Transcript
Z SND - Q RANGE DQ NON-INTRUSIVE INTELLECTUALIZED ELECTRIC ACTUATORS
OPERATION INSTRUCTION
CHANGZHOU POWER STATION AUXILIARY EQUIPMENT WORKS Ltd.
CONTENT
PAGE
1.
GENERAL DESCRIPTION OF ACTUATOR ························································································ 1
2.
MAIN TECHNICAL PARAMETERS ···································································································· 1
3.
REPRESENTATION OF TYPE ·············································································································· 2
4.
GENERAL SAFETY DESCRIPTIONS ·································································································· 2
5. TRANSPORTATION AND STORAGE ·································································································· 3 6.
INSTALLATION AND CONNECTION ································································································ 3 6.1 ASSEMBLY BETWEEN ACTUATOR AND VALVE ···································································· 3 6.2 ELECTRIACAL WIRING ··············································································································· 4
7.
MANUAL AND ELECTRIC OPERATION ·························································································· 5 7.1 MANUAL OPERATION ················································································································· 5 7.2 ELECTRIC OPERATION ··············································································································· 5 7.3 LOCAL/REMOTE OPERATION ······················································································· 6 7.4 SITE VALVE POSITION INDICATION ······················································································· 6 7.4.1 OPERATION INTERFACE ········································································································ 6 7.4.2 DISPLAY OF VALVE OPEN AND CLOSE ················································································· 7
8.
SETTING AND COMMISSIONING OF PARAMETERS ···································································· 7 8.1 SETTING AND COMMISSIONING METHODS OF PARAMETERS ········································· 7 8.2 ENTERING PAGE LAYOUT OF OPTION SETTING ··································································· 8 8.3 SETTING OF PARAMETERS ········································································································ 8 8.3.1 SETTING OF TRAVEL PARAMETERS ····················································································· 8 8.3.1.1 SETTING OF CLOSING TRAVEL LIMIT ··············································································· 9 8.3.1.2 SETTING OF OPENING TRAVEL LIMIT ··············································································· 9 8.3.2 SETTING OF OPENING PROPORTION, AND 4~20mA ANALOG SIGNAL ······················ 10 8.3.3 SETTING OF TORQUE PARAMETERS ·················································································· 10 8.3.3.1 SETTING OF TORQUE VALUE IN CLOSING DIRECTION ·············································· 10 8.3.3.2 SETTING OF TORQUE VALUE IN OPENING DIRECTION ·············································· 11 8.3.4 SETTING OF REMOTE CONTROL MODE ············································································ 11 8.3.5 SETTING OF DOUBLE SPEED CONFIG (SLOW CLOSING) ··············································· 12 8.3.5.1SETTING OF START POINT OF DOUBLE SPEED CONFIG (SLOW CLOING) ··············· 13 Ⅰ
8.3.5.2 SETTING OF DUTY FACTOR OF DOUBLE SPEED CONFIG (SLOW CLOING) ·············· 13 8.3.6 SETTING OF MID POSITION ····································································································· 13 8.3.7 OPTION OF LANGUAGE ······························································································ 15 8.3.8 SETTING OF PASSWORD CONFIG·····························································································15 8.3.9 EMERGENT SELF-HOLD····················································································· 16 8.3.10 SETTING OF MODBUS ······························································································ 17 8.3.11 PARAMETERS INTERROGATING ························································································· 18 9. INFRARED SETTING TOOL (RC-01) ··································································································· 19 9.1 INTRODUTION OF FUNCTION KEYS ························································································· 19 9.2 USAGE ·············································································································································· 19 9.3 SETTING AND ADJUSTING OF PARAMETERS ········································································· 19 10. FIELDBUS CONTROL ························································································································· 20 11. MAINTENANCE AND TROUBLESHOOTING ················································································· 20 11.1 MAINTENANCE ··························································································································· 20 11.2 TROUBLE DISPLAY AND TROUBLESHOOTING ··································································· 20 12. SCHEMATIC CIRCUIT DIAGRAM AND WIRING DIAGRAM ······················································· 22
APPENDIX: APPENDIX (A) Sctruture sketch drawing ····································································································24 APPENDIX (B) Overall size and connection dimensions of SND-Z Range ··············································· 25 APPENDIX (C) Overall size and connection dimensions features and main technical parameters of SND-Q range ··································································································28 APPENDIX (D) Main technical Parameters, Overall size and connection dimensions of SND-DQ ·········· 30 APPENDIX (E) Technical Parameters Table of SND-Z ·············································································· 33 APPENDIX (F ) Communication protocol of MODBUS for SND Range··················································· 34 APPENDIX (G) Communication protocol of PROFIBUS-DP for SND Range········································· 36
1 II
1. GENERAL DESCRIPTION OF ACTUATOR SND non-intrusive intellectualized electric modulating actuators are products of new generation developed by cooperation on the basis of introducing the newest control technology from international. These mechanic-electronic products have been integrated advanced multi-control technologies such as absolute coding technology, sensor technology, bus-mastering technology, infrared remote control technology, LED, magnetic control switch and advanced manufacturing technology. SND Range products are units to control the operation of final control element (e.g. valves) in open control system. Among the rest, SND actuators of Range Z are used for the control of globe valve, gate valve, throttle valve, water gate and etc. And SND actuators of Range Q and DQ are used for the control of ball valve, butterfly valve, and damper etc.
Fig 1
FEATURES OF ACTUATORS •Non-intrusive design is audio-visual and easy to adjust. •Measurement of position and torque is accurate and reliable. •Provided with speed-changeable and slow closing functions •Comprehensive data recording •Self-diagnostic and self-adapting functions •Automatic phase-rotation-corrective function •Trouble-diagnostic function in operation • Functions of network transmission •Overheat-protection for electric motor •Transient reverse protection •Capable to carry out valve closing at high speed •Capable to compensate valve seating at high temperature •Enclosure protection of IP68 (7 meter below water surface for 72 hours) •Provided with two series products of normal model and flame-proof model •Small in size, light in weight and extensive in speed range
2. MAIN TECHNICAL PARAMETERS 1) Power supply: 380 V, 50 Hz Optional: 380~660 V, 50 or 60 Hz, specified when ordering 2) Service environment (1) Environmental temperature: -20~60℃; Optional: -40~ +70℃ (2) Relative humidity: ≤90% (+25℃) (3) Enclosure protection: IP68 (7 meter below water surface for 72 hours) (4) Flameproof specification: Exd Ι, ExdibⅡBT4 and ExdibⅡCT4. The ExdibⅡCT4 is for special order. (5) Flameproof mark: Exd Ι, ExdibⅡBT4 and ExdibⅡCT4, for hazardous zone with Class ⅡB ~ⅡC explosive gases of temperature groups T1~T4. 3) The motor is of short time duty. Rated operating time is 15 min. Insulation: Class F
-1-
3. REPRESENTATION OF TYPE
B means Flame-proof specifications Common specifications without letters Output speed:r/min Connection mode:T is thrust mode,I is power station mode, Normal torque mode without letters Output torque:10N· m Type of product:Z means multi-turn; and Q or DQ means part-turn Type of product 4. GENERAL SAFETY DESCRIPTIONS This manual instruction is guidance for users to install, adjust and inspect the actuators of SND Range correctly. Users shall read this manual carefully and thoroughly before operating. Warning: Installation, commissioning and maintenance of valve must be performed by qualified personnel and inspected by quality inspector of speciality.
Electrical connection, mechanical installation and maintenance of actuator shall accord with general fitting and safety regulations, requirements specified by local authority and your factory as well as the conditions and relevant technical datas included in this manual. Meanwhile, the operators shall use protective articles (such as glasses, fatigue dress and gloves),tools, lifting and transportation facilities properly. Warning: If the electric actuator need to be installed in dangerous gas zone, you must check whether flame-proof classification indicated in the name plate is conformed to the environment.
In hazardous zone, electricity conductor or heat conductor is forbidden to contact the electric actuator. Repair and maintenance shall be performed after the actuator is cut off power supply, disassembled from the valve and transferred to non-hazardous zone excepting special permission. Warning: Maximum temperature of motor surface may reach 135℃.
We ensure consumers a quality guarantee to every electric actuator we delivered. The expiration of quality guarantee is one year since the date when the first consumer installed it, or 18 months since the delivering. Between both guarantee expirations, the one of which the closing date comes first is valid. Warranty void if misused, incorrect assembled, corroded, and modification or repair without authorization, as well as for the products or parts provided by other manufacturers. We should charge customers normally for maintenance service due to improper installation, operation and maintenance.
