Transcript
NEW Lo-Carbon Kitchen Box Fan (EKF) Features and Benefits • Energy efficient EC motor • 120°C airstream rated • Sealed for life motor • Flexible installation, straight through or turn through 90° as standard • Internal or external mounting as standard • 25mm Double skin casing • Integral IP65 Isolator • Simple potentiometer control • ERP 2015 compliant • Compliant part L 2013 SFP for requirements for kitchen ventilation systems Vent-Axia’s latest product offering in the Non Residential sector is a centrifugal box fan specifically designed for kitchen operation at elevated duct temperatures of up to 120°C. Working closely with our Engineering partner, the motor impeller arrangement has been specifically engineered to benefit from the efficiencies of an EC external rotor motor mounted out of the airstream to allow for operation at 120°C in duct temperatures.
Construction
90° and with the motor shaft either horizontal or vertical this enables the fan to be mounted in any orientation.
Motor The Kitchen Box Fan range is powered by highly efficient, electronically commutated (EC) motors with permanent magnets, exceeding the minimum efficiency requirements for IE3 motors. All units are fully speed controllable via the onboard electronics utilising a 0-10V input signal. Motors and the onboard electronics are protected to IP54 as standard mounted and are out of the airstream. The combination of an EC high efficiency motor and a high efficiency backward curved impeller ensures ERP 2015 compliance.
Impeller A backward curved welded Aluminium impeller is mounted on an extended shaft from the EC external motor. Motor and impeller is balanced as a finished assembly to G2.5 to ensure vibration free operation. Impeller matched to inlet cone for optimum performance.
Speed Control
10-12 Watts.
Electrical Depending on unit size the EKF range is suitable for either single phase 220-240V 50Hz or three phase 380-414V 50Hz. All mains wiring is direct to the built in IP65 isolator mounted on the motor support plate providing simple and safe connection and operation.
Accessories A full range of accessories are available for the EKF range including: •
Potentiometer speed controller (included as standard)
•
Square to round duct connectors
•
Flexible connectors
•
Mounting support and A/V mount set
•
Weather cowl
•
Discharge louvre
Online Documentation For digital catalogue information, fitting & wiring instructions and online fan selection programme visit www.vent-axia.com/ekf
By utilising EC motors the EKF range has been designed for simple Demand Ventilation control facilitated by use of a 0-10V potentiometer. This low voltage controller can then be mounted within the kitchen area thereby removing the risk of overheating or damaging the control cicuits.
Performance The fan performance has been tested in accordance with ISO 5801 DIN 24163. The casing is constructed from a framed 25mm double skin with acoustic insulation to minimise unit noise. With carefull thought to maximising the installation possibilities from one unit VentAxia have managed to create a single unit that is suitable for both internal and external mounting as standard. In addition to this the duct configuration can be either straight blow through or turn through
266
Sound Levels Fan sound levels were measured in a reverberant chamber in accordance with EN ISO 3745. Published dB(A) figures are free field at a distance of 3m with hemispherical propogation at a reference level of 2x10-5. The sound power level spectra figures are dB with a reference level of
T: 0844 856 0590
In-Line Fans
Fan Dimensions (mm) FRONT
TOP
BACK
C
A
B
B
B
A SIDE
B
Unit can be mounted either motor shaft vertical or horizontal D
A
Access doors and discharge panel are interchangeable
Model
A
B
C
D
Weight (kg)
EKF355E1
600
400
684
708
63
EKF400E1
700
500
784
826
81
EKF450E1
700
500
784
826
83.5
EKF450E3
700
500
784
826
83.5
EKF500E3
850
650
929
1017
130
EKF560E3
850
650
929
1017
132
W: www.vent-axia.com/industrial
267
Lo-Carbon Kitchen Box Fan (EKF) Performance Curve EKF355E1 500
0.50
400
0.40
0.30
300 Pressure Pa
Absorbed Power kW
100%
200
0.20
80%
100
0.10
60%
0
0.00 0.000
0.200
0.400
0.600
0.800
1.000
Air Volume m3/s
Performance Guide Speed 100%
80%
60%
40%
m3/s kW SFP m3/s kW SFP m3/s kW SFP m3/s kW SFP
0
50
100
150
0.920 0.29 0.32 0.737 0.16 0.22 0.554 0.08 0.14 0.368 0.04 0.095
0.866 0.31 0.35 0.665 0.17 0.26 0.475 0.09 0.18 0.230 0.04 0.172
0.815 0.32 0.39 0.605 0.18 0.30 0.375 0.09 0.24
0.767 0.32 0.42 0.538 0.19 0.35 0.230 0.08 0.36
Airflow, m3/s @ Pa 200 250 0.700 0.33 0.48 0.455 0.18 0.41
0.630 0.34 0.54 0.360 0.18 0.50
300
350
400
450
0.600 0.34 0.60 0.140 0.13 0.90
0.510 0.34 0.66
0.435 0.33 0.76
0.275 0.27 0.97
Fans F.L.C.
