Preview only show first 10 pages with watermark. For full document please download

Nz 100 - Fire Alarm Engineers

   EMBED


Share

Transcript

NZ 100 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL Document No ........................................................................G0097WO1 Issue No..................................................................................................1 Serial No ................................................................................................... Issue Date .............................................................19th December 1996 Software Version ................................................................................1.0 AMPAC TECHNOLOGIES LTD PTY UNIT D, 33 PORANA ROAD GLENFIELD AUCKLAND NEW ZEALAND PH : 64-9-443 8072 FAX : 64-9-443 8073 NOTE: INFORMATION CONTAINED IN THIS DOCUMENT IS SUBJECT TO CHANGE WITHOUT NOTICE. UNCONTROLLED DOCUMENT AMPAC INDUSTRIES LTD NZ 100 OPERATORS MANUAL CONTENTS 1.0 INTRODUCTION .................................................................................................................................3 1.1 1.2 2.0 INSTALLING THE NZ3200............................................................................................................11 INITIAL OPERATION ....................................................................................................................11 SYSTEM OPERATION ......................................................................................................................12 7.1 7.2 7.3 8.0 SMOKE ONLY ...............................................................................................................................10 GATING .........................................................................................................................................10 INSTALLATION AND INITIAL OPERATION ....................................................................................11 6.1 6.2 7.0 DETECTORS...................................................................................................................................9 DETECTOR LIMITATIONS .............................................................................................................9 BELLS AND SOUNDERS................................................................................................................9 SETTINGS .........................................................................................................................................10 5.1 5.2 6.0 GENERAL DESCRIPTION ..............................................................................................................5 FRONT PANEL LAYOUT ................................................................................................................5 INTERNAL LAYOUT........................................................................................................................6 DETECTOR CIRCUITS ...................................................................................................................6 BELL CIRCUITS ..............................................................................................................................6 DOOR HOLDER OUTPUT ..............................................................................................................7 WALK TEST ....................................................................................................................................7 BUZZER...........................................................................................................................................7 BUZZER MUTE ...............................................................................................................................7 DEFECT INDICATORS...............................................................................................................7 POWER SUPPLY........................................................................................................................7 MAINS ON