Transcript
NOTIFIER
®
12 Clintonville Road Northford, CT 06472-1610 203-484-7161 FAX: 203-484-7118
A Pittway Company
Software Release Summary for the Notifier AFP1010 Fire / Security Control Panel with the DIA-1010 Display Interface Assembly
A1ROM6.6N & AROM6.6N This document covers AFP1010 Release 6.6 Software as it affects the following ROMs: AROM6.6N-AMG A1ROM6.6N-CPU AROM6.6N-AMGX4 AROM6.6N-AMGZCF
A1ROM6.6N-DIA AROM6.6N-LIB AROM6.6N-AMGZC AROM6.6N-XPSC
AROM6.6N-SIB AROM6.6N-XPP AROM6.6N-LIB-B
CAUTION - System Reacceptance Test after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFPA 72-1993 Chapter 7 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
Document 50360 02/6/97 Revision P/N 50360:B
www.PDF-Zoo.com
B
ECN 97-018
Inventory List The following replacement ROMs must be ordered individually according to your system requirements. AROM6.6Ns and A1ROM6.6Ns cannot be used in conjunction with earlier ROMs. All system ROMs must be upgraded at the same time (see Compatibility Warning).
AROM6.6N-AMG (standard AMG operation at Annunciator address 29, 30, 31, or 32) Includes: EPROM for AMG-1/AMG-E Document # 15744 "Field Change Procedure for the AM2020 and AFP1010" Document # 15889 "Voice Alarm Multiplex-2020"
AROM6.6N-AMGX4 (for use with 5th through 8th AMG in one system at Annunciator address 25, 26, 27, or 28) Includes: EPROM forAMG-1/AMG-E Document # 15744 "Field Change Procedure for the AM2020 and AFP1010" Document # 15889 "Voice Alarm Multiplex-2020"
AROM6.6N-AMGZC (for zone coded AMG operation occupying addresses 2, 3, 4, and 5)
EPROM
Part #
AROM6.6N-AMG --------AROM6.6N-AMGX4 ----AROM6.6N-AMGZC ----AROM6.6N-AMGZCF --A1ROM6.6N-CPU -------A1ROM6.6N-DIA --------AROM6.6N-LIB ----------AROM6.6N-LIB-B -------AROM6.6N-SIB ----------AROM6.6N-XPP ---------AROM6.6N-XPSC --------
73284 73295 73529 73534 73759 73895 73760 73761 73790 73736 73737
Includes: EPROM for AMG-1/AMG-E Document # 15744 "Field Change Procedure for the AM2020 and AFP1010" Document # 15889 "Voice Alarm Multiplex-2020"
AROM6.6N-AMGZCF (for zone coded AMG operation occupying addresses 2, 3, 4, and 5) Includes: EPROM for AMG-1/AMG-E Document # 15744 "Field Change Procedure for the AM2020 and AFP1010" Document # 15889 "Voice Alarm Multiplex-2020"
A1ROM6.6N-CPU Includes: EPROM for CPU-2 Document # 15744 "Field Change Procedure for the AM2020 and AFP1010" Document # 15337 "The AM2020/AFP1010 Fire Alarm Control Panel Operator's Instructions"
DIA-1010 EPROM PROG. P/N 73895
DIA-1010 Label Provides a quick reference to the ROM software level currently installed in the AFP1010 DIA-1010 Assembly. Place this label on the inside of the DIA-1010 door during installation of the A1ROM6.6N-DIA.
A1ROM6.6N-DIA Includes: EPROM for DIA-1010 DIA-1010 Label Document # 15744 "Field Change Procedure for the AM2020 and AFP1010" Document # 15987 "LED Instruction Sheet" Document # 15088 "The AM2020/AFP1010 Manual" Document # 15088SUP Supplement to Document 15088
AC POWER FIRE ALARM TROUBLE/ SECURITY ALARM DISPLAY TROUBLE
AROM6.6N-LIB/AROM6.6N-LIB-B Includes: EPROM for LIB-200 Document # 15744 "Field Change Procedure for the AM2020 and AFP1010"
SIGNAL SILENCE
AROM6.6N-SIB
15454 Mylar Security LED Overlay
Includes: EPROM for SIB-2048 Document # 15744 "Field Change Procedure for the AM2020 and AFP1010"
When software is upgraded to this level, the label shown above must be placed over the existing DIA-1010 LED legend (if the existing legend differs from the above).
