Transcript
Operating Instructions
6 720 618 477-00.1RS
Room controller
For the user
RC35 user interface
Please read carefully before use.
6 720 640 226 - 05/2009 US/CA
Logamatic EMS
Overview of operation
Overview of operation Legend for figure: 1
Cover: Pull the recessed grip on the left to open
2
Display
3
Dial for changing values and temperatures or for navigating through the menus
4
5
Buttons for basic functions:
When the LED lights up
“AUT” (automatic)
•
... the program is active (automatic switchover between day and night room temperatures).
“Day mode” (manual)
•
... the heating system operates at the set day room temperature. DHW heating is switched on (factory setting).
“Night mode” (manual)
•
... the heating system operates at the set night setback room temperature. Frost protection is active. DHW heating is switched OFF (factory setting).
“DHW” (domestic hot water)
•
... the DHW temperature has fallen below its set value while in setback mode. The DHW can be heated up again (single change) by pressing the button (the LED will then flash).
Buttons for additional functions:
Function:
“Menu/OK”
Open the user menu and confirm the current selection.Turning the dial while pressing the button will change the value.
“Time”
Set the time.
“Date”
Set the date.
“Temperature”
Set the room temperature.
“Info”
Open the Info menu (to view values).
“Back”
Go back one step or one menu item.
In automatic mode, an additional LED lights up with the “AUT” LED to indicate which operating status is currently active (“day mode” or “night mode”). The “domestic hot water” LED can also be disabled.
2
Logamatic EMS RC35 user interface - Subject to technical modifications.
Contents
Contents 1
Explanation of symbols and safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.1 Explanation of symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2
Getting started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3
Product description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.1 Product description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.3 Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.4 Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.5 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11 11 11 11 11 11
4
Basic operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.1 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.2 Notes on functional scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3 Setting the operating mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.4 Changing the room temperature temporarily . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.5 Changing the room temperature permanently . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.6 Setting the room temperature for particular heating zones . . . . . . . . . . . . . . . . . . . . . . . 4.7 Setting the date and time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.8 Setting functions for domestic hot water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.9 Reviewing information (Info menu) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.10 Messages on the display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.11 Shut-down/switching OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12 12 12 13 14 15 16 17 18 20 22 22
5
User menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1 Introduction to the User menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2 Overview of the User menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3 Heating zone selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.4 Adjusting the standard display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.5 Selecting the operating mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.5.1 Operating modes for RC35 heating zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.5.2 Modes of operation for DHW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.5.3 Operating modes for DHW circulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.5.4 Operating modes for solar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.6 Setting the program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.6.1 Select program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
23 23 25 26 29 29 29 30 30 30 31 32
Logamatic EMS RC35 user interface - Subject to technical modifications.
3
Contents
5.6.2 5.6.3 5.6.4 5.6.5 5.6.6 5.7 5.8 5.9 5.10 5.11 5.12 5.13 5.14 5.15 5.16
Viewing the current program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Changing a switch point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Entering a switch point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Deleting set point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting room temperatures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting a DHW program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting the DHW circulation program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting the warm weather shutdown (WWSD) temperature . . . . . . . . . . . . . . . . . . . . . Setting the daylight savings time changeover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Set the DHW temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting vacation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting the party mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting the pause function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting thermal disinfection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Calibrating the room temperature display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
35 35 36 37 38 39 39 40 40 40 41 44 44 45 45
6
Information for setting the RC35 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 6.1 Control modes for the heating system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 6.2 Tips for energy efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
7
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1 Frequently asked questions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.2 Error messages and service messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.3 Resetting faults (reset) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
Setup log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
49 49 51 53
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
4
Logamatic EMS RC35 user interface - Subject to technical modifications.
Explanation of symbols and safety instructions
1
1
Explanation of symbols and safety instructions
1.1 Explanation of symbols Warnings Warnings in the text are indicated by a warning triangle with a gray background in a framed box.
In case of danger due to current, the exclamation point on the warning triangle is replaced with a lightning symbol.
Signal words at the beginning of a warning are used to indicate the type and seriousness of the ensuing risk if measures for minimizing damage are not taken. • NOTE indicates that damage to property may occur. • CAUTION indicates possible minor to medium personal injury. • WARNING indicates possible severe personal injury. • DANGER indicates that severe personal injury may occur. Important Information Important information that presents no risk to people or property is indicated with this symbol. They are separated by lines above and below the text.
Additional symbols Symbol
Explanation
B
Sequence of steps
Æ
Cross-reference to other points in this document or to other documents
•
Listing/list entry –
Listing/list entry (2nd level))
Tab. 1
Logamatic EMS RC35 user interface - Subject to technical modifications.
5
1
Explanation of symbols and safety instructions
Display text: Words appearing on the display are shown in bold in the text. Example: USER MENU
USER MENU
Bstandard display modes of operation program WWSD temperature
Action sequences: Sequences of steps are marked with a triangle with its point towards the text. Example: Press
.
If action sequences have more than two steps and the order of the steps is important, they are numbered (1., 2., ...). Note on using this manual: Section 5.1 "Introduction to the User menu" explains in detail the steps needed for programming all the settings in the Service menu. In the sections which come after it, programming is only exexplained in outline.
6
Logamatic EMS RC35 user interface - Subject to technical modifications.
Explanation of symbols and safety instructions
1
1.2 Safety instructions Installation and commissioning B Observe all instructions to ensure satisfactory operation. B Read and observe the safety information and codes of conduct! B Installation and commissioning must only be carried out by qualified and trained system installers. Use B Always use this device correctly and in conjunction with the stated control systems. B Observe all regulations, standards, and codes applicable to installation and operation of the system in your country. Risk of death from electric shock B The electrical supply must be connected by a qualified electrician. The terminal diagram must be followed. B Before installation: isolate all poles of the power supply (120 V AC). B Do not install this device in rooms with high moisture exposure (e.g. bathrooms, saunas). B Never directly connect this device to the 120 V AC power mains. Risk of scalding at the taps B Make sure that a thermostatic mixing valve is installed and that it is set to temperatures below 122 °F (50 °C). Warning: frost The heating system can freeze up in cold weather, if switched OFF or locked out. B Leave the heating system permanently switched ON. B Enable frost protection. B In the event of a fault: remedy the fault immediately. Warning: device damage The RC35 has no field serviceable parts inside. Any attempt to open the housing will cause internal damage, render the device inoperable, and void the manufacturer's warranty. B In case of system irregularities please consult the 7 "Troubleshooting" section of this manual.
Logamatic EMS RC35 user interface - Subject to technical modifications.
7
2
2
Getting started
Getting started
Initial situation: the cover is closed. What do I do
Operation
if it is temporarily too cool/warm in the entire home on a particular day?
B Turn the dial . The current room temperature setting starts flashing. B Use the dial to set the desired room temperature. B Release the dial. The modified room temperature is saved (and stops flashing). The standard display appears again.
Display/result SET ROOM TEMPERATURE Until next switch point, room temp. changed to: 70°F
In automatic mode, the modified room temperature remains active until the next switchover between night/day mode. if it is permanently too cool/warm? Æ change room temperature and activate automatic mode
B To change the day room temperature: hold down the button and turn the dial at the same time. B To change the nighttime room temperature: hold down the button and turn the dial at the same time.1) B Activating the automatic mode is recommended: Press the button. The modified room temperatures are saved. The LED next to the button lights up.
Tab. 2
8
SET ROOM TEMPERATURE Room temperature setting for day mode. 69°F
Automatic mode selected. Change between: day: night:
69°F 63°F
Getting started – room temperatures
Logamatic EMS RC35 user interface - Subject to technical modifications.
Getting started
2
What do I do
Operation
for a single boost outside the usual times (outside of the program)? Æ manual day mode (“continuous heating”); automatic mode is switched off
B Activate manual day mode: press the button. The LED next to the button lights up.
to save energy during long absences? Æ manual night mode (“permanently setback”); automatic mode is switched off
B Activate manual night mode: press the button. The LED next to the button lights up.1)
Tab. 2
To end the temporary heating phase: B Activate automatic mode again: press the button. The LED next to the button lights up.
When you return: B Activate automatic mode again: press the button. The LED next to the button lights up.
Display/result You day The set
have selected mode. room temperature is: 69°F
You have selected night mode. The room temperature set is: 57°F
Getting started – room temperatures
1) If “shut-down mode” is selected as the night reduction mode, the heating system is switched off at night. A night room temperature cannot be set. The display will show a message to that effect.
In the case of large heating systems with multiple heating zones, note the following: The modifications in room temperature described above apply to all heating zones assigned to the RC35 user interface (these are the RC35 heating zones Æ page 26). This is the normal setting. However, if you wish to change the room temperature for other heating zones: read page 38. Getting started – additional functions Some of the following functions are accessible via the User menu. To learn how to use this menu, read the section starting on page 23.
Logamatic EMS RC35 user interface - Subject to technical modifications.
9
2
Getting started
What do I do
Operating Instructions
to save energy when on vacation?
B Set vacation mode in the User menu (Æ page 41).
to change the vacation temperature?
