Minivent Shower Fan Kits 248710 AND 248810 WITH TIMER Fitting and Wiring Instructions 230-240V/1/50Hz
Kit contents: Minivent shower fan Inlet grille and fixings Outlet grille and fixings 3m flexible ducting 4 nylon straps Fan mounting strap and base
FITTING INSTRUCTIONS FOR VENT-AXIA MINIVENT SHOWER FAN READ INSTRUCTIONS CAREFULLY BEFORE STARTING INSTALLATION. IMPORTANT 1. All electrical connections should be made by a properly qualified electrician. The fan must be sited and connected in accordance with current IEE regulations (BS7671) or the appropriate standards in your country. 2. This is intended to ventilate a shower area or cubicle, but the fan motor must be mounted outside the shower area or cubicle, and away from direct sources of water spray (see fig. 1.). The motor must be out of reach of a person using a fixed bath or shower. Site away from direct sources of heat in excess of 45 °C. Do not site in an area containing excessive levels of grease. 3. When the fan extracts from a room containing a fuel burning appliance, the installer must ensure that the air replacement is adequate for both the fan and the fuel burning appliance. 4. Wiring should be via a switched spur with a 3 amp fuse (UK). Double pole switch or plug and socket should be located outside the room containing a fixed bath or shower. 5. Ducted applications. In circumstances where an excessive amount of moisture is present in the air, then a condensation trap will need to be installed in the exhaust duct. Horizontal ducts should fall away from the fan unit. Ducts passing through an unheated roof void should be insulated together with the fan unit.
INSTALLATION See Fig. 1 1. Mark positions where the grilles are to be sited, having ensured that there is adequate clearance behind. 2. Cut a 115mm hole in the ceiling and screw the inlet grille in place. 3. Cut a 115mm hole for the outlet grille. 4. Position the fan at the highest point on the system with a slope downwards to both grilles. In this position fix the fan mounting strap base to a suitable support using a woodscrew or other suitable fixing.
With the fan positioned so that the cable is pointing downwards and the arrow is pointing towards the outlet grille, pass the fan mounting strap through the base slots and wrap around the centre of the fan and pull tight. 5. Stretch and cut the duct (see note) to fit between each grille and the centreline of the fan. Attach the outlet grille to the duct using a nylon strap, pass the duct through the outlet hole and secure the grille using the fixings provided. Slide the free end of the duct onto the outlet end of the fan and secure with a nylon strap. 6. Attach the inlet duct to the inlet grille using a nylon strap. Pierce a hole in the TOP of the duct approximately 40mm from the fan, pass the cable through and then slide the duct onto the fan. Secure the duct with a nylon strap. Seal wiring hole as necessary. NOTE: The duct should be stretched without any holes or splits and should not exceed 3 metres in order to obtain best performance.
WIRING See Figs 2, 3 , 4 & 5. 1. ENSURE THAT THE MAINS SUPPLY IS SWITCHED OFF BEFORE PROCEEDING WITH THE WIRING. This fan is only suitable for connection to a 230-240V 50Hz Supply and MUST be earthed. The fan is intended for connection to fixed wiring. 2. The installation must be provided with a double pole isolator switch having a contact separation of not less than 3mm. 3. Using a suitable 5 amp junction box and 3 core cable of 5 amp rating, connect the fan leads to the switched fuse outlet as shown in the wiring diagrams. Note that the leads are colour coded: brown - live (L), blue - neutral (N), black - switched live (Ls, timer model only), and green/yellow - earth (E/ ). 4. Switch on the mains supply and check the fan operation.
Fig. 1. ADDITIONAL WOOD BATTEN FAN CABLE MOUNTING STRAP BASE
INLET GRILLE
LOFT AND DUCT INSULATION OMITTED FOR CLARITY
FIXING SCREW
OUTLET GRILLE
FAN MOUNTING STRAP
Fig. 2. Fan and room lighting switched On/Off at same time. (248710. Minivent SK). 240V 50Hz
240V 50Hz
FAN LEAD CONNECTIONS
L
E/
N
E
L
N
FAN LEAD CONNECTIONS
L
E/
N
L
3 AMP
N
3 AMP
E
Fig. 3. Fan and room lighting switched On/Off separately. (248710. Minivent SK).
