Air/Water Heat Pumps Indoor installation
Operating Manual LW 101 – LW 121 83054300eUK – Translation into English of the original German operating manual
UK
Please read first
Symbols
This operating manual provides important information on the handling of the unit. It is an integral part of the product and must be stored so that it is accessible in the immediate vicinity of the unit. It must remain available throughout the entire service life of the unit. It must be handed over to subsequent owners or operators of the unit.
The following symbols are used in the operating manual. They have the following meaning:
Information personnel.
Read the operating manual before working on or operating the unit. This applies in particular to the chapter on safety. Always follow all instructions completely and without restrictions. It is possible that this operating manual may contain instructions that seem incomprehensible or unclear. In case of questions or uncertainty, contact the factory customer service department or the manufacturer’s local service partner. Since this operating manual was written for several different models of the unit, always comply with the parameters for the respective model. This operating manual is intended only for persons assigned to work on or operate the unit. Treat all constituent parts confidentially. The information contained herein is protected by copyright. No part of this information may be reproduced, transmitted, copied, stored in electronic data systems or translated into another language, either wholly or in part, without the express written permission of the manufacturer.
Information for operators. or
instructions
for
qualified
DANGER!
Indicates a immediate danger of serious injuries or death.
WARNING!
Indicates a potentially dangerous situation that could result in serious injuries or death.
CAUTION!
Indicates a potentially dangerous situation that could result in medium or slight injuries.
ATTENTION.
Indicates a potentially dangerous situation, which could result in property damage.
NOTICE.
Emphasised information.
€
ENERGY SAVING TIP Indicates suggestions that help to save energy, raw materials and costs. Reference to other sections of the operating manual. Reference to other documents of the manufacturer.
2
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Contents INFORMATION FOR USERS AND QUALIFIED PERSONNEL PLEASE READ FIRST.. .................................................................2 SYMBOLS......................................................................................2 INTENDED USE...........................................................................4 EXCLUSION OF LIABILITY.. .....................................................4 EC CONFORMITY......................................................................4 SAFETY..........................................................................................4 CUSTOMER SERVICE.................................................................5 WARRANTY / GUARANTEE. . .................................................5 DISPOSAL.....................................................................................5 FUNCTIONING PRINCIPLE OF HEAT PUMP SYSTEM.........6 AREA OF UTILISATION.. ...........................................................6 HEAT QUANTITY RECORDING.............................................6 OPERATION.................................................................................6 CARE OF THE UNIT.. .................................................................7 MAINTENANCE OF THE UNIT. . ..............................................7 Cleaning and flushing of unit components. . .......................7 MALFUNCTIONS........................................................................7
INSTRUCTIONS FOR QUALIFIED TECHNICIANS SCOPE OF DELIVERY.................................................................8 INSTALLATION AND ASSEMBLY. . ..........................................8 Sound.......................................................................................9 Installation location.............................................................10 Transport to installation location.....................................10 Installation............................................................................. 11 Mounting the air ducts. . ......................................................12 Installation / connection to heating circuit....................15 Condensate discharge.........................................................16
SET THE OVERFLOW VALVE..................................................23 COMMISSIONING....................................................................23 Safety temperature limiter.................................................24 DISMANTLING..........................................................................24 TECHNICAL DATA / SCOPE OF DELIVERY LW 101 – LW 121.................................................................26 PERFORMANCE CURVES Heating capacity/COP / power consumption / Heat pump pressure loss LW 101...................................................................................28 LW 121...................................................................................29 DIMENSIONAL DRAWINGS AND INSTALLATION PLANS LW 101 Dimensional drawings.........................................................30 Installation plan Version 1..................................................31 Installation plan Version 2..................................................32 Installation plan Version 3..................................................33 Installation plan Version 4..................................................34 LW 121 Dimensional drawings.........................................................35 Installation plan Version 1..................................................36 Installation plan Version 2..................................................37 Installation plan Version 3..................................................38 Installation plan Version 4..................................................39 HYDRAULIC INTEGRATION LW 101 – LW 121 Row tank.............................................................................. 40 Separate buffer tank............................................................41 Legend Hydraulic integration.............................................42 TERMINAL DIAGRAMS LW 101 – LW 121.................................................................43 CIRCUIT DIAGRAMS LW 101 – LW 121................................................................ 44 EC DECLARATION OF CONFORMITY...............................47
PRESSURE RELIEF......................................................................16 OVERFLOW VALVE...................................................................16 BUFFER TANK...........................................................................16 CIRCULATING PUMPS............................................................ 17 WATER HEATING..................................................................... 17 HOT-WATER TANK.................................................................. 17 ELECTRICAL CONNECTIONS.............................................. 17 FLUSHING, FILLING AND BLEEDING THE SYSTEM........18 Water quality of the fill and additional water in hot water heating systems according to VDI 2035. . ................................................18 INSULATING THE HYDRAULIC CONNECTIONS...........20 INSTALLATION OF THE CONTROL ELEMENT................20 INSTALLATION AND REMOVAL OF THE SCREEN..........22
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
3
Intended use
Safety
The unit may be used only for the intended purpose. This means:
The unit is operationally safe when used for the intended purpose. The construction and design of the unit conform to the state of the art, all relevant DIN/VDE regulations and all relevant safety regulations.
• for heating. • for heating hot water. The unit may be operated only within its technical parameters. Overview "Technical data / scope of delivery“.
NOTICE.
Notify the responsible power supply company of the use of a heat pump or heat pump system.
ATTENTION
Every person who performs work on the unit must have read and understood the operating manual prior to starting any work. This also applies if the respective person has already worked with such a unit or a similar unit or has been trained by the manufacturer. Every person who performs work on the unit must comply with the applicable accident prevention and safety regulations. This applies in particular to the wearing of personal safety gear.
The unit is not suitable for use in IT network systems.
Exclusion of liability
The manufacturer will not be liable for damage resulting from unauthorised use of the unit. The manufacturer’s liability will also be voided in the following cases:
• if work is performed on the unit and its compo-
nents in a manner that does not comply with the terms of this operating manual;
• if work is performed on the unit and its components in an improper manner;
• if work is performed on the unit that is not described in this operating manual, and this work was not expressly approved in writing by the manufacturer;
• if the unit or components in the unit are modified,
redesigned or removed without the express written permission of the manufacturer.
EC conformity The unit bears the CE mark of conformity. EC declaration of conformity
4
DANGER!
Unit operates using high electric voltage!
DANGER!
Danger of fatal injury due to electric shock! Electrical connections may be installed only by qualified electricians. Before opening the unit, disconnect the system from the power supply and secure it from being switched back on!
CAUTION!
If using the unit in 3~230V systems, please note that the residual-current circuit breaker (RCCB) used must be AC-DC sensitive.
DANGER!
Only qualified technicians (trained heating, cooling, refrigerant and electrical technicians) may perform work on the unit and its components.
WARNING!
Observe safety labels on and in the unit.
WARNING!
Unit contains refrigerants! Leaking refrigerant can result in personal injury or material damage. Therefore: – Shut down unit. – Notify the manufacturer’s authorised service center.
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
ATTENTION
For safety reasons: Never disconnect the unit from the power supply, unless the unit is being opened.
ATTENTION
Install the heat pump only indoors and operate only with outside air as the heat source. The air ducts must discharge into the open air. Do not restrict or block the air ducts.
For a current list and additional partners of the manufacturer, please visit DE: www.alpha-innotec.de EU: www.alpha-innotec.com
Warranty / Guarantee
WARNING!
For warranty and guarantee conditions, please refer to the purchase documents.
Switch on unit only if air ducts are mounted on the unit. Take measures on the fan side to prevent injuries from the rotating fan (aboveground air duct discharge: weather grille, below-ground air-channel discharge: rain guard – accessories not included in scope of delivery).
The integration of the heat pump in ventilation systems is not permissible. The use of the cooled air for cooling purposes is not permitted.
ATTENTION
For technical assistance, please contact your qualified technician or the manufacturer's local service partner.
Dimensional drawing and installation plan for respective model.
ATTENTION
Customer service
NOTICE.
Please contact your dealer concerning warranties and guarantees.
Disposal When decommissioning the unit, always comply with applicable laws, directives and standards for the recovery, recycling and disposal of materials and components of colling units. Dismantling.
The ambient air in the location where the heating pump is installed and also the intake air which is used as a source of heat must not contain any kind of corrosive components! Components such as ammonia, sulphur, chlorine, salt, sewer gas, flue gases etc. may cause damage leading to complete failure or even a total write-off of the heating pump!
CAUTION!
In the air outlet area the air temperature is ca. 5 K below the ambient temperature. Under certain climatic conditions, therefore, an ice layer can form in the air outlet area. Install the heat pump so that the air blower does not blow in the direction of footpaths.
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
5
Functioning principle of heat pump system Heat pumps operate on the principle of a refrigerator: the same technology, only with the opposite effect. The refrigerator extracts heat from foods, which is released into the room through fins on the back. The heat pump extracts heat from our environment: air, earth or ground water. The extracted heat is conditioned in the unit and supplied to the heating water. Even when it is extremely cold outside, the heat pump draws enough heat to heat a house.
Heat quantity recording In addition to proof of the unit's efficiency, heating legislation also requires heat quantity recording (referred to as WME in this manual). The WME is mandatory with air/water heat pumps. With brine/ water and water/ water heat pumps, a WME is only required when the feed temperature is ≥ 35 °C. The WME must record the total warm energy release (heating and hot water) in the building. In heat pumps with heat quantity recording, the analysis is conducted by the regulator. The regulator displays the thermal energy that is exchanged from the heating system in kWh.
Example: drawing of a brine/water heat pump with floor heating:
Operation Your decision to purchase a heat pump or a heat pump system is a long-term contribution to protecting the environment through low emissions and reduced primary energy use. You can operate and control the heat pump system with the control element of the heating and heat pump regulator.
NOTICE. 4 ⁄4 = ca. 3 ⁄4 = ca. 1 ⁄4 =
usable energy environmental energy external electrical energy
Area of utilisation
Make sure that the control settings are correct. Operating manual of the heating and heat pump regulator.
To ensure that your heat pump or heat pump system operates efficiently and ecologically, the following are especially important: €
Avoid unnecessarily high flow temperatures. A lower flow temperature on the hot water side increases the efficiency of the system.
Taking into consideration the ambient conditions, limits of application and the applicable regulations, every heat pump can be utilized in new or existing heating systems. Overview "Technical data / scope of delivery".
6
€
ENERGY SAVING TIP
ENERGY SAVING TIP When letting in fresh air, do not leave windows open for an extended period, thus saving energy and reducing your heating costs.
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Care of the unit The outer surfaces of the unit can be cleaned with a damp cloth and household cleaning products.
