Heating
Meltemi Door Curtains
Heating
SABIANA ENVIRONMENTAL COMFORT
COD. A4390100 C/09/06
MELTEMI - EX - 09/06
Meltemi Door Curtains
ICIM ISO 9001 - Cert. n° 0545/3
Sabiana s.p.a.
•
via Piave, 53 • 20011 Corbetta • Milano • Italy • phone +39.02.97203.1 r.a. / +39.02.97270429 / +39.02.97270576 fax +39.02.9777282 / +39.02.9772820 • www.sabiana.it •
[email protected]
Unit heaters Radiant panels Fan coils Air handling units Flues
SABIANA ENVIRONMENTAL COMFORT
Copertina MELTEMI Inglese
12-09-2006
12:00
Pagina 2
CONTENTS
Introduction
Constructional characteristics of the main components
“MELTEMI” door curtains Pag. 03
Dimensions and weight
Pag. 03
Installation notes
Pag. 03
Models
Pag. 04
Correct selection of the door curtain
Pag. 06
Technical specifications
Pag. 08
Thermal emissions of the “MELTEMI” with hot water coil
Pag. 09
Water side pressure drop
Pag. 10
Position of the water connections
Pag. 10
Electrical connections (Power supply and Controls)
Pag. 11
Wall mounted electronic control
Pag. 12
Accessories
Pag. 16
The range of SABIANA MELTEMI door curtains offers the maximum flexibility in the protection of doors and open access compartments; by connecting the door curtain modules, the openings can be protected with a continuous system and an uninterrupted air barrier. This range of high speed door curtains can protect against the entrance of cold air streams in the winter, the loss of cooled air in the summer and the effects of dust and pollution, maintaining the ambient air clean and in the desired conditions. Furthermore, the systems can also be used to protect the areas dedicated to refrigeration so as to reduce the loss of cold air. The use of high speed fans allows the installation of the door curtains even in areas where food is prepared, to prevent the entrance of insects. In essence, SABIANA offers a protection solution wherever there is the need to open a door.
MU Model
MC Model
MI Model
2
Constructional characteristics of the main components Cabinet Made from hot galvanised metal plate, epoxy powder painted, furnace baked. Class of protection of the unit IP 20.
Fan assembly Made up of aluminium tangential fans with concave fins positioned in a spiroidal configuration along the length of the fan. The fan shaft is made from two galvanised plate.
Motor Single phase 230V 50Hz, two speeds for MU-MC models. Three phase 400V 50Hz, two speed sliding motor for MI models.
Hot water coil (MU-W, MC-W, MI-W) The W series units are complete with a hot water coil (for heating only), made from copper pipes with aluminium fins bonded to the pipes by mechanical expansion. Maximum water temperature 100°C, maximum operating pressure 8 bars. The coils are fitted with female threaded fittings 3/4” (MC, MI models) and male threaded fittings 1/2” (MU). The coils have either 2 rows, for MC-MI models, or 1 row for MU.
Electric resistance (MU-E, MC-E) The “E series” units come with sealed electric resistances or galvanised steel filament resistances.
Dimensions and weight
MODEL Dimensions (mm) Weight (kg)
A B C A W E
MU-1000 1064 300 200 11 17 18
MU-1500 1564 300 200 16 23,5 26
MC-1000 1070 417 280 26 29 30
MC-1500 1570 417 280 34 38 39
MI-1000 1070 534 355 55 60 –
MI-1500 1570 534 355 72 76 –
Installation notes Distance that must be guaranteed for the correct operation of the door curtain
In order to allow suitable space for maintenance personnel to work, but above all to guarantee the correct operation of the door curtain, the distance indicated to the side must be observed. The product, in addition, must not be installed in compartments or false-ceilings without adequate air intake. 3
Models
MU model The MU range of modular door curtains for offices and commercial environments combines the benefits of the most advanced aeraulic technology with the flexibility of a modular system. These very compact units can be fitted individually or joined to create a continuous door curtain. The remote controls and the connection kit allow any number of units to be managed by one single control. The high performance tangential fans coupled with a powerful “twin shaft” motor provide each module the best performance characteristics for entrances up to 2.5m in height, offering protection against winter cold, summer heat, dust and pollution.
MC model The MC range of modular door curtains for larger commercial applications uses powerful “twin shaft” motors and high efficiency tangential fans to provide thermal protection for entrances up to 4m in height. The 1m and 1.5m modules can be joined to create a continuous door curtain and an uninterrupted unit profile.
