
www.leoni-infrastructure-datacom.com
Colour of sheath
Order no.
● Rape yellow RAL 1021
LKD 7KS7 0253 0000
MegaLine® Cu data cables
Frequency MHz
28
MegaLine® F10-115 S/F
Types KS-02YSCH 4x2xAWG 23/1 PIMF KS-02YSCH 2/4/6x(4x2xAWG 23/1 PIMF) Category 7A
S3 P4 A4 C4 E5
Construction 4 p
Conductor
Bare copper wire, AWG 23/1
Insulation Twisting element
Cellular-PE, core-diameter: nominal value 1.4 mm Pair
Individual shielding Twisting
Aluminium-bonded polyester foil, metal side outside (PiMF) 4 pairs
Overall shielding
Tinned copper braiding
Outer sheath
Halogen-free, flame-retardant compound
Security (fire behaviour) Fire behaviour Flame retardancy Halogen free Smoke density Calorific value (approx.)
acc. to IEC 60332-3-24 acc. to IEC 60754-1/2 acc. to IEC 61034-1/2 0.60 MJ/m (Sx), 1.2 MJ/m (Dx), 4.24 MJ/m (4 p), 6.29 MJ/m (6 p)
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Performance Better than Category 7A acc. to EN 50288 and IEC 61156 excellent NEXT, very low attenuation, excellent shielding characteristics (shielding of pairs and overall shielding), low skew, bandwidth 1,150 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Application (Ethernet, TV) Applications Installation cable for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition). Ideal for all applications from Classes D to FA Multimedia (video, data, voice) >10 GbE acc. to IEEE 802.3 an, cable sharing, VoIP, PoE.
A
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during installation after installation Tensile strength (max.) Crush strength Impact strength (number of shocks)
8 x overall diameter (min.) 4 x overall diameter (min.) 110 N (Sx), 220 N (Dx), 440 N (4 p), 650 N (6 p) 1,000 N/100 mm 10
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Transfer impedance at 10 MHz (nominal value) 5 mΩ/m Shielding attenuation up to 1,000 MHz (nominal value) 70 dB Coupling attenuation up to 1,000 MHz (nominal value) 85 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office
DataCenter
Industry
29
Electrical characteristics (HF) at 20 °C Attenuation dB/100 m typ.
NEXT dB
PSNEXT dB
ACR dB at 100 m
PSACR dB at 100 m
ACRF dB at 100 m
PSACRF dB at 100 m
Cat. 7A min.*
typ.
typ.
typ.
Cat. 7A max.*
typ.
Cat. 7A min.*
typ.
Cat. 7A min.*
typ.
Cat. 7A min.*
Cat. 7A min.*
RL dB
Cat. 7A min.*
typ.
Cat. 7A min.*
1
1.9
2.1
105
78
102
75
104
75.9
101
72.9
98
78
95
75
26.6
20
10
4.8
5.8
105
78
102
75
101
72.2
98
69.2
103
75.3
100
72.3
35.3
25 20.1
100
16.3
18.5
105
75.4
102
72.4
89
56.9
86
53.9
89
55.3
86
52.3
39.6
200
24.3
26.5
105
70.9
102
67.9
81
44.4
78
41.4
82
49.3
79
46.3
36
18
250
27.5
29.7
105
69.4
102
66.4
78
39.7
75
36.7
79
47.3
76
44.3
34
17.3
500
37.9
42.8
100
64.9
97
61.9
62
22.2
59
19.2
67
41.3
64
38.3
29
17.3
600
42.4
47.1
95
63.7
92
60.7
53
16.6
50
13.6
60
39.7
57
36.7
25.4
17.3 16.6
700
47.2
51.1
95
62.7
92
59.7
48
11.6
45
8.6
57
38.4
54
35.4
24.6
800
50.3
54.9
93
61.9
90
58.9
43
6.9
40
3.9
53
37.2
50
34.2
23.5
16.1
900
54.6
58.5
90
61.1
87
58.1
35
2.6
32
–0.4
49
36.2
46
33.2
22.6
15.5
1000
58
61.9
88
60.4
85
57.4
30
–1.5
27
–4.5
44
35.3
41
32.3
21.5
15.1
1150
61.9
–
86
–
83
–
25
–
22
–
39
–
36
–
20.6
–
1200
64
–
85
–
82
–
21
–
18
–
35
–
32
–
19
–
* EN 50288-4-1 (2004)/IEC 61156-5 (2002)
Printing on outer sheath 4 p
Electrical characteristics (LF) at 20 °C DC resistance
max.
75 Ω/km
LEONI MegaLine F10-115 S/F 4P H SPACE Code 34445
Insulation resistance
min.
5 GΩ x km
"VDE approval mark" "production lot code" "meter marking"
Mutual capacitance
approx.
42 pF/m
Capacitive coupling (e)
approx.
1,500 pF/km
Colour code
Signal velocity (c)
approx.
0.80
wh/bu, wh/or, wh/gn, wh/bn
Propagation delay
approx.
420 ns/100 m
Skew at 100 MHz
approx.
5 ns/100 m
Characteristic impedance
at 100 MHz
100 ± 5 Ω
Testing voltage Ueff Operating voltage
1,000 V max.
125 V
Certificates and approvals Quality mark with production control: Link performance: LEONI MegaLine® systems and further commercial connector systems Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204
Thermal characteristics
Conforms to LVD (73/23/EEC):
For fixed installation
–20 °C up to +60 °C
For mobile operation
0 °C up to +50 °C
Chemical characteristics Free from hazardous substances acc. to RoHS 2002/95/EC
Dimensions
Outer diam. approx.
Weight approx.
Cu content
Colour of sheath
Order no.
mm
kg/km
kg/km
4p
7.5
67
37
● Rape yellow RAL 1021
LKD 7KS7 0008 0000
2x4p
7.5 x 15.2
136
74
● Rape yellow RAL 1021
LKD 7KS7 0009 0000
4x4p
19.9
365
148
● Rape yellow RAL 1021
LKD 7KS7 0161 0000
6x4p
23.6
514
222
● Rape yellow RAL 1021
LKD 7KS7 0186 0000
Package: Drum 1,000 m
www.leoni-infrastructure-datacom.com
MegaLine® Cu data cables
Frequency MHz
30
MegaLine® F6-90 S/F
Types KS-02YSCH 4x2xAWG 23/1 PIMF KS-02YSCH 2/4/6/8x(4x2xAWG 23/1 PIMF) Category 7
S3 P3 A4 C4 E5
Construction 4 p
Conductor
Bare copper wire, AWG 23/1
Insulation Twisting element
Cellular-PE, core-diameter: nominal value 1.4 mm Pair
Individual shielding Twisting
Aluminium-bonded polyester foil, metal side outside (PiMF) 4 pairs
Overall shielding
Tinned copper braiding
Outer sheath
Halogen-free, flame-retardant compound
Security (fire behaviour) Fire behaviour Flame retardancy Halogen free Smoke density Calorific value (approx.)
acc. to IEC 60332-3-24 acc. to IEC 60754-1/2 acc. to IEC 61034-1/2 0.60 MJ/m (Sx), 1.2 MJ/m (Dx), 4.3 MJ/m (4 p), 6.9 MJ/m (6 p), 9.6 MJ/m (8 p)
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Performance Better than Category 7 acc. to EN 50288 and IEC 61156 excellent NEXT, excellent shielding characteristics (shielding of pairs and overall shielding), low skew, bandwidth 1,000 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Application (Ethernet, TV) Applications Installation cable for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition). Ideal for all applications from Classes D to F Multimedia (video, data, voice) >10 GbE acc. to IEEE 802.3 an, cable sharing, VoIP, PoE.
A
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during installation after installation Tensile strength (max.) Crush strength Impact strength (number of shocks)
8 x overall diameter (min.) 4 x overall diameter (min.) 110 N (Sx), 220 N (Dx), 400 N (4 p), 600 N (6 p), 850 N (8 p) 1,000 N/100 mm 10
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Transfer impedance at 10 MHz (nominal value) 5 mΩ/m Shielding attenuation up to 1,000 MHz (nominal value) 70 dB Coupling attenuation up to 1,000 MHz (nominal value) 85 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office
DataCenter
Industry
31
Electrical characteristics (HF) at 20 °C Attenuation dB/100 m typ.
NEXT dB
Cat. 7 max.*
typ.
PSNEXT dB
Cat. 7 min.*
typ.
ACR dB at 100 m
PSACR dB at 100 m
ELFEXT dB at 100 m
PSELFEXT dB at 100 m
Cat. 7 min.*
typ.
Cat. 7 min.*
typ.
typ.
Cat. 7 min.*
typ.
Cat. 7 min.*
typ.
Cat. 7 min.* 23
Cat. 7 min.*
RL dB
1
1.9
2
102
80
99
77
101
78
98
75
109
80
106
77
25.4
10
4.8
5.7
102
80
99
77
98
74
95
71
108
74
105
71
31.1
25
100
16.4
18.5
102
72
99
69
86
54
83
51
93
54
90
51
33.2
20.1
200
24.5
26.8
102
68
99
65
78
41
75
38
85
48
82
45
33.2
18
250
27.8
30.2
102
66
99
63
75
36
72
33
82
46
79
43
33.4
17.3
450
36.1
41.6
97
63
94
60
61
21
58
18
72
41
69
38
31.4
17.3
500
38.2
44.1
97
62
94
59
59
18
56
15
68
40
65
37
30.5
17.3
600
42.9
48.9
92
61
89
58
49
12
46
9
62
38
59
35
27.6
17.3
700
47.7
–
92
–
89
–
44
–
41
–
59
–
56
–
26.2
–
800
50.8
–
90
–
87
–
39
–
36
–
56
–
53
–
23.9
–
900
55.1
–
85
–
82
–
30
–
27
–
52
–
49
–
21.7
–
1000
58.0
–
80
–
77
–
22
–
19
–
42
–
39
–
18.0
–
* EN 50288-4-1(2004)/IEC 61156-5(2002) Stranding together multiple single elements can result in attenuation values that are up to 5 % higher and frequency-selective reflections in the case of multi-types.
Printing on outer sheath
Electrical characteristics (LF) at 20 °C DC resistance
max.
75 Ω/km
LEONI MegaLine F6-90 S/F 4P H SPACE Code 33445
Insulation resistance
min.
5 GΩ x km
"VDE approval mark" "production lot code" "meter marking"
Mutual capacitance
approx.
42 pF/m
Capacitive coupling (e)
approx.
1,500 pF/km
Colour code
Signal velocity (c)
approx.
0.80
wh/bu, wh/or, wh/gn, wh/bn
Propagation delay
approx.
420 ns/100 m
Skew at 100 MHz
approx.
5 ns/100 m
Characteristic impedance
at 100 MHz
100 ± 5 Ω
Testing voltage Ueff Operating voltage
1,000 V max.
125 V
Certificates and approvals Quality mark with production control: Link performance: LEONI MegaLine® systems and further commercial connector systems Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204
Thermal characteristics
Conforms to LVD (73/23/EEC):
For fixed installation
–20 °C up to +60 °C
For mobile operation
0 °C up to +50 °C
Chemical characteristics Free from hazardous substances acc. to RoHS 2002/95/EC
Dimensions
Outer diam. approx.
Weight approx.
Cu content
Colour of sheath
Order no.
mm
kg/km
kg/km
4p
7.4
57
35
● Rape yellow RAL 1021
LKD 7KS7 0010 0000 LKD 7KS7 0011 0000
2x4p
7.5 x 15.2
117
70
● Rape yellow RAL 1021
4x4p
18.9
338
148
● Rape yellow RAL 1021
LKD 7KS7 0114 0000
6x4p
24.9
507
222
● Rape yellow RAL 1021
LKD 7KS7 0198 0000
8x4p
27.9
674
296
● Rape yellow RAL 1021
LKD 7KS7 0194 0000
Package: Drum 1,000 m
www.leoni-infrastructure-datacom.com
MegaLine® Cu data cables
Frequency MHz
32
MegaLine® E5-70 S/F
Types KS-02YSCH 4x2xAWG 23/1 PIMF KS-02YSCH 2x(4x2xAWG 23/1 PIMF) Category 6A
S3 P2 A3 C4 E4
Construction 4 p
Conductor
Bare copper wire, AWG 23/1
Insulation Twisting element
Cellular-PE, core-diameter: nominal value 1.4 mm Pair
Individual shielding Twisting
Aluminium-bonded polyester foil, metal side outside (PiMF) 4 pairs
Overall shielding
Tinned copper braiding
Outer sheath
Halogen-free, flame-retardant compound
Security (Fire behaviour) Fire behaviour Flame retardancy Halogen free Smoke density Calorific value (approx.)
acc. to IEC 60332-3-24 acc. to IEC 60754-1/2 acc. to IEC 61034-1/2 0.60 MJ/m (Sx), 1.2 NJ/m (Dx)
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Performance Better than Category 6A acc. to EN 50288 and IEC 61156 very good NEXT, very good shielding characteristics (shielding of pairs and overall shielding), low skew, bandwidth 700 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Application (Ethernet, TV) Applications Installation cable for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition). Ideal for all applications from Classes D to EA up to 10 GbE acc. to IEEE 802.3 an, cable sharing, VoIP, PoE.
A
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during installation after installation Tensile strength (max.) Crush strength Impact strength (number of shocks)
8 x overall diameter (min.) 4 x overall diameter (min.) 110 N (Sx), 220 N (Dx) 1,000 N/100 mm 10
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Transfer impedance at 10 MHz (nominal value) 5 mΩ/m Shielding attenuation up to 1,000 MHz (nominal value) 60 dB Coupling attenuation up to 1,000 MHz (nominal value) 80 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 33
Electrical characteristics (HF) at 20 °C Attenuation dB/100 m typ.
NEXT dB typ.
Cat. 6A max.*
PSNEXT dB
Cat. 6A min.*
typ.
Cat. 6A min.*
ACR dB at 100 m
PSACR dB at 100 m
ACRF dB at 100 m
PSACRF dB at 100 m
typ.
Cat. 6A min.*
typ.
Cat. 6A min.*
typ.
Cat. 6A min.*
typ.
RL dB
Cat. 6A min.*
typ.
Cat. 6A min.*
1
1.9
2.1
95
75.3
92
72.3
93
73.2
90
70.2
91
68
88
65
26
20
10
5.2
5.9
90
60.3
87
57.3
85
54.4
82
51.4
96
48
93
45
35.9
25 20.1
100
17.7
19.1
75
45.3
72
42.3
57
26.2
54
23.2
90
28
87
25
37.2
200
26.4
27.6
68
40.8
65
37.8
42
13.2
39
10.2
78
22
75
19
33.1
18
250
29.9
31.1
66
39.3
63
36.3
36
8.3
33
5.3
75
20
72
17
30.5
17.3
300
31.9
34.3
65
38.1
62
35.1
33
3.9
30
0.9
72
18.5
69
15.5
29.9
17.3
450
38.9
42.7
63
35.5
60
32.5
24
–7.2
21
–10.2
69
14.9
66
11.9
28.9
17.3
500
41.2
45.3
61
34.8
58
31.8
20
–10.4
17
–13.4
66
14
63
11
28.3
17.3
600
46.2
–
57
–
54
–
11
–
8
–
60
–
57
–
27.2
–
700
51.4
–
54
–
51
–
3
–
0
–
56
–
53
–
26.2
–
* EN 50288-10-1 (draft)/EN 50288-5-1 (2004)/IEC 61156-5 (2009)
Printing on outer sheath 4 p
Electrical characteristics (LF) at 20 °C DC resistance
max.
82 Ω/km
LEONI MegaLine E5-70 S/F 4P H SPACE Code 32344
Insulation resistance
min.
5 GΩ x km
"VDE approval mark" "production lot code" "meter marking"
Mutual capacitance
approx.
42 pF/m
Capacitive coupling (e)
approx.
1,500 pF/km
Colour code
Signal velocity (c)
approx.
0.80
wh/bu, wh/or, wh/gn, wh/bn
Propagation delay
approx.
420 ns/100 m
Skew at 100 MHz
approx.
7 ns/100 m
Characteristic impedance
at 100 MHz
100 ± 5 Ω
Testing voltage Ueff Operating voltage
1,000 V max.
125 V
Certificates and approvals Quality mark with production control: Link performance: LEONI MegaLine® systems and further commercial connector systems Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204
Thermal characteristics
Conforms to LVD (73/23/EEC):
For fixed installation
–20 °C up to +60 °C
For mobile operation
0 °C up to +50 °C
Chemical characteristics Free from hazardous substances acc. to RoHS 2002/95/EC
Dimensions
Outer diam. approx.
Weight approx.
Cu content
Colour of sheath
Order no.
mm
kg/km
kg/km
4p
7.4
55
30
● Rape yellow RAL 1021
LKD 7KS6 0024 0000
2x4p
7.4 x 15.0
112
60
● Rape yellow RAL 1021
LKD 7KS6 0025 0000
Package: Drum 1,000 m
www.leoni-infrastructure-datacom.com
MegaLine® Cu data cables
Frequency MHz
34
MegaLine® E5-70 F/F
Types KS-02YS(ST)H 4x2xAWG 23/1 PIMF KS-02YS(ST)H 2x(4x2xAWG 23/1 PIMF) Category 6A
S3 P2 A3 C4 E3
Construction 4 p
Conductor
Bare copper wire, AWG 23/1
Insulation Twisting element
Cellular-PE, core-diameter: nominal value 1.4 mm Pair
Individual shielding Twisting
Aluminium-bonded polyester foil, metal side outside (PiMF) 4 pairs
Overall shielding
Aluminium-bonded polyester foil, metal side inside and underlayed tinned copper drain wire
Outer sheath
Halogen-free, flame-retardant compound
Security (fire behaviour) Fire behaviour Flame retardancy Halogen free Smoke density Calorific value (approx.)
acc. to IEC 60332-3-24 acc. to IEC 60754-1/2 acc. to IEC 61034-1/2 0.60 MJ/m (Sx), 1.2 MJ/m (Dx)
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Performance Better than Category 6A acc. to EN 50288 and IEC 61156 very good NEXT, good shielding characteristics (shielding of pairs and overall shielding), low skew, bandwidth 700 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Application (Ethernet, TV) Applications Installation cable for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition). Ideal for all applications from Classes D to EA up to 10 GbE acc. to IEEE 802.3 an, cable sharing, VoIP, PoE.
A
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during installation after installation Tensile strength (max.) Crush strength Impact strength (number of shocks)
8 x overall diameter (min.) 4 x overall diameter (min.) 110 N (Sx), 220 N (Dx) 1,000 N/100 mm 10
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Transfer impedance at 10 MHz (nominal value) 50 mΩ/m Shielding attenuation up to 1,000 MHz (nominal value) 60 dB Coupling attenuation up to 1,000 MHz (nominal value) 70 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 35
Electrical characteristics (HF) at 20 °C Attenuation dB/100 m typ.
NEXT dB typ.
Cat. 6A max.*
PSNEXT dB
Cat. 6A min.*
typ.
Cat. 6A min.*
ACR dB at 100 m
PSACR dB at 100 m
ACRF dB at 100 m
PSACRF dB at 100 m
typ.
Cat. 6A min.*
typ.
Cat. 6A min.*
typ.
Cat. 6A min.*
typ.
Cat. 6A min.*
RL dB typ.
Cat. 6A min.*
1
1.9
2.1
95
75.3
92
72.3
93
73.2
90
70.2
91
68
88
65
25.1
–
10
5.2
5.9
90
60.3
87
57.3
85
54.4
82
51.4
96
48
93
45
35.2
25 20.1
100
17.7
19.1
75
45.3
72
42.3
57
26.2
54
23.2
90
28
87
25
37.2
200
26.4
27.6
68
40.8
65
37.8
42
13.2
39
10.2
78
22
75
19
31.1
18
250
29.9
31.1
66
39.3
63
36.3
36
8.3
33
5.3
75
20
72
17
29.5
17.3
300
31.9
34.3
65
38.1
62
35.1
33
3.9
30
0.9
72
18.5
69
15.5
28.3
17.3
450
38.9
42.7
63
35.5
60
32.5
24
–7.2
21
–10.2
69
14.9
66
11.9
26.7
17.3
500
41.2
45.3
61
34.8
58
31.8
20
–10.4
17
–13.4
66
14
63
11
26.3
17.3
600
46.2
–
57
–
54
–
11
–
8
–
60
–
57
–
25.8
–
700
51.4
–
54
–
51
–
3
–
0
–
56
–
53
–
–
–
* EN 50288-10-1 (draft)/EN 50288-5-1(2004)/IEC 61156-5(2009)
Printing on outer sheath 4 p
Electrical characteristics (LF) at 20 °C DC resistance
max.
82 Ω/km
LEONI MegaLine E5-70 F/F 4P H SPACE Code 32343
Insulation resistance
min.
5 GΩ x km
"VDE approval mark" "production lot code" "meter marking"
Mutual capacitance
approx.
42 pF/m
Capacitive coupling (e)
approx.
1,500 pF/km
Colour code
Signal velocity (c)
approx.
0.80
wh/bu, wh/or, wh/gn, wh/bn
Propagation delay
approx.
417 ns/100 m
Skew at 100 MHz
approx.
7 ns/100 m
Characteristic impedance
at 100 MHz
100 ± 5 Ω
Testing voltage Ueff Operating voltage
1,000 V max.
125 V
Certificates and approvals Quality mark with production control: Link performance: LEONI MegaLine® systems and further commercial connector systems Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204
Thermal characteristics
Conforms to LVD (73/23/EEC):
For fixed installation
–20 °C up to +60 °C
For mobile operation
0 °C up to +50 °C
Chemical characteristics Free from hazardous substances acc. to RoHS 2002/95/EC
Dimensions
Outer diam. approx.
Weight approx.
Cu content
mm
kg/km
kg/km
Colour of sheath
Order no.
4p
7.5
58
23,5
● Rape yellow RAL 1021
LKD 7KS6 0022 0000
2x4p
7.5 x 15.2
120
47
● Rape yellow RAL 1021
LKD 7KS6 0023 0000
Package: Drum 1,000 m
www.leoni-infrastructure-datacom.com
MegaLine® Cu data cables
Frequency MHz
36
MegaLine® E5-60 U/F
Types KS-02YSH 4x2xAWG 23/1 PIMF KS-02YSH 2x(4x2xAWG 23/1 PIMF) Category 6A
S3 P2 A3 C4 E3
Construction 4 p
Conductor
Bare copper wire, AWG 23/1
Insulation Twisting element
Cellular-PE, core-diameter: nominal value 1.4 mm Pair
Individual shielding Twisting
Aluminium-bonded polyester foil, metal side outside (PiMF) 4 pairs
Overall shielding
Plastic foil (optional) and underlayed tinned copper drain wire AWG 24/1
Outer sheath
Halogen-free, flame-retardant compound
Security (fire behaviour) Fire behaviour Flame retardancy Halogen free Smoke density Calorific value (approx.)
acc. to IEC 60332-3-24 acc. to IEC 60754-1/2 acc. to IEC 61034-1/2 0.60 MJ/m (Sx), 1.2 MJ/m (Dx)
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Performance Better than Category 6A acc. to EN 50288 and IEC 61156 very good NEXT, good shielding characteristics (shielding of pairs and overall shielding), low skew, bandwidth 600 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Application (Ethernet, TV) Applications Installation cable for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition). Ideal for all applications from Classes D to EA up to 10 GbE acc. to IEEE 802.3 an, cable sharing, VoIP, PoE.
A
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during installation after installation Tensile strength (max.) Crush strength Impact strength (number of shocks)
8 x overall diameter (min.) 4 x overall diameter (min.) 110 N (Sx), 220 N (Dx) 1,000 N/100 mm 10
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Transfer impedance at 10 MHz (nominal value) 50 mΩ/m Shielding attenuation up to 1,000 MHz (nominal value) 55 dB Coupling attenuation up to 1,000 MHz (nominal value) 65 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 37
Electrical characteristics (HF) at 20 °C Attenuation dB/100 m typ.
NEXT dB typ.
Cat. 6A max.*
PSNEXT dB
Cat. 6A min.*
typ.
Cat. 6A min.*
ACR dB at 100 m
PSACR dB at 100 m
ACRF dB at 100 m
PSACRF dB at 100 m
typ.
Cat. 6A min.*
typ.
Cat. 6A min.*
typ.
Cat. 6A min.*
typ.
Cat. 6A min.*
RL dB typ.
Cat. 6A min.*
1
1.9
2.1
95
75.3
92
72.3
93
73.2
90
70.2
91
68
88
65
25.1
–
10
5.2
5.9
90
60.3
87
57.3
85
54.4
82
51.4
96
48
93
45
35.2
25 20.1
100
17.7
19.1
75
45.3
72
42.3
57
26.2
54
23.2
90
28
87
25
37.2
200
26.4
27.6
68
40.8
65
37.8
42
13.2
39
10.2
78
22
75
19
31.1
18
250
29.9
31.1
66
39.3
63
36.3
36
8.3
33
5.3
75
20
72
17
29.5
17.3
300
31.9
34.3
65
38.1
62
35.1
33
3.9
30
0.9
72
18.5
69
15.5
28.3
17.3
450
38.9
42.7
63
35.5
60
32.5
24
–7.2
21
–10.2
69
14.9
66
11.9
26.7
17.3
500
41.2
45.3
61
34.8
58
31.8
20
–10.4
17
–13.4
66
14
63
11
26.3
17.3
600
46.2
–
57
–
54
–
11
–
8
–
60
–
57
–
25.8
–
* EN 50288-10-1 (draft)/EN 50288-5-1(2004)/IEC 61156-5(2009)
Printing on outer sheath 4 p
Electrical characteristics (LF) at 20 °C DC resistance
max.
82 Ω/km
LEONI MegaLine E5-60 U/F 4P H SPACE Code 32343
Insulation resistance
min.
5 GΩ x km
"VDE approval mark" "production lot code" "meter marking"
Mutual capacitance
approx.
42 pF/m
Capacitive coupling (e)
approx.
1,500 pF/km
Colour code
Signal velocity (c)
approx.
0.80
wh/bu, wh/or, wh/gn, wh/bn
Propagation delay
approx.
420 ns/100 m
Skew at 100 MHz
approx.
7 ns/100 m
Characteristic impedance
at 100 MHz
100 ± 5 Ω
Testing voltage Ueff Operating voltage
1,000 V max.
125 V
Certificates and approvals Quality mark with production control: Link performance: LEONI MegaLine® systems and further commercial connector systems Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204
Thermal characteristics
Conforms to LVD (73/23/EEC):
For fixed installation
–20 °C up to +60 °C
For mobile operation
0 °C up to +50 °C
Chemical characteristics Free from hazardous substances acc. to RoHS 2002/95/EC
Dimensions
Outer diam. approx.
Weight approx.
Cu content
Colour of sheath
Order no.
mm
kg/km
kg/km
4p
7.2
53
25
● Rape yellow RAL 1021
LKD 7KS6 0035 0000
2x4p
7.4 X 15.0
112
50
● Rape yellow RAL 1021
LKD 7KS6 0036 0000
Package: Drum 1,000 m
www.leoni-infrastructure-datacom.com
MegaLine® Cu data cables
Frequency MHz
38
MegaLine® E2-45 U/F
Types KS-02YSH 4x2xAWG 23/1 PIMF KS-02YSH 2x(4x2xAWG 23/1 PIMF) Category 6
S2 P1 A2 C4 E2
Construction 4 p
Conductor
Bare copper wire, AWG 23/1
Insulation Twisting element
Cellular-PE, core-diameter: nominal value 1.4 mm Pair
Individual shielding Twisting
Aluminium-bonded polyester foil, metal side outside (PiMF) 4 pairs
Tape
Plastic foil (optional) and underlayed tinned copper drain wire AWG 24/1
Outer sheath
Halogen-free, flame-retardant compound
Security (fire behaviour) Fire behaviour Flame retardancy Halogen free Smoke density Calorific value (approx.)
acc. to IEC 60332-1-2 acc. to IEC 60754-1/2 acc. to IEC 61034-1/2 0.60 MJ/m (Sx), 1.2 NJ/m (Dx)
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Performance Better than Category 6 acc. to EN 50288 and IEC 61156 very good NEXT, low skew, bandwidth 450 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Application (Ethernet, TV) Applications Installation cable for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition). Ideal for all applications from Classes D to E up to 1 GbE acc. to IEEE 802.3 ab, cable sharing, VoIP, PoE.
A
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during installation after installation Tensile strength (max.) Crush strength Impact strength (number of shocks)
8 x overall diameter (min.) 4 x overall diameter (min.) 110 N (Sx), 220 N (Dx) 1,000 N/100 mm 10
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Transfer impedance at 10 MHz (nominal value) 80 mΩ/m Shielding attenuation up to 1,000 MHz (nominal value) 50 dB Coupling attenuation up to 1,000 MHz (nominal value) 60 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 39
Electrical characteristics (HF) at 20 °C Attenuation dB/100 m typ.
NEXT dB
Cat. 6 max.*
PSNEXT dB
typ.
Cat. 6 min.*
ACR dB at 100 m
PSACR dB at 100 m
ELFEXT dB at 100 m
PSELFEXT dB at 100 m typ.
Cat. 6 min.*
typ.
Cat. 6 min.*
typ.
Cat. 6 min.*
typ.
Cat. 6 min.*
typ.
Cat. 6 min.*
RL dB typ.
Cat. 6 min.*
1
1.9
2.1
95
66
92
64
93
64
90
62
88
66
85
64
25.4
–
4
3.2
3.8
95
65
92
63
92
61
89
59
89
58
86
55
28.6
23
10
5.2
6
90
59
87
57
85
53
82
51
92
50
89
47
33.5
25
16
7
7.6
90
56
87
54
83
49
80
47
98
46
95
43
35.6
25
31.25
9.9
10.7
85
52
82
50
75
41
72
39
98
40
95
37
37
23.6
62.5
13.5
15.5
80
47
77
45
66
32
63
30
95
34
92
31
35.9
21.5
100
17.9
19.9
75
44
72
42
57
24
54
22
88
30
85
27
34.3
20.1
155
22.5
25.3
72
41
69
39
49
16
46
14
81
26
78
23
32.2
18.8
200
26.9
29.1
68
40
65
38
41
11
38
9
75
24
72
21
31.3
18
250
30.4
33
66
38
63
36
36
5
33
3
72
22
69
19
29.2
17.3
300
33.1
–
65
–
62
–
32
–
29
–
69
–
66
–
28
–
450
39.3
–
63
–
60
–
24
–
21
–
64
–
61
–
27
–
* EN 50288-5-1(2004)/IEC 61156-5(2002)
Printing on outer sheath 4 p
Electrical characteristics (LF) at 20 °C DC resistance
max.
82 Ω/km
LEONI MegaLine E2-45 U/F 4P H SPACE Code 21242
Insulation resistance
min.
5 GΩ x km
"VDE approval mark" "production lot code" "meter marking"
Mutual capacitance
approx.
42 pF/m
Capacitive coupling (e)
approx.
1,500 pF/km
Colour code
Signal velocity (c)
approx.
0.80
wh/bu, wh/or, wh/gn, wh/bn
Propagation delay
approx.
420 ns/100 m
Skew at 100 MHz
approx.
7 ns/100 m
Characteristic impedance
at 100 MHz
100 ± 5 Ω
Testing voltage Ueff Operating voltage
1,000 V max.
125 V
Certificates and approvals Quality mark with production control: Link performance: LEONI MegaLine® systems and further commercial connector systems Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204
Thermal characteristics
Conforms to LVD (73/23/EEC):
For fixed installation
–20 °C up to +60 °C
For mobile operation
0 °C up to +50 °C
Chemical characteristics Free from hazardous substances acc. to RoHS 2002/95/EC
Dimensions
Outer diam. approx.
Weight approx.
Cu content
Colour of sheath
Order no.
mm
kg/km
kg/km
4p
7.4
55
23,5
● Rape yellow RAL 1021
LKD 7KS6 0005 0000
2x4p
7.4 x 15.0
114
47
● Rape yellow RAL 1021
LKD 7KS6 0006 0000
Package: Drum 1,000 m
www.leoni-infrastructure-datacom.com
MegaLine® Cu data cables
Frequency MHz
40
MegaLine® E2-30 F/U
Type KS-2Y(ST)H 4x2xAWG 23/1
Category 6
S2 P1 A2 C4 E2
Construction
Conductor
Bare copper wire, AWG 23/1
Insulation Twisting element
PE Pair
Twisting
4 pairs separated by a cross element
Overall shielding
Aluminium-bonded polyester foil, metal side inside and underlayed tinned copper drain wire
Outer sheath
Halogen-free, flame-retardant compound
Security (fire behaviour) Fire behaviour Flame retardancy Halogen free Smoke density Calorific value (approx.)
acc. to IEC 60332-1-2 acc. to IEC 60754-1/2 acc. to IEC 61034-1/2 0.7 MJ/m
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Performance Better than Category 6 acc. to EN 50288 and IEC 61156 bandwidth 300 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Application (Ethernet, TV) Applications Installation cable for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition). Ideal for all applications from Classes D to E up to 1 GbE acc. to IEEE 802.3 ab, VoIP, PoE.
A
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during installation after installation Tensile strength (max.) Crush strength Impact strength (number of shocks)
8 x overall diameter (min.) 4 x overall diameter (min.) 110 N 1,000 N/100 mm 10
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Transfer impedance at 10 MHz (nominal value) 40 mΩ/m Shielding attenuation up to 1,000 MHz (nominal value) 50 dB Coupling attenuation up to 1,000 MHz (nominal value) 70 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 41
Electrical characteristics (HF) at 20 °C Attenuation dB/100 m typ.
NEXT dB
Cat. 6 max.*
PSNEXT dB
typ.
Cat. 6 min.*
typ.
Cat. 6 min.*
ACR dB at 100 m
PSACR dB at 100 m
ELFEXT dB at 100 m
PSELFEXT dB at 100 m
typ.
Cat. 6 min.*
typ.
Cat. 6 min.*
typ.
Cat. 6 min.*
typ.
Cat. 6 min.*
RL dB typ.
Cat. 6 min.*
1
1.8
2.1
93
66
90
64
91
64
88
62
103
66
100
64
24.6
–
4
2.9
3.8
87
65
84
63
84
61
81
59
95
58
92
55
30.8
23
10
5.1
6
80
59
77
57
75
53
72
51
85
50
82
47
36.7
25
16
7
7.6
75
56
72
54
68
49
65
47
78
46
75
43
38.4
25
32.25
10
10.9
71
52
68
50
61
41
58
39
71
40
68
37
37.9
23.6
62.5
13.5
15.5
67
47
64
45
53
32
50
30
65
34
62
31
35.5
21.5
100
17.8
19.9
63
44
60
42
45
24
42
22
60
30
57
27
31.9
20.1
155
22.4
25.3
59
41
56
39
37
16
34
14
53
26
50
23
28.7
18.8
200
26.8
29.1
57
40
54
38
30
11
27
9
48
24
45
21
25.9
18
250
30.4
33
56
38
53
36
26
5
23
3
44
22
41
19
25.5
17.3
300
32.8
–
53
–
50
–
20
–
17
–
38
–
35
–
23.6
–
* EN 50288-5-1(2004)/IEC 61156-5(2002)
Electrical characteristics (LF) at 20 °C
Printing on outer sheath
DC resistance
max.
75 Ω/km
LEONI MegaLine E2-30 F/U 4P H SPACE Code 21242
Insulation resistance
min.
5 GΩ x km
"production lot code" "meter marking"
Mutual capacitance
approx.
41 pF/m
Capacitive coupling (e)
approx.
1,500 pF/km
Colour code
Signal velocity (c)
approx.
0.66
whbu/bu, whor/or, whgn/gn, whbn/bn
Propagation delay
approx.
510 ns/100 m
Skew at 100 MHz
approx.
25 ns/100 m
Certificates and approvals
Characteristic impedance
at 100 MHz
100 ± 5 Ω
Link performance: LEONI MegaLine® systems
Testing voltage Ueff Operating voltage
1,000 V max.
125 V
and further commercial connector systems Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204 Conforms to LVD (73/23/EEC):
Thermal characteristics For fixed installation
–20 °C up to +60 °C
For mobile operation
0 °C up to +50 °C
Chemical characteristics Free from hazardous substances acc. to RoHS 2002/95/EC
Dimensions
Outer diam. approx.
Weight approx.
Cu content
mm
kg/km
kg/km
7.2
55
21
4p
Package: Drum 1,000 m/500 m, box 305 m
www.leoni-infrastructure-datacom.com
Colour of sheath
Order no.
● Rape yellow RAL 1021
LKD 7KS6 0004 0000
MegaLine® Cu data cables
Frequency MHz
42
MegaLine® E2-30 U/U
Type KS-2YH 4x2xAWG 23/1
Category 6
S2 P1 A2 C4 E1
Construction
Conductor
Bare copper wire, AWG 23/1
Insulation Twisting element
PE Pair
Twisting
4 pairs separated by a cross element
Outer sheath
Halogen-free, flame-retardant compound
Security (fire behaviour) Fire behaviour Flame retardancy Halogen free Smoke density Calorific value (approx.)
acc. to IEC 60332-1-2 acc. to IEC 60754-1/2 acc. to IEC 61034-1/2 0.65 MJ/m
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Performance Better than Category 6 acc. to EN 50288 and IEC 61156 bandwidth 300 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Application (Ethernet, TV) Applications Installation cable for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition). Suitable for applications from Classes D to E up to 1 GbE acc. to IEEE 802.3 ab, VoIP, PoE.
A
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during installation after installation Tensile strength (max.) Crush strength Impact strength (number of shocks)
8 x overall diameter (min.) 4 x overall diameter (min.) 110 N 1,000 N/100 mm 10
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Coupling attenuation up to 1,000 MHz (nominal value) 45 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 43
Electrical characteristics (HF) at 20 °C Attenuation dB/100 m typ.
NEXT dB
PSNEXT dB
Cat. 6 max.*
typ.
Cat. 6 min.*
typ.
Cat. 6 min.*
ACR dB at 100 m
PSACR dB at 100 m
ELFEXT dB at 100 m
PSELFEXT dB at 100 m
typ.
Cat. 6 min.*
typ.
Cat. 6 min.*
typ.
Cat. 6 min.*
typ.
Cat. 6 min.*
RL dB typ.
Cat. 6 min.*
1
1.8
2.1
94
66
91
64
92
64
89
62
102
66
99
64
25.4
–
4
2.7
3.8
88
65
85
63
85
61
82
59
96
58
93
55
30.3
23 25
10
4.7
6
81
59
78
57
76
53
73
51
85
50
82
47
33.9
16
6.6
7.6
76
56
73
54
70
49
67
47
78
46
75
43
33.6
25
32.25
9.5
10.9
72
52
69
50
62
41
59
39
70
40
67
37
33.7
23.6
62.5
13
15.5
68
47
65
45
55
32
52
30
63
34
60
31
34.4
21.5
100
17.4
19.9
64
44
61
42
46
24
43
22
57
30
54
27
33.5
20.1
155
22
25.3
60
41
57
39
38
16
35
14
50
26
47
23
32.2
18.8
200
26.6
29.1
58
40
55
38
31
11
28
9
45
24
42
21
30.5
18
250
30.4
33
57
38
54
36
27
5
24
3
40
22
37
19
29
17.3
300
33.1
–
54
–
51
–
20
–
17
–
37
–
34
–
27
–
* EN 50288-6-1(2004)/IEC 61156-5(2002)
Electrical characteristics (LF) at 20 °C
Printing on outer sheath
DC resistance
max.
78 Ω/km
LEONI MegaLine E2-30 U/U 4P H SPACE Code 21241
Insulation resistance
min.
5 GΩ x km
"production lot code" "meter marking"
Mutual capacitance
approx.
50 pF/m
Capacitive coupling (e)
approx.
1,500 pF/km
Colour code
Signal velocity (c)
approx.
0.67
whbu/bu, whor/or, whgn/gn, whbn/bn
Propagation delay
approx.
528 ns/100 m
Skew at 100 MHz
approx.
30 ns/100 m
Certificates and approvals
Characteristic impedance
at 100 MHz
100 ± 5 Ω
Link performance: LEONI MegaLine® systems
Testing voltage Ueff
1,000 V
Operating voltage
max.
125 V
and further commercial connector systems Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204 Conforms to LVD (73/23/EEC):
Thermal characteristics For fixed installation
–20 °C up to +60 °C
For mobile operation
0 °C up to +50 °C
Chemical characteristics Free from hazardous substances acc. to RoHS 2002/95/EC
Dimensions
Outer diam. approx.
Weight approx.
Cu content
mm
kg/km
kg/km
6.4
45
21
4p Package: Drum 1,000 m, box 305 m
www.leoni-infrastructure-datacom.com
Colour of sheath
Order no.
● Rape yellow RAL 1021
LKD 7KS6 0002 0000
MegaLine® Cu data cables
Frequency MHz
44
MegaLine® D1-20 SF/U
Types KS-02YS(ST+C)H 4x2xAWG 24/1 KS-02YS(ST+C)H 2x(4x2xAWG 24/1) Category 5
S2 P0 A1 C3 E3
Construction 4 p
Conductor
Bare copper wire, AWG 24/1
Insulation Twisting element
Cellular-PE, core-diameter: nominal value 1.1 mm Pair
Twisting
4 pairs
Overall shielding
Aluminium-bonded polyester foil and tinned copper braiding
Outer sheath
Halogen-free, flame-retardant compound
Security (fire behaviour) Fire behaviour Flame retardancy Halogen free Smoke density Calorific value (approx.)
acc. to IEC 60332-1-2 acc. to IEC 60754-1/2 acc. to IEC 61034-1/2 0.4 MJ/m (Sx), 0.81 MJ/m (Dx)
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Performance Better than Category 5 acc. to EN 50288 and IEC 61156 excellent shielding characteristics, bandwidth 200 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Application (Ethernet, TV) Applications Installation cable for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition). Ideal for all applications from Class D up to 1 GbE acc. to IEEE 802.3 ab, VoIP, PoE.
A
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during installation after installation Tensile strength (max.) Crush strength Impact strength (number of shocks)
8 x overall diameter (min.) 4 x overall diameter (min.) 85 N (Sx), 170 N (Dx) 1,000 N/100 mm 10
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Transfer impedance at 10 MHz (nominal value) 10 mΩ/m Shielding attenuation up to 1,000 MHz (nominal value) 55 dB Coupling attenuation up to 1,000 MHz (nominal value) 70 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 45
Electrical characteristics (HF) at 20 °C Attenuation dB/100 m
NEXT dB typ.
PSNEXT dB
typ.
Cat. 5 max.*
Cat. 5 min.*
1
2
2.1
75
4
3.1
4
69
10
5.1
6.3
62
50
16
7
8
58
47
31.25
9.7
11.4
53
62.5
13.2
16.5
100
17.6
21.3
155
22.3
200
26.5
ACR dB at 100 m
PSACR dB at 100 m
ELFEXT dB at 100 m
PSELFEXT dB at 100 m
typ.
Cat. 5 min.*
typ.
Cat. 5 min.*
typ.
Cat. 5 min.*
typ.
Cat. 5 min.*
RL dB
typ.
Cat. 5 min.*
typ.
Cat. 5 min.*
65
72
62
73
63
70
60
89
64
86
61
24.8
–
56
66
53
66
52
63
49
84
52
81
49
28.6
23
59
47
57
44
54
41
76
44
73
41
33.3
25
55
44
51
39
48
36
70
40
67
37
34.3
25
43
50
40
44
31
41
28
63
34
60
31
33.9
23.6
49
38
46
35
36
22
33
19
58
28
55
25
31.3
21.5
45
35
42
32
28
14
25
11
52
24
49
21
27.7
20.1
–
42
–
39
–
20
–
17
–
49
–
46
–
24.7
–
–
40
–
37
–
14
–
11
–
45
–
42
–
22.4
–
* EN 50288-2-1(2004)/IEC 61156-5(2002)
Electrical characteristics (LF) at 20 °C
Printing on outer sheath
DC resistance
max.
95 Ω/km
LEONI MegaLine D1-20 SF/U 4P H SPACE Code 20133
Insulation resistance
min.
5 GΩ x km
"production lot code" "meter marking"
Mutual capacitance
approx.
45 pF/m
Capacitive coupling (e)
approx.
1,500 pF/km
Colour code
Signal velocity (c)
approx.
0.75
whbu/bu, whor/or, whgn/gn, whbn/bn
Propagation delay
approx.
440 ns/100 m
Skew at 100 MHz
approx.
15 ns/100 m
Certificates and approvals
Characteristic impedance
at 100 MHz
100 ± 5 Ω
Link performance: LEONI MegaLine® systems
Testing voltage Ueff
1,000 V
Operating voltage
max.
125 V
and further commercial connector systems Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204 Conforms to LVD (73/23/EEC):
Thermal characteristics For fixed installation
–20 °C up to +60 °C
For mobile operation
0 °C up to +50 °C
Chemical characteristics Free from hazardous substances acc. to RoHS 2002/95/EC
Dimensions
Outer diam. approx.
Weight approx.
Cu content
Colour of sheath
Order no.
mm
kg/km
kg/km
4p
6.0
42
26
● Rape yellow RAL 1021
LKD 7KS5 0005 0000
2x4p
6.0 x 12.5
86
52
● Rape yellow RAL 1021
LKD 7KS5 0006 0000
Package: Drum 1,000 m, box 305 m
www.leoni-infrastructure-datacom.com
MegaLine® Cu data cables
Frequency MHz
46
MegaLine® F10-120 S/F flex
Types KS-02YSCH 4x2xAWG 26/7 PIMF KS-(02YSCH) 8x(4x2xAWG 26/7 PIMF) Category 7
S2 P4 A5 C2 E5
Construction 4 p
Conductor
Bare stranded copper wire, AWG 26/7
Insulation Twisting element
Cellular-PE, core-diameter: max. 1.05 mm Pair
Individual shielding Twisting
Aluminium-bonded polyester foil, metal side outside (PiMF) 4 pairs
Overall shielding
Tinned copper braiding
Outer sheath
Halogen-free, flame-retardant compound
Security (fire behaviour) Fire behaviour Flame retardancy Halogen free Smoke density Calorific value (approx.)
acc. to IEC 60332-1-2 acc. to IEC 60754-1/2 acc. to IEC 61034-1/2 0.38 MJ/m (Sx), 6.92 (8 p)
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Performance Better than Category 7 acc. to EN 50288 and IEC 61156 excellent NEXT, low attenuation, excellent shielding characteristics (shielding of pairs and overall shielding), low skew, bandwidth 1,200 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Application (Ethernet, TV) Applications Consolidation point cable, connection cable and patch cord for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition) as well as ISO/IEC 24764 and EN 50173-5. Ideal for all applications from Classes D to FA Multimedia (TV, video, data, voice) >10 GbE acc. to IEEE 802.3 an, cable sharing, VoIP, PoE.
A
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during operation Tensile strength (max.)
5 x overall diameter (min.) 60 N (Sx), 400 N (8 p)
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Transfer impedance at 10 MHz (nominal value) 5 mΩ/m Shielding attenuation up to 1,000 MHz (nominal value) 60 dB Coupling attenuation up to 1,000 MHz (nominal value) 85 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office
DataCenter
Industry
47
Electrical characteristics (HF) at 20 °C Attenuation dB/10 m
NEXT dB
PSNEXT dB
typ.
Cat. 7 max.*
typ.
Cat. 7 min.*
ACR dB at 10 m
typ.
Cat. 7 min.*
typ.
Cat. 7 min.*
PSACR dB at 10 m
ELFEXT dB at 10 m
PSELFEXT dB at 10 m
typ.
Cat. 7 min.*
typ.
Cat. 7 min.*
typ.
Cat. 7 min.*
RL dB typ.
Cat. 7 min.* 23
1
0.25
0.29
100
80
97
77
100
80
97
77
100
80
97
80
24
10
0.76
0.85
99
80
96
77
99
79
96
77
95
74
92
71
33.9
25
100
2.49
2.78
95
72
92
69
93
70
90
69
69
54
66
51
38.3
20.1
200
3.69
4.01
92
68
89
65
88
64
85
65
65
48
62
45
35.3
18
250
4.18
4.53
90
66
87
63
86
62
83
63
62
46
59
43
32.9
17.3
500
5.6
6.62
83
62
80
59
78
55
75
59
54
40
51
37
29.7
17.3
600
6.74
7.33
81
61
78
58
74
53
71
58
50
38
47
35
30.6
17.3
700
7.32
–
80
–
77
–
72
–
69
–
50
–
47
–
31
–
800
7.89
–
77
–
74
–
69
–
66
–
50
–
47
–
26.7
–
900
8.5
–
75
–
72
–
67
–
64
–
34
–
31
–
28.6
–
1000
9.11
–
74
–
71
–
65
–
62
–
32
–
29
–
27.5
–
1100
9.5
–
72
–
69
–
63
–
60
–
28
–
25
–
26.9
–
1200
9.9
–
70
–
67
–
61
–
58
–
24
–
21
–
26.3
–
* EN 50288-4-2 (2004)/IEC 61156-6 (2002) Stranding together multiple single elements can result in attenuation values that are up to 3 % higher and frequency-selective reflections in the case of multi-types.
Printing on outer sheath 4 p
Electrical characteristics (LF) at 20 °C DC resistance
max.
145 Ω/km
LEONI MegaLine F10-120 S/F flex 4P H SPACE Code 24525
Insulation resistance
min.
5 GΩ x km
"VDE approval mark" "production lot code" "meter marking"
Mutual capacitance
approx.
44 pF/m
Signal velocity (c)
approx.
0.78
Colour code
Propagation delay
approx.
440 ns/100 m
wh/bu, wh/or, wh/gn, wh/bn
Skew at 100 MHz
approx.
2.5 ns/100 m
Characteristic impedance
at 100 MHz
100 ± 5 Ω
Testing voltage Ueff Operating voltage
1,000 V max.
125 V
Certificates and approvals Quality mark with production control: Link performance: LEONI MegaLine® systems and further commercial connector systems
Thermal characteristics
Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204
For fixed installation
–20 °C up to +60 °C
For mobile operation
0 °C up to +50 °C
Conforms to LVD (73/23/EEC):
Chemical characteristics Free from hazardous substances acc. to RoHS 2002/95/EC
Outer diam. approx.
Weight approx.
Cu content
mm
kg/km
kg/km
4p
5.8
41
8x4p
24
500
Dimensions
Package: Drum 1,000 m
www.leoni-infrastructure-datacom.com
Colour of sheath
Order no.
23.5
● Light grey RAL 7035
LKD 7KS7 0003 0000
188
● Light grey RAL 7035
LKD 7KS7 0142 0000
MegaLine® Cu data cables
Frequency MHz
48
MegaLine® F6-90 S/F flex
Type KS-02YSCH 4x2xAWG 27/7 PIMF
Category 7
S2 P3 A4 C1 E5
Construction
Conductor
Bare stranded copper wire, AWG 27/7
Insulation Twisting element
Cellular-PE, core-diameter: max. 1.0 mm Pair
Individual shielding Twisting
Aluminium-bonded polyester foil, metal side outside (PiMF) 4 pairs
Overall shielding
Tinned copper braiding
Outer sheath
Halogen-free, flame-retardant compound
Security (fire behaviour) Fire behaviour Flame retardancy Halogen free Smoke density Calorific value (approx.)
acc. to IEC 60332-1-2 acc. to IEC 60754-1/2 acc. to IEC 61034-1/2 0.33 MJ/m
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Performance Better than Category 7 acc. to EN 50288 and IEC 61156 excellent NEXT, excellent shielding characteristics (shielding of pairs and overall shielding), low skew, bandwidth 900 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Application (Ethernet, TV) Applications Connection cable and patch cord for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition). Ideal for all applications from Classes D to F Multimedia (video, data, voice) >10 GbE acc. to IEEE 802.3 an, cable sharing, VoIP, PoE.
A
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during operation Tensile strength (max.)
5 x overall diameter (min.) 40 N
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Transfer impedance at 10 MHz (nominal value) 5 mΩ/m Shielding attenuation up to 1,000 MHz (nominal value) 60 dB Coupling attenuation up to 1,000 MHz (nominal value) 80 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office
DataCenter
Industry
49
Electrical characteristics (HF) at 20 °C Attenuation dB/10 m typ.
Cat. 7 max.*
NEXT dB typ.
PSNEXT dB
Cat. 7 min.*
typ.
Cat. 7 min.*
ACR dB at 10 m
PSACR dB at 10 m
ELFEXT dB at 10 m
typ.
Cat. 7 min.*
typ.
Cat. 7 min.*
PSELFEXT dB at 10 m
typ.
Cat. 7 min.*
typ.
Cat. 7 min.*
RL dB typ.
Cat. 7 min.*
1
0.26
0.29
95
80
92
77
95
80
92
77
92
80
89
80
21.8
–
10
0.83
0.85
94
80
91
77
94
79
91
77
84
74
81
71
29.7
25 20.1
100
2.74
2.78
90
72
87
69
88
70
85
69
70
54
67
51
35
200
3.9
4.01
87
68
84
65
83
64
80
65
60
48
57
45
33
18
250
4.39
4.53
85
66
82
63
81
62
78
63
56
46
53
43
31.6
17.3
500
6.21
6.62
78
62
75
59
72
55
69
59
52
40
49
37
28.8
17.3
600
6.91
7.33
76
61
73
58
69
53
66
58
48
38
45
35
27.1
17.3 –
700
7.48
–
75
–
72
–
67
–
64
–
34
–
31
–
26.4
800
8.06
–
72
–
69
–
64
–
61
–
34
–
31
–
24.7
–
900
8.62
–
70
–
67
–
62
–
59
–
11
–
8
–
24.4
–
* EN 50288-4-2 (2004)/IEC 61156-6 (2002)
Printing on outer sheath
Electrical characteristics (LF) at 20 °C DC resistance
max.
170 Ω/km
LEONI MegaLine F6-90 S/F flex 4P H SPACE Code 23415
Insulation resistance
min.
5 GΩ x km
"VDE approval mark" "production lot code" "meter marking"
Mutual capacitance
approx.
44 pF/m
Signal velocity (c)
approx.
0.78
Colour code
Propagation delay
approx.
430 ns/100 m
wh/bu, wh/or, wh/gn, wh/bn
Skew at 100 MHz
approx.
2.5 ns/100 m
Characteristic impedance
at 100 MHz
100 ± 5 Ω
Testing voltage Ueff Operating voltage
1,000 V max.
125 V
Certificates and approvals Quality mark with production control: Link performance: LEONI MegaLine® systems and further commercial connector systems
Thermal characteristics
Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204
For fixed installation
–20 °C up to +60 °C
For mobile operation
0 °C up to +50 °C
Conforms to LVD (73/23/EEC):
Chemical characteristics Free from hazardous substances acc. to RoHS 2002/95/EC
Dimensions
Outer diam. approx.
Weight approx.
Cu content
Colour of sheath
Order no.
mm
kg/km
kg/km
4p
5.7
34
17
● Light grey RAL 7035
LKD 7KS7 0014 0000
4p
5.7
34
17
● Rape yellow RAL 1021
LKD 7KS7 0015 0000
4p
5.7
34
17
● Turquoise green RAL 6016
LKD 7KS7 0016 0000
4p
5.7
34
17
● Sky blue RAL 5015
LKD 7KS7 0017 0000
4p
5.7
34
17
● Flame red RAL 3000
LKD 7KS7 0018 0000
Package: Drum 1,000 m
www.leoni-infrastructure-datacom.com
MegaLine® Cu data cables
Frequency MHz
50
MegaLine® D1-20 SF/U flex
Type KS-02YS(ST+C)Y 4x2xAWG 26/7
Category 5
S2 P0 A1 C2 E3
Construction
Conductor
Bare stranded copper wire, AWG 26/7
Insulation Twisting element Twisting
Cellular-PE, core-diameter: max. 1.0 mm Pair 4 pairs
Overall shielding
Aluminium-bonded polyester foil and tinned copper braiding
Outer sheath
PVC
Security (fire behaviour) Fire behaviour Flame retardancy Calorific value (approx.)
acc. to IEC 60332-1-2 0.35 MJ/m
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Performance Better than Category 5 acc. to EN 50288 and IEC 61156 excellent shielding characteristics, bandwidth 200 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Application (Ethernet, TV) Applications Connection cable and patch cord for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition). Ideal for all applications from Class D up to 1 GbE acc. to IEEE 802.3 ab, VoIP, PoE.
A
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during operation Tensile strength (max.)
5 x overall diameter (min.) 60 N
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Transfer impedance at 10 MHz (nominal value) 10 mΩ/m Shielding attenuation up to 1,000 MHz (nominal value) 50 dB Coupling attenuation up to 1,000 MHz (nominal value) 65 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 51
Electrical characteristics (HF) at 20 °C Attenuation dB/10 m typ.
NEXT dB
Cat. 5 max.*
typ.
PSNEXT dB
Cat. 5 min.*
typ.
Cat. 5 min.*
ACR dB at 10 m typ.
PSACR dB at 10 m
ELFEXT dB at 10 m
PSELFEXT dB at 10 m
Cat. 5 min.*
typ.
Cat. 5 min.*
typ.
Cat. 5 min.*
typ.
Cat. 5 min.*
RL dB typ.