CLEANING AND FLUSHING OF UNIT COMPONENTS
Do not use cleaning or care products that contain abrasives, acids and/or chlorine. Such products would destroy the surfaces and could also damage the technical components of the unit.
Maintenance of the unit The cooling circuit of the heat pump requires no regular maintenance. According to EU regulation (EC) 517/2014, leak inspections and maintenance of a log book are required by law for certain heat pumps! Log book for heat pumps, Section “Information on use of the log book”. The components of the heating circuit and the heat source (valves, expansion vessels, circulating pumps, filters, dirt traps) should be inspected as well as cleaned as needed - at the very least annually - by a qualified heating or cooling system technician. It is a good idea to have a maintenance contract with a specialist company. The company will conduct the required maintenance at regular intervals.
ATTENTION
Check regularly to ensure that the condensate can drain out of the unit unobstructed. To this end, regularly check the condensate pan in the unit and the condensate drain to ensure that they are clean / free from obstructions and clean as needed.
CAUTION!
Unit components may be cleaned and flushed only by customer service personnel authorised by the manufacturer. Use only liquids recommended by the manufacturer. Flushing of the liquefier with chemical cleaning agents must be followed by neutralisation of residue and intensive rinsing with water. Always observe the technical data of the manufacturer of the heat exchanger.
Malfunctions In the event of a malfunction, you can detect the cause of the malfunction via the diagnostic program of the heating and heat pump regulator. Operating manual of the heating and heat pump regulator.
DANGER!
Service and repair work on the components of the unit may be performed only by customer service personnel authorised by the manufacturer.
Note that no malfunction is displayed if the safety temperature limiter on the electric heating element has been triggered (depending on model). “Commissioning”, “Safety temperature limiter” section.
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
7
Scope of delivery
Inspect delivery for outwardly visible signs of damage.
Example of scope of delivery:
Check to make sure that delivery is complete. Any defects or incorrect deliveries must be claimed immediately.
View 1:
ACCESSORIES NECESSARY FOR OPERATION
ATTENTION
Use only original accessories from the manufacturer of the unit.
Air ducts (with air duct accessories) must be ordered separately.
Installation and assembly Observe the following when performing all work:
View 2:
NOTICE.
8
Unit with a completely hermetically enclosed compressor, all safetyrelated components for monitoring of the cooling circuit, integrated heating and heat pump regulator, sensors mounted in the unit for the monitoring of hot gas, heating water forward flow and return flow temperatures, as well as a hose for condensate discharge (connected to heat pump side)
Always comply with applicable accident prevention regulations, statutory regulations, ordinances and directives.
WARNING!
The heat pump or heat pump system may be installed and assembled only by a qualified technician!
NOTICE.
Observe the sound levels of the respective model.
Overview “Technical data / scope of delivery”, “Sound” section.
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
SOUND
NOTE.
The noise emission from the heat pumps must be taken into account in the respective installation plans for air / water heat pumps. The respective regional regulations must be complied with.
The following sound pressure levels are calculated values. Other constellations, adjoining other buildings or even reflecting surfaces may lead to a level increase. An exact specification of each sound pressure level is possible only through a measurement spot when the heat pump is already installed.
The following sound pressure levels result, depending on the distance and installation variant with directivity factor Q (see sketches): LW 101
Directivity factor Q 2 4 8 LW 121
Directivity factor Q 2 4 8
Distance from the heat pump in m 1 2 3 4 5 6 7
8
9
10
11
12
13
14
15
16
17
18
19
20
Sound pressure level at max. heating output in dB(A) -
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
50
44
40,5
38
36
34,4
33,1
31,9
30,9
30
29,2
28,4
27,7
27,1
26,5
25,9
25,4
24,9
24,4
24
53
47
43,5
41
39
37,4
36,1
34,9
33,9
33
32,2
31,4
30,7
30,1
29,5
28,9
28,4
27,9
27,4
27
8
9
10
11
12
13
14
15
16
17
18
19
20
Distance from the heat pump in m 1 2 3 4 5 6 7
Sound pressure level at max. heating output in dB(A) -
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
50
44
40,5
38
36
34,4
33,1
31,9
30,9
30
29,2
28,4
27,7
27,1
26,5
25,9
25,4
24,9
24,4
24
53
47
43,5
41
39
37,4
36,1
34,9
33,9
33
32,2
31,4
30,7
30,1
29,5
28,9
28,4
27,9
27,4
27
The directivity factor Q for the different installation variants:
Q=4 Q=4
In case of 2 or more units of the same heat pump type, the respective level increase must be added to the corresponding sound pressure level from the following table Number of n equally loud sound sources 1 2 3 4 5 6 7 8 9 10 12
Level increase ∆ L in dB 0,0 3,0 4,8 6,0 7,0 7,8 8,5 9,0 9,5 10,0 10,8
Q=8 Q=8 Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
9
Level increase in dB
In case of different, not equally loud units, the level increase is read off the following diagram:
Unit is not fastened to the wooden pallet. Danger of tipping over during transport! This can result in personal injury and damage to the unit. – Take suitable precautionary measures to eliminate the danger of tipping.
ATTENTION
Level difference in dB Example: If the level difference between two unequal sound sources is 5 dB, the level increase is an additional 1.2 dB.
ATTENTION Install the unit only indoors.
The installation area must be frost-free and dry. It must meet the requirements of DIN EN 378. It must also fulfill applicable local regulations. Dimensional drawing and installation plan for respective model.
Do not damage the hydraulic connections under any circumstances.
ATTENTION
INSTALLATION LOCATION
Never use components and hydraulic connections on the unit for purposes of transport.
ATTENTION
DANGER!
Do not tilt the unit more than a maximum of 45° (in any direction).
LIFTING THE UNIT WITH PIPES The units can be lifted with 3 /4" and/or 1" pipes (provided by customer) that are suitable for the weight of the respective unit. Special holes are provided in the frame for this purpose. Remove lower facing panels on the switch cabinet side (= operator side) of the unit. To do so, loosen quick-release screws. Turn counter-clockwise 90°…
TRANSPORT TO INSTALLATION LOCATION To prevent damage during transport, always transport the unit to final installation location in its original packaging, using a lifting truck. If it is not possible to transport the unit to the final installation location using a lifting truck, you can also transport the heat pump using a hand truck or with pipes.
DANGER!
Several people are required to transport the unit. Do not underestimate the weight of the unit.
1 Quick-release screws 2 Lower facing panel
Overview “Technical data / scope of delivery”, “General unit data” section.
10
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Pull lower facing panel upwards and outwards, detach and set securely to the side…
Lift the unit on the pipes with at least four people and carry it to its final installation location…
NOTICE.
Carry the unit horizontally and secure it against slipping. Put the unit in its final installation location. Make sure that the frame of the unit is in full contact with the underlying surface… Remove the pipes and re-place the sealing grommets on the back side of the unit…
On the back of the unit, remove the sealing grommet…
Insert the pipes through the holes in the frame on the switch cabinet side (= operator side)…
If the electrical connections will not be carried out directly thereafter, mount the lower facing panel on the operating side.
INSTALLATION Set the unit on a stable, solid and level, preferably sound-insulated surface. Make sure that the foundation is designed for the weight of the heat pump.
ATTENTION
1 Holes in the frame 2 Inserted pipes
Make sure that pipes do not damage cable assemblies and components in the unit. Guide pipes carefully past cable assemblies and components in the unit… Guide pipes through the marked openings on the back side of the unit…
In the air outlet area the air temperature is ca. 5 K below the ambient temperature. Under certain climatic conditions, therefore, an ice layer can form in the air outlet area. Install the heat pump so that the air blower does not blow in the direction of footpaths.
DANGER!
Several people are required to install the unit.
CAUTION.
Do not tilt the unit more than a maximum of 45° (in any direction).
NOTICE.
Always observe the installation plan for the respective model. Note the size and minimum clearances. Installation plan for respective model.
Set up the unit so that the switch cabinet side (= operating side) is accessible at all times.
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
11
MOUNTING THE AIR DUCTS
Rotate the already-interlocked parts 90° and affix the final piece at the bottom…
ATTENTION
Use only original accessories or air ducts recommended by the manufacturer (fibreglass lightweight concrete ducts). Mount air ducts only according to the installation plan for the respective unit. Installation plan for respective model.
WALL DUCT(S) ASSEMBLY
Rotate the already-interlocked parts by 90° once again and set up the final connection…
Remove the parts necessary for the assembly of the wall duct(s) from their respective boxes…
Next, interlock the 2 pieces of the wall duct(s) that belong together, as illustrated in the following drawing. Use the lubricant supplied upon delivery to help in this process…
Stabilise the wall duct from the inside using the chipboard included with delivery…
Affix an additional part as illustrated…
12
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Install the wall duct in the masonry from the house exterior. This can either be done during the construction phase (by means of sealing)…
AIR DUCTS ASSEMBLY Remove the parts necessary for the assembly of the air duct(s) from their respective boxes…
NOTICE.
Mount the wall ducts 1 cm above the finished outer facade.
The interlocking of the air ducts is carried out as described in the section – entitled "Wall duct(s) assembly".
SECURING THE AIR DUCT INTO THE WALL DUCT 1 Masonry of the house exterior 2 Insert the wall duct in the masonry (1 cm above the finished outer facade)
Pull the roll seal included with delivery over the end of the air duct… Push this end of the air duct into the wall duct.
or retrofit (using foam in the masonry):
1 Finished outer facade
NOTICE.
Wall ducts fix wall openings, help avoid cold air transmission in the masonry as well as assist in the assembly of weather / rain guards and wire mesh grilles
1 2 3 4
Wall duct Air duct Roll seal Bentonite waterproofing tape (apply only after assembling the unit's connection fastener)
NOTICE.
After the other end of the air duct has been secured to the heat pump, close the opening between the wall duct and the air duct using the bentonite waterstop tape included with delivery.
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
13
SECURING THE AIR DUCT ON THE HEAT PUMP Clip on the assembly rail and secure it using special screws to the spots on the air duct designated as the air intake side…
SCREEN FRAME ASSEMBLY Screw the screen frame to the wall ducts on both the air intake and output sides.
Stick the adapter base included with delivery on the edge of the air duct… Position the air duct on the respective opening of the air intake side… Hook the tension springs included with delivery into the holes provided for them on the air intake side of heat pump 4… Hook the tension springs into the assembly tail that has been screwed on to the air duct… Secure a protective cap over the assembly rail…
NOTICE.
The screen frame has no function, it is included solely to provide an optically attractive transition to the wall duct.
WIRE MESH GRILLE AND WEATHER / RAIN GUARDS ASSEMBLY Remove the wire mesh grille and the weather / rain guards as well as the assembly frame and fastening material from their respective boxes…
Repeat
–
the process on the air output side.
NOTICE.