4
Models
MI model The MI range of modular door curtains for industrial applications provides a high speed barrier for the protection of industrial doors and logistics platforms in which doors must be left open to allow the movement of vehicles and goods. These high performance door curtains use three-phase motors to supply the maximum air flow, creating effective barriers for doors up to 6m high. Available in models with fan only or hot water supply. The MI series allows production areas and stores to be isolated, minimising the entrance of cold air streams and protecting the working areas.
5
Correct selection of the door curtain
Selecting the correct door curtain The quantity of air that passes through an open door depends on three main factors: - the difference in pressure between the indoor environment and the outdoor - the temperature difference - the wind speed Simplifying these phenomena, we can say that an air stream will pass through the door if the indoor conditions, in terms of temperature, pressure and air speed, are different from the outdoor conditions. The air streams are therefore generated by the natural trend to make the pressure and temperature uniform between two joining environments. In a heated environment, the hot air will leave the environment to be replaced by cold air. In the presence of wind, the currents of air through opening will be increased.
Indoor/Outdoor Pressure The difference in pressure between the environment and the surrounding space can be eliminated by controlling the ventilation system that neutralises the difference between the indoor and outdoor pressure.
Air flow generated by differences in temperature (QT) The hot air inside is less dense, and consequently lighter, than the cold outside air, and therefore a difference in pressure is created through an open door. The cold outdoor air flows through the bottom of the opening and pushes the hot air from the indoor environment to the outdoor, through the top of the opening.
The air flow varies according to the temperature difference between the inside and the outside.
Air flow due to the force of the wind (QV) When the wind blows against the door, air flows through the opening. The flow of air is distributed uniformly across the entire opening. The quantity of air that flows is therefore proportional to the component of the wind speed that is perpendicular to the door. (After a certain time, the environment will reach a value of overpressure such as to reduce the flow of air to just the level of the leakages from the room).
Total air flow (Qtot) The total air flow through an opening is equal to the sum of the flows due to the temperature difference and the flow due to the force of the wind.
Qtot = QT + QV
6
Correct selection of the door curtain
Operating principles of a door curtain
Door curtains are used to prevent cold air from entering an environment and the loss of hot air to the outside. They are also used to protect air conditioned rooms and cold stores against the entrance of hot air and losses of cold air. A door curtain creates a barrier across the open door, preventing unwanted currents of air. The speed of the air created by the door curtain must be high enough to force the resulting flow downwards. The door curtain should be aimed so that only a small part of the air is lost to the outside, keeping the cold air on the outside, following the air barrier, while the hot air remains inside the environment.
Criteria for selecting a door curtain It is important to choose the most appropriate model. The height of the door is a critical factor, as is the correct setting of the air speed.
If there is a negative pressure inside the environment, the performance of the door curtain will be substantially reduced: the ventilation should be balanced. In most cases, the door curtains must be installed on the inside of the opening that is being protected. Nonetheless, when having to protect a cold room, the curtain must be located on the warmer side, that is, the outside of the opening. For best performance, the door curtain should be located as near as possible to the opening, and cover the entire width of the door. The direction and speed of the air barrier should be adjusted according to the characteristics of the door compartment. The pressure generated by the wind tends to cancel the effect of the door curtain, forcing the curtain of air produced back inside the room. In these situations, the door curtain should be inclined towards the outside.
7
Technical specifications Meltemi ambient ventilation - A series MODEL
HORIZONTAL AND VERTICAL INST.
HORIZONTAL INSTALLATION ONLY
MU-1000A MU-1500A MC-1000A MC-1500A
MI-1500A
m3/h
1250/900
1900/1160
2400/1700
3600/2300
3800/3000
5700/4500
dB(A)
53/45
53/40
64/54
64/55
71/68
72/69
0,5
0,6
2,3
2,9
1,9
2,8
Air flow Sound pressure 1
MI-1000A
Absorption
A
Voltage
V
Meltemi with hot water coil - W series
230V~
230V~
HORIZONTAL AND VERTICAL INST.
