Transcript
NREL DAS Enclosure (battery box)
Combo GPS/Cell/WIFI Antenna IP 192.168.1.105 User: root Pass: pass
USB
#1MBCH8 M/M pins3,4,5,6
WAN
Relay 1 NC
Relay 1 OUT
Relay 2 NC
Relay 2 OUT
Router
Relay 3 NC
Relay 3 OUT
+12VDCIBR600E-VZ
AI 1 +
AI 2 +
Eth Hub 3-Port 10MB
Relay/Humidity X-300-I
Single Mode Fiber to Shore
fiber
Gigabit Eth
Moog TEL Series 201350 CAT5e
WAN IP 166.140.246.217 LAN IP 192.168.1.1 Router admin port 8443 (WAN) Password go4beer WiFi WETNZ no passoword
Humidity (WET-NZ dry box)
Relay 3 OUT
Relay 4 NC
Relay 4 OUT
Relay 5 NC
Relay 5 OUT
USB
USB
EtherTek RMS-100 Alarm 1 +
AI 3 +
Alarm 1 -
AI 3 -
Alarm 2 +
ETHERNET +12VDC IN
Alarm 2 -
coaxial
USB Memory
Default password 44124cf1 Ssl port 443
Eth Switch
Relay 2 OUT
Relay 3 NC
AI 1 -
LAN
AI 2 -
WET-NZ Drybox OR Hull
Relay 1 OUT
Relay 2 NC
EtherTek USB Relay
coaxial Cradlepoint
Relay 1 NC
10/100/1000MB
DC Supply
cRIO-9025/ cRIO-9118
9-35VDC
(not NREL supplied)
IP 192.168.1.106 User: Pass:
9-35VDC
NI GPS (timing) PSA-916 Altimeter TSS DMS05 MRU
#2 MBCH8 M/M #3 MBCH8 M/M #4 MBCH8 M/M
NI 9870 4-Port,RS232 Serial 8-28VDC
GPS A 9600 Position GPS B 19200 Heading
Voltage Input 10-36VDC
V101 GPS Compass UPS DC Supply
NI 9237 4-Channel, ±25 mV/V, 24-Bit Simultaneous Bridge Module
#1MBCH8 M/M pins +(1,2) -(7,8)
+ 10VDC excitation
24VDC to NREL DAS
NI 9219 4-Channel, ±25 mV/V, 24-Bit Universal AI
WET-NZ (various locations) Load Cell #1 LCM Systems
#5 MBCHRA8 M/M
0-55,000 Lbf
Load Cell #2 LCM Systems
Subsea Frame & Junction Box #6 MBCHRA8 M/M
0-55,000 Lbf Single Mode Fiber to Shore
Load Cell #3 LCM Systems
Prizm Micromux
RS-422
Nortek 600kHz AWAC
#7 MBCHRA8 M/M
0-55,000 Lbf
Load Cell #4 LCM Systems
#8 MBCHRA8 M/M
0-55,000 Lbf
AZURA @ Kaneohe Bay, NREL MOIS System
Ethernet Float Angle 4-20mA
#9 MBCHRA8 M/M pins 1,2
Water Depth 4-20mA
#9 MBCHRA8 M/M pins 3,4
RS232 Serial Analog
Instruments and Mounting Locations SIZE
NREL
SCALE
FSCM NO
N/A
DWG NO
11/18/2013
SHEET
REV
1 OF 7
PIN #1
Twisted pair
PIN #2
MCIL8M
Twisted pair
20AWG
PIN #1
20AWG
PIN #2
IL4F
PIN #3
20AWG
PIN #3
PIN #4
20AWG
PIN #4
PINS #5-#8 not connected 2 cables at 70' 2 cables at 85' Polyurethane outer jacket, PVC or Teflon wire insolation
MOIS @ Kaneohe Bay, NREL System
Ethernet RS232 Serial
Load cell cable
Analog SIZE
National Renewable Energy Laboratory
SCALE
FSCM NO
N/A
DWG NO
11/18/2013
SHEET
REV
2 OF 7
PIN #1
Twisted pair
PIN #2 PIN #3
MCIL8M
Twisted pair
PIN #4 PIN #5
Twisted pair
PIN #6 PIN #7 PIN #8
Twisted pair
White
PIN #1
Black
PIN #2
Red
PIN #3
Green
PIN #4
Orange
PIN #5
Blue
PIN #6