Don't forget: After the air ducts have been secured to the heat pump, close the opening between the wall duct and the air duct using the bentonite waterstop tape included with delivery.
From the outside of the house inwards, insert the assembly frame into the wall duct on the air intake side and secure with screws…
8x
NOTICE.
Secure the air ducts to the cover using appropriate measures.
14
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Position the wire mesh grille in the assembly frame…
INSTALLATION / CONNECTION TO HEATING CIRCUIT ATTENTION
Connect the unit to the heating circuit according to the hydraulic diagram for the respective model. “Hydraulic connection” instructions.
NOTICE.
Set the weather / rain guards on the assembly frame in the wall duct and screw down…
Check to make sure that the diameters and lengths of the pipes for the heating circuit are sufficiently dimensioned.
NOTICE.
8x
Circulating pumps must be multi-stage. They must be able to deliver at least the minimum hot water flow rate required for your model. Overview “Technical data / scope of delivery”, “heating circuit” section.
ATTENTION
The hydraulic system must be equipped with a buffer tank, the required volume of which depends on the model of your unit. Overview “Technical data / scope of delivery”, “heating circuit, buffer tank” section.
NOTICE.
If the wall duct is positioned above ground level, attach the weather guard. If the wall duct is positioned in a light well (below ground level), attach the rain guard. Repeat
–
ATTENTION
the process on the air output side.
When installing the connections, always secure the connections on the unit from twisting, in order to prevent damage to the copper pipes in the interior of the unit. Rinse heating circuit thoroughly prior to connecting the unit to the heating circuit…
NOTICE.
Contamination and deposits in the heating circuit can cause malfunctions. Install shut-off devices for the hot water outflow (forward flow) and hot water inflow (return flow) on the heat pump side.
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
15
NOTICE.
During installation of the shut-off devices, the liquefier of the heat pump can be flushed, if necessary. Connect the unit to the pipes of the heating circuit via vibration decouplers. They must be installed in order to prevent damage from vibrations to the pipes.
NOTICE.
Vibration decouplers are available as accessories.
The connections for the heating water outflow (forward flow) and the hot water inflow *(return flow) are marked accordingly. For positioining of the connections, reference the dimensional drawing for the respective model.
Pressure relief Equip the heating circuit in accordance with local standards and directives with a safety valve and an expansion tank. Also install filling and emptying devices, shut-off devices and non-return valves in the heating circuit.
Overflow valve Use an overflow valve for tanks integrated in series to ensure the minimum flow rate of the heating circuit volume flow through the heat pump. The overflow valve must be dimensioned so that the minimum flow rate of the volume flow through the heat pump is ensured when the heating circuit is shut off. “Set the overflow valve”, page 23
CONDENSATE DISCHARGE The condensation water that accumulated from the air must be drained via the pre-mounted hose in the unit for condensate discharge. To do so, connect the hose for condendate discharge with a water drain. For positioning of the connection for condensate discharge, see dimensional drawings for the respective model.
Buffer tank The hydraulic connection of the heat pump requires a buffer tank in the heating circuit. It ensures a minimum operating time of the heat pump when the heating circuit valves are closed. The required volume of the buffer tank is calculated based on the following formula: VBuffer tank =
1 Hose for condensate discharge in interior of unit 2 Connection for the condensate discharge on the outside of the unit
minimum flow rate of heat circuit volume flow / hour 10
For the minimum flow rate of the heat circuit volume flow, see overview “Technical data / Scope of delivery”, “Heating circuit” section. In mono-energetic air/water systems, integrate the buffer tank in the heating water outflow (forward flow) before the overflow valve.
ATTENTION
Guide the pre-mounted hose in the unit for condensate discharge in the interior of the unit as a siphon, as shown in the illustration.
Discharge of the condensate into the sewage system is permitted only via a funnel siphon, which must be accessible at all times.
16
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Circulating pumps ATTENTION
Always note the model. Do not use regulated circulating pumps. Circulating pumps and domestic hot water circulation pumps must be multi-stage pumps.
Electrical connections Observe the following when performing all work:
Water heating Water heating with the heat pump requires an additional hot water circuit, parallel to the heating circuit. Make sure that the heating water charge is not channelled through the buffer tank of the heating circuit. “Hydraulic connection” instructions.
Hot-water tank If the heat pump is to be used for heating hot water, you must integrate special hot-water tanks in the heat pump system. The storage volume must be sufficient so that the required hot water quantity is available even during a power cut.
NOTICE.
The heat exchanger surface of the hot water tank must be dimensioned so that the heating capacity of the heat pump is transferred with minimal spreading.
DANGER!
Danger of fatal injury due to electric shock! Electrical connections may be installed only by qualified electricians. Before opening the unit, disconnect the system from the power supply and secure it from being switched back on!
DANGER!
Observe the relevant EN‑, VDE and/or applicable local safety regulations during installation and during all electrical work. Comply with any technical connection requirements laid down by the responsible power supply company!
NOTICE.
All live wires must be stripped before they are installed in the cable duct of the switch cabinets!
POWER CONNECTION If the unit is closed, open the facing panels on the operating side… "Installation". Open electrical switch cabinet of unit…
We offer a variety of hot-water tanks for you to choose from. They are optimised for use with your heat pump.
NOTICE.
Integrate the hot-water tank in the heat pump system according to the hydraulic diagram for your system. “Hydraulic connection” instructions.
Example of open electrical switch cabinet…
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
17
Lead 230 V power cable, power cable for circulating pumps and cable for external temperature sensor through the rubber sockets on the facing panel in the unit…
• Cut out the rubber sockets on the facing panel…
NOTICE.
For positioning of the rubber sockets for inserting the wires, see "dimensional drawing" for the respective model.
• Insert the cables through the rubber sockets in the unit…
Close electrical switch cabinet of unit….
The wires inside the unit are guided in a closed wire duct to the terminals on the switch plate. Install electric connections according to the terminal diagram that applies to your model… Terminal diagram for respective model.
Attach the lower facing panels.
Flushing, filling and bleeding the system
ATTENTION
Ensure clockwise rotary field of the load power supply (compressor). – An incorrect rotary field of the compressor during operation can cause serious, irreparable damage to the compressor.
ATTENTION
Make sure to equip the power supply of the heat pump with a 3-pole automatic cut-out with at least 3 mm contact gap. Note the level of the release current. Overview “Technical data / scope of delivery”, “Electric” section.
ATTENTION
If using the unit in 3~230V systems, please note that the residual-current circuit breaker (RCCB) used must be AC-DC sensitive.
ATTENTION
Factory setting for the electric heating element in units with integrated electic heating elements is 6 kW (9 kW). It can be changed at contactor Q5 (Q6) for 2 (3) or 4 kW (6kW). For further information, see the adhesive label on the electric heating element.
18
Using a suitable network cable, the control element of the heat and heat pump regulator can be connected with a computer or a network allowing the heating and heat pump regulator to be controlled from there. If such a connection is desired, lay a category 6 screened network cable with RJ-45 plug through the unit parallel to the heating and heat pump regulator control cable already present when making the connections, and lead it through the front panel of the unit.
ATTENTION
The system must be absolutely free from air before commissioning.
WATER QUALITY OF THE FILL AND ADDITIONAL WATER IN HOT WATER HEATING SYSTEMS ACCORDING TO VDI 2035 PART I AND II Use of modern, energy-efficient heat pump systems is becoming increasingly widespread. Their ingenious technology enables these systems to achieve very good efficiencies. The decreasing space available for heat generators has led to the development of compact units with increasingly smaller cross-sections and high capacities. This means the complexity of the systems and the material diversity are also increasing, which plays an important role especially in their corrosion behaviour. Alpha InnoTec ensures continuous technological advances, but all these technical refinements require the system to be operated with correctly filled heating water. The heating water not only affects the efficiency of the system, but also the life of the heat generator and the heating components of a system. The guide values of VDI 2035 Part I and Part II must therefore be complied with as minimum requirements for proper operation of the systems. Our practical
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
experience has shown that the safest and most troublefree running of the systems is achieved with so-called low-salt operation. VDI 2035 Part I gives important information and recommendations regarding scaling and its prevention in heating and domestic hot water heating systems. VDI 2035 Part II primarily deals with the requirements for reducing heating water corrosion in hot water heating systems.
WATER SOFTENING TO VDI 2035 – PART I If the water is softened before the heating is filled, in accordance with the VDI 2035 guidelines, no scale can form. This effectively and permanently prevents limescale deposits and the resulting negative effects on the entire heating system.
CORROSION – AN UNDERESTIMATED PROBLEM PRINCIPLES OF PART I AND PART II The occurrence of scaling and corrosion damage in hot water heating systems is low, if - proper planning and commissioning is carried out - the system is closed in corrosion terms - adequately dimensioned pressurising is integrated - the guide values for the heating water are complied with - and regular servicing and maintenance are carried out. A system log should be kept, in which the relevant planning data is entered (VDI 2035). DAMAGE THAT CAN OCCUR IN CASE OF NONCOMPLIANCE - Malfunctions and the failure of components (e.g. pumps, valves) - Internal and external leaks (e.g. from heat exchangers) - Cross-section reduction and blockaging of components (e.g. heat exchanger, pipes, pumps) - Material fatigue - Gas bubbles and gas cushion formation (cavitation) - Negative effect on heat transfer (formation of coatings, deposits) and associated noises (e.g. boiling noises, flow noises) LIMESCALE – THE ENERGY KILLER Filling with untreated drinking water inevitably leads to the precipitation of all calcium as scale. The consequence: limescale deposits form on the heat transfer surfaces of the heating. The efficiency falls and the energy costs rise. A rule of thumb is that 1 millimetre of limescale deposit causes an energy loss of 10%. In extreme cases it can even cause damage to the heat exchangers.
VDI 2035, Part II, deals with the problem of corrosion. Softening the heating water can prove to be insufficient. The pH value can significantly exceed the limit of 10. pH values higher than 11 can set in, which even damage rubber seals. The VDI 2035, Part 1 guidelines are fulfilled, however, VDI 2035, Part 2 suggests a pH value between 8.2 and maximum 10. If aluminium materials are used, which is the case in many modern heating systems, a pH value of 8.5 must not be exceeded, because otherwise there is a threat of corrosion – and aluminium is attacked without the presence of oxygen. Therefore, apart from softening the heating fill and additional water, the heating water should also be appropriately conditioned. This is the only way to comply with the VDI 2035 requirements and the recommendations and installation instructions of the heat pump manufacturer. Part 2 of VDI 2035 also points out the reduction in total salt content (conductivity). The risk of corrosion is far lower if deionised water is used than is the case if the system is operated with salty, i.e. softened water. Even if the water has been softened beforehand, it contains dissolved, corrosion-promoting salts, which act as electrolytes due to the use of different materials in the heating system and therefore accelerate corrosion processes. This can ultimately result in pitting. Contamination and deposits in the heating circuit can cause malfunctions RINSE, FILL AND BLEED THE HEATING CIRCUIT AND HOT WATER BUFFER TANK To bleed the hot water tank, the heating circuit and hot water circuit must be rinsed simultaneously.
