OPERATION MANUAL DEHUMIDIFIER MODEL : ORTOS110 / ORTOS110 SC ORTOS140 / ORTOS140 SC ORTOS190 / ORTOS190 SC
Please read this operation manual before using the dehumidifier
CONTENTS Safety Instruction
3
Attention during Usage
4-5
Principle of dehumiditifier
6
Specification
6
Descriptions of Parts
7
Panel Controll
8
Exploded Views
9
Installation note
10
Remote Controller
11-12
Operation Guide
13
AUTO Operation Mode
14
Air Direction Adjustment
15
Timer Operations
16
Defrost system
17
Assistant heater
17
Water drainage system
17
Error codes
18
Wiring diagram
18
Maintenance
19-21
Trouble Shooting
22
2
Safety Instruction Please
read
the
following Safety
Instructions
carefully
prior
to use.
The instructions are classified into two levels, WARNING and CAUTION according to the seriousness of possible risks and damages as follows. Compliance to the instructions are strictly required for safety use.
Installation WARNING Please call
Sales/Service
Shop
for
the
Installation.
Do not attempt to install the air conditioner by yourself because improper works may cause electric shock, fire, water leakage.
lnstallation in a following place.
inadequate place
may cause
accidents. Do
not install
in
the
the
unit
CAUTION Do not install in the place where there is any possibility of inflammable gas leakage around the unit.
Connect the earth cable.
Do not get exposed to vapor or oil steam.
earthing
PROHIBITION
PROHIBITION
WARNING When abnormality such as burnt-small found, immediately stop the operation button and contact sales shop.
OFF
Use with
STRICT ENFORCEMENT
3
an exclusive power a circuit breaker
source
Attention during Usage WA R N I N G Ensure the power plug is secure If the plug is not secure, it may cause a electric shock, over-heat-
Never pull out the power plug during operation. otherwise, it may cause a elec-
ing or a fire.
tric shock or a fire due to over heating.
Do not use the same socket with other electric appliances or
Do not operate when the hands are wet.
use an extension cord. otherwise it may cause a electric shock or a fire due to over-
due to danger of a electric shock.
Never u se d amaged e lectric wires or unspecified electric wires. otherwise it may cause a electric shock or a fire.
Do not insert a rod or other objects into the inlet or outlet vents. otherwise, it may cause a electric shock or a fire.
heating.
Do not out a
expose
yourself
single directional airflow for a long period to avoid harming to your health.
to a In case of abnormal condition (burning smell etc.),pull out the power plug to stop the dehumidifier from running, or disconnect the power supply by means of a electric current protector. If the abnormal condition persists, it may cause a electric shock or a fire due to over-heating. Please consult the dealer of service centre as soon as possible to arrange for a repair.
4
Do
not
attempt
to
carry
repair. Improper repairs may cause a electric shock or a fire. You should contact the dealer of service cen- tre to arrange for a repair.
Attention during Usage
Do not hold the electric wire to pull out the power plug. Pulling of the electric wire may cause over-heating of the electric wire of a fire.
If the air-conditioner is not in use for a long time, it is necessary to pull out the power plug.
Switch off the power supply while cleaning d e - humidifier.
the
Excessive dust on the power plug may also cause over-heating or a fire.
Please take care not
to damage
Do not place a heater in front of the dehumidifier.
Do not pour water onto
the internal fan which is rotating at a high speed.
PROHIBITION
Do not use the dehumidifier for other purposes. Do not use it for keeping precision instruments, food, plants and ar-
If internal combustion of the heater is not complete, it may give out
tistic items.
poisonous carbon monoxide.
This may affect the
dehumidifier for cleaning. Due to danger of electric shocks.
quality of the food.