Requirement: vacation mode is active. B Turn the dial . The room temperature is changed for the rest of the vacation period.
Display/result
SET VACATION MODE Room temperature set for vacation mode:
57°F
in summer (DHW only, no central heating)?
The control unit switches automatically between summer mode and winter mode, triggered by temperature. However, if you want to switch the system over manually: B Turn the dial on the boiler controller to “0”. B Leave the RC35 settings unchanged.
if I feel too cool or too warm in spring or fall?
B Change the setting for the summer/winter switchover threshold in the User menu (Æ page 40). -orB Use manual mode.
when the time changes to/from daylight savings time?
Adjust the clock manually forward or backward (Æ page 40).
if my day/night rhythm changes (e.g. shift work)?
B Select a different program in the User menu (Æ page 31). B If necessary, adjust the program to suit your needs: change, insert or delete switch points (Æ page 35).
to change the contrast on the display?
B To change the contrast: hold down the buttons and and turn the dial at the same time.
Tab. 3
10
Example shown here: the BC10 on the boiler
Getting started – additional functions
Logamatic EMS RC35 user interface - Subject to technical modifications.
Product description
3
3
Product description
3.1 Product description The RC35 user interface makes it easy to operate your Buderus heating system. You can set the room temperature for your entire home using the dial. The automatic mode with its adjustable programs ensures energy-saving operation by reducing the room temperature at certain times or shutting down heating completely (adjustable night setback). The heating system is controlled in such a way that you benefit from optimum heating comfort and minimum energy consumption.
3.2 Intended use The RC35 control unit is intended for the operation and control of Buderus heating systems in single and multi-family houses. The boiler must be equipped with EMS (energy management system). Keep the RC35 user interface connected to the heating system at all times (only emergency operation is possible without it).
3.3 Certifications This product has been tested and is certified for both the US and Canadian markets, and meets all applicable US and Canadian standards.
3.4 Cleaning B The user interface should only be cleaned with a damp cloth.
3.5 Disposal B Dispose of packaging in an environmentally-responsible manner. B When replacing components, dispose of the old part in an environmentally responsible manner.
Logamatic EMS RC35 user interface - Subject to technical modifications.
11
Basic operation
4
4
Basic operation
4.1 Display The display on the RC35 user interface presents the following elements during normal operation:
am
1
71 F
2
4 2
Room
please open cover
3 6 720 618 414-01.1RS
Fig. 1 1 2 3 4
Elements on the display
Top information row: standard display (factory setting: date and time) Large display of room or boiler temperature Lower status row: displays various operating modes and indicates any error messages or service messages Solar symbol (when solar heating system is installed and active)
You can set which value is shown permanently in the first row of the default display (standard display) (Æ Fig. 1, [1]) (Æ page 29).
If the user interface is installed on the boiler, the room temperature cannot be recorded. Instead of the room temperature (Æ Fig. 1, [2]) the display then shows the boiler temperature (boiler).
4.2 Notes on functional scope These instructions describe all the possible functions of the RC35. Some of these functions may not be available, depending on which boiler (burner control unit) is used. For more information, refer to the relevant chapter. Contact your heating contractor for further details. To find out which version of burner control unit you have (in this case: UBA3.5) go to the Info menu under INFO\VERSIONS (Æ page 20).
12
INFO\VERSIONS RC35 UBA3.5
1.02 1.21
Logamatic EMS RC35 user interface - Subject to technical modifications.
Basic operation
4
4.3 Setting the operating mode You can set the operating mode directly by pressing the button shown: Operating mode
Button
Meaning
automatic (recommended setting)
The program is active. The system will switch over automatically between day mode and night mode at a set time (the switch point).1) At night the heating system will operate with a reduced room temperature (this is the factory setting; shutting down at night is also possible). Heating of domestic hot water (DHW) is ON during the day and OFF at night (factory setting). The LED for the Automatic button is lit up, along with the LED for either day or night mode, depending on which is currently active.
continuous heating (manual day mode)
The factory setting is 70 °F (21 °C). The manual day mode is useful if you want to heat the home occasionally outside of the usual times. The automatic mode is disabled. DHW heating is OFF (factory setting). Only the night mode LED is lit up.
permanently setback (manual night mode)
The factory setting is 63 °F (17 °C). At night the heating system will operate with a reduced room temperature (this is the factory setting; shutting down at night is also possible). The manual night mode is useful if you are occasionally absent for long periods. The automatic mode is disabled. DHW heating is OFF (factory setting). Only the night mode LED is lit up.
Tab. 4
Description of the operating modes
1) The automatic day and night modes correspond to the manual day and night modes. The only difference lies in the automatic switchover.
The settings made using the buttons above apply to all heating zones assigned to the RC35 user interface (these are referred to as the “RC35 heating zones” Æ page 26). To set the operating mode for other heating zones: use the User menu\modes of operation (Æ page 29).
Logamatic EMS RC35 user interface - Subject to technical modifications.
13
4
Basic operation
4.4 Changing the room temperature temporarily Follow this procedure if you only want to change the room temperature up until the next switch point. At the switch point, the automatic mode will switch the system over between day and night modes (Æ page 31). The heating system will then go back to the normal room temperature setting. Initial situation: the cover is closed. Operation 1.
Turn the dial
Result .
The current room temperature setting starts flashing. Turn the dial further. Turning the dial clockwise increases the room temperature, turning counter-clockwise lowers it. 2.
When you have reached the desired room temperature: release the dial. The modified room temperature is saved (and stops flashing). The standard display reappears.
INFO\ROOM\HTG.ZONE 1 room temperature set: 68.9°F measured room temperature: 69.0°F
In manual mode, the LED next to the button is not lit up. In this case the modified room temperature will be effective until you press one of the buttons . Ending a temporary change in room temperature B To return to automatic mode: press . The automatic program uses the temperatures normally set for day and night mode. -orB To return to manual mode: press either or . The temperatures normally set for day or night mode will be used.
14
Logamatic EMS RC35 user interface - Subject to technical modifications.
Basic operation
4
4.5 Changing the room temperature permanently NOTICE: Risk of system damage due to freezing. If room temperatures are set below 41 °F (5 °C), rooms may cool down so much that pipes in external walls (for example) may freeze in cold weather. B Set room temperatures higher than 41 °F (5 °C).
Operation 1.
To change the daytime room temperature: hold down the button and turn the dial at the same time.
Result SET ROOM TEMPERATURE Room temperature setting for day mode. 69°F
2.
Changing the nighttime room temperature1): Hold down the button and turn the dial at the same time.
SET ROOM TEMPERATURE Room temperature setting for night mode. 63°F
3.
We recommend activating the automatic mode. The automatic mode ensures automatic switchover between day and night mode (night setback).
Automatic mode selected. Change between:
Press
day: night:
.
69°F 63°F
The automatic mode is now active with the modified room temperatures. The LED next to the button lights up. The standard display appears again. 1) If “shut-down mode” is selected as the nighttime reduction mode, the heating system will be switched off at night. A night room temperature cannot be set. The display will show a message to that effect.
Logamatic EMS RC35 user interface - Subject to technical modifications.
15
4
Basic operation
4.6 Setting the room temperature for particular heating zones You can use the button to set the room temperature for selected heating zones if your heating system is equipped with multiple heating zones (Æ page 27). No selection is possible if there is only one heating zone to choose from. All RC35 heating zones have the same room temperature settings. If no selection is possible or if you select RC35 heating zones, you will be setting the same temperatures as described on page 15. NOTICE: Risk of system damage due to freezing. If room temperatures are set below 41 °F (5 °C), rooms may cool down so much that pipes in external walls (for example) may freeze in cold weather. B Set room temperatures higher than 41 °F (5 °C). B Open the cover (by pulling the recessed grip on the left). B Press and release. B Select the heating zone (Æ page 26 – 28). Heating zone selection is not available if there is only one heating zone installed. B To change the day room temperature: hold down the button and turn the dial at the same time. B Turn the dial to switch to the nighttime room temperature. B To change the nighttime room temperature: hold down the button and turn the dial at the same time. B Press several times or shut the cover to return to the default display. The modified room temperatures are now active. If “shut-down mode” is selected as the night reduction mode, the heating system will be switched off at night. A night room temperature cannot be set. The display will show a message to that effect.
16
Logamatic EMS RC35 user interface - Subject to technical modifications.
Basic operation
4
4.7 Setting the date and time Your heating system requires the date and time to operate correctly. The clock keeps running for about 8 hours in the event of a power failure. If a power failure lasts longer than that, the display will indicate that you need to reset the date and time. To set the date: 1. Open the cover (by pulling the recessed grip on the left). 2. Press . The year starts flashing. 3. To set the year: hold down the button and turn the dial at the same time. 4. Release the button. The year is saved. 5. Repeat steps 2 to 4 to set the month and day. The set date is shown briefly. The standard display then re-appears. To set the time: 1. Press . The hours start flashing. 2. To set the hours: hold down the button and turn the dial at the same time. 3. Release the button. The hours are saved. 4. Repeat steps 1 to 3 to set the minutes. The set time is shown briefly. The standard display then re-appears.