Supply Voltage
1.7
1.0 220V/ 1/ 50Hz 0.7
0.5
Sound Data Speed 100%
90%
80%
60%
Test Mode
63
125
250
Intake Discharge Breakout Intake Discharge Breakout Intake Discharge Breakout Intake Discharge Breakout
50 48 62 46 42 61 43 36 58 40 34 57
66 66 71 62 61 77 51 39 70 46 36 59
66 67 72 58 59 72 50 48 62 45 44 51
Octave Band Frequency SWL 500 1K 63 67 64 57 61 61 51 52 54 45 43 46
60 69 66 55 63 59 48 56 48 40 40 39
2K
4K
8K
61 66 58 55 60 53 48 55 44 39 39 33
58 62 53 51 55 47 43 52 37 33 35 27
52 55 47 46 48 41 37 46 32 30 30 31
SPL dB(A) @ 3m 49
47
38
29
ErP conform 2015, N=79.6, statA=69. 9%, VSD integrated, Integrated controller.
268
T: 0844 856 0590
In-Line Fans
Performance Curve EKF400E1
700
0.70
600
0.60
0.50
100%
0.40
400
80%
300
0.30
Absorbed Power kW
Pressure Pa
500
0.20
200 60%
0.10
100 40%
0.00
0 0.000
0.250
0.500
0.750
1.000
1.250
Air Volume m3/s
Performance Guide Speed 100%
80%
60%
40%
50
100
150
200
m3/s
1.206
1.160
1.115
1.065
1.020
0.965
kW
0.53
0.55
0.56
0.58
0.59
0.60
SFP m3/s kW SFP m3/s kW SFP m3/s kW SFP
0.44 0.961 0.28 0.29 0.721 0.13 0.18 0.480 0.06 0.11
0.47 0.907 0.30 0.33 0.640 0.14 0.22 0.351 0.05 0.16
0.50 0.845 0.31 0.36 0.552 0.15 0.27 0.012 0.03 2.50
0.55 0.780 0.32 0.40 0.438 0.14 0.33
0.58 0.705 0.32 0.45 0.235 0.12 0.51
0.62 0.622 0.32 0.51
100%
80%
60%
40%
Fans F.L.C.
350
400
450
500
600
0.907
0.845
0.765
0.685
0.586
0.175
0.61
0.61
0.60
0.59
0.56
0.33
0.67 0.520 0.31 0.59
0.72 0.350 0.26 0.75
0.79
0.86
0.96
1.90
Supply Voltage
3.0
2.2 220V/ 1/ 50Hz 1.6
0.8
Sound Data Speed
Airflow, m3/s @ Pa 250 300
0
Test Mode
63
125
250
Intake Discharge Breakout Intake Discharge Breakout Intake Discharge Breakout Intake Discharge Breakout
61 58 69 54 50 65 49 45 62 44 40 60
70 70 90 61 61 81 52 52 75 47 46 62
69 73 94 60 65 73 52 57 64 47 47 54
Octave Band Frequency SWL 500 1K 66 72 70 59 66 65 51 59 57 44 45 49
65 73 67 59 67 61 51 59 52 44 45 44
2K
4K
8K
64 69 63 58 63 56 50 54 46 43 43 35
60 64 57 54 58 50 45 49 40 40 42 28
54 57 53 47 51 44 38 45 34 33 35 31
SPL dB(A) @ 3m 56
49
42
32
ErP conform 2015, N=79.6, statA=69. 9%, VSD integrated, Integrated controller.
