Preview only show first 10 pages with watermark. For full document please download

Midos Type Mvaj Tripping And Control Relays

   EMBED


Share

Transcript

Midos Type MVAJ Tripping and Control Relays Features ● High speed operation ● High and low burden alternatives ● Low burden models suitable for ac and dc operation ● Models surge proof against high capacitance discharge currents in the dc supply system, are available ● Control relays immune to ac can be supplied Figure 1: Type MVAJ relay withdrawn from case Models Available Type MVAJ relays may broadly be divided into three groups: ● High burden tripping relays complying with ESI 48-4 Class EB2 ● Low burden tripping relays which comply with ESI 48-4 Class EB1 ● Control relays which meet the requirements of National Grid Company SPEC.NGTS 2.19:1996 Table 1 lists the general characteristics and includes information on how the relay burden is modified at, or just after operation. ‘Economy’ indicates that the burden is reduced to a low value. Instantaneous cut off is a feature of some hand and electrically reset elements and reduces the burden to 2 zero, whilst others incorporate a time delay to enable to series elements to operate. This time delay is 40ms to 60ms in all cases except that of the types MVAJ 26 and 56 in which the delay is 2s. All low burden relays are suitable for ac or dc operation. All high burden relays are for dc operation only. burden which is either cut off at operation or economised to a low figure, either instantaneously or after a time delay. Application The high burden also permits the use of supervision relays such as type MVAX where the wiring is at risk and provides reliable operation of series elements such as repeat relays type MCAA. For the latter purpose type MVAJ relays can be provided with a time delayed economising feature. High Burden Tripping Relays Types MVAJ 21, 23, 24, 25, 26, 27, 28, 29, 51, 53, 54, 55, 56, 57, 58 and 59 These relays are suitable for use in high security circuit breaker tripping circuits. In particular they can be used in distributed tripping or control relay contact logic schemes, where the initiating contact may be remote from the relay. The relays have a high The high burden provides immunity to capacitance discharge currents, which can result at the inception of an earth fault on battery wiring and immunity to the subsequent leakage current. Relay type Contact mechanism Operation indicator Cut off Specifications Group Outgoing contacts Case size single stack single stack double stack double stack MVAJ 11 SR H/R Economy ESI48-4 EB1 Low burden 5 10 4 4 MVAJ 13 HR H/R Instantaneous ESI48-4EB1 Low burden 5 10 2 4 MVAJ 14 ER H/SR Instantaneous ESI48-4EB1 Low burden 5* 10* 2 4 MVAJ 15 H/ER H/R Instantaneous ESI48-4EB1 Low burden 5* 10* 2 4 MVAJ 17 SR H/R Economy NGC SPEC. NGTS 3.6.3:1992 Low burden 4 – 5 – MVAJ 21 SR H/R Economy ESI48-4EB2 High burden 5 10 4 4 MVAJ 23 HR H/R Instantaneous ESI48-4EB2 High burden 4 10 2 4 MVAJ 24 ER H/R Instantaneous ESI48-4EB2 High burden 4* 9 2 4 MVAJ 25 H/ER H/R Instantaneous ESI48-4EB2 High burden 4* 9 2 4 MVAJ 26 SR H/R Time delay Economy ESI48-4EB2 High burden 5 10 4 4 MVAJ 27 HR H/R Time delay ESI48-4EB2 High burden 9 4 MVAJ 28 ER H.R Time delay ESI48-4EB2 High burden 8 4 MVAJ 29 H/ER H/R Time delay ESI48-4EB2 High burden 8 4 MVAJ 34 ER S/R Instantaneous NGC SPEC. NGTS 2.19:1996 Control in/out 7 4 4 stacks MVAJ 41 SR H/R Economy ESI48-4EB1 Lowburden 20 Contacts MVAJ 43 HR H/R Instantaneous ESI48-4EB1 Low burden 20 Contacts MVAJ 44 ER H/SR Instantaneous ESI48-4EB1 Lowburden * 18 Contacts MVAJ 45 H/ER H/R Instantaneous ESI48-4EB1 Lowburden * 18 Contacts All in size 8 MVAJ 51 SR H/R Economy ESI48-4EB2 Highburden 20 Contacts cases MVAJ 53 HR H/R Instantaneous ESI48-4EB2 High burden 20 Contacts MVAJ 54 ER H/R Instantaneous ESI48-4EB2 High burden 18 Contacts MVAJ 55 H/ER H/R Instantaneous ESI48-4EB2 High burden 18 Contacts MVAJ 56 SR H/R Time delay ESI48-4EB High burden 20 Contacts