Logamatic EMS RC35 user interface - Subject to technical modifications.
17
4
Basic operation
4.8 Setting functions for domestic hot water Risk of scalding from domestic hot water temperatures over 122 °F (50 °C)! WARNING: Risk of scalding! The factory setting for DHW temperature is 140 °F (60 °C). There is a risk of scalding at the taps if no thermostatic mixing valve is installed. B Make sure that a thermostatic mixing valve is installed and that it is set to temperatures below 122 °F (50 °C). WARNING: Risk of scalding! During the thermal disinfection process, the domestic hot water is heated to temperatures above 140 °F (60 °C). B Make sure that a thermostatic mixing valve is installed and that it is set to temperatures below 122 °F (50 °C).
What function? What is it for?
Operation Initial situation: the cover is closed.
Changing DHW temperature In the factory settings, hot water is available during the heating phases (day mode) of the selected program. The water in the hot water tank is heated once in the morning for 30 minutes before home heating starts. Tab. 5
18
B To change the DHW temperature: hold down the button and turn the dial at the same time. If you get a message saying that the setting is not possible: set the dial on the boiler control unit to “Aut”1).
Setting functions for domestic hot water
Logamatic EMS RC35 user interface - Subject to technical modifications.
Basic operation
4
What function? What is it for?
Operation
Heating up DHW once
button lights up, the DHW If the LED2) for the temperature has fallen below the set value. B To heat up the hot water manually: press the button. The LED on the button starts flashing2). The heating phase starts; it ends automatically as soon as the set temperature has been reached.
During day mode, domestic hot water is only reheated again automatically when its temperature has fallen by 9 °F (5 °C) below the set DHW temperature (to save energy). If you need large amounts of hot water after hours, you can heat up the hot water once again.
If no heating is necessary (because the water is still hot), a message will appear. Only the DHW recirculation pump will start up (if installed) to transport the hot water more quickly to the taps. B If you want to stop the heating process: press again.
Heating up DHW regularly
If you regularly need large amounts of hot water outside the set times for day mode, you can set a separate program for domestic hot water (Æ page 39).
Switching thermal disinfection on/off
B Set thermal disinfection (Æ page 45).
This function heats up the domestic hot water to a temperature sufficient to kill pathogens (e.g. legionella). Tab. 5
Setting functions for domestic hot water
1) The setting depends on the boiler used. 2) The “domestic hot water” LED may also have been deactivated by the heating contractor.
Logamatic EMS RC35 user interface - Subject to technical modifications.
19
4
Basic operation
4.9 Reviewing information (Info menu) You can use the Info menu to view set values and recorded values. The exact information available depends on the components installed in your heating system. Operation
Result
1.
Open the cover (by pulling the recessed grip on the left).
2.
Press
to open the INFO menu.
Turn the dial to
The display will show the message at right for five seconds. It then moves on automatically.
3.
-orTurn the dial
to move immediately to the next display.
Turn the dial
to view additional information.
obtain system information.
INFO\ROOM\HTG.ZONE 1 room temperature set: 68.9°F measured room temperature: 69.0°F
4.
To exit the Info menu: press the The standard display reappears.
Tab. 6
How to use the Info menu
button or close the flap.
DHW message in the Info menu DHW is switched off at the boiler. This message means that the dial is set to “0”. Set the dial
on the boiler controller
to “Aut”1). Set to allow water heating to be set from the RC35.
The operating mode buttons have no function in the Info menu.
1) Setting depends on the boiler used.
20
Logamatic EMS RC35 user interface - Subject to technical modifications.
Basic operation
4
Chart displays in the Info menu (outdoor temperature fluctuation and solar yield) The Info menu gives you the option of viewing graphs showing the fluctuation in outdoor temperature over the past two days and (if solar components are installed) the solar gyield. This way you have a clear overview allowing easy comparison of the relevant values. Both graphs are updated every 15 minutes and a new graph is started at 12:00 am (00:00) (midnight). Consequently, there will be no display available for the current day between 12:00 am and 12:14 am (00:00 and 00:14). The minimum and maximum values are updated progressively. Outdoor temperature curve (weather station) The temperature variation over the current and previous day is shown across two screens. The minimum and maximum values since midnight on the previous day are also shown. Solar yield 1) The solar yield display tells you how much the solar collector has contributed to domestic hot water heating. This is determined using the difference in temperature between the storage tank and the solar collector, together with the modulation of the solar pump. The solar yield is highly dependent on the installed system and its components and therefore cannot be expressed as a value in kWh. This means that the value displayed is a variable specific to this particular system, which cannot be easily compared with other solar heating systems. However it is suitable for comparing the yield on different days. This information is displayed as a graph for the previous and current day. The solar gain per day and also the weekly total is listed in a table: SOLAR YIELD THIS WEEK and also for the previous week: SOLAR YIELD LAST WEEK. In both cases the current day is indicated by a flashing dot. This value is updated every 15 minutes (also in the graph for the “current day”) and the total is saved at 12:00 h (midnight) as the value for the relevant day. The daily values for the current week (Mo-Su) are also added up every 15 minutes. The days in the current week which still have not passed are marked with “---”. At days where the solar yield could not be determined “0” is displayed.
SOLAR YIELD THIS WEEK Mo: 10 Fr: --Tu: 115 Sa: --We: 53 Su: --Th: --- Mo-Su: 178
SOLAR YIELD LAST WEEK Mo: 10 Fr: 75 Tu: 0 Sa: 102 We: 15 Su: 125 Th: 0 Mo-Su: 327
1) This function depends on the boiler in use.
Logamatic EMS RC35 user interface - Subject to technical modifications.
21
4
Basic operation
4.10 Messages on the display The controls will display a message if, for example, a particular setting is not available under current circumstances. When the display shows “continue with any key”: B Press any of the buttons to confirm and close the message.
continue with any key
4.11 Shut-down/switching OFF The RC35 user interface is supplied with power via the heating system and is permanently switched on. It is only switched off if the heating system is switched off, such as for maintenance purposes. B To switch the heating system on or off: set the ON / OFF switch on the boiler to position 1 (ON) or 0 (OFF). After switching the unit OFF or in the event of a power failure, the date and time are retained for up to 8 hours. All other settings are retained permanently.
22
Logamatic EMS RC35 user interface - Subject to technical modifications.
User menu
5
5
User menu
5.1 Introduction to the User menu The User menu allows you to enter certain settings. The procedure for operation is always the same: 1. 2. 3. 4. 5.
Open the cover (by pulling the recessed grip on the left). Press to open the USER MENU. Turn the dial to change the selected item (marked with). Press to make your selection. To change the value, hold down the button (the value starts flashing) and turn the dial at the same time. Release the button: the changed value is saved. 6. Press the button to go back one step -orpress the button several times or close the cover to return to the standard display. Example: Setting operating mode continuous heating for heating zone 1 Operating Instructions 1.
Open the cover (by pulling the recessed grip on the left).
2.
Press
to open the USER MENU.
Result
USER MENU
Bstandard display modes of operation program WWSD temperature
3.
Turn the dial to the left until modes of operation is selected (marked with).
USER MENU standard display
Bmodes of operation program WWSD temperature
Tab. 7
How to use the User menu (example)
Logamatic EMS RC35 user interface - Subject to technical modifications.
23
5
User menu
Operating Instructions 4.
Press
Result
to confirm the selection.
The USER\OPERATING MODE menu is opened. The appearance of the display depends on the number of heating zones. If there is only one heating zone installed with no DHW and no DHW recirculation pump, this screen will not appear at all (Æ page 26).
USER\OPERATING MODE
Bheating zone 1 heating zone 2 heating zone 3 domestic hot water
Continue to the next step. 5.
Press
to select heating zone 1.
OPERATING MODE\HZ 1 Which operation mode should be used? automatic
6.
To change the value, hold down the button (the value starts flashing) and turn the dial at the same time.
OPERATING MODE\HZ 1 Which operation mode should be used? automatic
7.
Release the
button.
OPERATING MODE\HZ 1
The value stops flashing. The modified value is saved.
Which operation mode should be used? continuous heating
8.
If you have carried out this example as practice only, make sure that the original setting is retained. To do so, repeat steps 6 and 7 if necessary.
OPERATING MODE\HZ 1 Which operation mode should be used? automatic
9.
Press
to go back one step.
-orTo finish entering the settings: press several times or shut the cover. The standard display appears again. You can enter all settings in the USER MENU using this procedure. Tab. 7
24
How to use the User menu (example)
Logamatic EMS RC35 user interface - Subject to technical modifications.
User menu
5
5.2 Overview of the User menu The User menu is divided into the following menu items: Menu item
Purpose of the menu item
standard display
Selecting the standard display
29
modes of operation
Setting the operating mode for all installed heating zones (automatic, continuous heating, permanently setback); also possible for the “DHW” and “DHW circulation” heating zones
29
program
Switching between day mode and night mode at defined times and on defined days of the week (only active in automatic mode); separate programs possible for DHW and DHW circulation
31
WWSD temperature
Switching automatically between summer mode and heating mode (triggered by temperature)
40
DHW temperature
Set the DHW temperature.