INDICATOR..............................................................................................................8 FUSING .......................................................................................................................................8 BATTERIES.................................................................................................................................8 CONNECTING DEVICES ....................................................................................................................9 4.1 4.2 4.3 5.0 POWER SUPPLY/BATTERY CHARGER .......................................................................................4 OUTPUTS........................................................................................................................................4 DETECTOR CIRCUIT .....................................................................................................................4 SYSTEM DESCRIPTION.....................................................................................................................5 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 3.10 3.11 3.12 3.13 3.14 4.0 UNPACKING AND INSPECTION....................................................................................................3 ANTI STATIC PRECAUTIONS........................................................................................................3 SPECIFICATIONS ...............................................................................................................................4 2.1 2.2 2.3 3.0 PAGE NO. RESETTING THE SYSTEM ..........................................................................................................12 USING THE WALK TEST FACILITY.............................................................................................12 TRIAL EVACUATION. ...................................................................................................................12 TROUBLESHOOTING ......................................................................................................................13 APPENDIX A. DETECTOR CIRCUIT LIMITATIONS. .............................................................................14 APPENDIX B. COMPATIBLE OUTPUT DEVICES .................................................................................18 Doc No: g0097wo1.doc Dir No: L:\manuals Page 2 Date: 10/5/00 Rev: 1 AMPAC INDUSTRIES LTD NZ 100 OPERATORS MANUAL 1.0 INTRODUCTION 1.1 UNPACKING AND INSPECTION Carefully check packing before unpacking goods for any transit damage. Unpack the goods and check both externally and internally for any loose or damaged components that may affect the appearance, installation or operation of the goods. 1.2 ANTI STATIC PRECAUTIONS To prevent damage to panel components please ensure before touching or handling any of the wiring or printed circuit boards within the panel that you are correctly earthed. Doc No: g0097wo1.doc Dir No: L:\manuals Page 3 Date: 10/5/00 Rev: 1 AMPAC INDUSTRIES LTD NZ 100 OPERATORS MANUAL 2.0 SPECIFICATIONS Size 2.1 2.2 220H x 290W x 80D POWER SUPPLY/BATTERY CHARGER Mains Supply Charger Output Voltage Output Current 13.5V DC 0.5A Battery (one of only) 12V 7AH System Quiescent Current (After 10 minutes battery operation) 22mA OUTPUTS Bell Circuits Voltage Maximum current End of line resistor Door Holder output Voltage Current 2.3 230V AC " 10% @ 0.5A (2 total) 12V DC 3A max 10kohm 1/4W 2% 12V 250mA DETECTOR CIRCUIT Line voltage (open circuit) Short circuit current Maximum Cable Loop Impedance End of line resistor Devices Smoke detectors Electronic heat detectors Doc No: g0097wo1.doc Dir No: L:\manuals 22V 22mA 100 ohm 6.8kohm 1/4W 2% 24V 24V Page 4 Date: 10/5/00 Rev: 1 AMPAC INDUSTRIES LTD NZ 100 OPERATORS MANUAL 3.0 SYSTEM DESCRIPTION 3.1 GENERAL DESCRIPTION The NZ100 is an automatic fire alarm system. The NZ100 has one fire detection circuit able to accommodate heat detectors, smoke detectors, manual call points or a combination of these devices. The NZ100 has a bell output to alert personnel in the event of a fire. This output is monitored. All circuitry except for the front panel LEDs is on a single printed circuit board. 