-2-
5. TRANSPORTATION AND STORAGE l Solid package is used for the transportation of electric actuators to the site of installation. l Before delivering electric actuators are perfect and each unit is appended with test report and conformity certificate. It is necessary to handle appropriately during transportation to hold the perfect performance of actuators. l Enclosure protection class of the actuator is IP68 and this enclosure can be kept only under correct storing and site installation /connection. l If the electric actuator cannot be installed immediately, it shall be kept in dry environment and placed on wooden board with dustproof measure. l If the actuator is stored outdoor, it shall be properly protected. It shall be prevented from damage due to weather changing (covered with waterproof canvas or similar stuffs). The actuator should be placed on wooden board or platform off the ground to avoid touching the ground directly. 6. INSTALLATION AND CONNECTION 6.1 ASSEMBLY BETWEEN ACTUATOR AND VALVE l Before assembling, it is necessary to check if output shaft and flange of the actuator is fit to the valve. A gap of 1~2 mm in axial direction should be provided between the three-claw output shaft of the actuator and the passive shaft. Joint surfaces of actuator and valve should be cleaned. l During assembling, you should lift the actuator with feasible rope. It is not permitted to lift the actuator and its assemblies by binding them. l Ensure that the actuator is aligned with the valve. Avoid knocking and vibrating. Any application of other forces is not permitted. l Fastening bolts (with spring washers) connecting actuator and valve shall be of strength level 8.8 at least. They shall be tightened evenly and in diagonal sequence.
Correct lifting
Fig 2 6.1.1 Assembly of thrust base The actuator of thrust mode is a combination of a thrust attachment and an actuator of torque mode as shown in Fig 3. Before assembling with valve, users or suppliers in package should machine the valve stem nut according to the parameters of the stem. Loosen the crew, remove the attachment and take out the nut. When reassembling, pay attention to omitting and damaging seal O-ring. Maximum thrust force the actuators of thrust mode could stand and maximum stem diameter shall not be above relevant specifications, or may result in parts damage. Fig 3
-3-
6.2 ELECTRIACAL WIRING Before wiring, check if the voltage of power supply is conformed to the voltage indicated in name plate of electric actuator. When wiring or commissioning, need to open the cover of the terminal chamber only. Terminals are round plug and round socket style.
Fig 4 Fig 5 Loosen the four screws fixed on the cover with a hexagonal socket (Allen) wrench of 6 mm and then pull out the terminal plug (see Fig 4). Back off the gland nut on the cover; take out the steel plug in seal ring. Then put in the metal washer and turn the gland nut on (see Fig 5). Caution: Do not lever off the cover with screwdriver. Levering off with screwdriver will damage O-ring and the certificated flame-proof joint surfaces. Prompt: Cables with diameter of Φ15 mm or Φ19 mm is allowed to lead through the seal ring.
Fig 6 Fig 7 Remove the terminal plug off the cover as shown in Fig 6 and connect power supply and wire the control line, insert the leads of cable into pins of terminal plug and then tighten screws to lock wiring ends according to the schematic circuit diagram and wiring diagram presented in Chapter 12 of this manual. Turn the terminal plug tight on the cover of terminal chamber and then plug it into the sockets on the actuator, meanwhile pay attention to the gap direction as shown in Fig 7. Finally tighten the gland nut on the cover of terminal chamber. There is an earthing mark on actuator housing. It must be connected properly before turn on power supply. Caution: During installation, ensure that sealing of cable entry and terminal cover is in good condition so that it can meet with the protection specifications. -4-
Caution: Pay attention to the internal ground wiring when removing the terminal plug. When power and control line leads are connected into the plug pins, the lead end shall be covered with insulation sleeve. Shielding cable shall be used for analog signal or digital signal and both ends of shielding layer shall be earthed. 7. MANUAL AND ELECTRIC OPERATION 7.1 MANUAL OPERATION
Fig 8 Fig 9 For SND-Z Range actuators, press down the manual/electric shift handle as shown in Fig 8 to make it on manual operation position.(When the shift handle can not be pressed down, turn the handwheel a little, then the handle may be pressed down. ) Undo the handle, it will turn back to original position. Rotate the handwheel till it gets mesh with the shift. Then the valve can be operated by handwheel (See Fig 9). When electric energized, the shift mechanism will declutch and turn back to electric operation mode automatically. And SND-Q Range actuators are provided with automatic clutch device, so no such shift handle are provided. 7.2 ELECTRIC OPERATION Put the red knob on OFF status and black knob on STOP status as shown in Fig 10, and then turn on power supply. At this time, the indicating lamp of power supply on cover of terminal box lights, LCD is backlit and comes forth OFF page layout. The electric actuator is provided with the function of automatic phase rotation correction. So it has no use for checking the phase sequence. When the power supply is turned on, the electric actuator will test the operating circuit automatically to ensure correct operation. If the equipment is abnormal, the troublestatus will present on local LCD and the remote set point signal will start alarm.
-5-
Fig 10
7.3 LOCAL/REMOTE OPERATION
Fig 11 Local control
Fig 12 Remote control
The red knob located on the bottom of the cover of terminal chamber is provided for the operating selection of local control or remote control. Each operation mode may be padlocked. Local operation: rotate the red knob clockwise to Local control position. The actuator is in local operation mode at present. Then local operation of opening and closing can be carried out by black knob adjacent. Rotating the black knob to STOP position, electric operation of the valve will stop. Remote operation: rotate the red knob counter-clockwise to Remote control position. The actuator is in remote operation mode at present and can only perform remote operating instruction. Then operation of black knob for opening and closing is invalid. 7.4 SITE VALVE POSITION INDICATION 7.4.1 The display consists of: [1] Infrared receiver [2] Indication of control mode [3] Reverse position indication [4] Valve position indication [5] Icon indication of valve opening or seating status [6] Indication of locked password [7] Percentage indication of torque [8] Red indicating lamp for valve opening [9] Red knob [10] Padlock and locking plate [11] Yellow indicating lamp for power supply [12] Black knob [13] Green indicating lamp for valve seating [14] Display of over torque [15] Display of motor overheat [16] Display of power failure [17] Monitoring for mechanical faults [18] Display of power phase sequence [19] LCD
Fig 13
-6-
7.4.2 DISPLAY OF VALVE OPENING AND CLOSING When valve is opening, the red lamp flashes; and when the valve reaches preset position, the red lamp lights steadily. When the valve is closing, the green lamp flashes; and when the valve reaches preset position, the green lamp lights steadily. During the course of opening or closing, LCD displays the status of valve opening or closing with numeral percentage and icon indication. As soon as power supply is turned on, the backlight of LCD is illuminated. Opening proportion of valve and alarming icon of trouble status will appear on LCD. When power supply is turned off, LCD gets dark and various output set point signals disappear. If power supply is off and consumers still want to know relevant parameters and various output set point signals on LCD, they need be provided with a standby DC uninterrupted power supply of 24 V, with power more than 8 W.(for each unit) 8. SETTING AND COMMISSIONING OF PARAMETERS 8.1 SETTING AND COMMISSIONING METHODS OF PARAMETERS 8.1.1 Without removing the cover of terminal chamber, there are two ways to set and commission parameters.
Fig 14 Fig 15 You may simply, safely and fast set or adjust various parameters such as torque level, travel limit and control mode with a RC-01 Infrared Setting Tool of Intrinsic Safety Type (as shown in Fig14), or by the two knobs on electric cover (as shown in Fig 15). RC-01 Infrared Setting Tool of Intrinsic Safety Type is more suitable to explosive hazardous area. Prompt: After the completion of adjustment with RC-01, press “off key” and enter the page layout of “OFF”, then the knobs can be manipulated. 8.1.2 All set data are recorded to data logger built in the actuator. Consumers may view all functions on LCD window via the two knobs on electric cover or the Infrared Setting Tool. 8.1.3 The procedure of setting and commissioning parameters are divided into two stages: enter page layout of Option Setting at first, and then enter page layout of Parameter Setting or Parameter Interrogation. Importance: in the course of setting and commissioning, the two knobs come up with different effects on different page layout. -7-
8.2 ENTERING PAGE LAYOUT OF OPTION SETTING Importance: instruction of functions of the knob Entering page layout of Option Setting, OPEN and CLOSE of black knob makes menu frame on page layout up shifting and downward shifting respectively.
Fig 16 Fig 17 Fig 18 On CL(OSE) or normal operating pages layout, make black knob on electric cover at ST(OP) status and red knob at Setting status as shown in Fig 16, page layout of Option Setting comes up. You can up shift or downward shift menu frame on page layout to select relevant option by turning black knob to OPEN or CLOSE position. Refer to Fig 17 and Fig 18. When selection is finished, turn black knob to STOP status. Selected page layout will appear 3 seconds later, and relevant parameters setting may be performed.
Prompt: If the red knob is locked, it can be rotated only when the locking plate is removed. 8.3 SETTING OF PARAMETERS 8.3.1 SETTING OF TRAVEL PARAMETERS When installation of actuator is finished, the actuator can be operated only after it is set in accordance with valve travel. Figures of the setting of travel parameters are provided by absolute coding electronic limit controller and each setting of these figures is a unique value among whole valve travel course.
-8-
8.3.1.1 SETTING OF CLOSING TRAVEL LIMIT
Fig 19
Fig 20
Fig 21
Entering page layout of Position Setting, turn black knob from STOP status as shown in Fig 19 to CLOSE status as shown in Fig 20, the actuator will operate in closing direction. Meanwhile figures indicating current proportion of opening will change continuously on top portion of page layout and prompt of “SET PARA” (Please set parameters...) will appear on bottom of page. As soon as it reaches fully closed position the consumer approves, turn black knob to STOP status. It may also be stopped by effect of torque control automatically and then turn red knob to Local Control status as shown in Fig 21, and hold it for 3 seconds till “CL CONFIG” (Setting of closing travel is finished) appears on bottom portion of page layout. At this time, figures indicating closing direction appears on layout shall be identical with figures indicates current proportion of opening.