PROHIBITION
PROHIBITION
PROHIBITION
5
the
Principle of dehumidifier
CONDENSER
EVAPORATOR COMPRESSOR
WARM DRY AIR OUTLET
COLD DRY AIR
AMBIENT AIR INLET
COLD DRY AIR
FAN CONDENSE WATER CAPILLARY
WATER TANK
WATER DRAIN OUT WATER PUMP
The dehumidifier use the refrigeration circuit to change the damp air warm dry air. When the damp air passes the condenser, the air water will be condensed and the air will become dry. The Specification Of Dehumidifier (R410a) Model
ORTOS110
ORTOS140
ORTOS190
4.5
6
8
2300
3200
4300
1300
1650
2300
850
850
1150
900
1250
1750
230V/50Hz/1Ph
230V/50Hz/1Ph
230V/50Hz/1Ph
5.8
7.0
10.5
2000
2000
2000
Rotary
Rotary
Rotary
Capacity(L/hr) Heating Power Air
capacity(W) consumption(W)
flow(m3/hr)
Refrigerant(g) Power
supply
Current(A) Aux
electric
Compressor
heater(W)(option) type
Compressor(brand Water
name)
Daikin
pump
or sanyo
Daikin
or sanyo
Daikin
or sanyo
Yes
Yes
Yes
100-150
150-200
200-250
Noise(dB(A))
47
48
53
Drain
500
500
500
Packing dimension(mm)(WxHxD)
535x1790x470
535x1790x470
535x1790x520
Unit
485x1725x320
485x1725x320
485x1725x370
Applicable
area(㎡)
pipe(mm)
dimension(mm)(WxHxD)
Weight(net/gross)(kg)
72/82 Test
condition:
Dry
ball
77/87 temperature
6
30℃.
Relative
84/94 humidity
of
80RH%.
Descriptions of Parts 1 2 3 4 5 6 7 8 9
Air Outlet Control Panel Air filter(inside) Air Inlet Humidity sensor Indoor temperature sensor Water drainage system Four way valve Compressor Electrical control Box
1
C %
A
TIM E R
HEATER
SWIN G
SWIN G
+
SPEED
_
FAN
MODE ON/O F F
2
10
3
4 8
9
5
7
7
6
Exploded Views 9 10 8 11 6
7
5
12
33 4 15 13 16
1
14
35
36 24
22
17
21 23
20
18
19 25 31
26
2 3
28 34
32
27
37 38
30 29
19
Plastic-base
38
Power Cord
18
Water pan 2
37
Defrost temperature sensor
17
Water pan 1
36
Humidity sensor
16
Evaporator
35
Filling gas valve
15
Plastic foam air duct
34
Stepper motor
14
Fan motor fixer
33
Flow detector
13
Fan motor
32
Electrical Box
12
Cover
31
Transformer
11
Cross flow fan
30
Circuit Board
10
Right panel
29
Motor Capacitor
9
Auxiliary electric heater
28
Public Terminal
8
Upper fixing board
27
Compressor Capacitor
7
Condenser
26
Terminal
6
Top cover
25
Truckle
5
Left panel
24
Drain pipe
4
Back board
23
Auto water drainage system
3
Control panel
22
Four Way Valve /Copper Pipe
2
Front Panel 2
21
Compressor
1
Front Panel 1
20
Chassis
8
Installation note To ensure dehumidifier is steady during running, it prepared top dead plate and root support foot, the installation and use as following fig. 1 and 2. fig. 1
Please note that root support foot can draw out or draw back, it is convenient for user moving dehumidifier to other place by root wheel. fig. 2
Function of the needle valve When the heat pump need to measure the pressure of the current system or to filling refrigerant, the operator can use this low-pressure needle and make the appropriate maintenance work! needle valve
9
Panel Control Signal Receiver
C
A
Display
%
TIMER
HEATER
SWING
_
+
SWING
FAN SPEED
MODE
Button
ON/OFF
Button ON / OFF
Press the button to start operation,
Mode is selected in a sequence:
MODE
press the button again to stop operation.
Automatic ; Dehumidifying ; Fan ; Heating.
FAN SPEED
Select the fan speed. Each time press the
+/
button; fan speed is selected in a sequence:
_
One press of the “ + “ button to raise o
the temperature by 1 C; One press of
LOW , MID , HIGH.
the “ - ” button to lower the temperature o
by 1 C.