3.2 FRONT PANEL LAYOUT SILENCE ALARMS BRIGADE USE ONLY TRIAL EVACUATION FIRE DEFECT NORMAL NZ100 Fire Alarm Panel Doc No: g0097wo1.doc Dir No: L:\manuals Page 5 Date: 10/5/00 Rev: 1 AMPAC INDUSTRIES LTD NZ 100 OPERATORS MANUAL 3.3 INTERNAL LAYOUT Walk test switch Buzzer mute switch Reset switch Mains Termination and Fuse Mains Transformer M3 R1 C3 D.H.250mA SW1 F1 BZ1 + SW2 C4 SW3 NORMAL U1 BELL3A F2 + BELL - TB3 SYS. BATT 800mA ZONE F3 RL1 BATT. DEFECTS K1 SMOKE ONLY D8 ZD2 Q3 Q4 GATING K2 U2 R7 R8 R6 RN2 C5 D9 X1 K3 C6 D10 R9 R10R11 R12 Batt RN1 BELL CN1 R5 Battery RESET Q2 TB2 D2 + BELL - BUZZER MUTE D1 R2 ZD1 R3 R4 + D.H - Door Holder fuse Bell fuse Battery fuse WALK TEST Q1 C1 C2 FRONT PANEL M2 M1 TB1 + DET - C8 + Q5 + C10+ C11 C12 C13 TESTED R15 R16 R17 R18 RN3 R14 C14 U4 + U3 + C16 R29 D11 3.4 D15 C21 + Secondary Fuse + + R27 TX 30V C.T 15V A.C. R28 R19 D12 C17 C20 D14 C19 R23 R26 C23 API 665 1/11/96 0V TB5 1 R20 L1 D13 0V C15 + C18 R21 U5 RN4 R13 + C9 + TB4 M4 CN2 C7 + ASPI / BRIGADE - C22 R25 2 3 R22 R24 SECONDARY FUSE D16 MAINS ON F4 800mA DETECTOR CIRCUITS The detector circuits can accept smoke detectors, heat detectors or manual call points. Detectors and manual call point types used are subject to the compatibility limitations as described in section 4. Open circuit operating devices will cause the panel to go into alarm in one second. Devices such as smoke detectors, which signal by increasing line current, can, when signalling, go through “gating” or Alarm Verification. As such, when a detector goes into alarm, it is reset and not monitored for two to three seconds, if an alarm is still present after this time, the system will then latch into alarm. This function may be de-selected if not required by removing link K2. See section 5 for details. Important: Detector line voltage is 22V (open circuit). Current signalling detectors (smoke or electronic heat) must be rated for 24V operation. 3.5 BELL CIRCUITS The NZ100 provides a monitored bell circuit split to drive up to three (3) Amps of alarm load. The circuit is split into two parallel lines, which must be less than three (3) Amps total. Each line requires a 10K EOL resistor to give a system normal indication. If either output line is open or shorted, a defect signal is generated and the “BELLS” defect LED is illuminated. See section 4 for connection details. Doc No: g0097wo1.doc Dir No: L:\manuals Page 6 Date: 10/5/00 Rev: 1 AMPAC INDUSTRIES LTD NZ 100 OPERATORS MANUAL 3.6 DOOR HOLDER OUTPUT The NZ100 system provides a door holder output, marked D.H on P.C.B. This can provide 12V(nominal) @250mA. This output is switched off during an alarm. It is also switched off ten minutes after mains failure is detected to conserve battery power. 3.7 WALK TEST This function is initiated by pressing the walk test button on the API665.When this button is pressed a LED directly above the switch indicates. While the panel is in the walk test mode the detectors can be operated in the field and the panel will automatically reset them after a period of four seconds. To restore the panel to normal operation simply repress the switch and the walk test indicator will turn off. This Function will operate for ten minute after which it will be automatically cancelled 3.8 BUZZER The NZ100 has an internal buzzer, which will sound for any defect, which may occur. 3.9 BUZZER MUTE Pressing this switch will cause the buzzer to stop sounding for all defects, which are currently present. Any new defects will cause the buzzer to sound again. The buzzer will also emit a short beep for confirmation of switch operation. 