Prompt: during the course of setting, users may also turn black knob to operate actuator opening or closing for proper setting of fully closed.
8.3.1.2 SETTING OF OPENING TRAVEL LIMIT
Fig 22 Fig 23 Fig 24 Entering layout of Position Setting, turn black knob from STOP status as shown in Fig 22 to OPEN status as shown in Fig 23, the actuator will operate in opening direction. Meanwhile figures indicating current proportion of opening will change continuously on bottom portion of page layout and prompt of “SET PARA” (Please set parameters…) will appear on bottom portion of page layout. As soon as it reaches fully opened position the consumer approves, turn black knob to STOP status and turn red knob to Remote Control status as shown in Fig 24, and hold it for 3 seconds till “OP CONFIG” (Setting of opening position is finished) appears on bottom portion of page layout. At this time, figures indicating opening appears on layout shall be the same as figures indicating current proportion of opening. -9-
Prompt: during the course of setting, users may also turn black knob to operate actuator opening or closing for proper setting of fully open. When position Setting is finished, enter OFF page layout. For detailed operation, please see 7.2 ELECTRIC OPERATION. 8.3.2 SETTING OF OPENING PROPORTION, AND 4~20mA ANALOG SIGNAL when full open and full close position is set, any random position within whole travel will be calculated by the actuator automatically, and percentage of position will appear on LCD to indicate local valve position. If analog signal of 4~20 mA is sent out at the same time, setting of signal is also finished automatically. 8.3.3 SETTING OF TORQUE PARAMETERS Before leaving factory, torque level of actuator has been configured according to consumer’s ordering requirement and set value is filled in certificate form of product quality. If there is not such requirement in consumer’s order list, for SND-Z range, torque value in closing direction and in opening direction is set to respectively 70% and 100% of nominal torque value; for SND-Q range, torque value in both closing direction and in opening direction is set to 100% of nominal torque value in general. Consumers may adjust the set value in accordance with their actual requirement. Adjustable range of torque value in opening direction is 80%~120% of nominal torque value, and that in closing direction is 30%~100%. Requirement beyond such range should consult with us before ordering. Importance: instruction of functions of the knob On page layout of Torque Setting, Local Control and Remote Control of red knob is used as confirmed key for setting of closing torque and setting of opening torque respectively.
8.3.3.1 SETTING OF TORQUE VALUE IN CLOSING DIRECTION
Fig 25
Fig 26
Fig 27
Entering page layout of Torque Setting, turn black knob from STOP status as shown in Fig 25 to CLOSED status as shown in Fig 26, torque in closing direction may be set. A prompt of “SET PARA” (Please set parameters...) will appear in the bottom portion of the page. Setting value of closing torque on top of page layout decreases from 100% to 30% in continuous decrement of 1%. As soon as it reaches the -10-
percentage of torque level in closing direction that the consumer approves, turn black knob to STOP status and turn red knob to Local Control status as shown in Fig 27, and hold it for 3 seconds till “CL CONFIG” (Setting of closing torque is finished) appears in bottom portion of page layout, i.e. the percentage of torque in closing direction has been set. 8.3.3.2 SETTING OF TORQUE LEVEL IN OPENING DIRECTION
Fig 28 Fig 29 Fig 30 Entering page layout of Torque Setting, turn black knob from STOP status as shown in Fig 28 to OPEN status as shown in Fig 29, torque in opening direction may be set. A prompt of “SET PARA” (Please set parameters…) will appear in the bottom portion of page layout. Setting value of opening torque on page layout decreases from 120% to 80% in continuous decrement of 1%. As soon as it reaches the percentage of torque in opening direction that the consumer approves, turn black knob to STOP status and turn red knob to Remote Control status as shown in Fig 30, and hold it for 3 seconds till “OP CONFIG” (Setting of opening torque is finished) appears in the bottom portion of page layout, i.e. the percentage of torque in opening direction has been set. When Torque Setting is finished, enter OFF page layout. For detailed operation, see 7.2 ELECTRIC OPERATION. 8.3.4 SETTING OF REMOTE CONTROL MODE Before leaving factory, Remote Control Mode is set as long-distance self-hold. There are 4 types of Remote Control Mode: self-hold, clicking, On-opening, and On-closing. l Self-hold style can carry out valve opening, closing and stopping control; control signal shall last for 500 mS. l Clicking style can carry out valve opening and closing control; control signal shall last till it reaches required position. l On-opening style can carry out valve opening and closing control by two wires and a single passive contact; valve opens when passive contact is on and closes when passive contact is off. l On-closing style can carry out valve opening and closing control by two wires and a single passive contact; valve opens when passive contact is off and closes when passive contact is on. Emergent Self-hold can override other kinds of control signal and enforce its implementation. This signal will last till the valve reached preset position. Emergent Self-hold is a kind of remote control signal but it does not appear in the page layout of remote mode. It is always valid whenever the actuator is in any status among local operation, remote control, off status and motor thermal protection status
-11-
Importance: instruction of functions of the knob Entering the page layout of Remote Control, both OPEN and CLOSE of black knob can make the symbol of “√” move up and down among all selections circularly. Local Control or Remote Control of red knob can be used as confirmed key for Remote Control mode. Prompt: For the wiring of 4 styles of Remote Control Mode and Emergency Self-hold, see Chapter 12 in this instruction manual.
Fig 31
Fig 32
Fig 33
Entering the layout of Remote Control Mode, A prompt of “SET PARA ” (Please set parameters...) will appear on the bottom portion of page layout as shown in Fig 32. Turn black knob to OPEN or CLOSE status, the symbol of “√” will be able to shift among all selections circularly. When it reaches the selection that the consumer confirms, turn black knob to STOP status, and turn red knob to Local Control Mode or Remote Control Mode as shown in Fig 33 and hold it for 3 seconds, till “MODE CONFIG” (Setting has been configured) appears on bottom portion of page layout, i.e. Remote Control Mode has been set. When Setting of Remote Control Mode finished, enter the layout of OFF. For detailed operation, please see 7.2 ELECTRIC OPERATION. 8.3.5 SETTING OF DOUBLE SPEED CONFIG (SLOW CLOSING) Before delivering actuators, Start Point of Slow Closing and Duty Factor are set as 0% and 100% respectively (i.e. Double Speed function has not been started up). Start Point of Slow Closing means a position approaching the seating of valve travel (≤20%) from which the operating speed comes slow. Duty Factor means what the percentage of the specific cyclic duration (it is set as 5 seconds in this system) the actual valve operating time accounts for. Duty Factor may be available from the relational expression: Duty Factor (%) = total interval (s) × Start Point of Slow Closing (%) /required time of Slow Closing (s)
Importance: instruction of functions of the knob Entering the page layout of Double Speed Config, CLOSE and OPEN of black knob represents respectively set key for Start Point of Slow Closing and Duty Factor. Local Control and Remote Control action of red knob is used as confirmed key for Start Point of Slow Closing and Duty Factor respectively.
-12-
8.3.5.1 SETTING OF START POINT OF DOUBLE SPEED CONFIG (SLOW CLOSING)
Fig 34 Fig 35 Fig 36 Entering the page layout of 2 SPEED, turn black knob from STOP status as shown in Fig 34 to CLOSE status as shown in Fig 35, a prompt of “SET PARA” (Please set parameters...) will appear in the bottom portion of page layout. Figures representing Start Point of low speed will begin from 0%, and increase to 20% in continuous increment of 1% circularly. As figures reaches the percentage that the consumer confirms, turn black knob to STOP status, and turn red knob to Local Control Mode as shown in Fig 36 and hold it for 3 seconds, till “START P CONFIG” (Start Point of Slow Closing has been set) appears in the bottom portion of page layout. 8.3.5.2 SETTING OF DOUBLE SPEED (SLOW CLOSING) DUTY FACTOR
Fig 37 Fig 38 Fig 39 Entering the page layout of 2 SPEED, turn black knob from STOP status as shown in Fig 37 to OPEN status as shown in Fig 38, a prompt of “SET PARA” (Please set parameters...) will appear in the bottom portion of page layout. Setting figures representing Duty Factor will begin from 100%, and decrease to 10% in continuous decrement of 5% circularly. As figures reaches the percentage that the consumer confirms, turn black knob to STOP status, and turn red knob to Remote Control Mode as shown in Fig 39 and hold it for 3 seconds, till “DUTY CONFIG” (Duty Factor has been set) appears in the bottom portion of page layout. When Setting of Slow Closing has finished, enter the page layout of OFF. For detailed operation, see 7.2 ELECTRIC OPERATION. 8.3.6 SETTING OF MID TRAVEL Mid 1 and Mid 2 can be used as mid position in opening direction or closing direction, or used to increase contact points in opening or closing course according to user’s requirement. Before delivering, Mid 1 and Mid 2 of the actuator are respectively set to 0% and 100% of full travel. If consumers want to set mid position, please proceed as following. -13-
Importance: instruction of functions of the knob Entering the page layout of Mid Travel, CLOSE and OPEN of black knob represents respectively set key of Mid 1 and Mid 2. Local Control and Remote Control of red knob is used as confirmed key of Mid 1 and Mid 2 respectively.