40
vacation
Interrupting the set program when on vacation (to save energy if away or to ensure comfort if at home)
41
party program
Temporary extension of day mode for a certain amount of time
44
pause function
Temporary interruption of day mode for a certain amount of time (when absent) 44
therm. disinfection1)
Heating up domestic hot water to kill potential pathogens
45
corrected room tmp.
Calibrate displayed room temperature with the help of a thermometer.
45
Tab. 8
Page
User menu
1) This function depends on the boiler in use.
Logamatic EMS RC35 user interface - Subject to technical modifications.
25
5
User menu
5.3 Heating zone selection If your heating system is equipped with more than one heating zone: before entering some settings, you will need to select the heating zone(s) to which the settings apply. Only the heating zones actually installed will be displayed: Heating zone selection
Meaning
Heating zone 1
Heating zone without mixing valve
From heating zone 21)
Heating zones with mixing valve, i. e. with reducible flow temperature
RC35 heating zones
All heating zones assigned to the RC35, i.e. those that do not have their own remote control unit (Æ Fig. 2, [1]). Displayed only if more than one heating zone is assigned to the RC35.
DHW
Hot water supply that is controlled by the RC35
Hot water recirculation1)
DHW recirculation pump that is controlled by the RC35
Solar1)
Solar heating system, if installed
Complete system
All heating zones, DHW, DHW recirculation pump, and solar
Tab. 9
Heating zones that could be installed in your heating system
1) This function depends on the boiler in use.
Recommended: if more than one heating zone is installed, it is usually recommended to select RC35 heating zones.
If there is only one heating zone installed with no DHW, no DHW recirculation pump and no solar heating system, heating zone selection is not available. Heating zone selection is not available with some boilers.
26
Logamatic EMS RC35 user interface - Subject to technical modifications.
User menu
5
What is a heating zone? A heating zone describes the route taken by the heating water from the boiler to the radiators and back to the boiler. Multiple heating zones can be connected to one boiler; for example, one heating zone for panel radiators or baseboard and another heating zone for radiant floor heating. In this case, the radiators are supplied at a higher supply temperature than the radiant floor heating system. The supply temperature is the heating water temperature, generated by the boiler, as it is supplied to the heating zone. With the RC35 user interface, you can operate and control multiple heating zones (Æ Fig. 2).
HZ1
HZ2
Fig. 2
Options for a heating system with two heating zones
Logamatic EMS RC35 user interface - Subject to technical modifications.
27
5
User menu
Names of the heating zones in the example in Fig. 2 When you enter settings for a particular heating zone, you first need to select it from the list. You will then be asked to choose from a list of names as shown in Tab. 10. Different temperatures for the heating zones (Æ Tab. 10, b) can also be entered using the RC35 user interface without a remote control unit, if your heating contractor has set it accordingly. In that case, the room temperatures for the separate heating zone can be set via the User menu (Æ page 38).
a b
For heating zone 1+2: Factory setting Different room temperatures are possible 2)
Names of the heating zones on the display HZ1+HZ2 = RC35 heating zones 1) HZ1 = RC35 heating zones HZ2 = heating zone 2
Set the room temperature page 14 – 16 HZ1: page 14 – 16 HZ2: page 16 or 38
Tab. 10 Names of the heating zones in the example in Fig. 2 1) Heating zone selection is not possible if there are no other heating zones available, such as DHW for example. 2) Here: setting by heating contractor HZ1 = RC35, HZ2 = none
28
Logamatic EMS RC35 user interface - Subject to technical modifications.
User menu
5
5.4 Adjusting the standard display This menu item can be used to select the information to be displayed as the default in the upper row of the display screen (the “standard display”). 1. Open the User menu. 2. Select standard display. You can choose from the following standard displays: – date + time (factory setting) – outdoor temperature (recorded outdoor temperature) – boiler temperature (recorded boiler temperature, supply temperature) – DHW temperature (in hot water storage tank) – collector temperature (with solar heating systems only)
5.5 Selecting the operating mode 5.5.1 Operating modes for RC35 heating zones For the RC35 heating zones, the operating mode can be set directly by pressing the corresponding button (e.g. ). For other heating zones, use this menu item. 1. Open the User menu. 2. Select modes of operation. 3. If your heating system is equipped with more than one heating zone (Æ page 26): select the desired heating zone and confirm. 4. Set the operating mode for the selected heating zone: – automatic (program) – continuous heating (manual day mode) – permanently setback (manual night mode) For more information on the operating modes, refer to page 13. If there is only one heating zone installed and no DHW, heating zone selection is not possible.
Logamatic EMS RC35 user interface - Subject to technical modifications.
29
5
User menu
5.5.2 Modes of operation for DHW You can set one of the following operating modes for your hot water supply: • automatic (program) This can be either the program for central heating or a specific DHW program (Æ page 39). • permanent ON (manual continuous mode). The hot water is permanently maintained at the set temperature. • permanent OFF (manual night mode). You can use the button to start DHW heating when needed (“Heating up DHW once”, Æ page 19). 5.5.3 Operating modes for DHW circulation1) The DHW recirculation pump ensures quick supply of hot water to the taps (if installed). This is achieved by circulating the hot water once or more per hour through the DHW recirculation pump via a separate recirculation pipeline. The recirculation interval (the number of times per hour) can be adjusted by your heating contractor in the Service menu. You can set one of the following operating modes for DHW circulation: • automatic: 30 minutes before the first heating zone is switched on, the DHW recirculation pump starts to run at the set interval, and stops when the last heating zone is switched off (factory setting). Alternatively, you can set a separate circulation program (Æ page 39). • permanent ON: The DHW recirculation pump runs constantly at the set interval, regardless of the heating zones. • permanent OFF: The DHW recirculation pump is not run at a set interval. You can use the button to heat up the DHW and start DHW circulation when needed. 5.5.4 Operating modes for solar • automatic (default setting) • permanent OFF (manually switched off) • permanent ON (manual constant operation). The solar heating system will be in constant operation for 30 minutes at maximum pump output. After 30 minutes the solar heating system automatically switches back to automatic mode. The solar pump is controlled manually in “constant operation” operating mode; however, the solar heating system will cut out if either the collector array or the solar tank exceed their maximum permissible temperature (collector protection function). For explanations of the settings, see the documentation for the solar module.
1) Menu is always displayed, the function depends on the boiler in use.
30
Logamatic EMS RC35 user interface - Subject to technical modifications.
User menu
5
5.6 Setting the program The automatic mode ensures automatic switchover between day and night mode at defined times of day. In the factory setting, 70 °F (21 °C) is set for day mode, and 63 °F (17 °C) for night mode. Before you select a program (i.e. a heating program), consider the following: • At what time in the morning should your home be warm? Does this time vary depending on the day of the week? • Are there days when you do not need your home to be heated during the day? • From what time in the evening does your home no longer need to be heated? This too may vary depending on the day of the week. 1. Open the User menu. 2. Select program. 3. If your heating system is equipped with more than one heating zone (Æ page 26): select the desired heating zone and confirm. A separate program can be set for each heating zone. You will then see the following options to choose from: – select program (Æ page 32) – show current prog. (Æ page 35) – change switch point (Æ page 35) – enter switch point (Æ page 36) – delete switch point (Æ page 37) – room temperatures (Æ page 38, not possible for DHW, DHW circulation and solar heating zones) 4. Recommended: Use the select program option to select the program which best corresponds to your lifestyle. 5. If the standard program needs to be adjusted: change, insert or delete individual switch points. -or6. If you want to create a completely new program: select program and set a new program. The enter switch point menu item (Æ page 36) opens automatically for you to create your program. In the factory setting, the program also determines the times for DHW heating and the operation of the DHW i.e. circulation pump. However, you can also set separate programs for both functions (Æ sections 5.7 and 5.8).
Logamatic EMS RC35 user interface - Subject to technical modifications.
31
5
User menu
5.6.1 Select program Here you can select and activate a program. This can be one of the pre-set standard programs (Æ Tab. 11, page 33) or one created or modified by you. You can save and later select two new or modified programs as custom 1 or custom 2. Selecting a pre-set program: 1. Hold down the button and turn the dial to select and activate a program. 2. Press to return to the list of options. 3. To view the selected program as a graph, select show current prog. (Æ page 35). -or4. Press several times or shut the cover to return to the default display. Creating a new program: B Select new program. The enter switch point menu item (Æ page 36) opens automatically for you to create your program.
32
Logamatic EMS RC35 user interface - Subject to technical modifications.