3.10 DEFECT INDICATORS Defect indicators are provided on the NZ100 for the following. (a) Battery Fault. This indicates one of the following: Battery voltage is below 12.2 Volts during discharge (mains failure). Battery voltage is below 12.6 Volts whilst charging. Battery voltage is above 14 Volts. Battery is not connected. Battery failed automatic test. 3.11 (b) Bell Fault. This indicates an open or short circuit on bell line/s. (c) System Fault. This indicates mains has failed. (d) Zone fault. This indicates a fault on the zone wiring. Normally this would be a short circuit, however if “SMOKE ONLY” is selected it can also be an open circuit. POWER SUPPLY The API665 has an on board power supply providing 13.5VDC at 0.5A for system power and charging the system batteries. The system incorporates a test function, controlled by the CPU on the API 665, which decreases the power supply output voltage to 10V for forty minutes every two days to check the condition of the system batteries. If the battery voltage falls below 12.2V during the test period a defect signal is generated and the battery fault LED is illuminated. Doc No: g0097wo1.doc Dir No: L:\manuals Page 7 Date: 10/5/00 Rev: 1 AMPAC INDUSTRIES LTD NZ 100 OPERATORS MANUAL 3.12 MAINS ON INDICATOR This LED is illuminated when the mains supply is connected and operational. 3.13 FUSING The NZ100 has five fuses: F1 Door holder circuit fuse F2 Bell circuit fuse F3 Battery circuit fuse F4 Power supply fuse Mains fuse 3.14 0.25 Amp M205 3 Amp M205 0.8 Amp M205 0.8 Amp M205 0.5 Amp M205 BATTERIES The NZ100 system is designed to accept one 12V, 7 AH sealed lead acid battery. This should provide more than 240 hours of backup capacity leaving sufficient capacity to drive the alarm load for the required 30 minutes. Doc No: g0097wo1.doc Dir No: L:\manuals Page 8 Date: 10/5/00 Rev: 1 AMPAC INDUSTRIES LTD NZ 100 OPERATORS MANUAL 4.0 CONNECTING DEVICES 4.1 DETECTORS Devices such as heat detectors or manual call points which are normally closed, open circuiting for the alarm condition will give a fire signal within one second of operating. Devices, which increase the current in the detector line such as smoke detectors, may be operated with “gating” (alarm verification) as per section 3.4 to eliminate false alarms due to transient conditions. See also section 5 for details on alarm verification settings. Note: These detectors must not directly short the line as a short circuit gives a defect signal. Devices that have closing contact outputs, such as beam detectors, should have a resistor, in the range of 220ohm to 560ohm installed in series with the contacts. Each circuit must be terminated with an end of line resistor with a value of 6.8K (2% tolerance or better, power rating 1/4W) L1 OUT L2 EOL RESISTOR 6.8K 560 Ohm Resistor HEAT DETECTOR MANUAL OPENING ON CALL ALARM POINT BEAM DETECTOR CONTACTS L1 IN + Zone - SMOKE DETECTOR (eg APOLLO SERIES 60 DETECTOR) THIS DRAWING IS INDICATIVE OF WIRING ONLY. ANY COMBINATION OF DETECTORS AND MANUAL CALL POINTS WITHIN SPECIFIED LIMITS IS PERMISSABLE. 4.2 DETECTOR LIMITATIONS Most detectors, with the exception of thermostatic heat detectors, draw a small monitoring current and this limits the number detectors which can be connected to a given zone circuit. The total quiescent current of all devices on a zone circuit must be less than 1.6mA @ 24V to ensure correct operation. Appendix A lists the number of detector types which may be fitted to a zone circuit. 4.3 BELLS AND SOUNDERS Two bell/sounder circuits are provided, capable of driving a combined load of three (3) Amps. These lines are monitored using a small current in reverse polarity to normal operation. For this reason it is necessary to connect the bells via diodes, 1N4004 diodes are recommended, as shown in Figure 4.2. Also observe bell/sounder polarity. + 1N4004 DIODES EOL 10K RESISTOR S B BELLS B - Doc No: g0097wo1.doc Dir No: L:\manuals Page 9 Date: 10/5/00 Rev: 1 AMPAC INDUSTRIES LTD NZ 100 OPERATORS MANUAL 5.0 SETTINGS The NZ100 system has two (2) link options. These are set by simply fitting or removing the jumper plug. If removing a jumper link, it is a good idea to refit it to one of the header pins. This will avoid losing the jumper, which may be required at a later date. Important: There is also a link K3 for use during factory testing, this must not be fitted. 