Cat. 5 min.*
1
0.24
0.32
76
65
73
62
76
65
73
62
91
64
88
61
24.9
–
4
0.44
0.60
71
56
68
53
70
56
67
53
76
52
73
49
29.8
23
10
0.80
0.95
64
50
61
47
63
49
60
47
68
44
65
41
38.2
25
16
1.01
1.21
60
47
57
44
59
46
56
44
64
40
61
37
39.3
25
31.25
1.44
1.71
56
43
53
40
54
41
51
40
58
34
55
31
36.7
23.6
62.5
2.07
2.48
52
38
49
35
50
36
47
35
52
28
49
25
35
21.5
100
2.66
3.2
48
35
45
32
45
32
42
32
47
24
44
21
29.9
20.1
155
3.26
–
45
–
42
–
42
–
39
–
42
–
39
–
26.2
–
200
3.86
–
42
–
39
–
39
–
36
–
37
–
34
–
23.5
–
* EN 50288-2-2(2004)/IEC 61156-6(2002)
Electrical characteristics (LF) at 20 °C
Printing on outer sheath
DC resistance
max.
145 Ω/km
LEONI MegaLine D1-20 SF/U flex 4P Y SPACE Code 20123
Insulation resistance
min.
5 GΩ x km
"production lot code" "meter marking"
Mutual capacitance
approx.
47 pF/m
Signal velocity (c)
approx.
0.69
Colour code
Propagation delay
approx.
485 ns/100 m
whbu/bu, whor/or, whgn/gn, whbn/bn
Skew at 100 MHz
approx.
15 ns/100 m
Characteristic impedance
at 100 MHz
100 ± 5 Ω
Certificates and approvals
1,000 V
Link performance: LEONI MegaLine® systems
Testing voltage Ueff Operating voltage
max.
125 V
and further commercial connector systems Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204
Thermal characteristics
Conforms to LVD (73/23/EEC):
For fixed installation
–20 °C up to +60 °C
For mobile operation
0 °C up to +50 °C
Chemical characteristics Free from hazardous substances acc. to RoHS 2002/95/EC
Dimensions
Outer diam. approx.
Weight approx.
Cu content kg/km
Colour of sheath
Order no.
mm
kg/km
4p
5.3
32
21
● Light grey RAL 7035
LKD 7KS5 0008 0000
4p
5.3
32
21
● Rape yellow RAL 1021
LKD 7KS5 0009 0000
4p
5.3
32
21
● Turquoise green RAL 6016
LKD 7KS5 0010 0000
4p
5.3
32
21
● Sky blue RAL 5015
LKD 7KS5 0011 0000
4p
5.3
32
21
● Flame red RAL 3000
LKD 7KS5 0012 0000
Package: Drum 1,000 m
www.leoni-infrastructure-datacom.com
MegaLine® Cu data cables
Frequency MHz
52
MegaLine® F10-130 S/F (L)2Y
Category "7A"
S0 P4 I4 C5 E5
Construction
Conductor
Bare copper wire, AWG 22/1
Insulation Twisting element
Cellular-PE, core-diameter: nominal value 1.6 mm Pair
Individual shielding Twisting
Aluminium-bonded polyester foil, metal side outside (PiMF) 4 pairs
Overall shielding
Tinned copper braiding
Inner sheath
Halogen-free, flame-retardant compound
Outer sheath
AL-PE
Security (fire behaviour) Fire behaviour Halogen free Smoke density Calorific value (approx.)
acc. to IEC 60754-1/2 acc. to IEC 61034-1/2 3.04 MJ/m
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Performance Better than Category 7 acc. to EN 50288 and IEC 61156 excellent NEXT, low attenuation, excellent shielding characteristics (shielding of pairs and overall shielding), low skew, bandwidth 1,300 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Industrial application (Ethernet, TV) Applications Installation cable for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition) as well as ISO/IEC 24702 and EN 50173-3. Ideal for all applications from Classes D to FA Multimedia (video, data, voice) >10 GbE acc. to IEEE 802.3 an, cable sharing, VoIP, PoE. For use outdoors and underground installation.
I
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during installation after installation Tensile strength (max.) Crush strength Impact strength (number of shocks)
8 x overall diameter (min.) 4 x overall diameter (min.) 130 N 2,000 N/100 mm 20
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Transfer impedance at 10 MHz (nominal value) 5 mΩ/m Shielding attenuation up to 1,000 MHz (nominal value) 70 dB Coupling attenuation up to 1,000 MHz (nominal value) 85 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office Office
Industry Industry
DataCenter 53
Electrical characteristics (HF) at 20 °C Attenuation dB/100 m typ.
NEXT dB
PSNEXT dB
ACR dB at 100 m
PSACR dB at 100 m
ELFEXT dB at 100 m
PSELFEXT dB at 100 m
typ.
Cat. "7" max.*
typ.
Cat. "7" max.*
Cat. "7" max.*
typ.
Cat. "7" max.*
typ.
Cat. "7" max.*
typ.
Cat. "7" max.*
typ.
Cat. "7" max.*
RL dB typ.
Cat. "7" max.* 23
1
1.7
2
105
80
102
77
104
78
101
75
105
80
102
77
27.1
10
4.5
5.7
105
80
102
77
101
74
98
71
108
74
105
71
35.2
25
100
15.4
18.5
105
72
102
69
90
54
87
51
93
54
90
51
38.9
20.1
200
22.9
26.8
105
68
102
65
83
41
80
38
85
48
82
45
36.6
18
250
26
30.2
105
66
102
63
79
36
76
33
82
46
79
43
35.3
17.3
500
35.9
44.1
100
62
97
59
64
18
61
15
70
40
67
37
29.4
17.3
600
40.4
48.9
95
61
92
58
55
12
52
9
63
38
60
35
26.6
17.3
700
44.6
-
95
–
92
–
50
–
47
–
60
–
57
–
25.8
–
800
47.7
–
93
–
90
–
45
–
42
–
57
–
54
–
25
–
900
51.6
–
90
–
87
–
38
–
35
–
53
–
50
–
23.6
–
1000
54.8
–
88
–
85
–
33
–
30
–
48
–
45
–
22.3
–
1100
56.9
–
87
–
84
–
30
–
27
–
44
–
41
–
21.4
–
1300
61.4
–
80
–
77
–
21
–
18
–
39
–
36
–
18.3
–
* EN 50288-4-1(2004)/IEC 61156-5(2002)
Printing on outer sheath
Electrical characteristics (LF) at 20 °C DC resistance
max.
57.1 Ω/km
LEONI MegaLine F10-130 S/F 4P H(L)2Y SPICE Code 04455
Insulation resistance
min.
5 GΩ x km
"VDE approval mark" "production lot code" "meter marking"
Mutual capacitance
approx.
40 pF/m
Capacitive coupling (e)
approx.
1,500 pF/km
Colour code
Signal velocity (c)
approx.
0.80
wh/bu, wh/or, wh/gn, wh/bn
Propagation delay
approx.
420 ns/100 m
Skew at 100 MHz
approx.
5 ns/100 m
Characteristic impedance
at 100 MHz
100 ± 5 Ω
Testing voltage Ueff Operating voltage
1,000 V max.
125 V
Certificates and approvals Quality mark with production control: Link performance: LEONI MegaLine® systems and further commercial connector systems Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204
Thermal characteristics
Conforms to LVD (73/23/EEC):
For fixed installation
–25 °C up to +70 °C
For mobile operation
–10 °C to +50 °C
Chemical characteristics Free from hazardous substances acc. to RoHS 2002/95/EC, resistant to UV rays acc. to UL 1581 and ISO 4892
Dimensions
Outer diam. approx.
Weight approx.
Cu content
mm
kg/km
kg/km
12
150
45
4p Package: Drum 1,000 m
www.leoni-infrastructure-datacom.com
Colour of sheath
● Jet black RAL 9005
Order no.
LKD 7KS7 002U 0000
MegaLine® Cu data cables
Frequency MHz
54
MegaLine® F10-130 S/F QH
Type KS-02YSCHQH 4x2xAWG 22/1 PIMF
Category "7A"
S3 P4 I4 C5 E5
Construction
Conductor
Bare copper wire, AWG 22/1
Insulation Twisting element
Cellular-PE, core-diameter: nominal value 1.6 mm Pair
Individual shielding Twisting
Aluminium-bonded polyester foil, metal side outside (PiMF) 4 pairs
Overall shielding
Tinned copper braiding
Inner sheath
Halogen-free, flame-retardant compound
Armour
Galvanised steel wire braiding
Outer sheath
Halogen-free, flame-retardant compound
Security (fire behaviour) Fire behaviour Flame retardancy Halogen free Smoke density Calorific value (approx.)
acc. to IEC 60332-3-24 acc. to IEC 60754-1/2 acc. to IEC 61034-1/2 1.53 MJ/m
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Performance Better than Category 7 acc. to EN 50288 and IEC 61156 excellent NEXT, low attenuation, excellent shielding characteristics (shielding of pairs and overall shielding), low skew, bandwidth 1,300 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Industrial application (Ethernet, TV) Applications Installation cable for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition) as well as ISO/IEC 24702 and EN 50173-3. Ideal for all applications from Classes D to FA Multimedia (video, data, voice) >10 GbE acc. to IEEE 802.3 an, cable sharing, VoIP, PoE. For use indoors and outdoors (with reservations) and in harsh environments. With rodent protection.
I
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during installation after installation Tensile strength (max.) Crush strength Impact strength (number of shocks)
8 x overall diameter (min.) 4 x overall diameter (min.) 1,400 N 3,000 N/100 mm 50
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Transfer impedance at 10 MHz (nominal value) 5 mΩ/m Shielding attenuation up to 1,000 MHz (nominal value) 70 dB Coupling attenuation up to 1,000 MHz (nominal value) 85 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office Office
Industry Industry
DataCenter 55
Electrical characteristics (HF) at 20 °C Attenuation dB/100 m typ.
NEXT dB
PSNEXT dB
ACR dB at 100 m
PSACR dB at 100 m
ELFEXT dB at 100 m
PSELFEXT dB at 100 m
typ.
Cat. "7" max.*
typ.
Cat. "7" max.*
Cat. "7" max.*
typ.
Cat. "7" max.*
typ.
Cat. "7" max.*
typ.
Cat. "7" max.*
typ.
Cat. "7" max.*
RL dB typ.
Cat. "7" max.* 23
1
1.7
2
105
80
102
77
104
78
101
75
105
80
102
77
27.1
10
4.5
5.7
105
80
102
77
101
74
98
71
108
74
105
71
35.2
25
100
15.4
18.5
105
72
102
69
90
54
87
51
93
54
90
51
38.9
20.1
200
22.9
26.8
105
68
102
65
83
41
80
38
85
48
82
45
36.6
18
250
26
30.2
105
66
102
63
79
36
76
33
82
46
79
43
35.3
17.3
500
35.9
44.1
100
62
97
59
64
18
61
15
70
40
67
37
29.4
17.3
600
40.4
48.9
95
61
92
58
55
12
52
9
63
38
60
35
26.6
17.3
700
44.6
-
95
–
92
–
50
–
47
–
60
–
57
–
25.8
–
800
47.7
–
93
–
90
–
45
–
42
–
57
–
54
–
25
–
900
51.6
–
90
–
87
–
38
–
35
–
53
–
50
–
23.6
–
1000
54.8
–
88
–
85
–
33
–
30
–
48
–
45
–
22.3
–
1100
56.9
–
87
–
84
–
30
–
27
–
44
–
41
–
21.4
–
1300
61.4
–
80
–
77
–
21
–
18
–
39
–
36
–
18.3
–
* EN 50288-4-1(2004)/IEC 61156-5(2002)
Printing on outer sheath
Electrical characteristics (LF) at 20 °C DC resistance
max.
57.1 Ω/km
LEONI MegaLine F10-130 S/F 4P HQH SPICE Code 34455
Insulation resistance
min.
5 GΩ x km
"production lot code" "meter marking"
Mutual capacitance
approx.
40 pF/m
Capacitive coupling (e)
approx.
1,500 pF/km
Colour code
Signal velocity (c)
approx.
0.80
wh/bu, wh/or, wh/gn, wh/bn
Propagation delay
approx.
420 ns/100 m
Skew at 100 MHz
approx.
5 ns/100 m
Characteristic impedance
at 100 MHz
100 ± 5 Ω
Testing voltage Ueff Operating voltage
1,000 V max.
125 V
Certificates and approvals Quality mark with production control: Link performance: LEONI MegaLine® systems and further commercial connector systems Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204
Thermal characteristics
Conforms to LVD (73/23/EEC):
For fixed installation
–20 °C up to +60 °C
For mobile operation
0 °C to +50 °C
Chemical characteristics Free from hazardous substances acc. to RoHS 2002/95/EC
Dimensions
Outer diam. approx.
Weight approx.
Cu content
mm
kg/km
kg/km
11.7
185
45
4p Package: Drum 1,000 m
www.leoni-infrastructure-datacom.com
Colour of sheath
● Sky blue RAL 5015
Order no.
LKD 7KS7 001U 0000
MegaLine® Cu data cables
Frequency MHz
56
MegaLine® F10-130 S/F Vö
Type KS-02YSCHVö 4x2xAWG 22/1 PIMF
Category "7A"
S3 P4 I4 C5 E5
Construction
Conductor
Bare copper wire, AWG 22/1
Insulation Twisting element
Cellular-PE, core-diameter: nominal value 1.6 mm Pair
Individual shielding Twisting
Aluminium-bonded polyester foil, metal side outside (PiMF) 4 pairs
Overall shielding
Tinned copper braiding
Outer sheath
Halogen-free, flame-retardant compound
Security (fire behaviour) Fire behaviour Flame retardancy Halogen free Smoke density Calorific value (approx.)
acc. to IEC 60332-3-24 acc. to IEC 60754-1/ 2 acc. to IEC 61034-1/2 0.80 MJ/m
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Performance Better than Category 7 acc. to EN 50288 and IEC 61156 excellent NEXT, low attenuation, excellent shielding characteristics (shielding of pairs and overall shielding), low skew, bandwidth 1,300 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Industrial application (Ethernet, TV) Applications Installation cable for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition) as well as ISO/IEC 24702 and EN 50173-3. Ideal for all applications from Classes D to FA Multimedia (video, data, voice) >10 GbE acc. to IEEE 802.3 an, cable sharing, VoIP, PoE. Suitable for use in harsh environments thanks to particularly robust H sheath.
I
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during installation after installation Tensile strength (max.) Crush strength Impact strength (number of shocks)
8 x overall diameter (min.) 4 x overall diameter (min.) 130 N 1,000 N/100 mm 10
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Transfer impedance at 10 MHz (nominal value) 5 mΩ/m Shielding attenuation up to 1,000 MHz (nominal value) 70 dB Coupling attenuation up to 1,000 MHz (nominal value) 85 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office Office
Industry Industry
DataCenter 57
Electrical characteristics (HF) at 20 °C Attenuation dB/100 m typ.
NEXT dB
PSNEXT dB
ACR dB at 100 m
PSACR dB at 100 m
ELFEXT dB at 100 m
PSELFEXT dB at 100 m
typ.
Cat. "7" max.*
typ.
Cat. "7" max.*
Cat. "7" max.*
typ.
Cat. "7" max.*
typ.
Cat. "7" max.*
typ.
Cat. "7" max.*
typ.
Cat. "7" max.*
RL dB typ.
Cat. "7" max.* 23
1
1.7
2
105
80
102
77
104
78
101
75
105
80
102
77
27.1
10
4.5
5.7
105
80
102
77
101
74
98
71
108
74
105
71
35.2
25
100
15.4
18.5
105
72
102
69
90
54
87
51
93
54
90
51
38.9
20.1
200
22.9
26.8
105
68
102
65
83
41
80
38
85
48
82
45
36.6
18
250
26
30.2
105
66
102
63
79
36
76
33
82
46
79
43
35.3
17.3
500
35.9
44.1
100
62
97
59
64
18
61
15
70
40
67
37
29.4
17.3
600
40.4
48.9
95
61
92
58
55
12
52
9
63
38
60
35
26.6
17.3
700
44.6
-
95
–
92
–
50
–
47
–
60
–
57
–
25.8
–
800
47.7
–
93
–
90
–
45
–
42
–
57
–
54
–
25
–
900
51.6
–
90
–
87
–
38
–
35
–
53
–
50
–
23.6
–
1000
54.8
–
88
–
85
–
33
–
30
–
48
–
45
–
22.3
–
1100
56.9
–
87
–
84
–
30
–
27
–
44
–
41
–
21.4
–
1300
61.4
–
80
–
77
–
21
–
18
–
39
–
36
–
18.3
–
* EN 50288-4-1(2004)/IEC 61156-5(2002)
Printing on outer sheath
Electrical characteristics (LF) at 20 °C DC resistance
max.
57.1 Ω/km
LEONI MegaLine F10-130 S/F 4P HVö SPICE Code 34455
Insulation resistance
min.
5 GΩ x km
"VDE approval mark" "production lot code" "meter marking"
Mutual capacitance
approx.
40 pF/m
Capacitive coupling (e)
approx.
1,500 pF/km
Colour code
Signal velocity (c)
approx.
0.80
wh/bu, wh/or, wh/gn, wh/bn
Propagation delay
approx.
420 ns/100 m
Skew at 100 MHz
approx.
5 ns/100 m
Characteristic impedance
at 100 MHz
100 ± 5 Ω
Testing voltage Ueff Operating voltage
1,000 V max.
125 V
Certificates and approvals Quality mark with production control: Link performance: LEONI MegaLine® systems and further commercial connector systems Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204
Thermal characteristics
Conforms to LVD (73/23/EEC):
For fixed installation
–20 °C up to +60 °C
For mobile operation
0 °C to +50 °C
Chemical characteristics Free from hazardous substances acc. to RoHS 2002/95/EC, oil resistant acc. to ICEA S-82-552 (60 °C)
Dimensions
Outer diam. approx.
Weight approx.
Cu content
mm
kg/km
kg/km
8.8
84
45
4p Package: Drum 1,000 m
www.leoni-infrastructure-datacom.com
Colour of sheath
Order no.
● Rape yellow RAL 1021
LKD 7KS7 0089 0000
MegaLine® Cu data cables
Frequency MHz
58
MegaLine® F10-115 S/F V
Type KS-02YSCHV 4x2xAWG 23/1 PIMF
Category "7A"
S3 P4 I4 C4 E5
Construction
Conductor
Bare copper wire, AWG 23/1
Insulation Twisting element
Cellular-PE, core-diameter: nominal value 1.4 mm Pair
Twisting
4 pairs
Overall shielding
Tinned copper braiding
Outer sheath
Halogen-free, flame-retardant compound, wall thickness 1.0 mm
Security (fire behaviour) Fire behaviour Flame retardancy Halogen free Smoke density Calorific value (approx.)
acc. to IEC 60332-3-24 acc. to IEC 60754-1/2 acc. to IEC 61034-1/2 0.7 MJ/m
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Performance Better than Category 7 acc. to EN 50288 and IEC 61156 excellent NEXT, excellent shielding characteristics (shielding of pairs and overall shielding), low skew, bandwidth 1,150 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Industrial application (Ethernet, TV) Applications Installation cable for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition) as well as ISO/IEC 24702 and EN 50173-3. Ideal for all applications from Classes D to FA Multimedia (video, data, voice) >10 GbE acc. to IEEE 802.3 an, cable sharing, VoIP, PoE. Suitable for use in harsh environments thanks to particularly robust H sheath.
I
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during installation after installation Tensile strength (max.) Crush strength Impact strength (number of shocks)
8 x overall diameter (min.) 4 x overall diameter (min.) 110 N 1,000 N/100 mm 10
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Transfer impedance at 10 MHz (nominal value) 5 mΩ/m Shielding attenuation up to 1,000 MHz (nominal value) 70 dB Coupling attenuation up to 1,000 MHz (nominal value) 85 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office Office
Industry Industry
DataCenter 59
Electrical characteristics (HF) at 20 °C Attenuation dB/100 m typ.
NEXT dB
PSNEXT dB
ACR dB at 100 m
PSACR dB at 100 m
ELFEXT dB at 100 m
PSELFEXT dB at 100 m
typ.
Cat. "7" max.*
typ.
Cat. "7" max.*
typ.
Cat. "7" max.* 23
Cat. "7" max.*
typ.
Cat. "7" max.*
typ.
Cat. "7" max.*
typ.
Cat. "7" max.*
typ.
Cat. "7" max.*
RL dB
1
1.9
2
105
80
102
77
104
78
101
75
98
80
95
77
26.6
10
4.8
5.7
105
80
102
77
101
74
98
71
103
74
100
71
35.2
25
100
16.3
18.5
105
72
102
69
89
54
86
51
89
54
86
51
39.6
20.1
200
24.3
26.8
105
68
102
65
81
41
78
38
82
48
79
45
36
18
250
27.5
30.2
105
66
102
63
78
36
75
33
79
46
76
43
34
17.3
500
37.9
44.1
100
62
97
59
62
18
59
15
67
40
64
37
29
17.3
600
42.4
48.9
95
61
92
58
53
12
50
9
60
38
57
35
25.4
17.3 –
700
47.2
-
95
–
92
–
48
–
45
–
57
–
54
–
24.6
800
50.3
–
93
–
90
–
43
–
40
–
53
–
50
–
23.5
–
900
54.6
–
90
–
87
–
35
–
32
–
49
–
46
–
22.6
–
1000
58
–
88
–
85
–
30
–
27
–
44
–
41
–
21.5
–
1150
61.9
–
86
–
83
–
25
–
22
–
39
–
36
–
20.6
–
*EN 50288-4-1(2004)/IEC 61156-5(2002)
Printing on outer sheath
Electrical characteristics (LF) at 20 °C DC resistance
max.
75 Ω/km
LEONI MegaLine F10-115 S/F 4P HV SPICE Code 34445
Insulation resistance
min.
5 GΩ x km
"VDE approval mark" "production lot code" "meter marking"
Mutual capacitance
approx.
42 pF/m
Capacitive coupling (e)
approx.
1,500 pF/km
Colour code
Signal velocity (c)
approx.
0.80
wh/bu, wh/or, wh/gn, wh/bn
Propagation delay
approx.
420 ns/100 m
Skew at 100 MHz
approx.
5 ns/100 m
Characteristic impedance
at 100 MHz
100 ± 5 Ω
Testing voltage Ueff Operating voltage
1,000 V max.
125 V
Certificates and approvals Quality mark with production control: Link performance: LEONI MegaLine® systems and further commercial connector systems Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204
Thermal characteristics
Conforms to LVD (73/23/EEC):
For fixed installation
–20 °C up to +60 °C
For mobile operation
0 °C to +50 °C
Chemical characteristics Free from hazardous substances acc. to RoHS 2002/95/EC
Dimensions
Outer diam. approx.
Weight approx.
Cu content
mm
kg/km
kg/km
8.1
77
37
4p Package: Drum 1,000 m
www.leoni-infrastructure-datacom.com
Colour of sheath
Order no.
● Rape yellow RAL 1021
LKD 7KS7 0049 0000
MegaLine® Cu data cables
Frequency MHz
60
MegaLine® F6-90 S/F 2Y
Type KS-02YSC2Y 4x2xAWG 23/1 PIMF
Category 7
S0 P3 I4 C4 E5
Construction
Conductor
Bare copper wire, AWG 23/1
Insulation Twisting element
Cellular-PE, core-diameter: nominal value 1.4 mm Pair
Individual shielding Twisting
Aluminium-bonded polyester foil, metal side outside (PiMF) 4 pairs
Overall shielding
Tinned copper braiding
Outer sheath
PE
Security (fire behaviour) Fire behaviour Halogen free Smoke density
acc. to IEC 60754-1/2 acc. to IEC 61034-1/2
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Performance Better than Category 7 acc. to EN 50288 and IEC 61156 excellent NEXT, excellent shielding characteristics (shielding of pairs and overall shielding), low skew, bandwidth 900 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Industrial application (Ethernet, TV) Applications Installation cable for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition) as well as ISO/IEC 24702 and EN 50173-3. Ideal for all applications from Classes D to F Multimedia (video, data, voice) >10 GbE acc. to IEEE 802.3 an, cable sharing, VoIP, PoE. For use outdoors and underground installation.
I
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during installation after installation Tensile strength (max.) Crush strength Impact strength (number of shocks)
8 x overall diameter (min.) 4 x overall diameter (min.) 110 N 2,000 N/100 mm 20
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Transfer impedance at 10 MHz (nominal value) 5 mΩ/m Shielding attenuation up to 1,000 MHz (nominal value) 70 dB Coupling attenuation up to 1,000 MHz (nominal value) 85 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office Office
Industry Industry
DataCenter 61
Electrical characteristics (HF) at 20 °C Attenuation dB/100 m typ.
NEXT dB
Cat. 7 max.*
typ.
PSNEXT dB
Cat. 7 min.*
typ.
ACR dB at 100 m
PSACR dB at 100 m
ELFEXT dB at 100 m
PSELFEXT dB at 100 m
Cat. 7 min.*
typ.
Cat. 7 min.*
typ.
typ.
Cat. 7 min.*
typ.
Cat. 7 min.*
typ.
Cat. 7 min.*
RL dB Cat. 7 min.*
1
1.9
2
102
80
99
77
101
78
98
75
109
80
106
77
25.4
23
10
4.8
5.7
102
80
99
77
98
74
95
71
108
74
105
71
31.1
25 20.1
100
16.4
18.5
102
72
99
69
86
54
83
51
93
54
90
51
33.2
200
24.5
26.8
102
68
99
65
78
41
75
38
85
48
82
45
33.2
18
250
27.8
30.2
102
66
99
63
75
36
72
33
82
46
79
43
33.4
17.3
450
36.1
44.6
97
63
94
60
61
21
58
18
72
41
69
38
31.4
17.3
500
38.2
44.1
97
62
94
59
59
18
56
15
68
40
65
37
30.5
17.3
600
42.9
48.9
92
61
89
58
49
12
46
9
62
38
59
35
27.6
17.3
700
47.7
–
92
–
89
–
44
–
41
–
59
–
56
–
26.2
–
800
50.8
–
90
–
87
–
39
–
36
–
56
–
53
–
23.9
–
900
55.1
–
85
–
82
–
30
–
27
–
52
–
49
–
21.7
–
*EN 50288-4-1(2004)/IEC 61156-5(2002)
Electrical characteristics (LF) at 20 °C
Printing on outer sheath
DC resistance
max.
75 Ω/km
LEONI MegaLine F6-90 S/F 4P 2Y SPICE Code 03445
Insulation resistance
min.
5 GΩ x km
"production lot code" "meter marking"
Mutual capacitance
approx.
42 pF/m
Capacitive coupling (e)
approx.
1,500 pF/km
Colour code
Signal velocity (c)
approx.
0.80
wh/bu, wh/or, wh/gn, wh/bn
Propagation delay
approx.
420 ns/100 m
Skew at 100 MHz
approx.
5 ns/100 m
Certificates and approvals
Characteristic impedance
at 100 MHz
100 ± 5 Ω
Link performance: LEONI MegaLine® systems
Testing voltage Ueff Operating voltage
1,000 V max.
125 V
and further commercial connector systems Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204 Conforms to LVD (73/23/EEC):
Thermal characteristics For fixed installation
–25 °C up to +70 °C
For mobile operation
–10 °C to +50 °C
Chemical characteristics Free from hazardous substances acc. to RoHS 2002/95/EC, resistant to UV rays acc. to UL 1581 and ISO 4892, free from paint-wetting impairment substances (e.g. silicone oil)
Dimensions
Outer diam. approx.
Weight approx.
Cu content
mm
kg/km
kg/km
9.0
70
35
4p Package: Drum 1,000 m
www.leoni-infrastructure-datacom.com
Colour of sheath
● Jet black RAL 9005
Order no.
LKD 7KS7 0169 0000
MegaLine® Cu data cables
Frequency MHz
62
MegaLine® D1-20 SF/U 2Y
Type KS-02YS(ST+C)H2Y 4x2xAWG 24/1
Category 5
S0 P0 I1 C3 E3
Construction
Conductor
Bare copper wire, AWG 24/1
Insulation Twisting element Twisting
Cellular-PE, core-diameter: nominal value 1.1 mm Pair 4 pairs
Overall shielding
Aluminium-bonded polyester foil and tinned copper braiding
Inner sheath
Halogen-free, flame-retardant compound
Outer sheath
PE
Security (fire behaviour) Fire behaviour Halogen free Smoke density Calorific value (approx.)
acc. to IEC 60754-1/2 acc. to IEC 61034-1/2 1.88 MJ/m
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Performance Better than Category 5 acc. to EN 50288 and IEC 61156 excellent shielding characteristics, bandwidth 200 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Industrial application (Ethernet, TV) Applications Installation cable for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition) as well as ISO/IEC 24702 and EN 50173-3. Ideal for all applications from Class D up to 1 GbE acc. to IEEE 802.3 ab, VoIP, PoE. For use outdoors and underground installation.
I
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during installation after installation Tensile strength (max.) Crush strength Impact strength (number of shocks)
8 x overall diameter (min.) 4 x overall diameter (min.) 85 N 3,000 N/100 mm 50
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Transfer impedance at 10 MHz (nominal value) 10 mΩ/m Shielding attenuation up to 1,000 MHz (nominal value) 55 dB Coupling attenuation up to 1,000 MHz (nominal value) 70 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office Office
Industry Industry
DataCenter 63
Electrical characteristics (HF) at 20 °C Attenuation dB/100 m
NEXT dB typ.
PSNEXT dB
typ.
Cat. 5 max.*
Cat. 5 min.*
1
2
2.1
75
4
3.1
4
69
10
5.1
6.3
62
50
16
7
8
58
47
31.25
9.7
11.4
53
62.5
13.2
16.5
100
17.6
21.3
155
22.3
200
26.5
ACR dB at 100 m
PSACR dB at 100 m
ELFEXT dB at 100 m
PSELFEXT dB at 100 m
typ.
Cat. 5 min.*
typ.
Cat. 5 min.*
typ.
Cat. 5 min.*
typ.
Cat. 5 min.*
RL dB
typ.
Cat. 5 min.*
typ.
Cat. 5 min.*
65
72
62
73
63
70
60
89
64
86
61
24.8
–
56
66
53
66
52
63
49
84
52
81
49
28.6
23
59
47
57
44
54
41
76
44
73
41
33.3
25
55
44
51
39
48
36
70
40
67
37
34.3
25
43
50
40
44
31
41
28
63
34
60
31
33.9
23.6
49
38
46
35
36
22
33
19
58
28
55
25
31.3
21.5
45
35
42
32
28
14
25
11
52
24
49
21
27.7
20.1
–
42
–
39
–
20
–
17
–
49
–
46
–
24.7
–
–
40
–
37
–
14
–
11
–
45
–
42
–
22.4
–
*EN 50288-4-1(2004)/IEC 61156-5(2002)
Electrical characteristics (LF) at 20 °C
Printing on outer sheath
DC resistance
max.
95 Ω/km
LEONI MegaLine D1-20 SF/U 4P H2Y SPICE Code 00133
Insulation resistance
min.
5 GΩ x km
"production lot code" "meter marking"
Mutual capacitance
approx.
45 pF/m
Capacitive coupling (e)
approx.
1,500 pF/km
Colour code
Signal velocity (c)
approx.
0.75
whbu/bu, whor/or, whgn/gn, whbn/bn
Propagation delay
approx.
440 ns/100 m
Skew at 100 MHz
approx.
15 ns/100 m
Certificates and approvals
Characteristic impedance
at 100 MHz
100 ± 5 Ω
Link performance: LEONI MegaLine® systems
Testing voltage Ueff Operating voltage
1,000 V max.
125 V
and further commercial connector systems Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204 Conforms to LVD (73/23/EEC):
Thermal characteristics For fixed installation
–25 °C up to +70 °C
For mobile operation
–10 °C to +50 °C
Chemical characteristics Free from hazardous substances acc. to RoHS 2002/95/EC, resistant to UV rays acc. to UL 1581 and ISO 4892
Dimensions
Outer diam. approx.
Weight approx.
Cu content
mm
kg/km
kg/km
8.8
70
26
4p Package: Drum 1,000 m
www.leoni-infrastructure-datacom.com
Colour of sheath
● Jet black RAL 9005
Order no.
LKD 7KS5 001U 0000
MegaLine® Cu data cables
Frequency MHz
64
MegaLine® D1-20 SF/U HQH
Type KS-02YS(ST+C)HHQH 4x2xAWG 24/1
Category 5
S2 P0 I1 C3 E3
Construction
Conductor
Bare copper wire, AWG 24/1
Insulation Twisting element Twisting
Cellular-PE, core-diameter: nominal value 1.1 mm Pair 4 pairs
Overall shielding
Aluminium-bonded polyester foil and tinned copper braiding
Inner sheath
2 layers halogen-free, flame-retardant compound
Armour
Galvanised steel wire braiding
Outer sheath
Halogen-free, flame-retardant compound
Security (fire behaviour) Fire behaviour Flame retardancy Halogen free Smoke density Calorific value (approx.)
acc. to IEC 60332-1-2 acc. to IEC 60754-1/2 acc. to IEC 61034-1/2 2.1 MJ/m
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Performance Better than Category 5 acc. to EN 50288 and IEC 61156 excellent shielding characteristics, bandwidth 200 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Industrial application (Ethernet, TV) Applications Installation cable for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition) as well as ISO/IEC 24702 and EN 50173-3. Ideal for all applications from Class D up to 1 GbE acc. to IEEE 802.3 ab, VoIP, PoE. For universal use indoors and outdoors.
I
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during installation after installation Tensile strength (max.) Crush strength Impact strength (number of shocks)
8 x overall diameter (min.) 4 x overall diameter (min.) 1,200 N 3,000 N/100 mm 50
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Transfer impedance at 10 MHz (nominal value) 10 mΩ/m Shielding attenuation up to 1,000 MHz (nominal value) 55 dB Coupling attenuation up to 1,000 MHz (nominal value) 70 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office Office
Industry Industry
DataCenter 65
Electrical characteristics (HF) at 20 °C Attenuation dB/100 m
NEXT dB typ.
PSNEXT dB
typ.
Cat. 5 max.*
Cat. 5 min.*
1
2
2.1
75
4
3.1
4
69
10
5.1
6.3
62
50
16
7
8
58
47
31.25
9.7
11.4
53
62.5
13.2
16.5
100
17.6
21.3
155
22.3
200
26.5
ACR dB at 100 m
PSACR dB at 100 m
ELFEXT dB at 100 m
PSELFEXT dB at 100 m
typ.
Cat. 5 min.*
typ.
Cat. 5 min.*
typ.
Cat. 5 min.*
typ.
Cat. 5 min.*
RL dB
typ.
Cat. 5 min.*
typ.
Cat. 5 min.*
65
72
62
73
63
70
60
89
64
86
61
24.8
–
56
66
53
66
52
63
49
84
52
81
49
28.6
23
59
47
57
44
54
41
76
44
73
41
33.3
25
55
44
51
39
48
36
70
40
67
37
34.3
25
43
50
40
44
31
41
28
63
34
60
31
33.9
23.6
49
38
46
35
36
22
33
19
58
28
55
25
31.3
21.5
45
35
42
32
28
14
25
11
52
24
49
21
27.7
20.1
–
42
–
39
–
20
–
17
–
49
–
46
–
24.7
–
–
40
–
37
–
14
–
11
–
45
–
42
–
22.4
–
*EN 50288-2-1(2004)/IEC 61156-5(2002)
Electrical characteristics (LF) at 20 °C
Printing on outer sheath
DC resistance
max.
95 Ω/km
LEONI MegaLine D1-20 SF/U 4P HHQH SPICE Code 20133
Insulation resistance
min.
5 GΩ x km
"production lot code" "meter marking"
Mutual capacitance
approx.
45 pF/m
Capacitive coupling (e)
approx.
1,500 pF/km
Colour code
Signal velocity (c)
approx.
0.75
whbu/bu, whor/or, whgn/gn, whbn/bn
Propagation delay
approx.
440 ns/100 m
Skew at 100 MHz
approx.
15 ns/100 m
Certificates and approvals
Characteristic impedance
at 100 MHz
100 ± 5 Ω
Link performance: LEONI MegaLine® systems
Testing voltage Ueff Operating voltage
1,000 V max.
125 V
and further commercial connector systems Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204 Conforms to LVD (73/23/EEC):
Thermal characteristics For fixed installation
–20 °C up to +60 °C
For mobile operation
0 °C to +50 °C
Chemical characteristics Free from hazardous substances acc. to RoHS 2002/95/EC
Dimensions
Outer diam. approx.
Weight approx.
Cu content
mm
kg/km
kg/km
11.9
194
26
4p Package: Drum 1,000 m
www.leoni-infrastructure-datacom.com
Colour of sheath
● Jet black RAL 9005
Order no.
LKD 7KS5 002U 0000
MegaLine® Cu data cables
Frequency MHz
66
MegaLine® F10-120 S/F 11Y flex
Type KS-02YSC11Y 4x2xAWG 26/7 PIMF
Category "7A"
S1 P4 I5 C2 E5
Construction
Conductor
Bare stranded copper wire, AWG 26/7
Insulation Twisting element
Cellular-PE, core-diameter: max. 1.05 mm Pair
Individual shielding Twisting
Aluminium-bonded polyester foil, metal side outside (PiMF) 4 pairs
Overall shielding
Tinned copper braiding
Outer sheath
PUR
Security (fire behaviour) Fire behaviour Flame retardancy Halogen free Smoke density Calorific value (approx.)
acc. to IEC 60332-2-2 acc. to 60754-1/2 acc. to IEC 61034-1/2 0.7 MJ/m
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Performance Better than Category 7 acc. to EN 50288 and IEC 61156 excellent NEXT, low attenuation, excellent shielding characteristics (shielding of pairs and overall shielding), low skew, bandwidth 1,200 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Industrial application (Ethernet, TV) Applications Connection cable and patch cord for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition) as well as ISO/IEC 24702 and EN 50173-3. Ideal for all applications from Classes D to FA Multimedia (TV, video, data, voice) >10 GbE acc. to IEEE 802.3 an, cable sharing, VoIP, PoE. Suitable for use in harsh environments thanks to particularly robust PUR sheath.
I
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during operation Tensile strength (max.)
5 x overall diameter (min.) 60 N
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Transfer impedance at 10 MHz (nominal value) 5 mΩ/m Shielding attenuation up to 1,000 MHz (nominal value) 60 dB Coupling attenuation up to 1,000 MHz (nominal value) 85 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office Office
Industry Industry
DataCenter 67
Electrical characteristics (HF) at 20 °C Attenuation dB/10 m
NEXT dB
PSNEXT dB
typ.
Cat. 7A max.*
typ.
Cat. 7A min.*
1
0.25
0.29
100
10
0.76
0.85
99
ACR dB at 10 m
typ.
Cat. 7A min.*
typ.
Cat. 7A min.*
80
97
77
100
80
80
96
77
99
79
PSACR dB at 10 m typ.
ELFEXT dB at 10 m
PSELFEXT dB at 10 m
RL dB
Cat. 7A min.*
typ.
Cat. 7A min.*
typ.
Cat. 7A min.*
typ.
Cat. 7A min.*
97
77
100
80
97
80
24
23
96
77
95
74
92
71
33.9
25 20.1
100
2.49
2.78
95
72
92
69
93
70
90
69
69
54
66
51
38.3
200
3.69
4.01
92
68
89
65
88
64
85
65
65
48
62
45
35.3
18
250
4.18
4.53
90
66
87
63
86
62
83
63
62
46
59
43
32.9
17.3
500
5.6
6.62
83
62
80
59
78
55
75
59
54
40
51
37
29.7
17.3
600
6.74
7.33
81
61
78
58
74
53
71
58
50
38
47
35
30.6
17.3
700
7.32
–
80
–
77
–
72
–
69
–
50
–
47
–
31
–
800
7.89
–
77
–
74
–
69
–
66
–
50
–
47
–
26.7
–
900
8.5
–
75
–
72
–
67
–
64
–
34
–
31
–
28.6
–
1000
9.11
–
74
–
71
–
65
–
62
–
32
–
29
–
27.5
–
1100
9.5
–
72
–
69
–
63
–
60
–
28
–
25
–
26.9
–
1200
9.9
–
70
–
67
–
61
–
58
–
24
–
21
–
26.3
–
*EN 50288-4-2(2004)/IEC 61156-6(2002)
Electrical characteristics (LF) at 20 °C
Chemical characteristics
DC resistance
max.
145 Ω/km
Free from hazardous substances acc. to RoHS 2002/95/EC,
Insulation resistance
min.
5 GΩ x km
oil resistant acc. to EN 60811-2-1,
Mutual capacitance
approx.
44 pF/m
resistant to microbes acc. to DIN VDE 0282,
Signal velocity (c)
approx.
0.78
resistant to chemicals,
Propagation delay
approx.
440 ns/100 m
resistant to hydrolysis acc. to DIN 53504,
Skew at 100 MHz
approx.
2.5 ns/100 m
free from paint-wetting impairment substances (e.g. silicone oil)
Characteristic impedance
at 100 MHz
100 ± 5 Ω
Testing voltage Ueff Operating voltage
max.
1,000 V
Printing on outer sheath
125 V
LEONI MegaLine F10-120 S/F flex 4P 11Y SPICE Code 14525 "production lot code" "meter marking"
Thermal characteristics For fixed installation
–40 °C up to +70 °C
Colour code
For mobile operation
–10 °C to +50 °C
wh/bu, wh/or, wh/gn, wh/bn Certificates and approvals Link performance: LEONI MegaLine® systems and further commercial connector systems Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204 Conforms to LVD (73/23/EEC):
Dimensions
Outer diam. approx.
Weight approx.
Cu content
mm
kg/km
kg/km
6.4
45
23,5
4p Package: Drum 1,000 m
www.leoni-infrastructure-datacom.com
Colour of sheath
Order no.
● Rape yellow RAL 1021
LKD 7KS7 0090 0000
MegaLine® Cu data cables
Frequency MHz
68
MegaLine® F6-70 S/F 11Y flex
Type KS-02YSC11Y 4x2xAWG 24/7 PIMF
Category 7
S2 P3 I4 C3 E5
Construction
Conductor
Bare stranded copper wire, AWG 24/7
Insulation Twisting element
Cellular-PE, core-diameter: nominal value 1.55 mm Pair
Individual shielding Twisting
Aluminium-bonded polyester foil, metal side outside (PiMF) 4 pairs
Overall shielding
Tinned copper braiding
Outer sheath
PUR, flame-retardant
Security (fire behaviour) Fire behaviour Flame retardancy Halogen free Smoke density Calorific value (approx.)
acc. to IEC 60332-1-2 acc. to IEC 60754-1/2 acc. to IEC 61034-1/2 0.99 MJ/m
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Performance Better than Category 7 acc. to EN 50288 and IEC 61156 excellent NEXT, low attenuation, excellent shielding characteristics (shielding of pairs and overall shielding), low skew, bandwidth 700 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Industrial application (Ethernet, TV) Applications Connection cable and patch cord for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition) as well as ISO/IEC 24702 and EN 50173-3. Ideal for all applications from Classes D to F Multimedia (video, data, voice) >10 GbE acc. to IEEE 802.3 an, cable sharing, VoIP, PoE. Suitable for use in harsh environments thanks to particularly robust PUR sheath.
I
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during operation Tensile strength (max.) Crush strength Impact strength (number of shocks)
5 x overall diameter (min.) 100 N 1,000 N/100 mm 10
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Transfer impedance at 10 MHz (nominal value) 5 mΩ/m Shielding attenuation up to 1,000 MHz (nominal value) 60 dB Coupling attenuation up to 1,000 MHz (nominal value) 90 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office Office
Industry Industry
DataCenter 69
Electrical characteristics (HF) at 20 °C Attenuation dB/10 m typ.
Cat. 7 max.*
NEXT dB typ.
PSNEXT dB
Cat. 7 min.*
typ.
Cat. 7 min.*
ACR dB at 10 m typ.
Cat. 7 min.*
PSACR dB at 10 m typ.
Cat. 7 min.*
ELFEXT dB at 10 m typ.
Cat. 7 min.*
PSELFEXT dB at 10 m typ.
RL dB
Cat. 7 min.*
typ.
Cat. 7 min.*
1
0.23
0.29
90
80
87
77
90
80
87
77
90
80
87
77
23.3
–
4
0.4
0.55
90
80
87
77
90
79
87
77
90
80
87
77
25
23
10
0.63
0.85
90
80
87
77
89
79
86
77
90
74
87
71
30
25
16
0.79
1.08
90
80
87
77
89
79
86
77
90
70
87
67
30
25
20
0.91
1.21
90
80
87
77
89
79
86
77
85
68
82
65
30
25
100
2.07
2.78
81
72.4
78
69
79
70
76
69
64
54
61
51
24
20.1
200
3.07
4.01
76
67.9
73
65
73
64
70
65
57
48
54
45
24
18
250
3.43
4.53
74
66.5
71
63
71
62
68
63
53
46
50
43
24
17.3
500
4.77
6.62
70
61.9
67
59
65
55
62
59
45
40
42
37
21
17.3
600
5.23
7.33
68
60.8
65
58
63
53
60
58
42
38
39
35
21
17.3
700
5.65
–
65
–
62
–
59
–
56
–
39
–
36
–
19
–
*EN 50288-4-2(2004)/IEC 61156-6(2002)
Electrical characteristics (LF) at 20 °C
Chemical characteristics
DC resistance
max.
84 Ω/km
Free from hazardous substances acc. to RoHS 2002/95/EC,
Insulation resistance
min.
5 GΩ x km
oil resistant acc. to EN 60811-2-1,
Mutual capacitance
approx.
42.5 pF/m
resistant to ozone acc. to EN 60811,
Signal velocity (c)
approx.
0.72
resistant to microbes acc. to DIN VDE 0282,
Propagation delay
approx.
460 ns/100 m
resistant to chemicals,
Skew at 100 MHz
approx.
7 ns/100 m
resistant to hydrolysis acc. to DIN 53504,
Characteristic impedance
at 100 MHz
100 ± 5 Ω
free from paint-wetting impairment substances (e.g. silicone oil)
Testing voltage Ueff Operating voltage
1,000 V max.
125 V
Printing on outer sheath LEONI MegaLine F6-70 S/F flex 4P 11Y SPICE Code 23435
Thermal characteristics
"production lot code" "meter marking"
For fixed installation
–40 °C up to +70 °C
For mobile operation
–10 °C to +50 °C
Colour code wh/bu, wh/or, wh/gn, wh/bn Certificates and approvals Link performance: LEONI MegaLine® systems and further commercial connector systems Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204 Conforms to LVD (73/23/EEC):
Dimensions
Outer diam. approx.
Weight approx.
Cu content
mm
kg/km
kg/km
8.8
73
35
4p Package: Drum 1,000 m
www.leoni-infrastructure-datacom.com
Colour of sheath
Order no.
● Rape yellow RAL 1021
LKD 7KS7 0139 0000
MegaLine® Cu data cables
Frequency MHz
70
MegaLine® D1-20 S/U 11Y superflex
Type KS-6Y3GC11Y 4x2xAWG 26/19
Category 5
S1 P0 I1 C2 E4
Construction
Conductor
Bare stranded copper wire, AWG 26/19
Insulation Twisting element Twisting Tape
FEP, core-diameter: nominal value 1.0 mm Pair 4 pairs Fleece foil
Inner sheath Tape
EPDM Fleece foil
Overall shielding
Tinned copper braiding, approx. 90% optically opaque
Outer sheath
PUR
Security (fire behaviour) Fire behaviour Flame retardancy Calorific value (approx.)
acc. to IEC 60332-2-2 0.7 MJ/m
S
1 IEC 603322-2
2 IEC 603321-2
3 IEC 603323-24
4 EFP Grade 1
5 EFP Grade 2
Performance (cabling class, bandwidth) Performance Better than Category 5 acc. to EN 50288 and IEC 61156 excellent shielding characteristics, bandwidth 100 MHz
P
1 > Class E > 250 MHz
2 > Class E A > 500 MHz
3 > Class F > 600 MHz
4 5 > Class FA > Class "G" > 1000 MHz > 1200 MHz
Industrial application (Ethernet, TV) Applications Connection cable and patch cord for use in structured cabling systems acc. to ISO/IEC 11801 and EN 50173 (2nd edition) as well as ISO/IEC 24702 and EN 50173-3. Ideal for all applications from Class D up to 1 GbE acc. to IEEE 802.3 ab, VoIP, PoE. Suitable for use in harsh environments thanks to EPDM inner sheath and particularly robust PUR outer sheath. Suitable for use with drag chains.
I
1 > 100 MbE
2 > 1 GbE
3 Up to 10 GbE
4 > 10 GbE
5 > 10 GbE TV
Construction (conductor dimensions, tensile strength) Mechanical characteristics Bending radius during operation Tensile strength (max.) Crush strength Impact strength (number of shocks)
5 x overall diameter (min.) 60 N 2,000 N/100 mm 20
C
1 AWG 27
2 AWG 26/25
3 AWG 24
4 AWG 23
5 AWG 22
3 > 60 dB
4 > 70 dB
5 > 80 dB
EMC (coupling attenuation) Electromagnetic behaviour Transfer impedance at 10 MHz (nominal value) 25 mΩ/m Shielding attenuation up to 1,000 MHz (nominal value) 55 dB Coupling attenuation up to 1,000 MHz (nominal value) 75 dB
E
1 > 40 dB
2 > 50 dB
www.leoni-infrastructure-datacom.com
Office Office
Industry Industry
DataCenter 71
Electrical characteristics (HF) at 20 °C Attenuation dB/10 m typ.
NEXT dB
Cat. 5 max.*
typ.
PSNEXT dB
Cat. 5 min.*
ACR dB at 10 m
typ.
Cat. 5 min.*
typ.
Cat. 5 min.*
PSACR dB at 10 m
ELFEXT dB at 10 m
typ.
Cat. 5 min.*
typ.
Cat. 5 min.*
PSELFEXT dB at 10 m typ.
Cat. 5 min.*
RL dB typ.
Cat. 5 min.*
1
0.22
0.32
80
65
77
62
80
65
77
62
80
64
77
61
27
–
4
0.56
0.60
67
56
64
53
67
56
64
53
69
52
66
49
26
23
10
1
1.05
63
50
60
47
62
49
59
47
61
44
65
58
30
25
16
1.35
1.45
61
47
58
44
60
46
57
44
56
40
53
37
30
25
20
1.5
1.6
59
46
56
43
58
44
55
43
53
38
50
35
30
25
31.25
1.95
2
57
43
54
40
55
41
52
40
48
34
45
31
30
23.6
62.5
2.95
3
52
38
49
35
50
36
47
35
43
28
40
25
28
21.5
100
3.95
4
45
35
42
32
42
32
39
32
38
24
35
21
26
20.1
* Based on EN 50288-2-2(2004)/IEC 61156-6(2002)
Electrical characteristics (LF) at 20 °C
Chemical characteristics
DC resistance
max.
130 Ω/km
Free from hazardous substances acc. to RoHS 2002/95/EC,
Insulation resistance
min.
5 GΩ x km
oil resistant acc. to EN 60811-2-1,
Mutual capacitance
approx.
50 pF/m
resistant to ozone acc. to EN 60811,
Signal velocity (c)
approx.
0.68
resistant to microbes acc. to DIN VDE 0282,
Propagation delay
approx.
490 ns/100 m
resistant to chemicals,
Skew at 100 MHz
approx.
15 ns/100 m
resistant to hydrolysis acc. to DIN 53504,
Characteristic impedance
at 100 MHz
100 ± 5 Ω
free from paint-wetting impairment substances (e.g. silicone oil)
Testing voltage Ueff Operating voltage
1,000 V max.
125 V
Printing on outer sheath LEONI MegaLine D1-20 S/U superflex 4P 11Y SPICE Code 10124
Thermal characteristics
"production lot code" "meter marking"
For fixed installation
–40 °C up to +85 °C
For mobile operation
0 °C to +50 °C
Colour code gr/or, bl/rd, gn/ye, bu/bn Certificates and approvals Link performance: LEONI MegaLine® systems and further commercial connector systems Inspection certificates: acc. to DIN 55350-18-4.2.1/EN 10204 Conforms to LVD (73/23/EEC):
Dimensions
Outer diam. approx.
Weight approx.
Cu content
mm
kg/km
kg/km
6.8
58
28,6
4p Package: Drum 1,000 m
www.leoni-infrastructure-datacom.com
Colour of sheath
Order no.
● Rape yellow RAL 1021
LKD 7KS5 0051 0000
MegaLine® Cu data cables
Frequency MHz
72
VarioKeystone Cu connectivity ®
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter
VarioKeystone® Cu connectivity VarioKeystone®
The innovative connection concept.
74
VarioKeystone®
One click takes you to the next generation.
75
VarioKeystone®
Benefits that speak for themselves.
76
VarioKeystone®
No limits.
77
VarioKeystone®
System overview
78
o dc i
Cable plugs
• Cable plug Cat. 7/6A • Crossconnect cable plug Cat. 7
o dc i
Jack modules
• Jack module 4K7 Cat. 7 • Jack module RJ45 Cat. 6A
81
o dc i
Double modules RJ45
• Double module Ethernet • Double module ISDN • Double module Ethernet/ISDN
82
o dc i
Link extender
Class EA
83
o dc i
Telephone patch panel
1 RU, 25 ports
83
o dc i
Patch panels 19"
• Patch panel 19" fixed 6x4 • Patch panel 19" telescopic 6x4
84
dc
Modular patch panel 19"/1 RU
For VarioKeystone® single or double modules
85
dc
Modular patch panel 19“/1 RU
For VarioKeystone® link extenders
86
i
DIN rail housing
Dual, with double DIN rail clip
87
i
Industrial housing IP44
For wall mounting
88
i
Industrial housing IP65/67
Han® 3 A, equipped with VarioKeystone® RJ45
88
o dc i
Wall outlets
For VarioKeystone® jack modules
89
VarioKeystone® accessories
• Dust protective cap • Dummy cover • Dust protective plug • Measuring cable set Tera – Tera • Measuring cable set RJ45 – RJ45 • Measuring cable set Tera – Crossconnect
90
o dc i
Cable assembly tools
• Parallel pliers • UTP/FTP/foil stripping tool • Stripper • Release tool • Copper tape • Assembly set 1/2
91
o
Office
o dc i
dc i
DataCenter Industry
www.leoni-infrastructure-datacom.com
80
VarioKeystone® Cu connectivity
73
74
VarioKeystone® The innovative connection concept
Long downtimes and high installation costs are constant
The basic configuration consisting of a Category 7 data cable
challenges for those in charge of IT when the existing
and cable connector is completed by simply snapping on the
cabling infrastructure is changed. The problem will
desired jack module.
worsen in future as a result of the constantly increasing requirements for data transmission.
The user can choose between RJ45 jack modules according to Category 6A (IEC 60603-7-51) and 4K7 (interface according
Against this background, cabling systems that allow upgrades
to IEC 61076-3-104) according to Category 7.
and migrations to be performed in an extremely short time without costly re-installation take on greater significance. VarioKeystone® is a cabling system whose modular design allows migration from Category 6 to Category 7 at any time without the necessity of re-installing the existing cabling infrastructure.
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 75
VarioKeystone®
VarioKeystone® Cu connectivity
One click takes you to the next generation
VarioKeystone® release tool – for easy and fast migration "with a click"
For migration, the new release tool allows the cable plug and
extremely short link lengths of one metre to be realised.
jack module to be separated safely, rapidly and effortlessly
The permanent link of Class EA is reached with considerable
using lever action.
reserves of typically 6 dB in near-end crosstalk (NEXT).
In this way, the existing cabling system can be adapted
Modular patch panels, wall outlets, floorbox solutions and
to fit the new requirements in a few minutes "with a click".
consolidation point housings complete the product range.
Easy installation is particularly useful in DataCenters where system migrations must be achieved with zero downtime.
VarioKeystone® combines a secure future with flexibility while
Pre‑assembled trunks help to keep the necessary assembly
ensuring maximum performance and ease of assembly.
times to a minimum. The cable links in the DataCenter are often below the 15 m mark. The standards speak of a "short link" here, and this is where the men are separated from the boys in terms of product technology. The VarioKeystone® system allows
www.leoni-infrastructure-datacom.com
76
VarioKeystone® Benefits that speak for themselves
+ High performance
+ Flexibility
• For all classes (D to F) and categories (5 to 7)
• Thanks to interchangeable jack modules
• Thanks to the release tool
• For permanent link above 1 m with class EA
• Thanks to the extension option with
• High EMC, alien crosstalk by design
• PoE and PoE plus
• Thanks to modular and telescopic patch panels
• Extremely sturdy thanks to solid metal design
• Thanks to pre-assembled links
• Excellent strain relief
incl. Multimedia +40 GbE
the VarioKeystone® link extender
+ Cost-efficiency
+ Future-proofing
• Thanks to unique, multi-use cable connection
• Thanks to interchangeable jack modules with different
• Thanks to upward and downward compatibility
• Thanks to modular and telescopic patch panels
• Thanks to conformity with standards
• Thanks to low maintenance and service costs
• Thanks to independent certification
• Thanks to short upgrade times using the release tool
• Thanks to short mounting times
• Thanks to pre-assembled links (minimal downtime)
(maintains value) performance levels and mating faces
• Thanks to a variety of interchangeable jack modules different performance levels and mating faces (acc. to standard or customer-specific)
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 77
VarioKeystone®
VarioKeystone® Cu connectivity
No limits
Cat. 5/6
Cat. 6A
Cat. 7
Upward compatibility when it comes to performance…
…AND what the future holds.