ESI48-4EB2 High burden 18 Contacts Economy MVAJ 57 HR H/R Time delay MVAJ 58 ER H/R Time delay ESI48-4EB2 High burden 16 Contacts MVAJ 59 H/ER H/R Time delay ESI48-4EB2 High burden 16 Contacts KEY SR - Self reset HR - Hand reset ER - Electrical reset H/ER - Hand/electrical reset H/SR - Hand/self reset Note: Relay types indicated * do not have continuously rated reset coils or internally wired cut-off contacts. If required, one pair of outgoing contacts may be wired externally for this duty; this will obviously reduce the number of available contacts. Table 1: List of MVAJ types available Low Burden Tripping Relays Types MVAJ 11, 13, 14, 15, 41, 43, 44, 45 connected directly to the dc supply via case terminals. Description These relays are suitable for applications where immunity to capacitance discharge and high minimum operation currents are not required. Since this reduces the necessary break duty on the associated protection output relay, this feature is particularly useful when several tripping relays are operated in parallel. High Burden Tripping Relays Types MVAJ 21, 23, 24,25, 26, 27, 28, 29, 51, 53, 54, 55, 56, 57, 58 and 59 Low Burden Self-reset Tripping Relay Type MVAJ 17 Control Relay Type MVAJ 34 The type MVAJ 17 is a low burden self-resetting tripping relay which complies with the provisions of NGC SPEC. NGTS.3.63:1992. Its main feature is the facility which allows the economising element circuit to be All relays use common standardised parts. Versions have one, two or four contact stacks depending upon the number of output contacts required. This is a dual-rated electrically reset relay, the main function of which is to switch protection and auto-reclosing equipment in and out of service from a remote point via pilot wires. It complies with NGC. SPEC. NGTS 2.19:1996. 3 Types MVAJ 21, 51 high burden self-resetting relays These relays use a contact on the main contact stack to energise a separate, rear-mounted economising element. After operation this reduces the burden by switching in resistance in series with the main element and switching out shunt resistance. Figure 2 shows a typical circuit diagram for self-resetting relays of this type with high speed economy. When the main attracted armature unit RL1 is energised by the protection contact PR, a contact RL1-a energises auxiliary element RL2. When contacts RL2-a and RL2-b open, resistor R4 is put in series with RL1 while the circuit to resistor R2 is broken. Types MVAJ 23, 24, 25, 53, 54, 55 high burden tripping relays with Instantaneous cut-off These relays incorporate a break contact in series with the operate coil. Located on the main contact stack, it is arranged to break the coil circuit once the relay mechanism has completely operated. This reduces the relay burden to zero as soon as mechanical latching of the contacts has occurred. cannot conveniently provide an auxiliary contact with a dwell time long enough to ensure correct tripping of the lower voltage circuit breaker. Types MVAJ 23 and 53 hand reset whilst the types MVAJ 24 and 54 have a second coil which, when energised, unlatches the relay resetting mechanism. Types MVAJ 25 and 55 may be reset either by hand or electrically, by means of the same design of mechanism. See Figure 3. Typically the relay is initiated by transformer protection, such as overall differential, restricted earth fault, and Buchholz relays, in arrangements where both the HV and LV circuit breakers are to be tripped simultaneously. Type MVAJ 26 and 56 time delay on drop-off relays The types MVAJ 26 and 56 relays have been specially designed for applications requiring a tripping relay which is self-resetting after a nominal delay of 2 seconds. This relay may be used, for example, for intertripping between the higher voltage and lower voltage circuit breakers of a large three phase power transformer. This may become necessary when the higher voltage circuit breaker is tripped after a heavy internal fault, by protection