SWING
HEATER
Set the swing or stop of Left-Right Airflow
Press once to switch on assistant heater;
1
5
9
7
2 A
6
Auto operation mode
6
2
Fan operation mode
7
3
Heating operation mode
8
4 5
Set the TIMER ON / OFF.
4
C %
A
1
vane.
TIMER
Press again to switch off assistant heater.
Display
Set the swing or stop of Up-Down Airflow
SWING
vane.
Dehumidifying operation mode
9
8
3
Displays when
turns to CLOCK status
C
Displays when
turns to TEMPERATURE status
%
Displays when
turns to HUMIDITY status
CLOCK or TEMPERATURE or HUMIDITY display
Assistant heater display 10
Remote Controller
Signal Emitter : Sending out remote control signal to the air-conditioner
Temperature Adjustment Button : Adjust temperature settings Press once to set temperature 1 degree higher. Press once to set temperature 1 degree lower.
Remote Controller Display Panel : Display settings DRY
TEMP Mode Button : Select Automatic, Heating,
O
On/Off Button : Press once to start Air-conditioner running; Press again to stop running.
C
De-humidifying, Fan modes
AUTO
FAN
SW I NG
ON / OFF
FAN Button : Air flow setting
MODE
Timer Cancel Button : Cancel Timer-On and Timer-Off settings
OFF
Timer Off Button : Set Timer-off hour.
ON Timer On Button : Set Timer-on hour.
TIM E R
FA N
CANCEL CONFIRM
SWIN G
SLEEP
Timer Confirm Button : Send Timer-on or Timer-off data to the air-conditioner
HEATER Manual Assistant Heater Button Press once to switch on assistant heater; Press again to switch off assistant heater.( option )
Air Direction Button : Set air louver swinging or stationary
11
:
Remote Controller Emission Indicator : This symbol flashes once when the Remote Controller emits signals to the Dehumidifier. Mode Display : Press "Mode" button to display the current working mode. Automatic, Heating, Dehumidifying, Fan modes
Temperature Display : It displays the current set temperature which may be adjusted by Temperature Adjustment Button or o within the range of 18 ~30 C. In Au- tomatic Mode, temperature is not dis- played but " Standard " (standard) o temperature + 2 C) or " Standard " o (standard -2 C) temperature is displayed.
O
C
Timer Display : It displays the time setting for TimerOn or Timer-Off in the range of 1~12 hours.
FAN Displa y : It displays the current amount of air flow. FAN
Automatic
Display on Remote Controller Air Direction Display : When "Swing" is in display, the updown louver of the air-conditioner is swinging. When the d i s p l a y disappears, the updown louver stops swinging.
AUTO FAN
Low
FAN
Mid
FAN
High
FAN
NOTE: All Displays on the diagram are listed out for demonstration. During operation, only the relevant Display will appear on the Remote Controller.
12
Operation Guide Proper settings of Heating, Dehumidifying and Fan modes Mode Selection ( 1 ) Press "Mode" button to select the required working mode, which is changed in the following sequence when pressed once: Automatic
Dehumidifying
Fan
Heating DRY TEMP
NOTE: Heating mode is available only on cooling-heating type air conditioner. Automatic operation will be explained in detail on next page.
C
AUTO
Air Flow Selection ( 2 )
FAN
SWING
Press "FAN" button to select the required amount of air flow, which is changed in the following sequence when pressed once : Automatic
3
O
Low
Mid
MODE
1
High
FA N NOTE: When Automatic FAN is selected, the air-conditioner will automatically select the suitable amount of air flow according to room temperature. When Dehumidifying is selected, the amount of air flow is set by the machine and fan setting is not functional.
Temperature Setting Selection ( 3 ) Press "Temperature Adjustment Button " to set temperature 1 degree higher. Press "Temperature Adjustment Button " to set temperature 1 degree lower. Hold down the Button to increase of decrease the temperature settings progressively. NOTE: o o Range of adjustable temperature settings : 16 C ~ 31 C.
Starting Operation ( 4 ) Press "On/Off" button, and when the unit receives the signal, it gives out two "beep" tones, the operation light is on and the dehumidi- fier starts operation.