ON THE SAFE SIDE WITH LOW-SALT OPERATION The problems listed above do not occur at all with low-salt operation, as neither corrosive salts such as sulphates, chlorides and nitrates nor alkalising sodium hydrogen carbonate are in the heating water. The corrosive properties of deionised water are very low and in addition, fur cannot form in the boiler. This is the
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
19
ideal approach for closed heating circuits, in particular, because low oxygen input into the heating circuit can also be tolerated. In general, when the system is filled with deionised water, the pH value sets itself within the ideal range due to “self-alkalinisation”. If necessary, a pH value of 8.2 can be very easily alkalised by adding chemicals. In this way, optimum protection of the entire heating system is achieved.
Insulating the hydraulic connections Insulate the vibration decouplers and the pipes of the heating circuit.
NOTICE.
Insulate in accordance with applicable local standards and directives.
MONITORING Analytical recording and monitoring of the relevant water values and the added active conditioning substances is of decisive importance. Therefore, they should be monitored regularly using appropriate water test equipment Flush, fill and bleed the heating circuit… In addition, bleed the condenser of the heat pump…
Situated at different heights in the front panel of the unit are four-pin sockets for fastening the control element:
• Open the lower facing panel… • Open the bleed valve…
Following bleeding, close the lower facing panel.
20
Installation of the control element
1 four upper recesses 2 four lower recesses
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Four hooks are located on the back side of the control element and can be used to hang the control element on the front facade of the unit:
Stick the heating and heat pump regulator's control cable into the right bushing on the bottom of the control element…
Hang the control element's hooks on the recesses of the front facade (either in the upper or lower recesses)…
NOTICE.
Example: Control element in upper recesses
A connection to a computer or a network can be installed via the left bushing on the bottom of the control element, allowing the heating and heat pump regulator to be controlled remotely. One pre-condition is that a screened network cable (category 6) be installed through the unit when installing the unit. Operating manual for the heating and heat pump regulator, version "Qualified technician", “Web server” section.
Push the control element down until it locks into position…
If this network cable is available, insert the network cable's RJ‑45 plug into the left bushing of the control element.
NOTICE.
The network cable can be exchanged at any time. In order to be able to connect it, the screen must first be removed.
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
21
Installation and removal of the screen INSTALLING THE SCREEN NOTICE.
The screen is provided at the time of delivery so that the control element may be inserted in the upper recesses of the front facade. If the control element has been inserted in the lower recesses of the front facade, you must first remove the screen's temporary cover and then reinsert it above the logo. Next, on the opposite side, moving upwards. lock the screen's snap-in lugs in place in the slots provided on the front of the facade… Finally, press the screen's upper snap-in lugs into the slots provided on the front of the facade.
Screen at time of delivery: 1 recess for control element 2 logo 3 temporary cover First, insert the screen below, in the provided slots on the front of the facade…
REMOVING THE SCREEN In order to remove the screen, the snap-in lugs must first be loosened by pressing one side completely toward the middle of the screen. Thereafter, remove the snap-in lugs from the opposite side.
Beginning first on one side and moving upwards, lock the screen's snap-in lugs in place in the slots provided on the front of the facade…
22
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Set the overflow valve
Commissioning
REMARQUE
The activities in this section are only necessary for in-line tank integration. Complete the worksteps quickly, otherwise the maximum return temperature can be exceeded and the heat pump switches to high-pressure fault. Turn the adjusting knob at the overflow valve to the right to increase the temperature difference (the temperature drop), turn it to the left to reduce it.
DANGER!
The unit may be commissioned only with the air ducts and weather grille or rain guard installed and with the covers closed.
NOTE.
The commissioning has to be in the heating mode. Carry out a thorough installation check and work through the general checklist…
System is running in heating mode (ideally in cold condition).
Manufacturer’s homepage.
In case of low heating curve: Set the system to “Forced heating”…
Operating manual of the heating and heat pump controller. Shut off valves to the heating circuit…
By checking the installation you prevent damage to the heat pump system, which could be caused by work carried out improperly.
Check that…
Ensure that the total flow is routed via the overflow valve…
• clockwise rotary field of the load power supply
Read out the flow and return temperature at the heating and heat pump controller…
• The heat pump installation and assembly have
Operating manual of the heating and heat pump controller. Turn the adjusting knob (1) of the overflow valve (2) until the temperature drop between the flow and return temperature is set as follows: External temperature Recommended settings -10 °C
4K
0 °C
5K
10 °C
8K
20 °C
9K
30 °C
10 K
(compressor) is ensured.
been carried out according to the requirements of this operating manual.
the electrical installation work has been • completed properly.
• The power supply for the heat pump must be
equipped with an all-pole automatic circuitbreaker with at least 3 mm contact spacing to IEC 60947-2.
• The heating circuit is flushed, filled and thoroughly vented.
• All valves and shut-off devices of the heating circuit are open.
• All pipe systems and components of the system are leaktight.
Carefully fill out and sign the completion report for heat pump systems... Manufacturer’s homepage.
Open valves to heating circuit… Reset the heating and heat pump controller.
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
23
Within Germany and Austria: Send completion report for heat pump systems and general checklist to the manufacturer’s factory customer service department… In other countries: Send completion report for heat pump systems and general checklist to the manufacturer’s local partner… The heat pump system is commissioned by customer service personnel authorised by the manufacturer. There is a fee for starting up!
SAFETY TEMPERATURE LIMITER A safety temperature limiter is built into the electric heating element (depending on model). In the event of a malfunction in the heat pump or air in the system, check whether the reset button of the safety temperature limiter has tripped. If this is the case, push in the button.
Dismantling
DANGER!
Danger of fatal injury due to electric shock! Electrical connections may be installed only by qualified electricians. Before opening the unit, disconnect the system from the power supply and secure it from being switched back on!
DANGER!
Only qualified heating or cooling system technicians are allowed to remove the unit from the system.
DANGER!
Only qualified cooling system technicians are allowed to dismantle the unit and its components.
ATTENTION
Recycle or provide for proper disposal of unit components, refrigerants and oil in accordance with the applicable regulations, standards and directives.
REMOVAL OF THE BUFFER BATTERY 1 Safety temperature button on electric heating element 2 Reset button
24
ATTENTION
Before scrapping the heating and heat pump regulator, remove the buffer battery on the processor board. The battery can be removed using a screwdriver. Dispose of battery and electronic components in keeping with environmental considerations.
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
25
Technical data / scope of delivery Model designation Heat pump type Installation location Conformity Performance data
Brine/water ı Air/water ı Water/water Indoors ı Outdoors
Sound
Heat source Heating circuit
General unit data
Electric
Heat Pump
• applicable ı — not applicable CE
Heating capacity/COP at A7/W35
Standard point acc. to EN14511
2 Compressors 1 Compressor
kW ı … kW ı …
A7/W45
Standard point acc. to EN14511
2 Compressors 1 Compressor
kW ı … kW ı …
A2/W35
Operating point according to EN14511
2 Compressors 1 Compressor
kW ı … kW ı …
A10/W35
Operating point according to EN14511
2 Compressors 1 Compressor
kW ı … kW ı …
A-7/W35
Operating point according to EN14511
2 Compressors 1 Compressor
kW ı … kW ı …
2 Compressors 1 Compressor
kW ı … kW ı …
A-15/W65 Limits of application
• applicable ı — not applicable
Heating circuit Heat source Additional operating points Internal sound pressure level (open air test field, distance of 1m around the engine, average)
dB(A)
External sound pressure level (open air test field, distance of 1m around the air supplies, average) (2x 1m original straight air duct)
dB(A)
Sound inside Sound outside Air volume flow at maximum external compression Maximum external pressure Volume flow: minimum flow rate ı nominal flow rate A7/W35 EN14511 ı maximum flow rate Pressure loss heat pump ∆p ı volume flow Free compression heat pump ∆p ı volume flow Content of buffer tank 3-way valve, heating/hot water Dimensions (see dimensional drawing for the specified unit size) Total weight Connections Heating circuit Heat source Refrigerant Refrigerant type ı Quantity Free cross section, air channels Cross section, condensate water / length from unit Voltage code ı all-pole circuit breaker heat pump **) Voltage code ı circuit breaker control voltage **) Voltage code ı circuit breaker electric heating element **)
dB(A)