8.3.6.1 SETTING OF MID 1 POSITION Entering the page layout of MID POS, turn black knob from STOP status as shown in Fig 40 to CLOSE status as shown in Fig 41, a prompt of “SET PARA” (Please set parameters...) will appear in the bottom portion of page layout. Figures representing Mid 1 will begin from 0%, and increase to 100% in continuous increment of 1% circularly. As figures reaches the percentage that the consumer confirms, turn black knob to STOP status, and turn red knob to Local Control Mode as shown in Fig 42 and hold it for 3 seconds, till “MID 1 CONFIG” (Position of Mid 1 has been set) appears in the bottom portion of page layout.
Fig 40
Fig 41
Fig 42
8.3.6.2 SETTING OF MID 2 POSITION Entering page layout of MID POS, turn black knob from STOP status as shown in Fig 43 to OPEN status as shown in Fig 44, a prompt of “SET PARA” (Please set parameters...) will appear in the bottom portion of page layout. Figures representing Med 2 will begin from 100%, and decrease to 1% in continuous decrement of 1% circularly. As figures reaches the percentage that the consumer confirms, turn black knob to STOP status, and turn red knob to Remote Control Mode as shown in Fig 45 and hold it for 3 seconds, till “MID 2 CONFIG” (Position of Mid 2 has been set) appears in the bottom portion of layout.
Fig 43 Fig 44 Fig 45 When Setting of Mid Travel finished, enter the page layout of OFF. For detailed operation, see 7.2) ELECTRIC OPERATION. -14-
8.3.7 OPTION OF LANGUAGE
Fig 46 Fig 47 Fig 48 In the page layout of LANGUAGE there are two options: English and Chinese. The default is simplified Chinese. Entering the page layout of LANGUAGE (Option of language), a prompt of “SET PARA… (Please set parameters...)” (as shown in Fig. 47) will appear on the bottom portion of page. Turning the black knob to either OPEN or CLOSE status, the symbol “√” can be made move up and down between the two options circularly. When the symbol shifts to the option the user confirmed, turn the black knob to STOP status and turn the red knob to Local Control or Remote Control status as shown in Fig. 48 and hold it for 3 seconds, till “Config” (setting has been configured) appears on the bottom portion of page, i.e. Option of Language has been set. When setting of Option of Language finished, enter the page of OFF. For detailed operation, please see 7.2 ELECTRIC OPERATION. Importance: instruction of functions of the knob Entering the page of Option of Language, OPEN and CLOSE of black knob both have the function to make the symbol “√” move up and down between the options circularly and either Local Control or Remote Control of the red knob has the function to confirm the option. 8.3.8 SETTING OF PASSWORD CONFIG
Fig 49 Fig 50 Fig 51 Entering the page layout of PASSWORD via page layout of “Option setting”(as shown if Fig. 49), a prompt of “SET PARA…” will appear on the bottom portion of the page (as shown in Fig. 50). Turning the black knob to either OPEN or CLOSE status, current password digit will shift circularly from 0 to 9, each shift in a interval of 1.2 seconds. When it shifts increasing to the figure required, turn the black knob to STOP status. and it will save the selected figure. Then turn black knob to either OPEN or CLOSE status to -15-
change to tens digit. Repeat above operation till the three-digit password is confirmed. Then turn the red knob to Local Control or Remote Control status as shown in Fig. 51 to save the set password. When setting of password is finished and the actuator is in any status among OFF, Local Control and Remote Control, the function of password protection will start if the control status does not alternate in 3 minutes. If it is necessary to alternate control mode at this time, enter corresponding password. Entering procedure is similar to the setting of password and the entering must be finished in 2 minutes or it will turn back to original control mode. The function of password protection is like the function of mechanical padlock. It does not react to the red knob or black knob. When setting of password finished, enter the page of OFF. For detailed operation, please see 7.2 ELECTRIC OPERATION. Prompt: The default of password protection has not been started at factory. If it is necessary to delete the password protection after it having started, enter “0 0 0” on the page of PASSWORD via above procedure. 8.3.9 EMERGENT SELF-HOLD
Fig 52 Fig 53 Fig 54 Emergent self-hold is adopted by user to handle the emergency. Emergent self-hold will function in any status among OFF, Local Control and Remote Control, and will neglect motor thermal protection failure and is the preferred control of top level. Emergent self-hold can not start in the default status, i.e. held in original status. Entering the page layout of “E.S.D.” via page layout of “Option setting”(as shown if Fig. 52), a prompt of “SET PARA…” will appear on the bottom portion of the page (as shown in Fig. 53). Turning the black knob to either OPEN or CLOSE status, the symbol “√” can be made move up and down among the options circularly. When it shifts to the option user confirmed, turn the black knob to STOP status and turn the red knob to Local Control or Remote Control status as shown in Fig. 54, and hold it for 3 seconds, till “MODE CONFIG!” (setting has been configured) appears on the bottom portion of page, i.e. Option of Emergent self-hold has been set. When setting of Emergent self-hold finished, enter the page of OFF. For detailed operation, please see 7.2 ELECTRIC OPERATION. Importance: instruction of functions of the knob Entering the page layout of “E.S.D.”, OPEN and CLOSE of black knob both have the function to make the symbol “ √ ” move up and down among the options circularly and Local Control or Remote Control of the red knob has the function to confirm the option.
-16-
8.3.10 SETTING OF MODBUS The actuator sustains Mod bus RTU to carry out feedback and control of the status. Users can set the address and baud rate of the communication according to requirements. Importance: instruction of functions of the knob Entering the page layout of “MODBUS SET”, both OPEN and CLOSE of black knob have the function to set the address and baud rate respectively; and Local Control or Remote Control of the red knob have the function to confirm the option of the address and baud rate respectively. 8.3.10.1 SETTING OF ADDRESS
Fig 55
Fig 56
Fig 57
Entering the page layout of MODBUS SET, turn the black knob from STOP status (as shown in Fig. 55) to CLOSE status (as shown in Fig. 56), a prompt of “CL SET ADD”(set address in close status) will appear on the bottom portion of the page and figures of address will appear on the page increasing from 2 to 127 circularly. When the figure shifts to the option user confirmed, turn the black knob to STOP status and the red knob to Local Control status as shown in Fig. 57, and hold it for 3 seconds, till “ADD CONFIG!” (setting of address has been configured) appears on the bottom portion of page. 8.3.10.2 SETTING OF BAUD RATE
Fig 58
Fig 59
Fig 60
Entering the page layout of MODBUS SET, turn the black knob from STOP status (as shown in Fig. 58) to OPEN status (as shown in Fig. 59), a prompt of “OP SET b/s”(set baud rate in open status) will appear on the bottom portion of the page and the options (four groups of baud rate are provided: 38400, 19200, 9600 and 4800, each including: O—Odd parity, E—Even parity, N—No parity) will appear on the page layout circularly. When the baud rate required appears, turn the black knob to STOP status and turn -17-
the red knob to Remote Control status (as shown in Fig. 60), and hold it for 3 seconds, till “b/s CONFIG!” (setting of baud rate has been configured) appears on the bottom portion of page. When setting of MODBUS finished, enter the page of OFF. For detailed operation, please see 7.2 ELECTRIC OPERATION. Prompt: The actuator of standard model does not sustain the Modbus RTU. Fieldbus communication function is as an option. It is also possible to enter the setting menu of MODBUS in the actuator of standard model, but the set parameters do not work. 8.3.11 PARAMETERS INTERROGATING Importance: instruction of functions of the knob Entering page layout of Parameter Interrogating shifts of black knob between CLOSE and STOP or between OPEN and STOP result in the shift among pages layout of Parameter Interrogating.
Fig 61 Fig 62 Fig 63 Fig 64 Entering the page layout of Parameter Interrogating, turn black knob to CLOSE status, the first page of the page layout of “PARA LST 1”will come out as shown in Fig 61. TC on the page represents rated torque in closing direction set by manufacturer. TO represents rated torque in opening direction set by manufacturer. LC represents set value of closing travel parameter. LO represents set value of opening travel parameter. CT represents set value of closing torque. OT represents set value of opening torque. As black knob comes back to STOP status, turn it again to CLOSE status, the second page of “PARA LST 2” will come out as shown in Fig 62. REMOTE on the page represents set Remote Control Mode. PS represents set value of Start Point of Slow Closing. PZ represents set value of Duty Factor. L1 represents set value of Mid 1. L2 represents set value of Mid 2. As black knob comes back to STOP status, turn it to CLOSE status once more, the third page of “PARA LST 3” will come out as shown in Fig 63. OD on the page represents cycles of valve operation. TD represents cycles of full travel operation. PCT represents three max torque levels of valve operations in closing direction. POT represents three max torque levels of valve operations in opening direction. Return the black knob to STOP status, and turn it to CLOSE status once again to change to page layout of “PARA LST 4” (as shown in Fig. 64). “PASSWORD:” on the page represents whether the function of password protection starts. “ESD:” represents Emergent self-hold and “BIT/S:” represents baud rate of communication and mode of parity check. When Parameters Interrogating finished, enter OFF page layout. For detailed operation, see 7.2 ELECTRIC OPERATION.