NOTE: If it is desired to run the machine at the same settings for mode, air flow and temperature as the last operation, skip Steps 1~3 and start the machine directly. If the interval is shorter than 3 minutes from last shut down to the present switch-on, the compressor only re-starts after 3 minutes to protect the system. After switching on and if the mode is changed, the system may delay for 3 minutes before starting operation. When heating mode is selected, the internal fan will delay operation for a while when the machine is switched on to prevent cool air circulation at the beginning. After switching on, air flow amount and temperature may be separately adjusted as desired.
13
2
ON / OFF
OFF
ON
TIMER
CANCEL
SWING
SLEEP
CONFIRM
HEAT ER
4
AUTO Operation Mode Automatic operation Mode Mode Selection (1) Press "Mode" button to select Automatic Operation mode. AUTO
Fan Selection (2)
TEMP
Press "FAN" button to select the required amount of air flow, which is changed in the following sequence when pressed once : Automatic
Low
Mid
AUTO
High
FAN
SWING
NOTE: When Automatic FAN is selected, the unit will automatically select the suitable amount of air flow according to room temperature.
MODE
OFF
1
Starting Operation (3)
3
ON
TIMER
FA N
2
Press " On/Off " button, and when the unit receives the signal, it gives out two " beep " tones, the operation light is on and the dehumidifier starts operation is automatic mode.
ON / OFF
SWING
CANCEL
CONFIRM
S LEE P
HEAT ER
NOTE: In automatic mode, the dehumidifier automatically selects "Dehumidifying” , "Heating" modes depending on room temperature and the humidity, with details as the follow-ing table:
Temperature Model
o < 23 C or
o
> 28 C
o
o
23 C ~ 28 C
o o < 23 C or > 28 C
humidity: > 80%
Dehumidify Heating
humidity: < 80%
Working
Working
Not Working
Not Working
Not Working Working
Adjustment in Automatic Mode Feeling Unsuitable fan speed
Button FAN
14
Operation Press once to change the air flow progressively until the suitable air flow is selected.
Air Direction Adjustment Up-Down Air Direction Adjustment C %
A
TIMER
SWING
HEATER
Airflow horizontally
_
+
SWING
FAN SPEED
MODE
ON/OFF
Airflow upward
Airflow downward
NOTE: To stop the up-down air louver in a desired position, set the louver to automatic swinging and when it reaches the desired position, stop the louver from swinging. It is necessary to adjust the louver angle by means of the remote controller, Setting of the louver with the hand may affect its normal operation, in which event, switch off the unit temporarily and re-start operation. To get the best effect, the up-down air flow is usually set in the following manner : Dehumidifying - Horizontal air direction or upward air direction. Heating Downward air direction.
Changing Left-Right Air Direction
COOL
C %
A
TIMER
HEATER
SWING
SWING
+
TEMP O
OR
_
AUTO FAN SPEED
MODE
ON/OFF
C FAN
SWING
MODE
ON / OFF
OFF
ON
TIMER
FA N
CANCEL
SWING LEEP
NOTE: Don’t move the Left-Right vane directly.
15
S
CONFIRM
HEATER
Timer Operations Timer Switch On 1.
Press "Timer On" button to set time for timer-on switching. Press the button once to change the time interval of 1 hour in a cyclic manner of 6, 7, 8 ...12 ..1, 2..5,6 (The display is showing the previous time as the starting time of the present setting) If the button is held down, the time interval will increase progressively by 1 hour unit.
2. Point the remote controller towards the receiver on the unit, press "Timer Confirm" button send the timer setting the deto to humidifier. Then the timer light on the unit lights up, indicating that the unit is in the timer mode. When it reaches the switch-on time, the dehumidifier will operate in the pre-set modes.
NOTE: Before timer operation, please set the operation mode, temperature, air flow etc. on the remote controller, With timer being set to switch-on mode. the Dehumidifier will operate according to the last setting. Usually, timer-on setting is made while the dehumidifier is not in operation. If timer-on is set while the dehumidifier is running, then the unit will shut down immediately and re-start at the pre-set time. If the "On-Off" button is pressed while the unit is under timer-on setting, then the unit will start immediately, the timer setting is cancelled and the timer light will be off.
