U P S Transformerless Type
Taurus Pro 3P/3P
Taurus Pro 10K/15K/20K/30K/40K/60K
Taurus Pro 80K/100K/120K
Taurus Pro 160K/200K
O N L I N E
7” touch LCD (optional)
U P S
• Online double conversion technology with DSP control • Output power factor 0.9 • Advanced control with Adaptive Feed Forward Cancellation (AFC) technology for very low harmonic distortion • Very low input current distortion (THDi < 1%) • Input power factor 0.99 at 10% load • Output efficiency up to 95% • Space-saving compact design • Over 60% materials recyclable • Remaining backup time calculation • Front access makes maintenance and replacement easily • Highly flexibility in single phase/ three-phase set-ups • Parallel redundant operation with up to 4 units • Variety of communications and options available • Flexible battery type configuration by request (only available for Taurus Pro 400V models)
Taurus Pro 3P/3P 400V Online UPS Selection Guide MODEL PHASE CAPACITY
Taurus Pro 10K
Taurus Pro 15K
Taurus Pro 20K
Taurus Pro 30K
10KVA/ 9KW
15KVA/ 13.5KW
20KVA/ 18KW
30KVA/ 27KW
Taurus Pro Taurus Pro Taurus Pro 40K 60K 80K 3-phase in / 3-phase out 40KVA/ 36KW
60KVA/ 54KW
80KVA/ 72KW
Taurus Pro 100K
Taurus Pro 120K
Taurus Pro 160K
Taurus Pro 200K
100KVA/ 90KW
120KVA/ 108KW
160KVA/ 144KW
200KVA/ 180KW
INPUT Nominal Voltage
3 x 400V (3Ph + N)
Acceptable Voltage Range
+15% or –20%
Frequency
50 / 60 Hz ±5 % < 1.0% @ 100% load < 2.0% @ 50% load < 5.0% @ 10% load High overload: PFC Limit (discharging batteries)
< 1.5% @ 100% load < 2.5% @ 50% load < 6.0% @ 10% load
Total Harmonic Distortion (THDi) Current Limitation Power Factor
< 1.5% @ 100% load < 2.0% @ 50% load < 6.0% @ 10% load
1.0
INVERTER Nominal Voltage
3 x 400V (3Ph + N)
Precision
Stationary: ±1% ; Transitory: ±2% (load variations 100-0-100%)
Frequency
50/60 Hz synchronised ±4 % With mains absent ±0.05%
Max. Synchronisation Speed
10 Hz/s
Waveform
Pure Sinewave
Total Harmonic Distortion (THDv)
< 0.5% (Linear Load) ; < 1.5% (Non-linear Load)
Phase Displacement
120º ±1% (balanced load) ; 120º ±2% (imbalances 50% of the load)
Dynamic Recovery Time
10 ms. at 98 % of the static value
Admissible Overload
Phase Overload: 125% for 10 min., 150% for 60s ; Total Overload: 112.5% for 10 min., 135% for 60s
Admissible Crest Factor
3.4 : 1
3.2 :1
Admissible Power Factor
2.8 : 1
3.2 :1
3.0 :1
0.7 inductive to 0.7 capacitive
Imbalance Output Voltage @ 100%Unbalanced Load
<1%
Current Limit
High overload, short-circuit: RMS Voltage Limit ; High Crest-Factor current: Peak Voltage Limit
STATIC BYPASS Type
Solid state
Voltage
3x400V (3Ph + N)
Frequency
50/60 Hz
Activation Criterion
Microprocessor control
Transfer Time
Zero
Admissible Overload
400% for 10 sec.
