Transcript
OPzV 2-1200
2V1200Ah
OPzV Series SLA Battery Range Summary By combining the newly developed tubular positive plates with fumed gelled electrolyte, BSB created the innovative OPzV range of batteries. The range offers 20 years design life and very high deep cycling capabilities. This range is recommended for telecom outdoor applications, renewable energy systems and other harsh environment applications.
Application · Medical Equipment · UPS · Railroad Utility · Photovoltaic System · Alternative Energy System
· Telecommunications · Cable Television · Electric Utility · Control Equipment · Security System
General Features · Sealed and maintenance free operation. · Non-Spillable construction design. · ABS containers and covers(UL94 V0, optional). · Safety valve installation for explosion proof. · High quality and high reliability. · Super long service life. · Lowest self discharge characteristic. · Super reliability.
7mm (0.28inch)
20mm (0.79inch)
M8mm (0.31inch)
Construction Safety valve Terminal Separator Electrolyte
...... ...... ...... ......
EPDR Copper Polymer Thixotropic Gel
275mm(10.83inch)
Terminal Dimensions
681mm(26.8inch)
Lead dioxide Lead ABS ABS Epoxy Resin
646mm(25.4inch)
Positive ...... Negative ...... Container ...... ...... Cover Sealant ......
210mm(8.27inch)
Battery Model
OPzV 2-1200
Designed Floating Life Capacity(20oC)
20 Years 20HR(64.0A,1.80V)
10HR(120A,1.80V)
5HR(211A,1.75V)
1HR(706A,1.75V)
1200Ah
1055Ah
706Ah
1280Ah Dimensions
Length
Width
Height
Total Height
275mm(10.83inch)
210mm(8.27inch)
646mm(25.4inch)
681mm(26.8inch)
Approx. Weight
84Kg (185 lbs)
Internal Resistance
Full charged at 20oC: 0.00027 Ohm
Self Discharge
2% of capacity declined per month at (20oC)
Capacity Affected by Temp.(10HR) Charge Voltage(20oC)
40oC 109%
20oC
0oC
100%
85%
Cycle use 2.35V-2.40V(-5mV/ oC), max. Current: 240A
Page 1 of 2
-15oC 65% Float use
2.25-2.29V(-3mV/ oC)
OPzV 2-1200
2V1200Ah
Charge Voltage
(CA) (V/Cell)
(%) 120
2.35 100 80
0.20
Discharge Characteristic (20oC)
Charge Characteristic o
Constant Charge at 0.2CA-2.35V (20 C) Charge Capacity
Charge Voltage
2.17 100%Discharge
60
0.15
40
0.10
20
0.05
2.00
50%Discharge
1.83 Charge Current
0
0
0
2
4
6
8
10
Discharge Voltage (V/Cell)
Current
Charge
Charge Capacity
OPzV Series SLA Battery
2.17 2.00 1.83 0.05CA 0.25CA 0.1CA
1.67 1.60
0
12
2
6
30
60
3
10 Hour
20
Self Discharge Characteristics
2.25
110 105
2.17
100 95 90
Capacity (%)
Battery Voltage (V/Cell)
12 Min
Relationship of OCV and state of charge
2.00
0.6CA
1.33
Time(hour)
2.08
1CA
85 80 75 70 65 60 55 50
1.92
45
1.83
0
10
20
30
40
50
60
70
80
90
100
40 0
o
3
20oC
30oC
40 C 6
9
12
15
18
21
24
27
30
Storage time:months
Remained Capacity(%)
Constant current discharge ratings-amperes at 20oC
F.V/Time 1.70V 1.75V 1.80V 1.83V 1.87V 1.90V
15min 1272 1128 984 888 720 624
30min 1032 936 840 756 660 588
1h 738 706 655 605 542 491
2h 429 417 399 384 354 330
3h 318 312 300 292 274 258
5h 213 211 208 203 195 185
8h 147 146 144 141 134 129
10h 122 121 120 117 112 107
20h 65.3 64.7 64.0 62.3 59.9 57.2
3h 640 623 603 596 583 540
5h 438 433 424 405 399 386
8h 290 284 280 268 262 251
10h 235 234 233 225 220 210
20h 125 124 122 120 118 115
Constant power discharge ratings-watts at 20oC
F.V/Time 1.70V 1.75V 1.80V 1.83V 1.87V 1.90V
15min 2193 2018 1788 1645 1555 1294
30min 1787 1712 1607 1378 1304 1199
1h 1339 1300 1227 1130 1098 1000
2h 814 793 770 735 730 705
ISO9001
COPYRIGHT BSB POWER COMPANY LIMITED Page 2 of 2