DRY TEMP O
HR
AUTO
1. Press "Timer Off" button to set time for timer-off switching. Press the button once to change the time interval of 1 hour in a cyclic manner of 6, 7, 8 ...12 ..1, 2..5,6 (The display is showing the previous time as the starting time of the present setting) If the button is held down, the time interval will increase progressively by 1 hour unit. 2. Press "Timer Confirm" button to send the timer setting to the Dehumidifier. Then the timer light on the unit lights up, indicating that the unit is in the timer mode. When it reaches the switch-off time, the air-conditioner will automatically shut down. NOTE: Timer-Off can only be set when the Dehumidifier is running. Timer-On and Timer-Off cannot be set at the same time. Timer display on the remote controller : While time passes, the display shows the remaining time. If the "On-Off" button is pressed while the unit is under timer-off setting, then the unit will shut down immediately, the timer setting is cancelled and the timer light will be off.
Timer Cancellation Press "Timer-Cancel" button to cancel the timer-on or timer-off settings.
16
AFT ON
FAN
SWING
MODE
FA N
SWING
Timer Switch Off
C
ON / OFF
OFF
ON
TIMER
CANCEL
CONFIRM
SLEEP
HEAT ER
1 2
Defrost system Sequences of the defrosting: 1- Start The defrosting is engaged if the following conditions are at the same time fulfiled: - the compressor and the fan motor run without stopping; o - the defrosting sensor temperature lower than 3 C , and the duration of time more than 45 minutes; o - the defrosting sensor temperature goes down to -7 C. 2- After 15 seconds, the 4 way valve shifts. 3- Five seconds after its stop, the compressor starts alone ; And the accumulated freeze on the gills becomes melting, what is generally with a steam cloud . 4- Stop: The defrosting stops if one of the following conditions is fulfiled: - the defrosting operates 20 seconds and the detected temperature by the o defrost sensor goes up to 12 C; - the compressor had run totally 8 minutes. 5- The compressor runs. 6- After 15 seconds the 4 way valve shifts 7- Five seconds after its stop the compressor and the fan start for restarting in heating mode. 8- The running light is blinking during defrosting.
Assistant heater ( Option ) 1〉Electric al heater doe s work only if i n
heating
temperature or dehumidify mode;
2〉w hen compressor is running, press button ‘heater’, the dis play board’s ‘ ’
l
ights,
electrical heater s tarts; press button‘heater’ again, the dis pl ay board’s ‘ ’turn off, electrica l heater stops . When get to desi re temperature, both compressor and electrical heater stop at the same ti me ; 3〉When compress or is not running, press button ‘heater’ , the disp lay board’s ‘
’ fl ashes,
the
heater i s standby at the moment, it works after compressor starts.
Water drainage system During the dehumidify mode, the condenser water will be drained into the internal water tank .When the water reaches the certain level, the water drain pump will work. If the water can be drained out in 8 mins, the dehumidifier will keep working. If not, the compressor and the motor will stop working. Mean while an error message “ E4 “ will appear in the control panel to inform you to empty the water. In this instance, you should cut the power off, and then restart the dehumidifier ,and the operation will continue .