User menu
5
Switch-on and switch-off points in the standard programs Program
Day
ON
OFF
family
Mo–Th
5:30 am
10:00 pm
ON
OFF
(05:30)
(22:00)
Fr
5:30 am
11:00 pm
(05:30)
(23:00)
Sa
6:30 am
11:30 pm
(06:30)
(23:30)
Su
7:00 am
10:00 pm
(07:00)
(22:00)
Mo–Th
4:30 am
10:00 pm
(04:30)
(22:00)
Fr
4:30 am
11:00 pm
(04:30)
(23:00)
Sa
6:30 am
11:30 pm
(06:30)
(23:30)
Su
7:00 am
10:00 pm
(07:00)
(22:00)
Mo–Fr
4:30 am
11:00 pm
(04:30)
(23:00)
Sa
6:30 am
11:30 pm
(06:30)
(23:30)
Su
7:00 am
11:00 pm
(07:00)
(23:00)
Mo–Th
5:30 am
8:30 am
12:00 am
10:00 pm
(05:30)
(08:30)
(12:00)
(22:00)
Fr
5:30 am
8:30 am
12:00 pm
11:00 pm
(05:30)
(08:30)
(12:00)
(23:00)
Sa
6:30 am
11:30 pm
(06:30)
(23:30)
Su
7:00 am
10:00 pm
(07:00)
(22:00)
Mo–Th
6:00 am
10:00 pm
4:00 pm
10:00 pm
(06:00)
(22:00)
(16:00)
(22:00)
(factory setting)
early morning (early shift work)
evening (late shift work)
morning (part-time work, mornings only)
afternoon (part-time work, afternoons only)
Fr
6:00 am
3:00 pm
11:00 pm
(06:00)
(15:00)
(23:00)
Sa
6:00 am
Su
7:00 am
ON
OFF
(06:00) (07:00)
Tab. 11 Standard programs (ON = day mode, OFF = night mode)
Logamatic EMS RC35 user interface - Subject to technical modifications.
33
5
User menu
Program
Day
ON
OFF
ON
OFF
ON
OFF
midday
Mo–Th
6:00 am
8:00 am
11:30 am
1:00 pm
5:00 pm
10:00 pm
(06:00)
(08:00)
(11:30)
(13:00)
(17:00)
(22:00)
Fr
6:00 am
8:00 am
11:30 am
11:00 pm
(06:00)
(08:30)
(11:30)
(23:00)
Sa
6:00 am
11:00 pm
(06:00)
(23:00)
Su
7:00 am
10:00 pm
(07:00)
(22:00)
Mo–Th
6:00 am
10:00 pm
4:00 pm
10:00 pm
(06:00)
(22:00)
(16:00)
(22:00)
(at home at midday)
single person
Fr
6:00 am
3:00 pm
11:00 pm
(06:00)
(15:00)
(23:00)
Sa
7:00 am
Su
8:00 am
Mo – Su
5:30 am
10:00 pm
(05:30)
(22:00)
(07:00) (08:00) senior citizens
new program If you select new program, you can use the enter switch point option to create a new program. You can save and later select two new or modified programs as custom 1 or custom 2. custom 1
Mo–Th Fr Sa Su
custom 2
Mo–Th Fr Sa Su
Tab. 11 Standard programs (ON = day mode, OFF = night mode)
34
Logamatic EMS RC35 user interface - Subject to technical modifications.
User menu
5
5.6.2 Viewing the current program You can use show current prog. to view the currently set program in the form of a graph (Æ Fig. 3). • The graph always shows the program for one day or block of days. • The current switch point will flash (circle and cross alternately). Below the graph, you can see the time for that switch point and the temperature that applies from that time onwards. • Other switch points are marked with a cross.
3 2 1
PROGRAM HZ1\ENTER 70
4
63 Mo
5:30am
70°F
5 6 720 640 225-02.1RS
Fig. 3 1 2 3 4 5
Example from the “morning” program Day temperature and night temperature Orientation row Switch-on points (switchover to day mode) Switch-off points (switchover to night mode) Row showing status and settings for the selected switch point
1. Turn the dial . The next switch point is displayed. 2. Turn the dial further to display the other days. 3. Press to return to the list of options. 5.6.3 Changing a switch point You can use change switch point to change the times in a program at which the system switches over to a different temperature level. 1. Turn the dial to select a different switch point. Turn it further to go to a different day of the week. The selected switch point starts flashing. 2. Hold down the button and turn the dial to change the time for that switch point.
Logamatic EMS RC35 user interface - Subject to technical modifications.
35
5
User menu
3. If desired: hold down the button and turn the dial to change this switch point from a switchoff point to a switch-on point or vice versa. 4. Repeat steps 1 to 3 to change other switch points. 5. Press when you have finished making entries. If you have changed the program and then do not press any button for 5 minutes, the system assumes you have finished making entries and goes on to the next step. 6. Hold down the button and turn the dial to save the modified program as custom 1 or custom 2 or select not saved to cancel. The selected program, custom 1 or custom 2, is used from now on for that heating zone. If you want to set switch points for a block of days (Mo-Th, Mo-Fr, Mo-Su, Sa-Su), select select program\new program.
5.6.4 Entering a switch point You can use enter switch point to add additional switch points for a heating phase or energysaving phase (day/night mode, respectively) or create a new program. You can enter switch points separately for each day. The minimum time between switch points is 10 min (period for which the zone is switched ON or OFF). For each switch-on point ([1], day mode), you also need to enter a switch-off point ([2], night mode) so that the heating will switch back to night mode again.
PROGRAM HZ1\ENTER 70
The maximum number of switch points is 42 per heating zone.
1 2
63 Mo
**:**
****
1. Turn the dial to select the day of the week. 2. Hold down the button and turn the dial to change the time for that switch point. The switch point will flash on the graph until it has been entered completely. 3. Hold down the button and turn the dial to specify whether the point is a switch-off point or a switch-on point. Once the switch point has been entered completely, all the values flash for three seconds. The switch point can still be changed during this time. Press when you have finished making entries. After that the switch point is saved. 4. Repeat steps 1 to 3 to enter other switch points. 5. Turn the dial to go to other days. 6. Press when you have finished making entries.
36
Logamatic EMS RC35 user interface - Subject to technical modifications.
User menu
5
If you have changed the program and then do not press any button for 5 minutes, the system assumes you have finished making entries and goes on to the next step. 7. Hold down the button and turn the dial to save the modified program as custom 1 or custom 2 or select not saved to cancel. The selected program, custom 1 or custom 2, is used from now on for that heating zone. 5.6.5 Deleting set point Turn the dial to select a different switch point.You can use delete switch point to delete switchover phases that you do not need. Make sure that you always delete two switch points for every switchover phase (the switch-ON point and the switch-OFF point) to ensure that the heating switches back to night mode again. 1. Turn the dial to select a different switch point. The selected switch point starts flashing. 2. Press when you have finished making entries. Hold down the button and turn the dial to yes. The switch point is deleted. 3. Turn the dial to go to other days. 4. Press when you have finished making entries. If you have changed the program and then do not press any button for 5 minutes, the system assumes you have finished making entries and goes on to the next step. 5. Hold down the button and turn the dial to save the modified or new program as custom 1 or custom 2 or select not saved to cancel. The selected program, custom 1 or custom 2, is used from now on for that heating zone.
Logamatic EMS RC35 user interface - Subject to technical modifications.
37
5
User menu
5.6.6 Setting room temperatures The room temperatures menu item is only available for heating zones without a remote control unit (the first case below). In the other two cases, the room temperatures menu item is not displayed. Possible case scenarios: • Heating zones without remote control (Æ page 54, setting “none”): different room temperatures are possible for each zone, in contrast to the RC35 heating zones. The room temperature is set as described below. • RC35 heating zones: the room temperatures are the same for all heating zones assigned to the RC35. For the RC35 heating zones, you need to set the room temperature using the button, not in the User menu (Æ page 16). If “shut-down mode” is selected as the night setback mode, the heating system will be switched OFF at night. A night room temperature cannot be set. The display will show a message to that effect. Setting room temperatures with User menu\program Here you can set the room temperature for the heating zone previously selected in the program. 1. 2. 3. 4.
Open the User menu. Select program. Select the heating zone (Æ page 26 – 28). Select room temperatures. CAUTION: Risk of system damage due to freezing. If room temperatures are set below 41 °F (5 °C), rooms may cool down so much that pipes in external walls (for example) may freeze in cold weather. B Set room temperatures higher than 10 °C.
5. Set the desired room temperature. 6. Turn the dial to switch between the temperatures for day and night mode.
38
Logamatic EMS RC35 user interface - Subject to technical modifications.
User menu
5
5.7 Setting a DHW program In the setting by heating zone (factory setting), the switch-ON and switch-OFF times for hot water heating follow those of the selected program. This ensures that hot water is available during the heating phases (i.e. when in day mode). If you want to enter a separate hot water program, Buderus recommends: • Heating the hot water tank only once in the morning before home heating starts. • Possibly also programming another heating phase in the evening if more hot water is regularly needed at that time. This would allow you to significantly reduce your energy consumption even further. To set a hot water program that is independent of the heating phases: 1. Open the User menu. 2. Select program. 3. Select the domestic hot water heating zone. 4. Adjust the program with change switch point, enter switch point or delete switch point (Æ page 35) or enter a new program. 5. Save the program as custom 1 or select not saved to cancel. 6. Check that automatic is set for operating mode\DHW to make sure that the program you have set is also active (Æ page 30). If you occasionally need more hot water outside the set time, you can activate hot water heating for a short time (“Heating up DHW once”, Æ page 19).
5.8 Setting the DHW circulation program1) You can use a DHW circulation program to enter the switch-ON and switch-OFF times for the DHW recirculation pump independently of the program for the heating system. Follow the same procedure as for entering a DHW program (Æ section 5.7).