VarioKeystone® is the innovative connection concept for structured and universal IT cabling systems. The modular component design means that jack modules can be exchanged at any time with minimal effort.
www.leoni-infrastructure-datacom.com
78
VarioKeystone® Cu connectivity System overview
VarioKeystone® is the innovative connection concept
The link extender is an easy means of extending cable links
for building cabling systems. The modular design
without any significant reduction in performance.
of the components enables both current and future requirements to be met.
VarioKeystone® maintains the value of your investments – in the long term.
The modular design of the available RJ45 jack modules Cat. 6A (IEC 60603-7-51) and 4K7 (IEC 61076-3-104) allows them to be replaced with relatively little effort. This makes it easy to choose the right mating face.
Pre-assembled cable Cable plug MegaLine® G12-150 S/F MegaLine® F10-130 S/F MegaLine® F10-115 S/F
Cat. 7
Cable plug Cat. 6A
Crossconnect cable plug Cat. 7
Cable
Cable plugs www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 79
Jack module
Cat. 6A
Cat. 7 (Tera)
Cat. 6A (RJ45)
see page 80
see page 80
see page 81
see page 81
Cat. 5/Cat. 3 (double module RJ45) (ETH/ETH) see page 82
(ETH/ISDN*) see page 82
(ISDN/ISDN) see page 82
✔ ✔
✔ ✔
✔
The following performance classes are reached with the cable plug/jack module combination
Class FA
✔
Class F
✔ ✔ ✔
✔ ✔
✔ ✔ ✔
✔ ✔
✔ ✔ ✔
✔ ✔ ✔
✔ ✔ ✔
✔ ✔ ✔
(channel)
Class EA (PL) Class EA
(channel)
Class E Class D Class C
✔
VarioKeystone® wall outlets
Jack module 4K7 Cat. 7
VarioLine® UF underfloor systems
Jack module RJ45 Cat. 6A
VarioLine® CP consolidation point housing
Double module RJ45
VarioKeystone® modular panel Link extender
19"/1 RU
Class EA
Jack modules www.leoni-infrastructure-datacom.com
Housing
VarioKeystone® Cu connectivity
Cable plug Cat. 7
80
VarioKeystone® Cable plugs Category 7/6A
Crossconnect cable plug Cat. 7 red contact block
Cable plug Cat. 6A aqua contact block
Cable plug Cat. 7 white contact block
VarioKeystone® Cable plug
VarioKeystone® Crossconnect cable plug
Description
Description
Interface to the individually interchangeable VarioKeystone®
Interface to the individually interchangeable VarioKeystone®
jack module. The cable plug enables generic transmission
jack module. The cable plug enables generic transmission
links far exceeding the requirements for Class F to be achieved.
links far exceeding the requirements for Class F to be achieved.
The mating face can also be identified later without any
The mating face can also be identified later without any
additional installation effort.
additional installation effort.
■■
Various mating faces available
■■
Various mating faces available
■■
Easy and quick assembly
■■
Easy and quick assembly
■■
Required for extending links in combination with the link extender
Construction
Construction
Material
Full metal; die-cast zinc, nickel-plated
Material
Full metal; die-cast zinc, nickel-plated
Wiring
4 pairs via punchdown method
Wiring
4 pairs via punchdown method
Strain relief
Via cable ties
Strain relief
Via cable ties
Shielding
Large-surface 360° shield connection
Shielding
Large-surface 360° shield connection
Contact block: white/aqua Electrical values
Contact block: red Electrical values
Category 7/6A
Standards
Standards
■■
ISO/IEC 11801
■■
ISO/IEC 11801
■■
EN 50173-1
■■
EN 50173-1
Article
Category 7
Cat.
Order no.
Article
Category
Order no.
9.0 mm hole for AWG 23
10.0 mm hole for AWG 22
VarioKeystone® Crossconnect (9.0 mm hole for AWG 23)
Cat. 7
LKD 9A46 0055 0000
VarioKeystone® Crossconnect (10.0 mm hole for AWG 22)
Cat. 7
LKD 9A46 0058 0000
VarioKeystone® cable plug – white
Cat. 7
LKD 9A46 0054 0000
LKD 9A46 0057 0000
VarioKeystone® cable plug – aqua
Cat. 6A
LKD 9A46 0129 0000
LKD 9A46 0130 0000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 81
VarioKeystone® Jack modules
VarioKeystone® Cu connectivity
Category 7/6A
Jack module Cat. 6A aqua
VarioKeystone® Jack module 4K7
Cat. 7
VarioKeystone® Jack module RJ45
Cat. 6A
Description
Description
For transmitting analogue and digital voice, image and data
For transmitting analogue and digital voice, image and data signals.
signals. The performance corresponds to Class F up to 600 MHz
The performance corresponds to Category 6A up to 500 MHz.
according to EN 50173-1. Aufbau
Construction Material
Full metal; die-cast zinc, nickel-plated
Material
Full metal; die-cast zinc, nickel-plated
Installation dimen-
According to the installation dimensions
Installation dimen-
According to the installation dimensions
of the jack module RJ45 and thus
sions
of the jack module 4K7 and thus
sions
interchangeable
interchangeable Wiring
4 pairs via cable plug
Wiring
4 pairs via cable plug
Connection
Jack 4K7
Connection
Jack RJ45
Standards ■■
ISO/IEC 11801
Standards
■■
EN 50173-1
■■
ISO/IEC 11801
■■
EN 61076-3-104
■■
EN 50173-1
■■
IEC 60603-7-51
Accessories
see from page 90
Installed by pushing onto the cable plug.
Accessories
Easy replacement using the release tool.
Installed by pushing onto the cable plug.
see from page 90
Easy replacement using the release tool.
Article
Category
Order no.
Article
Category
Order no.
VarioKeystone® jack module 4K7
Cat. 7
LKD 9A46 0061 0000
VarioKeystone® jack module RJ45 – aqua
Cat. 6A
LKD 9A46 0128 0000
www.leoni-infrastructure-datacom.com
82
VarioKeystone® Double modules RJ45 Category 6/3
Double module Ethernet
VarioKeystone® Double module Ethernet VarioKeystone® Double module ISDN VarioKeystone® Double module Ethernet/ISDN
Double module ISDN
Double module Ethernet/ISDN
Description
Construction
The double module RJ45 allows reversible cable sharing
Material
Full metal; die-cast zinc, nickel-plated
by splitting the four pairs between two RJ45 jacks.
Wiring
2x2 pairs via cable plug
Assignment
See table
Electrical values
See table
The transmission data corresponds to Cat. 6/3. Subsequent retrofitting to Cat. 7 is possible at any time if the cable is fitted with Category 7 cable plugs. The zinc die-cast housing offers maximum shielding and excellent stability. ■■
Fits all V arioKeystone® patch panels
■■
Can be used in the VarioKeystone® triple data outlet
Standards ■■
ISO/IEC 11801
■■
EN 50173-1
■■
IEC 60603-7-5, IEC 60603-7-3
in combination with the dummy cover (see from page 89)
Fig.
Article
Assignment
Category
Order no.
1
VarioKeystone® Double module Ethernet
RJ45 jack A RJ45 jack B
1.2 – 3.6 1.2 – 3.6
Cat. 6
LKD 9A46 0093 0000
2
VarioKeystone® Double module ISDN
RJ45 jack A RJ45 jack B
3.6 – 4.5 3.6 – 4.5
Cat. 3
LKD 9A46 0124 0000
3
VarioKeystone® Double module Ethernet/ISDN
RJ45 jack A RJ45 jack B
1.2 – 3.6 3.6 – 4.5
Jack A Jack B
Cat. 6 Cat. 3
LKD 9A46 0096 0000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 83
VarioKeystone® Telephone patch panel
Class EA
1 RU, 25 ports
VarioKeystone® Cu connectivity
VarioKeystone® Link extender
VarioKeystone® Link extender
VarioKeystone® Telephone patch panel
Description
Description
For extending an existing cable infrastructure to up to 90 m without
Patch panel for transmitting analogue and digital telephone
transmission losses on the basis of the VarioKeystone® system.
signals.
Its small size means that the extender can also be retrofitted
With integrated cable management for easy and safe installation.
in the cable duct at any time. Note that it is necessary to connect a standard cable plug on one side and the Crossconnect plug
Construction
on the other. This plug differs from the cable plug in that
Housing
Steel panel
it has a red LSA insert. Depending on the link used, the link
Colour
Light grey RAL 7035
performance to be achieved is suitable for Class E or Class EA.
Labelling
1–25
Capacity
25 x 8 IDC terminals for max. 100 DA
Each pair is continued with separate shielding, which means
(AWG 24 – AWG 23)
that the cable transmission data are only affected minimally.
Strain relief
Via cable ties
This means that it is possible to continue transferring 10 Gigabit
Cable entry
Over the entire width of the cable
Ethernet via an extended link.
management rail
Construction
Layout
25 ports (TERA 4 p)
Panel
44 mm x 485 mm x 100 mm (H x W x D)
Material
Full metal; die-cast zinc, nickel-plated
Shielding
Large-surface 360° shield connection
Dimensions
Electrical values
Class EA
19"/1 RU 100 mm installation depth
Standards ■■
ISO/IEC 11801
■■
EN 50173-1
Article
Class
Order no.
Article
Order no.
VarioKeystone® Link extender (1 piece)
Class E A
LKD 9A46 0062 0000
VarioKeystone® Telephone patch panel (1 piece)
LKD 9A62 0002 0000
www.leoni-infrastructure-datacom.com
84
VarioKeystone® Patch panel 19" fixed/telescopic
VarioKeystone® Patch panel 19" fixed 6x4
VarioKeystone® Patch panel 19" telescopic 6x4
Description
Description
The patch panel can be equipped with up to 24 jack modules.
The patch panel can be equipped with up to 24 jack modules.
For holding different module types simultaneously (RJ45, 4K7,
For holding different module types simultaneously (RJ45, 4K7,
double modules).
double modules).
As a result of its simple construction, this patch panel provides a
In the extended state, the drawer can be inclined downwards,
reasonably priced alternative to telescopic patch panels.
thus making the various jack modules easy to change. Easy opening and closing of the drawer is ensured by a captive screw connection accessible on the front.
Construction
Construction
Housing
Full metal
Housing
Full metal
Colour
Light grey RAL 7035
Colour
Light grey RAL 7035
Capacity
Up to 24 jack modules: 4K7/RJ45
Capacity
Up to 24 jack modules: 4K7/RJ45
4 jack modules (or two double modules)
4 jack modules (or two double modules)
can be mounted per window
can be mounted per window
Strain relief
Via cable ties
Strain relief
Via cable ties
Earthing
Via screw on the rear of the panel
Earthing
Via riveted cable shoe on the left-hand
Cable entry
Over the entire width of the cable management rail
and right-hand side of the drawer Cable entry
Over the entire width of the cable management rail
Dimensions
Dimensions
19"/1 RU
19"/1 RU
100 mm installation depth
100 mm installation depth
Article
Order no.
Article
Order no.
VarioKeystone® Patch panel fixed 6x4 (1 piece)
LKD 9A67 0006 0000
VarioKeystone® Patch panel telescopic 6x4 (1 piece)
LKD 9A67 0000 0000
www.leoni-infrastructure-datacom.com
Office
DataCenter Industry
Industry
85
VarioKeystone® Modular patch panels 19"/1 RU
Fig. 1 Patch panel 16 EM, fully mounted
Fig. 2 Patch panel 24 EM, fully mounted
VarioKeystone® Patch panel 16 EM VarioKeystone® Patch panel 24 EM VarioKeystone® Patch panel 8 DM VarioKeystone® Patch panel 12 DM
Fig. 3 Patch panel 8 DM, fully mounted
Fig. 4 Patch panel 12 DM, fully mounted
Description
Cable socket carrier
Modular three-part universal patch panel for 16 or 24 Vario
■■
Unit for cable plugs
Keystone® ports for installing single modules (EM) or double
■■
Mounted outside the cabinet or base carrier
modules (DM). Modules can be hot-swapped.
■■
Is inserted into the rear of the base carrier following mounting
■■
Secured using slide latch
■■
Potential equalisation by means of two threaded bolts M5
■■
Allows the integration of an electronic cable management system
■■
and/or two earth lugs
Can be replaced with single/double modules by changing the stainless steel front panel
Stainless steel front cover (depending on design) Patch panel 16 EM
Cut-outs for 16 single modules
Patch panel set
Patch panel 24 EM
Cut-outs for 24 single modules
Consisting of base carrier, cable socket carrier, stainless steel
Patch panel 8 DM
Cut-outs for 8 double modules
front panel
Patch panel 12 DM
Cut-outs for 12 double modules
Base carrier
Construction
■■
For holding a cable socket carrier
■■
Is pre-installed in the cabinet or rack
Strain relief
Via cable ties
Cable entry
Over the entire width of the cable management rail
Dimensions
Labelling Using labelling strip made from aluminium, self-adhesive (must be ordered separately, see table)
44 mm x 483 mm x 163 mm (H x W x D)
Accessories (must be ordered separately – from page 80) Single modules: RJ45 Cat. 6A , 4K7 (TERA) Double modules: Ethernet/Ethernet, Ethernet/telephony, telephony/telephony
Fig.
Article
Capacity
Ports
Order no.
1
VarioKeystone® Patch panel 16 EM
For installing 16 single modules: RJ45 Cat. 6A/4K7 (TERA)
For 16 VarioKeystone® ports
LKD 9A67 0019 0000
2
VarioKeystone® Patch panel 24 EM
For installing 24 single modules: RJ45 Cat. 6A/4K7 (TERA)
For 24 VarioKeystone® ports
LKD 9A67 0011 0000
3
VarioKeystone® Patch panel 8 DM
For installing 8 double modules: Ethernet/Ethernet, Ethernet/telephony, telephony/telephony
For 16 VarioKeystone® ports
LKD 9A67 0022 0000
4
VarioKeystone® Patch panel 12 DM
For installing 12 double modules: Ethernet/Ethernet, Ethernet/telephony, telephony/telephony
For 24 VarioKeystone® ports
LKD 9A67 0020 0000
–
VarioKeystone® Labelling strip
www.leoni-infrastructure-datacom.com
LKD 9A67 0024 0000
VarioKeystone® Cu connectivity
for VarioKeystone® single or double modules
86
VarioKeystone® Modular patch panels 19"/1 RU for VarioKeystone® link extenders
Base carrier Patch panel 24 EX, fully mounted
Cable socket carrier
VarioKeystone® Patch panel 16 EX VarioKeystone® Patch panel 24 EX
Stainless steel front panel
Description
Cable socket carrier
Modular three-part universal patch panel for 16 or 24
■■
Unit for holding the cable plugs
VarioKeystone® ports for holding the VarioKeystone® link
■■
Mounted outside the cabinet or base carrier
extender (EX).
■■
Is inserted into the rear of the base carrier following mounting
■■
Secured using slide latch
■■
Potential equalisation by means of two threaded bolts M5
■■
Allows the integration of an electronic cable management system
■■
and/or two earth lugs
Can be replaced with single/double modules by changing the stainless steel front panel
Stainless steel front panel
Patch panel set
Patch panel 16 EX
Cut-outs for 16 link extenders
Patch panel 24 EX
Cut-outs for 24 link extenders
Consisting of base carrier, cable socket carrier, stainless steel Construction
front panel Base carrier ■■
For holding a cable socket carrier
■■
Is pre-installed in the cabinet or rack
Strain relief
Via cable ties
Cable entry
Over the entire width of the cable management rail
Dimensions
44 mm x 483 mm x 163 mm (H x W x D)
Labelling
Accessories
Using labelling strip made from aluminium, self-adhesive
VarioKeystone® link extender (must be ordered separately)
see page 82
(must be ordered separately, see table)
Article
Capacity
Ports
Order no.
VarioKeystone® Patch panel 16 EX
For installing extension modules: VarioKeystone® link extender
For 16 VarioKeystone® ports
LKD 9A67 0023 0000
VarioKeystone® Patch panel 24 EX
For installing extension modules: VarioKeystone® link extender
For 24 VarioKeystone® ports
LKD 9A67 0021 0000
VarioKeystone® Labelling strip
LKD 9A67 0024 0000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 87
VarioKeystone® DIN rail housing
VarioKeystone® Cu connectivity
Dual, with DIN rail clip
VarioKeystone® DIN rail housing, dual Description With DIN rail clip for holding up to 2 VarioKeystone® jack modules. The housing is mounted by snapping it onto the existing DIN rails. The metal housing is particularly suitable for use in industrial environments (IP20). Construction Material
Steel panel, powder-coated
Colour
Light grey RAL 7035
Capacity
For up to 2 VarioKeystone® jack modules
Dimensions 85 mm x 35 mm x 95 mm (H x W x D)
Article
Order no.
VarioKeystone® DIN rail housing, dual (1 piece)
LKD 9A46 0097 0000
www.leoni-infrastructure-datacom.com
88
VarioKeystone® Industrial housing IP44 VarioKeystone® Industrial housing IP65/67 for wall mounting
Han® 3 A, equipped with VarioKeystone® RJ45
VarioKeystone® Industrial housing IP44
VarioKeystone® Industrial housing IP65/67
Description
Description
Suitable for up to 2 VarioKeystone® jack modules
Extremely robust housing, which means it can also be used near
(RJ45, 4K7 double module).
welding robots.
The robust plastic housing is suitable for use in harsh industrial environments (IP44). The wall housing is lockable and prevents
Construction
unauthorised use of the data network.
Interface
Han® 3 A, lockable
Housing
Steel panel, powder-coated
Colour
Light grey RAL 7035
Protection class
IP65/IP67
Construction Material
Plastic
Colour
Light grey RAL 7035
Housing
Lockable, unequipped
Connections
Mounting
Via 4 screws
■■
Includes 2 VarioKeystone® cable plugs (Cat. 7) and jack module RJ45 (Cat. 6A)
Dimensions
■■
Quick connection method for the horizontal cable via VarioKeystone® modules
120 mm x 120 mm x 90 mm (H x W x D) ■■
Office patch cord can be plugged in (e.g. for test purposes)
Article
Order no.
Article
Order no.
VarioKeystone® Industrial housing IP44 (1 piece)
LKD 9A46 0111 0000
VarioKeystone® Industrial housing IP65/67
LKD 9ZE9 7004 0000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 89
VarioKeystone® Wall outlets
Fig. 1 Wall outlet 50 x 50/single gang
Fig. 2 Wall outlet 50 x 50/double gang
VarioKeystone® Cu connectivity
For VarioKeystone® jack modules
Fig. 3 Wall outlet 50 x 50/triple gang
VarioLine® Wall outlets 50 x 50 Description
Installation dimensions
Wall outlets for installation in commercially available 50 x 50 mm
50 mm x 50 mm (H x W), downward inclination of 30°
cover frames for equipping with VarioKeystone® jack modules. Accessories (optional) Housing
VarioKeystone® cover frame, single and double gang
Housing body
Full metal; die-cast zinc, nickel-plated
40 mm surface-mounted housing incl. single-gang flush-
Colours
Pure white RAL 9010
mounted cover frame
or Oyster white RAL 1013
Spacer frame for single-gang surface-mounted housing, 10 mm
Labelling
Fig.
Via labelling field
Designation
1
VarioKeystone® Wall outlet 50 x 50/single gang (1 piece)
2
VarioKeystone® Wall outlet 50 x 50/double gang (1 piece)
3
VarioKeystone® Wall outlet 50 x 50/triple gang (1 piece)
Colour
Order no.
● Oyster white RAL 1013
LKD 9A46 0105 0000
Colour
Order no.
● Pure white RAL 9010
LKD 9A46 0108 0000
LKD 9A46 0107 0000
LKD 9A46 0104 0000
LKD 9A46 0106 0000
LKD 9A46 0109 0000
–
Single-gang flush-mounted cover frame (1 piece)
LKD 9A41 0002 0000
LKD 9A41 0003 0000
–
Double-gang flush-mounted cover frame (1 piece)
LKD 9A41 0004 0000
LKD 9A41 0005 0000
–
40 mm surface-mounted housing incl. single-gang flush-mounted cover frame (1 piece)
● Pure white LKD 9A46 0087 0000 RAL 9010
LKD 9A46 0086 0000
–
Spacer frame for single-gang surface-mounted housing, 10 mm (1 piece)
LKD 9A46 0089 0000
LKD 9A46 0088 0000
www.leoni-infrastructure-datacom.com
● Oyster white RAL 1013
90
VarioKeystone® Accessories
VarioKeystone® Dust protective cap
VarioKeystone® Dummy cover
Description ■■ ■■
VarioKeystone® Dust protective plug
Description
Description
For modules/link extenders or
■■
For wall outlets
■■
For 4K7 module
For cable plugs
■■
White or black
■■
White or black
Designation
Version
For modules/ VarioKeystone® link extenders Dust protective (50 pieces) cap For cable plugs (1 piece)
Order no.
Designation
Order no.
Designation
Order no.
LKD 9A46 0119 0000
VarioKeystone® dummy cover Pure white RAL 9010 (50 pieces)
LKD 9A46 0034 0000
VarioKeystone® Dust protective plug Pure white RAL 9010 (50 pieces)
LKD 9A46 0073 0000
VarioKeystone® dummy cover Jet black RAL 9005 (50 pieces)
LKD 9A46 0083 0000
VarioKeystone® Dust protective plug Jet black RAL 9005 (50 pieces)
LKD 9A46 0084 0000
LKD 9A46 0036 0000
VarioKeystone® Measuring cable set Tera – Tera Description
VarioKeystone® Measuring cable set RJ45 – RJ45 Description
VarioKeystone® Measuring cable set Tera – Crossconnect Description
■■
Tera – Tera
■■
RJ45
■■
Tera – Crossconnect
■■
Length 2 x 3 m
■■
Length 2 x 3 m
■■
Length 2 x 3 m
Designation
Order no.
Designation
Order no.
Designation
Order no.
VarioKeystone® Measuring cable set Tera – Tera (2 pieces)
LKD 9A04 0166 0000
VarioKeystone® Measuring cable set RJ45 – RJ45 (2 pieces)
LKD 9AW3 0020 0000
VarioKeystone® Measuring cable set LKD 9AW3 Tera – Tera (1 piece) 0023 0000 Tera – Crossconnect (1 piece)
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 91
VarioKeystone® Cu connectivity
Cable assembly tools
VarioKeystone® UTP/FTP/foil stripping tool
VarioKeystone® Parallel pliers
Designation VarioKeystone® Parallel pliers (1 piece)
Order no.
Designation
Designation
Order no.
LKD 9AW1 6007 0000
VarioKeystone® UTP/FTP/foil stripping tool LKD 9AW1 6008 0000 (1 piece)
MegaLine® Stripper (1 piece)
LKD 9AW1 6043 0000
VarioKeystone® Copper tape
VarioKeystone® Assembly set 1/2
VarioKeystone® Release tool Description ■■
Order no.
MegaLine® Stripper
Description
Release tool, 2-part
■■
Description (100 of each)
Length 33 m
■■
Set 1: Shrink-fit tube, silver wire, copper foil
■■
Designation VarioKeystone® Release tool (1 piece)
Order no.
Designation
LKD 9AW1 6039 0000
VarioKeystone® Copper tape (length 33 m)
www.leoni-infrastructure-datacom.com
Set 2: Shrink-fit tube, silver wire
Order no.
Designation
Order no.
LKD 9AW1 6011 0000
VarioKeystone® Assembly set 1
LKD 9AW1 6020 0000
VarioKeystone® Assembly set 2
LKD 9AW1 6023 0000
92
MegaLine® Connect45 Cu connectivity
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter
MegaLine® Connect45 Cu connectivity
92
MegaLine® Connect45
Connectivity can be so easy
94
MegaLine® Connect45
LEO (Light Emitting Outlet) the "pathfinder feature"
95
MegaLine® Connect45
System overview
96
o dc
MegaLine® Connect45 cable plugs
• For AWG 24–22 • For AWG 27–26
98
o dc
MegaLine® Connect45 jack modules in VarioKeystone® format
• Cat. 6A ISO/IEC • Cat. 6A EIA/TIA • LEO Cat. 6A ISO/IEC • LEO Cat. 6A EIA/TIA
99
o dc
MegaLine® Connect45 jack modules in keystone format
• Cat. 6A ISO/IEC • Cat. 6A EIA/TIA • LEO Cat. 6A ISO/IEC • LEO Cat. 6A EIA/TIA
100
o dc
MegaLine® Connect45 patch panel 19"/1 RU
• HD 48 Cat. 6A • Unequipped
101
o dc
MegaLine® Connect45 wall outlets
• Keystone 50 x 50 • Keystone 45 x 45
102
o dc
Accessories & tools (MegaLine® Connect45)
• LEO detector • Dust protective cap • Mounting tool • Entriegelungswerkzeug
103
o
Office
dc i
DataCenter Industry
www.leoni-infrastructure-datacom.com
MegaLine® Connect45
93
94
MegaLine® Connect45 Connectivity can be so easy
The shortest possible installation times and an uncompromising
Pre‑assembled trunks help to keep the necessary assembly
approach to electrical performance are the key features
times to a minimum.
of a future-proof cabling system. With this in mind, LEONI has developed a new copper connection
The release tool is a handy solution for opening modules.
system, MegaLine® Connect45. The innovative modular system
In this way, the existing cabling system can be fitted with
unites ultimate performance with maximum ease of assembly.
a new module – e.g. with LEO function – in next to no time
The basic version, consisting of a Category 7/7A data cable and
"with a click".
cable connector is completed by simply attaching the required jack module. You can choose from RJ45 jack modules in Category
Minimum assembly times – maximum performance.
6A (IEC 60603-7-51) and Category 6A (EIA/TIA 568-C.2).
The distances to be covered with cables in DataCenters are often less than 15 metres. The standards refer to these connections
Easy assembly – the wires are pressed together and precision-
as "short links" and, because not all products are of the same
cut in a single step.
quality, it is necessary to separate the wheat from the chaff when
The shortest possible assembly times are achieved by combining
assessing them. The MegaLine® Connect45 system can be used
the attachment of the cable plug with the cutting of the wires
to implement extremely short link lengths from one metre
to size. Easy assembly is particularly useful in DataCenters where
upwards. The requirements of the EA permanent link class are
installation work must be carried out with zero downtime.
easily exceeded.
Easy assembly – the wires are pressed together and cut to size in a single step.
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 95
LEO (Light Emitting Outlet)
MegaLine® Connect45
The "pathfinder feature"
Jack modules are equipped with the LEO function on an optional basis (LEO = Light Emitting Outlet).
A signal transmitter connected to one side of an installed link can be used as a convenient way to identify the corresponding opposite connection by means of a red LED indicator in the jack module. This feature is particularly useful in environments with a high packing density, enabling the corresponding modules to be located quickly and reliably.
The LEO detector (on the right in the photo) is used to feed the light signal into the link so that the red LED on the corresponding jack module on the other side lights up.
www.leoni-infrastructure-datacom.com
96
MegaLine® Connect45 System overview
All components are coordinated for optimum performance: ■■
Quick & easy installation
■■
Maximum performance
■■
Assured functionality for the entire service life
Pre-assembled cable
MegaLine® G12-150 S/F MegaLine® F10-130 S/F MegaLine® F10-115 S/F MegaLine® F6-90 S/F MegaLine® E5-70 F/F MegaLine® E5-60 U/F
MegaLine® Connect45 Cable plug AWG 27–26
MegaLine® Connect45 Cable plug AWG 24–22
Cables & cable plugs www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter
MegaLine® Connect45
97
VarioLine® UF underfloor systems
Floorbox solutions Jack modules with LEO function Keystone/VarioKeystone® format Cat. 6A (ISO/IEC)/Cat. 6A (EIA/TIA)
Wall outlets for MegaLine® Connect45 jack modules
Wall outlets
Jack modules Keystone/VarioKeystone® format Cat. 6A (ISO/IEC)/Cat. 6A (EIA/TIA)
VarioLine® CP6-B consolidation point housing
Housings
Jack modules
MegaLine® Connect45 panel high-density Cat. 6A 48 ports
High-density panels www.leoni-infrastructure-datacom.com
Patch panel 19"
MegaLine® Connect45 panel high-density Cat. 6A 48 ports
98
MegaLine® Connect45 cable plugs AWG 24–22/AWG 27–26
Fig. 1 Cable plug AWG 24–22
Fig. 2 Cable plug AWG 27–26
MegaLine® Connect45 cable plug AWG 24–22 MegaLine® Connect45 cable plug AWG 27–26 Description
Accessories
The MegaLine® Connect45 cable plug has a cutting-clamping
MegaLine® Connect45 dust protective cap
connector and is pressed directly onto the installation cable.
Once attached, the cable plug can be protected from environmental
It is the interface to the individually interchangeable MegaLine®
influences by means of the dust protective cap.
see page 103
Connect45 jack module. This means that generic transmission links far exceeding the requirements for Class EA can be achieved, depending on the relevant jack module. The jack module can also be changed later without any additional installation effort. ■■
Easy and quick assembly
Construction Material
Plastic
Wiring
4 pairs via IDC contacts acc. to EIA/TIA 568A/B
Wire type
AWG 24–22 solid and flex or AWG 27–26 solid and flex
Fig.
Article
Wire type
Colour
Order no.
1
MegaLine® Connect45 cable plug AWG 24–22 (25 pieces)
AWG 24–22 solid and flex
● Yellow plastic
LKD 9A50 4010 0000
2
MegaLine® Connect45 cable plug AWG 27–26 (25 pieces)
AWG 27–26 solid and flex
● Transparent plastic
LKD 9A50 4011 0000
www.leoni-infrastructure-datacom.com
Office
DataCenter
Industry
99
MegaLine® Connect45 jack modules in VarioKeystone® format
Jack module Cat. 6A with LEO function opal white Fig. 2 Jack module Cat. 6A white
Fig. 1 Jack module Cat. 6A aqua
MegaLine® Connect45 BM ISO/IEC MegaLine® Connect45 BM EIA/TIA
MegaLine® Connect45 LEO BM ISO/IEC MegaLine® Connect45 LEO BM EIA/TIA
Description
Description
For transmitting analogue and digital voice, image and data
For transmitting analogue and digital voice, image and data
signals. The performance corresponds to Cat. 6A (ISO/IEC) or Cat.
signals. The performance corresponds to Cat. 6A (ISO/IEC) or Cat.
6A (EIA/TIA) up to 500 MHz. The requirements of the Class EA
6A (EIA/TIA) up to 500 MHz. The requirements of the Class EA
channel and permanent link according to ISO/IEC 11801 Amd.
channel and permanent link according to ISO/IEC 11801 Amd.
1/2 are met above 1 m (Cat. 6A) or 10 m (Cat. 6A) respectively.
1/2 are met above 1 m (Cat. 6A) or 10 m (Cat. 6A) respectively.
The lengths relate to the 2-connector model.
The lengths relate to the 2-connector model.
Construction
Construction
Material
Full metal; die-cast zinc, nickel-plated
Material
Full metal; die-cast zinc, nickel-plated
Wiring
4 pairs via cable plug
Wiring
4 pairs via cable plug
Connection
RJ45 jack, with integrated dust flap
Connection
RJ45 jack, with integrated dust protective
compatible with VarioKeystone® Standards
flap compatible with VarioKeystone® Standards
■■
ISO/IEC 11801
■■
EN 50173-1
■■
IEC 60603-7-51/EIA/TIA 568-C.2
■■
ISO/IEC 11801 n EN 50173-1 n IEC 60603-7-51/EIA/TIA 568-C.2 LEO function
LEO =
Patch panels with LEO function
Light Emitting Outlet permit easy link identification during installation Light detection
≤ 200 m
Signal feed
Via the LEO detector Description see page 95
Fig.
Article
1
MegaLine® Connect45 BM ISO/IEC
2
MegaLine® Connect45 BM EIA/TIA
www.leoni-infrastructure-datacom.com
Colour
Order no.
Article
Colour
Order no.
aqua
LKD 9A50 2010 0000
MegaLine® Connect45 LEO BM ISO/IEC
aqua opal
LKD 9A50 2011 0000
white
LKD 9A50 2020 0000
MegaLine® Connect45 LEO BM EIA/TIA
white opal
LKD 9A50 2021 0000
MegaLine® Connect45
Category 6A/6A
100
MegaLine® Connect45 jack modules in keystone format Category 6A/6A
Jack module Cat. 6A with LEO function opal white Fig. 2 Jack module Cat. 6A white
Fig. 1 Jack module Cat. 6A aqua
MegaLine® Connect45 BM Keystone ISO/IEC MegaLine® Connect45 BM Keystone EIA/TIA
MegaLine® Connect45 LEO BM Keystone ISO/IEC MegaLine® Connect45 LEO BM Keystone EIA/TIA
Description
Description
For transmitting analogue and digital voice, image and data
For transmitting analogue and digital voice, image and data
signals. The performance corresponds to Cat. 6A (ISO/IEC) or Cat.
signals. The performance corresponds to Cat. 6A (ISO/IEC) or Cat.
6A (EIA/TIA) up to 500 MHz. The requirements of the Class EA
6A (EIA/TIA) up to 500 MHz. The requirements of the Class EA
channel and permanent link according to ISO/IEC 11801 Amd.
channel and permanent link according to ISO/IEC 11801 Amd.
1/2 are met above 1 m (Cat. 6A) or 10 m (Cat. 6A) respectively.
1/2 are met above 1 m (Cat. 6A) or 10 m (Cat. 6A) respectively.
The lengths relate to the 2-connector model.
The lengths relate to the 2-connector model.
Construction
Construction
Material
Full metal; die-cast zinc, nickel-plated
Material
Full metal; die-cast zinc, nickel-plated
Wiring
4 pairs via cable plug
Wiring
4 pairs via cable plug
Connection
Keystone RJ45 jack, with integrated
Connection
Keystone RJ45 jack, with integrated
dust protective flap
dust protective flap
Standards
Standards
■■
ISO/IEC 11801
■■
EN 50173-1
■■
IEC 60603-7-51/EIA/TIA 568-C.2
■■
ISO/IEC 11801 n EN 50173-1 n IEC 60603-7-51/EIA/TIA 568-C.2 LEO function
LEO =
Patch panels with LEO function
Light Emitting Outlet permit easy link identification during installation Light detection
≤ 200 m
Signal feed
Via the LEO detector Description see page 95
Fig.
Article
1
MegaLine® Connect45 BM Keystone ISO/IEC
2
MegaLine® Connect45 BM Keystone EIA/TIA
Colour
Order no.
Article
Colour
Order no.
aqua
LKD 9A50 1010 0000
MegaLine® Connect45 LEO BM Keystone ISO/IEC
aqua opal
LKD 9A50 1011 0000
white
LKD 9A50 1020 0000
MegaLine® Connect45 LEO BM Keystone EIA/TIA
white opal
LKD 9A50 1021 0000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 101
MegaLine® Connect45 patch panels 19"/1 RU
MegaLine® Connect45
Equipped/unequipped
MegaLine® Connect45 patch panel HD 48 Cat. 6A
MegaLine® Connect45 patch panel 19"
Description
Description
For transmitting analogue and digital voice, image and data
The patch panel can be equipped with up to 24 jack modules
signals. The performance corresponds to Cat. 6A (ISO/IEC)
in keystone format.
up to 500 MHz. The requirements of the Class EA channel and permanent link according to ISO/IEC 11801 Amd. 1/2 are met
Construction
above 1 m (Cat. 6A). The lengths relate to the 2-connector model.
Housing
Full metal
Colour
Light grey RAL 7035/Black RAL 9005
Capacity
Up to 24 jack modules
Strain relief
Via cable ties
Earthing
Via screw on the rear of the panel
■■
High packing density at a single level
■■
Pre-assembled jack modules reduce the installation effort significantly
Over the entire width of the cable
Construction
Cable entry
management rail
Housing
Full metal
Colour
Light grey RAL 7035/Black RAL 9005
Dimensions
Capacity
48 jack modules Cat. 6A (ISO/IEC)
19"/1 RU, 110 mm installation depth
Strain relief
Via cable ties
Earthing
Via screw on the rear of the panel Over the entire width of the cable
Cable entry
management rail
Note Patch panels for jack modules in VarioKeystone® format can be found on page 84
Dimensions 19"/1 RU, 121 mm installation depth Standards ■■
ISO/IEC 11801 n EN 50173-1 n IEC 60603-7-51
Article
Colour
Order no.
MegaLine® Connect45 patch panel HD 48 Cat. 6A (ISO/IEC)
● Light grey RAL 7035
LKD 9A50 3214 0000
● Jet black RAL 9005
LKD 9A50 3215 0000
www.leoni-infrastructure-datacom.com
Article
Colour
Order no.
MegaLine® Connect45 patch panel 19"
● Light grey RAL 7035
LKD 9A50 1200 0000
● Jet black RAL 9005
LKD 9A50 1201 0000
102
MegaLine® Connect45 wall outlets for keystone jack modules
Fig. 3 Wall outlet 50 x 50/triple gang
Fig. 1 Wall outlet 50 x 50/single gang
Fig. 4 Wall outlet 45 x 45/single gang
Fig. 2 Wall outlet 50 x 50/ double gang
MegaLine® Connect45 wall outlet keystone 50 x 50
Fig. 5 Wall outlet 45 x 45/double gang
MegaLine® Connect45 wall outlet keystone 45 x 45
French style
German style Wall outlets for equipping with MegaLine® Connect45 jack
Wall outlets for equipping with MegaLine® Connect45 jack
modules in keystone format.
modules in keystone format.
Construction
Construction
Housing body
Full metal; die-cast zinc, nickel-plated
Housing body
Plastic
Colours
Pure white RAL 9010
Colours
Pure white RAL 9010
Labelling
Via labelling field
Labelling
Via labelling field
Dimensions
Dimensions
50 mm x 50 mm x 30 mm (H x W x D),
45 mm x 45 mm x 42 mm (H x W x D),
downward inclination of 30°
downward inclination of 30°
Note Wall outlets in VarioKeystone® format can be found on page 89
Fig. 1 2 3
– –
Designation
Order no.
Fig.
Designation
Order no.
MegaLine® Connect45 wall outlet keystone 50 x 50/single gang
LKD 9A50 1100 0000
4
MegaLine® Connect45 wall outlet keystone 45 x 45/single gang
LKD 9A50 1104 0000
MegaLine® Connect45 wall outlet keystone 50 x 50/double gang
LKD 9A50 1101 0000
5
MegaLine® Connect45 wall outlet keystone 45 x 45/double gang
LKD 9A50 1103 0000
MegaLine® Connect45 wall outlet keystone 50 x 50/triple gang
LKD 9A50 1102 0000 –
VarioLine® cover frame 45 x 45 (8 pieces)
LKD 9ZE8 0013 0000
40 mm surface-mounted housing
LKD 9A46 0086 0000
Spacer frame for single-gang surface-mounted housing, 10 mm
LKD 9A46 0088 0000
www.leoni-infrastructure-datacom.com
Office
DataCenter
Industry
103
Accessories & tools
The cable assembled with the Connect45 cable plug is simply inserted into the dust protective cap and locked
MegaLine® Connect45 LEO detector
MegaLine® Connect45 dust protective cap
Accessories
Accessories
Detector for feeding in the voltage when using a Connect45 jack
For the safe and convenient protection of pre-assembled trunk
module with LEO function.
cables equipped with MegaLine® Connect45 cable plugs.
Housing
Full metal
Contact
RJ45 plug
Power supply
4 x LR41 batteries (included)
Article
Order no.
Article
Order no.
MegaLine® Connect45 LEO detector
LKD 9A50 4002 0000
MegaLine® Connect45 dust protective cap (25 pieces)
LKD 9A50 4003 0000
MegaLine® Connect45 mounting tool
MegaLine® Connect45 release tool
Accessories
Accessories
It takes just a single step to press the contacts of the cable plug
For quick and easy opening of the MegaLine® Connect45 jack
together and remove the excess wires.
module.
Article
Order no.
Article
Order no.
MegaLine® Connect45 mounting tool
LKD 9A50 4001 0000
MegaLine® Connect45 release tool
LKD 9A50 4000 0000
www.leoni-infrastructure-datacom.com
MegaLine® Connect45
for MegaLine® Connect45
104 104
ELine 1200® EC7 Cu connectivity
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter
ELine 1200® EC7 Cu connectivity
104
ELine 1200® EC7
Cu connectivity The passive cabling system for multimedia applications
106
ELine 1200® EC7
System overview
108
o dc
EC7 jack and accessories
• EC7 jack • EC7 dust protective plug 1 p • EC7 mounting tool
o dc
Wall outlet insert
50 x 50
111
o dc
EC7 patch panel
Telephone patch panel
112
o dc
EC7 accessories
Telephone termination plug
112
o dc
EC7 patch panel 19"
• 1 RU with 24 ports • 1 RU with 48 ports • 1 RU with 24 ports, angled
113
o dc
EC7 mini patch panel
With 6 ports
114
o dc
EC7 mounting tool
For ELine 1200® EC7 jacks
114
o dc
EC7 measuring equipment
• EC7 measuring adapter (for Fluke DTX 1800) • EC7-EC7 plug
115
o
Office
dc i
DataCenter Industry
www.leoni-infrastructure-datacom.com
110
ELine 1200® EC7 Cu connectivity
105
106
ELine 1200® EC7 Cu connectivity The passive cabling system for multimedia applications
Multimedia in a systematic way
Connection options
Multimedia up to 1.5 GHz via twisted pair The chamber system of the ELine 1200® EC7 connector is based on the principle of paired shielding of the 100 Ω data cables used in the MegaLine® series. The cable and connector form a perfect combination of four pairs and four chambers with GHz performance. The signal paths are separate throughout, which opens up a wide range of possible uses: A passive cabling system for multimedia applications – is that even possible? After all, it is a term that is more
■■
often used in connection with consumer electronics.
Cable sharing: Simultaneous use of two data services from Class A to F with just one cable and one EC7 jack
ELine 1200® EC7 supports multimedia by allowing different media to be used in parallel via a structured cabling system:
■■
Service sharing: Simultaneous operation of different services (e.g. telephone/ data) in parallel - without the risk of NEXT problems
Data/voice/images/TV signals – in one connection. This unique copper connectivity from LEONI delivers
The devices are connected using appropriately matched ELine
a sophisticated system solution, the only one of its kind, geared
1200® EC7 connection cable in one, two or four pairs.
towards the needs of the market. ELine 1200® EC7 delivers multimedia directly to the desktop as a four-lane data highway.
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter
2 data services from Class A to F
Mixed telephone and data services
Cable sharing
Service sharing Telephone/fax
PC
PC
PC
Telephone
TV via twisted pair
"High tech" and "added value" have their price
Transmitting analogue and digital CATV services via twisted
The ELine 1200® EC7 system is no more expensive than
pair is extremely challenging from a technical point of view.
conventional systems overall, because separate cables
Transmission frequencies of up to 862 MHz are required
or connectors are not needed for each service. This allows
for transmitting all channels, which requires a system with
savings of up to 50 % of the necessary cables, connectors,
extremely high performance reserves and, in particular, good
wall outlets and patch panels.
attenuation characteristics. Multiple use also reduces the system costs (depending on the ELine 1200® EC7 is specifically optimised for this application
services used) by 15 – 30 %. The reduction in the number
and the extensive product range provides all the tools needed
of cables and wall outlets actually required usually also allows
to transmit CATV signals. The twisted pair infrastructure
reductions in the costs for cable ducts or switching cabinets.
(100 Ω) is connected to the TV infrastructure (75 Ω) via passive connection cables with integrated balun.
"Service sharing" with ELine 1200® EC7 means saving costs.
In contrast to previous solutions, the outlets are completely flexible.
The system solution is already successfully in use worldwide,
For example, a telephone or data outlet can become a TV
which means that we can refer to a wide installed base with
connection at any time.
testimonials from well-known customers.
www.leoni-infrastructure-datacom.com
ELine 1200® EC7 Cu connectivity
107
108
ELine 1200® EC7 Cu connectivity System overview
ELine 1200® EC7 jack ■■
VarioLine® modular system peripherals
Modular jack for multimedia applications
Consolidation points – CP Underfloor range – UF
ELine 1200® EC7 wall outlets ■■
Double-gang wall outlet for up to two modular jacks
MegaLine® Patch
■■
Triple-gang wall outlet for up to three modular jacks
■■
Patch cord
■■
Trunk cable
ELine 1200® EC7 panels ■■
Panel with 24 ports (standard version)
■■
48-port panel with double packing density at a single level
Pre-assembled cable
MegaLine® G12-150 S/F
ELine 1200® EC7
Cable
Jack module www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter
ELine 1200® EC7 Cu connectivity
109
ELine 1200® EC7 patch panel 1 RU/48 ports can be equipped with ELine 1200® EC7 jacks
ELine 1200® EC7 patch panel 1 RU/24 ports can be equipped with ELine 1200® EC7 jacks
VarioLine® housing CP6/CP12/CP24 Consolidation point housing for 6, 12 or 24-port module panel
Housings
VarioLine® UF underfloor systems
Floorbox solutions
ELine 1200® EC7 Cu wall outlet insert 50 x 50 double gang/triple gang
Wall outlets www.leoni-infrastructure-datacom.com
110
ELine 1200® EC7 jack and accessories Multimedia up to 1.5 GHz via twisted pair
ELine 1200® EC7 jack Application
Compatibility
For fast installation in patch panels, floorbox solutions and wall
VarioLine® CP
Consolidation point range (from page 237)
outlet inserts.
VarioLine® UF
Underfloor systems/floorbox solutions (from page 253)
Construction Jack
Die-cast zinc, nickel-plated
Accessories
Contacts
Gold-plated
ELine 1200® EC7 dust protective plug 1 p ELine 1200® EC7 mounting tool (description see page 140)
Insulation displace- Bronze, tinned ment contacts Dimensions Jack
14 mm x 16 mm x 36.9 mm (W x H x D)
Installation depth 40 mm
ELine 1200® EC7 dust protective plug 1 p
Article
Order no.
ELine 1200® EC7 jack (8 pieces)
LKD 9ZE4 4444 0000
ELine 1200® EC7 dust protective plug 1 p (1 piece)
LKD 9ZE3 0066 0000
ELine 1200® EC7 mounting tool (1 piece)
LKD 9ZE3 0007 0000
ELine 1200® EC7 mounting tool
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 111
ELine 1200® Wall outlet insert
Fig. 1 Cu wall outlet insert 50 x 50/ double gang, can be equipped with 2 ELine 1200® EC7 jacks
Fig. 2 Cu wall outlet insert 50 x 50/ triple gang, can be equipped with 3 ELine 1200® EC7 jacks
ELine 1200® EC7 Cu wall outlet insert 50 x 50 Description
Accessories (optional)
Unequipped wall outlet insert with dust protective cover, for
VarioKeystone® cover frame
installation in commercially available 50 x 50 mm cover frames.
Order no.: LKD 9A41 0003 0000
Housing
■■
Plastic cover frame 80 x 80 mm Cut-out 50 x 50 mm, square
Housing body
Plastic
■■
Colour
Pure white RAL 9010
■■
Colour: Pure white RAL 9010
Earth connection
Via M4 thread
■■
PU: 1 piece
Dimensions 50 mm x 50 mm x 30.5 mm (H x W x D empty) Downward inclination 62° Installation depth 25 mm
Matching jacks
Fig.
ELine 1200® EC7
Article
Order no.
1
ELine 1200® EC7 Cu wall outlet insert/double gang LKD 9ZE3 0010 0000 (8 pieces)
2
ELine 1200® EC7 Cu wall outlet insert/triple gang (8 pieces)
www.leoni-infrastructure-datacom.com
LKD 9ZE3 0041 0000
ELine 1200® EC7 Cu connectivity
for surface or flush mounting, duct and many underfloor systems
112
ELine 1200® EC7 patch panel
ELine 1200® EC7 accessories
Telephone
Telephone
ELine 1200® EC7 telephone patch panel
ELine 1200® EC7 termination plug
Application
Application
Telephone patch panel for operating up to 100 telephone
As a connectable termination in ISDN So bus-networks ELine
services at a single level (100 DA).
1200® EC7.
Connections
Construction
■■
Complete with 25 x (1 x 4) double-core jacks
■■
EC7 resistor/termination plug
■■
25 x 8 LSA connectivity on the rear
■■
2p
■■
IDC terminal connections on 5 x 5 basic modules
■■
With 2 x 100 Ω terminating resistors
Dimensions Panel
485 mm x 44 mm x 106 mm (W x H x D)
Installation depth
104 mm
Article
Order no.
Article
Order no.
ELine 1200® EC7 telephone patch panel (1 piece)
LKD 9ZE1 0221 0000
ELine 1200® EC7 termination plug (1 piece)
LKD 9ZE1 0104 0000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 113
ELine 1200® EC7 patch panel 19"
Fig. 1 patch panel with 48 ports, can be equipped with ELine 1200® EC7 jacks
Fig. 2 patch panel with 24 ports, can be equipped with ELine 1200® EC7 jacks
ELine 1200® EC7 patch panel 1 RU/24 ports ELine 1200® EC7 patch panel 1 RU/24 ports, angled
ELine 1200® EC7 patch panel 1 RU/48 ports
Description
Description
Patch panel 19", unequipped, for holding up to 24 or 48 ELine
Patch panel 19" , unequipped, for holding up to 24 ELine 1200®
1200® EC7 jacks (including a mixture).
EC7 jacks (including a mixture).
■■
Snap-in assembly
■■
Snap-in assembly
■■
Strain relief
■■
Strain relief
■■
Earth connection
■■
Earth connection
Housing Housing
Housing Steel panel
Colour of front panel Light grey RAL 7035 or Jet black RAL 9005
Housing
Steel panel
Labelling
1 – 24 (screen printing)
Colour of front panel Jet black RAL 9005 Dimensions 19"/1 RU
44 mm x 483 mm x 98 mm (H x W x D)
Dimensions 19"/1 RU
Fig.
44 mm x 483 mm x 175 mm (H x W x D)
Article
Colour
Order no.
Article
Colour
Order no.
1
ELine 1200® EC7 patch panel 1 RU/48 ports (1 piece)
Light grey RAL 7035
LKD 9ZE3 0052 0000
Jet black RAL 9005
LKD 9ZE3 0047 0000
ELine 1200® EC7 patch panel 1 RU/24 ports, angled (1 piece)
Jet black RAL 9005
LKD 9ZE3 0061 0000
2
ELine 1200® EC7 patch panel 1 RU/24 ports (1 piece)
Light grey RAL 7035
LKD 9ZE3 0002 0000
Jet black RAL 9005
LKD 9ZE3 0046 0000
www.leoni-infrastructure-datacom.com
ELine 1200® EC7 Cu connectivity
1 RU, with 24/48 ports
114
ELine 1200® EC7 mini patch panel
ELine 1200® EC7 mounting tool
with 6 ports
for ELine 1200® EC7 jacks
ELine 1200® EC7 mini patch panel with 6 ports
ELine 1200® EC7 mounting tool
Description
Description
Mini patch panel, unequipped, for holding up to 6 ELine 1200®
For easy and secure connection of the ELine 1200® EC7 jacks.
EC7 jacks. ■■
Snap-in assembly
■■
For mounting in a wall, floor, ceiling, furniture, DIN rails
■■
Suitable for industrial environments
Housing Housing
Closed, steel panel
Colour
Pure white RAL 9010
Dimensions 35 mm x 122 mm x 100 mm (H x W x D)
Article
Colour
Order no.
Article
Order no.
ELine 1200® EC7 mini patch panel with 6 ports (1 piece)
Pure white RAL 9010
LKD 9ZE3 0045 0000
ELine 1200® EC7 mounting tool (1 piece)
LKD 9ZE3 0007 0000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 115
ELine 1200® EC7 measuring adapter (for Fluke DTX 1800)
ELine 1200® EC7 Cu connectivity
ELine 1200® EC7 measuring equipment
ELine 1200® EC7-EC7 plug
Application
Application
Measuring adapter for testing EC7 cabling systems up to Class F
Replaceable measuring probe for Class F measurements EC7 for
(600 MHz), permanent link and channel.
permanent link and channel measuring adapter Fluke DTX 1800.
The measuring probe consists of an EC7-EC7 plug that can
Construction
be replaced in case of wear.
Mating face
Both sides EC7, 4 pairs
Article
Order no.
Article
Order no.
ELine 1200® EC7 measuring adapter (for Fluke DTX 1800) (1 pair)
LKD 9ZE3 0038 0000
ELine 1200® EC7-EC7 plug (1 piece)
LKD 9ZE3 0043 0000
www.leoni-infrastructure-datacom.com
116 116
MegaLine Cu patch cords / trunk cables ®
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter
MegaLine® Cu patch cords / trunk cables
117
o dc
Patch cord RJ45/RJ45
Cat. 5/100 MHz
118
o dc
Patch cord RJ45/RJ45
Cat. 6/250 MHz
119
o dc
Patch cord RJ45/RJ45
Cat. 6/500 MHz
120
o dc
Patch cord RJ45/RJ45
Cat. 6A/500 MHz
121
i
LED patch cord RJ45/RJ45
Cat. 6/500 MHz with LED signal in the plug
122
i
Industrial patch cord RJ45/RJ45
Cat. 5/100 MHz
123
i
Industrial patch cord with Han® 3A plugs
• Han 3A RJ45/RJ45 • Han 3A RJ45/IP20 RJ45
124
i
Industrial patch cord RJ45/RJ45
Cat. 6/500 MHz
125
o dc
Patch cord TERA
126
TM
o dc
Patch cord and connection cable EC7
• 4 p EC7/EC7 • 4 p EC7/RJ45 • 4 p EC7/open
o dc
Patch cord and connection cable EC7
• 2 p EC7/EC7 • 2 p EC7/open • 2 p EC7/RJ45 • 2 p EC7/RJ45 Cross over
129
o dc
Patch cord and connection cable EC7
• 1 p EC7/EC7 • 1 p EC7/open • 1 p EC7/RJ10 • 1 p EC7/RJ11
130
o dc
Patch cord and connection cable EC7
• 1 p EC7/RJ45 • 2 p EC7/RJ45
131
i
VarioKeystone® trunk cable, industrial
• Trunk cable • Crossconnect trunk cable
132
o dc
VarioKeystone® trunk cable
• Trunk cable • Crossconnect trunk cable
133
o dc i
RJ45 trunk cable, 8 port
• Trunk RJ45 plug/RJ45 plug
134
o dc i
VarioKeystone® trunk cable, 4 port/8 port
o dc
MegaLine® Connect45 trunk cable
• Cat. 6A modules • Cat. 6A modules
136
o dc
MegaLine® Connect45 trunk cable, 8 port
• Cat. 6A modules
137
o dc
MegaLine® Connect45 CP cable
• Cat. 6A/Cat. 6A
138
o dc
MegaLine® Connect45 CP cable
• Cat. 7, Class F
139
o dc
Accessories for LED patch cords
• LED colour clip • LED detector
140
o dc
Accessories for patch cords
• RJ45 colour coding clip
140
o dc
Test report
For all trunk cables
141
o
Office cable
dc i
DataCenter cables Industrial cables
www.leoni-infrastructure-datacom.com
128
135
MegaLine® Cu patch cords / trunk cables
117
118
MegaLine® Patch cord RJ45/RJ45 Cat. 5/100 MHz Shielded, Cat. 5, Class D, with coloured moulded boots
MegaLine® Patch 5D-RJ45
Description
Construction
The cable type used is suitable for transmission rates
EMC
Foil overall shielding
of up to 100 MHz. The pair shielding and the high-coverage
RJ45 plug
EN 60603-7
copper braiding as overall shielding ensure excellent NEXT
Electrical values
Cat. 5, Class D
and impedance values.
Assignment
1:1
Standards
ISO/IEC 11801/EN 50173
The patch cords and connection cables are equipped with a shielded RJ45 plug and moulded boots at both ends.