5.1 SMOKE ONLY If link K1 is fitted then the NZ100 will not sense manual call points or thermostatic heat detectors. This allows the removal of a smoke detector head to initiate a defect instead of an alarm. If desired electronic heat detectors may still be used on the “SMOKE ONLY” setting as these operate similarly to smoke detectors. 5.2 GATING “GATING” is an automatic verification facility to reduce nuisance alarms caused by a transient condition. When the “GATING” link (K2) has been fitted, the signal from smoke detectors and electronic heat detectors is verified before an alarm is recognised. Doc No: g0097wo1.doc Dir No: L:\manuals Page 10 Date: 10/5/00 Rev: 1 AMPAC INDUSTRIES LTD NZ 100 OPERATORS MANUAL 6.0 INSTALLATION AND INITIAL OPERATION 6.1 INSTALLING THE NZ3200 Do not apply power or connect batteries during this procedure. 1. Unpack NZ100. 2. Check for transit damage. 3. Drill all cable access and mounting holes. 4. Mount the unit into position. 5. Feed cables into the unit. 6. Connect mains cabling to the mains terminal block. 7. Connect detector cabling. 8. Connect ancillary cabling. 9. Set links as required. See section 5. 10. Ensure all swarf is removed from panel before applying power. 6.2 INITIAL OPERATION 1. 2. 3. 4. Doc No: g0097wo1.doc Switch on mains power to the unit. Battery defect LED should illuminate after 10 seconds. Connect batteries. Press ‘RESET’, Battery defect LED should extinguish. The unit is ready for operation. Dir No: L:\manuals Page 11 Date: 10/5/00 Rev: 1 AMPAC INDUSTRIES LTD NZ 100 OPERATORS MANUAL 7.0 SYSTEM OPERATION 7.1 RESETTING THE SYSTEM To reset the system after a fire, press the ‘RESET’ button on the API665. This will return the system back to its normal state. The buzzer will sound for confirmation. 7.2 USING THE WALK TEST FACILITY. To start the walk test facility, press the ‘Walk Test’ switch on the API665. The buzzer will beep once and the LED above the switch will illuminate. The detectors can now be tested. As a detector is set into alarm the system will operate as normal, except that after approximately four seconds the detectors on the circuit in alarm will be reset. After testing is complete, press the ‘Walk Test’ switch to return to normal. The walk test facility has an internal time out and will be de-selected automatically after ten (10) minutes of operation. 7.3 TRIAL EVACUATION. On the door of the NZ100 a key switch is provided for Trial Evacuation, operating this key switch will cause the system to operate the bells. This will override any other bell isolate or silence condition. Doc No: g0097wo1.doc Dir No: L:\manuals Page 12 Date: 10/5/00 Rev: 1 AMPAC INDUSTRIES LTD NZ 100 OPERATORS MANUAL 8.0 TROUBLESHOOTING Problem Possible cause/s Suggested remedy/ action Mains LED is off Mains supply is not operational. Check mains supply. AC Fuse on API 665 is blown. Check and replace if necessary F4 on API665. System signals fire. Fire LED is on, zone not in alarm. Battery voltage below 9.6V. If main is off, see above. If mains is on, disconnect battery. If voltage rises, replace batteries. Bell circuits in defect. Diodes not fitted in series with bell. Fit diodes to bells as shown in section 4.2. End of line not fitted. Fit end of line resistor as stated in table 4.2 Fuse blown. Check fuse F2 on PCB. Replace if necessary. Too many smoke or electronic heat detectors on detector line. Reduce detectors on line to limits in Appendix A. Smoke only link is fitted. Remove smoke only link (K1). Too many smoke or electronic heat detectors on detector line. Reduce detectors on line to limits in table Appendix A. Smoke only link is fitted. Remove smoke only link (K1). Line is shorted. Check and remove short. Line is open. Check line and rectify. End of line not fitted. Fit 6K8 resistor to end of line. Zone always in defect. (Smoke only link not fitted) Line is shorted. Check and remove short. Zone always in fire. (Smoke only link not fitted) Line is open circuit Connect line correctly. End of line not fitted. Fit 6K8 end of line. Heat detector, opening contacts, will not signal fire. Manual call point will not signal fire. Zone always in defect. (Smoke only link fitted) Doc No: