Transcript
Models:
40/60KRC Diesel
Industrial Towable Generator Sets D
Kohler Co. provides one-source responsibility for the generating system and accessories. D Generator set features: d Durable, steel, sound-attenuated housing d Electrical power panel d Single-point lifting eye d Engine certified by the Environmental Protection Agency (EPA) to conform to Tier 2 nonroad emissions regulations d Decision-Makert 3+, 16-light controller with emergency stop switch and prime power switch d Fast-Responset II excitation system using a permanent magnet (PM)-excited alternator D Trailer features: d 2 5/16 in. ball hitch d Leveling jack, 3181 kg (7000 lb.) rated d Lockable housing doors d Running lights with 6-wire harness and connector d Electric brake system d 15 x 6 steel wheels and ST205/75R15 BC tires with 826 kg (1820 lb.) tire load rating d Internal polymer fuel tank with low fuel indicator, 757 L (200 gal.) d Environmental containment basin for fuel, oil, and antifreeze d Rear facing, enclosure mounted exterior DC lights (2) with 0--15 minute, no-lock-on timer d Installed mounting brackets for a customer-supplied load distribution hitch d Utility box integrated in the trailer D Engine features: d Battery, battery rack, and battery cables d Battery charger, 6 amp float/equalize d Closed crankcase ventilation system d Engine block heater, 120 volt d Exhaust silencer with flexible exhaust connector d Heavy-duty air cleaner with air restrictor indicator
Trailer-Mounted Generator Set Specifications Model 40 kW 60 kW
Trailer Length* mm (in.) 3779 (148.7) (148 7)
Trailer Width[ mm (in.)
Trailer Height mm (in.)
1877 (73.9) (73 9)
2530 (99.6) (99 6)
Gross Weight (no fuel)] kg (lb.) 2090 (4600) 2455 (5400)
Gross Weight (with fuel)] kg (lb.) 2526 (5568) 3135 (6912)
Fuel Tank L (gal.) 757 (200)
* Length includes trailer tongue. [ Width includes trailer fenders and spare tire. ] Gross weight includes trailer, generator set with engine fluids, sound housing, and fuel tank.
Electrical Power Panel Specifications Load Lug Circuit Breakers, Amp Load Lug Available SelecConnections 240 V 208 V 480 V tor Switch VoltQty., Min./Max. 1 Ph 3 Ph 3 Ph ages, 60 Hz Model 120/240 Volt, 40 kW 175 175 80 1 Phase 120/208 Volt, 1 cable/phase One 15 One, One 30 One, 3 Phase #6--350MCM 60 kW 250 250 100 277/480 Volt, 3 Phase w Reverse twistlock connection to utility for duplex receptacle power. 120 Volt GFCI Duplex Receptacles Qty., Amp
120 Volt Power Inlet Twistlockw Qty., Amp
G33-3 9/07e
Duplex Receptacle for Battery Charger and Block Heater
Remote Start Capability
Yes
Yes
KOHLER CO., Kohler, Wisconsin 53044 USA Phone 920-565-3381, Fax 920-459-1646 For the nearest sales and service outlet in the US and Canada, phone 1-800-544-2444 KohlerPower.com
Generator Set Specifications
Model 40 kW 60 kW
Generator Set Model 40REOZJB 60REOZJB
120/240 Volt, 1-Phase kW/ Amps kVA 154 37/37 225 54/54
Alternator Model 4P7 4P10
Engine John Deere 3029T John Deere 4045T
130_C Standby Rating 120/208 Volt, 277/480 Volt, 3-Phase 3-Phase kW/ kW/ Amps Amps kVA kVA 139 40/50 69 40/50 215 62/78 93 62/78
Fuel Consumption Lph (gph) at Standby Rating 25% 50% 75% 100% Load Load Load Load 4.6 (1.2) 7.4 (2.0) 10.1 (2.7) 13.0 (3.4) 6.7 (1.8) 10.2 (2.7) 14.0 (3.7) 18.1 (4.8)
120/240 Volt, 1-Phase kW/ Amps kVA 138 33/33 208 50/50
105_C Prime Rating 120/208 Volt, 277/480 Volt, 3-Phase 3-Phase kW/ kW/ Amps Amps kVA kVA 125 36/45 62 36/45 198 57/71 83 55/69
Fuel Consumption Lph (gph) at Prime Rating 25% 50% 75% 100% Load Load Load Load 4.3 (1.1) 6.8 (1.8) 9.3 (2.5) 11.6 (3.1) 5.9 (1.6) 9.8 (2.6) 13.5 (3.6) 17.2 (4.5)
Sound Level dBA with Full Load at 21 ft. (7 m) 65 65
Notes: See the respective generator set model’s specification sheet for specifications not shown. See the Additional Literature table for generator set and controller specification sheet part numbers.
Electrical Power Panel
Standard Equipment -
10
-
1
MAIN LINE BREAKER 120/240 VAC 1 120/208 VAC 3 ON
MAIN LINE BREAKER 277/480 VAC 3
120/240 VAC 1
-
2
-
Cable racks for customer-supplied cables Fuel/water separator Interior mounted DC lights (3) with a 0--15 minute, no-lock-on timer Isochronous electronic governor with ±0.25% steady state frequency regulation Rear leveling jacks Spare tire
20A 15A
ON
120/208 VAC 3 OFF
277/480 VAC 3
OFF
3
Voltage Selector Switch
120VAC 15A FROM UTILITY
9
GENERATOR OUTPUT L1
L2
L3
N
120/208V 277/480V 3 Phase 120/240V 3 Phase 1 Phase
GND
8
4 WARNING
7 6
120VAC 30A INPUT BLOCK HEATER & BATTERY CHARGER
WORK LIGHTS
5 REMOTE START
3-Position
Additional Literature Generator Set
GM39324-C
Model 40REOZJB 60REOZJB
1. 2. 3. 4. 5. 6. 7.
Circuit breaker 20 A, 1-pole for block heater and battery charger Circuit breaker 15 A, 1-pole for duplex receptacle GFCI duplex receptacle 120 V, 15 A Worklight timer switch for exterior DC lights Remote start connections Twistlock power inlet GFCI duplex receptacle 120 V, 20 A for block heater and battery charger (opposite side) 8. Load lug assembly 9. Circuit breakers (main disconnect) 10. Voltage indicator lamps
Spec Sheet G5-204 G5-206
Controller Type Decision Makert3+ Decision-Makert3+
DISTRIBUTED BY:
Availability is subject to change without notice. Kohler Co. reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. Contact your local Kohlerr generator set distributor for availability.
© 2004, 2005, 2007 by Kohler Co. All rights reserved.
G33-3 9/07e
Spec Sheet G6 30 G6-30