MODEL
400V~ (3ph+N)
HORIZONTAL INSTALLATION ONLY
MU-1000W MU-1500W MC-1000W MC-1500W MI-1000W
MI-1500W
1150/850
1700/1100
2200/1520
3300/1870
3400/2700
5100/4050
7,1/6,4
11,3/8,7
15,5/12,5
23,4/17,3
27,4/24,0
43,0/37,6
dB(A)
52/47
48/40
62/54
64/58
70/67
71/68
°C
18/20
19/23
20/24
22/27
24/26
25/27
Absorption
A
0,5
0,6
2,3
2,9
1,7
2,8
Voltage
V
m /h
Air flow
3
Emission
kW
Sound pressure ∆t
1
2
Meltemi with electric resistance - E series MODEL
230V~
230V~
400V~ (3ph+N)
HORIZONTAL INSTALLATION ONLY MU-1000E MU-1500E MC-1000E MC-1500E
m3/h
Air flow
1250/900
1900/1160
2400/1700
3600/2300
Emission 1 stage
kW
4,5
6,8
6
9
Emission 2
kW
9,0
13,5
12
18
dB(A)
53/45
53/40
64/54
64/55
°C
21/30
21/34
15/21
15/22
Absorption
A
0,5
0,6
2,4
2,9
Voltage
V
st
nd
stage
Sound pressure ∆t
3
1
400V~ (3ph+N)
1 - The sound pressure levels are measured at a distance of 5m; directional effect with factor 2 (hemispherical emission with unit hung in the centre of the ceiling); equivalent area of absorption = 200m2 (Sabine). 2 - Water temperature 80/60°C, Entering air temperature + 15°C. 3 - Increase in air temperature with the resistance in 2nd stage operation and low/high air flow.
Meltemi E series - Product description The "E series" door curtains are fitted with electric heaters and the corresponding control components (electromechanical contactors). The units are fitted with a safety thermostat to protect the internal devices in the event of excess temperature. Configuration with filament resistances In the configuration with galvanised steel filament resistances, there are two safety thermostats, both with automatic reset. If activated, power is instantly cut-off to both the resistances and the fan. Configuration with sealed resistances The configuration with sealed resistances, on the other hand, has only one safety thermostat, with manual reset, featuring a bulb sensor. If activated, power is only cut-off to the heaters. Post-ventilation The post-ventilation function is included in MC-E and MI-E versions. When the unit is switched off, the fan continues operating in order to cool the inside of the unit. This only occurs when the door curtain is switched off from the ESW control. When disconnecting the unit directly from the main power line, the post-ventilation function is not able to start, and consequently the safety thermostat will be activated. This must then be reset manually before correctly restarting the door curtain. 8
Thermal emissions of the “MELTEMI” with hot water coil - W series Entering air temperature: +15°C Water temperature EWT 80°C - LWT 70°C MODEL
MU-1000W MU-1500W MC-1000W MC-1500W MI-1000W MI-1500W
Water temperature EWT 80°C - LWT 60°C
Water temperature EWT 60°C - LWT 40°C
Speed
Air flow m3/h
Water flow l/h
Emission kW
Leaving air temp. °C
Water flow l/h
Emission kW
Leaving air temp. °C
Water flow l/h
Emission kW
Leaving air temp. °C
high
1150
684
8,2
36
288
7,1
33
144
4,2
26
low
950
612
7,3
38
252
6,4
35
144
3,7
27
high
1700
1080
12,9
37
468
11,3
34
252
6,7
26
low
1100
828
9,9
41
360
8,7
38
216
5,2
29
high
2200
1548
18,2
39
648
15,5
35
360
8,7
26
low
1520
1224
14,5
43
504
12,5
39
288
7,1
29
high
3300
2304
27,2
40
972
23,4
37
540
13,3
27
low
1870
1692
19,9
46
720
17,3
42
396
10
31
high
3400
2664
31,1
42
1152
27,4
39
684
16,3
29
low
2700
2304
27,1
45
1008
24
41
612
14,3
31
high
5100
4176
48,6
43
1836
43
40
1080
25,8
30
low
4050
3636
42,3
46
1584
37,6
42
936
22,6
31
Entering air temperature: +20°C Water temperature EWT 80°C - LWT 70°C MODEL
MU-1000W MU-1500W MC-1000W MC-1500W MI-1000W MI-1500W
Water temperature EWT 80°C - LWT 60°C
Water temperature EWT 60°C - LWT 40°C
Speed
Air flow m3/h
Water flow l/h
Emission kW
Leaving air temp. °C
Water flow l/h
Emission kW
Leaving air temp. °C
Water flow l/h
Emission kW
Leaving air temp. °C
high
1150
612
7,5
39
252
6,4
37
144
3,4
29
low
950
540
6,7
41
216
5,8
38
108
3,1
30
high
1700
1008
11,8
40
432
10,2
37
216
5,6
30
low
1100
756
9
44
324
7,9
41
180
4,4
32
high
2200
1404
16,6
42
576
13,9
38
288
7,1
29
low
1520
1116
13,2
46
468
11,2
42
216
5,8
31
high
3300
2124
24,8
43
900
21
40
468
10,9
30
low
1870
1548
18,1
49
648
15,5
45
324
8,2
33
high
3400
2412
28,4
45
1044
24,8
41
576
13,6
32
low
2700
2124
24,8
47
900
21,7
44
504
11,9
33
high
5100
3816
44,4
46
1656
39
42
900
21,5
32
low
4050
3312
38,7
48
1440
34
45
792
18,9
34
9
Water side pressure drop - W series
The water pressure drop figures refer to a mean water temperature of 65°C.