which The HV circuit breaker may be expected to trip more quickly than the LV breaker. So the tripping signal is maintained by the delayed resetting, to ensure complete clearance by the LV circuit breaker, even though the fault may have been cleared largely by the HV circuit breaker and the protection has started to reset. The MVAJ 26 and 56 relays can accept either a fleeting initiation or persistent initiation. With the latter, the relay will provide a tripping signal of corresponding duration plus the 2 seconds delay. The relay consists of a main attracted Combination of output contacts Left hand Note 1 (a) 14 16 CT shorting links make before (b) & (c) disconnect (b) Short terminals break before (c) (c) Long terminals A RL2-A 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 2 4 6 8 10 12 13 15 17 19 21 23 R1 R4 Case earth Right hand RL1 10 (OP) RL2-B RL1-A PR + 27 RL2 Vx V Module terminal block viewed from rear _ 28 Figure 2: MVAJ 21 self-reset with instantaneous economy (high burden) 4 R. Hand 1 2 3 4 5 6 4 5 6 B Output contacts to module terminals Contact stack L. hand 13 R. hand 1 R3 L. Hand 7 7 7 7 7 7 8 8 8 R2 Rear mounted facing rear viewed from front A 1 3 5 7 9 11 Combination 10M 9M 1B 8M 2B 7M 3B 6M 4B 5M 5B 4M 6B 3M 7B 2M 8B Module terminals 15 3 17 19 5 7 21 14 23 16 9 11 2 4 1 2 3 4 5 6 7 M M B B B B M M M M M B B M M M M M M M M M B B B B B M 8 B B M B Contact Description M : Make B : Break 6 8 M M M B B B 10 12 M M M M M B armature element with a hand reset operation indicator and one electromagnet with two contact stacks. Types MVAJ 27, 28, 29, 57, 58, 59 relays with time delayed drop-off. These relays are hand reset, electrically reset and hand/electrically reset respectively and all have time delayed cut-off circuits. The burden is reduced to zero 40/60ms after energisation by the use of a second attracted armature element mounted in the rear of the case. This time delay allows ample time for any flagging or auxiliary element in series with the tripping relay to operate before cut-off. Figure 4 shows a typical circuit diagram for an electrically reset trip relay with time delayed cut-off feature. When the contact PR is closed, relays RL1 (operate) and RL2(t) operate. After operation the current in the coil of RL1 (operate) is maintained by contact RL2-a; contacts RL1-a and RL1-b open, whilst RL1-c closes. The opening of RL1-a causes relay RL2(t) to start to reset. This resetting is delayed by 40-60ms by means of a copper slug fitted to the front of RL2(t). When RL2(t) resets, RL2-a opens, reducing the current through RL1 (operate) coil to zero. The relay is now latched mechanically into the operated state. It may now be reset via an external contact or pushbutton which energises the RL1 (reset) coil via the closed contact RL1-c. Low Burden Tripping Relays Types MVAJ 11, 13, 14, 15, 41, 43, 44, 45 These are low burden versions of types MVAJ 21, 23, 24, 25, 51, 53, 54 and 55 relays respectively. They comply with the less onerous requirements of ESI 48-4, Class EB1. Where self-reset reverse flags are fitted, a maximum of 8 output contacts is available. The operating time is not greater than 15ms Table 1 Front mounted facing front viewed from front Left hand Right hand Case earth 1 2 29 30 3 4 31 32 5 6 33 34 7 8 35 36 9 10 37 38 11 12 39 40 13 14 41 42 15 16 43 44 17 18 45 46 19 20 47 48 21 22 49 50 23 24 51 52 25 26 53 54 27 28 55 56 Module terminal block viewed from rear 42 44 30 32 34 36 38 40 41 43 45 47 B A Front mounted facing front viewed from front Left hand Right hand 29 31 33 35 37 39 14 16 A PR 27 RL1-A R1 RL1 9 (OP) RL2 9 (OP) Reset 25 28 Short terminals break before (c) (c) Long terminals – Output module to module terminals Contact Module terminals stack LH 41 45 42 43 47 44 RL1 RH 29 33 37 30 34 38 RL2 RL1-B RL1 RL2 (Reset) 26 31 35 39 32 36 40 17 14 15 19 16 1 5 9 2 6 10 3 7 11 4 8 12 LH 13 RH 1 2 CT shorting links make before (b) & (c) disconnect (b) Table 2 1 3 5 7 9 11 RL2-A RL2-B