W: www.vent-axia.com/industrial
269
Lo-Carbon Kitchen Box Fan (EKF) Performance Curve EKF450E1/EKF450E3 800
1.60
700
1.40
600
1.20 100%
1.00 0.80
400
300
0.60
80%
0.40
200 60%
100
0.20
40%
0 0.000
0.00
0.500
1.000 Air Volume m3/s
1.500
2.000
Performance Guide Speed 100%
80%
60%
40%
Absorbed Power kW
Pressure Pa
500
m3/s kW SFP m3/s kW SFP m3/s kW SFP m3/s kW SFP
0 1.602 0.99 0.62 1.285 0.51 0.40 0.962 0.23 0.24 0.640 0.08 0.13
50 1.555 1.01 0.65 1.228 0.53 0.43 0.881 0.24 0.27 0.511 0.09 0.17
E1 Model
100 1.505 1.03 0.68 1.166 0.54 0.46 0.786 0.25 0.31 0.290 0.08 0.26
150 1.458 1.04 0.71 1.095 0.55 0.50 0.685 0.24 0.35
200 1.408 1.05 0.75 1.015 0.55 0.55 0.556 0.24 0.43
250 1.356 1.07 0.79 0.938 0.55 0.59 0.350 0.20 0.58
Airflow, m3/s @ Pa 300 350 400 1.290 1.220 1.160 1.07 1.07 1.06 0.83 0.87 0.92 0.855 0.762 0..582 0.55 0.54 0.49 0.64 0..71 0.84
450 1.092 1.06 0.97
500 1.012 1.05 1.04
550 0.925 1.03 1.12
600 0.840 1.00 1.19
700 0.462 0.76 1.64
Fans F.L.C.
Supply Voltage
5.2
E3 Model Fans F.L.C.
Supply Voltage
1.8
3.8
1.0 220V/ 1/ 50Hz
400V/ 3/ 50Hz
2.7
0.8
1.9
0.5
Sound Data Speed 100%
80%
60%
40%
Test Mode
63
125
250
Intake Discharge Breakout Intake Discharge Breakout Intake Discharge Breakout Intake Discharge Breakout
55 54 70 51 46 71 50 36 66 45 31 65
70 70 81 70 48 84 57 45 78 50 42 66
67 77 86 59 68 76 53 56 66 46 48 55
Octave Band Frequency SWL 500 1K 68 77 74 63 69 69 55 62 62 48 53 52
70 78 68 65 72 63 58 64 54 51 55 46
2K
4K
8K
70 75 63 64 72 57 55 65 49 50 56 37
66 70 57 60 69 50 50 60 40 43 52 29
60 63 52 54 64 44 44 54 40 37 38 32
SPL dB(A) @ 3m 59
52
45
34
Three phase unit ErP conform 2015, N=79.6, statA=69. 9%, VSD integrated, Integrated controller Single phase unit ErP conform 2015, N=76.1, statA=66.6%, VSD integrated, Integrated controller
270
T: 0844 856 0590
In-Line Fans
Performance Curve EKF500E3 1200
3.00
1000
2.50
2.00
100%
1.50
600
80%
400
1.00
0.50
60%
200
Absorbed Power kW
Pressure Pa
800
40% 0
0 0.500
0.000
1.500
1.000
2.500
2.000
3.000
Air Volume m3/s
Performance Guide Speed 100%
80%
60%
40%
m3/s kW SFP m3/s kW SFP m3/s kW SFP m3/s kW SFP
0
100
200
300
400
2.543 1.71 0.67 2.002 0.88 0.44 1.499 0.40 0.26 0.966 0.18 0.19
2.450 1.76 0.72 1.900 1.01 0.53 1.330 0.47 0.35 0.665 0.22 0.33
2.320 1.82 0.78 1.765 1.04 0.59 1.129 0.49 0.43
2.190 1.89 0.86 1.570 1.05 0.67 0.850 0.46 0.54
2.075 1.96 0.95 1.372 1.04 0.76
100%
80%
60%
40%
1.935 2.03 1.05 1.178 1.02 0.87
1.835 2.07 1.13 0.754 0.87 1.16
700
800
900
1000
1.700 2.10 1.23
1.458 2.00 1.37
1.250 1.85 1.53
0.539 1.25 2.29
Fans F.L.C.
Supply Voltage
5.5
3.9 400V/ 3/ 50Hz 2.8
1.3
Sound Data Speed
Airflow, m3/s @ Pa 500 600
Test Mode
63
125
250
Intake Discharge Breakout Intake Discharge Breakout Intake Discharge Breakout Intake Discharge Breakout
62 60 75 60 56 70 51 50 66 46 43 63
73 76 82 66 67 81 61 62 74 56 55 62
70 82 88 62 72 77 56 65 70 51 56 58
Octave Band Frequency SWL 500 1K 71 80 73 66 74 69 58 66 61 53 57 52
77 83 69 67 75 64 61 68 57 50 59 48
2K
4K
8K
73 81 68 67 71 62 60 64 53 55 55 41
74 79 65 61 66 59 55 60 49 50 51 34
69 75 59 56 60 51 50 55 43 43 48 31
SPL dB(A) @ 3m 60
52
45
35
ErP conform 2015, N=73.4, statA=66.9%, VSD integrated, Integrated controller.