JUNCTION BOX
JUNCTION BOX
ROOM LIGHTING ROOM LIGHTING
FAN SWITCH
ON/OFF SWITCH
Fig. 4. Fan switched On/Off by Vent-Axia Humidiswitch. Room lighting by separate switch. (248710. Minivent SK). FAN LEAD CONNECTIONS
240V 50Hz
N
L
E/
N
L
3 AMP
E
LIGHT SWITCH
JUNCTION BOX 2 1 3
OPTIONAL HUMIDISWITCH VENT-AXIA STOCK REF. No. 563501
ROOM LIGHTING
ON/OFF SWITCH
Fig. 5. Fan runs on for 15 mins. after room lighting is switched off. (248810. Minivent SK with timer). 240V 50Hz
N
L
FAN LEAD CONNECTIONS 3 AMP
E
E/
Ls N L
NOTE: When power is first switched on to the unit, it will run for 15 mins. continuously. Following this initial period it will then only be triggered by the Ls (switched live) connection.
ROOM LIGHTING
PULLCORD SWITCH
VENT-AXIA SALES CENTRES SCOTLAND 12 Lambhill Quadrant, Scotland Street Trading Estate, Kinning Park, Glasgow G41 1SB Telephone: 0141 429 1166 Fax: 0141 429 6616. NORTH WEST Unit 2 Caledonia Way, Stretford Motorway Est. Barton Dock Road, Manchester M32 0ZH Telephone: 0161 865 8421 Fax: 0161 865 0098. NORTH EAST Telephone: 0113 245 2985 Fax: 0113 242 4430. MIDLANDS Telephone: 0121 783 8601 Fax: 0121 784 7506. SOUTH WEST 1340 Aztec West, Almondsbury, Bristol BS12 4RX Telephone: 01454 612000 Fax: 01454 612020. Internet site at: www.vent-axia.com
SOUTHEAST Newton Road, Crawley, West Sussex RH10 2JA Telephone: 01293 530202 Fax: 01293 565169. EASTERN Newton Road, Crawley, West Sussex RH10 2JA Telephone: 01293 530202 Fax: 01293 565169. LONDON Newton Road, Crawley, West Sussex RH10 2JA Telephone: 0181 549 2271 Fax: 01293 565169. NORTHERN IRELAND 11 Sydenham Road, Belfast BT3 9DH Telephone: 01232 455528 Fax: 01232 452529. REPUBLIC OF IRELAND Vent-Axia Ventilation Ltd. 921 Western Industrial Estate, Naas Road, Dublin 12 Telephone: 01 450 4133 Fax: 01 450 4570. email:
[email protected]
The Vent-Axia Guarantee Applicable only to products installed and used in the United Kingdom. For details of guarantee outside the United Kingdom contact your local supplier. Vent-Axia guarantees its products for two years from the date of purchase against faulty materials or workmanship. In the event of any part found to be defective, the product will be repaired, or at the Company's option replaced, without charge, provided that the product: 1) has been installed and used in accordance with the instructions given with each unit 2) has not been connected to an unsuitable electricity supply. (The corrrect electricity supply voltage is shown on the product rating label attached to the unit.) 3) has not been subject to misuse, neglect or damage. 4) has not been modified or repaired by any person not authorised by the company. IF CLAIMING UNDER TERMS OF GUARANTEE please return the complete product, carriage paid to your original supplier or nearest VentAxia Centre, by post or personal visit. Please ensure that it is adequately packed and accompanied by a letter clearly marked 'Guarantee Claim' stating the nature of the fault and providing evidence of date and source of purchase. This guarantee is offered to you as an extra benefit, and does not affect your legal rights.
As part of the policy of continuous product improvement Vent-Axia reserves the right to alter specifications without notice.
Head Office: Fleming Way, Crawley, West Sussex RH10 2NN Tel: 01293 526062 Fax: 01293 551188 468391 E
1099