-18-
Caution: After installation, commissioning and parameter setting, according to user’s requirement, red knob shall be locked in Local Control Mode or Remote Control Mode with padlock to prevent from entering set parameter status accidentally and damage of various set parameters.
9. INFRARED SETTING TOOL (RC-01) Power supply of 3 V has been built in Infrared Setting Tool (RC—01) before the tool delivering. Valid range of Infrared Setting Tool is 0.75 m from display window of actuator. Importance: instruction of functions of the knob First touch on the function keys of CLOSE, OPEN, CONFIRM 1, and CONFIRM 2 on Infrared Setting Tool transmits the command of the function key and the second touch on them cancels the command of the function key.
9.1 INTRODUTION OF FUNCTION KEYS (1) Closing key (2) Opening key (3) Confirming 1 key (4) Confirming 2 key (5) Setting key (6) Off key (7) Window of infrared transmitting
9.2 USAGE Fig 65 When the key pressed down, the Infrared Setting Tool can send out relevant instruction to the actuator via infrared pulse. So the Infrared Setting Tool must be operated within 0.75 m from display window of actuator and aiming at the window. When replacing battery, remove the cover on the back of the Infrared Setting Tool, and then proceed the replacing. 9.3 SETTING AND COMMISSIONING OF PARAMETERS Turn black knob to STOP status and turn red knob to OFF status as shown in Fig 66, then the Infrared Setting Tool may be used to set and commission parameters. Functions of Closing key and Opening key on the Tool are the same of functions of Closing status and Opening status of black knob on the actuator. Functions of OK 1 key, OK 2 key, SET key and OFF key on the Tool are the same of functions of Local Control function, Remote Control function, setting function and OFF function of red knob on the actuator. So commissioning of parameters with the Infrared Setting Tool is the same of setting and commissioning of parameters described in Chapter 8.
-19-
Fig 66
Warning: When setting and commissioning of parameters with the Infrared Setting Tool is finished, it is necessary to operate OFF key on the Tool and enter OFF page layout at first, then the actuator can be operated, or it will result in error of operating procedure.
10. FIELDBUS CONTROL Fieldbus communication of actuator is control Modbus communication. Control system of mechanism Modbus is as shown in Fig 67. or master unit actuator actuator actuator Modbus communication is a universal language applied on electronic controller with RS485 as interface, with twist pair as transfer medium, and with standard ModbusRTU as transport protocol. It supports semiduplex multipoint serial communication. Communication parameters such as equipment address, Fig 67 baud rate and check mode may be set and programmed in advance at site according to user’s requirement. Communication distance is generally 200~1200 m (according to different baud rate), up to 20 km (need be equipped with signal amplifier). 32 units of equipment can be connected to Modbus via a twist pair without repeaters. At most 126 units of equipment can be connected to Modbus. 11. MAINTENANCE AND TROUBLESHOOTING 11.1 MAINTENANCE Each unit of equipment has been checked and tested in the round before delivering. Installing, setting and commissioning in accordance with this manual, the actuator can carry out fault-free operation. These actuators are of non-intrusive type. For routine inspection, the cover of controller on the actuator shall not be opened. Because the control system is packaged in dry and clean environment and there is no component within that needs local adjusting. Routine maintenance includes followings: • Check if bolts between valve and actuator are fastened. • Ensure valve stem and drive sleeve clean and lubricated. • Check if outer parts are damaged and replace them if damaged. Broken window glass shall be replaced with entire assembly. • Repaint the peeled area. For chemical corrosive or salt spray environment, remove dust before repainting. • For electric actuators operating seldom, service schedule shall be programmed. 11.2 TROUBLE DISPLAY AND TROUBLESHOOTING If there is any trouble with the electric actuator, without the need for removing cover from actuator, you can carry out trouble diagnosis rapidly via trouble display of LCD. Actuator trouble display and troubleshooting: 1) When power supply is put on, LCD of actuator does not light Check if 3 phase power supply is normal and conformed to the voltage on the nameplate. Please measure phase voltage among terminals U, V, W.
-20-
2) Phase loss of power supply Symbol“ ”in the bottom portion of LCD changes into symbol “ ”and the middle strip flashes that as indicates phase loss of power supply. Please check the power supply. 3) Display of motor overheat Symbol“
”in the bottom portion of LCD changes into symbol“
”,symbol of heat elimination
flashes indicating motor overheat. Stop actuator running and restart it when thermostat embedded in motor windings recovers automatically. 4) Display of over torque Symbol“
” in the bottom portion of LCD changes into symbol“
”,indicating valve jamming.
When this symbol flashes, the valve jams in operation and is over torque. Please check if the valve and the set percentage of torque in opening direction and closing direction are normal. 5) Failure of phase rotation correction When phase sequence is in error, the mark “ * ” will appear on the upper right quarter of LCD and the function of phase rotation correction has already started so that the actuator is still operated normally. If the function of phase rotation correction fails, LCD will display power supply failure (The display is the same of Phase loss of power supply.) meanwhile the contact point of power supply failure will transmit remote alarm signal. Please check power supply. 6) Monitoring of mechanical faults If the actuator does not produce travel operation when receiving opening or closing instruction from local control or remote control in 10 seconds, the monitor will transmit alarm signal and “E” will flash on LCD. Please contact with the manufacturer.
-21-
12 SCHEMATIC CIRCUIT DIAGRAM AND WIRING DIAGRAM 12.1 SCHEMATIC CIRCUIT DIAGRAM AND WIRING DIAGRAM OF ELECTRIC ACTUATOR
Note: 1. What in dash line frame of this figure is for special order. 2.If there is no 380V ac input, user can provide backing power (24V dc) for LCD through terminal 1 and 2. Available of backing power or not, does not affect data access. Primary power and backing power are exchangeable automatically. -22-
12.2 CONTROL MODE The actuator has three control modes: local control, remote control, and emergent self-hold. 12.2.1 LOCAL CONTROL When the red knob is located at Local position, the actuator can carry out functions of valve opening, valve closing and stop via black knob. 12.2.2 REMOTE CONTROL When the red knob is located at Remote position, the actuator can carry out functions of valve opening, valve closing and stop via terminals. Power supply of Remote Control is DC 24 V (built in), power supply voltage of control signal is: Von>20 V, Voff<1.5 V. Following 4 kinds of Remote Control may be set via setting functions: (1)Click: open or close valve via click, with signal lasting till valve reaching designated position.
(2)Self-hold: open or close valve via self-hold control, with signal lasting for more than 500 mS.
Electric Actuator Control Room 7
Electric Actuator 7
Close
8
8
Open
9
9 10
Control Room Close Open Stop
(3)On-opening style: opens when circuit is on, and closes when circuit is off.
(4)On-closing style: closes when circuit is on, and opens when circuit is off.
Electric Actuator 7
Electric Actuator 7
Control Room Open
9
8
Control Room Close
12.2.3 EMERGENT SELF-HOLD Emergent Self-hold can override other kinds of control signal (Whatever status the actuator is in) and enforce its implementation (The action depends on presetting). This signal will last till the completion of . action. the Electric Actuator Control Room 7 11
Emergent Self-hold
-23-
-24-
Appendix B: Overall size and connection dimensions of SND-Z Range
OVERALL SIZE OF SND-Z5~SND-Z60 type SND-Z5 15
L1
L2
L3
H1
H2
H3
H4
B2
B3
B4
D1
D2
D3
145,180
110
145
46
214
62
108
21
242
144
260
140
126
SND-Z
20 40
180,190
120
160
54
217
82
111
21
266
144
360
185
175
SND-Z
45 60
200~285
148
239
80
245
97
118
55
277
142
420
225
210
B2
B3
B4
B5
D1
D2
D3
67
310
142
326
460
275
300
67
310
142
326
460
330
350
OVERALL SIZE OF SND-Z90~SND-Z250 type
L1
L2
L3
H1
H2
H3
H4
SND-Z
255~397
158
220
110
260
165
121
255~397
158
263
125
260
165
121
H5
90 120
SND-Z180 250
Note: SND-Z90 120 is without planet reducer.
-25-
158
OVERALL SIZE OF SND-Z350~SND-Z1000 type SND-Z
350 500
SND-Z 800 1000
L1
L2
L3
255~397
125
410
285~397
130
450.5
H custom
H1
H2
H3
φd
φD
φD1
222
38
169
115
380
415
238
51
195
138
510
510
Note for connection dimension in Appendix B: 1) The thrust base in dashed frame is used for thrust mode electric actuator. It is not needed for torque mode actuator. 2) If protection of valve stem is needed, it’s length would be determined by users. 3) For flameproof model, letter B is added after the type representation, e.g. SND-Z120-18B.
