Transcript
OPzV 2-2000 2V2000AH OPzV Series SLA Battery
Opzv Series BSB Opzv Series Valve Regulated Lead Acid batteries are designed with a proven combination of GEL and Tubular technologies to offer a very high lever of reliability. Opzv batteries benefit from an optimized plate design which gives capacities in excess of the DIN standard values. In addition, this series offers both a longest float life and a high cycle life in widely industrial field.
Application · Telecommunications · Cable Television · Electric Utility · Control Equipment · Security System
· Medical Equipment · UPS · Railroad Utility · Photovoltaic System · Alternative Energy System
General Features
3mm [0.12inch]
· Sealed and maintenance free operation. · Non-Spillable construction design. · ABS containers and covers(UL94HB, UL94V-0) optional. · Safety valve installation for explosion proof. · High quality and high reliability. · Super long service life. · Lowest self discharge characteristic. · Super reliability.
14mm [0.55inch] 8mm [0.31inch]
Construction · Sealant ........Epoxy Resin · Safety valve .....EPDR ! Terminal ........ Copper ! Separator ...... PVC-SiO2 ! Electrolyte .....Sulfuric acid Thixotropic Gel
Terminal Dimensions
399mm [15,71inch]
797mm [31,38inch]
772mm [30,39inch]
· Component ......Raw material · Positive ........Lead dioxide · Negative ........Lead · Container ........ABS · Cover ........ABS
212mm[8,35inch]
Battery Model
OPzV 2-2000
Designed Floating Life Capacity(25oC)
Dimensions
15 Years 20HR(102A,1.75V)
10HR(200A,1.75V)
5HR(347A,1.75V)
2040AH
2000AH
1735AH
1295AH
Length
Width
Height
Total Height
399mm(15.71inch)
212mm(8.35inch)
772mm(30.39inch)
797mm(31.38inch)
160Kg (352.80 lbs)
Approx. Weight
Full charged at 25oC: 0.0005 Ohm
Internal Resistance
3% of capacity declined per month at (25oC)
Self Discharge Capacity Affected by Temp.(20HR) Charge Voltage(25oC)
1HR(1295A,1.75V)
o
40 C
25oC
0oC
-15oC
102%
100%
85%
65%
Cycle use
Float use
2.3V-2.35V(-5mV/ oC), max. Current: 400A
2.25-2.27V(-3.3mV/ oC)
Page 1 of 2
OPzV 2-2000 2V2000AH
Charge Voltage
Constant Charge At 0.25CA-2.30V (25 C)
(CA) (V/Cell)
100 80
0.25
Charge Capacity
Charge Voltage
2.17 100%Discharge
0.20
60
2.00
50%Discharge
0.15
40
0.10 20
1.83
0.05
0
0
Charge Current
0
2
4
6
8
10
2.17 2.00 1.83 0.25CA 0.1CA
1.67 1.60
1CA
0.6CA
30
60
0.05CA
1.33 0
12
2
6
12
3
Min
Time(hour)
10 Hour
20
Self Discharge Characteristics
Relationship of OCV and state of charge 110 105
2.25
2.17
Capacity (%)
Battery Voltage (V/Cell)
25 C
o
120 2.33
o
Discharge Characteristic
Charge Characteristic Discharge Voltage (V/Cell)
Charge
(%)
Current
Charge Capacity
OPzV Series SLA Battery
2.08
2.00
100 95 90 85 80 75 70 65 60 55 50
1.92
o
1.83
0
10
20
30
40
50
60
70
80
90
100
40
0
1
2
20oC
o
40 C
45
30 C 3
4
5
6
7 8
9 10 11 12 13 14 15 16 17 18 19 20
Storage time:months
Remained Capacity(%)
Constant current discharge ratings-amperes at 25oC
F.V/Time 1.70V 1.75V 1.80V 1.83V 1.87V 1.90V
15MIN 1824 1600 1344 1216 960 800
30MIN 1552 1408 1232 1120 960 800
1HR 1168 1100 984 904 792 696
2HR 756 720 676 640 576 520
3HR 560 544 520 496 453 410
5HR 372 363 351 338 311 282
8HR 248 246 239 229 218 205
10HR 205 204 200 192 181 170
20HR 125 124 120 116 105 99.9
3HR 1050 1044 1003 964 872 788
5HR 752 732 707 666 600 518
8HR 510 495 460 439 408 383
10HR 398 392 362 362 335 322
20HR 243 238 216 205 195 189
Constant power discharge ratings-watts at 25oC
F.V/Time 1.70V 1.75V 1.80V 1.83V 1.87V 1.90V
15MIN 3057 2708 2201 2090 1669 1608
30MIN 2525 2212 2109 1801 1641 1610
1HR 1887 1815 1636 1603 1566 1378
2HR 1354 1396 1314 1248 1105 1005
ISO9001
Address:Meilong Road,LongHua Town,BaoAn District,Shenzhen,China. TEL.86-755-28094189
Fax:86-755-8372 2565
Email:
[email protected] Page 2 of 2
Http:// www.wbrbattery.com