°C °C °C
dB(A) m³/h Pa l/h bar ı l/h bar ı l/h l … unit size kg … … … ı kg mm mm ı m …ı A …ı A ı A
Effective power consumption in standard point A7/W35 according to EN14511: Power consumption ı current consumption ı cosφ
kW ı A ı …
Maximum device current within the limits of application A Starting current: direct ı with soft starter A ı A Protection type IP Output electric heating element 3 ı 2 ı 1 phase kW ı kW ı kW Components Circulating pump heating circuit at nominal flow rate: Power consumption ı current consumption kW ı A Safety equipment Safety component heating circuit ı Safety component heat source Includ. in sc. of del.: • yes — no Heating and heat pump regulator Includ. in scope of delivery: • yes — no Control and sensor wire Includ. in scope of delivery: • yes — no Power cable to unit Includ. in scope of delivery: • yes — no Electronic soft starter integrated: • yes — no Expansion vessels Heat source: Scope of delivery ı Volume ı Initial pressure • yes — no ı l ı bar Overflow valve integrated: • yes — no Vibration decouplers Heating circuit ı heat source Included in scope of delivery: • yes — no UK813517
26
*) depending on components tolerances and flow
**) comply with local regulations
n.n. = not detectable w.w. = to choice ¹) hot water return ²) hot water flow
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
LW 101
LW 121
— ı • ı — • ı — •
— ı • ı — • ı — •
— 10,3 ı 4,2
— 12,8 ı 4,2
— 10,1 ı 3,5
— 12,7 ı 3,5
— 9,5 ı 3,7
— 11,8 ı 3,7
— 11,1 ı 4,4
— 12,8 ı 4,4
— 7,5 ı 2,9
— 9,1 ı 2,9
— —
— —
20¹ – 50² -20 – 35 A> -7 / 60² 50 50 — 55 4000 25 1500 ı 2000 ı 2500 0,09 ı 2000 — ı — — — 2 260 G1”AG — R407C ı 4,8 570 x 570 30 ı 1 3~/N/PE/400V/50Hz ı C10 1~/N/PE/230V/50Hz ı B10 3~/N/PE/400V/50Hz ı B16 2,6 ı 5,4 ı 0,7 9,2 51,5 ı 19 20 9 ı 6 ı 3 — ı — — ı — • — — • — ı — ı — — —
20¹ – 50² -20 – 35 A> -7 / 60² 50 50 — 55 4000 25 1650 ı 2500 ı 3100 0,09 ı 2500 — ı — — — 3 280 G1”AG — R407C ı 5,8 570 x 570 30 ı 1 3~/N/PE/400V/50Hz ı C16 1~/N/PE/230V/50Hz ı B10 3~/N/PE/400V/50Hz ı B16 3,1 ı 6,4 ı 0,7 11,5 64 ı 23 20 9 ı 6 ı 3 — ı — — ı — • — — • — ı — ı — — —
813520d
813521d
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
27
LW 101
Performance curves
Qh (kW)
COP 7
20
6 18
5 4
16
3 2
14
1 -20
-15
-10
-5
0
5
10
15
20
25
30
35
20
25
30
35
Temp„ (°C)
12
Pe (kW)
10 5 8
4 35°C 1VD 50°C 1VD
6
3
4
2
2
1 -20
-15
-10
-5
0
5
10
15
20
25
30
35
-20
-15
Temp„ (°C)
-10
-5
0
5
10
15
Temp„ (°C)
∆p (bar) 0,4
0,3
0,2 ∆p” 0,1
0,0 0,0
0,5
1,0
1,5
2,0
2,5
3,0
3,5
4,0
“” (m³/h)
823152
Legend:DE823129L/170408 UK823129L/170408 Legende: “” “”
Volumenstrom Heizwasser Volume flow, heating water
Temp„ Temp„
Temperatur Wärmequelle Temperature, heat source
Qh Qh
Heizleistung Heating capacity
Pe
Pe
Leistungsaufnahme Power consumption
COP
Coefficient of performance / efficiency rating
∆p”
Pressure loss heat pump
VD
Compressor(s)
COP
∆p” VD
Coefficient of performance / Leistungszahl
Druckverlust Wärmepumpe Verdichter
Änd./Ä.M./Ersteller/Datum
- / PEP026-2009 / Opel / 16.04.10
Bezeichnung: Seite: 1/1
Leistungs-Druckverlustkurven LW 101 (A)
Zeichnungsnummer:
823152
Datei: 823152 Leistungs- Druckverlustkurven LW 101 (A).xls
28
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Performance curves
LW 121
Qh (kW)
COP 7
25
6 23
5 4
21
3 19
2 1
17
-20
-15
-10
-5
0
5
10
15
20
25
30
35
20
25
30
35
Temp„ (°C) 15
Pe (kW)
13
6
11
5 35°C 1VD 50°C 1VD
9
4
3
7
5
2 -20
-15
-10
-5
0
5
10
15
20
25
30
35
-20
-15
Temp„ (°C)
-10
-5
0
5
10
15
Temp„ (°C)
∆p (bar) 0,4
0,3
0,2 ∆p” 0,1
0,0 0,0
0,5
1,0
1,5
2,0
2,5
3,0
3,5
4,0
4,5
5,0
“” (m³/h)
823153
Legende: DE823129L/170408 “”
Volumenstrom Heizwasser
Temp„
Temperatur Wärmequelle
Qh
Heizleistung
Pe Legend:
Leistungsaufnahme UK823129L/170408
“” COP
performance / Leistungszahl Volume flow,Coefficient heatingofwater
∆p”
Druckverlust Wärmepumpe
Temp„
Temperature, heat source
Qh
Heating capacity
VD
Verdichter
Pe
Power consumption
COP
Coefficient of performance / efficiency rating
∆p”
Pressure loss heat pump
Bezeichnung:
VD
Compressor(s)
Zeichnungsnummer:
Änd./Ä.M./Ersteller/Datum
- / PEP027-2009 / Opel / 16.04.10
Seite: 1/1
Leistungs-Druckverlustkurven LW 121 (A) 823153
Datei: 823153 Leistungs- Druckverlustkurven LW 121 (A).xls
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
29
1
2
3
4
F
A
B
723 749 846 911
Dimensional drawings <50 0 97 123
LW 101
5
1
4x M8
1353
1298 1261
LR E
661 646
0 749 723
D 746
E
0
Schutzvermerk nach DIN 34 beachten
123 97 0
0 D
4x M8 1298 1261
C
661 646
2 3 5
325 280 205 0
B
0
0
61
631
4
Legende: D819352a Legend: UK819352a Technische Änderungen vorbehalten. in mm. Alle MaßeAll in dimensions mm.
A
A B D E LR
Front view A Vorderansicht Seitenasicht linksview from left B vonSide Seitenansicht von rechts Side view from right D Rückansicht Rear view E Luftrichtung LR
Item 1
30
1 2 3 4 5
Air direction
Designation Control panel Hot water outlet 2(flow) Hot water inlet (return) Bushings for electrical / sensor cables Condensate hose ø i 30
3
G 1" DIN ISO 228 G 1" DIN ISO 228
4
a
PEP 023/2010
-
PEP 026/2009
Zust. Änderungstext
Length from device 1m
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
1
2
3
Installation plan Version 1 1
1 6
<750
OKF
810
2
+20 0
KA 5
FA
B1
FWS
≥200
1
≥150
1590
7
630
E
G +20 0
≥2200 1983
5
LW 101
810
V1
F
4
9
≥700
3
BS
≥1000
4
≥700
LR
FA
≥2100
846
Schutzvermerk nach DIN 34 beachten
B2
D
C
746 ≥2535
Legend:
UK819345a-1
Item
Designation
FWS
All dimensions in mm. Dim.
With finished wall thickness 240 to 320 2060 With finished wall thickness 320 to 400 1980 With finished wall thickness 240 to 320 755 B2 B Legende: 819345a With finished wall thickness 320 to 400 665 Technische Änderungen vorbehalten. Item Alle Maße in mm. Version 1 1 V1 Version 1 floor finished OKF V1 Top edge of 2 OKF Oberkante Fertigfußboden façade FA FA Finished outer 3 Fertigaussenfassade LR LR Air direction 4 Luftrichtung Bedienseite BS BS Operator side 5 FWS Fertigwandstärke thickness FWSKA Finished wall Kondensatablauf discharge KA G Condensate 6 Detail Einbau im Lichtschacht Section in light well Speicher) ≈ 1540mm G Kippmaß derinstallation Wärmepumpe (ohne Achtung! Wird der Unterstellpufferspeicher durch einen A 7 Beistellpufferspeicher ersetzt, muss von allen Höhenkoordinaten 630mm abgezogen werden! Tilting dimension of heat pumps (without tank) ≈1540 9 Notice: If the lower buffer tank is replaced with an additional buffer tank, a sun of 630 must be taken from all of the height coordinates. 1 2 B1
Designation Accessory: wall duct 800x800x420 Accessory air duct 700x700x450 Accessory: air duct 700x700x1000 Accessory: air duct bend 700x700x750 Installation above ground level Accessory: weather guard 845x850 Installation in light well Accessory: rain guard 845x850 provided by customer: light well with water drain min. exposed cross section 0,6m² Minimum clearance for service purposes If the distances were to be reduced to the minimum a to dimension, the air ducts must be made shorter. This leads a significant increase in the sound intensity level! Zust. 3 4
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
31
PEP 0
PEP 0
Änder
1
LW 101 V2
3
4
Installation plan Version 2
1
G
5
1
810
+20 0
F
2
≥2200
≥150
OKF
E
7
630 <750
1590
1983
6
KA
5
2
1 ≥200
810
B1
FWS
FA
+20 0
3 FA
BS
≥700
≥700
≥1000
LR
≥2100
846
Schutzvermerk nach DIN 34 beachten
B2
D
9
4
C
FWS
Legend:
746 ≥2535
UK819345a-2
All dimensions in mm.
Item B1
B
A
Designation With finished wall thickness 240 to 320 With finished wall thickness 320 to 400 With finished wall thickness 240 to 320 B2 With finished wall thickness 320 to 400 Legende: 819345a Technische Änderungen vorbehalten. Version 2 V2 Alle Maße in mm. Top edge of finished floor OKF V2 Version 2 Finished outer façade FA OKF Oberkante Fertigfußboden Air direction LR FA Fertigaussenfassade Operator side BS LR Luftrichtung BS FinishedBedienseite wall thickness FWS FWS Condensate Fertigwandstärke discharge KA KA Kondensatablauf Section installation inim light well G G Detail Einbau Lichtschacht
Dim. 2060 1980 745 665
Item 1 2 3 4 5
Kippmaß der Wärmepumpe (ohne Speicher) ≈ 1540mm Achtung! Wird der Unterstellpufferspeicher durch einen ersetzt, muss von allen Höhenkoordinaten TiltingBeistellpufferspeicher dimension of heat pumps (without tank) ≈1540 630mm Notice: If the abgezogen lower bufferwerden! tank is replaced with an additional buffer tank, a sun of 630 must be taken from all of the height coordinates. 1
32
2
6 7 9
Designation Accessory: wall duct 800x800x420 Accessory air duct 700x700x450 Accessory: air duct 700x700x1000 Accessory: air duct bend 700x700x750 Installation above ground level Accessory: weather guard 845x850 Installation in light well Accessory: rain guard 845x850 provided by customer: light well with water drain min. exposed cross section 0,6m² Minimum clearance for service purposes If the distances were to be reduced to the minimum dimension, the air ducts must be made shorter. This leads to a significant increase in the sound intensity level! 3 4
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
a
PEP 0
-
PEP 0
Zust. Änder
1
2
3
4
5
Installation plan Version 3 F
LW 101
V3
G 1 ≥2200 1983 1590
6
<750
OKF
630
E
≥150
7
KA 810
+20 0
810
+20 0
1570 ≥1000
8 2
5
5
2
FA
1
9
4
≥700
4
LR BS
≥700
≥1000
≥2100
846
Schutzvermerk nach DIN 34 beachten
B2
≥200
FWS
D
1
C
746 ≥2670
Legend:
UK819345a-3
All dimensions in mm.
Item Designation Legende: 819345a Änderungen vorbehalten. With finished wall thickness 240 to 320 B2 Technische B Alle Maße in mm.wall thickness 320 to 400 With finished V3 OKF FA LR BS FWS KA AG
Dim. 320 240
V3 Version 3 Version 3 Oberkante Fertigfußboden OKF FATop edge ofFertigaussenfassade finished floor LR Luftrichtung Finished outer façade BS Bedienseite Air directionFertigwandstärke FWS KAOperator side Kondensatablauf G Detail Einbau im Lichtschacht Finished wall thickness Kippmaß der Wärmepumpe (ohne Speicher) ≈ 1540mm Condensate discharge Achtung! Wird der Unterstellpufferspeicher durch einen Beistellpufferspeicher Section installationersetzt, in lightmuss well von allen Höhenkoordinaten 630mm abgezogen werden!