1) This function depends on the boiler in use.
Logamatic EMS RC35 user interface - Subject to technical modifications.
39
5
User menu
5.9 Setting the warm weather shutdown (WWSD) temperature Requirements: An outdoor temperature sensor must be installed. The heating system is controlled by the outdoor temperature (with or without influence from room temperature: Æ page 47). In the case of room temperature control, the WWSD temperature menu is not displayed. When the outdoor temperature falls below this adjustable threshold, the heating system automatically switches over to winter mode (heating on). Make sure that the automatic mode is active. 1. Open the User menu. 2. Select WWSD temperature. 3. If your heating system is equipped with more than one heating zone (Æ page 26): select the desired heating zone and confirm. 4. To save energy in spring and autumn: lower the switchover threshold (factory setting: 63 °F (17 °C)). 5. To heat your home more comfortably in spring and autumn: increase the switchover threshold. If you occasionally feel too warm or too cold, you can also make use of the manual mode (Æ page 14).
The heat storage capability of the building is also taken into consideration and utilized during the switchover. Since the temperature in your home falls gradually, you may find that the heating system does not switch over to winter mode until some time after the outdoor temperature has dropped below the switchover threshold.
5.10 Setting the daylight savings time changeover There is no automatic summer/winter time change. Adjust the time as shown on page 17.
5.11 Set the DHW temperature The domestic hot water (DHW) temperature is the target water temperature in the hot water storage tank. WARNING: Risk of scalding! The factory setting for DHW temperature is 140 °F (60 °C). There is a risk of scalding at the taps if no thermostatic mixing valve is installed. B Make sure that a thermostatic mixing valve is installed and that it is set to temperatures below 122 °F (50 °C).
40
Logamatic EMS RC35 user interface - Subject to technical modifications.
User menu
5
1. Open the User menu. 2. Select DHW temperature. 3. Set the desired hot water temperature (factory setting: 140 °F (60 °C)). You can also enter the same setting without going through the User menu: B Hold down the button and turn the dial at the same time.
If you get a message saying that the setting is not possible: set the dial BC10 boiler control unit to “Aut”.
on the
5.12 Setting vacation mode Use the vacation mode to run the heating system differently from the normal program when on vacation. You can only set one vacation period at a time. 1. Open the User menu. 2. Select vacation. 3. Select the heating zone to be switched over to vacation mode: – complete system: heating zones, water heating and DHW circulation. – RC35 heating zones: this option is only displayed if one or more heating zones are assigned to the RC35; DHW and the other heating zones remain active. – Individual heating zones: only heating zones that are not assigned to the RC35 will be displayed; in other words, those that have their own remote control unit or that have no remote control unit. 4. Setting at home or away from home (absent): – absent: Heating is operated at a reduced, adjustable vacation temperature (setback mode). If complete system was selected in the previous step, DHW heating and DHW circulation will be shut down. If only some heating zones are in vacation mode, DHW heating and circulation remain active (Æ Tab. 12, page 43). – at home: Heating and hot water are available every day as on a normal Saturday. 5. Set the year, month and day for the first day of the vacation period, one after the other. Vacation mode starts at 12:00 am on the first day. 6. Press . The year starts flashing. 7. To set the year: hold down the button and turn the dial at the same time. 8. Release the button. The year is saved. 9. Repeat steps 6 to 8 twice to set the month and day. The start date of the vacation period has now been set.
Logamatic EMS RC35 user interface - Subject to technical modifications.
41
5
User menu
10.Turn the dial to the right to set the end date of the vacation period. 11.Set the end date of the vacation period by following steps 6 to 9. With absent, set the first day for normal operation (i.e. the day you return home) as the end date, so that your home is warm again when you return. With at home, set the last day of your vacation as the end date. 12.For absent only: turn the dial clockwise to set the temperature for the vacation period (factory setting 63 °F (17 °C)). Vacation mode has now been completely set. 13.Close the cover to conclude the setting procedure. During the vacation period, the end date is displayed when the cover is opened. During absent vacation mode, you can change the temperature simply by turning the dial. The cover must be closed when you do so. If you want to exit the vacation mode early: B Open User menu\vacation again. B Answer the question Continue cancelling the vacation mode? with yes.
42
Logamatic EMS RC35 user interface - Subject to technical modifications.
User menu
5
Domestic hot water (DHW)
Vacation set as absent: complete system absent: individual heating zones (HZ)
DHW program as per heating zones (factory setting) Vacation mode (DHW off)
If all HZ set to vacation: vacation mode (DHW off) If at least one HZ not set to vacation: no vacation mode3) absent: Same as complete program for system Saturdays at home: If all HZ set to individual vacation mode: heating same as zones (HZ) program for Saturdays3) If at least one HZ not set to vacation: no vacation mode3)
Separate DHW program (page 39)
DHW recirculation pump (CP)1) DHW program as per heating Separate zones and no DHW custom CP program program 2) (page 39) and Separate CP (factory no separate program setting) CP program2) (page 39) Vacation mode (CP off)
No vacation mode
If all HZ set to vacation: vacation mode (CP off) If at least one HZ not set to vacation: no vacation mode3) Same as DHW Same as program for program for Saturday 3) Saturdays No vacation If all HZ set to mode vacation mode: same as program for Saturdays3) If at least one HZ not set to vacation: no vacation mode3)
No vacation mode
No vacation mode
Same as DHW program for Saturdays3) No vacation mode
Same as CP program for Saturdays No vacation mode
Tab. 12 Functioning of DHW heating (DHW) and recirculation pump (CP) in vacation mode 1) This function depends on the boiler in use. 2) No separate program was created for the recirculation pump, that is, the switching times of the recirculation pump and of the DHW program are the same. 3) The earliest switch-on point and latest switch-off point out of all heating zones on this day will apply.
Logamatic EMS RC35 user interface - Subject to technical modifications.
43
5
User menu
5.13 Setting the party mode You can use the party program (extension of period of use) to postpone the time when your heating system normally switches to night mode (as defined in the program) to a later time. This means your home will be heated for longer in day mode (continuous heating) if you want to stay up later than usual in the evening. 1. Open the User menu. 2. Select party program. 3. If your heating system is equipped with more than one heating zone (Æ page 26): select the desired heating zone and confirm. 4. Hold down the button and turn the dial at the same time to set the number of hours (0 to 99) for your home to be heated in day mode. The party mode is now active. The remaining duration is shown on the display. When the time has expired, it will return to the automatic mode. Ending the party mode early: B Open USER MENU\party program again and select end. Instead of making the setting via the User menu, you can use the following short cut: B Press and hold down the button. B Open flap. B Turn the dial at the same time to set the number of hours (0 to 99).
5.14 Setting the pause function You can use the pause function (heating pause) to switch your heating to night mode (permanently setback) for a certain period, regardless of the current program, when you are away from home, for example. Once this period has elapsed, normal operation is automatically resumed as defined in the program. 1. Open the User menu. 2. Select pause function. 3. If your heating system is equipped with more than one heating zone (Æ page 26): select the desired heating zone and confirm. 4. Hold down the button and turn the dial at the same time to set the number of hours (0 to 99) for heating to be reduced. The pause function is now active. When the time has expired, it will return to the automatic mode. Ending the pause function early: B Open USER MENU\pause function again and select end.
44
Logamatic EMS RC35 user interface - Subject to technical modifications.
User menu
5
Instead of making the setting via the User menu, you can use the following short cut: B Press and hold down the button. B Open flap. B Turn the dial at the same time to set the number of hours (0 to 99).
5.15 Setting thermal disinfection If this function1) is activated, the DHW is heated once a week or once a day to a temperature sufficient to kill pathogens (e.g. legionella). WARNING: Risk of scalding from hot water at the taps. During the thermal disinfection process the DHW can be heated to a temperature above 140 °F (60 °C). B After thermal disinfection, mix in cold water with an open hot water tap. 1. Open the User menu. 2. Select therm. disinfection. 3. Set yes or no. If thermal disinfection is switched on: 4. Set the temperature to which the hot water should be heated during disinfection (factory setting:158 °F (70 °C)). 5. Set the day of the week (factory setting: Tuesday). 6. Set the time (factory setting: 1:00 am (01:00); can only be started on the hour).
5.16 Calibrating the room temperature display If there is a separate thermometer near the RC35 when installed in the living space, it may show a different room temperature to that shown on the unit. If you wish to adjust the RC35 to match the thermometer (i.e. “calibrate” the RC35) , you can use the corrected room tmp. function. Before calibrating the room temperature, consider the following: • Is the thermometer more accurate than the RC35? • Is the thermometer located close to the RC35 so that they are both subject to the same heat influences (e.g. sunlight, fireplace)?
1) The function depends on the boiler in use.
Logamatic EMS RC35 user interface - Subject to technical modifications.