AROM6.6N-XPP Includes: EPROM for XPP-1 Document # 15744 "Field Change Procedure for the AM2020 and AFP1010" Document # 15888 "The XP Series Transponder System"
AROM6.6N-XPSC
(For use in Canada when the second stage evacuation signal must be activated steadily, not at 120 PPM.)
Includes: EPROM for XPP-1 Document # 15744 "Field Change Procedure for the AM2020 and AFP1010" Document # 15888 "The XP Series Transponder System" Document # 50190 "Addendum to the XP Series Transponder System"
2
50360-B
02/6/97
www.PDF-Zoo.com
AROM6.6N and A1ROM6.6N Special Features / Notes Printer Trouble Inhibit The AM2020/AFP1010 monitors the primary printer's RX line for error conditions. This option inhibits the generation of a trouble message for Paper Out or Printer Off-Line. Enable for VGAS/UNINET applications only (refer to Document 50251).
Universal Digital Alarm Communicator Transmitter This feature allows the AM2020/AFP1010 to connect to and utilize the full functionality of the UDACT module (refer to Document 50050). The UDACT is not suitable for use when security features are employed in the AM2020/AFP1010.
www.PDF-Zoo.com
50360-B
02/6097
3
Previous AFP1010 Software Releases (The following features are included in the current software release) A1ROM5 (Rev A)
A1ROM6N (Rev A)
• Battery Charger Control
• Selectable Drift Compensation
• Block Acknowledge
• UL1076 / UL1610 Security
• Control-By-Time • Control Module Reporting • Day / Night Sensitivity
A1ROM6N (Rev B - E) • Revised Standard for DACT Operation
• Device Blink • Disabled Zones • Event Reminder • Expanded Read Status Functions
A1ROM6N (Rev F & G) • Zone Coded Voice (Female) A1ROM6.5N (Rev A & B)
• Expanded AMG Addressing
• Rapid XP Transponder All Call
• Expanded Status Line
• Rapid Polling Algorithm
• Expanded User Reports
• Pre-Alarm Option
• LED Latching
• Remote Terminal Mode
• Local Printer
• Supervisory Type ID
• New Type IDs • NIB-96 Trouble Reporting
• Piezo Disabled During Alter Status Programming
• Non-Alarm Module Reporting
• Pager Mode
• Periodic Detector Test • Prior / Next / Autostep Keys • Remote Page • Verification Counter Reset • Walk Test • Zone Coded Synthesized Chime • Zone Coded Voice (Male) A1ROM5 (Rev B) • New AMG Boards
A1ROM6.5N (Rev B - D) • Canadian Upgrade Kit AROM6.5N-XPSC Provides Steady Second Stage Evacuation Signal A1ROM6.6N (Rev B) • Printer Trouble Inhibit • Universal Digital Alarm Communicator Transmitter
A1ROM5 (Rev C - E) • NFPA 72-1993 Chapter 6 Sensitivity Calibrated Test • Drift Compensation • Manual Reset of Automatically Activated Control Modules.
Compatibility Warning Software Combinations: All software part numbers are not compatible with each other. Improper mixing of software part numbers may compromise LifeSafety functions. If in doubt about the compatibility of a particular software combination, consult the factory. CGAS, AMNET, AUTOPLEXOR, and VGAS/UNINET This software is not compatible with earlier versions of CGAS, AMNET, AUTOPLEXOR, and VGAS/UNINET systems. Software in these items must be upgraded for compatibility.
4
50360-B
02/6/97
www.PDF-Zoo.com