Fire behaviour Flame retardance
IEC 60332-1-2
Applications IEEE 802.3, 10Base-T, 100Base-T, 1000Base-T, IEEE 802.5 16MB,
Accessories
ISDN, FDDI, ATM
MegaLine® Patch RJ45 colour coding clip
Description see page 140
In different colours for visual coding of the patch cords
Length
Article
Order no. Grey (PVC)
Blue (PVC)
Green (PVC)
Yellow (PVC)
Red (PVC)
0.5
LKD 9A01 0400 0000
LKD 9A01 0410 0000
LKD 9A01 0420 0000
LKD 9A01 0430 0000
LKD 9A01 0440 0000
1.0
LKD 9A01 0401 0000
LKD 9A01 0411 0000
LKD 9A01 0421 0000
LKD 9A01 0431 0000
LKD 9A01 0441 0000
1.5
LKD 9A01 0402 0000
LKD 9A01 0412 0000
LKD 9A01 0422 0000
LKD 9A01 0432 0000
LKD 9A01 0442 0000
2.0
LKD 9A01 0403 0000
LKD 9A01 0413 0000
LKD 9A01 0423 0000
LKD 9A01 0433 0000
LKD 9A01 0443 0000
m
2.5 3.0
MegaLine® Patch 5D-RJ45
LKD 9A01 0404 0000
LKD 9A01 0414 0000
LKD 9A01 0424 0000
LKD 9A01 0434 0000
LKD 9A01 0444 0000
LKD 9A01 0405 0000
LKD 9A01 0415 0000
LKD 9A01 0425 0000
LKD 9A01 0435 0000
LKD 9A01 0445 0000
4.0
LKD 9A01 0406 0000
LKD 9A01 0416 0000
LKD 9A01 0426 0000
LKD 9A01 0436 0000
LKD 9A01 0446 0000
5.0
LKD 9A01 0407 0000
LKD 9A01 0417 0000
LKD 9A01 0427 0000
LKD 9A01 0437 0000
LKD 9A01 0447 0000
7.5
LKD 9A01 0408 0000
LKD 9A01 0418 0000
LKD 9A01 0428 0000
LKD 9A01 0438 0000
LKD 9A01 0448 0000
10.0
LKD 9A01 0409 0000
LKD 9A01 0419 0000
LKD 9A01 0429 0000
LKD 9A01 0439 0000
LKD 9A01 0449 0000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 119
MegaLine® Patch cord RJ45/RJ45 Cat. 6/250 MHz
MegaLine® Cu patch cords / trunk cables
Unshielded, Cat. 6, Class E, with grey moulded boots
MegaLine® Patch 6E-RJ45U
Description
Construction
The cable type used is suitable for transmission rates
RJ45 plug
EN 60603-7
of up to 250 MHz. The patch cord offers excellent NEXT
Electrical values
Cat. 6, Class E
and return loss values thanks to its construction.
Assignment
1:1
Standards
ISO/IEC 11801/EN 50173
The patch cords and connection cables are equipped with an unshielded RJ45 plug and moulded boots at both ends.
Fire behaviour Smoke density
IEC 61034
Applications
Halogen free
IEC 60754-2
IEEE 802.3, 10Base-T, 100Base-T, 1000Base-T, IEEE 802.5 16MB,
Flame retardance
IEC 60332-1-2
ISDN, FDDI, ATM Accessories
Description see page 140
MegaLine® Patch RJ45 colour coding clip In different colours for visual coding of the patch cords
Length
Article
Order no. Grey (LSOH)
m 0.5
LKD 9A05 0027 0000
1.0
LKD 9A05 0028 0000
1.5
LKD 9A05 0029 0000
2.0
LKD 9A05 0030 0000
2.5 3.0
MegaLine® Patch RJ45U
LKD 9A05 0031 0000 LKD 9A05 0032 0000
4.0
LKD 9A05 0033 0000
5.0
LKD 9A05 0034 0000
7.5
LKD 9A05 0035 0000
10.0
LKD 9A05 0036 0000
www.leoni-infrastructure-datacom.com
120
MegaLine® Patch cord RJ45/RJ45 Cat. 6/500 MHz Shielded, Cat. 6, Class EA, with coloured moulded boots
MegaLine® Patch 6EA-RJ45
Description
Construction
The cable type used is suitable for transmission rates
EMC
Combined shielding (PiMf + braiding)
of up to 500 MHz. The pair shielding and the high-coverage
RJ45 plug
EN 60603-7
copper braiding as overall shielding ensure excellent NEXT
Electrical values
Cat. 6, Class EA
and return loss values.
Assignment
1:1
Standards
ISO/IEC 11801/EN 50173
The patch cords and connection cables are equipped with a shielded RJ45 plug and moulded boots at both ends.
Fire behaviour Smoke density
Applications
Halogen free
IEEE 802.3, 10Base-T, 100Base-T, 1000Base-T,
Flame retardance
IEC 61034 IEC 60754-2 IEC 60332-1-2
suitable for 10GBase-T, IEEE 802.5 16MB, ISDN, FDDI, ATM Accessories
Description see page 140
MegaLine® Patch RJ45 colour coding clip In different colours for visual coding of the patch cords
Length
Article
Order no. Grey (LSOH)
Blue (LSOH)
Green (LSOH)
Yellow (LSOH)
Red (LSOH)
0.5
LKD 9A02 1132 0000
LKD 9A02 1152 0000
LKD 9A02 1162 0000
LKD 9A02 1142 0000
LKD 9A02 1172 0000
1.0
LKD 9A02 1133 0000
LKD 9A02 1153 0000
LKD 9A02 1163 0000
LKD 9A02 1143 0000
LKD 9A02 1173 0000
m
1.5
LKD 9A02 1134 0000
LKD 9A02 1154 0000
LKD 9A02 1164 0000
LKD 9A02 1144 0000
LKD 9A02 1174 0000
2.0
LKD 9A02 1135 0000
LKD 9A02 1155 0000
LKD 9A02 1165 0000
LKD 9A02 1145 0000
LKD 9A02 1175 0000
2.5 3.0
MegaLine® Patch 6EA-RJ45
LKD 9A02 1136 0000
LKD 9A02 1156 0000
LKD 9A02 1166 0000
LKD 9A02 1146 0000
LKD 9A02 1176 0000
LKD 9A02 1137 0000
LKD 9A02 1157 0000
LKD 9A02 1167 0000
LKD 9A02 1147 0000
LKD 9A02 1177 0000
4.0
LKD 9A02 1138 0000
LKD 9A02 1158 0000
LKD 9A02 1168 0000
LKD 9A02 1148 0000
LKD 9A02 1178 0000
5.0
LKD 9A02 1139 0000
LKD 9A02 1159 0000
LKD 9A02 1169 0000
LKD 9A02 1149 0000
LKD 9A02 1179 0000
7.5
LKD 9A02 1140 0000
LKD 9A02 1160 0000
LKD 9A02 1170 0000
LKD 9A02 1150 0000
LKD 9A02 1180 0000
10.0
LKD 9A02 1141 0000
LKD 9A02 1161 0000
LKD 9A02 1171 0000
LKD 9A02 1151 0000
LKD 9A02 1181 0000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 121
MegaLine® Patch cord RJ45/RJ45 Cat. 6A/500 MHz
MegaLine® Cu patch cords / trunk cables
Shielded, Cat. 6A, Class EA, with coloured moulded boots
MegaLine® Patch 6AEA-RJ45
Description
Construction
The cable type used is suitable for transmission rates
EMC
Combined shielding (PiMf + braiding)
of up to 500 MHz. The pair shielding and the high-coverage
RJ45 plug
EN 60603-7
copper braiding as overall shielding ensure excellent NEXT
Electrical values
Cat. 6A, Class EA
and return loss values.
Assignment
1:1
Standards
ISO/IEC 11801/EN 50173
The patch cords and connection cables are equipped with a shielded RJ45 plug and moulded boots at both ends.
Fire behaviour Smoke density
IEC 61034
Applications
Halogen free
IEC 60754-2
IEEE 802.3, 10Base-T, 100Base-T, 1000Base-T,
Flame retardance
IEC 60332-1-2
suitable for 10GBase-T, IEEE 802.5 16MB, ISDN, FDDI, ATM Accessories
Description see page 140
MegaLine® Patch RJ45 colour coding clip In different colours for visual coding of the patch cords
Length
Article
Order no. Grey (LSOH)
Blue (LSOH)
Green (LSOH)
Yellow (LSOH)
Red (LSOH)
0.5
LKD 9A02 3020 0000
LKD 9A02 3030 0000
LKD 9A02 3040 0000
LKD 9A02 3050 0000
LKD 9A02 3060 0000
1.0
LKD 9A02 3021 0000
LKD 9A02 3031 0000
LKD 9A02 3041 0000
LKD 9A02 3051 0000
LKD 9A02 3061 0000
m
1.5
LKD 9A02 3022 0000
LKD 9A02 3032 0000
LKD 9A02 3042 0000
LKD 9A02 3052 0000
LKD 9A02 3062 0000
2.0
LKD 9A02 3023 0000
LKD 9A02 3033 0000
LKD 9A02 3043 0000
LKD 9A02 3053 0000
LKD 9A02 3063 0000
LKD 9A02 3024 0000
LKD 9A02 3034 0000
LKD 9A02 3044 0000
LKD 9A02 3054 0000
LKD 9A02 3064 0000
LKD 9A02 3025 0000
LKD 9A02 3035 0000
LKD 9A02 3045 0000
LKD 9A02 3055 0000
LKD 9A02 3065 0000
2.5 3.0
MegaLine® Patch 6AEA-RJ45
4.0
LKD 9A02 3026 0000
LKD 9A02 3036 0000
LKD 9A02 3046 0000
LKD 9A02 3056 0000
LKD 9A02 3066 0000
5.0
LKD 9A02 3027 0000
LKD 9A02 3037 0000
LKD 9A02 3047 0000
LKD 9A02 3057 0000
LKD 9A02 3067 0000
7.5
LKD 9A02 3028 0000
LKD 9A02 3038 0000
LKD 9A02 3048 0000
LKD 9A02 3058 0000
LKD 9A02 3068 0000
10.0
LKD 9A02 3029 0000
LKD 9A02 3039 0000
LKD 9A02 3049 0000
LKD 9A02 3059 0000
LKD 9A02 3069 0000
www.leoni-infrastructure-datacom.com
122
MegaLine® LED patch cord RJ45/RJ45 Cat. 6/500 MHz Shielded, Cat. 6, Class EA, with LED light signal in the plug
MegaLine® Patch LED 6EA-RJ45
Description
Construction
Specially for use in offices, industrial plants and DataCenters.
Cable type
LEONI Megaline® F6-90 S/FTP
The plug contains one red LED. The light signal is activated using
Outer sheath
Halogen-free, flame-retardant compound
a detector that is placed on a contact pair on the rear of the plug.
Plug
RJ45 shielded, IEC 60603-7, grey
Strain relief
Moulded plug, with separate boot
Three different signal types can be selected by repeatedly pressing the detector button:
Performance
➔ continuous light/slow flashing/fast flashing
Transmission
The other end of the LED patch cord then responds with the
bandwidth
Max. 500 MHz (Class EA)
Electrical values
Cat. 6 acc. to ISO/IEC 11801,
identical light signal and in this way can be clearly identified.
EN 50173-x, IEC 60603-7-5
Applications
Fire behaviour
For use in structured cabling systems according
Smoke density
to ISO/IEC 11801 and EN 50173-x. Ideal for all applications
Halogen free
up to Class EA (video, data, telephony)
Flame retardance
IEC 60754-2
>10 GbE according to IEEE 802.3 an, cable sharing, VoIP, PoE.
Fire load
IEC 60332-1-2
IEC 61034
0.33 MJ/m (approx.)
Length
Article
Order no. Grey (LSOH)
m
Blue (LSOH)
Aqua (LSOH)
Yellow (LSOH)
Red (LSOH)
Red (LSOH) Crossover
0.5
LKD 9A09 0100 0000
LKD 9A09 0110 0000
LKD 9A09 0140 0000
LKD 9A09 0130 0000
LKD 9A09 0120 0000
LKD 9A09 0160 0000
1.0
LKD 9A09 0101 0000
LKD 9A09 0111 0000
LKD 9A09 0141 0000
LKD 9A09 0131 0000
LKD 9A09 0121 0000
LKD 9A09 0161 0000
1.5
LKD 9A09 0102 0000
LKD 9A09 0112 0000
LKD 9A09 0142 0000
LKD 9A09 0132 0000
LKD 9A09 0122 0000
LKD 9A09 0162 0000
2.0
LKD 9A09 0103 0000
LKD 9A09 0113 0000
LKD 9A09 0143 0000
LKD 9A09 0133 0000
LKD 9A09 0123 0000
LKD 9A09 0163 0000
LKD 9A09 0104 0000
LKD 9A09 0114 0000
LKD 9A09 0144 0000
LKD 9A09 0134 0000
LKD 9A09 0124 0000
LKD 9A09 0164 0000
2.5 3.0
MegaLine® Patch LED 6EA-RJ45
4.0
LKD 9A09 0105 0000
LKD 9A09 0115 0000
LKD 9A09 0145 0000
LKD 9A09 0135 0000
LKD 9A09 0125 0000
LKD 9A09 0165 0000
LKD 9A09 0106 0000
LKD 9A09 0116 0000
LKD 9A09 0146 0000
LKD 9A09 0136 0000
LKD 9A09 0126 0000
LKD 9A09 0166 0000
5.0
LKD 9A09 0107 0000
LKD 9A09 0117 0000
LKD 9A09 0147 0000
LKD 9A09 0137 0000
LKD 9A09 0127 0000
LKD 9A09 0167 0000
7.5
LKD 9A09 0108 0000
LKD 9A09 0118 0000
LKD 9A09 0148 0000
LKD 9A09 0138 0000
LKD 9A09 0128 0000
LKD 9A09 0168 0000
10.0
LKD 9A09 0109 0000
LKD 9A09 0119 0000
LKD 9A09 0149 0000
LKD 9A09 0139 0000
LKD 9A09 0129 0000
LKD 9A09 0169 0000
Other lengths on request www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 123
MegaLine® Industrial patch cord RJ45/RJ45 Cat. 5/100 MHz
MegaLine® Cu patch cords / trunk cables
Shielded, Cat. 5, Class D, with yellow moulded boots
MegaLine® Patch Industry 5D-RJ45
Description
Construction
The cable type used is suitable for transmission rates
EMC
Shielding (braiding)
of up to 100 MHz. The pair shielding and the high-coverage
RJ45 plug
EN 60603-7
copper braiding as overall shielding ensure excellent NEXT
Electrical values
Cat. 5, Class D
and return loss values.
Cable/boot
Yellow (PUR superflex)/yellow
The patch cords and connection cables are equipped with
Fire behaviour
a shielded RJ45 plug and moulded boots at both ends.
Smoke density
IEC 61034-1/2
Halogen free
IEC 60754-1/2
Flame retardance
IEC 60332-2-2
The "superflex" design is ideal for challenging industrial applications (e.g. drag chains). Applications IEEE 802.3, 10Base-T, 100Base-T, 1000Base-T, suitable for 10GBase-T, IEEE 802.5 16MB, ISDN, FDDI, ATM
Length
Article
Order no. Yellow (PUR)
m 10.0
LKD 9A07 0084 0000
20.0 30.0
LKD 9A07 0155 0000 MegaLine® Patch Industry 5D-RJ45
LKD 9A07 0082 0000
40.0
LKD 9A07 0179 0000
50.0
LKD 9A07 0085 0000
www.leoni-infrastructure-datacom.com
124
MegaLine® Industrial patch cord with Han® 3A plugs Cat. 6, Class E
MegaLine® Patch Han 3A RJ45/RJ45
MegaLine® Patch Han 3A RJ45/IP20 RJ45
Description
Description
Pre-assembled system cable ready for connection with
Pre-assembled system cable ready for connection with
Han® 3A RJ45 to Han® 3A RJ45.
Han® 3A RJ45 to IP20 RJ45.
■■
Han® 3A interface in metal also offers increased protection
■■
against heat ■■
against heat
Mating compatible with many controllers, devices and
■■
automation systems ■■
Han® 3A interface in metal also offers increased protection Mating compatible with many controllers, devices and automation systems
With extremely robust RJ45, IP65/IP67 cords
Construction
■■
With extremely robust RJ45, IP65/IP67 cords
Construction
Sheath material
PUR, LSZH
Sheath material
PUR, LSZH
Performance
Acc. to Cat. 6 or for Class E (250 MHz)
Performance
Acc. to Cat. 6 or for Class E (250 MHz)
Length
Article
1.5 m 3.0 m 5.0 m 10.0 m
MegaLine® Patch Han 3A RJ45/RJ45
Order no.
Length
LKD 9A07 0110 0000
1.5 m
LKD 9A07 0111 0000
3.0 m
LKD 9A07 0112 0000
5.0 m
LKD 9A07 0113 0000
10.0 m
Article
Order no. LKD 9A07 0088 0000
MegaLine® Patch Han 3A RJ45/IP20 RJ45
LKD 9A07 0089 0000 LKD 9A07 0090 0000 LKD 9A07 0091 0000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 125
MegaLine® Industrial patch cord RJ45/RJ45 Cat. 6/500 MHz
MegaLine® Cu patch cords / trunk cables
Shielded, Cat. 6, Class EA, with black moulded boots
MegaLine® Patch Industry 6EA-RJ45
Description
Construction
The cable type used is suitable for transmission rates
EMC
Combined shielding (PiMf + braiding)
of up to 500 MHz. The pair shielding and the high-coverage
RJ45 plug
EN 60603-7
copper braiding as overall shielding ensure excellent NEXT
Electrical values
Cat. 6, Class EA
and return loss values.
Cable/boot
Yellow (PUR)/black
The patch cords and connection cables are equipped with
Fire behaviour
a shielded RJ45 plug at both ends.
Smoke density
IEC 61034-1/2
Halogen free
IEC 60754-1/2
Flame retardance
IEC 60332-2-2
Applications IEEE 802.3, 10Base-T, 100Base-T, 1000Base-T, suitable for 10GBase-T,IEEE 802.5 16MB, ISDN, FDDI, ATM
Accessories
see page 140
MegaLine® Patch RJ45 colour coding clip In different colours for visual coding of the patch cords
Length
Article
m
Order no. Yellow (PUR)
0.5
LKD 9A07 0160 0000
1.0
LKD 9A07 0161 0000
1.5
LKD 9A07 0162 0000
2.0 2.5
LKD 9A07 0163 0000 MegaLine® Patch Industry 6EA-RJ45
LKD 9A07 0164 0000
3.0
LKD 9A07 0165 0000
5.0
LKD 9A07 0166 0000
7.5
LKD 9A07 0167 0000
10.0
LKD 9A07 0168 0000
www.leoni-infrastructure-datacom.com
126
MegaLine® Patch cord TERA™ Shielded, with moulded boots
MegaLine® Patch TERA
Description
Applications
Wiring
The patch cord and connection cable are equipped with TERA™
n 10BASE-T/100BASE-T2
TERA™ 2-pair to RJ45
or RJ45 plugs as required (the RJ45 plug has a moulded boot).
n Token ring
TERA™ 2-pair to RJ45
n ISDN
TERA™ 2-pair to RJ45
The appropriate cable type for the application is used for
n Telephone line
TERA™ 1-pair to RJ45
assembly. The cable type F10-120 S/F flex used is designed
n Telephone line
TERA™ 1-pair to RJ11
for a bandwidth of up to 1,000 Mhz with 4-pair assignment.
n User-defined
TERA™ 4-pair to RJ45
n 2-pair connecting line
TERA™ to TERA™
n 4-pair connecting line
TERA™ to TERA™
Applications
10BASE-T/100BASE-T2
Token ring
ISDN
Telephone line
TERA™ 2-pair to RJ45
TERA™ 2-pair to RJ45
TERA™ 2-pair to RJ45
TERA™ 1-pair to RJ45
Patch cord
Wiring
Length
Article
m 1.0 2.0 3.0 5.0
MegaLine® Patch TERA™ 2-pair to RJ45* (F10-120 S/F flex)
Order no.
Article
10BASE-T/100BASE-T2
Token ring
ISDN
LKD 9A04 0000 0000
LKD 9A04 0006 0000
LKD 9A04 0012 0000
LKD 9A04 0001 0000
LKD 9A04 0007 0000
LKD 9A04 0013 0000
LKD 9A04 0002 0000
LKD 9A04 0008 0000
LKD 9A04 0014 0000
LKD 9A04 0003 0000
LKD 9A04 0009 0000
LKD 9A04 0015 0000
Order no. Telephone line LKD 9A04 0022 0000
MegaLine® Patch TERA™ 1-pair to RJ45* (326 flex)
LKD 9A04 0023 0000 LKD 9A04 0024 0000 LKD 9A04 0025 0000
TERA™ is a registered trademark of the Siemon Company
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter
MegaLine® Cu patch cords / trunk cables
127
Applications
Telephone line
Any
2-pair connecting line
4-pair connecting line
TERA™ 1-pair to RJ11
TERA™ 4-pair to RJ45
TERA™ to TERA™
TERA™ to TERA™
Patch cord
Wiring
Length
Article
m
3.0 5.0
Article
Telephone line
MegaLine® Patch TERA™ 1-pair to RJ11* (326 flex)
LKD 9A04 0018 0000 LKD 9A04 0019 0000 LKD 9A04 0045 0000
TERA™ is a registered trademark of the Siemon Company
www.leoni-infrastructure-datacom.com
Article User-defined
LKD 9A04 0017 0000
1.0 2.0
Order no.
LKD 9A04 0039 0000 MegaLine® Patch TERA™ 4-pair to RJ45* (F10-120 S/F flex)
LKD 9A04 0040 0000 LKD 9A04 0041 0000 LKD 9A04 0042 0000
MegaLine® Patch TERA™ to TERA™ (F10-120 S/F flex)
Order no. 2-pair connecting line
4-pair connecting line
LKD 9A04 0026 0000
LKD 9A04 0032 0000
LKD 9A04 0027 0000
LKD 9A04 0033 0000
LKD 9A04 0028 0000
LKD 9A04 0034 0000
LKD 9A04 0029 0000
LKD 9A04 0035 0000
128
MegaLine® Patch cord and connection cable EC7 4-pair, shielded, with yellow boots
MegaLine® Patch 4P EC7/EC7 MegaLine® Patch 4P EC7/RJ45 MegaLine® Patch 4P EC7/open
Description
Construction
Patch cord and connection cable for Gigabit Ethernet.
Cable type
4 p, Light grey RAL 7035
Boot
Yellow
MegaLine® Patch 4P EC7/EC7
MegaLine® Patch 4P EC7/RJ45
MegaLine® Patch 4P EC7/open
4-pair EC7 plug 4-pair EC7 plug
4-pair EC7 plug RJ45 plug
4-pair EC7 plug Open (e.g. for self-assembly of an RJ45 plug)
Patch cord and connection cable
Equipment at end A Equipment at end B
Plug rear view
Plug rear view
Plug rear view
Assignment
Open end
1 2 3 4 5 6 7 8
RJ45 front view
EC7/RJ45: 1/2-4/5, 3/4-7/8, 5/6-2/1, 7/8-3/6
EC7/EC7: 1/1
Length
Article
1.0 2.0 3.0 5.0
Order no.
Article
Yellow (LSOH)
m
LKD 9KEC 1020 0000 LKD 9KEC 1030 0000 LKD 9KEC 1050 0000
Article
Order no.
Yellow (LSOH)
LKD 9KEC 1010 0000 MegaLine® Patch 4P EC7/EC7 (1 piece)
Order no.
Yellow (LSOH)
LKD 9KEC 2010 0000 MegaLine® Patch 4P EC7/RJ45 (1 piece)
LKD 9KEC 2020 0000 LKD 9KEC 2030 0000 LKD 9KEC 2050 0000
MegaLine® Patch 4P EC7/open (1 piece) LKD 9KEC 0050 0000
www.leoni-infrastructure-datacom.com
Office
DataCenter
Industry
129
MegaLine® Patch cord and connection cable EC7
MegaLine® Cu patch cords / trunk cables
2-pair, shielded, with coloured boots
MegaLine® Patch 2P EC7/EC7 MegaLine® Patch 2P EC7/open MegaLine® Patch 2P EC7/RJ45 MegaLine® Patch 2P EC7/RJ45 Cross over
Description
Construction
Patch cord and connection cable for Gigabit Ethernet.
Cable type
2 p, Light grey RAL 7035
Boot
Grey or yellow
MegaLine® Patch 2P EC7/EC7
MegaLine® Patch 2P EC7/open
MegaLine® Patch 2P EC7/RJ45
MegaLine® Patch 2P EC7/RJ45 Cross over
2-pair EC7 plug 2-pair EC7 plug
2-pair EC7 plug Open (e.g. for self-assembly of an RJ45 plug)
2-pair EC7 plug RJ45 plug
2-pair EC7 plug RJ45 plug
Patch cord and connection cable
Equipment at end A Equipment at end B
Plug rear view
Plug rear view
Plug rear view
Plug rear view
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Open end
Assignment EC7 rear view
RJ45 front view
EC7/EC7: 1/1
Length
Article
Order no.
EC7/RJ45: 1/2, 3/6 for Ethernet
Article
Grey (LSOH)
m
Order no.
Article
Grey (LSOH)
Order no.
LKD 9KE0 1005 0000
LKD 9KE0 3005 0000
1.0
LKD 9KE0 1010 0000
LKD 9KE0 3010 0000
2.0 3.0 5.0
LKD 9KE0 1020 0000 LKD 9KE0 1030 0000 LKD 9KE0 1050 0000
www.leoni-infrastructure-datacom.com
MegaLine® Patch 2P EC7/open (1 piece)
MegaLine® Patch 2P EC7/RJ45 (1 piece) LKD 9KE0 2050 0000
Article
Yellow (LSOH)
0.5 MegaLine® Patch 2P EC7/EC7 (1 piece)
RJ45 front view
EC7/RJ45: 1/2, 3/6 for Ethernet cross over
LKD 9KE0 3020 0000 LKD 9KE0 3030 0000 LKD 9KE0 3050 0000
Order no. Yellow (LSOH) LKD 9KE3 1005 0000
MegaLine® Patch 2P EC7/RJ45 Cross over (1 piece)
LKD 9KE3 1010 0000 LKD 9KE3 1020 0000 LKD 9KE3 1030 0000 LKD 9KE3 1050 0000
130
MegaLine® Patch cord and connection cable EC7 1-pair, shielded, with black boots
MegaLine® Patch 1P EC7/EC7 MegaLine® Patch 1P EC7/open MegaLine® Patch 1P EC7/RJ10 MegaLine® Patch 1P EC7/RJ11
Description
Construction
Patch cord and connection cable for analogue and digital
Cable type
3-core, Jet black RAL 9005
telephone systems.
Boot
Black
MegaLine® Patch 1P EC7/EC7
MegaLine® Patch 1P EC7/open
MegaLine® Patch 1P EC7/RJ10
MegaLine® Patch 1P EC7/RJ11
1-pair EC7 plug 1-pair EC7 plug
1-pair EC7 plug Open (e.g. for self-assembly of an RJ11 plug)
1-pair EC7 plug RJ10 plug
2-pair EC7 plug RJ11 plug
Patch cord and connection cable
Equipment at end A Equipment at end B
EC7 1P rear view
EC7 1P rear view oblique outer edge
EC7 1P rear view oblique outer edge
oblique outer edge
EC7/EC7: 1/1
Article
0.5 1.0
3.0 5.0
oblique outer edge
Order no.
Article
Order no.
Article
Black (PVC)
LKD 9KE7 4005 0000 MegaLine® Patch 1P EC7/EC7 (1 piece)
LKD 9KE7 4010 0000 LKD 9KE7 4020 0000 LKD 9KE7 4030 0000 LKD 9KE7 4050 0000
1 2 3 4
1 2 3 4 5 6
RJ10 (4/4) front view
RJ11 (6/4) front view
EC7/RJ10: 4/4
Black (PVC)
m
2.0
oblique outer edge
Open end
Assignment
Length
EC7 1P rear view
MegaLine® Patch 1P EC7/open (1 piece)
MegaLine® Patch 1P EC7/RJ10 (1 piece) LKD 9KE7 5050 0000
Order no.
EC7/RJ11: 6/4
Article
Order no.
Black (PVC)
Black (PVC)
LKD 9KE7 6005 0000
LKD 9KE7 8005 0000
LKD 9KE7 6010 0000 LKD 9KE7 6020 0000 LKD 9KE7 6030 0000 LKD 9KE7 6050 0000
MegaLine® Patch 1P EC7/RJ11 (1 piece)
LKD 9KE7 8010 0000 LKD 9KE7 8020 0000 LKD 9KE7 8030 0000 LKD 9KE7 8050 0000
www.leoni-infrastructure-datacom.com
Office
DataCenter
Industry
131
MegaLine® Patch cord and connection cable EC7
MegaLine® Cu patch cords / trunk cables
1-pair/2-pair, shielded, with black boots
MegaLine® Patch 1P EC7/RJ45 MegaLine® Patch 2P EC7/RJ45
Description
Construction
Patch cord and connection cable for telephone systems.
Cable type
3-core, Jet black RAL 9005
Boot
Black
MegaLine® Patch 1P EC7/RJ45
MegaLine® Patch 1P EC7/RJ45
MegaLine® Patch 2P EC7/RJ45
1-pair EC7 plug RJ45 plug
1-pair EC7 plug RJ45 plug
2-pair EC7 plug RJ45 plug without boot
Patch cord and connection cable
Equipment at end A Equipment at end B
EC7 1P rear view
EC7 1P rear view oblique outer edge
EC7 2P rear view oblique outer edge
Assignment 1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
RJ45 front view
RJ45 front view
RJ45 front view
For digital telephony
Length
Article
m 0.5 1.0 2.0 3.0
MegaLine® Patch 1P EC7/RJ45 (1 piece)
5.0
www.leoni-infrastructure-datacom.com
Order no.
For analogue telephony For terminals with earthing key
Article
Order no.
EC7/RJ45: 3/6, 4/5 for ISDN
Article
Order no.
Black (PVC)
Black (PVC)
Black (PVC)
LKD 9KE7 9005 0000
LKD 9KE8 0005 0000
LKD 9KE6 7005 0000
LKD 9KE7 9010 0000 LKD 9KE7 9020 0000 LKD 9KE7 9030 0000 LKD 9KE7 9050 0000
MegaLine® Patch 1P EC7/RJ45 (1 piece)
LKD 9KE8 0010 0000 LKD 9KE8 0020 0000 LKD 9KE8 0030 0000 LKD 9KE8 0050 0000
MegaLine® Patch 2P EC7/RJ45 (1 piece)
LKD 9KE6 7010 0000 LKD 9KE6 7020 0000 LKD 9KE6 7030 0000 LKD 9KE6 7050 0000
132
MegaLine® Trunk cable, industrial VarioKeystone® cable plug Cat. 7, pre-assembled With documented acceptance measurement on CD on request (page 79)
With documented acceptance measurement on CD on request (page 79)
Trunk Contact block: white/white
Crossconnect trunk Contact block: white/red
MegaLine® Trunk cable
MegaLine® Crossconnect trunk cable
Description
Description
The data cable is assembled with cable plugs at both ends.
The data cable is assembled with cable plugs at both ends.
Ideal for clean rooms or for fast manipulation on site. During
Ideal for clean rooms or for fast manipulation on site. During
pre-assembly, the cable plug is moulded with a casting
pre-assembly, the cable plug is moulded with a casting
compound that simultaneously protects against bending.
compound that simultaneously protects against bending.
The pre-assembled cable is supplied as a ring.
The pre-assembled cable is supplied as a ring.
Construction
Construction
Material
Full metal; die-cast zinc, nickel-plated
Material
Cable
MegaLine®F10-115 S/F AWG 23/1
Cable
(Order no.: LKD 7KS7 0008 0000)
Full metal; die-cast zinc, nickel-plated MegaLine®F10-115 S/F AWG 23/1 (Order no.: LKD 7KS7 0008 0000)
Side A
VarioKeystone® cable plug Cat. 7
Side A
VarioKeystone® cable plug Cat. 7
Side B
VarioKeystone® cable plug Cat. 7
Side B
VarioKeystone® cable plug Cat. 7
Assignment
1:1
Assignment
Crossconnect
Shielding
Large-surface 360° shield connection
Shielding
Large-surface 360° shield connection
Contact block: white/white Electrical values
Category 7
Contact block: white/red Electrical values
Category 7
Standards Standards ■■
ISO/IEC 11801
■■
EN 50173-1
Article
MegaLine® Trunk cable
Length
Order no.
10.0 m
LKD 9A06 0095 0000
15.0 m
LKD 9A06 0096 0000
20.0 m
LKD 9A06 0097 0000
30.0 m
LKD 9A06 0099 0000
40.0 m
LKD 9A06 0101 0000
50.0 m
LKD 9A06 0103 0000
Standard lengths, further lengths and cable types (also assembled at one end) on request
■■
ISO/IEC 11801
■■
EN 50173-1
Article
MegaLine® Crossconnect trunk cable
Length
Order no.
10.0 m
LKD 9A06 0129 0000
15.0 m
LKD 9A06 0130 0000
20.0 m
LKD 9A06 0131 0000
30.0 m
LKD 9A06 0133 0000
40.0 m
LKD 9A06 0135 0000
50.0 m
LKD 9A06 0137 0000
Standard lengths, further lengths and cable types (also assembled at one end) on request
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 133
MegaLine® Trunk cable
With documented acceptance measurement on CD on request (page 79)
With documented acceptance measurement on CD on request (page 79)
Trunk Contact block: white/white
Crossconnect trunk Contact block: white/red
MegaLine® Trunk cable
MegaLine® Crossconnect trunk cable
Description
Description
The data cable is assembled with cable plugs at both ends.
The data cable is assembled with cable plugs at both ends.
Ideal for clean rooms or for fast manipulation on site. During
Ideal for clean rooms or for fast manipulation on site. During
pre-assembly, the cable plug is moulded with a casting
pre-assembly, the cable plug is moulded with a casting
compound that simultaneously protects against bending.
compound that simultaneously protects against bending.
The pre-assembled cable is supplied as a ring.
The pre-assembled cable is supplied as a ring.
■■
Oil resistant acc. to ICEA S-82-552 (+60 °C)
Construction
■■
Oil resistant acc. to ICEA S-82-552 (+60 °C)
Construction
Material
Full metal; die-cast zinc, nickel-plated
Material
Full metal; die-cast zinc, nickel-plated
Cable
MegaLine®F10-130 Vö AWG 22/1
Cable
MegaLine®F10-130 Vö AWG 22/1
(Order no.: LKD 7KS7 0089 0000)
(Order no.: LKD 7KS7 0089 0000)
Side A
VarioKeystone® cable plug Cat. 7
Side A
VarioKeystone® cable plug Cat. 7
Side B
VarioKeystone® cable plug Cat. 7
Side B
VarioKeystone® cable plug Cat. 7
Assignment
1:1
Assignment
Crossconnect
Shielding
Large-surface 360° shield connection
Shielding
Crossconnect
Contact block: white/white Electrical values
Category 7
Large-surface 360° shield connection Electrical values
Contact block: white/red Category 7
Standards
Standards
■■
ISO/IEC 11801
■■
ISO/IEC 11801
■■
EN 50173-1
■■
EN 50173-1
Article
MegaLine® Trunk cable
Length*
Order no.
15.0 m
LKD 9A06 0201 0000
20.0 m
LKD 9A06 0202 0000
30.0 m
LKD 9A06 0204 0000
40.0 m
LKD 9A06 0206 0000
50.0 m
LKD 9A06 0208 0000
Standard lengths, further lengths and cable types (also assembled at one end) on request
www.leoni-infrastructure-datacom.com
Article
MegaLine® Crossconnect trunk cable
Length*
Order no.
15.0 m
LKD 9A06 0231 0000
20.0 m
LKD 9A06 0232 0000
30.0 m
LKD 9A06 0234 0000
40.0 m
LKD 9A06 0236 0000
50.0 m
LKD 9A06 0238 0000
Standard lengths, further lengths and cable types (also assembled at one end) on request
MegaLine® Cu patch cords / trunk cables
VarioKeystone® cable plug Cat. 7, pre-assembled
134
MegaLine® Trunk cable, 8 port RJ45 Shielded, Cat. 6, Class EA
MegaLine® Trunk RJ45 plug/RJ45 plug Description Pre-assembled trunk cable, 8 ports equipped with RJ45 plugs at both ends. Construction Cable type
F10-120 S/F flex 8x4P AWG 26/7
Side A
RJ45 plug, grey boot
Side B
RJ45 plug, grey boot
Labels
16 x laminated label, printed according to customer's
Whip length
specification
Electrical values
0.4 m Cat. 6, Class EA
Standards ■■
ISO/IEC 11801
■■
EN 50173-1
Length
Article
Order no.
20.0 m
MegaLine® Trunk RJ45 plug/RJ45 plug (1 piece)
LKD 9A06 0929 0000
Standard length, further lengths on request
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 135
MegaLine® Trunk cable, 4 port/8 port
With documented acceptance measurement on CD on request.
MegaLine® Trunk cable, 4 port MegaLine® Trunk cable, 8 port Description
Construction
The data cable is assembled with cable plugs at both ends.
Material
Full metal; die-cast zinc, nickel-plated
Ideal for clean rooms or for fast manipulation on site. During
Assignment
1:1
pre-assembly, the cable plug is moulded with a casting
Shielding
Large-surface 360° shield connection
compound that simultaneously protects against bending.
Contact block: white
The pre-assembled cable is supplied as a ring.
Electrical values
Cable
Standards
Type
MegaLine®F10-115 S/F 4x4P AWG 23/1 (Order no.: LKD 7KS7 0161 0000)
MegaLine®F10-120 S/F flex 8x4P AWG 26/7 (Order no.: LKD 7KS7 0142 0000)
Side A
VarioKeystone® cable plug Cat. 7
Side B
VarioKeystone® cable plug Cat. 7
Whip length
0.4 m
Article
Length*
Order no.
MegaLine® Trunk cable 4 port
10.0 m
LKD 9A06 1019 0000
15.0 m
LKD 9A06 1020 0000
5.0 m
LKD 9A06 0192 0000
MegaLine® Trunk cable 8 port
7.5 m
LKD 9A06 0193 0000
10.0 m
LKD 9A06 0194 0000
15.0 m
LKD 9A06 0195 0000
Standard lengths, further lengths and cable types (also assembled at one end) on request
www.leoni-infrastructure-datacom.com
■■
Category 7
ISO/IEC 11801 n EN 50173-1
MegaLine® Cu patch cords / trunk cables
VarioKeystone® cable plug Cat. 7, pre-assembled
136
MegaLine® Connect45 trunk cable Pre-assembled single cable with MegaLine® Connect45 jack modules Cat. 6A/Cat. 6A With documented acceptance measurement on CD on request.
Jack module Cat. 6A white
Jack module Cat. 6A aqua
MegaLine® Connect45 Trunk Cat. 6A modules MegaLine® Connect45 Trunk Cat. 6A modules Description
Construction – VarioKeystone® jack modules
The trunk cable is based on an F6-90 S/F data cable with
Cable
F6-90 S/F (4x2x AWG 23/1)
Thanks to the high quality of the components, the pre-assembled
Side A/side B
MegaLine® Connect45 Cat. 6A (ISO/IEC)
cable meets all permanent link requirements (>1 m, Cat. 6A
(version 1)
(Order no.: LKD 9A50 2010 0000)
to ISO/IEC 11801 and EN 50173 for 10 Gigabit Ethernet.
Side A/side B
MegaLine® Connect45 Cat. 6A (EIA/TIA)
The lengths relate to the 2-connector model.
(version 2)
(Order no.: LKD 9A50 2020 0000)
a MegaLine® Connect45 jack at both ends.
modules) or (>10 m, Cat. 6A modules) from Class EA according
Also available without a jack module – ideal in combination with high-density patch panels (see page 101). Standards n ISO/IEC
11801 n EN 50173-1
n IEC60603-7-51
(Cat. 6A) n EIA/TIA 568-C.2 (Cat. 6A)
Article
Jack module format
VarioKeystone®
MegaLine® Connect45 Trunk
Keystone
Construction – Keystone jack modules Cable
F6-90 S/F (4x2x AWG 23/1)
Side A/side B
MegaLine® Connect45 Cat. 6A (ISO/IEC)
(version 1)
(Order no.: LKD 9A50 1010 0000)
Side A/side B
MegaLine® Connect45 Cat. 6A (EIA/TIA)
(version 2)
(Order no.: LKD 9A50 1020 0000)
Length*
Cat. 6A modules
Cat. 6A modules
5.0 m
LKD 9A06 1173 0000
—
10.0 m
LKD 9A06 1174 0000
—
15.0 m
LKD 9A06 1175 0000
—
30.0 m
LKD 9A06 1176 0000
—
90.0 m
LKD 9A06 1177 0000
—
5.0 m
LKD 9A06 1132 0000
LKD 9A06 1127 0000
10.0 m
LKD 9A06 1133 0000
LKD 9A06 1128 0000
15.0 m
LKD 9A06 1134 0000
LKD 9A06 1129 0000
30.0 m
LKD 9A06 1135 0000
LKD 9A06 1130 0000
90.0 m
LKD 9A06 1136 0000
LKD 9A06 1131 0000
* Standard lengths/further lengths on request
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 137
MegaLine® Connect45 Trunk, 8 port
With documented acceptance measurement on CD on request.
Jack module Cat. 6A aqua
MegaLine® Connect45 Trunk, 8 port Cat. 6A modules Description
Construction – VarioKeystone® jack modules
The trunk cable is based on an 8-fold F10-120 S/F flex data cable
Cable
F10-120 S/F flex (8x4x2x AWG 26/7)
Side A/side B
MegaLine® Connect45 Cat. 6A
with a MegaLine® Connect45 jack at both ends. Thanks to the high quality of the components, the pre-assembled cable meets all permanent link requirements
(Order no.: LKD 9A50 2010 0000)
(>1 m, Cat. 6A modules) from Class EA according to ISO/IEC
0.4 m
Whip length
11801 and EN 50173 for 10 Gigabit Ethernet. Construction – Keystone jack modules Also available without a jack module – ideal in combination
Cable
F10-120 S/F flex (8x4x2x AWG 26/7)
Side A/side B
MegaLine® Connect45 Cat. 6A
with high-density patch panels (see page 101). (Order no.: LKD 9A50 1010 0000)
Whip length
0.4 m
Standards ■■
Article
Jack module format
VarioKeystone® MegaLine® Connect45 Trunk, 8 port Keystone
* Standard lengths/further lengths on request
www.leoni-infrastructure-datacom.com
ISO/IEC 11801 n EN 50173-1 n IEC60603-7-51
Length*
Cat. 6A modules
5.0 m
LKD 9A06 1178 0000
7.5 m
LKD 9A06 1179 0000
10.0 m
LKD 9A06 1180 0000
15.0 m
LKD 9A06 1181 0000
5.0 m
LKD 9A06 1137 0000
7.5 m
LKD 9A06 1138 0000
10.0 m
LKD 9A06 1139 0000
15.0 m
LKD 9A06 1140 0000
MegaLine® Cu patch cords / trunk cables
Pre-assembled multi cable with MegaLine® Connect45 jack modules Cat. 6A
138
MegaLine® Connect45 CP cable Pre-assembled single cable with MegaLine® Connect45 jack modules Cat. 6A/Cat. 6A With documented acceptance measurement on CD on request.
Jack module Cat. 6A VarioKeystone® format
Jack module Cat. 6A Keystone format
MegaLine® Connect45 CP cable Description
Construction – VarioKeystone® jack modules
The consolidation point cable is based on an F10-120 S/F flex
Cable
F10-120 S/F flex (4x2x AWG 26/7)
a RJ45 SmartLock plug at the other.
Side A
MegaLine® Connect45 Cat. 6A (ISO/IEC)
Thanks to the high-quality components in combination
Side B
data cable with a MegaLine® Connect45 jack at one end and (Order no.: LKD 9A50 2010 0000)
RJ45 plug (SmartLock Cat. 6A)
with a CP Link (>10 m), the pre-assembled cable meets the requirements of the Class EA permanent link according
Construction – Keystone jack modules
to ISO/IEC 11801 Amendment 2 for 10 Gigabit Ethernet.
Cable
F10-120 S/F flex (4x2x AWG 26/7)
Standards
Side A
MegaLine® Connect45 Cat. 6A (ISO/IEC)
■■
ISO/IEC 11801 n EN 50173-1 n IEC60603-7-51
(Order no.: LKD 9A50 1010 0000)
Side B
Article
Jack module format
VarioKeystone®
MegaLine® Connect45 CP cable
Keystone
Length*
RJ45 plug (SmartLock Cat. 6A)
Cat. 6A modules
5.0 m
LKD 9A02 3353 0000
10.0 m
LKD 9A02 3354 0000
15.0 m
LKD 9A02 3355 0000
20.0 m
LKD 9A02 3356 0000
25.0 m
LKD 9A02 3357 0000
5.0 m
LKD 9A02 3343 0000
10.0 m
LKD 9A02 3344 0000
15.0 m
LKD 9A02 3345 0000
20.0 m
LKD 9A02 3346 0000
25.0 m
LKD 9A02 3347 0000
* Standard lengths/further lengths on request
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 139
MegaLine® EC7 CP cable
MegaLine® Cu patch cords / trunk cables
Shielded, Cat. 7, Class F
MegaLine® EC7 CP cable Description Trunk and consolidation point cable, assembled with an ELine 1200® EC7 plug and an ELine 1200® EC7 plug. Construction Cable type
F10-120 S/F flex 1x4P AWG 26/7
Side A
ELine 1200® EC7 plug
Side B
ELine1200® EC7 jack
Electrical values
Cat. 7, Class F
Standards ■■
ISO/IEC 11801
■■
EN 50173-1
Length
Article
Order no.
5.0 m
LKD 9KEJ 8050 0000
10.0 m
LKD 9KEJ 8100 0000
15.0 m 20.0 m
MegaLine® EC7 CP cable (1 piece)
LKD 9KEJ 8150 0000 LKD 9KEJ 8200 0000
25.0 m
LKD 9KEJ 8250 0000
30.0 m
LKD 9KEJ 8300 0000
www.leoni-infrastructure-datacom.com
140
MegaLine® Patch accessories
MegaLine® Patch accessories
for LED patch cords
for RJ45 patch cords
MegaLine® Patch LED colour clip MegaLine® Patch LED detector
MegaLine® Patch RJ45 colour coding clip
Accessories
Accessories
Colour clip:
Colour coding clip for visual coding of the patch cords.
For visual coding of the LED patch cords.
Can be installed by simply pushing on.
Can be installed by simply snapping into the RJ45 plugs. Compatibility MegaLine® Patch 5D-RJ45 MegaLine® Patch 6E-RJ45U MegaLine® Patch 6EA-RJ45 MegaLine® Patch 6AEA-RJ45 MegaLine® Patch Industry 6EA-RJ45
Detector: For feeding the light signal for identifying the patch cord. Batteries included: 4 x LR41
Order no.
Article
Colour
Order no.
Article
Colour ● Rape yellow RAL 1021
LKD 9A09 0180 0000
● Light grey RAL 7035
LKD 9AW1 6031 0000
MegaLine® Patch LED colour clip (100 pieces)
● Flame red RAL 3000
LKD 9A09 0181 0000
● Turquoise green RAL 6016
LKD 9AW1 6032 0000
● Sky blue RAL 5015
LKD 9A09 0182 0000
● Turquoise green RAL 6016 LKD 9A09 0183 0000 MegaLine® Patch LED detector (1 piece)
LKD 9A09 0190 0000
● Sky blue RAL 5015 MegaLine® Patch RJ45 colour coding clip ● Flame red RAL 3000 (100 pieces) ● Pastel orange RAL 2003
LKD 9AW1 6033 0000 LKD 9AW1 6034 0000 LKD 9AW1 6035 0000
● Rape yellow RAL 1021
LKD 9AW1 6036 0000
● Jet black RAL 9005
LKD 9AW1 6037 0000
www.leoni-infrastructure-datacom.com
Office
DataCenter
Industry
141
MegaLine® Test report
MegaLine® Cu patch cords / trunk cables
for all trunk cables
Also order
Measurements for trunks
The measurement carried out prior to delivery can be documen-
➔ Permanent link Class EA (with ISO/IEC jack module)
ted on CD as a test report and supplied on request.
➔ Permanent link Class EA (with EIA/TIA jack module) ➔ Channel Class EA (with ISO/IEC jack module) ➔ Channel Class EA (with EIA/TIA jack module) Measurements for CP cables ➔ Permanent link Class EA (with ISO/IEC jack module) Acceptance measurements ➔ Channel Class FA ➔ Permanent link Class F ➔ Permanent link Class EA ➔ Channel Class EA (with Cat. 6 module) ➔ Channel Class EA (with Cat. 6
Product family
MegaLine® Connect45
MegaLine® Connect45
VarioKeystone®
Measurement
for trunks
for CP cable
for trunks
www.leoni-infrastructure-datacom.com
A
module)
Acceptance measurement
Order no.
Permanent link Class EA (with ISO/IEC jack module)
LKD 9A50 4020 0000
Permanent link Class E A (with EIA/TIA jack module)
LKD 9A50 4021 0000
Channel Class E A (with ISO/IEC jack module)
LKD 9A50 4022 0000
Channel Class E A (with EIA/TIA jack module)
LKD 9A50 4023 0000
Permanent link Class E A (with ISO/IEC jack module)
LKD 9A50 4024 0000
Channel Class FA
LKD 9A46 0132 0000
Permanent link Class F
LKD 9A46 0123 0000
Permanent link Class E A
LKD 9A46 0125 0000
Channel Class E A (with Cat. 6A module)
LKD 9A46 0131 0000
Channel Class E A (with Cat. 6 module)
LKD 9A46 0126 0000
142
MegaLine® Acceptance measurement
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 143
Acceptance measurement of the MegaLine® cabling systems The acceptance measurement for the MegaLine® cabling systems for the channel or permanent link is carried out in accordance with the requirements of SO/IEC 11801 or EN 50173, 2nd Edition Amendment 1/2. Further standards regarding the acceptance measurement (measurement procedure): DIN EN 50346 and DIN EN 61935.
www.leoni-infrastructure-datacom.com
144
Channel Class E/EA/F/FA
Frequency/MHz
1
16
100
250
Return loss
19.0
18.0
12.0
8.0
Insertion loss
4.0
8.3
21.7
35.9
500
600
1000
Channel Class E
NEXT
65.0
53.2
39.9
33.1
PS NEXT/dB
62.0
50.6
37.1
30.2
ACR-N/dB
61.0
44.9
18.2
–2.8
PS-ACR-N/dB
58.0
42.3
15.4
–5.8
ACR-F/dB
63.3
39.2
23.3
15.3
PS-ACR-F/dB
60.3
36.2
20.3
12.3
Runtime/µs
0.580
0.553
0.548
0.546
Runtime difference/µs
0.050
0.050
0.050
0.050
Return loss
19.0
18.0
12.0
8.0
6.0
Insertion loss
4.0
8.2
20.9
33.9
49.3
Channel Class E A
NEXT
65.0
53.2
39.9
33.1
27.9
PS NEXT/dB
62.0
50.6
37.1
30.2
24.8
ACR-N/dB
61.0
45.0
19.0
–0.8
–21.4
PS-ACR-N/dB
58.0
42.4
16.2
–3.7
–24.5
ACR-F/dB
63.3
39.2
23.3
15.3
9.3
PS-ACR-F/dB
60.3
36.2
20.3
12.3
6.3
Runtime/µs
0.580
0.553
0.548
0.546
0.546
Runtime difference/µs
0.050
0.050
0.050
0.050
0.050
Return loss
19.0
18.0
12.0
8.0
49.3
8.0
Insertion loss
4.0
8.1
20.8
33.8
52.4
54.6
Channel Class F
NEXT
65.0
65.0
62.9
56.9
49.4
51.2
PS NEXT/dB
62.0
62.0
59.9
53.9
3.1
48.2
ACR-N/dB
61.0
56.9
42.1
23.1
0.1
–3.4
PS-ACR-N/dB
58.0
53.9
39.1
20.1
32.6
–6.4
ACR-F/dB
65.0
57.5
44.4
37.8
29.6
31.3
PS-ACR-F/dB
62.0
54.5
41.4
34.8
8.0
28.3
Runtime/µs
0.580
0.553
0.548
0.546
0.546
0.545
Runtime difference/µs
0.030
0.030
0.030
0.030
0.03
0.030
Return loss
19.0
18.0
12.0
8.0
8.0
8.0
6.0
Insertion loss
4.0
8.0
20.3
32.5
46.7
51.4
67.6
Channel Class FA
NEXT
65.0
65.0
65.0
59.1
53.6
52.1
47.9
PS NEXT/dB
62.0
62.0
62.0
56.1
50.6
49.1
44.9
ACR-N/dB
61.0
57.0
44.7
26.7
6.9
0.7
–19.6
PS-ACR-N/dB
58.0
54.0
41.7
23.7
3.9
–2.3
–22.6
ACR-F/dB
65.0
63.3
47.4
39.4
33.4
31.8
27.4
PS-ACR-F/dB
62.0
60.3
44.4
36.4
30.4
28.8
24.4
Runtime/µs
0.580
0.553
0.548
0.546
0.546
0.545
0.545
Runtime difference/µs
0.030
0.030
0.030
0.030
0.030
0.030
0.030
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 145
Permanent link
Frequency/MHz
1
16
100
250
500
600
1000
Permanent link Class E 21.0
20.0
14.0
10.0
Insertion loss
Return loss
4
7.1
18.5
30.7
NEXT
65
54.6
41.8
35.3
PS Next/dB
62
52.2
39.3
32.7
ACR-N/dB
61
47.5
23.3
4.7
PS ACR-N/dB
58
45.1
20.8
2
64.2
40.1
24.2
16.2
ACR-F/dB PS ACR-F/dB
61.2
37.1
21.2
13.2
Runtime/µs
0.521
0.496
0.491
0.490
Runtime difference/µs
0.044
0.044
0.044
0.044
Permanent link Class EA Return loss
21.0
20.0
14.0
10.0
8.0
Insertion loss
4
7
17.8
28.9
42.1
NEXT
65
54.6
41.8
35.3
29.2/27.9*
PS Next/dB
62
52.2
39.3
32.7
26.4/24.8*
ACR-N/dB
61
47.6
24
6.4
–12.9/14.2*
PS ACR-N/dB
58
45.2
21.5
3.8
–15.7/16.3*
ACR-F/dB
64.2
40.1
24.2
16.2
10.2
PS ACR-F/dB
61.2
37.1
21.2
13.2
7.2
Runtime/µs
0.521
0.496
0.491
0.490
0.490
Runtime difference/µs
0.044
0.044
0.044
0.044
0.044
Permanent link Class F 21.0
20.0
14.0
10.0
10.0
10.0
Insertion loss
Return loss
4
6.9
17.7
28.8
42.1
46.6
NEXT
65
65
65
60.4
55.9
54.7
PS Next/dB
62
62
62
57.4
52.9
51.7
ACR-N/dB
61
58.1
47.3
31.6
13.8
8.1
PS ACR-N/dB
58
55.1
44.3
28.6
10.8
5.1
ACR-F/dB
65
59.3
46
39.2
34
32.6
PS ACR-F/dB
62
56.3
43
36.2
31
29.6
Runtime/µs
0.521
0.496
0.491
0.490
0.490
0.489
Runtime difference/µs
0.026
0.026
0.026
0.026
0.026
0.026
Permanent link Class FA Return loss
21.0
20.0
14.0
10.0
10.0
10.0
8.0
Insertion loss
4
6.8
17.3
27.7
39.8
43.9
57.6
NEXT
65
65
65
61.7
56.1
54.7
49.1/47.9*
PS Next/dB
62
62
62
58.7
53.1
51.7
46.1/44.9*
ACR-N/dB
61
58.2
47.7
34
16.4
10.8
–8.5/9.7*
PS ACR-N/dB
58
55.2
44.7
31
13.4
7.8
–11.5/12.7
ACR-F/dB
65
64.7
48.8
40.8
34.8
33.2
28.8
PS ACR-F/dB
62
61.7
45.8
37.8
31.8
30.2
25.8
Runtime/µs
0.521
0.496
0.491
0.490
0.490
0.489
0.489
0.026
0.026
0.026
0.026
0.026
0.026
0.026
Runtime difference/µs
* = 3-connector link
www.leoni-infrastructure-datacom.com
MegaLine® Cu data cables
Class E/EA/F/FA
146
Acceptance measurement Class EA VarioKeystone® RJ45/MegaLine® Connect45
The measuring device is set to the measuring bandwidth
Make sure that the measuring adapter is connected to the
of 500 MHz for the acceptance measurement according
measuring device and firmly engaged. Take the corresponding
to Class EA.
measuring cable and make sure that it is firmly plugged in. If synchronisation is required, this is then carried out according
Refer to the instructions on setting the measuring device.
to the instructions for the device.
Information can be found under: www.idealindustries.de/www.flukenetworks.com.
Standard acceptance: Channel or permanent link
VarioKeystone® RJ45
Ideal LanTEK II/7G (available from Ideal Industries)
Fluke DTX 1800 (available from Fluke Networks)
Measuring cable set Order no.: 9A024414
MegaLine® Connect45
Ideal LanTEK II/7G (available from Ideal Industries)
Fluke DTX 1800 (available from Fluke Networks)
Measuring cable set Order no.: 9A024414
System
Approved measuring devices
Approved measuring cables www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 147
Acceptance measurement Class F VarioKeystone® 4K7/ELine 1200® EC7
The measuring device is set to the measuring
Make sure that the measuring adapter is connected to the
bandwidth of 600 MHz for the acceptance measurement
measuring device and firmly engaged. Take the corresponding
according to Class F.
measuring cable and make sure that it is firmly plugged in. If synchronisation is required, this is then carried out according
Refer to the instructions on setting the measuring device.
to the instructions for the device.