Tilting dimension of heat pumps (without tank) ≈1540 Notice: If the lower buffer tank is replaced with an additional buffer tank, a sun of 630 must be taken from all of the height coordinates. 1
2
Item 1 2 4 5 6 7 8
9
Designation Accessory: wall duct 800x800x420 Accessory air duct 700x700x450 Accessory: air duct bend 700x700x750 Installation above ground level Accessory: weather guard 845x850 installation in light well Accessory: rain guard 845x850 provided by customer: light well with water drain min. exposed cross section 0,6m² Ventilation separation: Depth: ≥ 1000 a PEP 023/20 Height by light well installation ≥ 1000 PEP 026/20 Height by installation above ground level: ≥ 1000, 300- above Zust. Änderungst weather guard 3 4 Minimum clearance for service purposes If the distances were to be reduced to the minimum dimension, the air ducts must be made shorter. This leads to a significant increase in the sound intensity level!
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
33
LW 101
1
2
3
4
Installation plan Version 4
V4
F
G 1
≥2200 1983 1590
6
<750
OKF
810
2
2570
5
810
+20 0
2
5
FA
1
FWS
1
KA
+20 0
4
4
LR
3
BS
≥700
≥700
≥1000
≥2100
846
Schutzvermerk nach DIN 34 beachten
B2
D
9
≥200
630
E
≥150
7
C
746 ≥3670
Legend:
UK819345a-4
Item B2
Designation With finished wall thickness 240 to 320 With finished wall thickness 320 to 400
All dimensions in mm. Dim. 320 240
Item Legende: Version819345a 4 V4 1 Technische Änderungen vorbehalten. Top edge of finished floor OKF 2 Alle Maße in mm. Finished outer façade FA 4 V4 Air direction Version 4 LR 5 OKF OperatorOberkante Fertigfußboden side BS FA Fertigaussenfassade wall thickness FWS 6 LR FinishedLuftrichtung BS Condensate Bedienseite discharge KA Fertigwandstärke in light well GFWS Section installation 7 KA Kondensatablauf G Detail Einbau im Lichtschacht TiltingKippmaß dimension heat pumps (without tank) ≈1540 9 derofWärmepumpe (ohne Speicher) ≈ 1540mm Notice: If the lower buffer tank is replaced with an Achtung! Wird der Unterstellpufferspeicher durch einen A Beistellpufferspeicher muss be vontaken allenfrom Höhenkoordinaten additional buffer tank, a sunersetzt, of 630 must all abgezogen werden! of the 630mm height coordinates. B
1
34
2
Designation Accessory: wall duct 800x800x420 Accessory air duct 700x700x450 Accessory: air duct bend 700x700x750 Installation above ground level Accessory: weather guard 845x850 installation in light well Accessory: rain guard 845x850 provided by customer: light well with water drain min. exposed cross section 0,6m² Minimum clearance for service purposes If the distances were to be reduced to the minimum dimension, the air ducts must be made shorter. This leads to a significant increase in the sound intensity level!
3
4
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
a
PEP 0
-
PEP 0
Zust. Änder
1
2
3
4
5
LW 121 0 47 53
F
693 699 746 811
Dimensional drawings B
A
4x M8
1523
1
1381
1372
LR
E
720
711
280 0
0
0 61
846
D 699 693
E
53 47 0
Schutzvermerk nach DIN 34 beachten
0
D
0
4x M8 1381
1372 C
720 4
711
5
2
421 164
B
0
61 0
996 896 Legende: Legend: D819354- UK819354 Technische Änderungen vorbehalten. All dimensions in mm. Alle Maße in mm. A
A B D E LR
A
3
0
0
Front view
Vorderansicht Side view from left B von links Seitenasicht view from right D vonSide Seitenansicht rechts Rückansicht Rear view E Luftrichtung
LR
Item 1
1 2 3 4 5
Air direction
Designation Control panel 2 Hot water outlet (flow) Hot water inlet (return) Bushings for electrical / sensor cables Condensate hose ø i 30
3G 1" DIN ISO 228
4
-
PEP 027/200
Zust.
Änderungs
G 1" DIN ISO 228 Length from device 1m
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
35
1
2
3
LW 121 V1
1 +20 0
G 1
810
5
6 7
5
KA
FA
≥200
2
B1
FWS
1
+20 0
≥2100
746
≥700
B2
Schutzvermerk nach DIN 34 beachten
LR
3 4
BS
≥700
FA
C
9
≥1000
810
≥150
1675 <750
OKF
630
E
D
5
Installation plan Version 1
≥2300 2153
F
4
846 ≥2630
FWS
Pos.
Bezeichnung Maß Pos. Bezeichnung Bei Fertigwandstärke 240 bis 320 2160 1 Zubehör: Wanddurchführung 800x800x420 B1 Bei Fertigwandstärke 320 bis 400 2080 2 Zubehör: Luftkanal 700x700x450 Bei Fertigwandstärke 240 bis 320 745 3 Zubehör: Luftkanal 700x700x1000 Legend: UK819346-1 All dimensions in mm. B2 4 Zubehör: Luftkanalbogen 700x700x750 Bei Fertigwandstärke 320 bis 400 665 Item Designation Dim. Einbau über Erdgleiche B Legende: 819346 5 With finished wall thickness 240 to 320 2160 B1 Zubehör: Wetterschutzgitter 845x850 Technische Änderungen vorbehalten. Alle Maße in mm. With finished wall thickness 320 to 400 2080 Einbau im Lichtschacht 6 Zubehör: Regenschutzgitter 845x850 With finished wall thickness 240 to 320 745 B2 V1 Version 1 Bauseits: Lichtschacht mit Wasserablauf With finished wall thickness 320 to 400 665 OKF Oberkante Fertigfußboden 7 Item Designation FA Fertigaussenfassade min. freier Querschnitt 0,6m2 LR Luftrichtung Version 1 1 Accessory: wall duct für 800x800x420 V1 Mindestabstände Servicezwecke: BS Bedienseite Wenn Abstände auf das Mindestmaß Top edge of Fertigwandstärke finished floor air duct bis 700x700x450 OKF FWS 2 Accessory reduziert air werden, muss man die Luftkanäle Finished outer façade duct 700x700x1000 FA KA 3 9Accessory: Kondensatablauf einkürzen. eine700x700x750 erhebliche Erhöhung airDies ducthat bend LR GAir direction Detail Einbau im Lichtschacht 4 Accessory: Wärmepumpe (ohne Speicher) ≈ 1740mm des Schalldruckpegels Folge! Operatorder side above groundzur level BS Kippmaß 5 Installation A Achtung! Wird der Unterstellpufferspeicher durch einen Accessory: weather guard 845x850 Finished wall thickness FWS Beistellpufferspeicher ersetzt, muss von allen Höhenkoordinaten abgezogen werden! Condensate discharge KA 630mm 6 Installation in light well Accessory: rain guard 845x850 Section installation in light well G 7 provided by customer: light well with water drain min. PEP 027/20 exposed cross section 0,6m² Zust. Änderungs 1 2 3 4 Tilting dimension of heat pumps (without tank) ≈1540 9 Minimum clearance for service purposes If the distances were to be reduced to the minimum Notice: If the lower buffer tank is replaced with an 819346_Aufstellungsplan_LW121,_LW90Solar~-.SLDDRW 819346_Aufstellungsplan_LW121,_LW90Sola dimension, the air ducts must be made shorter. This leads to additional buffer tank, a sun of 630 must be taken from all a significant increase in the sound intensity level! of the height coordinates.
36
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
1
2
3
4
V2
1 5
LW 121 G 1
810
F
+20 0
Installation plan Version 2
630
E
≥2300
≥150
7
<750
1675
2153
6
OKF
KA
1
2
5
FA FWS
B1
≥700
746
LR
4
FA
BS
≥700
≥1000
3
9
≥2100
B2
D
Schutzvermerk nach DIN 34 beachten
≥200
810
+20 0
C
FWS
846 ≥2630
Pos.
Bezeichnung Maß Bei Fertigwandstärke 240 bis 320 2160 Legend:B1 UK819346-2 Bei Fertigwandstärke 320 bis 400 2080 Item Designation Bei Fertigwandstärke 240 bis 320 745 B1 B2 With finished wall thickness 240 to 320 Bei Fertigwandstärke 320 bis 400 With finished wall thickness 320 to 400665
Dim. 2160 2080 745 665
Pos. Bezeichnung All dimensions in mm. 1 Zubehör: Wanddurchführung 800x800x420
With finished B2 Legende: 819346 wall thickness 240 to 320 With finished wall vorbehalten. thickness 320 to 400 Technische Änderungen Alle Maße in mm. Item Version 2 1 V2 V2 Version 2 Top edge of finished floor OKF 2 OKF Oberkante Fertigfußboden Finished outer façade FA 3 FA Fertigaussenfassade LR Luftrichtung Air direction LR 4 BS Bedienseite Operator side BS 5 FWS Fertigwandstärke FinishedKondensatablauf wall thickness FWS KA G Detaildischarge Einbau im Lichtschacht Condensate KA 6 Kippmaß der Wärmepumpe Speicher) ≈ 1740mm Section installation in(ohne light well G Achtung! Wird der Unterstellpufferspeicher durch einen A 7 Beistellpufferspeicher ersetzt, muss von allen Höhenkoordinaten 630mm abgezogen werden! Tilting dimension of heat pumps (without tank) ≈1540 9 Notice: If the lower buffer tank is replaced with an additional buffer tank, a sun of 630 must be taken from all of the height coordinates. 1 2 B
819346_Aufstellungsplan_LW121,_LW90Solar~-.SLDDRW
2 3 4
Zubehör: Luftkanal 700x700x450 Zubehör: Luftkanal 700x700x1000 Zubehör: Luftkanalbogen 700x700x750 Einbau über Erdgleiche 5 Zubehör: Wetterschutzgitter 845x850 Designation Einbau im Lichtschacht 6 Accessory: duct 800x800x420 Zubehör:wall Regenschutzgitter 845x850 Accessory airLichtschacht duct 700x700x450 Bauseits: mit Wasserablauf 7 Accessory: airQuerschnitt duct 700x700x1000 min. freier 0,6m2 Accessory: air duct bend Mindestabstände für 700x700x750 Servicezwecke: Installation above ground Wenn Abstände bis auflevel das Mindestmaß 845x850 reduziertweather werden, guard muss man die Luftkanäle 9Accessory: Installation in light einkürzen. Dies well hat eine erhebliche Erhöhung Accessory: rain guard 845x850 des Schalldruckpegels zur Folge! provided by customer: light well with water drain min. exposed cross section 0,6m² Minimum clearance for service purposes If the distances were to be reduced to the minimum dimension, the air ducts must be made shorter. This PEP 0 leads to a significant increase in the sound intensity Zust. Änder 3 4 level!