17
Error Codes E1 : Room temperature sensor error; E2 : Defrost temperature sensor error; E3 : Humidity sensor error; E4 : Drain error;
TIMER
SWING
HEATER
SWING
_
+
FAN SPEED
MODE
ON/OFF
Wiring diagram With electrical assistant heater WIRING DIAGRAM FAN MOTOR
COMPRESSOR
Y/G
G
STEP MOTOR
MS
MS
2
PUMP
RED WHITE
S CM R
Synchronization MOTOR
C1 Y/G
FM
C
G
C
5
5
AC-N2 RY1 RY2
AC-N
HF MF LF AC-N
LEFT
RY9
TEMPERATURE CONTROLLER
PCB
NO
L
RY6
WATER LEVEL SWITCH
BLACK
BLACK WHITE
ROOM TEMPERATURE SENSOR DEFROST
BLACK
N
Y/G WHITE
CNA
3
CNB
G
TEMPERATURE SENSOR HUMIDITY TEMPERATURE SENSOR
TERMINAL 11
ASSISTANT HEATER RED
WHIT
PUBLIC TERMINAL
NO
COM
DISPLAY RECEIVE BOARD
CN-DISP
Without electrical assistant heater WIRING DIAGRAM COMPRESSOR
PUMP
RED
S
C1
Y/G
G
R
CM
Y/G
WHITE
Synchronization STEP MOTOR MOTOR
FAN MOTOR
FM
MS MS
C2
G 5
C
5
AC-N2 HF MF LF ACN
RY1 RY2
AC-N
RY6
LEFT
WATER LEVEL SWITCH ROOM TEMPERATURE SENSOR DEFROST
NO
L
PCB
BLACK
N
WHITE Y/G CNA
CNB
3
G
TERMINAL 11
TRANSFORMER
DISPLAY RECEIVE CN-DISP BOARD
18
TEMPERATURE SENSOR HUMIDITY TEMPERATURE SENSOR
Maintenance For smart use of the Dehumidifier:
Setting of
proper
Do
room temperature
not
inlet or
block
the
air
outlet
Proper temperature
Close
doors
and
Use
the
timer
Use
the
louvers
effectively
windows during operation
If
the
be time,
unit
is
used
for
turn
off
not a
to long
the power
TMIEHRASWNGI
+
A C
FAN
% _
SPEMDON/F
supply
main
switch.
OFF
19
effectively
Maintenance For smart use of the Dehumidifier:
WARNING Before maintenance,be
sure
to turn off the system
Remote Controller
not
Wipe the air conditioner by using a soft and dry cloth.For serious stains,use a neutral detergent diluted with water.Wring the water out of the cloth before wiping.then wipe off the detergent completely.
use
the
following
for
cleaning
Hot water over 40 oC (104 oC ) may cause discoloring or deformation.
Gasoline,benzine, thinner or cleanser may damage the coating of the unit.
Air
Filter
the circuit breaker.
Body
Do not use water, wipe the controller with a dry cloth.Do not use glass cleaner or chemical cloth.
Do
and
cleaning
Press the clasp on the top of the grill and pull the grill out, and then the filter will be taken out along a gradient way.
Clean
the
filter.
Use a vacuum cleaner to remove dust, or wash the filter with water.After washing, dry the filter completely in the shade. Then, reinstall it onto the unit.
20
Once every two weeks
Maintenance To keep your Dehumidifier in good condition after season:
1. Operate in
FAN
mode
for
about
half a
On a fine day, unit shall be started and operate FAN mode for about half a day until the inside of the unit becomes thoroughly dry.
2.
day. in
Turn off the power supply main switch.
OFF
3.
Cleaning the
body.
4. Take out the batteries wireless remote controller.
from
the
21
Trouble shooting Before
asking
for
service,
check
Phenomenon The system does restart immediately.
the Cause
following or
check
first. points
When unit is stopped, it won't restart immediately until 3 minutes have elapsed to protect the system.
not
When the electric plug is pulled out and reinserted, the protection circuit will work for 3 minutes to protect the dehumidifier. Noise
is
During unit operation or at stop, a swishing or gurgling noise may be heard. At first 2-3 minutes after unit start, this noise is more noticeable. (This noise is generated by refrigerant flowing in the system.)
heard:
Normal Performance inspection
During unit operation, a cracking noise may be heard. This noise is generated by the casing expanding or shrinking because of temperature changes. Should there be a big noise from air flow in unit operation, air filter may be too dirty.
Multiple check
Smells
are
generated.
Does
not
work
Inefficient
at
This is because the system circulates smells from the interior air such as the smell of furniture, cigarettes.
all.
Is power plug inserted? Is there a power failure? Is fuse blown out?
Is the air filter dirty? Normally it should be cleaned every 15 days. Are there any obstacles before outlet? Is temperature set correctly? Are
22
there some doors or
inlet
and
windows left open?