Information can be found under: www.idealindustries.de/www.flukenetworks.com
Standard acceptance: Channel or permanent link Standard acceptance: Channel or permanent link
VarioKeystone® 4K7
Ideal LanTEK II/7G (available from Ideal Industries)
EC7 measuring adapter (channel) (available from Ideal Industries)
Measuring cable set (Order no.: LKD 9ZE3 0053 0000)
ELine 1200® EC7
Ideal LanTEK II/7G (available from Ideal Industries)
EC7 measuring adapter (channel) (available from Ideal Industries)
Measuring cable set (Order no.: 9ZE30057)
ELine 1200® EC7
Fluke DTX 1800 (available from Fluke Networks)
EC7 measuring adapter (permanent link) (Order no.: 9ZE30038)
System
www.leoni-infrastructure-datacom.com
Approved measuring devices
Approved measuring adapters
Approved measuring cables
148
Acceptance measurement Class FA ELine 1200® EC7
The measuring device is set to the measuring bandwidth
Make sure that the measuring adapter is connected to the
of 1,000 MHz for the acceptance measurement according
measuring device and firmly engaged. Take the corresponding
to Class FA.
measuring cable and make sure that it is firmly plugged in. Next carry out the field zero adjustment according to the instructions
Refer to the instructions on setting the measuring device.
for the device.
Information can be found under: www.idealindustries.de/www.flukenetworks.com
Standard acceptance: Channel or permanent link
ELine 1200® EC7
System
Ideal LanTEK II/7G (available from Ideal Industries)
Approved measuring devices
EC7 measuring adapter (available from Ideal Industries)
Approved measuring adapters
Measuring cable set (Order no.: 9ZE30057)
Approved measuring cables www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 149
www.leoni-infrastructure-datacom.com
150
Alien crosstalk
AlienX (AXT)
EMI NIC
10Gbit/s
10Gbit/s
Switch
NEXT
FEXT Return Loss
Transmission model and alien crosstalk 10GBASE- T
Alien crosstalk describes the undesirable mutual electrical
These characteristics are design-specific and do not change
influence between parallel links in the installation duct and
in the installation environment. IEEE 802.3an considers shielded
in the vicinity of the patch fields. In contrast to NEXT and
cabling systems to be the preferred solution.
attenuation, disturbance through alien crosstalk cannot be compensated for electronically. Alien crosstalk has become extremely important from a technical point of view. ISO/IEC 11801 Amendment 1 (Generic cabling for customer premises) takes this into account with relevant specifications for the new transmission classes EA (500 MHz) and FA (1,000 MHz). MegaLine® S/FTP cabling systems meet the requirements for alien crosstalk with a high degree of reliability. External
Frequency MHz
Minimum PS ANEXT dB Class E A, F
Class FA
1
67.0
67.0
100
60.0
67.0
250
54.0
67.0
500
49.5
64.5
1,000
N/A
60.0
Requirements for PS Alien Next and PS AACR-F at selected frequencies
influences from adjacent channels are prevented and suppressed simultaneously via the double shielding of the S/FTP cables and the modular shielding of the connectivity. Alien crosstalk is attenuated by >100 dB (a factor of 100,000).
Frequency MHz 1
Minimum PS AACR-F db Class EA, F
Class FA
67.0
67.0
100
37.0
52.0
250
29.0
44.0
500
23.0
38.0
1,000
N/A
32.0
Requirements for PS Alien Next and PS AACR-F at selected frequencies
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 151
Alien crosstalk configuration with MegaLine®: 6 "culprits" and 1 "victim"
Coupling attenuation
MegaLine® test results
Coupling attenuation evaluates the overall EMC behaviour
All MegaLine® cabling systems with modular or individual
of a cable or individual link. The coupling attenuation consists
shielding have met the extended requirements for coupling
of the shielding attenuation and the asymmetrical attenuation
attenuation according to Class EA. ELine 1200® EC7 and
taken together and defines the degree of reduction of electrical
VarioKeystone® 4K7 even meet the requirements according
influences on a signal path.
to Class FA. It was possible to conclude the comprehensive assessments with the relevant certifications
If the coupling attenuation for Class EA is 10.0 dB better or for Class FA links is 25.0 dB better than in the table below, the values for the parameters Power Sum Alien NEXT (PS ANEXT) and Power Sum Alien ACR-F (PS AACR‑F) are complied with automatically as a result of the design, making it unnecessary to demonstrate them explicitly.
Class
Frequency MHz
Min. coupling attenuation dB
D, E, E A, F, FA
30 ≤ ƒ ≤ Note 2
80 – 20lg(ƒ) Coupling attenuation (Class E A) of VarioKeystone® RJ45
Note 1: Round down calculated values of greater than 40 db to 40 dB. Note 2: Coupling attenuation is measured to 1,000 MHz but the limit is determined by the upper frequency of the class being tested. Requirements for coupling attenuation for cabling classes D to FA
Coupling attenuation for Class EA and F: > 90 – 20 log(f), > 50 dB up to 100 MHz Coupling attenuation for Class FA: > 105 – 20 log(f), > 65 dB up to 100 MHz Due to the coupling mechanisms, this connection only applies for shielded cablings and not for unshielded ones.
www.leoni-infrastructure-datacom.com
Coupling attenuation (Class FA) of ELine 1200® EC7
152
GigaLine FO data cables ®
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 153
Page
GigaLine® FO data cables
The fiber
154
GigaLine® FO data cables
For LAN, WAN and SAN
157
GigaLine® fiber qualities
158
GigaLine® colour codes
159
GigaLine® type codes
160
Jacketing material for optical cables
161
Rodent protection for fiber optic cables
162
Pictograms
163
Handling and safety notices
164
GigaLine® FO data cables
165
o dc
GigaLine® indoor cable, duplex fig 8
KL-I-V(ZN)H 2 G/E
165
o dc i
GigaLine® indoor cable, duplex fig 0
KL-I-V(ZN)HH 2 G/E
166
o dc
GigaLine® indoor cable, mini breakout
KL-I-V(ZN)H n G/E
167
o dc i
GigaLine® breakout cable
KL-I-V(ZN)HH n G/E
168
o dc i
GigaLine® universal cable, mini breakout 800 N
KL-U-VQ(ZN)H n G/E
169
o dc i
GigaLine® universal cable, central 2,500 N
KL-U-DQ(ZN)BH 1xn G/E
170
o dc i
GigaLine® universal cable, stranded 4,000 N
KL-U-DQ(ZN)BH nxm G/E
171
o dc i
GigaLine® universal cable, central 2,500 N
KL-U-DQ(ZN)H(SR)H 1xn G/E
172
LEONI "fire secured" FO data cables
173
o dc i
GigaLine® "fire secured" universal cable, central with CI
KL-U-D(ZN)BH 1xn G/E Total system integrity at least 90 min
174
o dc i
GigaLine® "fire secured" universal cable, central with CI
KL-U-DQ(ZN)H(SR)H 1xn G/E Total system integrity at least 120 min
175
o i
GigaLine® outdoor cable, central 1,750 N
KL-A-DQ(ZN)B2Y 1xn G/E
176
o i
GigaLine® outdoor cable, stranded 4,000 N
KL-A-DQ(ZN)B2Y nxm G/E
177
o i
GigaLine® outdoor cable, central 1,750 N
KL-A-DQ(ZN)2Y(SR)2Y 1xn G/E
178
o i
GigaLine® outdoor cable, stranded 4,000 N
KL-A-DQ(ZN)2Y(SR)2Y nxm G/E
179
o i
GigaLine® outdoor cable, stranded with sheath 4,000 N
KL-A-DF (ZN)(L) 2y nxm G/E
180
o
Office cables
dc i
DataCenter cables Industrial cables
www.leoni-infrastructure-datacom.com
GigaLine® FO data cables
GigaLine® FO data cables
154
GigaLine® FO data cables The fiber
The steady increase in Internet and intranet traffic, multimedia applications and the establishment of central storage networks (SAN or Storage Area Networks) in companies have fundamentally changed the traffic and load distribution in networks. New media require new, more powerful passive network infrastructures. LEONI offers a future-proof cabling system with reserves well beyond those stipulated in the standards.
Comparison of requirements
Fiber category OM1 G62.5/125
Fiber category OM1 G62.5/125
for Standard and GigaGrade
at 850 nm
at 1,300 nm
LEONI OM1e GigaGrade G62.5/125 M
Standard OM1 Attenuation
LEONI OM1e GigaGrade G62.5/125 M
Standard OM1
3.5 dB/km
3.0 dB/km
1.5 dB/km
0.8 dB/km
200 MHz x km
250 MHz x km
500 MHz x km
800 MHz x km
Gigabit Ethernet segment length
275 m
500 m
550 m
1,000 m
10 Gigabit Ethernet segment length
32 m
65 m
300 m
450 m
Modal bandwidth
Comparison of requirements
Fiber category OM2 G50/125
Fiber category OM2 G50/125
for Standard and GigaGrade
at 850 nm
at 1,300 nm
Standard OM2 Attenuation
LEONI OM2 Standard GigaGrade G50/125
LEONI OM2e High Performance GigaGrade G50/125
Standard OM2
LEONI OM2 Standard GigaGrade G50/125
LEONI OM2e High Performance GigaGrade G50/125
3.5 dB/km
2.7 dB/km
2.5 dB/km
1.5 dB/km
0.8 dB/km
0.7 dB/km
500 MHz x km
500 MHz x km
600 MHz x km
500 MHz x km
500 MHz x km
1,200 MHz x km
Gigabit Ethernet segment length
550 m
550 m
750 m
550 m
550 m
2,000 m
10 Gigabit Ethernet segment length
82 m
82 m
150 m
300 m
300 m
700 m
Modal bandwidth
The right fiber
GigaGrade multimode fibers
LEONI offers a comprehensive range of optical fibers tailored to
GigaGrade G62.5/125 and GigaGrade G50/125 are the reliable
the various network requirements such as future-proof high-
and proven fibers for network technology in industrial
performance transmission in DataCenters, reliable office
applications and in office cabling in the categories OM1
networks and stable industrial networks.
and OM2.
The optimum multimode fiber for every application: GigaGrade
GigaGrade
OptiGrade 300
OptiGrade 550
OM1
OM2
OM3
OM4
LAN DataCenter LAN Office LAN Industry
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter
Comparison of requirements
Fiber category OM3 G50/125
Fiber category OM3 G50/125
for Standard and OptiGrade
at 850 nm
at 1,300 nm LEONI OM3 OptiGrade 300
Standard OM3 Attenuation
LEONI OM3 OptiGrade 300
Standard OM3
3.5 dB/km
2.5 dB/km
1.5 dB/km
0.7 dB/km
Modal bandwidth (overfilled launch)
1,500 MHz x km
1,500 MHz x km
500 MHz x km
500 MHz x km
EMB (effective modal bandwidth)
2,000 MHz x km
2,000 MHz x km
n.a.
n.a.
Gigabit Ethernet segment length
550 m
900 m
550 m
550 m
10 Gigabit Ethernet segment length
300 m
300 m
300 m
300 m
40/100 Gigabit Ethernet segment length
100 m
100 m
100 m
100 m
Comparison of requirements
Fiber category OM4 G50/125
Fiber category OM4 G50/125
for Standard and OptiGrade
at 850 nm
at 1,300 nm
Standard OM4
LEONI OM4 OptiGrade 550
Standard OM4
LEONI OM4 OptiGrade 550
2.5 dB/km
2.5 dB/km
1.5 dB/km
0.7 dB/km
Modal bandwidth (overfilled launch)
3,500 MHz x km
3,500 MHz x km
500 MHz x km
500 MHz x km
EMB (effective modal bandwidth)
4,700 MHz x km
4,700 MHz x km
n.a.
n.a.
Gigabit Ethernet segment length
550 m
1,000 m
550 m
550 m
10 Gigabit Ethernet segment length
550 m
550 m
300 m (LX4)
300 m (LX4)
40/100 Gigabit Ethernet segment length
150 m
150 m
150 m
150 m
Attenuation
OptiGrade 300 for 10 GbE networks
OptiGrade 550 future-proof without comprises
The sophisticated IT cabling in DataCenters and office buildings,
The OptiGrade 550 multimode fiber fulfils the requirements
with a 10 Gigabit Ethernet-compatible network, is based on the
of the OM4 standard for the serial transmission of 10 Gb/s with
laser-optimised OptiGrade 300 OM3 fiber.
an EMB of 4,700 MHz x km over 550 m. The fiber has been optimised for applications with 850 nm VCSEL and offers the possibility of use at higher transmission rates such as 40 Gb/s or 100 Gb/s going into the future. OptiGrade 550 is the first choice when it comes to speed and high data rates.
www.leoni-infrastructure-datacom.com
GigaLine® FO data cables
155
156
Fiber category OS2 E9/125 (G.652.D)
Comparison of requirements for Standard and j-LWP SMF+
Attenuation Attenuation at 1,383 nm
at 1,310 nm
at 1,550 nm
Standard OS2 IEC 60793-2-50 B6_a
LEONI OS2 j-LWP SMF+
Standard OS2 IEC-60793-2 50-B1.3
LEONI OS2 j-LWP SMF+
0.40 dB/km
0.36 dB/km
0.30 dB/km
0.23 dB/km
< 0.40 dB/km
0.36 dB/km
—
—
1 Gigabit Ethernet segment length
5,000 m
5,000 m
—
—
10 Gigabit Ethernet segment length
10,000 m
10,000 m
22,250 m
40,000 m
40 Gigabit Ethernet segment length
10,000 m
10,000 m
—
—
Fiber category E9/125 (G.657.A)
Comparison of requirements for Standard and j-LBL SMF
Attenuation Attenuation at 1,383 nm
at 1,310 nm
at 1,550 nm
Standard OS2 IEC 60793-2-50 B6_a
LEONI OS2 low bend j-LBL SMF
Standard OS2 IEC 60793-2-50 B6_a
LEONI OS2 low bend j-LBL SMF
0.40 dB/km
0.36 dB/km
0.30 dB/km
0.23 dB/km
< 0.40 dB/km
0.36 dB/km
—
—
1 Gigabit Ethernet segment length
5,000 m
5,000 m
—
—
10 Gigabit Ethernet segment length
10,000 m
10,000 m
22,250 m
40,000 m
40 Gigabit Ethernet segment length
10,000 m
10,000 m
—
—
100 Gigabit Ethernet segment length
10,000/40,000 m
10,000/40,000 m
—
—
j-LWP SMF+ proven for long links
j-LBL SMF flexible and compatible
The low-water-peak singlemode fiber, j-LWP SMF+ as per ITU-T
The j-LBL SMF as per ITU-T G657.A is a high-performance field-
G652.D or as per EN 50173 OS2, offers the best transmission
tested singlemode fiber for applications where the need for
performance across the entire wavelength range from 1,260
compatibility with installed G.652.D networks is linked with
nm to 1,625 nm. The fiber can be used in the wavelength
the requirement for improved bending characteristics for sturdy,
ranges from 1,360 nm to 1,480 nm due to the reliably stable, low
flexible and space-saving installations. The j-LBL SMF offers
attenuation at 1,383 nm. The j-LWP SMF+ is the preferred fiber
maximum transmission performance with minimum attenuation.
wherever maximum flexibility and long transmission lengths are
Due to the reliably and permanently low attenuation at
required. The use of WDM systems enables the full spectrum of
1,383 nm, it can be used in the wavelength range from
fiber capacity to be used – the prerequisite for flexible network
1,360 nm to 1,480 nm and the fiber is therefore also suitable
planning. The fiber is fully compatible with installed singlemode
for wavelength multiplexing (DWDM and CWDM).
networks and enables network solutions with maximum The fiber exhibits excellent splicing properties thanks to its
Attenuation [dB]
performance and flexibility. 30 25
first-rate uniformity and geometry. This means it is backwards
Bending sensitivity at different wavelengths 1,310 nm 1,550 nm 1,625 nm
compatible with already installed conventional singlemode fibers (to ITU-T G.652.A+B) and low-water-peak singlemode fibers (to ITU-T G.652 C+D).
20 Bending characteristics
15
Macro-bending losses, bending-induced attenuation
10 5 0
8 10 12 14 16 18 20 Bend diameter [mm]
Values
Unit
≤ 0.03
dB
10 bends, radius 15 mm
1,550 nm 1,652 nm
≤ 0.20
dB
1 bend, radius 10 mm
1,550 nm
≤ 0.30
dB
1,625 nm
≤ 1.00
dB
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 157
GigaLine® FO data cables
The use of fiber optic data cables is especially
The process used to manufacture the fibers has been optimised
recommended if…
in such a way that the profile of the multimode fiber is
■■
electromagnetic influences can occur
extremely precise and disturbances in the fiber core are virtually
■■
reliable potential isolation is required
eliminated. As differential mode delay does not occur under
■■
a wide transmission bandwidth is required
these circumstances, mode-conditioning patch cords are not
■■
low attenuation and therefore long transmission links
necessary. For more than ten years now, the standard versions
are required
of fiber optic cables with an improved gradient fiber G50/125
■■
crosstalk is not permitted
from the category "OM2e" have provided bandwidth-length
■■
sparking (for areas subject to explosion hazards) is not
products of 600 MHz x km in the first window (850 nm) and
permitted
1,200 MHz x km in the second window (1,300 nm) as well as
■■
low weight and small dimensions are an advantage
Gigabit Ethernet segment lengths of 750/2,000 m.
■■
increased security against interception is required GigaLine® fiber optic cables with OM3 and OM4 fibers are
The product range at a glance: ■■
the optimum transmission medium, whatever the future
Easy-to-assemble indoor cables with compact buffered fiber
might hold.
technology for the patch and horizontal areas ■■
Universal cables for the backbone area indoors and outdoors
Using the OM4 fibers with a laser bandwidth of 4,700 MHz x km
■■
Outdoor cables for LAN and WAN applications
in the first window enables segment lengths of up to 550 m
■■
A wide range of designs such as outdoor cables with
with 10 GbE, up to 300 m with 16 GB/s Fiberchannel or up to
– corrugated steel cladding
150 m with 40 and 100 GbE. This in turn enables cost-effective
– steel band or steel wire armour
realisation of 10 GbE in the backbone of a building in nearly
– additional lead covering as protection against chemicals
all cases.
Gigabit, 10, 40 and 100 Gigabit Ethernet – strictest
Singlemode fibers must be used over long distances. The
requirements for the quality of the fiber optic cabling.
singlemode fibers exceed the current requirements of the
The Ethernet protocol is the state of the art today in every
OS2 standard according to EN 50173-1 with attenuation of just
area of structured cabling. The corresponding standards for
0.36 dB/km at 1,310 nm and less than 0.22 db/km at 1,550 nm.
transmission rates from 1 Gigabit/s to 100 Gigabit/s are defined in IEEE 802.3ba.
This means that the wavelength ranges around 1,383 nm can also be used to increase the transmission capacity. The graph shows the steadily dropping attenuation curve from 1,300 nm
Comparison SMF G652B/G652D
to 1,625 nm for all singlemode fibers. These characteristics and
Attenuation [dB/km]
the PMD link design value of just 0.06 ps/ km guarantee large n ITU T 652B
0.8
n ITU T 652D
and WDM transmission systems. The use of high-quality optical fibers is the key to managing
0.6
future data volumes. GigaLine® fiber optic data cables
0.4
are the first step in careful planning and implementation of a passive network infrastructure.
0.2 0 1250 1300 1350 1400 1450 1500 1550 1600 1650 Wavelength [nm]
www.leoni-infrastructure-datacom.com
reserves for faster transmission rates over very long distances
GigaLine® FO data cables
for LAN, WAN and SAN
158
GigaLine® Fiber qualities
Fiber specifications
GigaGrade G62.5/125
GigaGrade G50/125
GigaGrade G50/125
OM1e
OM2
OM2e
OptiGrade IEC 11801/EN 50173 IEC 60793-2
A1b
OptiGrade 300 OptiGrade 550 G50/125 G50/125 OM3
OM4
j-LWP SMF+ E9...10/125
j-LWP SMF+ E9...10/125
OS2
OS2 low bend
A1a.1
A1a.1
A1a.2
A1a.3
B1.3
B6_a
G.651
G.651
G.651
G.651
G.652.D
G.657.A
max. 2.7 max. 0.8
max. 2.5 max. 0.7
max. 2.5 max. 0.7
max. 2.5 max. 0.7 max. 0.36 max. 0.40 max. 0.23 max. 0.23
max. 0.36 max. 0.40 max. 0.23 max. 0.23
at 1,310 nm
max. 3.5 ps/nm x km
max. 3.5 ps/nm x km
at 1,550 nm
max. 18 ps/nm x km
max. 18 ps/nm x km
ITU-T Attenuation coefficient dB/km at 850 nm dB/km at 1,300 nm
max. 3.0 max. 0.7
dB/km at 1,310 nm dB/km at 1,383 nm dB/km at 1,550 nm dB/km at 1,625 nm Bandwidth MHz x km at 850 nm
min. 250
min. 500
min. 600
min. 1,500
min. 3,500
MHz x km at 1,300 nm
min. 800
min. 500
min. 1,200
min. 500
min. 500
min. 2,000
min. 4,700
Laser bandwidth MHz x km at 850 nm Dispersion
Zero-dispersion wavelength Zero-dispersion slope
1,302 ≤ λ0 ≤ 1,322
1,302 ≤ λ0 ≤ 1,322
≤ 0.092 ps/nm² x km
≤ 0.092 ps/nm² x km
PMD Fiber
< 0.1 ps/ km
< 0.1 ps/ km
Link
< 0.06 ps/ km
< 0.06 ps/ km
5,000 m
5,000 m
10,000 m
10,000 m
40,000 m
40,000 m
10,000 m
10,000 m
0.12
0.12
Segment length with Gigabit Ethernet at 850 nm (1000 base SX)
500 m
550 m
750 m
900 m
1,000 m
at 1,300 nm (1000 base LX)
1,000 m
550 m
2,000 m
550 m
550 m
Segment length with 10 Gigabit Ethernet at 850 nm (10G base-SR/SW)
65 m
82 m
150 m
300 m
550 m
at 1,300 nm (10G base-LX4)
450 m
300 m
700 m
300 m
300 m
at 1,550 nm (10G base-ER/EW) Segment length with 40/100 Gigabit Ethernet at 850 nm 40/100 GBASE-SR4/SR10
100 m
150 m
at 1,310 nm 40/100 GBASE-LR4 Numerical aperture Nominal value
0.275
0.20
0.20
0.20
0.20
at 850 nm
1.497
1.483
1.483
1.483
1.483
at 1,300 nm
1.493
1.478
1.478
1.478
1.478
Refractive index (nominal value)
at 1,310 nm
1.467
1.467
at 1,550 nm
1.467
1.467
Test load 100 kpsi ≥ 8.8 N
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 159
Wires (with stranded loose tubes)
Counting wire
Red
Counting direction wire
White
Other wires
Green for G50/125
Fibers (in loose tubes) IEC 60304
Fiber no.
Fiber no.
Colour
Colour
1
Blue
1
Red
2
Orange
2
Green
3
Green
3
Blue
Yellow for E9…10/125
4
Brown
4
Yellow
Natural colours
5
Grey
5
White Grey
Blue for G62.5/125
Dummy elements
Mini breakout cable EIA/TIA 598C
The wires are consecutively counted, starting with the wire closest to the counting element. The dummy elements are not counted.
6
White
6
7
Red
7
Brown
8
Black
8
Violet
9
Yellow
9
Turquoise Black
10
www.leoni-infrastructure-datacom.com
Violet
10
11
Pink
11
Orange
12
Turquoise
12
Pink
13
Red/black
14
Green/black
15
Blue/black
16
Yellow/black
17
White/black
18
Grey/black
19
Brown/black
20
Violet/black
21
Turquoise/black
22
Natural/black
23
Orange/black
24
Pink/black
GigaLine® FO data cables
GigaLine® Colour codes
160
GigaLine® Type codes for easy assignment of the construction elements in fiber optic cables
GigaLine® 1 2 3 4 5 6 7 8 9 Cable type Communication cable
KL
Field of application Indoor cable
I
Universal cable
U
Outdoor cable
A
Breakout outdoor cable
AT
Buffered fiber Tight buffered loose tube
V
Gel-filled loose tube
D
Constructional composition Swelling material, dry, longitudinally watertight
Q
Water-blocking gel-filled, longitudinally watertight
F
Non-metallic strain relief
(ZN)
Steel strain relief
(ZS)
Armour
B
Corrugated steel tape
SR
Cable sheath PE
Polyethylene sheath
2Y
Al + PE
PE coated aluminium sheath
(L)2Y
FRNC
Halogen-free/flame-retardant sheath
H
PVC
Polyvinyl chloride sheath
Y
PA
Polyamide sheath
4Y
PUR
Polyurethane sheath
11Y
Fiber number and fiber bundling Number of fibers
n
Number of loose tubes x number of fibers per tube
nxm
Miscellaneous n Field diameter/sheath diameter in…
E9/125
n Core diameter/sheath diameter in…
G50/125 or G62.5/125
Wavelength 850 nm
B
1,300/1,310 nm
F
1,550 nm
H
Bandwidth/dispersion coefficient in MHz · km with multimode fibers, dispersion parameters in ps/nm · km with singlemode fibers
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 161
Jacketing material for optical cables
Balancing application and fire prevention criteria The sheath around the cable protects the optical fiber(s) from
However, it is often extremely difficult to meet all the
the effects of mechanical, thermal and chemical action as
requirements using just one sheath material. To best satisfy
well as the ingress of moisture. In the event of a fire, however,
the prevailing local operating conditions, LEONI offers a choice
the cable sheath should prevent a fire from spreading and stop
of different materials.
toxic and corrosive gases from being produced. Please contact us if the criteria for your particular application The use of halogen-free, flame-retardant materials is advisable
are not met by the cable constructions in this catalogue.
in order to protect equipment and buildings but above all
Additional requirements can often be met through customised
to protect people. In harsh environments, PUR and PVC,
measures when making the sheath (e.g. aluminium tape or
in particular, are used owing to their high resistance to oils and
special mixtures of sheaths).
material for outdoor applications.
Cable sheath material Material characteristics
FRNC
PUR
PVC
PE
Resistance to aging
+
+
+
+
Halogen-free
+
+
––
+
Flame retardancy
+
●
+
– –/●
Elasticity
–
+
●
–
Abrasion resistance
–
++
+
+/–
Low smoke gas generation
++
●
–
– –/●
Low emission of corrosive gases
++
●
––
+/●
Low smoke gas toxicity
++
●
––
+/●
No toxicological risk
++
●
–
+/●
General resistance to
FRNC
PUR
PVC
PE
UV light
1)
1)
1)
1)
Water absorption
–
–
+
+
Gas diffusion
–
2)
–
●
Fuels
–
+
+/–
+
Petroleum/lubricants
–
++
●
+
Organic solvents
–
+ 3)
–
+ 4)
Alcohol
–
–
+
+
Oxidants
–
–
+
–
Acids
+
––
+
++
Alkaline solutions
+
––
+
+
Saline solutions
+
–
+
+
www.leoni-infrastructure-datacom.com
++ excellent + good ● depends on recipe – weak – – inadequate
1) UV resistance can be increased by adding black colour pigments or UV stabilisers 2) Permeation depends on the type of gas, e.g. Ar, CH4, N2, O2 low gas permeation, CO2, H2, He higher gas permeation 3) Low swelling in saturated hydrocarbons; significant swelling in aromatic hydrocarbons. Aliphatic esters cause swelling, highly polar organic solvents dissolve under the effect of extreme swelling 4) Swelling in aliphatic and aromatic hydrocarbons and in chlorinated hydrocarbons
GigaLine® FO data cables
their abrasion resistance. PE is also commonly used as a sheath
162
Rodent protection for fiber optic cables
Fiber optic cables are relatively thin and therefore very susceptible to rodent damage. Depending on the application it is important that fiber optic cables can offer protection against this type of damage. There are no national or indeed international standards or test specifications covering the corresponding requirement for rodent protection.
The following construction has been customary in the market in
Metal armouring must be recommended as rodent protection
Europe (particularly in Germany, Austria and Switzerland) since
for all applications where rodent damage is to be expected. This
the early 1990s:
is the case, for example, with installation in shafts or conduits
For outdoor cables, the usual aramid yarns for strain relief are
with a correspondingly large diameter, e.g. along railway lines
replaced with glass rovings. These glass yarns shatter and get
or motorways.
into the mouth and throat of the rodents. The animals associate gnawing on cables with pain and usually stop.
The following types of metal armouring are available: ■■
Corrugated steel cladding
The general rule is:
The most common metal armouring is the 0.155 mm thick
The more glass rovings, the greater the protection for
corrugated steel cladding due to its very good flexibility.
the cable.
■■
Steel wire armour The steel wire armour made from wires with a thickness of up to 1.25 mm is very robust.
The overall diameter should also be as large as possible. Constructions with stranded loose tubes give even less
■■
Steel band
favourable leverage in combination with the larger core
Steel band sheathing consists of two overlapping layers
diameter. The cable then acts like a gag bit. Before the rodent
of steel band that are wound around the cable.
reaches the glass rovings, however, it first has to gnaw through the outer sheath. Constructions with an additional polyamide
In the case of cables with two sheaths with sheathing between
sheath (thickness 0.5 mm) have also proven themselves here
them, the ingress of water into the cable core is also prevented
as polyamide is very hard and smooth.
provided the internal sheath is not damaged.
This combination of plastic, glass and moisture-absorbing
Despite all precautions, however, damage to the outer
swelling material has to be gnawed through before rodent
sheath can never be fully ruled out.
reaches the loose tubes containing the internal optical fibers.
www.leoni-infrastructure-datacom.com
Office Office
Industry
DataCenter 163
Pictograms
Flame-retardant and halogen-free sheath The outer sheath of the cable is self-extinguishing and does not propagate fire. The halogen-free sheath material forms neither toxic nor corrosive combustion gases in the event of fire.
Rodent proof The cable core is protected against damage by rodents with glass rovings. Note: Despite all the precautions, damage to the outer sheath can never be fully ruled out. Rodent proof The cable core is more heavily protected against damage by rodents with two sheaths and metal armouring. Note: Despite all the precautions, damage to the outer sheath can never be fully ruled out. Resistance to UV rays The cable outer sheath is resistant to UV rays.
Longitudinal watertightness Water in the cable core cannot spread out in longitudinal direction.
Lateral watertightness Lateral diffusion of water into the cable core is prevented.
www.leoni-infrastructure-datacom.com
GigaLine® FO data cables
Chemical resistance Generally good resistance to oil, petrol, acids and alkaline solutions.
164
Handling and safety notices when using optical cables
Please note the following when installing optical fibers: ■■
Valid installation regulations for optical fibers
■■
Valid industrial safety guidelines for handling optical fibers
■■
VDE regulations (DIN EN 50174 Parts 1 to 3, Cabling installation)
The following regulations also apply: ■■
The drums must always be stored and transported standing on their flanges
■■
Immersion with water must be avoided – the fibers and connectors must not come into contact with water
■■
Do not remove the protective packaging from the cable ends during installation
All cable ends must be protected from the ingress of moisture before, during and after installation
■■
Please note the limit values specified in the respective data sheet
■■
■■
Optical fibers must be unwound from the coil or ring without torsion so that no kinks or twists can occur
■■
Install optical cables with extreme care. Please make sure
■■
Do not go below the permitted bending radius (see data sheet)
that the fibers are neither overstretched nor compressed –
■■
Avoid soiling and mechanical loading of the assembled
in addition to immediate damage, this also poses the threat
connectors
of problems with the long-term behaviour
■■
Do not exceed the maximum tensile load of the cable in axial
■■
these have no sharp edges and that kinks are avoided
direction during and after installation (use suitable aids) ■■
The maximum tensile load only applies in conjunction with
■■
adhesion with the strain relief elements ■■
warranty claims may arise ■■
Cable runs must be selected so as to avoid mechanical loads Mechanical stresses, for example caused by movement, must
Body and eye protection must be worn when handling bare fibers from glass optical fibers, including if the cable
as far as possible and also minimise future loads ■■
The attenuation of each cable must be checked immediately after installation using a suitable calibrated meter, otherwise
Installation is not permitted if the ambient temperature is exceeded or gone below (specific value in the data sheet)
■■
When installing in protective conduits, please make sure that
is damaged ■■
Please note all regulations relating to eye safety
be prevented, even during provisional installation ■■
Compression of the outer sheath, for example by cable ties, must be avoided when securing the cables
■■
After installation: carefully free the cable ends from the packaging/pull tool
www.leoni-infrastructure-datacom.com
Office
DataCenter
Industry
165
GigaLine® Indoor cable, duplex fig 8 Type KL-I-V(ZN)H 2 G/E
Outer sheath Strain relief elements
Description
Thermal characteristics
Connection cable and patch cord for structured cabling acc.
Transport/storage
–25 °C up to +70 °C
to ISO/IEC 11801 and EN 50173 (2nd edition).
Installation
–5 °C up to +50 °C
Operating temperature
–10 °C up to +70 °C
GigaLine® FO data cables
Semi-tight buffered fiber
In keeping with the fiber type ideal for all applications from Classes OF 300 to OF 10000. Suitable for direct connector
Mechanical characteristics
assembly.
Min. bending radius
Installation in dry areas, in cable ducts, on cable trays
Max. crush strength
or in conduits.
static
30 mm
dynamic
60 mm
long-term 600 N/dm short-term 1000 N/dm
Construction
Fire performance
Two single cables (2.8 mm with 900 µm semi-ight buffered
Smoke density
IEC 61034
loose tubes) with strain relief in figure 8 sheath with separator
Halogen free
IEC 60754-1
Strain relief
Non-metallic (aramid yarns)
Flame retardancy
IEC 60332-1-2, IEC 60332-3-24
Cable sheath
Halogen-free, flame-retardant compound
Sheath colour
OS2
● Yellow
● Orange OM1e/OM2e ● Aqua OM3 ● Heather violet OM4
Fiber number
Buffered Overall fiber diam. Weight type approx. approx. kg/km
Max. strain relief
Fire load approx.
N
MJ/m kWh/m
Order no. OM1e G62.5/125
OM2e G50/125
OM3 G50/125
OM4 G50/125
OS2 E9…10/125
µ
mm
2
900
2.8x5.7
15.8
600
0.36
0.10
LKD 8DB7 0003 0000 LKD 8DA2 0003 0000 LKD 8DA5 2000 0000 LKD 8DA7 2000 0000 LKD 8DC7 2001 0000
2
600
1.8x3.7
7
400
0.14
0.04
LKD 8XB7 0013 0000
www.leoni-infrastructure-datacom.com
LKD 8XA2 0013 0000
LKD 8XA5 2013 0000
LKD 8XA7 0013 0000
LKD 8XC7 0013 0000
166
GigaLine® Indoor cable, duplex fig 0 Type KL-I-V(ZN)HH 2 G/E
Outer sheath Strain relief Semi-tight buffered fiber Subcable sheath
Description
Thermal characteristics
Connection cable and patch cord for structured cabling acc.
Transport/storage
–25 °C up to +70 °C
to ISO/IEC 11801 and EN 50173 (2nd edition).
Installation
–5 °C up to +50 °C
Operating temperature
–10 °C up to +70 °C
In keeping with the fiber type ideal for all applications from Classes OF 300 to OF 10000. Suitable for direct connector
Mechanical characteristics
assembly.
Min. bending radius
Installation in dry areas, in cable ducts, on cable trays or in conduits.
static
35 mm
dynamic
65 mm
for single elements 30 mm Max. tensile force
long-term
600 N
Max. crush strength
long-term
500 N/dm
short-term
750 N/dm
Construction Two single cables (2.1 mm with 900 µm semi-tight buffered fibers) with strain relief running parallel under one sheath
Fire performance
Strain relief
Non-metallic (aramid yarns)
Smoke density
IEC 61034
Cable sheath
Halogen-free, flame-retardant compound
Halogen free
IEC 60754-1
Sheath colour
OS2
Flame retardancy
IEC 60332-1-2, IEC 60332-3-24
● Yellow
● Orange OM1e/OM2e ● Aqua OM3
Further characteristics:
● Heather violet OM4
Cable bending
Fiber number
2
Overall diam. approx.
Weight approx.
Max. strain relief
Fire load approx.
mm
kg/km
N
MJ/m kWh/m
3.1x5.2
18
600
0.63
0.18
IEC 60794-1-2 E11
Order no. OM1e G62.5/125
OM2e G50/125
OM3 G50/125
OM4 G50/125
OS2 E9…10/125
LKD 8DB7 0011 0000 LKD 8DA2 0011 0000 LKD 8DA5 2001 0000 LKD 8DA7 2005 0000 LKD 8DC7 0010 0000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 167
GigaLine® Indoor cable, mini breakout Type KL-I-V(ZN)H n G/E
Outer sheath Strain relief
Description
Thermal characteristics
Campus/backbone cabling, suitable for direct connector
Transport/storage
–25 °C up to +70 °C
assembly. Connection cable and patch cord for structured
Installation
–5 °C up to +50 °C
cabling acc. to ISO/IEC 11801 and EN 50173 (2nd edition).
Operating temperature
–10 °C up to +70 °C
In keeping with the fiber type ideal for all applications from Classes OF 300 to OF 10000.
Mechanical characteristics Min. bending radius
static
10 x overall diameter
dynamic
15 x overall diameter
Construction
for single
Up to 12 semi-tight buffered fibers (900 µm) stranded under
elements
30 mm
Max. tensile force
long-term
600 N
Max. crush strength
long-term
500 N/dm
short-term
1000 N/dm
one outer sheath Strain relief
Non-metallic (aramid yarns)
Cable sheath
Halogen-free, flame-retardant compound
Sheath colour
OS2
● Yellow
● Orange OM1e/OM2e
Fire performance
● Aqua OM3 ● Heather violet OM4
Smoke density
IEC 61034
Halogen free
IEC 60754-1
Flame retardancy
IEC 60332-1-2, IEC 60332-3-24
Further characteristics:
Cable bending
Fiber number
Overall diam. approx.
Weight approx.
Max. strain relief
Fire load approx.
mm
kg/km
N
MJ/m kWh/m
IEC 60794-1-2 E11
Order no. OM1e G62.5/125
OM2e G50/125
OM3 G50/125
OM4 G50/125
OS2e E9…10/125
2
4.2
14
800
0.45
0.13
LKD 8MB7 0011 0000 LKD 8MA2 0011 0000 LKD 8MA5 2011 0000 LKD 8MA7 0011 0000 LKD 8MC7 0011 0000
4
4.8
21
800
0.47
0.13
LKD 8MB7 0012 0000 LKD 8MA2 0012 0000 LKD 8MA5 2012 0000 LKD 8MA7 0012 0000 LKD 8MC7 0012 0000
6
5.9
25
800
0.50
0.14
LKD 8MB7 0013 0000 LKD 8MA2 0013 0000 LKD 8MA5 2013 0000 LKD 8MA7 0013 0000 LKD 8MC7 0013 0000 LKD 8MB7 0014 0000 LKD 8MA2 0014 0000 LKD 8MA5 2014 0000 LKD 8MA7 0014 0000 LKD 8MC7 0014 0000
8
6.1
30
800
0.52
0.14
10
7.0
38
800
0.53
0.14
LKD 8MB7 0015 0000 LKD 8MA2 0015 0000 LKD 8MA5 2015 0000 LKD 8MA7 0015 0000 LKD 8MC7 0015 0000
12
7.0
38
800
0.55
0.15
LKD 8MB7 0016 0000 LKD 8MA2 0016 0000 LKD 8MA5 2016 0000 LKD 8MA7 0016 0000 LKD 8MC7 0016 0000
www.leoni-infrastructure-datacom.com
GigaLine® FO data cables
Tight buffered fiber
168
GigaLine® Breakout cable Type KL-I-V(ZN)HH n G/E
Outer sheath Strain relief Central element Semi-tight buffered fiber Subcable sheath
Description
Thermal characteristics
Connection cable and patch cord for structured cabling acc.
Transport/storage
–25 °C up to +70 °C
to ISO/IEC 11801 and EN 50173 (2nd edition).
Installation
–5 °C up to +50 °C
Operating temperature
–10 °C up to +70 °C
In keeping with the fiber type ideal for all applications from Classes OF 300 to OF 10000. Suitable for direct connector
Mechanical characteristics
assembly.
Min. bending radius
static
15 x overall diameter
dynamic
20 x overall diameter
Installation in dry areas, in cable ducts, on cable trays
for single
or in conduits.
elements
30 mm
long-term
1000 N/dm
short-term
1500 N/dm
Max. crush strength Construction Up to 12 single cables with strain relief as breakout elements (2.1 mm with 900 µm semi-tight buffered fibers) stranded under
Fire performance
one outer sheath
Smoke density
IEC 61034
Ripcord under the outer sheath
Halogen free
IEC 60754-1
Strain relief
Non-metallic (aramid yarns)
Flame retardancy
IEC 60332-1-2, IEC 60332-3-24
Cable sheath
Halogen-free, flame-retardant compound
Sheath colour
OS2
● Yellow
Further characteristics:
● Orange OM1e/OM2e
Cable bending
IEC 60794-1-2 E11
● Aqua OM3 ● Heather violet OM4
Overall diam. Fiber approx. number mm 2
7.0
Weight approx.
Max. strain relief
Fire load approx.
kg/km
N
MJ/m kWh/m
40
800
1.10
0.30
Order no. OM1e G62.5/125
OM2e G50/125
OM3 G50/125
OM4 G50/125
OS2 E9...10/125
LKD 8BB7 0011 0000 LKD 8BA2 0011 0000 LKD 8BA5 2011 0000 LKD 8BA7 0011 0000 LKD 8BC7 0011 0000
4
7.0
45
800
1.10
0.30
LKD 8BB7 0012 0000 LKD 8BA2 0012 0000 LKD 8BA5 2012 0000 LKD 8BA7 0012 0000 LKD 8BC7 0012 0000
6
8.2
65
1000
1.18
0.32
LKD 8BB7 0013 0000 LKD 8BA2 0013 0000 LKD 8BA5 2013 0000 LKD 8BA7 0013 0000 LKD 8BC7 0013 0000
8
9.6
95
1000
1.31
0.36
LKD 8BB7 0014 0000 LKD 8BA2 0014 0000 LKD 8BA5 2014 0000 LKD 8BA7 0014 0000 LKD 8BC7 0014 0000
10
11.0
135
1000
1.42
0.39
LKD 8BB7 0015 0000 LKD 8BA2 0015 0000 LKD 8BA5 2015 0000 LKD 8BA7 0015 0000 LKD 8BC7 0015 0000
12
12.5
155
1000
1.57
0.44
LKD 8BB7 0016 0000 LKD 8BA2 0016 0000 LKD 8BA5 2016 0000 LKD 8BA7 0016 0000 LKD 8BC7 0016 0000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 169
GigaLine® Universal cable, mini breakout 800 N Type KL-U-VQ(ZN)H n G/E
Outer sheath Strain relief
Description
Thermal characteristics
Campus/backbone cabling, suitable for direct connector
Transport/storage
–25 °C up to +70 °C
assembly. Connection cable and patch cord for structured
Installation
–5 °C up to +50 °C
cabling acc. to ISO/IEC 11801 and EN 50173 (2nd edition).
Operating temperature
–25 °C up to +60 °C
In keeping with the fiber type ideal for all applications from Classes OF 300 to OF 10000. House connections possible without
Mechanical characteristics
additional interconnection points (splices).
Min. bending radius
static
10 x overall diameter
dynamic
15 x overall diameter
Installation indoors and outdoors in dry conduits, on covered
for single
cable trays or in cable ducts. Mechanical pulling in with winches
elements
30 mm
long-term
300 N/dm
short-term
500 N/dm
is only permitted in conjunction with force measuring devices
Max. crush strength
with a logging feature. Construction
Fire performance
Up to 24 tight buffered fibers (900 µm) stranded under
Smoke density
IEC 61034
one outer sheath
Halogen free
IEC 60754-1
Flame retardancy
IEC 60332-1-2, IEC 60332-3-24
Buffered fiber colour code acc. to EIA/TIA598C Strain relief
Non-metallic (aramid yarns)
Cable sheath
Halogen-free, flame-retardant compound
Further characteristics:
Sheath colour
● Yellow
Longitudinal watertightness IEC 60794-1-2 F5 Cable bending
Fiber number
Overall diam. approx.
Weight approx.
Max. strain relief
Fire load approx.
mm
kg/km
N
MJ/m kWh/m
IEC 60794-1-2 E11
Order no. OM1e G62.5/125
OM2e G50/125
OM3 G50/125
OM4 G50/125
OS2 E9...10/125
6
5.9
25
800
0.50
0.14
LKD 8NB7 1003 0000 LKD 8NA2 1003 0000 LKD 8NA5 1003 0000 LKD 8NA7 1003 0000 LKD 8NC7 1003 0000
12
7.0
38
800
0.55
0.15
LKD 8NB7 1006 0000 LKD 8NA2 1006 0000 LKD 8NA5 1006 0000 LKD 8NA7 1006 0000 LKD 8NC7 1006 0000
24
9.4
72
800
0.92
0.25
LKD 8NB7 1009 0000 LKD 8NA2 1009 0000 LKD 8NA5 1009 0000 LKD 8NA7 1009 0000 LKD 8NC7 1009 0000
www.leoni-infrastructure-datacom.com
GigaLine® FO data cables
Tight buffered fiber
170
GigaLine® Universal cable, central 2500 N Type KL-U-DQ(ZN)BH 1xn G/E
Outer sheath Strain relief
Loose tube, gel-filled
Description
Thermal characteristics
Installation cable, suitable for campus/backbone cabling and
Transport/storage
–25 °C up to +70 °C
for structured cabling acc. to ISO/IEC 11801 and EN 50173
Installation
–5 °C up to +50 °C
(2nd edition). Ideal for all applications from Classes OF 300, OF 500,
Operating temperature
–25 °C up to +60 °C
OF 2000, OF 5000 and OF 10000. Suitable for installation indoors in applications involving increased mechanical requirements
Mechanical characteristics
as well as risk of rodent damage. Suitable for splicing. House
Min. bending radius
connections possible without additional interconnection points (splices). Installation indoors and outdoors in conduits, on covered
Max. crush strength
cable trays, in cable ducts or directly in the ground (in a bed of
static
15 x overall diameter
dynamic
20 x overall diameter
long-term
2000 N/dm
short-term
3500 N/dm
sand). Mechanical pulling in with winches is only permitted in conjunction with force measuring devices with a logging feature.
Fire performance Smoke density
IEC 61034
Construction
Halogen free
IEC 60754-1
Central filled loose tube with max. 24 fibers, up to 12 fibers
Flame retardancy
IEC 60332-1-2, IEC 60332-3-24
diameter 2.9 mm, up to 24 fibers diameter 3.5 mm Fiber colour code acc. to IEC 60304
Further characteristics:
Loose tube colour: Yellow (E9/125), green (G50/125), blue (G62.5/125)
Longitudinal watertightness IEC 60794-1-2 F5
Strain relief
Non-metallic (glass rovings)
Impact resistance
IEC 60794-1-2 E4
Cable sheath
Halogen-free, flame-retardant compound
Cable bending
IEC 60794-1-2 E11
Sheath colour
● Black
Resistance to microbes
Fiber number
Overall Max. diam. Weight strain approx. approx. relief mm
kg/km
N
Fire load approx. MJ/m kWh/m
Order no. OM1e G62.5/125
OM2e G50/125
OM3 G50/125
OM4 G50/125
OS2 E9…10/125
1x2
7.6
65
2500
0.95
0.26
LKD 8UB7 00M1 0000 LKD 8UA2 00M1 0000 LKD 8UA500M1 0000 LKD 8UA7 00M1 0000 LKD 8UC7 00M1 0000
1x4
7.6
65
2500
0.95
0.26
LKD 8UB7 00M2 0000 LKD 8UA2 00M2 0000 LKD 8UA500M2 0000 LKD 8UA7 00M2 0000 LKD 8UC7 00M2 0000
1x6
7.6
65
2500
0.95
0.26
LKD 8UB7 00M3 0000 LKD 8UA2 00M3 0000 LKD 8UA500M3 0000 LKD 8UA7 00M3 0000 LKD 8UC7 00M3 0000 LKD 8UB7 00M4 0000 LKD 8UA2 00M4 0000 LKD 8UA500M4 0000 LKD 8UA7 00M4 0000 LKD 8UC7 00M4 0000
1x8
7.6
65
2500
0.95
0.26
1x10
7.6
65
2500
0.95
0.26
LKD 8UB7 00M5 0000 LKD 8UA2 00M5 0000 LKD 8UA500M5 0000 LKD 8UA7 00M5 0000 LKD 8UC7 00M5 0000
1x12
7.6
65
2500
0.95
0.26
LKD 8UB7 00M6 0000 LKD 8UA2 00M6 0000 LKD 8UA500M6 0000 LKD 8UA7 00M6 0000 LKD 8UC7 00M6 0000
1x16
8.2
73
2500
1.06
0.30
LKD 8UB7 00M7 0000 LKD 8UA2 00M7 0000 LKD 8UA500M7 0000 LKD 8UA7 00M7 0000 LKD 8UC7 00M7 0000
1x20
8.2
73
2500
1.06
0.30
LKD 8UB7 00M8 0000 LKD 8UA2 00M8 0000 LKD 8UA500M8 0000 LKD 8UA7 00M8 0000 LKD 8UC7 00M8 0000
1x24
8.2
73
2500
1.06
0.30
LKD 8UB7 00M9 0000 LKD 8UA2 00M9 0000 LKD 8UA500M9 0000 LKD 8UA7 00M9 0000 LKD 8UC7 00M9 0000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 171
GigaLine® Universal cable, stranded 4000 N Type KL-U-DQ(ZN)BH nxm G/E
Outer sheath Strain relief
Loose tube, gel-filled GFR central strength
Description
Thermal characteristics
Installation cable, suitable for campus/backbone cabling
Transport/storage
–25 °C up to +70 °C
and for structured cabling acc. to ISO/IEC 11801 and EN 50173
Installation
–5 °C up to +50 °C
(2nd edition). Ideal for applications from Classes OF 300 to
Operating temperature
–25 °C up to +60 °C
OF 10000. Suitable for installation in applications involving increased mechanical requirements as well as risk of rodent
Mechanical characteristics
damage. Suitable for splicing. House connections possible without
Min. bending radius
additional interconnection points (splices). Installation indoors and outdoors in conduits, on covered
Max. crush strength
cable trays, in cable ducts or directly in the ground (in a bed of
static
15 x overall diameter
dynamic
20 x overall diameter
long-term
3000 N/dm
short-term
4000 N/dm
sand). Mechanical pulling in with winches is only permitted in conjunction with force measuring devices with a logging feature.
Fire performance Smoke density
IEC 61034
Construction
Halogen free
IEC 60754-1
Stranded filled loose tube with up to 12 fibers
Flame retardancy
IEC 60332-1-2, IEC 60332-3-24
Fiber colour code acc. to IEC 60304 Loose tube colour: Counting wire red, counting direction wire
Further characteristics:
white, yellow (E9/125), green (G50/125), blue (G62.5/125)
Longitudinal watertightness IEC 60794-1-2 F5
Twisting
Loose tubes and if applicable dummy elements
Impact resistance
IEC 60794-1-2 E4
around a central strength member
Cable bending
IEC 60794-1-2 E11
Cable core
Central GFR strength member
Resistance to microbes
Stranded filled loose tubes
Strain relief
Non-metallic (glass rovings)
Cable sheath
Halogen-free, flame-retardant compound
Sheath colour
● Black
Overall diam. Fiber approx. number mm
Weight approx.
Max. strain relief
Fire load approx.
kg/km
N
MJ/m kWh/m
141
4000
2x12
11.4
Order no. OM1e G62.5/125
OM2e G50/125
OM3 G50/125
OM4 G50/125
OS2 E9...10/125
2.95
0.82
LKD 8UB7 1K06 0000 LKD 8UA2 1K06 0000 LKD 8UA5 1K06 0000 LKD 8UA7 1K06 0000 LKD 8UC7 1K06 0000 LKD 8UB7 1K08 0000 LKD 8UA2 1K08 0000 LKD 8UA5 1K08 0000 LKD 8UA7 1K08 0000 LKD 8UC7 1K08 0000
4x12
11.4
141
4000
2.95
0.82
8x12
13.7
200
4000
3.24
0.90
LKD 8UB7 1K11 0000 LKD 8UA2 1K11 0000 LKD 8UA5 1K11 0000 LKD 8UA7 1K11 0000 LKD 8UC7 1K11 0000
12x12
17
300
4000
4.32
1.20
LKD 8UB7 1K13 0000 LKD 8UA2 1K13 0000 LKD 8UA5 1K13 0000 LKD 8UA7 1K13 0000 LKD 8UC7 1K13 0000
Other types on request
www.leoni-infrastructure-datacom.com
GigaLine® FO data cables
member
172
GigaLine® Universal cable, central 2500 N Type KL-U-DQ(ZN)H(SR)H 1xn G/E
Strain relief Outer sheath Corrugated steel cladding Loose tube, gel-filled
Description
Thermal characteristics
Installation cable, suitable for campus/backbone cabling and
Transport/storage
–25 °C up to +70 °C
for structured cabling acc. to ISO/IEC 11801 and EN 50173
Installation
–5 °C up to +50 °C
(2nd edition). Ideal for all applications from Classes OF 300, OF 500,
Operating temperature
–25 °C up to +60 °C
OF 2000, OF 5000 and OF 10000. Suitable for installation in applications involving increased mechanical requirements as well
Mechanical characteristics
as risk of rodent damage. Suitable for splicing. House connections
Min. bending radius
possible without additional interconnection points (splices). Installation indoors and outdoors in dry conduits, on covered
Max. crush strength
cable trays, in cable ducts or directly in the ground. Mechanical
static
15 x overall diameter
dynamic
20 x overall diameter
long-term
2500 N/dm
short-term
3500 N/dm
pulling in with winches is only permitted in conjunction with force measuring devices with a logging feature.
Fire performance Smoke density
IEC 61034
Construction
Halogen free
IEC 60754-1
Central filled loose tube with max. 24 fibers, up to 12 fibers
Flame retardancy
IEC 60332-1-2, IEC 60332-3-24
diameter 2.9 mm, up to 24 fibers diameter 3.5 mm Fiber colour code acc. to IEC 60304
Further characteristics:
Loose tube colour: Yellow (E9/125), green (G50/125), blue (G62.5/125)
Longitudinal watertightness IEC 60794-1-2 F5
Strain relief
Non-metallic (glass rovings)
Impact resistance
IEC 60794-1-2 E4
Inner sheath
Halogen-free, flame-retardant compound
Cable bending
IEC 60794-1-2 E11
Inner sheath colour ● Black Armouring
Resistance to microbes
Corrugated steel cladding
Cable sheath
Halogen-free, flame-retardant compound
Sheath colour
● Black
Overall diam. Fiber approx. number mm
Weight approx.
Max. strain relief
Fire load approx.
kg/km
N
MJ/m kWh/m
Order no. OM1e G62.5/125
OM2e G50/125
OM3 G50/125
OM4 G50/125
OS2 E9…10/125
1x2
11.6
171
2500
1.93
0.53
LKD 8UB7 99K1 0000 LKD 8UA2 99K1 0000 LKD 8UA5 99K1 0000 LKD 8UA7 99K1 0000 LKD 8UC7 99K1 0000
1x4
11.6
171
2500
1.93
0.53
LKD 8UB7 99K2 0000 LKD 8UA2 99K2 0000 LKD 8UA5 99K2 0000 LKD 8UA7 99K2 0000 LKD 8UC7 99K2 0000
1x6
11.6
171
2500
1.93
0.53
LKD 8UB7 99K3 0000 LKD 8UA2 99K3 0000 LKD 8UA5 99K3 0000 LKD 8UA7 99K3 0000 LKD 8UC7 99K3 0000
1x8
11.6
171
2500
1.93
0.53
LKD 8UB7 99K4 0000 LKD 8UA2 99K4 0000 LKD 8UA5 99K4 0000 LKD 8UA7 99K4 0000 LKD 8UC7 99K4 0000
1x10
11.6
171
2500
1.93
0.53
LKD 8UB7 99K5 0000 LKD 8UA2 99K5 0000 LKD 8UA5 99K5 0000 LKD 8UA7 99K5 0000 LKD 8UC7 99K5 0000
1x12
11.6
171
2500
1.93
0.53
LKD 8UB7 99K6 0000 LKD 8UA2 99K6 0000 LKD 8UA5 99K6 0000 LKD 8UA7 99K6 0000 LKD 8UC7 99K6 0000 LKD 8UB7 99K7 0000 LKD 8UA2 99K7 0000 LKD 8UA5 99K7 0000 LKD 8UA7 99K7 0000 LKD 8UC7 99K7 0000
1x16
12.1
181
2500
2.14
0.59
1x20
12.1
181
2500
2.14
0.59
LKD 8UB7 99K8 0000 LKD 8UA2 99K8 0000 LKD 8UA5 99K8 0000 LKD 8UA7 99K8 0000 LKD 8UC7 99K8 0000
1x24
12.1
181
2500
2.14
0.59
LKD 8UB7 99K9 0000 LKD 8UA2 99K9 0000 LKD 8UA5 99K9 0000 LKD 8UA7 99K9 0000 LKD 8UC7 99K9 0000 www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 173
LEONI "fire secured" FO data cables
GigaLine® FO data cables
with a fire barrier to protect the fibers in the event of a fire
A functioning communication system is of vital importance in the event of a fire. It is therefore vital that a fiber optic cable maintains its total system integrity. The results of the fire tests certify that the "fire secured" fiber optic data cables maintain their total system integrity and their insulation integrity for 90 and 120 minutes respectively in the event of a fire.