819346_Aufstellungsplan_LW121,_LW90
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
37
1
2
3
LW 121 F
4
5
Installation plan Version 3
V3
G 1
≥2300 2153 1675
6
<750
OKF
630
E
≥150
7
KA 810
810
1665
+20 0
≥1000
8 2
5
5
2
FA
1
≥200
1
9
4
LR
≥700
≥700
4
BS
≥1000
≥2100 746
B2
FWS
Schutzvermerk nach DIN 34 beachten
D
+20 0
C
846 ≥2770 Bezeichnung Legend: Pos. UK819346-3
Item B2
B
V3
Bei Fertigwandstärke 240 bis 320 B2 Designation Bei Fertigwandstärke 320 bis 400
With finished wall thickness 240 to 320
Maß 370 290
Legende: 819346 With finished wall thickness 320 to 400 Technische Änderungen vorbehalten. Alle Maße in mm.
Version 3
Pos. Bezeichnung All dimensions in mm. 1 Zubehör: Wanddurchführung 800x800x420 Dim. 2 Zubehör: Luftkanal 700x700x450 370 4 Zubehör: Luftkanalbogen 700x700x750 Einbau über Erdgleiche 290 5 Zubehör: Wetterschutzgitter 845x850 Item EinbauDesignation im Lichtschacht 6 1 Accessory: wall duct 800x800x420 Zubehör: Regenschutzgitter 845x850 Bauseits: Lichtschacht Wasserablauf air mit duct 700x700x450 2 Accessory 7 2 min. Querschnitt Accessory: air0,6m duct bend 700x700x750 4 freier Lufttechnische Trennung: Tiefe ≥ 1000mm, levelHöhe … 5 Installation above ground
V3 Version 3 Top edge ofOberkante finished floor OKF Fertigfußboden façade FAFinished outer Fertigaussenfassade LRAir directionLuftrichtung BS Bedienseite Operator side FWS Fertigwandstärke thickness KAFinished wall Kondensatablauf G CondensateDetail Einbau im Lichtschacht discharge Kippmaß Wärmepumpe (ohne Sectionder installation in light wellSpeicher) ≈ 1740mm Achtung! Wird der Unterstellpufferspeicher durch einen A Beistellpufferspeicher ersetzt, muss von allen Höhenkoordinaten 630mm abgezogen Tilting dimension of heat pumps (without tank)werden! ≈1540
OKF FA LR BS FWS KA G
Notice: If the lower buffer tank is replaced with an additional buffer tank, a sun of 630 must be taken from all of the height coordinates. 1
2
819346_Aufstellungsplan_LW121,_LW90Solar~-.SLDDRW
38
8
9
Accessory: weather guard 845x850 ... bei Lichtschachtmontage ≥ 1000mm
light well …6überinstallation Erdgleiche ≥in 1500mm, 300mm über Wetterschutzgitter Accessory: rain guard 845x850 Mindestabstände für Servicezwecke: providedbis byauf customer: light well with water 7 Abstände Wenn das Mindestmaß reduziert werden,drain min. muss man die Luftkanäle einkürzen. Dies hat eine erhebliche exposed cross section 0,6m² Erhöhung des Schalldruckpegels separation: zur Folge! 8 Ventilation
9
Depth: ≥ 1000 Height by light well installation ≥ 1000 Height by installation above ground level: ≥ 1500, 300- above PEP 027/20 weather guard Zust. Änderungs 3 4 Minimum clearance for service purposes 819346_Aufstellungsplan_LW121,_LW90Sola If the distances were to be reduced to the minimum dimension, the air ducts must be made shorter. This leads to a significant increase in the sound intensity level!
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
1
2
3
4
5
Installation plan Version 4 F
LW 121
V4
G 1
OKF
810
2
2665
5
KA
810
5
+20 0
2
FA
1
FWS
1
+20 0
≥200
E
<750
≥150
1675
7
630
≥2300 2153
6
LR
≥700
≥700
4 4
BS
3
≥1000
≥2100
746
Schutzvermerk nach DIN 34 beachten
B2
D
9
C
846 ≥3770
Legend: Pos. Item B2 B2
UK819346-4 All dimensions in mm. Pos. Bezeichnung Bezeichnung Maß Designation Dim. 1 Zubehör: Wanddurchführung 800x800x420 Bei Fertigwandstärke 240 bis 320 370 With finished wall thickness 240 to 320 370 2 Zubehör: Luftkanal 700x700x450 Bei Fertigwandstärke 320 bis 400 290 With finished wall thickness 320 to 400 290 3 Zubehör: Luftkanal 700x700x1000 Item Designation Legende: 819346 4 Zubehör: Luftkanalbogen 700x700x750 B Technische Änderungen vorbehalten. Version 4 wall duct 800x800x420 V4 1 Accessory: Einbau über Erdgleiche Alle Maße in mm. Top edge of finished floor air duct 700x700x450 OKF 25 Accessory Zubehör: Wetterschutzgitter 845x850 Finished outer4façade duct bend 700x700x750 FA 4 Accessory: V4 Version Einbau imair Lichtschacht OKF Oberkante Fertigfußboden Air direction above ground level LR 56 Installation Zubehör: Regenschutzgitter 845x850 FA Fertigaussenfassade Accessory: weather guard 845x850 Operator side BS Bauseits: Lichtschacht mit Wasserablauf LR Luftrichtung Finished wall thickness FWS 67 installation in light well BS Bedienseite min. freier Querschnitt 0,6m2 Accessory: rain guard 845x850 Condensate discharge KA FWS Fertigwandstärke Mindestabstände für Servicezwecke: KA Kondensatablauf Section installation in light well G 7 provided by customer: light well with water drain min. Wenn Abstände bis auf das Mindestmaß G Detail Einbau im Lichtschacht exposed cross section 0,6m² 9 reduziert werden, muss man die Luftkanäle Kippmaß der Wärmepumpe (ohne Speicher) ≈ 1740mm Tilting dimension of heat pumps (without tank) ≈1540 9 Minimum clearance for service purposes Achtung! Wird der Unterstellpufferspeicher durch einen einkürzen. Dies hat eine erhebliche Erhöhung A Notice: If the distances were to be reduced to the minimum If the lower buffer ersetzt, tank is replaced Beistellpufferspeicher muss vonwith allenanHöhenkoordinaten des Schalldruckpegels Folge! dimension, the air ductszur must be made shorter. This additional tank, awerden! sun of 630 must be taken from all 630mmbuffer abgezogen leads to a significant increase in the sound intensity of the height coordinates. level! -
1
2
19346_Aufstellungsplan_LW121,_LW90Solar~-.SLDDRW
3
4
PEP 027
Zust. Änderun
819346_Aufstellungsplan_LW121,_LW90So
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
39
LW 101 – LW 121
40
Row tank
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Separate buffer tank
LW 101 – LW 121
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
41
42
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Heat pump Underfloor heating / radiators Vibration isolation Sylomer strip machine underlay Closure and drainage Expansion vessel packing list Safety valve Closure Heating circulation pump Non return valve/ one way valve Individual room regulation Overflow valve Steamtight insulation Service water circulation pump Mixer circuit three-way mixer (MK1 discharge) Expansion vessel supplied by customer Heating rod (heating) Mixer circuit four-way mixer (MK1 charge) Heating rod (SW) Mixer circuit circulation pump (FP1) Feed circulating pump (reconnect the integrated circulating pump in the heat pump) Manifuld Heating circulation pump Switching valve (heating/service water)(B = normally open) Heating element Brine circulation pump Dirt-trap 0.6 mm mesh Spill-tray für brine mix Wall breakthrough Inlet pipe Brine manifuld Ground collector Ground slinkies Groundwater spring pump Wall bracket Flow switch Suction well Inverted well Rinse fitting heating circuit Circulation pump Brine / Water heat exchanger (cooling function) Three-way mixer valve (cooling function MK1) Cap valve Filler and drainage valve Domestic hot water charging pump Direction of groundwater flow Buffer storage
Seperation tank Gas- or oil-boiler Wood boiler Hot water cylinder Brine pressure switch Swimming pool heat exchanger Geothermal heat exchanger Ventilation system Plate heat exchanger Cooling cylinder Compact distributor Fancoils Solar/ service water cylinder Solar/ service water cylinder Multifunction tank Dual hydraulic module Buffer tank wall mounted Pipe lead-in Ventower Scope of delivery, hydraulic tower, dual Fresh water station Scope of supply water/water booster Accessories water/water booster optional
Room thermostat for cooling (optional) Controls supplied by customer Dew-point monitor (optional) Room thermostat for reference space in packing list Supply heat pump Cooling circuit module box removeable for installation Specific glycole mixture Scald protection / thermostatic mixer valve Solar pump assembly Overflow valve must be closed Packing list hydraulic tower Mounting for additional heating element Minimum distance to thermal decoupling of the mixing valve
51 52 53 54 55 56 57 58 59 61 65 66 67 68 69 71 72 73 74 75 76 77 78
100 101 102 103 104 105 106 107 108 109 110 111 112
Temperature sensor immersion heater
BT19
Comfort board: 15 Mixer circuit three-way mixer (MK2-3 discharge) 17 Temperature difference regulator 19 Mixer circuit four-way mixer (MK2 charge) 21 Mixer circuit circulation pump (FP2-3) 22 Swimming pool circulating pump 44 Three-way mixer valve (cooling function MK2) Changeover valve swimming bath preparation(B = normally open) 47 60 Changeover valve cooling operation(B = normally open) 62 Heat meter (optional) 63 Changeover valve solar circuit(B = normally open) 64 Cooling circulation pump 70 Solar seperation module TB2-3/C Feedwater sensor mixer circuits 2-3 TSS/E Sensor, temperature difference control (low temperature) TSK/E Sensor, temperature difference control (high temperature) TEE/F Sensor external energy source
Temperature sensor 2nd heat generator
Motor valve Mixing valve Split heat pump outdoor unit Split heat pump indoor unit Circulation pump Switching valve Connection 2nd heat generator Outdoor temperature sensor Flow temperature sensor Return temperature sensor Domestic hot water temperature sensor Flow temperature liquefier
79 80 81 82 83 84 113 BT1 BT2 BT3 BT6 BT12 BT24
External sensor Domestic hot water sensor Feedwater sensor mixer circuits 1 Floor tmperature limiter Sensor external return Line pressure regulator valve Sensor return (hydraulic module, dual)
TA/A TBW/B TB1/C D TRL/G STA TRL/H
140304
These hydraulic diagrams are schematic representations and are for assistance only. They do not relieve of the obligation to carry out appropriate planning! They do not include all necessary shut-off valves, ventilator fittings or safety devices. These must be incorporated in accordance with the standards and regulations applicable to the respective installation. All country-specific standards, laws and regulations must be observed! The tubes have to be dimensioned according to the nominal volume flow of the heat pump resp. the free pressing of the integrated circulating pump. For detailed information and advice please contact our local sales partner!