-26-
CONNECTION DIMENSIONS OF TORQUE MODE (JB 2920)
CONNECTION DIMENSIONS OF THRUST MODE (ISO 5210 i.e. GB12222)
CONNECTION DIMENSIONS TABLE OF SND-Z RANGE ACTUATORS TORQUE MODE TYPE
Frame D2 d1 d2 n-d size (H9)
(JB2920-81) D1
D
THRUST MODE
h1 h
f
(ISO5210i.e.GB12222)
Flange size
D
D1
D2 (f8)
F10
126
102
70
F14
175
d1
n-d
L
f
T32 4-M10 40
3
140 100 T40 4-M16 50
4
F16
210 165 130 T50 4-M20 80
5
F25
300 254 200 T60 8-M16 114 5
2
30 45 90 4-M10 120 140 2
8
4
2I
26 39 75
6
4
3
46 58 125 4-M12 160 180 2 10 4
3I
30 45 90 4-M10 120 180 2
4
52 72 150 4-M16 195 225 2 12 5
5
62 82 180 4-M20 235 275 2 14 5
5I
46 72 150 4-M16 195 230 2 12 5
7
73 98 220 4-M24 285 330 3 16 6
F30
350 298 230 T70 8-M20 130 5
8
80 118 280 8-M20 340 380 3 20 6
F35
415 356 260 T100 8-M30 170 5
SND-Z
9
85 128 300 8-M24 380 510 3 25 8
10
105 158 360 8-M30 450 510 3 30 8
F40
510 406 300 T120 8-M36 230 8
800 1000
SND-Z5 15 SND-Z2035 SND-Z4560 SND-Z90 120 SND-Z180 250 SND-Z
350 500
4-M8 95
140 2
8
4
Explanation: 1) For flameproof model, letter B is added after the type representation, e.g. SND-Z4560B; 2) I in frame size represents power station mode; 3) Screwed holes for mounting are distributed symmetrical and staggered to motor shaft axis; 4) Valid depth of screwed holes for mounting ≥ 1.8 times of nominal diameter of screw.
-27-
Appendix C: Overall size and connection dimensions features and main technical parameters of SND-Q range
OVERALL SIZE AND CONNECTION DIMENSIONS TABLE OF SND-Q L
H
H1
D
D1
d1 H9
d2 F8
d3
d4
d5
h1
h2
h3
b
SND-Q12.5
180
137
0
0
0
22
35
65
M6
50
14
3
30
6
SND-Q25,40
180
122
0
0
0
28
55
90
M8
70
16
3
35
8
SND-Q50
145
104
132
210
155
42
70
125
M10
102
20
3
50
12
SND-Q100
145
104
132
210
155
50
85
150
M12
125
24
3
57
14
SND-Q150,200
145
104
139
285
196
60
100
175
M16
140
30
4
65
18
TYPE
Note: SND-Q12.5~40 need not additional reducer, so sizes of H1,D,D1 are 0. FEATURES OF SND- Q RANGE STRUCTURE: 1 SNS-Q Range actuators are provided with automatic clutch device. So you may rotate the handwheel directly when hand operation is needed. 2 A spline housing is inserted in the output shaft. It may be taken out to rotate a tiny angle to commission full closed position of valve. The spline housing is not fixed in the output shaft and user can orient it with set screw or by shaft shoulder of valve. 3 There are two models of drive structure: essential and combined. The combined model is connected with reducer of different ratio to extend the torque range and speed range. Schematic drawing of mechanical limit 4 SND-Q Range actuators are provided with mechanical limit device. Refer to the schematic drawing of mechanical limit. Backing off gland nut, you will see the adjusting thread stem. Screw in or out the adjusting thread stem to change valve position and rotation angle. Adjustment range in both opening and closing direction is ± 6º. Full stroke is generally 90º. Various protruding length L of the adjusting thread stem off the housing is as following: 24 for essential model; 30 for combination No 1; 28 for combination No 2. -28-
Essential model Motor TYPE
Power (kW)
TYPE
YDF3802-12Ⅰ 0.09 12.5
SND-Q 40
Speed Rated & Locked Current(A)
Max. Time for Hand dia. of Weight 90 rotate Oper stem (kg) (s) ratio (mm)
r/min
1
3
5
Torque (N·m)
0.91, 6.3 125,250,400
YDF3631-4Ⅰ
0.09
0.63, 4
YDF3632-4Ⅰ
0.12
0.74, 5
YDF3633-4Ⅰ
0.18
1.0, 7
125,250 400 125,250 400
125N·m 22, 83 other 28
1r 15S 3r 5S 5r 3S
48
Combination No1 Reducer Motor TYPE
SND-Q50 100
TYPE
Power (kW)
Speed
Rated & Locked Current(A)
r/min
Time for 0.6 1 1.5 90 rotate (s) Torque (N·m)
YDF3631-4Ⅰ
0.09
0.63, 4 500,1000
YDF3631-4Ⅰ
0.09
0.63, 4
500
YDF3632-4Ⅰ
0.12
0.74, 5
1000
YDF3633-4Ⅰ
0.18
1.0, 7
Hand Oper ratio
Max. dia. of Weight stem (kg) (mm)
500N·m 0.6r 25S 0.6r 1r 42, 1r 15S 401, 1000N·m 500 1.5r 10S 1.5r 278 50 1000
63
Combination No2 Reducer Motor TYPE
SND-Q
150 200
TYPE
Power (kW)
Speed Rated & Locked Current(A)
0.6
r/min 1
Torque (N·m)
YDF3631-4Ⅰ
0.09
0.63, 4
1500
YDF3632-4Ⅰ
0.12
0.74, 5
2000
YDF3633-4Ⅰ
0.18
1.0, 7
1500 2000
Time for Hand 90 rotate Oper (s) ratio 0.6r 25S 1r/ 15S
414
Max. dia. of stem (mm) 60
Weight (kg)
84
Explanation: 1 There is two kinds of ratio for Combination No 1 Reducer: 4.84 and 3.36. Ratio for Combination No 2 Reducer is 5. 2 Motor YDF38002-12Ⅰis of 12 poles and the rest types are of 4 poles. Start current and max. current of motor is approximately 7 times of the value indicating in the table. During operation, the current more than rated value is normal phenomena. 3 Dimension of valve stem diameter in tables is d1 in overall size and connection dimension table and is the maximum value of corresponding specifications. If other diameter value is needed, user must make declaration in order list.
-29-
Appendix D: Main technical parameters, overall size and connection dimensions of SND-DQ range 1.Main technical parameters of SND-DQ400~SND-DQ16500 Type
Torque N·m
Speed r/min
Hand ratio
Actuator
Motor power kW
Reducer 1
Rated & Locked Current(A) Type
Reducer 2
Ratio Type
SND-DQ400
4000
0.316(47.5S)
57
SND-Z30-18
0.37
1.8, 12
DJ2A
57
SND-DQ600
6000
0.316(47.5S)
57
SND-Z40-18
0.55
2.4, 16
DJ2A
57
SND-DQ800
8000
0.327(45.8S)
156
SND-Z45-18
0.75
2.8, 19
DJ3A
55
SND-DQ1000
10000
0.327(45.8S)
156
SND-Z60-18
1.1
4.0, 28
DJ3A
55
SND-DQ1600
16000
0.31 (48.3S)
249
SND-Z90-18
1.5
5.0, 35
DJ4A
58
SND-DQ2000
20000
0.31 (48.3S)
249
SND-Z120-18
2.2
7.0, 49
DJ4A
58
3200 4000
0.333 (45S)
620
SND-Z250-18
3.0
9.0, 63
DJ5A
54
SND-DQ6300
63000
0.26 (57.5S)
792
SND-Z250-18
3.0
9.0, 63
DJ6A
69
SND-DQ8000
80000
0.26 (57.5S)
1187
SND-Z90-72
4.0
9.7, 67
XJ4A
4
SND-DQ12500 125000 0.168 (89S)
2452
SND-Z180-36
4.0
9.7, 67
SND-DQ16500 165000 0.168 (89S)
2452
SND-Z250-36
5.5
13.3, 93
SND-DQ
3200 4000
Ratio
DJ6A
69
XJ4B
2.67 DJ7A
80
XJ4B
2.67 DJ7A
80
Explanation: 1. Among the reducers, XJ means planet reducers, DJ means worm gear reducers (the worm gear pairs are all clockwise and self-locking ) 2. If the output speed different from those in the table is needed, please consult with us. 3. All of the key-way positions in following figures indicate valve seated. 2.Overall size and connection dimensions of SND-DQ400~SND-DQ16500
Overall size and connection dimensions of SND-DQ400 and SND-DQ600 -30-
Overall size and connection dimensions of SND-DQ800 and SND-DQ1000
Overall size and connection dimensions of SND-DQ1600 and SND-DQ2000
-31-
Overall size and connection dimensions of SND-DQ3200 4000
Overall size and connection dimensions of SND-DQ6300~SND-DQ16500 Type
C
D4
E
F
H
J
J1
L1
L2
P
V
SND-DQ6300
335
380
356
450
301
745
158
285
263
340
145
SND-DQ8000
335
380
356
450
301
745
212
240
220
340
145
SND-DQ12500
465
380