Red/Black
PIN #7
White/Black
PIN #8
IL8M
Mates to BH8MSS
Cable Type P4TSP20# Cable length 10(ft)
MOIS @ Kaneohe Bay, NREL System
Ethernet RS232 Serial
Ethernet and Power Cable
Analog SIZE
National Renewable Energy Laboratory
SCALE
FSCM NO
N/A
DWG NO
11/18/2013
SHEET
REV
3 OF 7
Twisted pair
PIN #1
24AWG
PIN #1
24AWG
PIN #2
24AWG
PIN #3
24AWG
PIN #4
24AWG
PIN #5
24AWG
PIN #6
24AWG
PIN #7
24AWG
PIN #8
White/Blue + Blue PIN #2
Twisted pair
PIN #3 White/Orange + Orange
MCIL8M
PIN #4
Twisted pair
PIN #5
IL8M
Mates to BH8MSS
White/Green + Green PIN #6
Twisted pair
PIN #7 White/Brown + Brown PIN #8
Subconn Power / Ethernet Cable, Type D/P-P4TP24#/4C18# OR equivalent without the power conductors Cable length 9(ft)
MOIS @ Kaneohe Bay, NREL System
Ethernet RS232 Serial
WetNzAnalog Signals Cable
Analog SIZE
National Renewable Energy Laboratory
SCALE
FSCM NO
N/A
DWG NO
11/18/2013
SHEET
REV
4 OF 7
Both sides mate to MCHBRAF
Twisted pair
PIN #1
24AWG
PIN #1
24AWG
PIN #2
24AWG
PIN #3
24AWG
PIN #4
24AWG
PIN #5
24AWG
PIN #6
24AWG
PIN #7
24AWG
PIN #8
White/Blue + Blue PIN #2
Twisted pair
PIN #3 White/Orange + Orange
MCIL8M
PIN #4
Twisted pair
PIN #5
MCIL8M
White/Green + Green PIN #6
Twisted pair
PIN #7 White/Brown + Brown PIN #8
Subconn Power / Ethernet Cable, Type D/P-P4TP24#/4C18# OR equivalent without the power conductors Cable length 13(ft)
MOIS @ Kaneohe Bay, NREL System
Ethernet RS232 Serial
GPS Compass Cable
Analog SIZE
National Renewable Energy Laboratory
SCALE
FSCM NO
N/A
DWG NO
11/18/2013
SHEET
REV
5 OF 7
MCIL8M
PIN #1
+24VDC
PIN #1
PIN #2
DC RTN
PIN #2
PIN #3
TX Data
PIN #3
PIN #4
GPS RX
PIN #13
PIN #5
GPS Comm
PIN #14
PIN #6
Data Comm
PIN #6
PIN #7
RX Gyro
PIN #11
PIN #8
Gyro Comm
MHDG-16-CCP-UT
PIN #12
Supplied Teledyne TSS DMS-05 cable. Jacket is polyurethane /w a cable diameter of 0.5". Cable will be sent cut at 20ft in length and already has the MHDG-16-CCP-UT installed on one end.
All unassigned pins not connected
Cable length 16(ft)
MOIS @ Kaneohe Bay, NREL System
Ethernet RS232 Serial
TSS-DMS05 (MRU) Cable
Analog SIZE
National Renewable Energy Laboratory
SCALE
FSCM NO
N/A
DWG NO
11/18/2013
SHEET
REV
6 OF 7
MCIL8M
PIN #1
20AWG
PIN #1
PIN #2
20AWG
PIN #2
PIN #3
20AWG
PIN #3
PIN #4
20AWG
PIN #4
PIN #5
20AWG
PIN #5
PIN #6
20AWG
PIN #6
Impulse RMG-6-FS
PIN #7 PIN #8
All unassigned pins not connected
Polyurethane jacket. Cable length 80(ft)
MOIS @ Kaneohe Bay, NREL System
Ethernet RS232 Serial
PSA 916 (Depth) Cable
Analog SIZE
National Renewable Energy Laboratory
SCALE
FSCM NO
N/A
DWG NO
11/18/2013
SHEET
REV
7 OF 7