45
5
User menu
A thermometer may indicate temperature fluctuations more slowly or rapidly than the RC35. B so never calibrate the RC35 when your heating system is in the process of cooling down or heating up. 1. Open the User menu. 2. Select corrected room tmp. 3. Select Calibrating the room temperature: The factory setting is 0 °F (0 °C). Example: if the thermometer is showing a temperature 1.8 °F (1.0 °C) higher than the user interface, enter “+1.8 °F (+1.0 °C)” as the calibration value. The result will be displayed immediately as the corrected room temperature.
46
Logamatic EMS RC35 user interface - Subject to technical modifications.
Information for setting the RC35
6
6
Information for setting the RC35
6.1 Control modes for the heating system The heating system has three different control modes. Your heating contractor will select one according to your requirements and will set it up for you: • Outdoor temperature control (weather-dependent control): the outdoor temperature is recorded by means of a temperature sensor. The level of the supply temperature is calculated solely on the basis of the outdoor temperature in accordance with the characteristic heating curve. You can set the room temperature for the entire home on the controls (which will push the heating characteristic curve up or down). If you have the thermostatic radiator valves installed, adjust them in every room so that the desired temperature is reached in each room. • Room temperature control: in this case, the RC35 must be mounted in a room that is representative of your home. The RC35 records the room temperature in this “reference room”. Control of the supply temperature is determined by the set room temperature and the recorded room temperature. This means that external temperature influences in the reference room (e.g. an open window, sunlight or heat from a fireplace) can have an effect on the entire home. Set the room temperature for the home/reference room on the RC35. You can produce higher or lower temperatures in the other rooms by adjusting the thermostatic radiator valves (if installed) or flow balancing valves. • Outdoor temperature control influenced by room temperature: With this control mode the supply temperature is primarily determined by the outdoor temperature, but it is also partly determined by the room temperature, to an extent set by your heating contractor. For room temperature control and for outdoor temperature control influenced by room temperature: If installed, the thermostatic radiator valves in the “reference room” (the room where the RC35 is mounted) must be completely open. Control of the supply temperature is determined by the room temperature recorded there. It must never be limited by closed thermostatic values.
Logamatic EMS RC35 user interface - Subject to technical modifications.
47
6
Information for setting the RC35
6.2 Tips for energy efficiency • You can save around 6 % on your heating costs by reducing the daytime room temperature by 2 °F (1 °C). • Only heat if you need warmth. Use the program for automatic night setback. • Ventilate your home wisely: Leave the windows wide open for a few minutes rather than leaving them slightly open all the time. • While ventilating rooms, set the RC35 to night mode. Do this by pressing the night button. • Have drafty windows and doors sealed or replaced. • Never position large objects such as a sofa immediately in front of radiators or baseboard (maintain a clearance of at least 20" (50 cm)). Otherwise, the heated air cannot circulate and heat the room adequately. • You can also increase the energy efficiency of your hot water supply: compare the times when you want your rooms to be warm with the times when you need hot water. It may be practical to use a separate program for DHW heating. • Arrange with your local heating contractor to have your heating system serviced annually. A clean and properly adjusted boiler uses fuel most efficiently and promotes a longer service life.
48
Logamatic EMS RC35 user interface - Subject to technical modifications.
Troubleshooting
7
7
Troubleshooting
This chapter contains frequently asked questions about your heating system and their answers. This will in many cases enable you to troubleshoot perceived faults. At the end of the chapter there is a table listing faults and corresponding remedies.
7.1 Frequently asked questions Why do I need to set a room temperature even though it is not recorded? When you set a room temperature – even if room temperature is not recorded, as is the case when heating is controlled by outdoor temperature – you are changing the characteristic heating curve. That changes the room temperature, because the temperature of the boiler water changes and with it the temperature of the radiators, baseboard or radiant floor heating.
Why does a separate thermometer not match the room temperature set in the RC35? Various different factors influence the room temperature. If the RC35 is installed on a cold wall, it will be influenced by the cold temperature of that wall. Conversely, it will be influenced by the heat from a fireplace or chimney, if it is installed in a warm part of the room. If you would like to compare the recorded room temperature with the measurement values of another thermometer, the following is important: • The separate thermometer and the user interface must be physically close to each other. • The thermometer must be accurate. • When comparing, do not measure the room temperature when the heating system is in the process of heating up, as the two devices may react at different speeds to the change in room temperature. If you have followed these instructions and you can still detect a discrepancy, you can now calibrate the room temperature display (Æ page 45).
Why do the radiators get (too) hot although the outdoor temperature is relatively high? If you have a heating system with a heating zone and no mixing valve (heating zone 1), this is normal. The pump only starts up when the boiler reaches a predefined supply temperature. If the supply temperature is higher than required based on the outdoor temperature, the radiators may get hotter for a short time. The heating control detects this and responds accordingly after a short time. Do not adjust the thermostatic valves if installed on the radiators or the room temperature on the RC35, and wait until the set room temperature is reached. Even in summer mode, the radiators may be heated for a short time under specific circumstances: namely when the pump is started up automatically at a predefined interval, to prevent it from “seizing up” (jamming). If the pump happens to be started up immediately after DHW heating, the unusable residual heat is dissipated via the heating zone and the radiators.
Logamatic EMS RC35 user interface - Subject to technical modifications.
49
7
Troubleshooting
Why does the pump run at night, even though the home is not being heated at all or only very little? This depends on the setting chosen by your heating contractor for night setback. • setback mode: even when the home is only being heated a little, the pump runs in order to achieve the set room temperature, even if low. • shut-down mode: the heating system (and therefore also the pump) is automatically shut down in night mode. If the outdoor temperature drops below the frost protection temperature, the pump is automatically switched on by the “Frost protection” function. • Outdoor setback mode and Room setback mode: The heating system is switched on automatically when the recorded temperature falls below the set value. The heating pump runs:
The recorded room temperature is higher than the set room temperature. Why is the boiler running anyway? The boiler may be heating the domestic hot water. The heating system has three different control modes (Æ page 47): • Room temperature control: the boiler shuts down when the set room temperature has been reached. • Outdoor temperature control: the heating system runs on the basis of the outdoor temperature. • Outdoor temperature control influenced by room temperature: the heating system uses the advantages of both of the above control modes. In the last two cases the boiler may run even if the recorded room temperature is higher than the set room temperature.
50
Logamatic EMS RC35 user interface - Subject to technical modifications.
Troubleshooting
7
7.2 Error messages and service messages The RC35 makes a distinction between three types of messages: • Faults (in boiler operation) • System errors (incorrect settings on the RC35, or component malfunctions) • Service messages (indicating that servicing is due) Faults The display shows the following message: Your system has a fault present. Please open the cover of the user interface. NOTICE: Risk of system damage due to freezing. The heating system can freeze up in cold weather if it has been disabled due to a fault shutdown. B Try to reset the fault. B If that is not possible, notify your heating contractor immediately. 1. Open the cover (by pulling the recessed grip on the left). The display may show the name and telephone number of your heating contractor if set to do so. 2. Turn the dial (several times if necessary, if there are multiple messages) to display the message and the code (in the last row on the display). 3. Check whether you can eliminate the fault yourself with a reset (Æ page 53). 4. Otherwise notify your heating contractor immediately (be sure to mention the message and code). Press or shut the cover to return to the default display. The faults depend on the specific type of boiler in use. Information about the faults can be found in the boiler documentation.
Logamatic EMS RC35 user interface - Subject to technical modifications.
51
7
Troubleshooting
System errors and service messages The display shows please open cover at the bottom of the display. The heating system will attempt to operate as much as possible; in other words, heating of the home can continue. 1. Open the cover (by pulling the recessed grip on the left). 2. Turn the dial . The display indicates whether there is a fault message (= system error) or a service message. The display may also show the name and telephone number of your heating contractor if set to do so. 3. Turn the dial (several times if necessary, if there are multiple messages) to display the message and the code (in the last row on the display). 4. Check whether you can deal with the message yourself with the aid of Tab. 13. Press or shut the cover to return to the default display. 5. Otherwise notify your heating contractor (be sure to mention the message and code). Press or shut the cover to return to the default display. Code
A01/ 816
A11/ 802 A11/ 803
Display Display is blank.
RC35 version: ... connect to: ... connecting... No communication with UBA/MC10 or DBA.
Time not set. Date not set.
Cause Remedy Your heating system is switched B Switch on the heating off. system. The power supply to the heating B Check that the RC35 is system has been cut off. correctly seated in its wall bracket. B Check that the cables are connected on the RC35 wall bracket. After start-up, data is transferred B Wait a few seconds. between EMS/UBA and the RC35 (no fault). Communication to EMS/UBA is B Check that the RC35 is faulty, possibly due to a loose correctly seated in its wall contact or electromagnetic bracket. interference, for example. B Check that the cables are connected on the RC35 wall bracket. Time and/or date settings are B Enter the time and/or date so missing. This may have been that the program and other caused by a lengthy power functions can work correctly. outage, for example.
Tab. 13 Table with plant errors and service messages
52
Logamatic EMS RC35 user interface - Subject to technical modifications.
Troubleshooting
Code Hxx
H7
Display please open cover
Water pressure too low.
7
Cause Servicing is required. The heating system remains active as long as possible. The water pressure in the heating system has fallen to a low level. This value is only displayed if your heating system is equipped with a digital pressure sensor.