Note 1 (a) 2 4 6 8 10 12 13 15 17 19 B Vx + Combination of output contacts RL1 RL2 Combination R. L. R. L. Hand Hand Hand Hand 18M 1 2 1 2 M M M M M M M M M Contact description M : Make B : Break (Reset) Note: The numbers quoted in table 1 are for L. hand and R. hand stacks on RL1 and RL2. The code numbers used are for cross references to module terminals in table 2. Figure 3: MVAJ 55 hand and electrically reset (high burden) 5 Combination of output contacts Front mounted facing front viewed from front Left hand Right hand Case earth 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 B Vx 1 3 5 7 9 11 2 4 6 8 10 12 13 15 17 19 C A + – PR RL1-B 27 R1 RL2-A 25 Reset 28 (OP) RL1 8 R2 RL1-C (Reset) RL1 8 26 R3 Note 1 (a) (t) RL2 CT shorting links make before (b) & (c) disconnect (b) Short terminals break before (c) (c) Long terminals Contact stack L. hand 13 R. Hand 1 2 3 4 5 6 7 6 7 Module terminals 15 R. hand 1 A RL1-A L. Hand 8 8 8 8 8 8 8 9 9 Output contacts to module terminals Rear mounted facing rear viewed from front Module terminal block viewed from rear Combination 8M 7M 1B 6M 2B 5M 3B 4M 4B 3M 5B 2M 6B 1M 7B 8B 3 17 19 5 7 1 2 3 4 5 6 7 M M B B B B B M M M M B B B 8 9 M B M B 9 11 2 M M M M M M B 4 6 M B B B B B B 10 8 12 M M M B B B B M M M M M B B Contact Description M : Make B : Break Figure 4: MVAJ 28 electrically reset with time delayed cut off (high burden) Table 1 Front mounted facing front viewed from front Left hand Right hand Case earth 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 14 16 A RL1-A PR 27 R1 RL1 10 1 3 5 7 9 11 (OP) L. Hand 7 7 7 7 7 7 8 8 8 Table 2 Module terminal block viewed from rear V (b) Short terminals break before (c) (c) Long terminals Module terminals 17 21 14 15 19 23 16 28 CT shorting links make before (b) & (c) disconnect Contact stack L. hand 13 R. hand 1 2. Resistor fitted on 220/250V versions only 3. The numbers quoted for L. hand and R. hand stacks in table1 are code numbers used for cross references to module terminals in table 2 3 5 7 9 11 Figure 5: MVAJ 13 hand reset (low burden) 2 4 1 2 3 4 5 6 7 M M B B B B M M M M M B B M M M M M M M M M B B B B B M 8 B B M B Contact Description M : Make B : Break 6 R. Hand 1 2 3 4 5 6 4 5 6 Output contacts to module terminals Vx Notes 1. (a) 2 4 6 8 10 12 13 15 17 19 21 23 Combination of output contacts Combination 10M 9M 1B 8M 2B 7M 3B 6M 4B 5M 5B 4M 6B 3M 7B 2M 8B 6 8 M M M B B B 10 12 M M M M M B Technical Data Ratings All relays except MVAJ 17. and MVAJ 34 MVAJ 17 Rated voltage (Vx) Operative range (V) 24/27 30/34* 48/54* 110/125* 220/250 110/125 14.4 – 32.4 18 – 40.8 28.8 – 64.8 66 – 150 122 – 300 66 –150 MVAJ 34 dual rated 48/54 110/125 220/250 0Ω pilot 200Ω pilot 37.5 – 60 87.5 –137.5 122 – 286 46 – 56 87.5 – 137.5 175 – 275 *These ranges only are applicable to ESI 48-4 Burdens Burden (W) To operate Relay type Single stack MVAJ 11 25 MVAJ 13 25 MVAJ 14 25 MVAJ 15 25 MVAJ 17 25 MVAJ 21 150 MVAJ 23 150 MVAJ 24 150 MVAJ 25 150 MVAJ 26 150 MVAJ 27 – MVAJ 28 – MVAJ 29 – MVAJ34 (See Note 3 below) MVAJ 41 MVAJ 43 MVAJ 44 MVAJ 45 MVAJ 51 MVAJ 53 MVAJ 54 MVAJ 55 MVAJ 56 MVAJ 57 MVAJ 58 MVAJ 59 Operated To reset Double stack Single stack Double stack 50 10 50 – 50 – 50 – (See Note 2 below) 150 10 150 – 150 – 150 – 150 12.5 150 – 150 – 150 – 10 – 25 – 50 – 50 12.5 50 – 50 – 50 – 150 15 150 – 150 – 150 – 150 12.5 150 – 150 – 150 – – – 15 15 – – 25 25 – – 50 50 – – – – – – 50 50 – – 50 50 10 25 25 – – 45 45 – – 70 70 – – 70 70 Minimum operating current (mA) 25 25 25 25 25 100 100 100 100 100 100 100 100 25 25 25 25 25 25 25 100 100 100 100 100 100 100 100 Note 1: Minimum operating current for relays specified in ESI 48-4 Class EB1 is 25mA and in EB2 is 50mA for 110V dc rating Note 2: The burden of the relay before it economises is less than 25W, reducing to 2.1W after. The auxiliary, which is fed from a separate supply, remains at 3.85W. Note 3: The 3 sets of burdens quoted for MVAJ 34 apply to the 48/54, 110/125 and 220/250V versions respectively. 