Important notice !
24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 48 49 50
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 18 19 20 21 23
Legend hydraulic diagramm
LW 101 – LW 121 1
2
3
5
L1
-F11
A3
N
-F12
L3
5
L2
3~N/PE/400V/50Hz
ÄM 999/2010
3
1L2
1L3
2
5
Datum Bearb.
N N
N
N
14.04.2010 Achim Pfleger
PE
PE
PE
PE
8
9
L1
L1
MOT
9
11
13
14
-X4
15
15
16
16
Bl von Anz 1/1
Blatt-Nr. 1
10 - 24 kW
TRL
12
ZIP
831171
14
GND
A1
ZIP
M M
MA1
MIS
13
GND
-X3
BUP
ZW2/SST
12
TB1
11
FP1 ZUP
M M
HUP
ZUP
MZ1
10
10
TB1
GND
-X2
EVU
ZW1
GND
PEX
Hot water circulating pump/switching valve Energy supplier contact; closed on release; bridge if no blocking interval Pump for mixing circuit 1 Heating circuit circulating pump Charge/discharge/cooling mixer 1 open Charge/discharge/cooling mixer 1 closed Overload protection; internally wired No function Accessories: Remote control External sensor Sensor mixing circuit 1 Hot water gauge/thermostat External return sensor Ventilator; internally wired Terminal strips on controller board (see sticker) Terminal strip in switchbox of heat pump; N/PE distribution for external 230V units Power supply compressor; 3x400V; Important: Clockwise rotary field is absolutely necessary! Power supply additional heating; 3 x400V Power supply controller 230V Auxiliary circulation pump circulation pump Control signal of additional heat generator 1; internally wired Control signal of additional heat generator 2 (alternative is general malfunction)
10X530-10X537;
8
RFV
RFV
-X0
HUP
BUP
7
PE
UK831171a Function Controller board; Attention: I-max = 6A/230VAC Terminals in heat pump switchbox Sub-distribution unit internal installation Hot water or buffer storage tank 3-pol. Cut out compressor; Attention: Right-hand rot. field is mandatory! Cut out auxiliary heating 1 Cut out controller unit Cut out auxiliary heating 2 Contactor electric heating element hot water or buffer tank
VBO
6
PE
7
ASD
A2
N
Air water inside 10 - 24kW
N
6
L1
-X10
PE
Legend: Name A1 A2 A3 A4 ZW2 F10 F11 F12 F13 ZW2 K13 ZW2 Terminals BUP EVU FP1 HUP MA1/MIS MZ1/MIS MOT PEX RFV EVU TA TB1 TBW TRL VBO X0-X4 X10 X10:L1,L2,L3,PE X10:1L1,1L2,1L3,1N,PE X10:L,N,PE ZUP ZIP ZW1 ZW2/SST
L
5
A2
A1
PE
Achim Pfleger
1N Name
N
4
3
1L1
07.07.2010
4
Datum
GND
TA
TA
TBW
GND
TBW
A4
PEP 026-029/2009
2
a
Änderung
-
1
Zustand
PE
1~N/PE/230V/50Hz B10 A
ZW2
5
A1 A2
-K13
-F10
3~N/PE/400V/50Hz
Information on fuses can be found in the technical data
-F13
3~N/PE/400V/50Hz
Terminal diagram LWI 101-251 LUX2
Terminal diagram
43
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
1
2
ws PE
3
4
-Q1 /2.B3
-Q11
-M1 1
2
M
3
-Q1 /2.B3
PE
4
5
5
-S10 -E20
-F4
-G1 1
6
M
1~ -G1
VEN
2
PE
3
4
-F3 -E23
com
817335
1
7
2
7
3
+10V 0-10V GND
-Q5
sw br 1
3
5 2 ws
VD1
3~ -M1
6
NC
/2.B5
ZW1
-E22 6 4 sw br
-X10
5
N PE
A
-X10
3
Stromlaufplan
UK 817335d Function
ZW1
VENT1 VD1 VD1 ZW1
02.12.2015 Pfleger
2
AIT ait-deutschland GmbH
Sump heating for compressor 1 Auxiliary heating Nozzle heating fan Motor protection fan Fan fuse 6.3 A Fan` Compressor Contactor for compressor 1 Contactor for auxiliary heating Starting current limit compressor Thermostat Sump heating for compressor 1 Terminal in switch box heat pump AP Datum AP Bearbeiter AP Geprüft Name Norm
LW 101-121
Legend: Equipement
E20 E22 E23 F3 F4 G1 M1 Q1 Q5 Q11 S10 X10
28.04.2011 21.11.2014 02.12.2015 Datum
4
L1,L2,L3,PE; power supply, output, compressor; clockwise rotary field is absolutely necessary! 1L2,3L4,5L6,7N,PE; power supply, additional heating
3~N/PE/400V/50Hz
L1 L2 L3 N PE
3~N/PE/400V/50Hz 3~N/PE/400V/50Hz
3~N/PE/400V/50Hz
1L1 1L2 1L3 1N PE
ÄM012/2011 ÄM037/2014 ÄM066/2015 1
L
1 3 5 2 4 6
21 22
1 3 5 2 4 6 L1 L2 L3 T1 T2 T3
T1 T2 T3 PE
B
C
D
E
F
b c d
R. Änderung
L Reg
N Reg
E23
+10V 0-10V GND
8
8
/2.B1
/2.C1
/2.B1
/2.B1 /2.B1 /2.B1
Blatt 1 3 Bl.
F
E
D
C
B
A
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
44
Circuit diagram 1/3 LW 101 – LW 121
LW 101 – LW 121 Circuit diagram 2/3
A
-K10
/1.A8 /1.B8 /1.B8 /1.B8 /1.B8
/1.A8
1
Datum
-K3
2
+13 14
-X10
Datum Bearbeiter Geprüft Name Norm
02.12.2015 Pfleger
2
-F1
3
HD
VD1
-Q1
a1
b2 c4
sw bl
-X1
P HDP
AIT ait-deutschland GmbH 3
VD1
rt
-K3
VBO
AV
-X3
-STB
-Q5
ZW1
5
-X1
-F2
P NDP
ND
sw
Stromlaufplan
sw
LW 101-121 5
-B10 P
AEP
1
b2 c4
a1
2
6
PE
6
-X0
L L L
817335
-X2
EVU
7
7
8
45
8
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
4
VBO
28
-X10
-K10
4
MOT ASD EVU
1
-X0
L Reg E23 GND 0-10V +10V
N Reg
-X10
-R51
ZW1
A1 A2
A1 A2
A1 A2
UK 817335d Function
-R50
3
Legend: Equipement
2
L/N/PE: Control supply Defrosting pressostat Energy supplier contact; closed on release; bridge if no blocking interval High-pressure switch Low-pressure switch Optocoupler, switching on the fan Controller board; Attention: I-max = 6,3A/230VAC Defrosting valve Contactor for compressor 1 Contactor for auxiliary heating 3,24 kOhm Voltage divider 7,50 kOhm Voltage divider Safety temperature limiter heating element Terminal in switch box heat pump
1~N/PE/230V/50Hz
1
1~N/PE/230V/50Hz AEP B10 EVU HDP F1 NDP F2 K3 K10 K20 VD1 Q1 ZW1 Q5 R50 R51 STB X10
R. Änderung
c4 a1
B
C
D
E
F
L N PE L N PE
Bla
A
B
C
D
E
F
-K10
1
-X4
-R7 TA
Datum
GND
-X4
-R8
-X4
-R9
RFV
RFV
02.12.2015 Pfleger
2
GND
GND
AIT ait-deutschland GmbH 3
-X5
-R2
TWE
TWE
4
4
-X5
-R3
TWA
TWA
5
-X5
TRL TRL
-R4
Stromlaufplan
GND
LW 101-121 5
-X5
-R5
TVL
6
6
TVL
3
-X4
-R11 TB1
TB1
2
GND
UK 817335d Function
TBW
TBW
Controller board; Attention: I-max = 6,3A/230VAC If installed: heat source input gauge If installed: heat source outlet gauge Return sensor Flow sensor Hot gas sensor External sensor Hot water gauge/thermostat Accessories: Remote control Encoding resistor 1470 Ohm Sensor mixing circuit 1
Datum Bearbeiter Geprüft Name Norm
TA
TWE TWA TRL TVL THG TA TBW RVF CW TB1
Legend: Equipement
1
K10 R2 R3 R4 R5 R6 R7 R8 R9 R10 R11
R. Änderung
817335
-X5
-R6
THG
THG
7
-X5
CW
-R10
CW
7
8
8
Blatt 3 3 Bl.
F
E
D
C
B
A
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
46
Circuit diagram 3/3 LW 101 – LW 121
GND
GND
GND
GND
GND
EC Declaration of Conformity in accordance with the EC Machinery Directive 2006/42/EC, Annex II A
The undersigned confirms that the following designated device(s) as designed and marketed by us fulfill the standardized EC directives, the EC safety standards and the product-specific EC standards. In the event of modification of the device(s) without our approval, this declaration shall become invalid.
Designation of the device(s) Heat Pump Unit model LW 71A LW 81A LW 101A LW 121A LW 140A LW 180A LW 251A * LW 310A * LW 100H-A LW 180H-A LW 100H LW 180H LW 160H-A/V LW 160HL/V
Unit model LW 101 LW 121 LW 140 LW 140L LW 180 LW 180L LW 251 * LW 251L * LW 310 * LW 310L * LW 380/1 * LW 380L/1 * LW 160H/V
Number 100 530 100 531 100 532 100 533 100 534 100 535 100 536 100 537 100 538 100 539 100 474 100 475 100 623
EC Directives 2006/42/EG 2009/125/EG 2006/95/EG 2010/30/EU 2004/108/EG *97/23/EG 2011/65/EG * Pressure equipment component Category II Module A1 Designated position: TÜV-SÜD Industrie Service GmbH (Nr.:0036)
Standardized EN EN 378 EN 60529 EN ISO 12100-1/2 EN ISO 13857
EN 349 EN 60335-1/-2-40 EN 55014-1/-2 EN 61000-3-2/-3-3
Company: ait-deutschland GmbH Industrie Str. 3 93359 Kasendorf Germany
Place, date:
Kasendorf, 14.12.2015
UK818154e
Number 100 540 100 541 100 542 100 543 100 544 100 545 100 546 100 547 100 587 100 589 100 586 100 588 100 625 100 624
Signature: Jesper Stannow Head of Heating Development
Subject to change without notice | 83054300eUK – Translation into English of the original German operating manual | ait-deutschland GmbH
47