In particular in public facilities and buildings where large numbers of people gather (e.g. tunnels, airports, hotels, etc.), fire alarm, SOS telephone and video monitoring systems are used to coordinate rescue measures and fire fighting efforts as efficiently as possible. Also in industrial facilities, processes have to be terminated in a controlled manner in order to avoid serious secondary damage to humans and the environment. Modern communication systems are increasingly using optical data transmission systems for transmitting data. These are often the only option given the high requirements for data rates and transmission paths. With its "fire secured" universal cables, LEONI offers products which are tested according to IEC 60331-25 and EN 50200 and protect the fibers from exposure to fire thanks to their special construction with a fire barrier.
www.leoni-infrastructure-datacom.com
174
GigaLine®
"Fire secured" universal cable, central with CI
Type KL-U-D(ZN)BH 1xn G/E Total system integrity during exposure to fire for at least 90 minutes Outer sheath Ripcord Loose tube, gel-filled Strain relief Inner fire protection barrier
Description
Thermal characteristics
Installation cable suitable for campus/backbone cabling
Transport/storage
–25 °C up to +70 °C
and structured cabling acc. to ISO/IEC 11801 and EN 50173
Installation
– 5 °C up to +50 °C
(2nd edition). Ideal for all applications from Classes OF 300 to
Operating temperature
–25 °C up to +60 °C
OF 10000. Suitable for installation in applications involving increased mechanical requirements as well as risk of rodent
Mechanical characteristics
damage. Suitable for splicing. House connections possible
Min. bending radius
without additional interconnection points (splices). Max. crush strength Installation in dry areas, in cable ducts, on cable trays or in conduits.
static
15 x overall diameter
dynamic
20 x overall diameter
long-term
3000 N/dm
short-term
4500 N/dm
Construction
Fire performance
Central filled loose tube with max. 24 fibers, up to 12 fibers diam.
Smoke density
IEC 61034
3.5 mm, up to 24 fibers diam. 4.0 mm, with fire protection barrier
Halogen free
IEC 60754-1
Fiber colour code acc. to IEC 60304
Flame retardancy
IEC 60332-1-2, IEC 60332-3-22
Loose tube colour: Yellow (E9/125), green (G50/125), blue (G62.5/125) Strain relief
Non-metallic (glass rovings)
Further characteristics:
Cable sheath
Halogen-free, flame-retardant compound
Total system and
Ripcords under the sheath
insulation integrity EN 50200/DIN VDE 0482 Part 1
Sheath colour
● Yellow
Acc. to IEC 60331-11 and -25 (90 minutes)
Max. change in attenuation 2.0 dB
Overall diam. approx.
Weight approx.
Max. strain relief
Fire load approx.
mm
kg/km
N
MJ/m kWh/m
1x2
10.3
115
2500
1.03
0.29
LKD 8UB7 00B1 0000 LKD 8UA2 00B1 0000 LKD 8UA5 00B1 0000 LKD 8UA7 00B1 0000 LKD 8UC7 00B1 0000
1x4
10.3
115
2500
1.03
0.29
LKD 8UB7 00B2 0000 LKD 8UA2 00B2 0000 LKD 8UA5 00B2 0000 LKD 8UA7 00B2 0000 LKD 8UC7 00B2 0000
1x6
10.3
115
2500
1.03
0.29
LKD 8UB7 00B3 0000 LKD 8UA2 00B3 0000 LKD 8UA5 00B3 0000 LKD 8UA7 00B3 0000 LKD 8UC7 00B3 0000 LKD 8UB7 00B4 0000 LKD 8UA2 00B4 0000 LKD 8UA5 00B4 0000 LKD 8UA7 00B4 0000 LKD 8UC7 00B4 0000
Fiber number
Order no. OM1e G62.5/125
OM2e G50/125
OM3 G50/125
OM4 G50/125
OS2 E9…10/125
1x8
10.3
115
2500
1.03
0.29
1x10
10.3
115
2500
1.03
0.29
LKD 8UB7 00B5 0000 LKD 8UA2 00B5 0000 LKD 8UA5 00B5 0000 LKD 8UA7 00B5 0000 LKD 8UC7 00B5 0000
1x12
10.3
115
2500
1.03
0.29
LKD 8UB7 00B6 0000 LKD 8UA2 00B6 0000 LKD 8UA5 00B6 0000 LKD 8UA7 00B6 0000 LKD 8UC7 00B6 0000
1x16
10.8
125
2500
1.28
0.36
LKD 8UB7 00B7 0000 LKD 8UA2 00B7 0000 LKD 8UA5 00B7 0000 LKD 8UA7 00B7 0000 LKD 8UC7 00B7 0000
1x20
10.8
125
2500
1.28
0.36
LKD 8UB7 00B8 0000 LKD 8UA2 00B8 0000 LKD 8UA5 00B8 0000 LKD 8UA7 00B8 0000 LKD 8UC7 00B8 0000
1x24
10.8
125
2500
1.28
0.36
LKD 8UB7 00B9 0000 LKD 8UA2 00B9 0000 LKD 8UA5 00B9 0000 LKD 8UA7 00B9 0000 LKD 8UC7 00B9 0000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 175
GigaLine®
"Fire secured" universal cable, central with CI
Type KL-U-DQ(ZN)H(SR)H 1xn G/E Total system integrity during exposure to fire for at least 120 minutes
Outer sheath Corrugated steel cladding Inner sheath Strain relief
Description
Thermal characteristics
Installation cable suitable for campus/backbone cabling
Transport/storage
–25 °C up to +70 °C
and structured cabling acc. to ISO/IEC 11801 and EN 50173
Installation
–5 °C up to +50 °C
(2nd edition). For applications from Classes OF 300 to OF 10000.
Operating temperature
–25 °C up to +60 °C
Suitable for installation in applications involving increased mechanical requirements as well as risk of rodent damage.
Mechanical characteristics
Suitable for splicing. House connections possible without
Min. bending radius
additional interconnection points (splices). Installation indoors and outdoors in dry conduits, on covered cable trays or in cable
Max. crush strength
ducts. Mechanical pulling in with winches is only permitted in
static
15 x overall diameter
dynamic
20 x overall diameter
long-term
2500 N/dm
short-term
3500 N/dm
conjunction with force measuring devices with a logging feature. Fire performance Construction
Smoke density
IEC 61034
Central filled loose tubes with max. 24 fibers, up to 12 fibers diam. 3.5
Halogen free
IEC 60754-1
mm, up to 24 fibers diam. 4.0 mm, fiber colour code acc. to IEC 60304
Flame retardancy
IEC 60332-1-2, IEC 60332-3-22
Loose tube colour: Yellow (E9/125), green (G50/125), blue (G62.5/125) Strain relief
Non-metallic (glass rovings)
Inner sheath
Halogen-free, flame-retardant compound
Armouring
Corrugated steel sheath as fire protection
barrier
and rodent protection
Cable sheath
Halogen-free, flame-retardant compound
Sheath colour
● Yellow
Fiber number
Overall diam. approx.
Weight approx.
Max. strain relief
Fire load approx.
mm
kg/km
N
MJ/m kWh/m
Further characteristics:
Total system and
Acc. to IEC 60331-11 and -25
insulation integrity
EN 50200: 2000 Class PH120
& BS 8434: 2003 Part 2 (120 minutes)
Order no. OM1e G62.5/125
OM2e G50/125
OM3 G50/125
OM4 G50/125
OS2 E9…10/125
1x2
12.5
215
2500
2.80
0.78
LKD 8UB7 00C1 0000 LKD 8UA2 00C1 0000 LKD 8UA5 00C1 0000 LKD 8UA7 00C1 0000 LKD 8UC7 00C1 0000
1x4
12.5
215
2500
2.80
0.78
LKD 8UB7 00C2 0000 LKD 8UA2 00C2 0000 LKD 8UA5 00C2 0000 LKD 8UA7 00C2 0000 LKD 8UC7 00C2 0000
1x6
12.5
215
2500
2.80
0.78
LKD 8UB7 00C3 0000 LKD 8UA2 00C3 0000 LKD 8UA5 00C3 0000 LKD 8UA7 00C3 0000 LKD 8UC7 00C3 0000
1x8
12.5
215
2500
2.80
0.78
LKD 8UB7 00C4 0000 LKD 8UA2 00C4 0000 LKD 8UA5 00C4 0000 LKD 8UA7 00C4 0000 LKD 8UC7 00C4 0000
1x10
12.5
215
2500
2.80
0.78
LKD 8UB7 00C5 0000 LKD 8UA2 00C5 0000 LKD 8UA5 00C5 0000 LKD 8UA7 00C5 0000 LKD 8UC7 00C5 0000
1x12
12.5
215
2500
2.80
0.78
LKD 8UB7 00C6 0000 LKD 8UA2 00C6 0000 LKD 8UA5 00C6 0000 LKD 8UA7 00C6 0000 LKD 8UC7 00C6 0000
1x16
12.5
215
2500
2.80
0.78
LKD 8UB7 00C7 0000 LKD 8UA2 00C7 0000 LKD 8UA5 00C7 0000 LKD 8UA7 00C7 0000 LKD 8UC7 00C7 0000
1x20
12.5
215
2500
2.80
0.78
LKD 8UB7 00C8 0000 LKD 8UA2 00C8 0000 LKD 8UA5 00C8 0000 LKD 8UA7 00C8 0000 LKD 8UC7 00C8 0000
1x24
12.5
215
2500
2.80
0.78
LKD 8UB7 00C9 0000 LKD 8UA2 00C9 0000 LKD 8UA5 00C9 0000 LKD 8UA7 00C9 0000 LKD 8UC7 00C9 0000
www.leoni-infrastructure-datacom.com
GigaLine® FO data cables
Loose tube, gel-filled
176
GigaLine®
Outdoor cable, central 1750 N
Type KL-A-DQ(ZN)B2Y 1xn G/E
Outer sheath Loose tube, gel-filled Strain relief and rodent protection
Description
Thermal characteristics
Outdoor cable for direct installation in the ground, in conduits
Transport/storage
–25 °C up to +70 °C
and where there is a risk of rodent damage in MAN (city
Installation
–5 °C up to +50 °C
networks) and LAN (campus/backbone). Suitable for structured
Operating temperature
–25 °C up to +60 °C
cabling acc. to ISO/IEC 11801 and EN 50173 (2nd edition). In keeping with the fiber type ideal for all applications from
Mechanical characteristics
Classes OF 300 to OF 10000. Easy to install thanks to grease-
Min. bending radius
free, dry cable core. Suitable for splicing. Max. crush strength Installation indoors, in conduits, on covered cable trays,
static
15 x overall diameter
dynamic
20 x overall diameter
long-term
1500 N/dm
short-term
2500 N/dm
in cable ducts or directly in the ground. Mechanical pulling in with winches is only permitted in conjunction with force measuring devices with a logging feature.
Fire performance Halogen free
IEC 60754-1
Construction
Further characteristics:
Central filled loose tube with up to 24 fibers
Longitudinal watertightness IEC 60794-1-2 F5
Fiber colour code acc. to IEC 60304
Impact resistance
IEC 60794-1-2 E4
Loose tube colour: Yellow (E9/125), green (G50/125), blue (G62.5/125)
Cable bending
IEC 60794-1-2 E11
Strain relief
Non-metallic (glass rovings)
Cable sheath
Resistant to PE, UV rays
Sheath colour
● Black
Fiber number
Overall diam. approx.
Weight approx.
Max. strain relief
Fire load approx.
mm
kg/km
N
MJ/m kWh/m
Order no. OM1e G62.5/125
OM2e G50/125
OM3 G50/125
OM4 G50/125
OS2 E9…10/125
1x2
7.4
39
1750
1.21
0.34
LKD 8AB7 00A1 0000 LKD 8AA2 00A1 0000 LKD 8AA5 00A1 0000 LKD 8AA7 00A1 0000 LKD 8AC7 00A1 0000
1x4
7.4
39
1750
1.21
0.34
LKD 8AB7 00A2 0000 LKD 8AA2 00A2 0000 LKD 8AA5 00A2 0000 LKD 8AA7 00A2 0000 LKD 8AC7 00A2 0000
1x6
7.4
39
1750
1.21
0.34
LKD 8AB7 00A3 0000 LKD 8AA2 00A3 0000 LKD 8AA5 00A3 0000 LKD 8AA7 00A3 0000 LKD 8AC7 00A3 0000
1x8
7.4
39
1750
1.21
0.34
LKD 8AB7 00A4 0000 LKD 8AA2 00A4 0000 LKD 8AA5 00A4 0000 LKD 8AA7 00A4 0000 LKD 8AC7 00A4 0000
1x10
7.4
39
1750
1.21
0.34
LKD 8AB7 00A5 0000 LKD 8AA2 00A5 0000 LKD 8AA5 00A5 0000 LKD 8AA7 00A5 0000 LKD 8AC7 00A5 0000
1x12
7.4
39
1750
1.21
0.34
LKD 8AB7 00A6 0000 LKD 8AA2 00A6 0000 LKD 8AA5 00A6 0000 LKD 8AA7 00A6 0000 LKD 8AC7 00A6 0000
1x16
7.8
45
1750
1.39
0.39
LKD 8AB7 00A7 0000 LKD 8AA2 00A7 0000 LKD 8AA5 00A7 0000 LKD 8AA7 00A7 0000 LKD 8AC7 00A7 0000
1x20
7.8
45
1750
1.39
0.39
LKD 8AB7 00A8 0000 LKD 8AA2 00A8 0000 LKD 8AA5 00A8 0000 LKD 8AA7 00A8 0000 LKD 8AC7 00A8 0000
1x24
7.8
45
1750
1.39
0.39
LKD 8AB7 00A9 0000 LKD 8AA2 00A9 0000 LKD 8AA5 00A9 0000 LKD 8AA7 00A9 0000 LKD 8AC7 00A9 0000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 177
GigaLine®
Outdoor cable, stranded 4000 N
Type KL-A-DQ(ZN)B2Y nxm G/E
Outer sheath Water-absorbent fleece Loose tube, gel-filled Strain relief GFR central strength
Description
Thermal characteristics
Outdoor cable for direct installation in the ground, in conduits
Transport/storage
–40 °C up to +70 °C
and where there is a risk of rodent damage in MAN (city
Installation
–10 °C up to +50 °C
networks) and LAN (campus/backbone). Suitable for structured
Operating temperature
–40 °C up to +60 °C
cabling acc. to ISO/IEC 11801 and EN 50173 (2nd edition). In keeping with the fiber type ideal for all applications from
Mechanical characteristics
Classes OF 300 to OF 10000. Easy to install thanks to grease-
Min. bending radius
free, dry cable core. Suitable for splicing. Max. crush strength Installation indoors, in conduits, on covered cable trays, in
static
15 x overall diameter
dynamic
20 x overall diameter
long-term
3000 N/dm
short-term
4000 N/dm
cable ducts or directly in the ground. Mechanical pulling in with winches is only permitted in conjunction with force measuring devices with a logging feature.
Fire performance Halogen free
IEC 60754-1
Construction
Further characteristics:
Stranded filled loose tube diameter 2.4 mm with up to 12 fibers
Longitudinal watertightness IEC 60794-1-2 F5
Fiber colour code acc. to IEC 60304
Impact resistance
IEC 60794-1-2 E4
Loose tube colour: Counting wire red, counting direction wire
Cable bending
IEC 60794-1-2 E11
white, yellow (E9/125), green (G50/125), blue (G62.5/125) Twisting
Loose tubes and if applicable dummy elements
around central strength member
Strain relief
Non-metallic (glass rovings)
Cable sheath
Resistant to PE, UV rays
Sheath colour
● Black
Overall diam. Fiber approx. number mm
Weight approx.
Max. strain relief
Fire load approx.
kg/km
N
MJ/m kWh/m
115
4000
2x12
11.5
4.10
Order no. OM1e G62.5/125
OM2e G50/125
OM3 G50/125
OM4 G50/125
OS2 E9...10/125
1.14
LKD 8AB7 0K06 0000 LKD 8AA2 0K06 0000 LKD 8AA5 0K06 0000 LKD 8AA7 0K06 0000 LKD 8AC7 0K06 0000 LKD 8AB7 0K08 0000 LKD 8AA2 0K08 0000 LKD 8AA5 0K08 0000 LKD 8AA7 0K08 0000 LKD 8AC7 0K08 0000
4x12
11.5
115
4000
4.10
1.14
8x12
13.7
165
4000
4.96
1.38
LKD 8AB7 0K11 0000 LKD 8AA2 0K11 0000 LKD 8AA5 0K11 0000 LKD 8AA7 0K11 0000 LKD 8AC7 0K11 0000
12x12
17.0
230
4000
6.19
1.72
LKD 8AB7 0K13 0000 LKD 8AA2 0K13 0000 LKD 8AA5 0K13 0000 LKD 8AA7 0K13 0000 LKD 8AC7 0K13 0000
Other types on request
www.leoni-infrastructure-datacom.com
GigaLine® FO data cables
member
178
GigaLine®
Outdoor cable, central 1750 N
Type KL-A-DQ(ZN)2Y(SR)2Y 1xn G/E
Outer sheath Corrugated steel cladding Inner sheath Loose tube, gel-filled Strain relief
Description
Thermal characteristics
Outdoor cable for direct installation in the ground, in conduits
Transport/storage
–25 °C up to +70 °C
and where there is an increased risk of rodent damage in
Installation
– 5 °C up to +50 °C
MAN (city networks) and LAN (campus/backbone). Suitable
Operating temperature
–25 °C up to +60 °C
for structured cabling acc. to ISO/IEC 11801 and EN 50173 (2nd edition). In keeping with the fiber type ideal for all
Mechanical characteristics
applications from Classes OF 300 to OF 10000. Easy to install
Min. bending radius
thanks to grease-free, dry cable core. Suitable for splicing. Max. crush strength Installation outdoors in conduits, on covered cable trays.
static
15 x overall diameter
dynamic
20 x overall diameter
long-term
2500 N/dm
short-term
3500 N/dm
Mechanical pulling in with winches is only permitted in conjunction with force measuring devices with a logging feature.
Fire performance Halogen free
IEC 60754-1
Construction Central filled loose tube with up to 24 fibers
Further characteristics:
Fiber colour code acc. to IEC 60304
Longitudinal watertightness IEC 60794-1-2 F5
Strain relief
Non-metallic (glass rovings)
Impact resistance
IEC 60794-1-2 E4
Inner sheath
PE
Cable bending
IEC 60794-1-2 E11
Armouring Corrugated steel cladding as highly effective rodent protection Outer sheath
Resistant to PE, UV rays
Sheath colour
● Black
Fiber number
Overall diam. approx.
Weight approx.
Max. strain relief
Fire load approx.
mm
kg/km
N
MJ/m kWh/m
Order no. OM1e G62.5/125
OM2e G50/125
OM3 G50/125
OM4 G50/125
OS2 E9…10/125
1x2
11.0
119
1750
3.01
1.08
LKD 8AB7 00L1 0000 LKD 8AA2 00L1 0000 LKD 8AA5 00L1 0000 LKD 8AA7 00L1 0000 LKD 8AC7 00L1 0000
1x4
11.0
119
1750
3.01
1.08
LKD 8AB7 00L2 0000 LKD 8AA2 00L2 0000 LKD 8AA5 00L2 0000 LKD 8AA7 00L2 0000 LKD 8AC7 00L2 0000
1x6
11.0
119
1750
3.01
1.08
LKD 8AB7 00L3 0000 LKD 8AA2 00L3 0000 LKD 8AA5 00L3 0000 LKD 8AA7 00L3 0000 LKD 8AC7 00L3 0000
1x8
11.0
119
1750
3.01
1.08
LKD 8AB7 00L4 0000 LKD 8AA2 00L4 0000 LKD 8AA5 00L4 0000 LKD 8AA7 00L4 0000 LKD 8AC7 00L4 0000
1x10
11.0
119
1750
3.01
1.08
LKD 8AB7 00L5 0000 LKD 8AA2 00L5 0000 LKD 8AA5 00L5 0000 LKD 8AA7 00L5 0000 LKD 8AC7 00L5 0000
1x12
11.0
119
1750
3.01
1.08
LKD 8AB7 00L6 0000 LKD 8AA2 00L6 0000 LKD 8AA5 00L6 0000 LKD 8AA7 00L6 0000 LKD 8AC7 00L6 0000
1x16
11.6
127
1750
3.30
1.19
LKD 8AB7 00L7 0000 LKD 8AA2 00L7 0000 LKD 8AA5 00L7 0000 LKD 8AA7 00L7 0000 LKD 8AC7 00L7 0000
1x20
11.6
127
1750
3.30
1.19
LKD 8AB7 00L8 0000 LKD 8AA2 00L8 0000 LKD 8AA5 00L8 0000 LKD 8AA7 00L8 0000 LKD 8AC7 00L8 0000
1x24
11.6
127
1750
3.30
1.19
LKD 8AB7 00L9 0000 LKD 8AA2 00L9 0000 LKD 8AA5 00L9 0000 LKD 8AA7 00L9 0000 LKD 8AC7 00L9 0000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 179
GigaLine®
Outdoor cable, stranded 4000 N
Type KL-A-DQ(ZN)2Y(SR)2Y nxm G/E
Outer sheath Corrugated steel cladding Inner sheath Water-absorbent fleece Loose tube, gel-filled Strain relief GFR central strength
Description
Thermal characteristics
Outdoor cable for direct installation in the ground, in conduits
Transport/storage
–25 °C up to +70 °C
and where there is an increased risk of rodent damage in MAN
Installation
–5 °C up to +50 °C
(city networks) and LAN (campus/backbone). Suitable for use
Operating temperature
–25 °C up to +60 °C
in structured cabling acc. to ISO/IEC 11801 and EN 50173 (2nd edition). In keeping with the fiber type ideal for all applications
Mechanical characteristics
from Classes OF 300 to OF 10000. Easy to install thanks to
Min. bending radius
grease-free, dry cable core. Suitable for splicing. Installation outdoors, in conduits, on covered cable trays
Max. crush strength
or directly in the ground. Mechanical pulling in with winches is only permitted in conjunction with force measuring devices with a logging feature.
static
15 x overall diameter
dynamic
20 x overall diameter
long-term
3000 N/dm
short-term
5000 N/dm
Fire performance Halogen free
IEC 60754-1
Construction
Further characteristics:
Stranded filled loose tube diameter 2.4 mm with up to 12 fibers
Longitudinal watertightness IEC 60794-1-2 F5
Fiber colour code acc. to IEC 60304 Loose tube colour: Counting wire red, counting direction wire white, yellow (E9/125), green (G50/125), blue (G62.5/125) Twisting
Loose tubes and if applicable dummy elements
around central strength member
Strain relief
Non-metallic (glass rovings)
Inner sheath
PE, colour ● Black
Impact resistance
IEC 60794-1-2 E4
Cable bending
IEC 60794-1-2 E11
Armouring Corrugated steel cladding as highly effective rodent protection Outer sheath
Resistant to PE, UV rays
Sheath colour
● Black
Overall diam. Fiber approx. number mm
Weight approx.
Max. strain relief
Fire load approx.
kg/km
N
MJ/m kWh/m
285
4000
10.62
2x12
17.5
Order no. OM1e G62.5/125
OM2e G50/125
OM3 G50/125
OM4 G50/125
OS2 E9…10/125
2.95
LKD 8AB7 0A06 0000 LKD 8AA2 0A06 0000 LKD 8AA5 0A06 0000 LKD 8AA7 0A06 0000 LKD 8AC7 0A06 0000 LKD 8AB7 0A08 0000 LKD 8AA2 0A08 0000 LKD 8AA5 0A08 0000 LKD 8AA7 0A08 0000 LKD 8AC7 0A08 0000
4x12
17.5
285
4000
10.62
2.95
8x12
19.6
345
4000
12.24
3.40
LKD 8AB7 0A11 0000 LKD 8AA2 0A11 0000 LKD 8AA5 0A11 0000 LKD 8AA7 0A11 0000 LKD 8AC7 0A11 0000
12x12
21.5
400
4000
13.80
3.80
LKD 8AB7 0A13 0000 LKD 8AA2 0A13 0000 LKD 8AA5 0A13 0000 LKD 8AA7 0A13 0000 LKD 8AC7 0A13 0000
Other types on request
www.leoni-infrastructure-datacom.com
GigaLine® FO data cables
member
180
GigaLine®
Outdoor cable, stranded with sheath 4,000 N
Type KL-A-DF(ZN)(L)2Y nxm G/E
Outer sheath Aluminium tape Loose tube, gel-filled Water-blocking gel filling Strain relief GFR central strength member
Description
Thermal characteristics
Water-blocking gel-filled longitudinally and transversely
Transport/storage
watertight outdoor cable for installation directly in the ground,
Installation
–5 °C up to +50 °C
in conduits and where there is a risk of rodent damage in
Operating temperature
–40 °C up to +60 °C
–40 °C up to +70 °C
MAN (city networks) and LAN (campus/backbone). Suitable for use in structured cabling acc. to ISO/IEC 11801 and EN
Mechanical characteristics
50173 (2nd edition). In keeping with the fiber type ideal for all
Min. bending radius
applications from Classes OF 300 to OF 10000. Suitable for splicing. Installation indoors and outdoors in conduits, on covered cable trays or directly in the ground. Mechanical pulling in with winches
Max. crush strength
is only permitted in conjunction with force measuring devices with a logging feature.
static
15 x overall diameter
dynamic
20 x overall diameter
long-term
1500 N/dm
short-term
3000 N/dm
Fire performance Halogen free
IEC 60754-1
Construction Stranded filled loose tube diameter 2.4 mm with up to 12 fibers
Further characteristics:
Fiber colour code acc. to IEC 60304
Longitudinal watertightness IEC 60794-1-2 F5
Loose tube colour: Counting wire red, counting direction wire
Impact resistance
IEC 60794-1-2 E4
white, yellow (E9/125), green (G50/125), blue (G62,5/125)
Cable bending
IEC 60794-1-2 E11
Twisting
Loose tubes and if applicable dummy elements
around central strength member
Filling
Water-blocking gel filling in twist cavities
of the cable core
Strain relief
Non-metallic (glass rovings)
Outer sheath
Aluminium sheath, resistant to UV rays
(aluminium tape with PE sheath)
Sheath colour
● Black
Overall diam. Fiber approx. number mm
Weight approx.
Max. strain relief
Fire load approx.
kg/km
N
MJ/m kWh/m
140
4000
2x12
12.1
Order no. OM1e G62.5/125
OM2e G50/125
OM3 G50/125
OM4 G50/125
OS2 E9…10/125
4.97
1.38
LKD 8AB7 0406 0000 LKD 8AA2 0406 0000 LKD 8AA5 0406 0000 LKD 8AA7 0A06 0000 LKD 8AC7 0406 0000 LKD 8AB7 0408 0000 LKD 8AA2 0408 0000 LKD 8AA5 0408 0000 LKD 8AA7 0A08 0000 LKD 8AC7 0408 0000
4x12
12.1
140
4000
4.97
1.38
8x12
14.4
200
4000
5.87
1.63
LKD 8AB7 0411 0000 LKD 8AA2 0411 0000 LKD 8AA5 0411 0000 LKD 8AA7 0A11 0000 LKD 8AC7 0411 0000
12x12
17.7
300
4000
7.24
2.01
LKD 8AB7 0413 0000 LKD 8AA2 0413 0000 LKD 8AA5 0413 0000 LKD 8AA7 0A13 0000 LKD 8AC7 0413 0000
Other types on request
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter
GigaLine® FO data cables
181
www.leoni-infrastructure-datacom.com
182
GigaLine FO connectivity ®
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 183
GigaLine® FO connectivity
182
GigaLine® FO cabling systems
184
GigaLine® trunk and splice boxes
o dc
Fiber optic trunk box
o dc
Fiber optic splice box
• Telescopic splice box • Fixed splice box
188 189 190 192
GigaLine® Compact – fiber optic distribution system
195
o dc
Compact fiber optic rack
196
o dc
Compact fiber optic module
For pre-assembled breakout cables
197
o dc
Compact fiber optic module
For splicing solutions
198
GigaLine® office and floor distributors
o
Fiber optic office and floor distributors
• Size A for up to 4 splice cassettes • Size B for up to 24 splice cassettes
GigaLine® Fiber-To-The-Desk (FTTD) wall outlets
201 202 203 205
o
FTTD wall outlets
• For surface mounting • For flush mounting
o
FTTD wall outlets
• Cable reservoir • Splice tray for cable reservoir
o o
FTTD outlet for cable ducts
208
FTTD mounting bracket for cable ducts
209
o dc i
Office DataCenter Industry
www.leoni-infrastructure-datacom.com
206 207
GigaLine® FO connectivity
187 • Telescopic trunk box • Fixed trunk box
184
GigaLine®
FO cabling systems
High-performance components for building a fiber optic infrastructure
GigaLine® is a perfectly coordinated system made up
The GigaLine® system is determined by the application, required
of components optimised for performance and quality.
link length and transmission protocol.
The interplay of high-quality fibers which far exceed the
The table below shows the protocol-dependent attenuation
standard and connectors with high-quality workmanship enable
budget according to EN 50173-1 for the 10 Gigabit Ethernet
maximum performance and range for the respective application
protocol. From this is derived the number of possible
(GbE/10 GbE).
connections based on the overall link. The following harmonised
The requirements for fibers and connectors differ depending on the field of application. OM1e
OM2
OM2e
OM3
OM4
components were taken into consideration when putting together the system:
OS2
Industry
SC, ST
Office
LC, SC
DataCenter
■■
multimode fibers that far exceed the standard and have
LC, MTP/MPO
Campus
Fiber optic cables (GigaLine®) with laser/dispersion-optimised appropriate performance reserves (for fiber specifications see
LC, SC
section on GigaLine® fiber optic data cables) The system components are optimised to meet the
■■
requirements for both distance and data rate. That is why LEONI
Fiber optic connectors with low insertion losses and high return losses
consistently uses its own j-fiber fibers (cables, pigtails, patch cords).
Industry Office DataCenter Campus
GigaLine® Compact
Maximum transmission lengths for 10 Gigabit Ethernet system solutions. GigaLine® DClink
GigaLine® trunk and splice boxes
GigaLine® wall distributors
GigaLine® wall outlets
GigaLine® has components for every field of application.
Max. link length*
OM2e
OM3
OM4
OS2
150
300
550
10,000
Attenuation budget**
1.8 dB
2.6 dB
2.6 dB
6.2 dB
Max. fiber attenuation
0.37 dB
0.75 dB
1.37 dB
3.6 dB
6
8
6
12
LC, MTP/ MPO, SC
LC, MTP/ MPO, SC
LC, MTP/ MPO, SC
LC, SC
Number of possible connectors Recommended connectors
* Based on 10 GbE ** All specifications are based on 850 nm or 1,310 nm
www.leoni-infrastructure-datacom.com
Office Office
Industry
DataCenter 185
Graph 1 shows the system reserves afforded by the high-quality
Quality is our benchmark
fibers and connectors in relation to EN 50173.
Assembly of fiber optic connectors involves both adjustment of the fibers in the ferrule as well as time-consuming grinding and
■■
polishing. The aim here is to machine the connector so precisely
Longer transmission lengths for certain applications
by means of optimised processes that the insertion loss and
(100 Mb/s, 1 GbE, 10 GbE, 40 GbE, 100 GbE)
reflections are kept to a minimum. This is done by means of
■■
The option to insert more patch cords or splices
PC polishing (PC = physical contact). Spherical polishing of the
■■
Additional attenuation caused by aging processes
ferrule spring mounted in the connector housing produces
can be curtailed
a fiber/fiber transition at the end faces. In other words when
Network extensions can be realised with ease and a certain
two connectors are plugged into one coupling, the spring
level of assurance within the link lengths
pressure pushes out all the air between the mating fibers of
■■
both connectors. The glass/glass transition then has very low reflections and low attenuation.
Distance/km
To maximise the performance of a PC connector, the surface Attenuation-limited operation
LEONI OM4 LEONI OM3 LEONI OM2e Standard OM3 Standard OM2
parameters of the connectors must be carefully checked during the polishing process. The interferometer is an indicatory measuring instrument for this. The overlaps of coherent light waves are used to measure the quality of optical surfaces (ferrule surfaces).
Dispersion-limited operation
The most important parameters are: ■■
Apex offset (offset between the highest point and the centre of the fiber)
Bandwidth/MHz
Graph 1: System reserves of GigaLine® 150, 300 and 550 relative to the standard
■■
Radius of the connector interface (fiber/ferrule)
■■
Fiber height (undercut, protrusion)
These parameters are decisive for the long-term behaviour and therefore the quality of a fiber optic connector. Insertion loss of the connectors used in GigaLine® system components. Insertion loss typ.
Return loss
G62.5/125 OM1e
0.2 dB
> 40 dB
G50/125
OM2e
0.2 dB
> 40 dB
G50/125
OM3
0.2 dB
> 40 dB
G50/125
OM4
0.2 dB
> 40 dB
E9..10/125
OS2
0.2 dB
> 50 dB
E9..10/125
OS2 APC
0.2 dB
> 70 dB
Fiber type
www.leoni-infrastructure-datacom.com
GigaLine® FO connectivity
Decisive advantages of these system reserves are:
186
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 187
GigaLine® Trunk and splice boxes Multifunctional housing technology, 19" GigaLine® trunk and splice boxes can be used in all areas of
Your guarantee for quick and reliable installation:
building data cabling. The construction of the components
■■
The box body is made from aluminium and therefore very light
ensures speed and reliability during initial installation,
■■
The boxes are assembled ready to install
maintenance and extension.
■■
The permissible bending radii as well as ease of installation are guaranteed even with high packing densities
All boxes are pre-assembled ready to install and constructed so
■■
The telescopic version offers the advantage that all components are easily accessible for testing and maintenance work
that two cables can be inserted via cable glands or two divider heads can be inserted from above. A breakout panel to which the cables can be secured using cable ties is available as an
GigaLine® trunk and splice box:
alternative.
■■
Boxes with one rack unit as fixed installation or telescopic Boxes with two rack units are always telescopic
■■
The front panel is made from galvanised steel panel and Light grey RAL 7035, powder coated
■■
One rack unit can be equipped with up to 24 x SC Duplex, 24 x LC Duplex, 24 x MT-RJ, 24 x E 2000, 24 x ST, 24 x FC couplings
www.leoni-infrastructure-datacom.com
GigaLine® FO connectivity
version ■■
188
GigaLine®
Fiber optic trunk box
Box 19"/1 RU, telescopic or fixed
GigaLine® trunk box, telescopic Description
Configuration
Telescopic fiber optic patch panel for pre-assembled trunk
Equipment
Available with up to 24 slots
cables. Suitable for terminating up to 48 optical fibers.
Couplings
SC Duplex, FC-PC/FC-APC, ST E2000/E2000 HRL, MTRJ, LC Duplex
Construction Box
Aluminium, with dust protective cover
Accessories (optional)
telescopic and removable drawer, depth
Breakout panel
For securing cables using cable ties
continuously adjustable by up to 50 mm Front panel and
Galvanised steel panel, powder coated
mounting bracket
colour: Grey RAL 7035
Capacity
Installation of up to 2 trunk cables
Labelling
Channel 1–12/1–24 (screen printing)
Dimensions
A/B coding with SC/ST/FC configuration
Designation
Order no.
19"/1 RU
GigaLine® trunk box, telescopic
See table
44 mm x 483 mm x 220 mm (H x W x D)
Breakout panel
LKD 9D60 0000 0000
Approx. 1.7 kg
Weight
Singlemode Number of fibers 6
SC Duplex Met/Cer
SC Duplex, blue Plastic/Cer
LCD, blue Plastic/Cer
E2000, blue Plastic/Cer
E2000HRL, green Plastic/Cer
LKD 9D32 A039 0000
LKD 9D32 A003 0000
LKD 9D32 A014 0000
LKD 9D32 A017 0000
LKD 9D32 A020 0000
12
LKD 9D32 A040 0000
LKD 9D32 A004 0000
LKD 9D32 A015 0000
LKD 9D32 A018 0000
LKD 9D32 A002 0000
24
LKD 9D32 A041 0000
LKD 9D32 A005 0000
LKD 9D32 A001 0000
LKD 9D32 A019 0000
LKD 9D32 A021 0000
48
LKD 9D32 A095 0000
LKD 9D32 A006 0000
LKD 9D32 A016 0000
SC Duplex, beige Plastic/PhBz
LC Duplex, beige Plastic/PhBz
LC Duplex, aqua Plastic/Cer
LC Duplex, heather violet Plastic/Cer
E2000, beige Plastic/Cer
LKD 9D32 A022 0000
LKD 9D32 A032 0000
LKD 9D32 A178 0000
LKD 9D32 A181 0000
LKD 9D32 A036 0000
Multimode Number of fibers 6 12
LKD 9D32 A023 0000
LKD 9D32 A033 0000
LKD 9D32 A179 0000
LKD 9D32 A182 0000
LKD 9D32 A037 0000
24
LKD 9D32 A000 0000
LKD 9D32 A034 0000
LKD 9D32 A180 0000
LKD 9D32 A183 0000
LKD 9D32 A038 0000
48
LKD 9D32 A024 0000
LKD 9D32 A035 0000
LKD 9D32 A177 0000
LKD 9D32 A184 0000
Other configurations available on request
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter DataCenter 189
Description
Configuration
Fiber optic patch box for pre-assembled trunk cables. Suitable
Equipment
Available with up to 24 slots
for terminating up to 48 optical fibers.
Couplings
SC Duplex, FC-PC/FC-APC, ST E2000/E2000 HRL, MTRJ, LC Duplex
Construction Box
Aluminium, with dust protective cover
Accessories (optional)
Front panel
Galvanised sheet panel, powder coated
Breakout panel
using cable ties
colour: Grey RAL 7035 Capacity
Installation of up to 2 trunk cables
Labelling
Channel 1–12/1–24 (screen printing)
For securing cables
A/B coding with SC/ST/FC configuration Dimensions
19"/1 RU
Weight
44 mm x 483 mm x 220 mm (H x W x D)
Designation
Order no.
Approx. 1.4 kg
GigaLine® Smart trunk, fixed
See table
Breakout panel
LKD 9D60 0000 0000
Singlemode Number of fibers 6
SC Duplex Met/Cer
SC Duplex, blue Plastic/Cer
LKD 9D42 A034 0000
LKD 9D42 A003 0000
LCD, blue Plastic/Cer LKD 9D42 A012 0000
E2000, blue Plastic/Cer
E2000HRL, green Plastic/Cer
LKD 9D42 A014 0000
LKD 9D42 A017 0000
12
LKD 9D42 A035 0000
LKD 9D42 A004 0000
LKD 9D42 A013 0000
LKD 9D42 A015 0000
LKD 9D42 A018 0000
24
LKD 9D42 A036 0000
LKD 9D42 A005 0000
LKD 9D42 A033 0000
LKD 9D42 A016 0000
LKD 9D42 A002 0000
48
LKD 9D42 A047 0000
LKD 9D42 AXXX 0000
LKD 9D42 A001 0000
SC Duplex, beige Plastic/PhBz
LC Duplex, beige Plastic/PhBz
LC Duplex, aqua Plastic/Cer
LC Duplex, heather violet Plastic/Cer
E2000, beige Plastic/Cer
LKD 9D42 A019 0000
LKD 9D42 A027 0000
LKD 9D42 A113 0000
LKD 9D42 A117 0000
LKD 9D42 A030 0000
Multimode Number of fibers 6 12
LKD 9D42 A020 0000
LKD 9D42 A028 0000
LKD 9D42 A114 0000
LKD 9D42 A118 0000
LKD 9D42 A031 0000
24
LKD 9D42 A000 0000
LKD 9D42 A029 0000
LKD 9D42 A115 0000
LKD 9D42 A119 0000
LKD 9D42 A032 0000
48
LKD 9D42 A046 0000
LKD 9D42 A050 0000
LKD 9D42 A116 0000
LKD 9D42 A120 0000
Other configurations available on request
www.leoni-infrastructure-datacom.com
GigaLine® FO connectivity
GigaLine® trunk box, fixed
190
GigaLine®
Fiber optic splice box
Box 19"/1 RU, telescopic
GigaLine® splice box, telescopic Description
Optical characteristics
Telescopic fiber optic patch panel for up to 48 optical fibers. For
Insertion loss typ.
For all fiber types
0.2 dB
Return loss typ.
G62.5/125 OM1e
> 40 dB
Aluminium, with dust protective cover,
G50/125
OM2e
> 40 dB
telescopic and removable drawer, depth
G50/125
OM3
> 40 dB
continuously adjustable by up to 50 mm
G50/125
OM4
> 40 dB
Galvanised steel panel, powder coated
E9..10/125 OS2
> 50 dB
mounting bracket
colour: Grey RAL 7035
E9..10/125 OS2 APC
> 70 dB
Pigtails
Pigtails ready for splicing and plugged in
Configuration
(colours acc. to DIN IEC 60304)
Equipment
Available with up to 24 slots
Channel 1–12/1–24 (screen printing)
Couplings
SC Duplex, FC-PC/FC-APC, ST,
terminating fiber optic transmission links with pigtails. Construction Box
Front panel and
Labelling
A/B coding with SC/ST/FC configuration Dimensions Weight
E2000/E2000 HRL, MTRJ, LC Duplex
19"/1 RU 44 mm x 483 mm x 220 mm (H x W x D)
Accessories
Approx. 1.8 kg
1 x M20 cable gland Splice cassette Crimp splice protective holder Accessories (optional) Breakout panel
Designation
Order no.
GigaLine® splice box, telescopic
See table
Breakout panel
LKD 9D60 0000 0000
For securing cables using cable ties
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter DataCenter 191
Singlemode OS2 E9..10/125 Number of fibers
SC Duplex Met/Cer
SC Duplex, blue Plastic/Cer
LCD, blue Plastic/Cer
E2000, blue Plastic/Cer
E2000HRL, green Plastic/Cer
6
LKD 9D31 A093 0000
LKD 9D31 A003 0000
LKD 9D31 A014 0000
LKD 9D31 A018 0000
LKD 9D31 A021 0000
12
LKD 9D31 A094 0000
LKD 9D31 A004 0000
LKD 9D31 A015 0000
LKD 9D31 A019 0000
LKD 9D31 A022 0000
LKD 9D31 A020 0000
LKD 9D31 A023 0000
24
LKD 9D31 A002 0000
LKD 9D31 A005 0000
LKD 9D31 A016 0000
48
LKD 9D31 A096 0000
LKD 9D31 A006 0000
LKD 9D31 A017 0000
Number of fibers
SC Duplex, beige Plastic/PhBz
LCD, beige Plastic/PhBz LKD 9D31 A089 0000
6
LKD 9D31 A078 0000
12
LKD 9D31 A079 0000
LKD 9D31 A090 0000
24
LKD 9D31 A080 0000
LKD 9D31 A091 0000
48
LKD 9D31 A081 0000
LKD 9D31 A092 0000
Multimode OM2e G50/125 Number of fibers 6
SC Duplex, beige Met/Cer
SC Duplex, beige Plastic/PhBz
LCD, beige Plastic/PhBz
E2000, beige Plastic/Cer
LKD 9D31 AXXX 0000
LKD 9D31 A024 0000
LKD 9D31 A035 0000
LKD 9D31 A039 0000
12
LKD 9D31 AXXX 0000
LKD 9D31 A025 0000
LKD 9D31 A036 0000
LKD 9D31 A040 0000
24
LKD 9D31 A180 0000
LKD 9D31 A026 0000
LKD 9D31 A037 0000
LKD 9D31 A041 0000
48
LKD 9D31 AXXX 0000
LKD 9D31 A027 0000
LKD 9D31 A038 0000
SC Duplex, beige Plastic/PhBz
LCD, aqua Plastic/Cer
Multimode OM3 G50/125 Number of fibers
SC Duplex, beige Met/Cer
E2000, beige Plastic/Cer
6
LKD 9D31 AXXX 0000
LKD 9D31 A042 0000
LKD 9D31 A198 0000
LKD 9D31 A057 0000
12
LKD 9D31 A139 0000
LKD 9D31 A043 0000
LKD 9D31 A199 0000
LKD 9D31 A058 0000
24
LKD 9D31 A000 0000
LKD 9D31 A044 0000
LKD 9D31 A186 0000
LKD 9D31 A059 0000
48
LKD 9D31 A001 0000
LKD 9D31 A045 0000
LKD 9D31A281 0000
SC Duplex, beige Plastic/PhBz
LCD, heather violet Plastic/Cer
E2000, beige Plastic/Cer
Multimode OM4 G50/125 Number of fibers
SC Duplex, beige Met/Cer
6
LKD 9D31 AXXX 0000
LKD 9D31 A060 0000
LKD 9D31 A200 0000
LKD 9D31 A075 0000
12
LKD 9D31 AXXX 0000
LKD 9D31 A061 0000
LKD 9D31 A295 0000
LKD 9D31 A076 0000
24
LKD 9D31 A229 0000
LKD 9D31 A062 0000
LKD 9D31 AXXX 0000
LKD 9D31 A077 0000
48
LKD 9D31 A230 0000
LKD 9D31 A063 0000
LKD 9D31 AXXX 0000
Other configurations available on request
www.leoni-infrastructure-datacom.com
GigaLine® FO connectivity
Multimode OM1e G62.5/125
192
GigaLine®
Fiber optic splice box
Box 19"/1 RU, fixed
GigaLine® splice box, fixed Description
Optical characteristics
Fiber optic patch panel, for up to 48 optical fibers.
Insertion loss typ.
For all fiber types
0.2 dB
Return loss typ.
G62.5/125 OM1e
> 40 dB
OM2e
> 40 dB
For terminating fiber optic transmission links with pigtails. Construction Box
Aluminium with dust protective cover
G50/125
Front panel
Galvanised steel panel, colour: Grey RAL 7035
G50/125
OM3
> 40 dB
Pigtails ready for splicing and plugged in
G50/125
OM4
> 40 dB
(colours acc. to DIN IEC 60304)
E9..10/125 OS2
> 50 dB
Channel 1–12/1–24 (screen printing)
E9..10/125 OS2 APC
> 70 dB
Pigtails Labelling
A/B coding with SC/ST/FC configuration Dimensions Weight
19"/1 RU
Configuration
44 mm x 483 mm x 220 mm (H x W x D)
Equipment
Available with up to 24 slots
Approx. 1.5 kg
Couplings
SC Duplex/SC Duplex, FC-PC, FC-PC(HRL) (SM), ST/ST, E2000/E2000, E2000HRL/ E2000HRL (SM), MT-RJ/MT-RJ (MM), LC Duplex
Accessories 1 x M20 cable gland Splice cassette Crimp splice protective holder Accessories (optional) Breakout panel
Designation
Order no.
GigaLine® splice box, fixed
See table
Breakout panel
LKD 9D60 0000 0000
For securing cables using cable ties
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter DataCenter 193
Singlemode OS2 E9..10/125 Number of fibers
SC Duplex, blue Met/Cer
SC Duplex, blue Plastic/PhBz
E2000, blue Plastic/Cer
E2000HRL, green Plastic/Cer LKD 9D41 A021 0000
6
LKD 9D41 A100 0000
LKD 9D41 AXXX 0000
LKD 9D41 A018 0000
12
LKD 9D41 A080 0000
LKD 9D41 AXXX 0000
LKD 9D41 A019 0000
LKD 9D41 A022 0000
24
LKD 9D41 A081 0000
LKD 9D41 AXXX 0000
LKD 9D41 A020 0000
LKD 9D41 A023 0000
48
LKD 9D41 A159 0000
LKD 9D41 AXXX 0000
Number of fibers
SC Duplex, beige Met/Cer
SC Duplex, beige Plastic/PhBz
LCD, beige Plastic/PhBz
E2000, beige Plastic/Cer LKD 9D41 AXXX 0000
6
LKD 9D41 AXXX 0000
LKD 9D41 A065 0000
LKD 9D41 A074 0000
12
LKD 9D41 AXXX 0000
LKD 9D41 A066 0000
LKD 9D41 A075 0000
LKD 9D41 AXXX 0000
24
LKD 9D41 AXXX 0000
LKD 9D41 A067 0000
LKD 9D41 A076 0000
LKD 9D41 AXXX 0000
48
LKD 9D41 AXXX 0000
LKD 9D41 AXXX 0000
Multimode OM2e G50/125 Number of fibers
SC Duplex, beige Met/Cer
SC Duplex, beige Plastic/PhBz
LCD, beige Plastic/PhBz
E2000, beige Plastic/Cer
6
LKD 9D41 AXXX 0000
LKD 9D41 A024 0000
LKD 9D41 A035 0000
LKD 9D41 A039 0000
12
LKD 9D41 A079 0000
LKD 9D41 A025 0000
LKD 9D41 A036 0000
LKD 9D41 A040 0000
24
LKD 9D41 A169 0000
LKD 9D41 A026 0000
LKD 9D41 A037 0000
LKD 9D41 A041 0000
48
LKD 9D41 AXXX 0000
LKD 9D41 A147 0000
LKD 9D41 A166 0000
SC Duplex, beige Met/Cer
SC Duplex, beige Plastic/PhBz
LCD, aqua Plastic/Cer
E2000, beige Plastic/Cer
Multimode OM3 G50/125 Number of fibers 6
LKD 9D41 AXXX 0000
LKD 9D41 A002 0000
LKD 9D41 A229 0000
LKD 9D41 A047 0000
12
LKD 9D41 A121 0000
LKD 9D41 A006 0000
LKD 9D41 A230 0000
LKD 9D41 A048 0000
24
LKD 9D41 A077 0000
LKD 9D41 A010 0000
LKD 9D41 A231 0000
LKD 9D41 A049 0000
48
LKD 9D41 AXXX 0000
LKD 9D41 AXXX 0000
LKD 9D41 A232 0000
SC Duplex, beige Met/Cer
SC Duplex, beige Plastic/PhBz
LCD, heather violet Plastic/Cer
E2000, beige Plastic/Cer
Multimode OM4 G50/125 Number of fibers 6
LKD 9D41 AXXX 0000
LKD 9D41 A050 0000
LKD 9D41 AXXX 0000
LKD 9D41 A062 0000
12
LKD 9D41 AXXX 0000
LKD 9D41 A051 0000
LKD 9D41 A238 0000
LKD 9D41 A063 0000
24
LKD 9D41 AXXX 0000
LKD 9D41 A052 0000
LKD 9D41 A233 0000
LKD 9D41 A064 0000
48
LKD 9D41 AXXX 0000
LKD 9D41 AXXX 0000
LKD 9D41 A234 0000
Other configurations available on request
www.leoni-infrastructure-datacom.com
GigaLine® FO connectivity
Multimode OM1e G62.5/125
194
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter DataCenter 195
GigaLine® Compact – fiber optic distribution system For maximum packing density and flexibility
GigaLine® Compact is a user-friendly fiber optic distribution system that can be configured with up to 144 fibers with conventional couplings such as SC, ST, E 2000 and with 288 fibers with LC Duplex couplings. The system combines compactness with optimum fiber optic management. GigaLine® Compact is ideal for applications where
GigaLine® FO connectivity
space is tight and maximum flexibility is required.
GigaLine® Compact rack with excess-length drawer 3+1 RU ■■
Width: 19"/84 HP
■■
Height 4 RU (3 RU rack + 1 RU excess-length drawer)
■■
Can be configured with up to 12 modules
■■
Excess-length drawer can be pulled out towards the rear, for holding loose tube reserves and securing the fiber optic cables, alternatively up to 6 pre-assembled trunk cables with up to 48 fibers can be secured using cable glands
■■
Management panel for patch cord routing and adherence to the bending radii
GigaLine® rack with excess-length drawer 3+1 RU
GigaLine® Compact module 3 RU/7 HP ■■
For up to 24 fibers
■■
Available with up to 12 couplings
■■
Configured with SC Duplex, ST, E2000, FC-PC, MT-RJ or LC Duplex couplings
■■
Front panel: Aluminium, with mounting screws
■■
Including splicing cassette and excess-length cassette
■■
Buffered fiber pigtails are inserted, stripped and coloured (primary and secondary coating) acc. to the DIN IEC 60304 colour code ready for splicing for fast and secure installation
■■
Fiber qualities: OM1e, OM2e, OM3, OM4 and OS2
■■
The couplings can be retrofitted at any time GigaLine® Compact module 3 RU, 7 HP
www.leoni-infrastructure-datacom.com
196
GigaLine®
Compact fiber optic rack
with mounted excess-length drawer 3+1 RU
Loose tube guide plate
GigaLine® Compact rack Description
Accessories (optional)
Rack with 84 HP. The excess-length drawer for the loose tubes
Loose tube guide
To protect the loose tubes on the rear,
can be pulled out to the rear. Max. 6 trunk cables with 48 fibers
plate
especially in open racks
each can be inserted from above or up to 12 loose tube cables with max. 288 fibers can be inserted from the front.
Dummy front panel To close off unused 7 HP
module slots
Construction Box
Aluminium with permanently installed runners for the built-in modules
Excess-length
For clear organisation of the
drawer
loose tube reserves and securing, can be pulled out to the rear 19"/4 RU
Dimensions
176 mm x 483 mm x 295 mm (H x W x D)
Accessories 1 x M20 cable gland Rack – rear view
5 x patch cord routing
Designation
Order no.
GigaLine® Compact rack
LKD 9D50 0000 0000
Loose tube guide plate
LKD 9D50 0005 0000
Dummy front panel 7 HP
LKD 9D50 0004 0000
Rack for GigaLine® trunk cables – rear view
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter DataCenter 197
GigaLine®
Compact fiber optic module
Built-in module for pre-assembled breakout cables, 3 RU/7 HP
Description
Configuration
Built-in module, available with 3, 6 and 12 slots.
Couplings
Including excess-length cassette.
SC Duplex, ST, E2000, FC-PC, MT-RJ, LC Duplex, LC-Quad
Construction
Accessories
Module rack
Aluminium
Labelling strips
Front panel
Aluminium, with mounting screws
Cable ties
Capacity
For up to 24 fibers
Dimensions
7 HP/1 RU 128 mm x 35 mm x 240 mm (H x W x D)
Singlemode Number of fibers
SC Duplex, blue Plastic/Cer
LCD, blue Plastic/Cer
E2000, blue Plastic/Cer
6
LKD 9D52 0000 0000
LKD 9D52 0008 0000
LKD 9D52 0011 0000
12
LKD 9D52 0001 0000
LKD 9D52 0009 0000
LKD 9D52 0012 0000
24
LKD 9D52 0010 0000 (LC-Quad)
Multimode SC Duplex, beige Plastic/PhBz
LC Duplex, beige Plastic/PhBz
6
LKD 9D52 0016 0000
LKD 9D52 0024 0000
LKD 9D52 0XXX 0000
LKD 9D52 0XXX 0000
12
LKD 9D52 0017 0000
LKD 9D52 0025 0000
LKD 9D52 0XXX 0000
LKD 9D52 0XXX 0000
LKD 9D52 0026 0000 (LC-Quad)
LKD 9D52 0036 0000 (LC-Quad)
LKD 9D52 0037 0000 (LC-Quad)
Number of fibers
24 Further connectors available on request
www.leoni-infrastructure-datacom.com
LC Duplex, aqua Plastic/Cer
LC Duplex, heather violet Plastic/Cer
GigaLine® FO connectivity
GigaLine® Compact trunk module
198
GigaLine®
Compact fiber optic module
Built-in module for splicing solutions
GigaLine® Compact splice module Description
Optical characteristics
Built-in module, available with 3, 6 and 12 slots.
Insertion loss typ
For all fiber types
0.2 dB
(primary and secondary coating) acc. to the DIN IEC 60304
G62.5/125 OM1e
> 40 dB
colour code ready for splicing for fast and secure installation.
G50/125
OM2e
> 40 dB
G50/125
OM3
> 40 dB
G50/125
OM4
> 40 dB
Including splice cassette and excess-length cassette. The buffered fiber pigtails are inserted, stripped and coloured
Return loss typ.