For different temperatures, multiply the pressure drop figures by the correction factors K.
Position of the water connections - W series
10
Tm °C
K
40 50 60 70 80
1,14 1,08 1,02 0,96 0,90
Electrical connections (Power supply and Controls) Voltage
TYPE OF UNIT A SERIES
MODEL
W SERIES
E SERIES
MU
230V~ (single phase) at 50Hz 230V~ (single phase) at 50Hz
400V~ (3ph + N) at 50Hz
MC
230V~ (single phase) at 50Hz 230V~ (single phase) at 50Hz
400V~ (3ph + N) at 50Hz
MI
400V~ (3ph + N) at 50Hz
400V~ (3ph + N) at 50Hz
—
Table of combinations between CONTROLS - DOOR CURTAINS
TYPE OF CONTROL AVAILABLE
MODEL
MU - 1000A MO-3V (max. 4 units connected to one control) MU - 1500A
MO-3V (max. 4 units connected to one control)
MU - 1000W TMO-T (max. 4 units connected to one control) MU - 1500W TMO-T (max. 4 units connected to one control)
For installations with more than 4 units managed by one control, the SEL-ME speed selector must be used
MU - 1000E ESW + ETH MU - 1500E ESW + ETH MC - 1000A MO-3V (one unit only connected to one control) MC - 1500A MO-3V (one unit only connected to one control) MC - 1000W TMO-T (one unit only connected to one control) MC - 1500W TMO-T (one unit only connected to one control)
For installations with multiple units managed by one control, the SEL-ME speed selector must be used
MC - 1000E ESW + ETH MC - 1500E ESW + ETH MI - 1000A MO-3V MI - 1500A MO-3V MI - 1000W TMO-T MI - 1500W TMO-T
11
Wall mounted electronic controls for ambient ventilation units - A series (MU-A, MC-A and MI-A models) Identification
Code
MO - 3V
9060160
- Manual switch of the 2 fan speeds, without thermostatic control.
Connection Type BASIC A This type of connection allows: - fan ON / OFF control - fan high / low speed control with continuous operation
Requirements: - Wall mounted controller MO-3V (code 9060160)
Connection Type STANDARD A Identical functions to the BASIC A connection, with the addition of a door switch (DSW) that stops the fan when the door is closed and starts it again when the door opens.
Requirements: - Wall mounted controller MO-3V (code 9060160) - Door switch DSW (code 9039001) 12
Wall mounted electronic controls for units with hot water coil - W series (MU-W, MC-W and MI-W models)
-
Identification
Code
TMO - T
9060161
Manual switch of the 2 fan speeds. Summer / Winter switch. Electronic room thermostat for fan(ON - OFF). Electronic room thermostat for water valve (ON - OFF). It allows to control the low temperature cut-out thermostat (TME).
20°
°C
Connection Type BASIC W This type of connection allows: - fan ON / OFF control - fan high / low speed control with continuous operation - electronic room thermostat for water valve (ON - OFF) - it allows to control the low temperature cut-out thermostat (TME)
Requirements: - Wall mounted controller TMO-T (code 9060161)
- Water valve
Connection Type STANDARD W Identical functions to the BASIC W connection, with the addition of a door switch (DSW). This type of connection can be used to make the following two variants: - in the cases where the doors are opened and closed again quickly, no valve is connected but the hot water is allowed to circulate through the coil - in the cases where the doors remain open for long periods, fit the valve as shown in the wiring diagram; the valve is closed by the switch DSW when the door is closed and opened when the door is open (continuous ventilation)
Requirements: - Wall mounted controller TMO-T (code 9060161)
- Door switch DSW (code 9039001)
- Water valve 13
Wall mounted electronic controls for units with electric resistance - E series (MU-E and MC-E models) To complete the electrical control system, both the components shown below should be used to create the optimum configuration for managing the operation of the door curtain.
Identification
Code
Identification
Code
ESW
9039000
ETH
9039002
- Speed switch.