Remedy B Notify your heating contractor to arrange for servicing. This is the only service message that you can remedy yourself. B Top up the heating water as described in the boiler operating instructions.
Tab. 13 Table with plant errors and service messages
“Code” column in Tab. 13 The messages are marked with codes. These codes help to inform your heating contractor about the cause. The codes are shown at the bottom of the display, on the left and right. Service messages are not displayed for some boilers.
7.3 Resetting faults (reset) Some faults can be rectified by resetting the system. This applies to locking faults, for example. Locking faults are those which cause the display on the boiler control panel to flash. Carry out the reset function on the boiler control panel to reset the fault. For instructions on carrying out the reset function on the boiler control panel, see the technical documentation for the boiler. B If the fault cannot be reset (the display continues to flash), notify your heating contractor.
Logamatic EMS RC35 user interface - Subject to technical modifications.
53
8
8
Setup log
Setup log
The setup log is to be filled out by your heating contractor during commissioning and is for your information. Heating zone assignment: Part of the house
Remote control unit (RC35, none1))
Heating zone 1 Heating zone 22) Heating zone 32) Heating zone 42) Tab. 14 Heating zone assignment 1) With the setting “none”, the heating zone can be controlled from the RC35, but is not included in the “RC35 heating zones” (room temperatures can therefore be set separately). 2) Not installed with several boilers.
54
Logamatic EMS RC35 user interface - Subject to technical modifications.
Setup log
8
Important settings for your heating system: Setting options Reduction mode (night)
Outdoor setback mode, Room setback mode, shut-down mode, setback mode
Control function (Æ page 47)
Outdoor temperature controlled (with/without room influence), room temp. controlled
Characteristic heating curve
Design day temperature: Minimum outdoor temperature: Offset:
Type of building
light, medium, heavy
Operating time of DHW recirculation pump1)
Permanent; 2 x, 3 x, 4 x, 5 x, 6 x per hour for three minutes each time
DHW priority
yes, no
Program (times Æ page 31)
Standard program name: custom program
Setting
Tab. 15 Settings made during commissioning 1) This function depends on the boiler in use.
Logamatic EMS RC35 user interface - Subject to technical modifications.
55
Index
Index A Automatic mode . . . . . . . . . . . . . . . . . . . 13, 29 Away from home. . . . . . . . . . . . . . . . . . . . . 8–9 C Calibrating room temperature . . . . . . . . . . . 45 Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 Continuous heating (manual day) . . . . 13, 29 Contrast on display . . . . . . . . . . . . . . . . . 9–10 Control modes for heating control . . . . . . . .47 Correcting displayed room temperature . . .45 D Date, setting . . . . . . . . . . . . . . . . . . . . . . . . .17 Day mode . . . . . . . . . . . . . . . . . . . . . . . . 13, 35 Day/night rhythm . . . . . . . . . . . . . . . . . . . 9–10 Default display . . . . . . . . . . . . . . . . . . . . . . . .29 DHW circulation (operating modes) . . . . . .30 DHW circulation program . . . . . . . . . . . . . .39 DHW temperature, setting . . . . . . . . . . . . . .18 DHW, heating up once . . . . . . . . . . . . . . . . .18 Disinfection, thermal . . . . . . . . . . . . . . . . . . .45 Display, explanation of . . . . . . . . . . . . . . . . .12 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 Domestic hot water (operating modes) . . .30 Domestic hot water messages in the Info menu . . . . . . . . . . . . . . . . . . . . . . .20 Domestic hot water program . . . . . . . . . . . .39 E Energy . . . . . . . . . . . . . . . . . 9, 11, 25, 39–40 - tips for energy efficiency . . . . . . . . . . . . .48 Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51 F Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51 Faults, resetting . . . . . . . . . . . . . . . . . . . . . . .53 Freezing . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 53 - faults in freezing conditions . . . . . . . . . . .51 Frost protection . . . . . . . . . . . . . . . . . . . . . . .50 G Getting started . . . . . . . . . . . . . . . . . . . . . . . . 9
56
H Heating zone - meaning . . . . . . . . . . . . . . . . . . . . . . . . . .27 - names in list of options for selection . . .28 Heating zone, selecting . . . . . . . . . . . . 26–28 Heating zones (operating modes) . . . . . . . . 29 I Info menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 M Manual day/night mode . . . . . . . . . . . . . . . . 13 Messages on the display . . . . . . . . . . . . . . . 22 N Night mode . . . . . . . . . . . . . . . . . . . . . . 13, 35 Nighttime reduction . . . . . . . . . . . . . . . . . . . 50 O Operating modes . . . . . . . . . . . . . . . . . 13, 29 - DHW circulation . . . . . . . . . . . . . . . . . . . 30 - domestic hot water . . . . . . . . . . . . . . . . . 30 - heating zones . . . . . . . . . . . . . . . . . . . . . . 29 - solar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Outdoor setback mode . . . . . . . . . . . . . . . . 50 Outdoor temperature control . . . . . . . . 47, 50 Outdoor temperature variation . . . . . . . . . . 21 Outdoor temperature, higher . . . . . . . . . . . . 49 P Party mode . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Pause function . . . . . . . . . . . . . . . . . . . . . . . 44 Permanently reduced (manual night) . 13, 29 Plant errors . . . . . . . . . . . . . . . . . . . . . . . . . . 52 Please open cover . . . . . . . . . . . . . . . . . . . . 52 Power failure . . . . . . . . . . . . . . . . . . . . . . . . . 22 Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 - DHW circulation . . . . . . . . . . . . . . . . . . . 39 - domestic hot water . . . . . . . . . . . . . . . . . 39 - selecting a program . . . . . . . . . . . . . . . . . 32 - setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 - viewing . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Logamatic EMS RC35 user interface - Subject to technical modifications.
Index
Q Quick reference guide . . . . . . . . . . . . . . . . . . 8 R RC35 heating zones . . . . . . . . . . . . . . .26–28 Reduced operation . . . . . . . . . . . . . . . . . . . 50 Reference room . . . . . . . . . . . . . . . . . . . . . . 47 Remote control unit . . . . . . . . . . . . . . . . . . . 27 Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Room setback mode . . . . . . . . . . . . . . . . . . 50 Room temperature - calibrating displayed temperature . . . . . 45 - changing permanently . . . . . . . . . . . . . . 15 - changing temporarily . . . . . . . . . . . . . . . 14 - different temperatures in heating zones . . . . . . . . . . . . . . . . . . . 28 - discrepancy in displayed temperature . . . . . . . . . . . . . . . . . . . . . . . 49 - setting . . . . . . . . . . . . . . . . . . . . . . . . 28, 38 - setting for particular heating zone . . . . . 16 - setting for particular heating zones . . . . 28 - too cool / too warm . . . . . . . . . . . . . . . . . . 8 Room temperature control . . . . . . . . . . 47, 50 S Safety instructions . . . . . . . . . . . . . . . . . . . . . 7 Service messages . . . . . . . . . . . . . . . . . . . . 52 Set the DHW temperature . . . . . . . . . . . . . 40 Setup log . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Shut-down mode . . . . . . . . . . . . . . . . . . . . . 50 Shutting down . . . . . . . . . . . . . . . . . . . . . . . 22 Solar (operating modes) . . . . . . . . . . . . . . . 30 Solar yield . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Spring/fall, heating during . . . . . . . . . . . . 9–10 Standard display . . . . . . . . . . . . . . . . . . . . . 29 Summer time / winter time clock adjustment . . . . . . . . . . . . . . . . . . . . . 40 Summer/winter mode, switching between . . . . . . . . . . . . . . . . . . 9–10 Supply temperature . . . . . . . . . . . . . . . . . . . 27 Switch point - changing . . . . . . . . . . . . . . . . . . . . . . . . . 35 - deleting . . . . . . . . . . . . . . . . . . . . . . . . . . 37 - entering . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Switching off . . . . . . . . . . . . . . . . . . . . . . . . 22 Switch-off point . . . . . . . . . . . . . . . . . . . 33, 35 Switch-on point . . . . . . . . . . . . . . . . . . . 33, 35 Switchover threshold for summer/winter mode . . . . . . . . . . . . . . . 40 T Temperature, see Room temperature Thermal disinfection . . . . . . . . . . . . . . . . . . 45 Thermostatic valves . . . . . . . . . . . . . . . . 11, 47 Time, moving forward/backward for summer/winter time . . . . . . . . . . . . . . 9–10 Time, setting . . . . . . . . . . . . . . . . . . . . . . . . . 17 U User menu - introduction to using . . . . . . . . . . . . . . . 23 - overview of the menu items . . . . . . . . . . 25 V Vacation mode . . . . . . . . . . . . . . . . . . . . . . . 41 Vacation temperature . . . . . . . . . . . . . . . 9–10 W Weather-dependent control . . . . . . . . . . . . 47 WWSD temperature . . . . . . . . . . . . . . . . . . 40
Logamatic EMS RC35 user interface - Subject to technical modifications.
57
Notes
58
Logamatic EMS RC35 user interface - Subject to technical modifications.
Notes
Logamatic EMS RC35 user interface - Subject to technical modifications.
59