7 Operating time MVAJ 11–15 fitted with self reset reverse flags All other types 15ms Not greater than 10ms at rated voltage Operation indicator MVAJ 34 The operation indicator follows the relay operation. Contacts The number of contacts available is shown in Table 1. They may be any combination of make type and break type but with a maximum of 8 break. Contact ratings Make and carry for 3s ac 7500VA with maxima of 30A or 300V dc 7500W with maxima of 30A or 300V Make and carry continuously ac 1250VA with maxima of 5A or 300V dc 1250W with maxima of 5A or 300V Break ac 1250VA with maxima of 5A or 300V dc 100W resistive 50W inductive with maxima of 5A or 300V Withstand Ratings MVAJ 17 The relay shall not operate when a 1µf capacitor charged to 150V is discharged into its operate circuit. The relay is continously rated at 150V dc. MVAJ 34 Operation/resetting does not occur when 100V ac rms 50/60Hz is applied to the respective coil circuits. The relay (at 50V range or above) will operate with pilot wires having a resistance of 200Ω. MVAJ 21 – 29 & 51– 59 These relays will withstand without operating, the discharge into their operate circuits of a 10µF capacitor charged to a voltage equal to the highest in the operative range for the relay All relays are continously rated with the exceptions listed in Table 1. Specifications 8 MVAJ 17 NGC SPEC.NGTS 3.6.3:1992 MVAJ 34 NGC SPEC.NGTS 2.19:1996 All other relays IEC 255 High Voltage withstand Dielectric withstand IEC 255-5:1977 2kV rms for 1 minute between all terminals and case earth. 2kV rms for 1 minute between terminals of independent circuits including contact circuits,with terminals on each independent circuit connected together. 1kV rms for 1 minute across open contacts of output relays. High voltage impulse IEC 255-5:1977 Three positive and three negative impulses of 5kV peak, 1.2/50 µs, 0.5J between all terminals and all terminals and case earth. Electrical environment High frequency disturbance IEC 255-22-1:1988 Class III 2.5kV peak between independent circuits and case. 1.0kV peak across terminals of the same circuit. EMC compliance 89/336/EEC EN 50081-2:1994 EN 50082-2:1995 Product safety 72/23/EEC EN 61010-1:1993/A2:1995 EN 60950:1992/A3:1995 Compliance to the European Commission Directive on EMC is claimed via the Technical Construction File route. Generic Standards were used to establish conformity. Compliance with European Commission Low Voltage Directive Compliance is demonstrated by reference to generic safety standards. Atmospheric environment Temperature IEC 255-6:1988 IEC 68-2-1:1990 IEC 68-2-2:1974 Storage and transit -25°C to +70°C Operating -25°C to +55°C Cold Dry Heat Humidity IEC 68-2-3:1969 56 days at 93% RH and 40°C Enclosure protection IEC 529: 1989 IP50 (dust protected) Mechanical environment Vibration IEC 255-21-1:1988 0.5g between 10Hz and 150Hz Mechanical durability Loaded contact Unloaded contact 10,000 operations minimum 100,000 operations minimum 9 45 13 4 holes 4.4 24 168 159 Push button projection 10 max 48 Panel cut-out: Flush mounting fixing details 32 25 min. 212 177 157 max. Reset 51 Flush mounting All dimensions in mm Figure 6: Case outline size 2 4 holes 4.4 97 52 23.5 168 Push button projection 10 max 159 99 Panel cut-out: Flush mounting fixing details 32 212 177 25 min. 157 max. Reset 103 All dimensions in mm Figure 7: Case outline size 4 10 Flush mounting 11 4 holes 4.4 200 155.4 24 168 Push button projection 10 max 159 203 Panel cut-out: Flush mounting fixing details 32 212 177 25 min. 157 max. Reset 206 Flush mounting 11 All dimensions in mm Figure 8: Case outline size 8 Cases MVAJ relays are housed in size 2, 4 or 8 cases as indicated in Table 1. Dimensions for these cases are shown in Figures 6, 7 and 8 respectively. Information Required with Order Relay type Voltage rating Number and combination of contacts for tripping duties Hand reset operation indicator required Instantaneous or time delayed cut-off contact 11