Connection Type BASIC E This type of connection allows: - fan ON / OFF control - fan high / low speed control with continuous operation - thermostatic control of the emission of the electric resistance (full emission, half emission or off)
Requirements: - Electronic switch ESW (code 9039000) - Electronic thermostat ETH ( code 9039002)
Connection Type STANDARD E Identical functions to the BASIC E connection, with the addition of a door switch (DSW) that turns the heater off when the door is closed and turns it on when the door is open (continuous ventilation).
Requirements: - Electronic switch ESW (code 9039000) - Electronic thermostat ETH ( code 9039002) - Door switch DSW (code 9039001) 14
- 2 stage thermostat.
Connecting multiple units managed by just one control Connection of MU/MC models “A series” with SEL-ME
Connection of MU/MC models “W series” with SEL-ME
15
Accessories
DSW door switch Installed in the system as shown in the "Standard" diagrams in this catalogue, the DSW door switch enables the operation of the door curtain (fan, opening the valve, power supply to built-in heaters) when the doors are opened, and disables operation when the doors are closed. To prevent the continuous start-stop operation (stress on the motor) of the unit in places where the doors are frequently opened-closed, the DSW features a time-delay function. Specifically, a device (trimmer) is used to adjust the delay for switching off the fan (the delay can be adjusted from 2 seconds to 10 minutes).
Identification
Code
DSW
9039001
Connection kit Required to connect a series of units together (MU-MC and MI models). ATTENTION! For the electrical connections of multiple units, see the table of combinations between “CONTROLS - DOOR CURTAINS” on page 11.
Identification
Code
MU/MC KIT
9039005
MGS2, brackets Set for modular brackets mounting. Consists of two suspension brackets and four bracket plates. The set also includes plastic frames that will cover the cables that can be threated inside the brackets. The brackets may be cut for short installations.
Identification
Code
MGS2
9039015
VERSION
MU
SERIES
ALL
16
Accessories
TME cut out thermostat
To be fitted between the coil fins (only W series). To be used with the TMO-T control. Code 3021091.
VERSION
It stops the fan when the water temperature is lower than 38°C and it starts the fan when is higher than 42°C.
MODEL
MU - MC - MI BASIC W - STANDARD W
Three-way ON-OFF valves with electric control
M II
I
III
CODE
DN (Ø)
Kvs
9039030 15 (1/2") 1,6 9039031 20 (3/4") 2,5 9039032 20 (3/4") 4
R V
∆P max ∆P close off operating KPa KPa 150 50 50
50 50 50
Two-way ON-OFF valves with electric control
M R
V
CODE
DN (Ø)
Kvs
9039033 15 (1/2") 1,7 9039034 20 (3/4") 2,8 9039035 25 (1") 5,2
∆P max ∆P close off operating KPa KPa 50 50 60
250 150 80
The descriptions and illustrations provided in this publication are not binding: Sabiana reserves the right, whilst maintaining the essential characteristics of the types described and illustrated, to make, at any time, without the requirement to promptly update this piece of literature, any changes that it considers useful for the purpose of improvement or for any other manufacturing or commercial requirements. 17
Copertina MELTEMI Inglese
12-09-2006
12:00
Pagina 2
CONTENTS
Introduction
Constructional characteristics of the main components
“MELTEMI” door curtains Pag. 03
Dimensions and weight
Pag. 03
Installation notes
Pag. 03
Models
Pag. 04
Correct selection of the door curtain
Pag. 06
Technical specifications
Pag. 08
Thermal emissions of the “MELTEMI” with hot water coil
Pag. 09
Water side pressure drop
Pag. 10
Position of the water connections
Pag. 10
Electrical connections (Power supply and Controls)
Pag. 11
Wall mounted electronic control
Pag. 12
Accessories
Pag. 16
The range of SABIANA MELTEMI door curtains offers the maximum flexibility in the protection of doors and open access compartments; by connecting the door curtain modules, the openings can be protected with a continuous system and an uninterrupted air barrier. This range of high speed door curtains can protect against the entrance of cold air streams in the winter, the loss of cooled air in the summer and the effects of dust and pollution, maintaining the ambient air clean and in the desired conditions. Furthermore, the systems can also be used to protect the areas dedicated to refrigeration so as to reduce the loss of cold air. The use of high speed fans allows the installation of the door curtains even in areas where food is prepared, to prevent the entrance of insects. In essence, SABIANA offers a protection solution wherever there is the need to open a door.
MU Model
MC Model
MI Model
2
Copertina MELTEMI Inglese
12-09-2006
11:59
Pagina 1
Heating
Meltemi Door Curtains
Heating
SABIANA ENVIRONMENTAL COMFORT