g0097wo1.doc Dir No: L:\manuals Page 13 Date: 10/5/00 Rev: 1 AMPAC INDUSTRIES LTD NZ 100 OPERATORS MANUAL Appendix A. DETECTOR CIRCUIT LIMITATIONS. Detector Type Thermal Detector (opening on alarm) Quiescent Current 0mA Circuit Limit No limit Manual Call Point 0mA No limit Apollo Series 60 Heat Detector (55000-105) 57mA 28 Apollo Series 60 Heat Detector (55000-106) 57mA 28 Apollo Series 60 Heat Detector (55000-107) 57mA 28 Apollo Series 60 Heat Detector (55000-108) 57mA 28 Apollo Series 60 Ionisation Smoke Detector (55000-200) 45mA 35 Apollo Series 60 Photoelectric Smoke Detector (55000-300) 45mA 35 * Hochiki America SIH 24F Ionization Smoke Detector 40mA 40 Hochiki America SLK 24F Photoelectric Smoke Detector 45mA 35 Fenwal CDP7051 Ionization Smoke Detector 45mA 35 Fenwal CDP7155 Photoelectric Smoke Detector 55mA 29 * Photain Controls PRRP91 Heat Detector 65mA 24 Photain Controls ISD-P91 Ionisation Smoke Detectors 40mA 40 *This detector should be used with Gating switched off to meet the requirements of NZS 4512. See operators manual section 5 for details. Doc No: g0097wo1.doc Dir No: L:\manuals Page 14 Date: 10/5/00 Rev: 1 AMPAC INDUSTRIES LTD NZ 100 OPERATORS MANUAL Appendix A. DETECTOR CIRCUIT LIMITATIONS. Detector Type Thermal Detector (opening on alarm) Quiescent Current 0mA Circuit Limit No limit Manual Call Point 0mA No limit Apollo Series 60 Heat Detector (55000-105) 57mA 28 Apollo Series 60 Heat Detector (55000-106) 57mA 28 Apollo Series 60 Heat Detector (55000-107) 57mA 28 Apollo Series 60 Heat Detector (55000-108) 57mA 28 Apollo Series 60 Ionisation Smoke Detector (55000-200) 45mA 35 Apollo Series 60 Photoelectric Smoke Detector (55000-300) 45mA 35 * *This detector should be used with Gating switched off to meet the requirements of NZS 4512. See operators manual section 5 for details. Doc No: g0097wo1.doc Dir No: L:\manuals Page 15 Date: 10/5/00 Rev: 1 AMPAC INDUSTRIES LTD NZ 100 OPERATORS MANUAL Appendix A. DETECTOR CIRCUIT LIMITATIONS. Detector Type Quiescent Current Circuit Limit Thermal Detector (opening on alarm) 0mA No limit Manual Call Point 0mA No limit Apollo Series 60 Heat Detector (55000-105) 57mA 28 Apollo Series 60 Heat Detector (55000-106) 57mA 28 Apollo Series 60 Heat Detector (55000-107) 57mA 28 Apollo Series 60 Heat Detector (55000-108) 57mA 28 Apollo Series 60 Ionisation Smoke Detector (55000-200) 45mA 35 Apollo Series 60 Photoelectric Smoke Detector (55000-300) 45mA 35 * Photain Controls PRRP91 Heat Detector 65mA 24 Photain Controls ISD-P91 Ionisation Smoke Detectors 40mA 40 *This detector should be used with Gating switched off to meet the requirements of NZS 4512. See operators manual section 5 for details. Doc No: g0097wo1.doc Dir No: L:\manuals Page 16 Date: 10/5/00 Rev: 1 AMPAC INDUSTRIES LTD NZ 100 OPERATORS MANUAL Appendix A. DETECTOR CIRCUIT LIMITATIONS. Detector Type Quiescent Current Circuit Limit Thermal Detector (opening on alarm) 0mA No limit Manual Call Point 0mA No limit Apollo Series 60 Heat Detector (55000-105) 57mA 28 Apollo Series 60 Heat Detector (55000-106) 57mA 28 Apollo Series 60 Heat Detector (55000-107) 57mA 28 Apollo Series 60 Heat Detector (55000-108) 57mA 28 Apollo Series 60 Ionisation Smoke Detector (55000-200) 45mA 35 Apollo Series 60 Photoelectric Smoke Detector (55000-300) 45mA 35 * Hochiki America SIH 24F Ionization Smoke Detector 40mA 40 Hochiki America SLK 24F Photoelectric Smoke Detector 45mA 35 Fenwal CDP7051 Ionization Smoke Detector 45mA 35 Fenwal CDP7155 Photoelectric Smoke Detector 55mA 29 * *This detector should be used with Gating switched off to meet the requirements of NZS 4512. See operators manual section 5 for details. Doc No: g0097wo1.doc Dir No: L:\manuals Page 17 Date: 10/5/00 Rev: 1 AMPAC INDUSTRIES LTD NZ 100 OPERATORS MANUAL Appendix B. COMPATIBLE OUTPUT DEVICES Product Code Description BE0001 Bell 12VDC 30mA Red 150 mm. DETSQ07 Sounder with AS2220 Evac tone 9-28VDC 18mA. SO0001 Horn Siren 12VDC 115mA Red. SO0003 Flush sounder White 12/24V DC. SO0004 Flush sounder Red 12/24V DC. Doc No: g0097wo1.doc Dir No: L:\manuals Page 18 Date: 10/5/00 Rev: 1