Construction Aluminium
E9..10/125 OS2
> 50 dB
Front panel
Aluminium, with mounting screws
E9..10/125 OS2 APC
> 70 dB
Pigtails
Up to 24 pigtails ready for splicing and
Module rack
Dimensions
plugged in (colours acc. to DIN IEC 60304)
Configuration
7 HP/1 RU
Couplings
The couplings can be retrofitted at any time
128 mm x 35 mm x 240 mm (H x W x D) Accessories Labelling strips
Cable ties for securing the loose tubes Crimp splice protective holder Protective tube for loose tubes 90 cm
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter DataCenter 199
Singlemode OS2e E9.. 10/125 Number of fibers
SC Duplex, blue Met/Cer
LC Duplex, blue Plastic/Cer
E2000, blue Plastic/Cer
6
LKD 9D51 0003 0000
LKD 9D51 0010 0000
LKD 9D51 0014 0000
12
LKD 9D51 0036 0000
LKD 9D51 0011 0000
LKD 9D51 0015 0000
24
LKD 9D51 0012 0000 (LC-Quad)
Multimode OM1e G62.5/125 Number of fibers
SC Duplex Plastic/PhBz
LC Duplex Plastic/PhBz
6
LKD 9D51 0071 0000
LKD 9D51 0077 0000
12
LKD 9D51 0072 0000
LKD 9D51 0078 0000
24
LKD 9D51 0079 0000 (LC-Quad)
Number of fibers
SC Duplex Plastic/PhBz
LC Duplex Plastic/PhBz
6
LKD 9D51 0023 0000
LKD 9D51 0029 0000
12
LKD 9D51 0024 0000
LKD 9D51 0030 0000
24
LKD 9D51 0031 0000 (LC-Quad)
Multimode OM3 G50/125 Number of fibers
SC Duplex Plastic/PhBz
LC Duplex, aqua Plastic/Cer
6
LKD 9D51 0039 0000
LKD 9D51 00XX 0000
12
LKD 9D51 0040 0000
24
LKD 9D51 00XX 0000 LKD 9D51 0092 0000 (LC-Quad)
Multimode OM3e G50/125 Number of fibers
SC Duplex Plastic/PhBz
LC Duplex, heather violet Plastic/Cer
6
LKD 9D51 0055 0000
LKD 9D51 00XX 0000
12
LKD 9D51 0056 0000
24 Other configurations on request
www.leoni-infrastructure-datacom.com
LKD 9D51 XXXX 0000 LKD 9D51 0093 (LC-Quad)
GigaLine® FO connectivity
Multimode OM2e G50/125
200
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 201
GigaLine® Office and floor distributors Multifunctional housing for FTTD/FTTO cabling
Network installations are increasingly being implemented
GigaLine® stands for a high degree of flexibility:
with disturbance-proof fiber optic systems technology
■■
The GigaLine® office and floor distributors can be optionally
with future capabilities. This allows EMC problems as well
equipped with splice cassettes and/or distributor plates for
as different earthing potentials to be avoided for cabling
holding fiber optical couplings
reaching through whole buildings.
■■
When a fiber optic cabling system with a star structure is used
■■
Holds up to 288 fibers
in a building, the long ranges involved make it possible to
■■
The buffered fiber pigtails are coloured acc. to the DIN IEC
Later modifications to the components used are possible at any time
60304 colour code for fast and reliable installation
dispense with active components on the individual floors. 19"
The pigtail buffered fibers in the splice cassette are stripped and ready for splicing
as the associated power supply are no longer necessary. ■■
The incoming and outgoing fiber optic cables are fixed to a strain relief strip in the housing
The space-saving office and floor distributors are perfectly suited for the transitions from high-fiber backbone cables to
■■
The cable entries are sealed via brush strips or PG cable glands
breakout cables for workplace cabling. They are easy to install
■■
Housings have one removable/lockable swing door
and offer space-saving organisation and optimum protection
■■
Housing colour: Light grey RAL 7035
for fiber optic systems engineering. GigaLine® office and floor distributor ➔ Are tailored to the customer's requirements and supplied fully assembled ➔ Are available in 2 sizes
Office 1
Office 4
Office 5
Office 2
Office 6
Office 3
Office 7
Basement
www.leoni-infrastructure-datacom.com
GigaLine® FO connectivity
distributor cabinets and separate security areas (rooms) as well
■■
202
GigaLine®
Fiber optic office and floor distributor
Wall distributor for up to 4 or 24 splice cassettes
GigaLine® wall distributor size A Application
Dimensions
Space-saving distributor cabinets for Fiber-To-The-Office or
Size A
300 mm x 300 mm x 85 mm (H x W x D)
Fiber-To-The-Desk cabling systems. Suitable for distributing up to 24 channels (48 fibers).
Configuration Optionally only with couplings for pre-assembled trunks,
Features
as splice box or combined
For up to 4 splice cassettes with a total of 48 fibers. The buffered fiber pigtails are inserted, stripped and coloured acc. to the DIN
Accessories
IEC 60304 colour code (primary and secondary coating) ready
Up to 4 splice cassettes
for splicing for fast and reliable installation.
With crimp splice protective holder, buffered fiber strain relief and cover
Construction ■■
Powder-coated steel panel, colour Light grey RAL 7035
■■
Cable entry from above and below possible
■■
4 cable entries either as M20/M25 or strip brush
■■
Door with lock or bolt
■■
Weight approx. 4 kg
Up to 24 couplings: LCD, SCD or E2000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 203
Application
Dimensions
Space-saving distributor cabinets for Fiber-To-The-Office or
Size B
600 mm x 425 mm x 220 mm (H x W x D)
Fiber-To-The-Desk cabling systems. Suitable for distributing up to 144 channels (288 fibers).
Configuration See distributor A
Features For up to 24 splice cassettes for up to 288 fibers. The buffered
Accessories
fiber pigtails are inserted, stripped and coloured (primary and
Up to 24 splice cassettes with crimp splice protective holder,
secondary coating) acc. to the DIN IEC 60304 colour code ready
buffered fiber strain relief and cover
for splicing for fast and secure installation.
or up to 96 ST or LCD couplings or up to 48 SCD couplings with the corresponding number
Construction ■■
Powder-coated steel panel, colour Light grey RAL 7035
■■
Cable entry from above and below possible
■■
4 cable entries either as M20/M25 or strip brush
■■
Door with lock or bolt
■■
Weight approx. 7 kg
www.leoni-infrastructure-datacom.com
of splice cassettes
GigaLine® FO connectivity
GigaLine® wall distributor size B
204
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 205
GigaLine® Fiber-To-The-Desk (FTTD) wall outlets
Compact fiber optic connectivity – high performance,
GigaLine® flush-mounted outlet
immunity to disturbances, future capabilities
The flush-mounted outlet can be installed in ducts or,
Of course, the GigaLine® system also includes comprehensive
as the name suggests, mounted flush.
solutions for fiber-to-the-desk. Here it is possible to use a wide range of wall outlets with the corresponding installation
Special features:
materials for surface mounting and installation in ducts.
■■
As a result of a specific outlet design, bending never goes below
■■
Can be equipped with up to two duplex or four simplex couplings
the fiber keeps its full functionality even in the long term: A defined bending radius for the fiber ensures the service life
■■
An effective strain relief for cables and pigtails and clean
■■
by the cable reservoir and the cable guide ■■
The outlet has a downward inclination of 10°. This ensures optimum protection against mechanical stress
guidance within the outlet ensure minimum strain on the fiber and preservation of the physical characteristics ■■
The bending radius of the fiber of at least 30 mm is ensured
■■
The dimensions of the outlets are as small as possible
The universal carrying frame is compatible with usual mounting cups
■■
All current connecting techniques are supported: ➔ Assembly of fiber optic plugs on site ➔ Use of pre-assembled cables ➔ Splicing of buffered fiber pigtails
GigaLine® flush-mounted outlet
Lebensdauer (Jahre)
10 000
100
25 Jahre 1
– 5 loops – 4 loops
0,01
– 3 loops – 2 loops – 1 loop
0,0001 10
15
20
25
Biegeradius (mm)
www.leoni-infrastructure-datacom.com
30
35
GigaLine® FO connectivity
■■
Possible types of coupling: SC Duplex, ST Simplex, E 2000, LC Duplex
the admissible bending radii of the fibers, thus ensuring that
206
GigaLine®
FTTD wall outlets
for surface/flush mounting
GigaLine® wall outlet for surface mounting
GigaLine® wall outlet for flush mounting
Features
Features
Wall outlet for surface mounting.
Wall outlet for mounting in ducts and for underfloor mounting.
■■
Downward outlet direction
■■
Downward outlet direction (at an angle of 10°)
■■
Splice tray for four splices
■■
Termination of up to 4 fibers
■■
For 2 SC Duplex or LC Quad couplings
■■
Bending radius > 30 mm in combination with cable
■■
Cover with screw as access protection
■■
Cable entry for 3–10 mm cables
■■
Adherence to the bending radii of approx. 30 mm
reservoir KR or cable guide KF ■■
thanks to guided fiber paths
Colour: Oyster white RAL 1013
Optical characteristics Insertion loss typ.
Optical characteristics
G50/125
OM3
0.2 dB
E9..10/125 OS2
0.2 dB
G50/125
> 40 dB
Insertion loss
G50/125
typ.
E9..10/125 OS2
0.2 dB
E9..10/125 OS2
> 50 dB (PC)
Return loss
G50/125
> 40 dB
> 70 dB (APC)
typ.
E9..10/125 OS2
> 50 dB (PC)
Dimensions
> 70 dB (APC)
114 mm x 85 mm x 41 mm (H x W x D)
OM3
0.2 dB
OM3
Return loss typ.
OM3
Dimensions 120 mm x 80 mm x 25 mm (H x W x D)
Scope of delivery Equipped with 2 fiber optic couplings
Accessories
With labelling insert (enclosed)
Cable ties, coupling protection, wall mounting set
Designation GigaLine® wall outlet for surface mounting (1 piece)
Configuration
Order no. OS2 E9..10/125
OM3 G50/125
SC Duplex Plastic/Cer LKD 9D71 0020 0000 SC Duplex Plastic/PhBz LC Quad Plastic/Cer
LKD 9D71 0021 0000 LKD 9D71 0022 0000
LC Quad Plastic/PhBz
Designation GigaLine® wall outlet for flush mounting (1 piece)
Configuration
Order no.
2 LC Duplex Plastic/PhBz
LKD 9FK0 3026 0000
2 SC Duplex Plastic/PhBz
LKD 9FK0 3003 0000
2 SC Duplex Met/Cer
LKD 9FK0 3006 0000
4 ST Simplex Met/PhBz
LKD 9FK0 3001 0000
LKD 9D71 0023 0000 Without pigtails
GigaLine® wall outlet for surface mounting (1 piece)
SC Duplex Plastic/Cer LKD 9D72 0020 0000 SC Duplex Plastic/PhBz LKD 9D72 0021 0000 LC Quad Plastic/Cer
LKD 9D72 0022 0000
LC Quad Plastic/PhBz LKD 9D72 0023 0000 www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 207
GigaLine®
FTTD wall outlets
Cable reservoir/splice tray
GigaLine® splice tray for cable reservoir KR
Features
Features
For flush-mounted outlet to hold excess cable lengths in
For storing fiber optic splices when splicing plug pigtails.
the duct and/or safety reserves (up to 4 x 1 m for an overall
The separate storage of splice reserve and working reserve
diameter of 3 mm).
protects the sensitive splice area.
■■
Min. bending radius > 30 mm
■■
Direction-independent cable entry with cable tie strain relief
■■
on entry and exit side
Can be equipped with one or two splice holders for 4 fusion splices or mechanical splice connectors
■■
Snaps into cable reservoir KR
Dimensions 76 mm x 151 mm x 50/55 mm (H x W x D) 50 mm installation depth (KR50), 55 mm installation depth (KR55)
Designation
Order no.
Designation
Order no.
GigaLine® cable reservoir KR50 (1 piece)
LKD 9FK0 3007 0000
GigaLine® splice tray for cable reservoir KR (1 piece)
LKD 9FK0 3029 0000
GigaLine® cable reservoir KR55 (1 piece)
LKD 9FK0 3008 0000
www.leoni-infrastructure-datacom.com
GigaLine® FO connectivity
GigaLine® cable reservoir KR
208
GigaLine®
FTTD outlet for cable ducts
for installation in ducts
GigaLine® outlet EK for cable ducts Features
General characteristics
Extremely compact outlet for horizontal or vertical installation
■■
in ducts.
Can be equipped with 1 duplex coupling or 2 simplex couplings
Termination of 1 duct/2 fibers.
■■
Possible types of coupling: SC Duplex, E 2000, LC Quad
■■
Outlet direction: Downwards at an angle of 45°, defined
■■
bending radius in conjunction with suitable mounting bracket MH
to the minimum bending radius ■■
■■
Strain relief using cable ties
■■
Central plate 50 mm x 50 mm
The integrated cable guide guarantees adherence The universal central plate can be combined with various switch ranges
■■
Both cables with pre-assembled plugs and plugs assembled on site can be used
Designation
Configuration
Order no.
GigaLine® outlet EK for cable ducts (1 piece)
1 LC Quad Plastic/PhBz
LKD 9FK0 3031 0000
1 SC Duplex Plastic/PhBz LKD 9FK0 3012 0000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 209
GigaLine®
FTTD mounting bracket for installation in ducts
for outlet EK for cable ducts
Mounting bracket MH for vertical installation
Mounting bracket MH for horizontal installation
Features
Mounting options
For space-saving installation of the outlet EK for cable ducts.
T-slot mounting
Horizontal or vertical,
The mounting bracket is easy to install and guarantees
fits ducts from Thealit, OBO/
adherence to the required bending radii.
Bettermann, ASYCO and Alusor
■■
Bracket for horizontal or vertical installation with 50 mm
Design
and 55 mm installation depths available
Height 50 mm (MH50) Height 55 mm (MH55)
Designation
Order no.
GigaLine® horizontal mounting bracket MH50 (1 piece) LKD 9FK0 3014 0000 GigaLine® horizontal mounting bracket MH55 (1 piece) LKD 9ZK0 3015 0000 GigaLine® vertical mounting bracket MH50 (1 piece)
LKD 9FK0 3016 0000
GigaLine® vertical mounting bracket MH55 (1 piece)
LKD 9ZK0 3017 0000
www.leoni-infrastructure-datacom.com
GigaLine® FO connectivity
GigaLine® mounting bracket MH
210
GigaLine FO patch cords / trunk cables ®
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 211
GigaLine® FO patch cords / trunk cables
211
o dc o dc o dc dc o dc o dc i i o dc i o dc i
Fiber optic patch cord, breakout
212
Fiber optic patch cord, MiniZip
214
Fiber optic patch cord, LC/PC Uniboot
215
Fiber optic patch cord, MTP
216
• MTP I-F(ZN)H 1x12 • MTP I-F(ZN)HH 2x12
GigaLine® Trunk – pre-assembled trunk cables
219
Fiber optic trunk cable, mini breakout
220
Fiber optic trunk cable, breakout
222
Fiber optic trunk cable, outdoor
224
Fiber optic trunk cable, universal
226
Office DataCenter Industry
www.leoni-infrastructure-datacom.com
GigaLine® FO patch cords / trunk cables
GigaLine® FO patch cords
212
GigaLine®
Fiber optic patch cord, breakout
Type KL-I-V(ZN)HH
Breakout patch cord OS2 equipped with LC Duplex, SC Duplex, SC Simplex, E-2000 Simplex
GigaLine® Patch Figure 0 Construction Buffered fiber
Mechanical characteristics Two semi-tight buffered fibers with strain
Bending radius
static
35 mm
relief as breakout elements (diam. 2.1 mm)
(over flat side)
dynamic
65 mm
Single element
30 mm
running parallel under one outer sheath Colour: Orange (multimode), yellow (singlemode)
Optical characteristics (typical)
Strain relief
Aramid
Insertion loss
For all fiber types
0.2 dB
Cable sheath
Halogen-free, flame-retardant compound
Return loss
G62.5/125 OM1e
> 40 dB
Colour of sheath
OM1e, OM2, OM2e ● Orange
G50/125
OM2e
> 40 dB
OM3
> 40 dB
OS2
● Yellow
G50/125
OM3
● Aqua
G50/125
OM4
> 40 dB
● Heather violet
E9..10/125
OS2
> 50 dB
OM4 Dimensions
E9..10/125 OS2 APC
Overall cable diameter 3.1 x 5.2 mm
Thermal characteristics Transport/storage –25 °C up to +70 °C Installation
–5 °C up to +50 °C
Operating temp.
–10 °C up to +70 °C
> 70 dB
Fire performance Flame retardancy IEC 60332-1/IEC 60332-3-24 Halogen-free
IEC 60754-1
Smoke density
IEC 61034
Outer sheath Strain relief Tight buffered fiber Subcable sheath
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter DataCenter 213
Length m
OM1e G62.5/125 µm
OM2e G50/125 µm
OM3 G50/125 µm
OM4 G50/125
OS2 E9..10/125
Configuration ST-ST (IEC 61754-2) 1.0
LKD 9A12 0290 0000
LKD 9A11 0238 0000
–
–
LKD 9A13 0237 0000
1.5
LKD 9A12 0291 0000
LKD 9A11 0239 0000
–
–
LKD 9A13 0238 0000
2.0
LKD 9A12 0403 0000
LKD 9A11 0240 0000
–
–
LKD 9A13 0239 0000
2.5
LKD 9A12 0292 0000
LKD 9A11 0241 0000
–
–
LKD 9A13 0240 0000
3.0
LKD 9A12 0404 0000
LKD 9A11 0242 0000
–
–
LKD 9A13 0241 0000
5.0
LKD 9A12 0293 0000
LKD 9A11 0243 0000
–
–
LKD 9A13 0242 0000
7.5
LKD 9A12 0294 0000
LKD 9A11 0244 0000
–
–
LKD 9A13 0243 0000
10.0
LKD 9A12 0295 0000
LKD 9A11 0245 0000
–
–
LKD 9A13 0244 0000
1.0
LKD 9A12 0265 0000
LKD 9A11 0201 0000
LKD 9A11 1042 0000
LKD 9A11 1111 0000
LKD 9A13 0768 0000
1.5
LKD 9A12 0266 0000
LKD 9A11 0202 0000
LKD 9A11 1043 0000
LKD 9A11 1112 0000
LKD 9A13 0769 0000
2.0
LKD 9A12 0256 0000
LKD 9A11 0203 0000
LKD 9A11 1044 0000
LKD 9A11 1113 0000
LKD 9A13 0770 0000
2.5
LKD 9A12 0267 0000
LKD 9A11 0204 0000
LKD 9A11 1045 0000
LKD 9A11 1114 0000
LKD 9A13 0771 0000
3.0
LKD 9A12 0401 0000
LKD 9A11 0205 0000
LKD 9A11 1046 0000
LKD 9A11 1115 0000
LKD 9A13 0772 0000
5.0
LKD 9A12 0402 0000
LKD 9A11 0206 0000
LKD 9A11 1047 0000
LKD 9A11 1116 0000
LKD 9A13 0773 0000
7.5
LKD 9A12 0268 0000
LKD 9A11 0207 0000
LKD 9A11 1048 0000
LKD 9A11 1117 0000
LKD 9A13 0774 0000
10.0
LKD 9A12 0269 0000
LKD 9A11 0208 0000
LKD 9A11 1049 0000
LKD 9A11 1118 0000
LKD 9A13 0775 0000
Configuration LC Duplex/LC Duplex (IEC 61754-20) 1.0
LKD 9A12 0278 0000
LKD 9A11 0220 0000
LKD 9A11 1051 0000
LKD 9A11 1103 0000
LKD 9A13 0759 0000
1.5
LKD 9A12 0279 0000
LKD 9A11 0221 0000
LKD 9A11 1052 0000
LKD 9A11 1104 0000
LKD 9A13 0760 0000
2.0
LKD 9A12 0362 0000
LKD 9A11 0222 0000
LKD 9A11 1053 0000
LKD 9A11 1105 0000
LKD 9A13 0761 0000
2.5
LKD 9A12 0280 0000
LKD 9A11 0223 0000
LKD 9A11 1054 0000
LKD 9A11 1106 0000
LKD 9A13 0762 0000
3.0
LKD 9A12 0281 0000
LKD 9A11 0224 0000
LKD 9A11 1055 0000
LKD 9A11 1107 0000
LKD 9A13 0763 0000
5.0
LKD 9A12 0282 0000
LKD 9A11 0225 0000
LKD 9A11 1056 0000
LKD 9A11 1108 0000
LKD 9A13 0764 0000
7.5
LKD 9A12 0283 0000
LKD 9A11 0226 0000
LKD 9A11 1057 0000
LKD 9A11 1109 0000
LKD 9A13 0765 0000
10.0
LKD 9A12 0284 0000
LKD 9A11 0227 0000
LKD 9A11 1058 0000
LKD 9A11 1110 0000
LKD 9A13 0766 0000
www.leoni-infrastructure-datacom.com
GigaLine® FO patch cords / trunk cables
Configuration SC Duplex/SC Duplex (IEC 61754-4)
214
GigaLine®
Fiber optic patch cord, MiniZip Type KL-I-V(ZN)H
MiniZip patch cord OS2 equipped with LC Duplex, SC Duplex, SC Simplex, E-2000 Simplex
GigaLine® Patch MiniZip OS2 GigaLine® Patch MiniZip OM3 GigaLine® Patch MiniZip OM4
MiniZip patch cord OM3/OM2e/OM4 equipped with LC Duplex, SC Duplex, SC Simplex, E-2000 Simplex, MU
Construction Cable type
KL-I-V(ZN)H 2G50/125
Optical characteristics Insertion loss For all fiber types
Buffered fiber
Two semi-tight buffered fibers with strain
Return loss
> 50 dB (PC)
relief in figure 8 sheath with separator
> 70 dB (APC)
(1.8 mm x 3.7 mm)
Patch cord OM3/OM4 > 40 dB
Strain relief
Aramid
Cable sheath
Halogen-free, flame-retardant compound
Colour of sheath
OM1e, OM2, OM2e ● Orange
Cable diameter
0.2 dB (typical)
Patch cord OS2
Laser bandwidth
● Yellow
OM3
● Aqua
OM4
● Heather violet
1.8 mm
Thermal characteristics Transport/storage –25 °C up to +70 °C –5 °C up to +50 °C
Operating temp.
–10 °C up to +70 °C
Mechanical characteristics Bending radius static
30 mm
(over flat side)
60 mm
dynamic
2,000 MHz x km
Patch cord OM4
4,700 MHz x km
Fire performance Flame retardancy IEC 60332-1/IEC 60332-3-24
OS2
Installation
Patch cord OM3
Halogen-free
IEC 60754-1
Smoke density
IEC 61034
Configuration Patch cord OS2
LC Duplex, SC Duplex, SC Simplex, E-2000 Simplex
Patch cord
LC Duplex, SC Duplex, SC Simplex,
OM3/OM4
E-2000 Simplex, MU
Cable length See table, other plug types and lengths on request
GigaLine® Patch MiniZip OS2 E9..10/125 Length 2m
2 x LC/PC Duplex
2 x LC/APC Duplex
2 x SC/PC Duplex
2 x SC/APC Duplex
2 x E2000/PC Duplex
2 x E2000/APC Duplex
LKD 9A13 0033 0000
LKD 9A13 0090 0000
LKD 9A13 0091 0000
LKD 9A13 0092 0000
LKD 9A13 0093 0000
LKD 9A13 0094 0000
GigaLine® Patch MiniZip OM3 G50/125 Length 2m
2 x LC Duplex
2 x SC Duplex
2 x E2000 Duplex
2 x MU
LKD 9A11 0699 0000
LKD 9A11 0700 0000
LKD 9A11 0701 0000
LKD 9A11 0702 0000
GigaLine® Patch MiniZip OM4 G50/125 Length 2m
2 x LC Duplex
2 x SC Duplex
2 x E2000 Duplex
2 x MU
LKD 9A11 0693 0000
LKD 9A11 0694 0000
LKD 9A11 0695 0000
LKD 9A11 0696 0000
www.leoni-infrastructure-datacom.com
Office
DataCenter DataCenter
Industry
215
GigaLine®
Fiber optic patch cord, LC/PC-Uniboot
Type KL-I-V(ZN)H
Uniboot patch cord OS2 equipped with 2 x LC DuplexUniboot Uniboot patch cord OM4 equipped with 2 x LC DuplexUniboot
GigaLine® Patch LCD-Uniboot OS2 GigaLine® Patch LCD-Uniboot OM3 GigaLine® Patch LCD-Uniboot OM4 Construction Cable type
KL-I-V(ZN)H
Optical characteristics Insertion loss < 0,4 dB
Buffered fiber
Two semi-tight buffered fibers under a
Return loss
0.2 dB (typical)
Patch cord OS2
> 50 dB (PC) > 70 dB (APC)
common sheath (round diam. 2.8 mm)
Strain relief
Aramid
Patch cord OM3/OM4 > 40 dB
Cable sheath
Halogen-free, flame-retardant compound
Colour of sheath
OM1e, OM2, OM2e ● Orange
Cable diameter
OS2
● Yellow
OM3
● Aqua
OM4
● Heather violet
2.8 mm
Thermal characteristics Transport/storage
–25 °C up to +70 °C
Installation
–5 °C up to +50 °C
Operating temp.
–10 °C up to +70 °C
Laser bandwidth
Patch cord OM3
1,500 MHz x km
Patch cord OM4
4,700 MHz x km
Fire performance Flame retardancy
IEC 60332-1/IEC 60332-3-24
Halogen-free
IEC 60754-1
Smoke density
IEC 61034
Configuration LC Duplex Uniboot Cable length See table, other plug types and lengths on request
Mechanical characteristics Bending radius static
30 mm
(over flat side)
dynamic
60 mm
Tensile strength
300 N
GigaLine® Patch LCD-Uniboot OS2 E9..10/125
GigaLine® Patch LCD-Uniboot OM3 G50/125
GigaLine® Patch LCD-Uniboot OM4 G50/125
Configuration 2 x LC Duplex Uniboot
Configuration 2 x LC Duplex Uniboot
Configuration 2 x LC Duplex Uniboot
LKD 9A13 0713 0000
LKD 9A11 0866 0000
LKD 9A11 0875 0000
2.0
LKD 9A13 0715 0000
LKD 9A11 0868 0000
LKD 9A11 0877 0000
3.0
LKD 9A13 0717 0000
LKD 9A11 0870 0000
LKD 9A11 0879 0000
5.0
LKD 9A13 0718 0000
LKD 9A11 0871 0000
LKD 9A11 0880 0000
7.5
LKD 9A13 0719 0000
LKD 9A11 0872 0000
LKD 9A11 0881 0000
10.0
LKD 9A13 0720 0000
LKD 9A11 0873 0000
LKD 9A11 0882 0000
Length m 1.0
www.leoni-infrastructure-datacom.com
GigaLine® FO patch cords / trunk cables
Uniboot patch cord OM3 equipped with 2 x LC DuplexUniboot
216
GigaLine®
Fiber optic patch cord, MTP
Type KL-I-F(ZN)H/KL-I-F(ZN)HH
MTP/MPO patch cord
GigaLine® Patch MTP I-F(ZN)H 1x12 GigaLine® Patch MTP I-F(ZN)HH 2x12 Description
Thermal characteristics
Connection-ready MTP patch cord – assembled
Transport/storage
–25 °C up to +70 °C
at both ends with one or two MTP plugs (female) or one MTP
Installation
–5 °C up to +50 °C
(female) to six LC Duplex Uniboot plugs.
Operating temp.
–10 °C up to +70 °C
Construction
Mechanical characteristics
Cable type
Bending radius
KL-I-F(ZN)H 1x1 or KL-I-F(ZN)HH 2x12
Strain relief
Aramid
Cable sheath
Halogen-free, flame-retardant compound
Colour of sheath
OM3 ● Aqua | OM4 ● Heather violet
Cable diameter
3.0 mm (for 1x12) 8.9 mm (for 2x12)
■■
static 35 mm | dynamic 65 mm
Tensile strength KL-I-F(ZN)H 1x12
300 N
KL-I-F(ZN)HH 2x12
600 N
0.3 dB (MTP)
For all fiber types
0.2 dB (LCDU) For all fiber types
In DataCenters as a patch cord for applications acc. to
Return loss
GigaLine® Patch MTP–6LCDU (fanout) for multimode applications via two fibers (up to 10GBASE-SR)
■■
KL-I-F(ZN)HH 2x12
Insertion loss
ISO/IEC 11801 and EN 50173 (2nd edition) ■■
static 35 mm | dynamic 65 mm
Optical characteristics (typical)
Field of application ■■
KL-I-F(ZN)H 1x12
OM3/OM4
> 20 dB (MTP)
OM3/OM4
> 40 dB (LCDU)
GigaLine® Patch 1MTP–1MTP for multimode applications
Fire performance Flame retardancy
IEC 60332-1/IEC 60332-3-24
via 2 x 4 fibers (40GBASE-SR4)
Halogen-free
IEC 60754-1
GigaLine Patch 2MTP–2MTP for multimode applications
Smoke density
IEC 61034
via 2 x 10 fibers (100GBASE-SR10) Equipment on side A
Equipment on side B
Order no.
GigaLine® Patch 12
Designation OM3 6 LC/DU–1 MTP*
6x LC/Dx-Uniboot OM3
MTP female
12 OM3
LKD 9R72 1002 0000
GigaLine® Patch 12
OM4 6 LC/DU–1 MTP*
6x LC/Dx-Uniboot OM4
MTP female
12 OM4
LKD 9R72 4002 0000
GigaLine® Patch 12
OM3 MTP–MTP*
MTP female
12 OM3
MTP female
12 OM3
LKD 9R71 5xxx 0000
GigaLine® Patch 12
OM4 MTP–MTP*
MTP female
12 OM4
MTP female
12 OM4
LKD 9R71 3xxx 0000
GigaLine® Patch 2x12 OM3 MTP–MTP*
2x MTP female 2x12 OM3
2x MTP female 2x 12 OM3
LKD 9R71 6xxx 0000
GigaLine® Patch 2x12 OM4 MTP–MTP*
2x MTP female 2x12 OM4
2x MTP female 2x 12 OM4
LKD 9R71 4xxx 0000
* Logically crossed xxx = Length in m. 1 piece per packing unit.
www.leoni-infrastructure-datacom.com
Office Office
Industry
DataCenter DataCenter
GigaLine® FO patch cords / trunk cables
217
www.leoni-infrastructure-datacom.com
218
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 219
GigaLine® Trunk – pre-assembled trunk cables Safely through "thick and thin"
Ready-to-connect units are at the heart of our fiber optic
Time is money
system technology. Our pre-assembled cables (GigaLine®
GigaLine® trunk cables stand for reliable and calculable
trunk cables) guarantee rapid, reliable and economical
installation. Installations times are short. All GigaLine® 19"
installation. Coordinated system components ensure
trunk cable housings have recesses on the back in which the
the quality of the transmission line. Installations times
divider head is mounted to prevent rotation. The fast assembly
are calculable.
minimises any downtime e.g. as a result of an IT system's
A lasting solution
or fitting the plugs on site, which would sometimes involve
On-site installation frequently takes place under unfavourable
adverse conditions. This also does away with costly outlay on
conditions. Moisture, dirt and poorly accessible areas are
splicing equipment and specially trained staff. GigaLine® trunk
nothing unusual. This is why we use an IP67 protection
cables can also be used as a cable pre-assembled at one end.
class wire ripple tube for our GigaLine® trunk cables with universal or outdoor cable. Thanks to their particularly strong
Fields of application
construction with an encapsulated cable divider and bolted-on
GigaLine® trunk cables are ideal for backbone cabling in
wire ripple tube, our trunk cables are protected against water
the primary and secondary segments as well as for collapsed
spray and non-crush. They are ideal for harsh construction
backbone cabling.
site environments and outdoor cabling systems. Indoor cables are fitted with dust protection without strain relief to prevent
Quality means maximum safety
soiling of the plugs.
The plugs are assembled with high quality ceramic ferules under clean conditions. The plug faces are polished to the
GigaLine® trunk cables ensure that ambient conditions do not
highest standard, thereby ensuring outstanding plug transitions
affect the quality of the transmission lines – either during or
in reproducible quality (input and return attenuation). A test
after installation. The feeder aid is flexible and has a small cross
certificate with the attenuation readings of each fiber is
section. This enables pre-assembled trunk cables to be easily fed
supplied with the product. There is also the option of having
into tight, twisty manholes and installation channels. A frictional
OTDR measurements.
connection is formed with the divider head. It acts on the strain relief elements and the sheaths. The fibers thereby remain free of tension. The divider head design guarantees the stability of the physical parameters and a long service life.
www.leoni-infrastructure-datacom.com
GigaLine® FO patch cords / trunk cables
temporary shutdown. There is no need for splicing the cables
220
GigaLine®
Fiber optic trunk cable, mini breakout Type KL-I-V(ZN)H
Pre-assembled at both ends
GigaLine® Trunk Mini-Breakout Optical characteristics
Construction Single elements
Up to 12 semi-tight buffered fibers
Insertion loss typ.
For all fiber types
0.2 dB
Return loss typ.
with diameter 0.9 mm G62.5/125 OM1e
> 40 dB
Blue (1), orange (2), green (3), brown (4),
G50/125
OM2e
> 40 dB
grey (5), white (6), red (7), black (8), yellow (9),
G50/125
OM3
> 40 dB
violet (10), pink (11), turquoise (12)
G50/125
OM4
> 40 dB
Aramid threads
E9..10/125 OS2
> 50 dB
Halogen-free, flame-retardant compound
E9..10/125 OS2 APC
> 70 dB
Colour code acc. to EIA/TIA 598C
Strain relief Cable sheath
Patch element
OM1e, OM2e
● Orange
OS2
● Yellow
Mechanical characteristics
OM3
● Aqua
Bending radius
OM4
● Heather violet
static
10 x overall diameter
dynamic
15 x overall diameter
diam. 0.9 mm, shortest patch element 55 cm, gradation 5 cm
Fire performance
Dust protection
Protected with plastic tube
Flame retardancy
IEC 60332-1/IEC 60332-3-24
Protection class
Acc. to IP44
Halogen-free
IEC 60754-1
Smoke density
IEC 61034
Thermal characteristics Transport/storage
–25 °C up to +70 °C
Installation
–5 °C up to +50 °C
Operating temp.
–10 °C up to +50 °C
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter DataCenter 221
Plug
SC
E2000
LC
Singlemode OS2 E9..10/125 4
LKD 9Vxx x08B 0000
LKD 9Vxx x08L 0000
6
LKD 9Vxx x08C 0000
LKD 9Vxx x08M 0000
LKD 9Vxx x08E 0000
LKD 9Vxx x08O 0000
8 12
LKD 9Vxx x08N 0000
4
LKD 9Vxx x095 0000
LKD 9Vxx x09F 0000
6
LKD 9Vxx x096 0000
LKD 9Vxx x09G 0000
8
LKD 9Vxx x097 0000
12
LKD 9Vxx x098 0000
Multimode OM3 G50/125 4 6 8 12 Multimode OM1e G62.5/125 4
LKD 9Vxx x10O 0000
LKD 9Vxx x10Y 0000
6
LKD 9Vxx x10P 0000
LKD 9Vxx x10Z 0000
LKD 9Vxx x10R 0000
LKD 9Vxx x111 0000
8 12
xxx = Length in metres, measured from plug side A to plug side B Other plug types and fiber numbers on request
www.leoni-infrastructure-datacom.com
GigaLine® FO patch cords / trunk cables
Multimode OM2e G50/125
222
GigaLine®
Fiber optic trunk cable, breakout Type KL-I-V(ZN)HH
Pre-assembled at both ends
GigaLine® Trunk Breakout Construction Single elements
Optical characteristics Up to 12 buffered fibers with strain relief
Insertion loss typ
For all fiber types
0.2 dB
Return loss typ.
G62.5/125 OM1e
> 40 dB
G50/125
OM2e
> 40 dB
under one sheath, diameter 2.1 mm Strain relief
Aramid threads
Cable sheath
Halogen-free, flame-retardant compound OM1e, OM2e
● Orange
G50/125
OM3
> 40 dB
OS2
● Yellow
G50/125
OM4
> 40 dB
OM3
● Aqua
E9..10/125 OS2
> 50 dB
OM4
● Heather violet
E9..10/125 OS2 APC
> 70 dB
Patch element
Shortest patch element 55 cm,
Dust protection
Gradation 5 cm
Mechanical characteristics
Protection class
Protected with plastic tube
Bending radius
acc. to IP44
static
10 x overall diameter
dynamic
15 x overall diameter
Thermal characteristics
Fire performance
Transport/storage
–25 °C up to +70 °C
Flame retardancy
IEC 60332-1/IEC 60332-3-24
Installation
–5 °C up to +50 °C
Halogen-free
IEC 60754-1
Operating temp.
–10 °C up to +50 °C
Smoke density
IEC 61034
www.leoni-infrastructure-datacom.com
Office
Industry Industry
DataCenter DataCenter 223
Plug
SC
E2000
LC
Singlemode OS2 E9..10/125 4
LKD 9Vxx x11D 0000
LKD 9Vxx x11N 0000
8
LKD 9Vxx x11F 0000
LKD 9Vxx x11P 0000
12
LKD 9Vxx x11G 0000
LKD 9Vxx x11Q 0000
6
Multimode OM2e G50/125 4
LKD 9Vxx x127 0000
6 8 LKD 9Vxx x12A 0000
LKD 9Vxx x12K 0000
Multimode OM3 G50/125 4 6 8 12 Multimode OM1e G62.5/125 4
LKD 9Vxx x14U 0000
LKD 9Vxx x156 0000
LKD 9Vxx x15I 0000
8
LKD 9Vxx x14W 0000
LKD 9Vxx x158 0000
LKD 9Vxx x15K 0000
12
LKD 9Vxx x14Y 0000
LKD 9Vxx x15A 0000
LKD 9Vxx x15M 0000
6
xxx = Length in metres, measured from plug side A to plug side B Other plug types and fiber numbers on request
www.leoni-infrastructure-datacom.com
GigaLine® FO patch cords / trunk cables
12
224
GigaLine®
Fiber optic trunk cable, outdoor
Type KL-A-DQ(ZN)B2Y
Pre-assembled at both ends
GigaLine® Trunk A-DQ(ZN)B2Y IP67 Construction Single elements
Size of the divider head Up to 48 buffered fibers with strain relief
diameter divider
for 2–12 fibers
25 mm
under one sheath, diameter 1.8 mm
head max.
for 16–48 fibers
33 mm
Colour code
Acc. to IEC 60304
Strain relief
Non-metallic (glass rovings)
diameter pull tool
for 2–12 fibers
33 mm
Cable sheath
PE, resistant to UV rays,
max.
for 16–48 fibers
43 mm
Colour: Black Divider head
Aluminium
Mechanical characteristics
Strain relief
600 N
Bending radius
Patch element
Shortest patch element 55 cm,
static
15 x overall diameter
dynamic
20 x overall diameter
gradation 5 cm Strain relief
100 N
Dust protection
Protective tube
Protection class
Acc. to IP67
Fire performance
Thermal characteristics Transport/storage
–25 °C up to +70 °C
Installation
–5 °C up to +50 °C
Operating temp.
–25 °C up to +70 °C
Flame retardancy
IEC 60332-1/IEC 60332-3-24
Halogen-free
IEC 60754-1
Smoke density
IEC 61034
Other characteristics Longitudinally
IEC 60794-1-2 F5
watertight
Optical characteristics Insertion loss typ
For all fiber types
0.2 dB
Return loss typ.
G62.5/125 OM1e
> 40 dB
G50/125
OM2e
> 40 dB
G50/125
OM3
> 40 dB
G50/125
OM4
> 40 dB
E9..10/125 OS2
> 50 dB
E9..10/125 OS2 APC
> 70 dB
www.leoni-infrastructure-datacom.com
Office Office
Industry Industry
DataCenter 225
Plug
SC
E2000
E2000HRL
LC
Singlemode OS2 E9..10/125 4
LKD 9Vxx x005 0000
LKD 9Vxx x00J 0000
LKD 9Vxx x00Q 0000
6
LKD 9Vxx x006 0000
LKD 9Vxx x00K 0000
LKD 9Vxx x00R 0000
8
LKD 9Vxx x007 0000
LKD 9Vxx x00L 0000
LKD 9Vxx x00S 0000
12
LKD 9Vxx x008 0000
LKD 9Vxx x00M 0000
LKD 9Vxx x00T 0000
16
LKD 9Vxx x009 0000
LKD 9Vxx x00N 0000
LKD 9Vxx x00U 0000
24
LKD 9Vxx x00A 0000
LKD 9Vxx x00O 0000
LKD 9Vxx x00V 0000
LKD 9V10 0647 0000
48
LKD 9Vxx x00B 0000
LKD 9Vxx x00P 0000
LKD 9Vxx x00W 0000
LKD 9Vxx x01A 0000
Multimode OM2e G50/125 LKD 9Vxx x01B 0000
LKD 9Vxx x01P 0000
6
LKD 9Vxx x01C 0000
LKD 9Vxx x01Q 0000
8
LKD 9Vxx x01D 0000
LKD 9Vxx x025 0000
12
LKD 9Vxx x01E 0000
LKD 9Vxx x026 0000
16
LKD 9Vxx x023 0000
LKD 9Vxx x027 0000
24
LKD 9Vxx x01G 0000
LKD 9Vxx x028 0000
48
LKD 9Vxx x01H 0000
LKD 9Vxx x029 0000
Multimode OM3 G50/125 4 6 8 12
LKD 9V10 062A 0000
LKD 9Vxx x62J 0000
16 24
LKD 9Vxx x65G 0000
Multimode OM1e G62.5/125 4
LKD 9Vxx x03G 0000
LKD 9Vxx x03U 0000
6
LKD 9Vxx x03H 0000
LKD 9Vxx x03V 0000
8
LKD 9Vxx x03I 0000
LKD 9Vxx x03W 0000
12
LKD 9Vxx x03J 0000
LKD 9Vxx x03X 0000
LKD 9Vxx x03L 0000
LKD 9Vxx x03Z 0000
16 24
xxx = Length in metres, measured from plug side A to plug side B Other plug types and fiber numbers on request
www.leoni-infrastructure-datacom.com
GigaLine® FO patch cords / trunk cables
4
226
GigaLine®
Fiber optic trunk cable, universal
Type KL-U-DQ(ZN)BH
Pre-assembled at both ends
GigaLine® Trunk U-DQ(ZN)H IP67 Construction Single elements
Size of the divider head Up to 48 buffered fibers with strain relief
diameter divider
for 2–12 fibers
25 mm
under one sheath, diameter 1.8 mm
head max.
for 16–48 fibers
33 mm
Colour code
Acc. to IEC 60304
Strain relief
Non-metallic (glass rovings)
diameter pull tool
for 2–12 fibers
33 mm
Cable sheath
Halogen-free, flame-retardant compound
max.
for 16–48 fibers
43 mm
Colour: Black Divider head
Aluminium
Strain relief
600 N
Mechanical characteristics
Patch element
diam. 1.8 mm, assorted colours acc. to
Bending radius
IEC 60304, shortest patch element 55 cm,
static
15 x overall diameter
dynamic
20 x overall diameter
gradation 5 cm Strain relief
100 N
Fire performance
Dust protection
Protective tube IP67
Protection class
Acc. to IP67
Flame retardancy
IEC 60332-1/IEC 60332-3-24
Halogen-free
IEC 60754-1
Smoke density
IEC 61034
Thermal characteristics Transport/storage
–25 °C up to +70 °C
Other characteristics
Installation
–5 °C up to +50 °C
Operating temp.
–25 °C up to +70 °C
Longitudinally
IEC 60794-1-2 F5
watertight
Optical characteristics Insertion loss typ
For all fiber types
0.2 dB
Return loss typ.
G62.5/125 OM1e
> 40 dB
G50/125
OM2e
> 40 dB
G50/125
OM3
> 40 dB
G50/125
OM4
> 40 dB
E9..10/125 OS2
> 50 dB
E9..10/125 OS2 APC
> 70 dB
www.leoni-infrastructure-datacom.com
Office
Industry Industry
DataCenter DataCenter 227
Plug
SC
E2000
E2000HRL
LC
Singlemode OS2 E9..10/125 4
LKD 9Vxx x61N 0000
LKD 9Vxx x61T 0000
LKD 9Vxx x61Z 0000
LKD 9Vxx x60H 0000
6
LKD 9Vxx x61O 0000
LKD 9Vxx x61U 0000
LKD 9Vxx x620 0000
LKD 9Vxx x60I 0000
8
LKD 9Vxx x61P 0000
LKD 9Vxx x61V 0000
LKD 9Vxx x621 0000
LKD 9Vxx x60K 0000
12
LKD 9Vxx x61Q 0000
LKD 9Vxx x61W 0000
LKD 9Vxx x622 0000
LKD 9Vxx x60L 0000
24
LKD 9Vxx x61R 0000
LKD 9Vxx x61X 0000
LKD 9Vxx x623 0000
LKD 9Vxx x60M 0000
48
LKD 9Vxx x61S 0000
LKD 9Vxx x61Y 0000
LKD 9Vxx x624 0000
LKD 9Vxx x60N 0000
Multimode OM2e G50/125 LKD 9Vxx x61G 0000
LKD 9Vxx x60B 0000
6
LKD 9Vxx x61H 0000
LKD 9Vxx x60C 0000
8
LKD 9Vxx x61I 0000
LKD 9Vxx x60D 0000
12
LKD 9Vxx x61K 0000
LKD 9Vxx x60E 0000
24
LKD 9Vxx x61L 0000
LKD 9Vxx x60F 0000
48
LKD 9Vxx x61M 0000
LKD 9Vxx x60G 0000
Multimode OM3 G50/125 4
LKD 9Vxx x61A 0000
LKD 9Vxx x615 0000
6
LKD 9Vxx x61B 0000
LKD 9Vxx x616 0000
8
LKD 9Vxx x61C 0000
LKD 9Vxx x617 0000
12
LKD 9Vxx x61D 0000
LKD 9Vxx x618 0000
24
LKD 9Vxx x61E 0000
LKD 9Vxx x619 0000
48
LKD 9Vxx x61F 0000
LKD 9Vxx x60A 0000
Multimode OM4 G50/125 4
LKD 9Vxx x60U 0000
LKD 9Vxx x609 0000
6
LKD 9Vxx x60V 0000
LKD 9Vxx x610 0000
8
LKD 9Vxx x60W 0000
LKD 9Vxx x611 0000
12
LKD 9Vxx x60X 0000
LKD 9Vxx x612 0000
24
LKD 9Vxx x60Y 0000
LKD 9Vxx x614 0000
48
LKD 9Vxx x60Z 0000
LKD 9Vxx x613 0000
Multimode OM1e G62.5/125 4
LKD 9Vxx x60O 0000
6
LKD 9Vxx x60P 0000
8
LKD 9Vxx x60Q 0000
12
LKD 9Vxx x60R 0000
24
LKD 9Vxx x60S 0000
48
LKD 9Vxx x60T 0000
xxx = Length in metres, measured from plug side A to plug side B Other plug types and fiber numbers on request
www.leoni-infrastructure-datacom.com
GigaLine® FO patch cords / trunk cables
4
228
GigaLine DataCenter Links ®
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 229
GigaLine® DataCenter links GigaLine® DataCenter links
228
dc
DataCenter link
dc
DataCenter link
• DClink OS2 E9.10/125 • DClink OM3 G50/125 • DClink OM4 G50/125
232
dc
DataCenter MTP module
• DC MTP module OS2 E9..10/125 • DC MTP module OM3 G50/125 • DC MTP module OM4 G50/125
233
o dc i
Office DataCenter Industry
www.leoni-infrastructure-datacom.com
231
GigaLine® DataCentre links
230 • DClink 40/100 OM3 G50/125 • DClink 40/100 OM4 G50/125
230
GigaLine® DataCenter links Quick & easy solution for ready-to-use links in DataCenters
DataCenters have special requirements since downtimes
For transmissions up to 10 Gbit/s, fiber pairs are separated from
there can have catastrophic consequences.
the 12x fiber bundle using an MPO to LC duplex fanout (see
It must therefore be ensured that disruptions are kept to
Figure) so that 144 channels are available per rack unit.
a minimum, particularly when carrying out renovation work during operation. LEONI has developed systems for this that take these requirements into consideration right from the construction stages of a new DataCenter. As well as ensuring adherence to the applicable cabling standards, our systems also offer countless options for quick and reliable construction and renovation of DataCenters. DClink 40/100 is a cabling system that is suitable for all transmission protocols. It is delivered as a tested permanent
GigaLine® patch cord MPO-6LC-Dx (fanout)
FO link and consists of a cable with 8x12 OM3/OM4 fibers that is already equipped with a partial patch panel at both ends.
To retrofit the system for 40 Gbit/s systems (parallel transmission
The pre-assembled link just has to be installed by snapping
over 2 x 4 fibers), the fanout simply has to be replaced by simplex
it into the socket provided in the patch panel. This allows three
MPO patch cords (see Figure) with 12 fibers (24 systems per
GigaLine® DClink partial patch panels with 8 MPO couplings
rack unit).
each in the patch panel to be fitted at a single level.
GigaLine® patch cord MPO-MPO (12 OM3/OM4)
Two simplex MPO patch cords, i.e. 2x12 fibers (parallel transmission over 2 x 10 fibers) are used for 100 Gbit/s (12 systems per rack unit). VarioLine® DClink sockets with 3 GigaLine® DClink modules 40/100 Gbit/s with 8 MPO each
In contrast to conventional cabling systems in which the link has to be replaced, GigaLine® DClink offers numerous
The use of low or medium data rates of up to 10 Gbit/s and
advantages:
higher data rates of up to 40 and 100 Gbit/s can thus be
■■
replacing the patch cords (no need to modify the permanent
realised without modifications to the permanently installed
installation)
GigaLine® DClink cabling. This allows the fibers to be used both individually for applications up to 10 Gbit/s and in parallel for
■■
Rapid and economical installation as GigaLine® DClink is delivered fully assembled
40 and 100 Gbit/s. Migration or connection to the necessary transmission technology is carried out via application-specific
Migratability to all data rates used is possible by simply
■■
High reliability and quality as GigaLine® DClink is tested before leaving the factory
patch cords. ■■
Clear arrangement in spite of high packing density
www.leoni-infrastructure-datacom.com
Office Office
Industry
DataCenter DataCenter 231
GigaLine®
DataCenter link
Connection-ready links up to 100 Gbit/s
Description
DClink module
Connection-ready link – one DClink module in a high tensile
Housing
Steel panel, front Jet black RAL 9005
strength connection with a high-quality universal cable at each
Dimensions
40 mm x 135 mm x 150 mm (H x W x D)
end. The housing can be opened if necessary and the divider
Configuration
8 MTP/MPO
containing the patch elements removed and pulled through
Insertion loss
0.25 dB (typ.)
tight openings (≥ diam. 35 mm) with the help of a pull-in tube.
Return loss
OM3
> 20 dB
OM4
> 20 dB
Field of application In DataCenters acc. to ISO/IEC 11801 and EN 50173 (2nd edition).
Accessories (optional)
DClink OS3
GigaLine® DClink pull tool
For all applications from Classes >
Order no.: LKD 9R00 0008 0000
OF-100 (40 and 100 GBE), OF-300 (10 GbE), OF-500 (GbE/Fiber Channel) and OF-2000 (Fast Ethernet) DClink OM4
For all applications from Classes > OF-100(40 and 100 GBE), OF-300 (GigaLine 550), (10 GbE), OF-500 (GbE/FiberChannel) and OF-2000 (Fast Ethernet)
Colour
Designation
Cable type
GigaLine® DClink 40/100 OM3
KL-I-F(ZN)H(ZN)H 8x12 24 G50/125 2.5B1500 0.7F500 (IEC 60793-2 A1a.2)
Aqua
KL-I-F(ZN)H(ZN)H 8x12 24 G50/125 2.5B3500 0.7F500 (IEC 60793-2 A1a.3)
Heather violet
GigaLine® DClink 40/100 OM4
Configuration
8 MTP(male) – 8 MTP(male)
Strain relief
MHz x km
N
2,000 1,000 2,000
Cable sheath
Sheath diam. mm
Halogen-free and flameretardant
Order no. GigaLine® DClink OM3 G50/125
GigaLine® DClink OM4 G50/125
LKD 9R31 6xxx 0000
LKD 9R31 nxxx 0000
xxx = Length between the link modules in m. Other configurations on request. 1 piece per packing unit.
www.leoni-infrastructure-datacom.com
Laser bandwidth
14.0
GigaLine® DataCentre links
GigaLine® DClink 40/100 OM3 G50/125 GigaLine® DClink 40/100 OM4 G50/125
232
GigaLine®
DataCenter link
Connection-ready links
GigaLine® DClink OS2 E9.10/125 GigaLine® DClink OM3 G50/125 GigaLine® DClink OM4 G50/125 Description
DClink module
Connection-ready link – one DClink module in a high tensile
Housing
Steel panel, front Jet black RAL 9005
strength connection with a high-quality universal cable at each
Dimensions
40 mm x 135 mm x 150 mm (H x W x D)
end. The housing can be opened if necessary and the divider
Configuration
Fiber optic connector (see table)
containing the patch elements removed and pulled through
Insertion loss
0.2 dB (typ.)
tight openings (≥ diam. 35 mm) with the help of a pull-in tube.
Return loss
OS2
> 50 dB (PC), > 70 dB (APC)
OM3
> 40 dB
OM4
> 40 dB
Field of application In DataCenters acc. to ISO/IEC 11801 and EN 50173 (2nd edition). DClink OS2
For all applications up to Class OF-10000
Accessories (optional)
DClink OM3
For all applications from Classes
GigaLine® DClink pull tool
Order no.: LKD 9R00 0008 0000
OF-300 (10 GbE), OF-500 (GbE/Fiber Channel) and OF-2000 (Fast Ethernet) DClink OM4
For all applications from Classes > OF-300 (GigaLine 550), (10 GbE), OF-500 (GbE/FiberChannel) and OF-2000 (Fast Ethernet) Laser bandwidth
Strain relief
MHz x km
N
Designation
Cable type
GigaLine® DClink OS2
KL-U-DQ(ZN)BH 1x12 or 24 E9/125 0.36F3.5/0.22H18 (ITU G652.D)
–
GigaLine® DClink OM3
KL-U-DQ(ZN)BH 1x12 or 24 G50/125 2.5B1500 0.7F500 (IEC 60793-2 A1a.2)
2,000
GigaLine® DClink OM4
KL-U-DQ(ZN)BH 1x12 or 24 G50/125 2.5B3500 0.7F500 (IEC 60793-2 A1a.3)
4,700
Configuration
Cable sheath
Sheath diam. mm
1,000
Halogen-free and flameretardant
7.0 (12 fibers) 7.5 (24 fibers)
Order no. GigaLine® DClink OS2 E9..10/125 GigaLine® DClink OM3 G50/125
GigaLine® DClink OM4 G50/125
6 LC Duplex PC – 6 LC Duplex PC*
LKD 9R20 8xxx 0000
LKD 9R30 8xxx 0000
LKD 9R10 8xxx 0000
6 LC Duplex PC – 6 SC Duplex PC*
LKD 9R20 9xxx 0000
LKD 9R30 9xxx 0000
LKD 9R10 9xxx 0000
6 SC Duplex PC – 6 SC Duplex PC*
LKD 9R21 0xxx 0000
LKD 9R31 0xxx 0000
LKD 9R11 0xxx 0000
12 LC Duplex PC – 12 LC Duplex PC*
LKD 9R21 1xxx 0000
LKD 9R31 5xxx 0000
LKD 9R11 1xxx 0000
12 E2000 Simplex PC – 12 E2000 Simplex PC*
LKD 9R21 2xxx 0000
LKD 9R31 2xxx 0000
LKD 9R11 2xxx 0000
6 LC Duplex PC – 12 E2000 Simplex PC*
LKD 9R21 3xxx 0000
LKD 9R31 3xxx 0000
LKD 9R11 3xxx 0000
*Twisted in pairs xxx = Length between the link modules in m. Other configurations on request. 1 piece per packing unit. www.leoni-infrastructure-datacom.com
Office Office
Industry
DataCenter DataCenter 233
GigaLine®
DataCenter MTP module
for installation in DClink frame
Description
DC MTP module
Connection-ready MTP module for installation in a DClink frame.
Housing
Steel panel, front Jet black RAL 9005
Dimensions
40 mm x 135 mm x 150 mm (H x W x D)
Field of application In DataCenters and in structured cabling acc. to ISO/IEC 11801
Front side
and EN 50173 (2nd edition).
Configuration
For all applications from Classes > OF-300 (GigaLine 550)(10 GbE),
Insertion loss
typ. 0.2 dB
OF-500 (GbE/FiberChannel) and OF-2000 (Fast Ethernet).
Return loss
> 50 dB (SM, PC), > 70 dB (SM, APC),
Up to 12 LC Duplex, 6 SC Duplex, 12 SC Simplex, 12 E-2000 Simplex
> 40 dB (MM) Rear Configuration
1x or 2x MTP® (male)
Insertion loss
typ. 0.3 dB
Return loss
> 55 dB (SM), > 20 dB (MM)
Fiber types
OS2/OM4/OM3
Designation
Configuration
Order no.
Configuration
Order no.
1 x GigaLine® MTP module OS2 E9..10/125
6 LC Duplex PC*
LKD 9R70 0008 0000
6 LC Duplex PC**
LKD 9R7G 0008 0000
2 x GigaLine® MTP module OS2 E9..10/125
12 LC Duplex PC*
LKD 9R70 0009 0000
12 LC Duplex PC**
LKD 9R7G 0009 0000
1 x GigaLine® MTP module OM4 G50/125
6 LC Duplex PC*
LKD 9R70 0010 0000
6 LC Duplex PC**
LKD 9R7G 0010 0000
2 x GigaLine® MTP module OM4 G50/125
12 LC Duplex PC*
LKD 9R70 0011 0000
12 LC Duplex PC**
LKD 9R7G 0011 0000
1 x GigaLine® MTP module OM3 G50/125
6 LC Duplex PC*
LKD 9R70 0012 0000
6 LC Duplex PC**
LKD 9R7G 0012 0000
2 x GigaLine® MTP module OM3 G50/125
12 LC Duplex PC*
LKD 9R70 0013 0000
12 LC Duplex PC**
LKD 9R7G 0013 0000
1 piece per packing unit.