480
605
400
946
404
240
263
426
153
SND-DQ16500
465
380
480
605
400
946
404
285
263
426
153
Type
d (H9)
D1(f8)
D2
D3
h
b1
L
b
n-M
α
SND-DQ6300
180
300
406
470
8
9
250
45
8-M36
22.5°
SND-DQ8000
180
300
406
470
8
9
250
45
8-M36
22.5°
SND-DQ12500
220
370
483
560
8
8
285
50
12-M36
15°
SND-DQ16500
220
370
483
560
8
8
285
50
12-M36
15°
-32-
Appendix E: Technical Parameters Table of SND-Z (Remarks: actuators above 3500N·m are combined structures. ) Motor
Type Type
SND-Z515 SND-Z515B
SND-Z20 40 SND-Z20 40 B
45 60 45 60
SND-Z SND-Z B
90
SND-Z120 90
SND-Z120B
180 250 180 250
SND-Z SND-Z B
SND-Z350 500 SND-Z350 500B 800
SND-Z1000 800 1000
SND-Z
B
YDF3800-6Ⅰ YDF3631-4Ⅰ YDF3632-4Ⅰ YDF3633-4Ⅰ YDF3800-4Ⅰ YDF3801-4Ⅰ YDF3802-4Ⅰ YDF3800-2Ⅰ YDF3801-2Ⅰ YDF3801-6Ⅱ YDF3802-6Ⅱ YDF3801-4Ⅱ YDF3802-4Ⅱ YDF3901-4Ⅱ YDF3802-2Ⅱ YDF3901-2Ⅱ YDF3100M-6Ⅲ YDF3100M1-4Ⅲ YDF3100M2-4Ⅲ YDF3100L1-4Ⅲ YDF3100L2-4Ⅲ YDF3100L-2Ⅲ YDF3112M1-2Ⅲ YDF3112M2-2Ⅲ YDF3112L-2Ⅲ YDF3100L1-6Ⅲ YDF3100L2-6Ⅲ YDF3100L1-4Ⅲ YDF3100L2-4Ⅲ YDF3112L1-4Ⅲ YDF3112L2-4Ⅲ YDF3112M2-2Ⅲ YDF3112L-2Ⅲ YDF3132L1-2Ⅲ YDF3132L2-2Ⅲ YDF3100L1-4Ⅲ YDF3100L2-4Ⅲ YDF3112L1-4Ⅲ YDF3112M1-2Ⅲ YDF3112M2-2Ⅲ YDF3112L-2Ⅲ YDF3132L1-2Ⅲ YDF3132L2-2Ⅲ YDF3100L2-4Ⅲ YDF3112L1-4Ⅲ YDF3112L2-4Ⅲ YDF3112M2-2Ⅲ YDF3112L-2Ⅲ YDF3132L1-2Ⅲ YDF3132L2-2Ⅲ YDF3112L2-4Ⅲ YDF3112L-2Ⅲ YDF3132L1-2Ⅲ YDF3132L2-2Ⅲ
Output Speed
Power (kW)
Rated Current (A)
Locked Current (A)
0.18 0.09 0.12 0.18 0.25 0.37 0.55 0.37 0.55 0.25 0.37 0.37 0.55 0.75 0.75 1.1 0.75 0.75 1.1 1.5 2.2 2.2 3 4 5.5 1.1 1.5 1.5 2.2 3 4 4 5.5 7.5 10 1.5 2.2 3 3 4 5.5 7.5 10 2.2 3 4 4 5.5 7.5 10 4 5.5 7.5 10
1.1 0.63 0.74 1.0 1.4 1.8 2.4 1.38 1.86 1.42 1.96 1.8 2.4 2.8 2.4 3.3 3.11 2.8 4 5 7 6.3 7.8 9.7 13.3 4.2 5.7 5 7 9 11.9 9.7 13.3 17.1 22.8 5 7 9 7.8 9.7 13.3 17.1 22.8 7 9 11.9 9.7 13.3 17.1 22.8 11.9 13.3 17.1 22.8
7.5 4 5 7 9.5 12 16 9.5 13 9.5 13 12 16 19 16 23 21 19 28 35 49 44 54 67 93 29 39 35 49 63 83 67 93 119 159 35 49 63 54 67 93 119 159 49 63 83 67 93 119 159 83 93 119 159
6
9
12 (14 )
(r/min)
18
Data in brackets are for SND-Z180 and SND-Z250
24 ( 27 )
36
Nominal torque
48 ( 54 )
72
96
144
192
Thrust (KN)
(N·m)
Max.dia. Max. Hand of stem rotation ratio (mm) (rev)
Weight (kg)
100 150
50 80 100 150
50 80 100 150
50 80 100 150
50 80 100 150 80 120
50 100
80
40
28
≤1200
1
30~35
100
40
≤1200
1
40~50
150
50
≤1200
200
60
≤1200
325
70
≤449
11.48 180~260
700
100
≤300
17.2 300~400
1100
120
≤150
34.4 350~500
50
250 350 300 400
250 350 400
300 400
250 300 150 250
120 200
100 150
450 600
300 450 600
300 450 600
80 120
600 450 600
450 600
450 600
450 600
2.829 100~130
300 450 600
900 1200 900 1200
900 1200
900 1200
900 1200 900 1200
1800,2500
1800 2500
1800,2500
3500 5000
900 1200
120~170
900 1200
1800 2500 1800 2500
3500 5000
900 1200
4.3
1800 2500
1800 2500
1800 2500
3500 5000 3500 5000
3500 5000
3500 5000
3500 5000
8000 10000 8000 10000 8000 10000
8000 10000 8000 10000
Appendix F: Communication Protocol Of MODBUS for SND Range 1 Characteristic 1.1 Mode of transmission: MODBUS RTU 1.2 Physical layer: RS485 (differential, half duplex) 1.3 Data transmission rate (Baud rate) bit/s: 38400, 19200 (default); 9600, 4800 optional 1.4 Unit address: 2~127 1.5 Data format Coding 8 digit of binary system Start bit 1 bit Data bit 8 bit Parity bit 1 bit (even, odd, no parity ) Stop bit 1 bit Error checking CRC16 1.6 MODBUS function code supported by unit: Function code 03 04 06 16
Description Read Hold Register Read Input Register Write single register Write multi register
2 Data interchange address and definition 2.1 Input data: ① Control word for open , close, and stop --
--
--
--
--
--
--
Effect Obtain current binary value from one or more HR Obtain current binary value from one or more IR Load specific binary value into a single HR Load specific binary value into a series of HR
Address: 150 (decimal system) --
--
--
--
--
3
2
1
0
2
1
0
2
1
0
Bit 0: Close instruction, 1= Run, 0= Stop Bit 1: Open instruction, 1= Run, 0= Stop Bit 2: Stop instruction, 1= Stop, 0= invalid Bit 3: Emergent close instruction, 1= Run, 0= Stop 2
15
Control word for position set and run 14
--
--
--
--
--
Address: 151 (decimal system) --
--
6
5
4
3
Bit 15: characteristic bit, shall be set as “0” when transmitting Bit 14: characteristic bit, shall be set as “1” when transmitting Bit 0~6: Set value for actuator position, range: 0~100% 2.2 Output data ① Status word for electric actuator --
14
13
12
11
10
Address: 160 (decimal system) 9
8
7
6
5
4
3
Bit 0: Signal of full close, 1= position of full close, 0= position of not full close Bit 1: Signal of full open, 1= position of full open, 0= position of not full open Bit 2: Alarm for power failure, 1= Alarm, 0= Normal Bit 3: Alarm for motor overheat, 1= Alarm, 0= Normal Bit 4: Relay monitor, 1= monitor action of relay, 0= monitor no action of relay Bit 5: Signal of over torque in closing direction, 1= over toque closing, 0= not over torque closing Bit 6: Signal of over torque in opening direction, 1= over toque opening, 0= not over torque opening Bit 7: Signal of local operation, 1= actuator is in local operation status; 0= actuator isn’t in local operation status Bit 8: Signal of remote operation, 1= actuator is in remote operation status; 0= actuator isn’t in remote operation status Bit 9: If signal of remote closing is inputting (i.e. If Terminal ⑦ and ⑧ on actuator are on), 1= on, 0= off -34-
Bit 10: If signal of remote opening is inputting (i.e. If Terminal ⑦ and ⑨ on actuator are on), 1= on, 0= off Bit 11: If signal of remote stop is inputting (i.e. If Terminal ⑦ and ⑩ on actuator are on), 1= on, 0= off Bit 12 If signal of remote emergent close is inputting (i.e. If Terminal ⑦ and ⑾ on actuator are on), 1= on, 0= off Bit 13 : If signal of Mid 1 is outputting, 1= yes, 0= no Bit 14 : If signal of Mid 2 is outputting, 1= yes, 0= no ② Status word for remote control mode --
--
--
--
--
--
Address: 161 (decimal system) --
--
--
--
--
--
--
--
1
0
2
1
0
2
1
0
3
2
1
0
3
2
1
0
Value set as“00”, remote self hold Value set as“01”, remote inching Value set as“10”, remote two wire control with On-opening style Value set as“11”, remote two wire control with On-closing style ③ Position of actuator --
--
--
--
Address: 162 (decimal system) --
--
9
8
7
6
5
4
3
Bit 0~9: value of actuator position, range: 0~1000(0.0~100.0%) ④ Percentage of torque --
--
--
--
Address: 163 (decimal system) --
--
--
--
--
6
5
4
3
Bit 0~6: Percent of torque, range: 0~100% ⑤Operational times of actuator 15
14
13
12
11
Address: 164 (decimal system) 10
9
8
7
6
5
4
Range: 0~65535 ⑥Seating times of actuator 15
14
13
12
11
Address: 165 (decimal system) 10
9
8
Range: 0~65535 Note: Symbol of “--”means this bit is not used.