W: www.vent-axia.com/industrial
271
Lo-Carbon Kitchen Box Fan (EKF) Performance Curve EKF560E3 1300
4.00
1200
3.50
3.00
100%
800
2.50
600
2.00
80%
400
Absorbed Power kW
Pressure Pa
1000
1.50
1.00
200
60% 40% 0
0 0.000
1.000
2.000 Air Volume m3/s
3.000
4.000
Performance Guide Speed 100%
80%
60%
40%
m3/s kW SFP m3/s kW SFP m3/s kW SFP m3/s kW SFP
0
100
200
300
400
3.693 2.58 0.70 2.926 1.33 0.45 2.192 0.59 0.27 1.481 0.27 0.18
3.570 2.75 0.77 2.780 1.45 0.52 1.987 0.65 0.33 1.081 0.32 0.30
3.440 2.92 0.85 2.585 1.56 0.60 1.672 0.69 0.42 0.019 0.11 5.74
3.310 3.00 0.91 2.405 1.61 0.67 1.293 0.69 0.53
3.135 3.10 0.99 2.155 1.62 0.75 0.600 0.49 0.81
Airflow, m3/s @ Pa 500 600 2.940 3.14 1.07 1.860 1.60 0.86
2.725 3.17 1.16 1.500 1.51 1.01
700
800
900
1000
1100
2.507 3.20 1.27 0.900 1.20 1.33
2.278 3.15 1.38
2.004 3.08 1.54
1.650 2.83 1.72
0.930 2.16 2.32
Fans F.L.C.
Supply Voltage
3.6
2.6 400V/ 3/ 50Hz 1.8
1.0
Sound Data Speed 100%
80%
60%
40%
Test Mode
63
125
250
Intake Discharge Breakout Intake Discharge Breakout Intake Discharge Breakout Intake Discharge Breakout
64 62 82 65 63 77 60 56 73 53 48 68
78 76 87 78 77 85 67 65 78 60 55 67
81 83 87 75 79 80 63 67 72 56 57 64
Octave Band Frequency SWL 500 1K 74 83 81 72 81 76 60 70 68 53 60 60
77 83 73 75 81 68 64 70 62 57 60 55
2K
4K
8K
76 81 70 74 79 65 60 66 58 53 56 47
72 76 67 70 74 61 56 60 52 49 51 38
67 70 62 64 67 56 50 54 50 43 46 41
SPL dB(A) @ 3m 65
60
52
44
ErP conform 2015, N=72.4, statA=67.8%, VSD integrated, Integrated controller.
272
T: 0844 856 0590
In-Line Fans
Accessories
Unit Size
Mounting Bracket
Flexible
Square to Circular Duct
& A/V Mount Set
Connector
Transformation Section
Discharge Cowl
Weather Roof
EKF355
EKFMF355
EKFFC355
EKFTP35-35
EKFDC355
EKFWR355
EKF400
EKFMF400
EKFFC400
EKFTP40-40
EKFDC400
EKFWR400
EKF450
EKFMF400
EKFFC400
EKFTP40-45
EKFDC400
EKFWR400
EKF500
EKFMF500
EKFFC500
EKFTP50-50
EKFDC500
EKFWR500
EKF560
EKFMF500
EKFFC500
EKFTP50-56
EKFDC500
EKFWR500
Accessories Dimensions G
Mounting Bracket & A/V Mount Set Stock Ref
A
B
C
DØ
E
F
G
HØ
I
J
K
EKFMF355
600
100
400
13
25
700
750
9
30
100
35
EKFMF400
700
100
500
13
25
800
850
9
30
100
35
EKFMF400
700
100
500
13
25
800
850
9
30
100
35
EKFMF500
850
100
650
13
25
950
1000
9
30
100
35
EKFMF500
850
100
650
13
25
950
1000
9
30
100
35
E B
A
B
C
DØ
E
F
G
H
EKFTP35-35
600
100
400
348
50
400
540
570
EKFTP40-40
700
100
500
398
50
400
640
670
EKFTP40-45
700
100
500
448
50
400
640
670
EKFTP50-50
850
100
650
498
50
400
790
820
EKFTP50-56
850
100
650
558
50
400
790
820
Flexible Connector Stock Ref
A
C
D
EØ
F
K
B
E
C
G H A
EKFFC355
600
100
400
34
8
570
150
700
100
500
34
8
670
150
EKFFC500
850
100
650
34
8
820
150
W: www.vent-axia.com/industrial
F
DØ
A F C
G
G
EKFFC400
Note: weather roof and cowl dimensions on application
I J
B B
HØ
DØ
Square to Circular Duct Transformation Section Stock Ref
F A C
D
E
273