Transfer to Bypass
Immediate, for overloads above 150%
Retransfer
Automatic after alarm clear
MAINTENANCE BYPASS Type
Without interruption
Voltage
3 x 400V (3Ph + N)
Frequency Overall Efficiency (Line mode)
50/60 Hz 90.0%
90.5%
91.0%
92.0%
92.5%
93.0%
94.0%
93.0%
93.3%
12V 4.5Ah
12V 4.5Ah
12V 7Ah
12V 9Ah
12V 12Ah
-
5
3
5
3
3
-
92.8%
92.6%
BATTERY Built-in Battery Type (2x31) Back-up Time (minutes) Max. Charging Current
23.5 A
47 A
70.5 A
188 A
PHYSICAL Dimension, D x W x H(mm)
770 x 450 x 1100
805 x 590 x 1320
Net Weight (without batteries) (Kg)
78
86
94
110
122
Net Weight (w/built-in batteries) (Kg)
178
186
249
290
357
162
231
255
850 x 900 x 1900 550
-
*NOTE: When temperature is above 30°C, the output power will be derated. The output power is derated to 90% at 31°C -35°C and 80% at 36°C -40°C. * Product specifications are subject to change without further notice
Advancing Power
34
O n lin e
U P S Transformerless Type
Taurus Pro 3P/3P 208V Online UPS Selection Guide MODEL
Taurus Pro 7.5K
Taurus Pro 10K
Taurus Pro 15K
Taurus Pro 20K
7.5KVA/ 6.75KW
10KVA/ 9KW
15KVA/ 13.5KW
20KVA/ 18KW
PHASE
O N L I N E
U P S
CAPACITY
Taurus Pro Taurus Pro 30K 40K 3-phase in / 3-phase out 30KVA/ 40KVA/ 27KW 36KW
Taurus Pro 50K
Taurus Pro 60K
Taurus Pro 80K
Taurus Pro 100K
50KVA/ 45KW
60KVA/ 54KW
80KVA/ 72KW
100KVA/ 90KW
INPUT Nominal Voltage
3 x 208V (3Ph + N)
Acceptable Voltage Range
+15% or –20%
Frequency Total Harmonic Distortion (THDi)
50 / 60 Hz ±5 % < 1.0% @ 100% load < 2.0% @ 50% load < 5.0% @ 10% load High overload: PFC Limit (discharging batteries)
< 1.5% @ 100% load < 2.5% @ 50% load < 6.0% @ 10% load
Current Limitation Power Factor
< 1.5% @ 100% load < 2.0% @ 50% load < 6.0% @ 10% load
0.99 from 10% load
INVERTER Nominal Voltage
3 x 208V (3Ph + N)
Precision
Stationary: ±1% ; Transitory: ±2% (load variations 100-0-100%)
Frequency
50/60 Hz synchronised ±4 % With mains absent ±0.05%
Max. Synchronisation Speed
1 Hz/s
Waveform
Pure Sinewave
Total Harmonic Distortion (THDv)
< 0.5% (Linear Load) ; < 1.5% (Non-linear Load)
Phase Displacement
120º ±1% (balanced load) ; 120º ±2% (imbalances 50% of the load)
Dynamic Recovery Time
10 ms. at 98 % of the static value
Admissible Overload
125%~135% for 5 min., 135%~150% for 60 s
Admissible Crest Factor
3.4 : 1
3.2 :1
2.8 : 1
Admissible Power Factor
3.2 :1
3.0 : 1
0.7 inductive to 0.7 capacitive
Imbalance Output Voltage@ 100%Unbalanced Load
<1%
Current Limit
High overload, short-circuit: RMS Voltage Limit ; High Crest-Factor current: Peak Voltage Limit
STATIC BYPASS Type
Solid state
Voltage
3 x 208V (3Ph + N)
Frequency
50/60 Hz
Activation Criterion
Microprocessor control
Transfer Time
Zero
Admissible Overload
400% for 10 sec.
Transfer to Bypass
Immediate, for overloads above 150%
Retransfer
Automatic after alarm clear
MAINTENANCE BYPASS Type
Without interruption
Voltage
3 x 208V (3Ph + N)
Frequency Overall Efficiency (Line mode)
50/60 Hz 89.5%
90.0%
91.0%
91.5%
92.0%
12V 4.5Ah
12V 7Ah
12V 9Ah
12V 12Ah
93.0%
92.5%
92.0%
93.0%
93.0%
BATTERY Built-in Battery Type (2x19) Max. Charging Current
23.5 A
47 A
70.5 A
188 A
PHYSICAL Dimension, D x W x H(mm) Net Weight (without batteries) (Kg) Net Weight (w/built-in batteries) (Kg)
770 x 450 x 1100
805 x 590 x 1320
805 x 900 x 1900
86
94
110
122
162
231
255
255
151
195
227
272
-
-
-
-
550
*NOTE: When temperature is above 30°C, the output power will be derated. The output power is derated to 90% at 31°C -35°C and 80% at 36°C -40°C. * Product specifications are subject to change without further notice
External Battery Cabinet For 400V UPS BATTERY-12Ah Dimensions, D x W x H (mm) Built-in Battery Type (2 x 31) Net Weight (Kg) DIY Cabinet
BATTERY-18Ah 700 x 450 x 1100
12V 12Ah 250
12V 18Ah 410
BATTERY-26Ah 805 x 590 x 1320 12V 26Ah 710
BATTERY-40Ah 980 x 650 x 1320 12V 40Ah 1020
C16
C32-17Ah
C32-26Ah
C32-40Ah
C65
CH64-100
Dimensions, D x W x H (mm)
780 x 470 x 1190
780 x 880 x 1190
780 x 880 x 1190
780 x 880 x 1190
1500 x 860 x 1370
1600 x 970 x 1480
Built-in Battery Type (2 x 31)
12V 12Ah
12V 17Ah
12V 26Ah
12V 40Ah
12V65Ah
12V100Ah
45
45
95
95
150
180
Net Weight (Kg)
* Battery cabinet types of C16 to CH64-100 are DIY-made battery cabinets. For 208V UPS Dimensions, D x W x H (mm) Built-in Battery Type (2 x 19) Net Weight (Kg) * Product specifications are subject to change without further notice
35 www.voltronicpower.com
BATTERY-26Ah 700 x 450 x 1100 12V 26Ah 380
BATTERY-40Ah 805 x 590 x 1320 12V 40Ah 610