-35-
7
6
5
4
Appendix G: Communication Protocol Of PROFIBUS-DP for SND Range 1 General Description 1.1 Protocol PROFIBUS-DP/V0 confirms to Standard JB/T 10308.3—2005 Digital Data Communication for Measurement and Control — Fieldbus for Use in Industrial System — Type 3: PROFIBUS Specification (IEC61158 TYPE 3: 2002, MOD) 1.2 Standard PROFIBUS-DP drive interface is capable of automatically identifying the baud rates . Maximum baud rate is 12 M. 2 Main Technical Characteristic 2.1 Mode of transmission: PROFIBUS-DP/V0 2.2 Physical layer: RS485 (differential, half duplex) Network topology Linear bus, both ends connected to terminal resistance Medium
Shield, twisted pair copper cable, cable type A. Shield may be canceled according to environment condition (EMC)
No. of station
At most 32 each segment without relays and 126 with relays.
No. of relay
At most 4 repeater with signal refreshing
Pin connector
A, B and GND among 42-pin terminal connector of actuator
Data security
HD = 4, parity check bit, start/end delimiter
Characteristic of Type A Cable: Item Characteristic impedance/Ω capacitance per unit length/(pF/m) Loop resistance(Ω/km) Diameter of cable core/mm Sectional area of cable core/mm2
between 2 sites.
Type of cable: A 135~165 ﹤30 110 0.64 ﹥0.34
3 Data transmission rate (Baud rate) bit/s: Transmission rate of signal
Maximum length of
Maximum
network segment /m
extension
of
Remarks
network/m (with repeater)
9.6 kbit/s
1200
6000
19.2 kbit/s
1200
6000
45.45 kbit/s
1200
6000
93.75 kbit/s
1200
6000
187.5 kbit/s
1000
5000
500 kbit/s
400
2000
1.5 Mbit/s
200
1000
3 Mbit/s
100
500
6 Mbit/s
100
500
12 Mbit/s
100
500
-36-
Optional
4 Equipment address: 1~124 5 Data format 5.1 Type of Message and Frame Format Cycle time of bus information Tmc: TMC = [Tsyn + Tidl +(2×9 + input data byte + output data byte)×11+TSDR]×Tbit×number of slave station =[33+75+(2×9+ input data byte + output data byte) ×11+11] ×Tbit×number of slave station TMC: Cycle time of bus information Tsyn: synchronizing time Tidl: Pitch time to resending from master station, representative value 75 Tbit TSDR: Delay time of slave station, representative value 11 Tbit Tbit: bit time All data are transmitted Without interface between single character. The protocol chip conforms to these rules. Provided with PROFIBUS-DP/V0 Protocol and via MS0 communication mode, SND Intellectualized Electric Actuators are able to carry out periodic interchange of data between master station and slave station. Message format provides transmission security of high level to be used for point to point logical data transmission via SRD service, and for broadcast communication and multicast communication as well. During broadcast communication, a master station transmits information to all other slave station teams or to all stlave stations, and in the process of data interchange, the master station carries out global control of set slave station teams via SDN, meanwhile there is no response. 5.2 Message Format of Electric Actuator (PROFIBUS-DP/V0) SD
LE
LEr
SDr
DA
SA
FC
DSAP
SSAP
DU
FCS
ED
68h
**
**
68h
**
**
**
**
**
DATA
**
16h
Where: SD Start delimiter, to distinguish diverse message format LE Data length, all length of subscriber data including DA, SA, FC, DSAP, SSAP, and DU LEr Repeat of LE SDr Repeat of SD DA Destination address of transmission SA Source address of starter of frame transmission FC Range of function code, to identify type of frame DU Range of user data, to place user data being carried FCS Frame checking sequence ED End delimiter ** automatic configuration data provided by master station system 5.3 Definition of User data Field and Data Interchange Format in Electric Actuator (PROFIBUS-DP/V0) Protocol Data Format Fetched by Slave Station and Input by Master Station Message structure of master station request is as follows: DA SA SD LE LEr SDr 68h
**
**
68h
**
**
Message structure of slave station response is as follows: SD LE LEr SDr DA SA FC 68h
**
**
68h
**
**
**
-37-
FC
DSAP
SSAP
FCS
ED
**
39h
3Eh
**
16h
DSAP
SSAP
3Eh
3Eh
DU 1
2
FCS
ED
**
16h
The communication is provided with input of 13 bytes and output of 4 bytes: Serial No. of byte 1 2 3 4 5 6 7 8 9 10 11 12
Type
Input content
13
Content msb lsb msb lsb msb lsb msb lsb msb lsb msb lsb BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1
Status of DP module
Status word for electric actuator Status word for remote control mode Travel of actuator Percentage of torque Operational times of actuator Seating times of actuator
BIT0 1 2 3 4
Output content
Word of HO Word of LO Word of HO Word of LO
Hold Hold Hold Hold Hold Hold Hold Communication status with electric actuator Control word for open run, close run and stop Control word for travel set and run
Data output form Control Command of electric actuator within DU is as follows (2 word in total) : (1) Control word for open run, close run and stop (write) --
--
--
--
--
--
--
--
--
--
--
--
3
2
1
0
--
6
5
4
3
2
1
0
Bit 0: Close instruction, 1= Run, 0= Stop Bit 1: Open instruction, 1= Run, 0= Stop Bit 2: Stop instruction, 1= Stop, 0= invalid Bit 3: Emergent close instruction, 1= Run, 0= Stop (2) Control word for Actuator travel set and run (write) 15
14
--
--
--
--
--
--
Bit 15: Characteristic bit, shall be set as “0” when transmitting Bit 14: Characteristic bit, shall be set as “1” when transmitting Bit 0~6: Set value for actuator travel, range: 0~100% 5.4 Data Format Fetched by Master Station and Input by Slave Station Message structure of master station request is as follows: DA SA SD LE LEr SDr 68h
**
**
68h
**
**
Message structure of slave station response is as follows: SD LE LEr SDr DA SA FC -38-
FC
DSAP
SSAP
FCS
ED
**
38h
3Eh
**
16h
DSAP
SSAP
DU
FCS
ED
68h
**
**
68h
**
**
**
3Eh
1~6
38h
**
16h
Data input sequence from State Feedback of electric actuator within DU is as follows (6 word in total): (1) Status word for electric actuator (read) --
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Bit 0: Signal of full close, 1= position of full close, 0= position of negative full close Bit 1: Signal of full open, 1= position of full open, 0= position of negative full open Bit 2: Alarm for power failure, 1= Alarm, 0= Normal Bit 3: Alarm for motor overheat, 1= Alarm, 0= Normal Bit 4: Relay monitor, 1= monitor action of relay, 0= monitor no action of relay Bit 5: Signal of over torque in closing direction, 1= over toque closing, 0= not over torque closing Bit 6: Signal of over torque in opening direction, 1= over toque opening, 0= not over torque opening Bit 7: Signal of local operation, 1= actuator is in local operation status; 0= actuator is in negative local operation status Bit 8: Signal of remote operation, 1= actuator is in remote operation status; 0= actuator is in negative remote operation status Bit 9: If signal of remote closing is inputting, 1= on, 0= off Bit 10: If signal of remote opening is inputting, 1= on, 0= off Bit 11: If signal of remote stop is inputting, 1= on, 0= off Bit 12 If signal of remote emergent closeting is inputting, 1= on, 0= off Bit 13 : If signal of Mid 1 is inputting, 1= yes, 0= no Bit 14 : If signal of Mid 2 is inputting, 1= yes, 0= no (2) Status word for remote control mode (read) --
--
--
--
--
--
--
--
--
--
--
--
--
--
1
0
Value set as“00”, remote self hold Value set as“01”, remote inching Value set as“10”, remote two wire control with On-opening style Value set as“11”, remote two wire control with On-closing style l (3) Travel of actuator (read) --
--
--
--
--
--
9
8
7
6
5
4
3
2
1
0
Bit 0~9: Travel of actuator, range: 0~ 1000 (0.0~100.0%) (4) Percentage of torque (read) --
--
--
--
--
--
--
--
--
6
5
4
3
2
1
0
8
7
6
5
4
3
2
1
0
6
5
4
3
2
1
0
Bit 0~6: Percent of torque, range: 0~100% (5) Operation times of actuator(read) 15
14
13
12
11
10
9
Bit 0~15: Times of actuator operation, range: 0~65535 (6) Seating times of actuator (read) 15
14
13
12
11
10
9
8
7
Bit 0~15: Times of actuator seating, range: 0~65535 Note: Symbol of “--”means this bit is not used.
-39-