* Logically crossed
www.leoni-infrastructure-datacom.com
** Twisted in pairs
GigaLine® DataCentre links
GigaLine® DC MTP module OS2 E9..10/125 GigaLine® DC MTP module OM3 G50/125 GigaLine® DC MTP module OM4 G50/125
234
GigaLine Acceptance measurement ®
www.leoni-infrastructure-datacom.com
Office Office
Industry
DataCenter 235
Acceptance measurement for GigaLine® cabling systems
The acceptance measurement for GigaLine® cabling systems
The set measuring range must be twice as big as the
is carried out in accordance with the requirements of ISO/IEC
transmission link to be measured. The pulse width of the OTDR
11801 or EN 50173-1:2007. DIN ISO/IEC 14763-3 is also relevant
should be chosen as short as possible. This keeps the dead zones
to the acceptance measurement.
at reflected events to a minimum.
For an OTDR measurement, a launch fiber and receive fiber
Index-adjusting materials must not be used.
must be used. These must be longer than the dead zone of the OTDR being used. For multimode links, the fiber should be at least 100 m in length; for singlemode links, the fiber should be
Maximum attenuation of the transmission links in dB Class
850 nm
at least 500 m in length. A bidirectional measurement is necessary to avoid or eliminate measurement errors due to different backscatter coefficients if the overall link consists of several spliced or patched sublinks.
Attenuation meters
Both attenuation meters and OTDR are vital for professional fiber optic installation. The test engineer must have a valid calibration certificate for the testing device.
www.leoni-infrastructure-datacom.com
Multimode
Singlemode
1,300 nm
1,310 nm
1,550 nm
OF 300
2.55
1.95
1.80
1.80
OF 500
3.25
2.25
2.00
2.00
OF 2000
8.50
4.50
3.50
3.50
OF 5000
4.00
4.00
OF 10000
6.00
6.00
OTDR
Fiber identifiers
236
VarioLine® Modular system peripherals Consolidation point and underfloor solutions
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 237
VarioLine® CP – consolidation point range
236
240
241
o
Consolidation point housing
o
Consolidation point housing
For 6, 12, 24-port module panels
Module panels with 6, 12, 24 ports
•C an be equipped with ELine 1200® EC7 modules • Can be equipped with VarioKeystone® modules • Can be equipped with VarioKeystone® cable plugs
242
Module panels with 6, 12, 24 ports
•C an be equipped with keystone modules • Can be equipped with GigaLine™ SC Duplex couplings • Can be equipped with GigaLine™ LC Duplex couplings
243
Floor outlet
Round/rectangular
244
o
o o
VarioLine® DC – DataCenter range
o
DClink frame 19"/1 RU
o
DataCenter accessories
o
DataCenter cable routing panel 19"/1 RU
• F or holding up to 3 DClink modules •D Clink dummy cover
www.leoni-infrastructure-datacom.com
253
VarioLine® UF – underfloor systems/ floorbox solutions
System overview
254
o
Mounting plates for underfloor systems
• For installing wall outlets • For installing adapter panels
258 259
o
Adapter panels for underfloor systems
260
o o o o
Excess-length module
262
o dc i
Splice tray
262
Cable retainer
263
Dummy cover
263
Office DataCenter Industry
247 248 249
• With 82 mm metal clips • With 115 mm metal clips • With 78 mm plastic clips
VarioLine® UF – underfloor systems
239
•C an be equipped with MegaLine® Connect45 modules • Can be equipped with VarioKeystone® modules
250
VarioLine® Modular system peripherals
VarioLine® Modular system peripherals
238
www.leoni-infrastructure-datacom.com
Office Office
Industry
DataCenter DataCenter 239
VarioLine® CP – consolidation point range for copper and fiber optic connectivity
The consolidation point range is an efficient and cost-
The robust VarioLine® consolidation points are made of galvanised
effective solution for designing highly flexible floor,
steel panel and are available in three sizes for 6, 12 and 24 ports.
DataCenter or industrial cabling systems. There are different module panels available for VarioLine® In office cabling (EN 50173-2), consolidation points (CPs)
CP housings:
between floor distributors (FD) and telecommunication outlets
■■
VarioKeystone® modules
(TO) offer extremely flexible solutions for rapidly changing
■■
VarioKeystone® link extenders
office configurations.
■■
MegaLine® Connect45 modules
■■
ELine® 1200 EC7 modules
The CP can be installed in raised floors, suspended ceilings,
■■
All common keystone modules
columns or ducts. From there, flexible cables (CP cables) lead
■■
GigaLine® LC Duplex
to the data outlets at the workstation.
■■
GigaLine® SC Duplex
The CP cabling connects the permanent cabling with modular
If necessary, the VarioLine® CP range can be expanded by
or mobile office systems such as partitions or office furniture into
using additional module panels for copper as well as fiber
which the TO is already installed. In industrial cabling, a so-called
optic systems.
intermediate distributor (ID) is used to connect the floor distributor (FD) with the telecommunication outlet (TO) which
Features of VarioLine®:
for example allows temporary machine cablings (EN 50173-3).
■■
The easy snap-in installation of the cover on the floor or zone distributor side makes troublesome screwing and the use
provide an additional patching option between a zone
■■
The patch side is covered by a hinged cover with a strip brush.
distributor (ZD) and equipment outlet (EO) (EN50173-5).
■■
The incoming cables and the patch cords can be held by cable ties.
■■
The housings can be earthed if necessary.
■■
The CP cables pass through the raised floor via the necessary floor outlets which are installed in the base plate.
■■
VarioLine® CP floor outlets can be closed flush with the floor when they are not required and are set upright to pass cables through.
■■
www.leoni-infrastructure-datacom.com
The cover then also protects the cables as they come out.
VarioLine® Modular system peripherals
of special tools unnecessary.
In DataCenters, CPs as local distribution points (LDP) can
240
VarioLine® Consolidation point housing 6-port, with DIN rail clip
Fig. 2 6-port module panel in VarioKeystone® format
Fig. 3 6-port module panel in keystone format
Fig. 1 Consolidation point housing
VarioLine® CP6-B VarioLine® CPL6-B VarioLine® CPL6-B VarioLine® CP6-B
Fig. 4 6-port protective flap/ strip brush
consolidation point housing 6-port VarioKeystone® module panel 6-port keystone module panel 6-port protective flap/strip brush
Description
Configuration of VarioKeystone® module panel
For installation in raised floors or suspended ceilings. CP housing
■■
For up to 6 VarioKeystone® single modules or up to 3 VarioKeystone® double modules
with strain relief using cable ties (not included in the scope of delivery). Can be equipped with MegaLine® Connect45 or VarioKeystone® modules.
Configuration of keystone module panel ■■
For up to 6 MegaLine® Connect45 modules
A protective flap with strip brush can optionally be used on the patch side.
Mounting ■■
■■
Modular (interchangeable module panel)
■■
Also available with 12/24 ports as an option
■■
Robust housing made from galvanised steel panel
■■
RoHS-compliant
The CP housing is attached using the DIN rail mounting technique (a suitable clip is included)
■■
The housing can alternatively be attached using screws or nailed dowels (not included in the scope of delivery)
■■
The module panel is attached by snapping it into the housing
■■
The modules are attached by snapping them into the module panel
Fig.
Designation
Dimensions
Order no.
1
VarioLine® CP6-B consolidation point housing
33 x 121.5 x 100 mm (H x W x D)
LKD 9ZE6 1007 0000
2
VarioLine® CPL6-B 6-port VarioKeystone® module panel
31 x 121 mm (H x W)
LKD 9ZE6 1014 0000
3
VarioLine® CPL6-B 6-port keystone module panel
31 x 121 mm (H x W)
LKD 9ZE6 1064 0000
4
VarioLine® CP6-B 6-port protective flap with strip brush
31 x 121 mm (H x W)
LKD 9ZE6 1008 0000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 241
VarioLine® Consolidation point housing for 6, 12, 24-port module panels
Fig. 1 Consolidation point housing for 6-port module panel
Fig. 2 Consolidation point housing for 12-port module panel
Fig. 3 Consolidation point housing for 24-port module panel
VarioLine® CP6/CP12/CP24 Description
Housing
For installation in raised floors or suspended ceilings, can be
Housing
Galvanised sheet panel
equipped with 6, 12 or 24-port module panels in different
Dimensions
CP 6
55 mm x 155 mm x 215 mm (H x W x D)
designs.
CP 12 55 mm x 290 mm x 215 mm (H x W x D)
The module panel is installed by pushing it into place;
CP 24 55 mm x 550 mm x 215 mm (H x W x D)
can additionally be screwed. Accessories ■■
Bottom plate with hinged flap and dust protective brush
see from page 90
6, 12 or 24-port module panels
■■
VarioLine® Modular system peripherals
on the patch side Cover can be removed/mounted on the tertiary cable side without the use of tools ■■
Potential equalisation possible (drilled hole diam. 5 mm)
■■
The housing can be attached using screws or nailed dowels (not included in the scope of delivery)
Fig.
Designation
Configuration
Order no.
1
VarioLine® CP6
(1 piece)
Consolidation point housing for 6-port module panel
LKD 9ZE6 1001 0000
2
VarioLine® CP12 (1 piece)
Consolidation point housing for 12-port module panel
LKD 9ZE6 1002 0000
3
VarioLine® CP24 (1 piece)
Consolidation point housing for 24-port module panel
LKD 9ZE6 1003 0000
www.leoni-infrastructure-datacom.com
242
VarioLine® Module panels with 6, 12, 24 ports for consolidation points
VarioLine® CPL12 ELine 12-port module panel can be equipped with ELine 1200® EC7 modules
VarioLine® CPL6 ELine EC7 VarioLine® CPL12 ELine EC7 VarioLine® CPL24 ELine EC7
VarioLine® CPL12 VK module 12-port module panel can be equipped with VarioKeystone® modules
VarioLine® CPL6 VK module VarioLine® CPL12 VK module VarioLine® CPL24 VK module
VarioLine® CPL12 VK LE 12-port module panel can be equipped with VarioKeystone® link extenders
VarioLine® CPL6 VK LE VarioLine® CPL12 VK LE VarioLine® CPL24 VK LE
Description Module panel made from galvanised steel panel for installation in corresponding CP housing. The module panel is installed in the housing by pushing it into place; can additionally be screwed. ■■
Modules or cable plugs are attached by snapping them in
■■
Can be equipped with 6/12/24 modules depending on the version (see table)
Matching modules/ cable plugs
ELine 1200® EC7
VarioKeystone® 4K7
VarioKeystone® RJ45
MegaLine® Connect 45 (VarioKeystone® format)
VarioKeystone® link extender
Module panel CPL6/CPL12/CPL24 ELine for ELine 1200® EC7 modules Module panel CPL6/CPL12/CPL24 VK module for VarioKeystone® modules Module panel CPL6/CPL12/CPL24 VK LE for VarioKeystone® link extender
Designation
Order no.
Designation
Designation
Order no.
VarioLine® CPL6 EC7*
LKD 9ZE6 1031 0000
VarioLine® CPL6 VK module* LKD 9ZE6 1011 0000
Order no.
VarioLine® CPL6 VK LE*
LKD 9ZE6 1021 0000
VarioLine® CPL12 EC7*
LKD 9ZE6 1032 0000
VarioLine® CPL12 VK module* LKD 9ZE6 1012 0000
VarioLine® CPL12 VK LE*
LKD 9ZE6 1022 0000
VarioLine® CPL24 EC7*
LKD 9ZE6 1033 0000
VarioLine® CPL24 VK module* LKD 9ZE6 1013 0000
VarioLine® CPL24 VK LE*
LKD 9ZE6 1023 0000
* (1 piece)
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 243
VarioLine® CPL12 keystone 12-port module panel can be equipped with keystone modules
VarioLine® CPL6 keystone VarioLine® CPL12 keystone VarioLine® CPL24 keystone
VarioLine® CPL12 SC Duplex 12-port module panel can be equipped with GigaLine® SC Duplex couplings
VarioLine® CPL6 SC Duplex VarioLine® CPL12 SC Duplex VarioLine® CPL24 SC Duplex
VarioLine® CPL12 LC Duplex 12-port module panel can be equipped with GigaLine® LC Duplex couplings
VarioLine® CPL6 LC Duplex VarioLine® CPL12 LC Duplex VarioLine® CPL24 LC Duplex
Description
Equipped module panels
Module panel made from galvanised steel panel for installation
CPL SC Duplex and CPL LC Duplex module panels can
in corresponding CP housing.
be supplied equipped on request.
The module panel is installed in the housing by pushing it into place; can additionally be screwed. ■■
Modules are attached by screwing or snapping Can be equipped with 6/12/24 modules depending on the version (see table)
Matching couplings
MegaLine® Connect45 GigaLine® (keystone) SC Duplex
GigaLine® SC Duplex/ST
GigaLine® SC Simplex
GigaLine® LC Duplex
GigaLine® E-2000
Module panel CPL6/CPL12/CPL24 Keystone for MegaLine® Connect45 modules Module panel CPL6/CPL12/CPL24 SC Duplex for GigaLine® couplings Module panel CPL6/CPL12/CPL24 LC Duplex for GigaLine® couplings
Designation
Order no.
Designation
Order no.
Designation
Order no.
VarioLine® CPL6 keystone*
LKD 9ZE6 1061 0000
VarioLine® CPL6 SC Duplex*
LKD 9ZE6 1041 0000
VarioLine® CPL6 LC Duplex*
LKD 9ZE6 1051 0000
VarioLine® CPL12 keystone*
LKD 9ZE6 1062 0000
VarioLine® CPL12 SC Duplex* LKD 9ZE6 1042 0000
VarioLine® CPL12 LC Duplex* LKD 9ZE6 1052 0000
VarioLine® CPL24 keystone*
LKD 9ZE6 1063 0000
VarioLine® CPL24 SC Duplex* LKD 9ZE6 1043 0000
VarioLine® CPL24 LC Duplex* LKD 9ZE6 1053 0000
* (1 piece)
www.leoni-infrastructure-datacom.com
VarioLine® Modular system peripherals
them in (with CPL keystone module panel) ■■
244
VarioLine® Floor outlet round/rectangular
VarioLine® CPB1 rectangular floor outlet
VarioLine® CPB2 round floor outlet
Description
Description
For installation in raised floors.
For installation in raised floors.
Attached by screwing into the base plate (screws not included
Attached by screwing into the base plate (screws not included
in the scope of delivery).
in the scope of delivery).
■■
Rotatable
■■
Square frame, round cover
■■
Three positions possible
■■
Two positions possible
1. Closed flush with the floor
1. Closed flush with the floor
2. Open
2. Open
3. Open, flush with the floor with strip brush ■■
■■
RoHS-compliant
RoHS-compliant Housing
Housing Housing
Brushed stainless steel
Housing
Dimensions
80 mm x 160 mm x 63 mm (H x W x D)
Dimensions
Brushed stainless steel
Open
60 mm x 140 mm x 140 mm (H x W x D)
Closed
47 mm x 140 mm x 140 mm (H x W x D)
Designation
Order no.
Designation
Order no.
VarioLine® CPB1 rectangular floor outlet (1 piece)
LKD 9ZE6 1010 0000
VarioLine® CPB2 round floor outlet (1 piece)
LKD 9ZE6 1020 0000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter
VarioLine® Modular system peripherals
245
www.leoni-infrastructure-datacom.com
246
www.leoni-infrastructure-datacom.com
Office Office
Industry
DataCenter DataCenter 247
VarioLine® DC – DataCenter range for holding DClink modules
The most notable characteristic of the DataCenter range is that rather than just meeting the current standards and requirements for DataCenters, it actually exceeds them. The quick and easy installation ensures uninterrupted DataCenter operation. The "true" plug and play solution for copper and fiber optic
Advantages at a glance:
applications consists of a VarioLine® DClink frame (19", 1 RU)
■■
"True" plug and play solution
for holding MegaLine® DClink and GigaLine® DClink modules.
■■
Minimal attenuation
The DClink modules are simply inserted and audibly clicked
■■
Maximum reliability
into place from the rear after the links are installed.
■■
Factory-tested
Modules
Accessories
VarioLine® DClink dummy cover
VarioLine® Modular system peripherals
GigaLine® DClink module 40/100
GigaLine® DClink module
VarioLine® DClink release tool GigaLine® DC MTP module
VarioLine® DClink frame, 19"
www.leoni-infrastructure-datacom.com
Frame
248
VarioLine® DClink frame 19"/1 RU for holding up to 3 DClink modules
Fig. 1 DClink frame 19"/1 RU
Fig. 2 DClink dummy cover
VarioLine® DClink frame 19"/1 RU VarioLine® DClink dummy cover Description
Housing
For quick, easy and reliable installation of pre-assembled
Housing
Powder-coated steel panel
DClink modules in DataCenters.
Colour
Jet black RAL 9005
Unused module openings are closed off with the dummy cover. Dimensions ■■
Can be equipped with GigaLine® and/or MegaLine® DClink
19"/1 RU
44 mm x 483 mm x 175 mm (H x W x D)
modules (see DataCenter links from page 230) ■■
For holding up to 3 modules
Accessories (optional) Dummy cover
For closing off a module opening 42 mm x 133 mm x 39 mm (H x W x D)
Matching modules/segments GigaLine® DClink 40/100
Fig.
GigaLine® DClink
GigaLine® DC MTP module
GigaLine® DClink dummy cover
Designation
Configuration
Order no.
1
VarioLine® DClink frame 19"/1 RU (8 pieces)
GigaLine® DClink modules
LKD 9R00 0005 0000
2
VarioLine® DClink dummy cover (8 pieces)
LKD 9R00 0006 0000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 249
VarioLine® DataCenter accessories for DClink
VarioLine® DClink release tool Description For easy removal of the DClink modules from the DClink frame. Construction Stainless steel
Dimensions
65 mm x 40 mm x 4 mm (H x W x D)
VarioLine® Modular system peripherals
Material
Designation
Order no.
VarioLine® DClink release tool (1 pair)
LKD 9R00 0002 0000
www.leoni-infrastructure-datacom.com
250
VarioLine® DataCenter cable routing panel 19"/1 RU for installing copper or fiber optic patch cords
Fig. 1 VarioLine® DC CMP1 with 82 mm metal clips
Fig. 2 VarioLine® DC CMP2 with 115 mm metal clips
Fig. 3 VarioLine® DC CMP3 with 78 mm plastic clips
VarioLine® DC CMP1 with metal clips 82 mm VarioLine® DC CMP2 with metal clips 115 mm VarioLine® DC CMP3 with plastic clips 78 mm Description For reliable installation of fiber optic and copper patch cords in the distribution cabinet. With metal or plastic clips depending on the model. Construction Panel
Powder-coated steel panel
Colours
Light grey RAL 9005/Jet black RAL 9005
Dimensions DC CMP1
44 mm x 483 mm x 95 mm (H x W x D)
DC CMP2
44 mm x 483 mm x 127 mm (H x W x D)
DC CMP3
44 mm x 483 mm x 90 mm (H x W x D)
Fig.
Designation
Colour
Order no.
1
VarioLine® DC CMP1 with 82 mm metal clips (1 piece)
Jet black RAL 9005
LKD 9ZE3 0050 0000
–
VarioLine® DC CMP1 with 82 mm metal clips (1 piece)
2
VarioLine® DC CMP2 with 115 mm metal clips (1 piece)
3
VarioLine® DC CMP3 with 78 mm plastic clips (1 piece)
LKD 9ZE1 0006 0000 Light grey RAL 7035
LKD 9A61 0028 0000
LKD 9A61 0020 0000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter
VarioLine® Modular system peripherals
251
www.leoni-infrastructure-datacom.com
252
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 253
VarioLine® UF – underfloor systems Mounting plate solution – modular and universal
The "VarioLine® UF" underfloor systems (floorbox solutions)
The mounting plate replaces the equipment rack, offering
offer an efficient and cost-effective solution for terminating
maximum space for the cable feed. The tilted feed-in and feed-out
copper and fiber optic systems.
guarantees secure cable routing, even with very low raised floors.
They offer a high degree of flexibility in the office environment.
Adapter plates allow cost-effective and efficient installation
Desks can be connected to the power and IT network without
of all LEONI connectivity components, whether copper or fiber
the usual jumble of cables. The modular and universal mounting
optic.
plate solutions are available for all common underfloor systems
VarioLine® Modular system peripherals
(e.g. Ackermann or Electraplan).
Example of an underfloor solution from LEONI in an Ackermann floorbox
www.leoni-infrastructure-datacom.com
254
VarioLine® UF – underfloor systems/floorbox solutions System overview – based on VarioKeystone®/ELine 1200® EC7/keystone modules
VarioKeystone® 4K7
VarioKeystone® RJ45
MegaLine®Connect45 (in VarioKeystone® format)
VarioLine® UF AP3 for up to 3 VarioKeystone® modules or for up to 3 MegaLine® Connect45 modules (in VarioKeystone® format)
VarioKeystone® double module RJ45
MegaLine®Connect45 (in VarioKeystone® format)
VarioLine® UF APD1 for 1 VarioKeystone® double module for up to 2 MegaLine® Connect45 modules (in VarioKeystone® format)
VarioLine® UF AP3 EC7 for up to 3 ELine 1200® EC7 modules
ELine 1200® EC7
VarioLine® UF APD3 for up to 3 MegaLine® Connect45 modules (in keystone format)
MegaLine®Connect45 (in keystone format)
Jack
Adapter plate www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 255
VarioLine® UF TA2 for Ackermann GES 2, 4, 6, R4, R7
VarioLine® Modular system peripherals
VarioLine® UF TA3 for Ackermann GES 9, R7, R9
VarioLine® UF TEK3 for Electraplan KDR series (old type)
VarioLine® UF TEV3 for Electraplan VQ12, VR12, VR10
Mounting plate www.leoni-infrastructure-datacom.com
256
System overview – based on GigaLine® couplings
GigaLine® SC Duplex
Dummy cover for VarioLine® UF mounting plates
VarioLine® UF TA2 for Ackermann GES 2, 4, 6, R4, R7
VarioLine® UF AP4-SCD for up to 4 couplings
GigaLine® SC Duplex/ST
VarioLine® UF TA3 for Ackermann GES 9, R7, R9
GigaLine® SC Simplex
GigaLine® LC Duplex
VarioLine® UF AP4-LCD for up to 4 couplings
VarioLine® UF TEK3 for Electraplan KDR series (old type)
GigaLine® E-2000 VarioLine® UF TEV3 for Electraplan VQ12, VR12, VR10
Jacks
Adapter plate
Mounting plate www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 257
VarioLine® UF O2 for mounting plates T2
VarioLine® UF-SC2 for excess-length module UM2
VarioLine® UF O3 for mounting plates T3
VarioLine® UF-SC3 for excess-length module UM3
VarioLine® Modular system peripherals
VarioLine® UF K1
VarioLine® UF K2
Strain relief www.leoni-infrastructure-datacom.com
Excess-length module
Splice tray
258
VarioLine® Mounting plates for underfloor systems For installing wall outlets
Fig. 1 Mounting plate VarioLine® UF TOA2-2 For Ackermann GES 2, 4, 6, R4, R7
Fig. 2 Mounting plate VarioLine® UF TOA3-2 For Ackermann GES 9, R7, R9
Fig. 3 Mounting plate VarioLine® UF TOA3-3 For Ackermann GES 9, R7, R9
VarioLine® UF TOA2-2/UF TOA3-2
VarioLine® UF TOA3-3
Description
Description
UF TOA2-2 ➔ for mounting up to 2 wall outlets with 50 mm x
For mounting up to 3 wall outlets with 50 mm x 50 mm
50 mm central plate and lateral attachment or one wall outlet
central plate and lateral fastening or two wall outlets with
with circumferential ring.
circumferential ring. ■■
For installation in Ackermann device inserts
UF TOA3-2 ➔ for mounting up to 2 wall outlets with 50 mm x 50 mm central plate and lateral attachment or two wall outlets
Housing
with circumferential ring.
Mounting plate
Powder-coated steel panel, 1.5 mm
Colour
Jet black RAL 9005
■■
For installation in Ackermann device inserts
Housing
Accessories (optional)
see from page 262
Mounting plate
Powder-coated steel panel, 1.5 mm
Cable retainer VarioLine® UF K1/VarioLine® UF K2 adjustable
Colour
Jet black RAL 9005
cable strain relief for up to 9 individual cables
Accessories (optional)
see from page 262
Cable retainer for VarioLine® UF K1/VarioLine® UF K2 Adjustable cable strain relief for up to 9 individual cables
Fig.
Designation
Order no.
1
VarioLine® UF TOA2-2 (1 piece)
LKD 9ZE6 0014 0000
2
VarioLine® UF TOA3-2 (1 piece)
LKD 9ZE6 0012 0000
Fig. 3
Designation
Order no.
VarioLine® UF TOA3-3 (1 piece)
LKD 9ZE6 0013 0000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 259
VarioLine® Mounting plates for underfloor systems for installing adapter panels
Fig. 1 Mounting plate VarioLine® UF TA2 for Ackermann GES 2, 4, 6, R4, R7
Fig. 2 Mounting plate VarioLine® UF TA3 for Ackermann GES 9, R7, R9
Fig. 1 Mounting plate VarioLine® UF TEK3 for Electraplan KDR series (old type)
VarioLine® UF TA2/UF TA3
Fig. 2 Mounting plate VarioLine® UF TEV3 for Electraplan VQ12, VR12, VR10
VarioLine® UF TEK3/UF TEV3
Description
Description
For mounting up to 2 or 3 adapter plates.
For mounting up to 3 adapter plates.
For installation in Ackermann device inserts
■■
Compatibility
For installation in Electraplan device inserts
Compatibility
UF TA2
Ackermann GES 2, 4, 6, R4, R7
UF TEK3
Electraplan KDR series (old type)
UF TA3
Ackermann GES 9, R7, R9
UF TEV3
Electraplan VQ12, VR12, VR10
Housing
Housing
Mounting plate
powder-coated steel panel, 1.5 mm
Mounting plate
powder-coated steel panel, 1.5 mm
Colour
Jet black RAL 9005
Colour
Jet black RAL 9005
Accessories (optional)
see page 263
Accessories (optional)
see page 263
Cable retainer for VarioLine® UF K1/VarioLine® UF K2 Adjustable
Cable retainer VarioLine® UF K1/VarioLine® UF K2 adjustable
cable strain relief for up to 9 individual cables
cable strain relief for up to 9 individual cables
Fig.
Designation
Order no.
1
VarioLine® UF TA2 (1 piece)
LKD 9ZE6 0001 0000
2
VarioLine® UF TA3 (1 piece)
LKD 9ZE6 0002 0000
www.leoni-infrastructure-datacom.com
Fig.
Designation
Order no.
1
VarioLine® UF TEK3 (1 piece)
LKD 9ZE6 0008 0000
2
VarioLine® UF TEV3 (1 piece)
LKD 9ZE6 0042 0000
VarioLine® Modular system peripherals
■■
260
VarioLine® Adapter panels for underfloor systems for installation in VarioLine® UF mounting plates
Fig. 1 Adapter panel VarioLine® UF APD1 VK For 1 VarioKeystone® double module or up to 2 MegaLine® Connect45 modules (VarioKeystone)
Fig. 2 Adapter panel VarioLine® UF AP3 VK For up to 3 VarioKeystone® modules or up to 3 MegaLine® Connect45 modules (VarioKeystone)
VarioLine® UF APD1 VK VarioLine® UF AP3 VK VarioLine® UF AP3 MC45 Description
Compatibility
Adapter panel for installation in VarioLine® UF mounting plates.
UF APD1 VK
For installing up to 3 modules.
Fig. 3 Adapter panel VarioLine® UF AP3 MC45 For up to 3 MegaLine® Connect45 modules (keystone)
➔ For 1 VarioKeystone® double module or up to 2 MegaLine® Connect45 modules
■■
With self-adhesive labels for personal labelling
■■
2 nut-and-washer assemblies included
(VarioKeystone®) UF AP3 VK
➔ For up to 3 VarioKeystone® modules or up to 3 MegaLine® Connect45 modules (VarioKeystone®)
UF AP3 MC45
➔ For up to 3 MegaLine® Connect45 modules (keystone)
Construction
Matching jacks
VarioKeystone® 4K7
VarioKeystone® RJ45
Adapter panel
Powder-coated steel panel, 1.5 mm
Surface
Zn – black, conductive
VarioKeystone® Double module RJ45
MegaLine® Connect45 (VarioKeystone)
MegaLine® Connect45 (keystone)
VarioLine® UF APD1 VK
VarioLine® UF AP3 VK
VarioLine® UF AP3 MC45
Fig. 1
Designation
Order no.
VarioLine® UF APD1 VK (1 piece)
LKD 9ZE6 0040 0000
2
VarioLine® UF AP3 VK (1 piece)
LKD 9A46 0118 0000
3
VarioLine® UF AP3 MC45 (1 piece)
LKD 9ZE6 0044 0000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 261
Fig. 1 Adapter panel VarioLine® UF AP3 ELine For up to 3 ELine 1200® EC7 modules
Fig. 2 Adapter panel VarioLine® UF AP4 SCD For up to 4 SC Duplex couplings
VarioLine® UF AP3 EC7
Fig. 3 Adapter panel VarioLine® UF AP4 LCD For up to 4 LC Duplex couplings
VarioLine® UF AP4-SCD/UF AP4-LCD
Description
Description
Adapter panel for installation in VarioLine® UF mounting plates.
Adapter panel for installation in VarioLine® UF mounting plates.
For installing up to 3 ELine 1200® EC7 modules.
For installing up to 4 SC or LC Duplex couplings.
■■
With earth or ground connection
■■
With self-adhesive labels for personal labelling
■■
With self-adhesive labels for personal labelling
■■
2 nut-and-washer assemblies included
■■
2 nut-and-washer assemblies included Compatibility UF AP4-SCD
Adapter panel
Steel panel, 1.5 mm
Surface
Aluminium zinc
For up to 4 SC Duplex or SC Duplex/ ST couplings
UF AP4-LCD
For up to 4 LC Duplex, SC Simplex or E-2000 couplings
Construction
Matching jacks
ELine 1200® EC7
GigaLine® SC Duplex
Adapter panel
Powder-coated steel panel, 1.5 mm
Surface
ZN – black, conductive
GigaLine® SC Duplex/ST
GigaLine® SC Simplex
GigaLine® LC Duplex
GigaLine® E-2000
VarioLine® UF AP3 EC7
VarioLine® UF AP4 SCD
VarioLine® UF AP4 LCD
Fig. 1
Designation
Order no.
VarioLine® UF AP3 EC7 (1 piece)
LKD 9ZE6 0006 0000
www.leoni-infrastructure-datacom.com
Fig.
Designation
Order no.
2
VarioLine® UF AP4-SCD (1 piece)
LKD 9FZZ 0078 0000
3
VarioLine® UF AP4-LCD (1 piece)
LKD 9FZZ 0079 0000
VarioLine® Modular system peripherals
Construction
262
VarioLine® Excess-length module
VarioLine® Splice tray
for underfloor systems
for underfloor systems
Fig. 1 Excess-length module for mounting plates T2
Fig. 3 Splice tray for excess-length module UM2
Fig. 2 Excess-length module for mounting plates T3
VarioLine® UF O2 VarioLine® UF O3
Fig. 4 Splice tray for excess-length module UM3
VarioLine® UF SC2 VarioLine® UF SC3
Description
Description
Excess-length module for mounting on VarioLine®UF mounting
Splice tray with cover and splice holder for 12 crimp splices.
plates. Can be mounted without the use of tools.
For mounting on the underside of the corresponding excesslength module.
Compatibility/dimensions (available in two sizes)
Compatibility/dimensions (available in two sizes)
UF O2
UF SC2
For mounting plates T2 61 mm x 75 mm x 135 mm (H x W x D)
UF O3
10 mm x 75 mm x 113 mm (H x W x D) UF SC3
For mounting plates T3
For excess-length module UM2
61 mm x 75 mm x 176 mm (H x W x D)
For excess-length module UM3 10 mm x 75 mm x 154 mm (H x W x D)
Housing
Housing
Excess-length module Powder-coated steel panel, 1.5 mm
Splice tray
Powder-coated steel panel, 1.5 mm
Colour
Colour
Jet black RAL 9005
Jet black RAL 9005
Accessories (optional)
see page 263
A cable retainer is required for mounting the excess-length module
Fig.
Designation
Order no.
1
VarioLine® UF O2 (1 piece)
LKD 9FZZ 0080 0000
2
VarioLine® UF O3 (1 piece)
LKD 9FZZ 0018 0000
Fig.
Designation
Order no.
3
VarioLine® UF SC2 (1 piece)
LKD 9FZZ 0020 0000
4
VarioLine® UF SC3 (1 piece)
LKD 9FZZ 0081 0000
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 263
VarioLine® Cable retainer
VarioLine® Dummy cover
for underfloor systems
for VarioLine® UF mounting plates
Fig. 3 Dummy cover UF mounting plates
Fig. 2 Cable retainer depth 64.5 mm
Fig. 1 Cable retainer depth 45 mm
VarioLine® UF K1 VarioLine® UF K2
Fig. 4 Dummy cover UF mounting plates for wall outlet inserts
VarioLine® UF BP-T VarioLine® UF BP-TO
Description
Description
Cable retainer for attachment to VarioLine® UF mounting plates.
Blind cover for closing off an unused opening in the VarioLine® UF mounting plate. 2 nut-and-washer assemblies included
Compatibility/dimensions (available in two sizes)
Compatibility
UF K1
Depth 45 mm
UF BP-T
For VarioLine® UF mounting plates
61 mm x 72 mm x 45 mm (H x W x D)
UF BP-TO
For VarioLine® UF mounting plates
UF K2
Depth 64.5 mm
For wall outlet inserts
61 mm x 72 mm x 64.5 mm (H x W x D) Housing Housing Strain relief
Powder-coated steel panel, 1.5 mm
Colour
Jet black RAL 9005
Fig.
Mounting plate
Powder-coated steel panel, 1.5 mm
Colour
Jet black RAL 9005
Designation
Order no.
1
VarioLine® UF K1 (1 piece)
LKD 9ZE6 0003 0000
3
VarioLine® UF BP-T (1 piece)
LKD 9ZE6 0005 0000
2
VarioLine® UF K2 (1 piece)
LKD 9ZE6 0004 0000
4
VarioLine® UF BP-TO (1 piece)
LKD 9ZE6 0015 0000
www.leoni-infrastructure-datacom.com
Fig.
Designation
Order no.
VarioLine® Modular system peripherals
■■
264
Field of application Office www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 265
Generic cabling in office buildings The complete cable system, from distribution equipment to workstation
ISO/IEC 11801 and EN 50173-2
ISO/IEC 24702 and EN 50173-3
ISO/IEC 15018 and EN 50173-4
ISO/IEC 24764 and EN 50173-5
Information technology
Information technology
Information technology
Information technology
Generic communication cable systems
Generic communication cable systems
Generic communication cable systems
Generic communication cable systems
Office buildings
Industry
Apartments
DataCenters
ISO/IEC 11801 and EN 50173-1 Information technology Generic communication cable systems General requirements
These days, the future of a company depends to a large
The smart use of fiber optics and copper data technologies for
extent on reliable and timely data processing.
the backbone and horizontal wiring to the user enables costeffective networking of standard resources such as PCs and
The rapid development of data bit rates and the wide range of
printers, with an extension to IP telephony and multimedia
applications require a very flexible, high-performance network
applications. Other applications, such as Power-over-Ethernet
infrastructure that will be able to meet the demands for the
(PoE), support the powering of devices such as web cameras,
next ten years.
wireless LAN access points, IP phones and laptops via the copper data cabling.
High-quality generic IT networks form the backbone of the business in research & development, banks, insurance
These structured, generic communication cable systems meet
companies, universities, hospitals, hotels, airports and many
both the international and European standards set by ISO/IEC
other sectors, providing smooth operation and financial success.
11801 and DIN EN 50173-1/2 respectively.
CD
Campus distributor
EI
Building distributor
FD
Floor distributor
CP
Consolidation point
TO
Telecommunications outlet
TE
Terminal equipment
www.leoni-infrastructure-datacom.com
CD
EI
FD
CP
Subsystem of Subsystem the primary of the Subsystem of the tertiary cabling secondary cabling system system cabling system Generic communication cable system
TO
TE
Equipment connection cabling system
Fields of application
Structure of a generic communication cable system ISO/IEC 11801 and DIN EN 50173-1/2
Field of application Industry www.leoni-infrastructure-datacom.com
Industry
Office
DataCenter 267
Generic cabling in the industrial environment
ISO/IEC 11801 and EN 50173-2
ISO/IEC 24702 and EN 50173-3
ISO/IEC 15018 and EN 50173-4
ISO/IEC 24764 and EN 50173-5
Information technology
Information technology
Information technology
Information technology
Generic communication cable systems
Generic communication cable systems
Generic communication cable systems
Generic communication cable systems
Office buildings
Industry
Apartments
DataCenters
ISO/IEC 11801 and EN 50173-1 Information technology Generic communication cable systems General requirements
Office/IP20
ID
TO NI
Office/IP20
IP67
Structure of a generic communication cable system in industrial facilities ISO/IEC 24702 and EN 50173-3
www.leoni-infrastructure-datacom.com
Automation island
Fields of application
FD/ID
IP67
268
Industrial IT cabling Uniform IT platforms are increasingly used to connect different worlds
The worlds of office and industrial cabling are growing ever
A consistent extension of the use of generic
closer. The need for sales departments to receive current
cabling offers enormous advantages, including:
production data or to engage in short-term planning
■■
Reduction in the assortment of products
of production processes requires a uniform group-wide
■■
Deployment and distribution of mass-produced products
IT platform.
■■
Standardisation of acceptance measurements
■■
Reduction in training costs
Manufacturers of automation and control equipment demand
■■
Easy trouble-shooting
consistent, future-proofed international standards, while users
■■
Simplification of the network operation, maintenance and
are looking for secure investments. Ever more applications in
documentation
production processes are implemented via Ethernet, reducing maintenance and operating costs. Existing standards and
It is frequently observed these days that the transmission
applications, such as PROFINET, will still need support in the
requirements in industrial environments are less challenging
years to come.
than those in the office area. This can lead to a reduction in costs without risking the future requirements of the network.
This results in a requirement for a clear separation between
Since cable laying is expensive, and an expansion of technical
"application" and "network", which can only be achieved
requirements would lead to unnecessary additional costs,
using a uniform IT platform as a base, combined with generic
we recommend that data cables should be selected to meet
communication cabling, in both the office and manufacturing
the highest standards (Category 7 or above).
environments. This requirement has been standardised in the EN 50173-1, -2, -3 series, and in the ISO/IEC11801 and ISO/IEC
The connectivity can certainly be limited to the level currently
24702 international standards.
required, if the equipment used can be adapted cleverly to meet changing requirements in both transmission rates and building or manufacturing construction. This balancing act is easily manageable using the VarioKeystone® connection system from LEONI.
www.leoni-infrastructure-datacom.com
Industry
Office
DataCenter 269
MICE concept Classification of environmental conditions
MICE
Requirement/level
Requirement/level
Requirement/level
1
2
3
M Mechanical
M1
M2
M3
I Ingress
I1
I2
I3
C Climatic/chemical
C1
C2
C3
E Electromagnetic
E1
E2
E3
The environmental factor
The MICE classification can vary over the length of the
As well as the electrical or optical transmission channel,
transmission link, for example mechanical loads in the office
the different conditions in office and industrial settings mean
environment are fairly low and the ingress of liquids or
that the environmental factor also plays an important role.
significant climatic and chemical loads are equally unlikely. The conditions in buildings used for industrial purposes,
These environmental conditions are described using four
on the other hand, are harsher:
basic characteristics: Mechanical
Mechanical properties
Mechanical loads as well as the risk of ingress of dust, dirt and
Ingress
Ingress properties
liquids; high, quickly changing temperatures; solar radiation and
Climatic/chemical Climatic and chemical properties
corrosive substances can affect the components. Electromagnetic
Electromagnetic
interference also influences the data communication.
Electromagnetic properties
The four MICE criteria are broken down into different
M1 I1 C1 E1
MICE
2 2 1 1 Telecommunications room Factory floor
M1 I2 C3 E2
M 3 I3 C 3 E 3
Automation area
Automation island
more stringent the requirements: ■■
Office environment
M1 / I1 / C1 / E1
■■
Factory environment (light duty) M2 / I2 / C2 / E2
■■
Machine environment (heavy duty) M3 / I3 / C3 / E3
Distributor
www.leoni-infrastructure-datacom.com
Cabling channel
Fields of application
parameters, each with three levels. The higher the level, the
270
Industrial IT cabling VarioKeystone® connectivity
The VarioKeystone® system from LEONI Kerpen offers a
VarioKeystone® – One click takes you to the next generation
flexible connection concept with an extremely secure future. The high-quality components allow transmission links exceeding the requirements of Class E to be established.
■■
Outstanding performance
The modular structure makes it possible to change the plug face from RJ45 to Tera with little effort if required. It is not necessary
■■
Just change the plug for a new interface
to reinstall the data outlets for this purpose. ■■
Dispenses with the need to strip wires
This makes choosing the required connectivity much easier and opens the door to a future with high data transmission rates. If new mating faces come onto the market in future, it will be possible to adapt to them. VarioKeystone® also offers the unique option of extending or changing a link – this is especially
Upward compatibility with VarioKeystone® technology
important in the case of cabling systems only designed for a few years of service, for example in the automotive industry. The cable plugs are assembled on site using common tools; the only other thing that is required is a set of parallel press pliers. The jack modules can be pushed onto the cable plugs by hand and removed again if necessary using a simple release tool.
Cat. 7
LEONI offers the following for connections in the office environment: ■■
Fixed and telescopic patch panels
■■
Wall outlets
■■
2-port DIN rail housings
■■
A modular/universal consolidation point range "VarioLine® CP" for 6, 12 and 24 channels
Cat. 6A
Cat. 5/6
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 271
Han® 3A industrial outlets The best choice for use in harsh industrial environments
Han® 3A industrial outlets
The certified industrial range is being extended for the first
The Han® 3A metal outlet can be used for special mechanical
time with a high-quality cabling system whose primary
loads, in which case the plug connection is held by a latching clip.
characteristics are maximum future-proofing and unparalleled flexibility. No matter how adverse the ambient conditions
The watertightness of the class IP65/IP67 is also ensured with
(i.e. all MICE classes), it signals the end to problems with
the matching industrial patch cords. As well as robustness and
performance, breaker conditions and new mating faces.
abrasion resistance, the construction and PUR sheath of the
Han® 3A industrial outlet RJ45 jack module, equipped
www.leoni-infrastructure-datacom.com
Fields of application
flexible cables used also offer exceptional chemical properties.
272 272
Field of application DataCenter www.leoni-infrastructure-datacom.com
Office
DataCenter
Industry
273
Generic cabling in DataCenters
ISO/IEC 11801 and EN 50173-2
ISO/IEC 24702 and EN 50173-3
ISO/IEC 15018 and EN 50173-4
ISO/IEC 24764 and EN 50173-5
Information technology
Information technology
Information technology
Information technology
Generic communication cable systems
Generic communication cable systems
Generic communication cable systems
Generic communication cable systems
Office buildings
Industry
Apartments
DataCenters
ISO/IEC 11801 and EN 50173-1 Information technology Generic communication cable systems General requirements
The structure
The standards
The maximum extension is 2,000 metres. In DataCenters the
Generic communication cable systems are defined
main distribution cabling is frequently designed using fiber
in the standards EN 50173-1 and ISO/IEC 11801.
optic technology, while in smaller networks the external network interface (ENI) is connected directly to the zone
In addition, specific requirements for DataCenters are defined
distributor (ZD). The standards describe various models for
in EN 50173-5 and ISO/IEC 24764.
flexible and fixed connections in and between the subsystems. The cabling used in DataCenters consists of three subsystems: The cabling of the main and zone distribution must, according
■■
Network access cabling
to ISO/IEC 24764, meet the requirements of Class EA for copper
■■
Main distribution cabling
technology and transmission classes OF-300, OF-500 and
■■
Zone distribution cabling
OF-2000 for fiber optic technology as a minimum.
ENI
External network interface
MD
Main distributor
ZD
Zone distributor
LDP
Local distribution point
(optional) EO
External network interface
EQP
Application-specific
transmission equipment
ENI
MD
ZD
LDP
EQP
Distributor acc. to EN 50173-1 Main Network distribution access cabling
Zone distribution cabling
Generic communication cable system
www.leoni-infrastructure-datacom.com
EO
Equipment cabling
Fields of application
Structure of a generic communication cable system
274
Requirements and solutions Fast – high-quality – cost-optimised
DataCenter
➔ High quality
The DataCenter, the heart of the business, controls the
Quality testing at the factory, performance and safety are
production and administrative processes. A failure here can
already built into LEONI products.
have catastrophic consequences, and the availability of a DataCenter must be therefore guaranteed more or less around
➔ Minimise downtime
the clock. The cabling system makes a key contribution to its
Installation and commissioning take a very short time,
operation reliability.
with no need for special tools or assembly skills. This keeps downtime to a minimum.
Performance requirements for modern DataCenters Maximum availability, zero downtime ➔ maximum reliability
➔ Cost reduction
■■
Short installation times
The use of GigaLine® DClink results
Costs per link*
■■
Maximum performance
in cost savings of up to 55 % in
100 %
■■
Minimal space requirement – high packing density
comparison with traditional modular
■■
Cost efficiency
systems using MPO connection
■■
Environmental compatibility – Green IT
technology.
separately. For example, optimising the environmental performance will lead to a reduction in costs. Investing in industrially pre-assembled components is usually associated with higher costs, but enables installation and testing times to be reduced, thus reducing the cost associated with downtime.
45 %
DClink
The diverse requirements for DataCenters cannot be considered
Modular solutions with MPO
■■
* Example: Link length: 30 m, fibers: 24 x OS2e, plugs: LC Duplex
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 275
The advantages Exceed all requirements with LEONI
Giga Meg Giga
Va r i
oLin
aLin
Line ®
Line ®
D Clin
k
e DC link ®
D Cf le
x
e ® CP
LEONI can offer a range of high-quality products that go well beyond the current standards and requirements for data centers. ■■
An EC7 plug and the corresponding cable delivers performance far exceeding Class FA
■■
Fiber optic cable systems constructed using LEONI cables
The Installation
Ecologically aware cabling
Plug and play solutions for copper and fiber optic applications
Environmentally sound materials and production methods,
consist of pre-assembled links and the VarioLine® DClink
the possibility of recycling or ecologically viable recovery
frame (19", 1 RU) for the DClink modules. The DClink modules
and, last but not least, the reusability of products if required
are simply inserted and clicked into place from the rear after
guarantee maximum environmental compatibility. Cables
the links are installed.
and components are RoHS-compliant.
DClink system solutions
Optimising attenuation
DClink can be used to create fiber optic, copper or mixed
A GigaLine® DClink offers up to 70 %
Attenuation per link*
configurations in various categories. This renders on-site
less attenuation than conventional
IL = 1.4 dB 100 %
connectivity.
IL = 0.4 dB > 30 %
* Example: Link length: 30 m, fibers: 24 x OS2e, plugs: LC Duplex
www.leoni-infrastructure-datacom.com
DClink
modular systems using MPO
removed again using a simple release tool.
Modular solutions with MPO
assembly completely unnecessary. The modules can be easily
Fields of application
offer enormous reserves for attenuation and bandwidth
276
Comparison of cabling systems Single cable vs. multi cable
Single cables – complex installation and cannot be reused It is not just installing new cables that is difficult and timeconsuming, but also removing the old cables. The only options are either to cut them out or simply leave them where they are. This means that there is no practical way of reusing them and they are not recycled. The disorganised way in which the cables are installed obstructs the flow of cooling air. Only a higher volumetric flow rate and/or a lower air temperature can help here. Both mean higher costs and increased environmental impact.
www.leoni-infrastructure-datacom.com
Office
Industry
DataCenter 277
Multi cables – quick and clean installation and can be reused at any time Pre-assembled multi cable solutions ensure a clean and clear cabling layout in the raised floor. As well as making installation easier and therefore quicker, this also helps to improve cooling air circulation. Cables and components are RoHS-compliant. The low volume of the installed multi cables guarantees an
Fields of application
unobstructed flow of cooling air and therefore uses less energy.
www.leoni-infrastructure-datacom.com
278
Index Introduction
2
Cable plugs
80
Portfolio
2
Jack modules
81
Contents
3
Double modules RJ45
82
Welcome to the datacom mega store for cable and system solutions
4
Link extenders
83
The LEONI Group
6
Telephone patch panel
83
Infrastructure & Datacom Business Unit
7
Patch panel 19"
84
Quality and environmental management
8
Modular patch panels 19"/1 RU
85 86
Industrial patch cord RJ45/RJ45
Cat. 6/500 MHz
125
Patch cord TERATM
126
Patch cord and connection cable EC7, 4 pairs
128
Patch cord and connection cable EC7, 2 pairs
129
Patch cord and connection cable EC7, 1 pair, shielded
130
Patch cord and connection cable EC7, 1 pair/2 pairs, shielded
131
Trunk cable
132
MegaLine® Cu data cables
10
Modular patch panels 19"/1 RU for link extenders
SPACE concept
12
DIN rail housing
87
Trunk cable, industrial
133
SPACE- Security
13
Industrial housing IP44
88
Trunk cable, 8-port RJ45
134
SPACE - Performance
14
Industrial housing IP65/67
88
Trunk cable, 4-port/8-port
135
SPACE - Application
16
89
SPACE - Construction
17
Wall outlets for VarioKeystone® jack modules
MegaLine® Connect45 trunk cable with jack modules Cat. 6A/Cat. 6A
136
SPACE - EMC
18
VarioKeystone® accessories
90
MegaLine® Connect45 trunk cable, 8-port
137
Cable assembly tools
91
CP cable
138
EC7 CP cable
139
Patch accessories
140
Type codes
19
Cable types
20
MegaLine® Connect 45 Cu connectivity
92
MegaLine® G12-150 S/F
22
Connectivity can be so easy
94
MegaLine® F10-130 S/F
24
LEO (Light Emitting Outlet)
95
MegaLine® F10-115 S/F
26
System overview
96
MegaLine® F6-90 S/F
28
Cable plugs
98
MegaLine® F6-80 S/F
30
Jack modules in VarioKeystone® format
99
MegaLine® E5-70 S/F
32
Jack modules in keystone format
100
MegaLine® E5-70 F/F
34
Patch panels 19"/1 RU
101
MegaLine® E5-60 U/F
36
Wall outlets
102
MegaLine® E2-45 U/F
38
Accessories & tools
103
MegaLine® E2-30 F/U
40
ELine 1200® EC7 Cu connectivity
104
The passive cabling system for multimedia applications
106
System overview
108
EC7 jack and accessories
110
Wall outlet insert
111
EC7 patch panel
112
EC7 accessories
MegaLine® E2-30 U/U
42
MegaLine® D1-20 SF/U
44
MegaLine® F10-120 S/F flex
46
MegaLine® F6-90 S/F flex
48
MegaLine® D1-20 SF/U flex
50
MegaLine® F10-130 S/F (L)2Y
52
MegaLine® F10-130 S/F QH
54
MegaLine® F10-130 S/F Vö
56
MegaLine® F10-115 S/F V
58
MegaLine® F6-90 S/F 2Y
60
MegaLine® D1-20 SF/U 2Y
62
MegaLine® D1-20 SF/U HQH
64
MegaLine® F10-120 S/F 11Y flex
66
MegaLine® F6-70 S/F 11Y flex
68
MegaLine® D1-20 S/U 11Y superflex
70
VarioKeystone® Cu connectivity
72
The innovative connection concept
74
One click takes you to the next generation
75
Benefits that speak for themselves
76
No limits
77
System overview
78
®
Test report
141
MegaLine® Acceptance measurement
142
Acceptance measurement
143
Channel
144
Permanent link
145
Acceptance measurement Class EA
146
Acceptance measurement Class F
147
Acceptance measurement Class FA
148
Alien crosstalk
150
GigaLine® FO data cables
152
The fiber
154
For LAN, WAN and SAN
157
Fiber qualities
158
Colour codes
159
Type codes
160
112
Cable sheath material for fiber optic cables
161
Patch panel 19" with 24/48 ports
113
Rodent protection for fiber optic cables
162
EC7 mini patch panel with 6 ports
114
Pictograms
163
EC7 mounting tool
114
Handling and safety notices
164
EC7 measuring equipment
115
GigaLine® indoor cable, duplex fig 8
165
MegaLine® Cu patch cords/ trunk cables
116
GigaLine® indoor cable, duplex fig 0
166
Patch cord RJ45/RJ45 Cat. 5/100 MHz
118
GigaLine® indoor cable, mini breakout
167
Patch cord RJ45/RJ45 Cat. 6/250 MHz
119
GigaLine® breakout cable
168
Patch cord RJ45/RJ45 Cat. 6/500 MHz
120
169
Patch cord RJ45/RJ45 Cat. 6A/500 MHz
121
GigaLine® universal cable, mini breakout 800 N
LED patch cord RJ45/RJ45
GigaLine® universal cable, central 2500 N
170
122
Industrial patch cord RJ45/RJ45 Industrial patch cord with Han® 3A plugs
Cat. 6/500 MHz Cat. 5/100 MHz Cat. 6/Class E
123
GigaLine® universal cable, stranded 4000 N
171
GigaLine® universal cable, central 2500 N
172
LEONI "fire secured" fiber optic data cables
173
124
www.leoni-infrastructure-datacom.com
279
LEONI news VarioLine® Modular system peripherals
236
VarioLine® CP – Consolidation point range
238
Consolidation point housing, 6-port
240
177
Consolidation point housing, for 6, 12, 24-port module panels
241
178
Module panels with 6, 12, 24 ports
242
GigaLine® outdoor cable, stranded 4000 N
179
Floor outlet, round/rectangular
244
To request a copy of LEONInews, simply send an
GigaLine® outdoor cable, stranded
180
VarioLine® DC – DataCenter range
246
e-mail to:
[email protected]
GigaLine® FO connectivity
182
DClink frame 19"/1 RU
248
Fiber optic cabling systems
184
DataCenter accessories
249
GigaLine® Trunk and splice boxes
186
DataCenter cable routing panel 19"/1 RU
250
Fiber optic trunk box
188
VarioLine® UF – Underfloor systems
252
Fiber optic trunk box, telescopic
190
System overview
254
Fiber optic splice box, fixed
192
258
GigaLine® Compact – FO distribution system
Mounting plates for underfloor systems for mounting wall outlets
194
259
Compact fiber optic rack
196
Mounting plates for underfloor systems for mounting adapter plates
Compact fiber optic module
197
Adapter plates for underfloor systems
260
Compact fiber optic module, for splicing solutions
Excess-length module
262
198
Splice tray
262
GigaLine® Office and floor distributor
201
Cable retainer
263
Office and floor distributors
202
Dummy cover
263
Office field of application
264
GigaLine® "fire secured" universal cable, central with CI, 90 min total system integrity
174
GigaLine® "fire secured" universal cable, central with CI, 120 min total system integrity
175
GigaLine® outdoor cable, central 1750 N
176
GigaLine® outdoor cable, stranded 4000 N GigaLine® outdoor cable, central 1750 N
GigaLine® Fiber-To-The-Desk (FTTD) wall outlets
205
Our regularly updated information services such as the LEONI newsletter keep you abreast of recent developments at LEONI and on the market.
Generic cabling in office buildings
265
206
Industry field of application
266
FTTD wall outlets cable reservoir/splice tray
207
Generic cabling in industrial setting
267
FTTD outlet for cable ducts
208
Industrial IT cabling
268
FTTD mounting bracket for cable ducts
209
MICE concept
269
GigaLine® FO patch cords/trunk cables
210
Industrial IT cabling
270
Fiber optic patch cord, breakout
212
Fiber optic patch cord, MiniZip
214
Fiber optic patch cord, LC/PC Uniboot
215
Fiber optic patch cord, MTP
216
GigaLine® Trunk – pre-assembled trunk cables
219
Fiber optic trunk cable, mini breakout
220
Fiber optic trunk cable, breakout
222
Fiber optic trunk cable, outdoor
224
Visit our homepage:
Fiber optic trunk cable, universal
226
www.leoni-infrastructure-datacom.com
GigaLine® DataCenter links
228
DataCenter links
230
Here you will find the latest information
DataCenter link up to 100 Gbit/s
231
■■
Product and company news
DataCenter link
232
■■
Specialist articles
DataCenter link MTP module
233
■■
Trade fairs, seminars and roadshows
GigaLine® Acceptance measurement
234
■■
Acceptance measurement
235
Announcement texts
■■
Standardisations/certification programmes
FTTD wall outlets for surface/flush mounting
www.leoni-infrastructure-datacom.com
Han® 3A industrial outlets
271
DataCenter field of application
272
Generic cabling in DataCenters
273
Requirements and solutions
274
The benefits
275
Comparison of cabling systems
276
Find out more:
Business Unit Infrastructure & Datacom
[email protected] www.leoni-infrastructure-datacom.com
LEONI Kerpen GmbH
LEONI Studer AG
Zweifaller Strasse 275–287
Herrenmattstrasse 20
52224 Stolberg
4658 Däniken
Germany
Switzerland
Telephone +49 (0) 2402 17 1
Telephone +41 (0) 62 288 82 82
Telefax
Telefax
+49 (0) 2402 75154
+41 (0) 62 288 83 83