Transcript
OPzV 2-500
2V500Ah
OPzV Series SLA Battery Range Summary By combining the newly developed tubular positive plates with fumed gelled electrolyte, BSB created the innovative OPzV range of batteries. The range offers 20 years design life and very high deep cycling capabilities. This range is recommended for telecom outdoor applications, renewable energy systems and other harsh environment applications.
Application · Telecommunications · Cable Television · Electric Utility · Control Equipment · Security System
· Medical Equipment · UPS · Railroad Utility · Photovoltaic System · Alternative Energy System
General Features · Sealed and maintenance free operation. · Non-Spillable construction design. · ABS containers and covers(UL94 V0, optional). · Safety valve installation for explosion proof. · High quality and high reliability. · Super long service life. · Lowest self discharge characteristic. · Super reliability.
7mm (0.28inch)
20mm (0.79inch)
M8mm (0.31inch)
Construction Safety valve Terminal Separator Electrolyte
Lead dioxide Lead ABS ABS Epoxy Resin
...... ...... ...... ......
EPDR Copper Polymer Thixotropic Gel
506mm(19.9inch)
166mm(6.54inch)
Terminal Dimensions
471mm(18.5inch)
Positive ...... Negative ...... Container ...... ...... Cover Sealant ......
206mm(8.11inch)
Battery Model
OPzV 2-500
Designed Floating Life Capacity(20oC)
20 Years 20HR(27.0A,1.80V)
10HR(50.0A,1.80V) 500Ah
540Ah Dimensions
5HR(88.2A,1.75V) 441Ah
274Ah
Length
Width
Height
Total Height
166mm(6.54inch)
206mm(8.11inch)
471mm(18.5inch)
506mm(19.9inch)
Approx. Weight
35.5Kg (78.3 lbs)
Internal Resistance
Full charged at 20oC: 0.00065 Ohm
Self Discharge
2% of capacity declined per month at (20oC)
Capacity Affected by Temp.(10HR) Charge Voltage(20oC)
1HR(274A,1.75V)
40oC 109%
20oC
0oC
100%
85%
Cycle use 2.35V-2.40V(-5mV/ oC), max. Current: 100A
Page 1 of 2
-15oC 65% Float use
2.25-2.29V(-3mV/ oC)
Opzv 2-500
2V500Ah
Charge Voltage
(CA) (V/Cell)
(%) 120
2.35 100 80
0.20
Discharge Characteristic (20oC)
Charge Characteristic o
Constant Charge At 0.2CA-2.35V (20 C) Charge Capacity
Charge Voltage
2.17 100%Discharge
60
0.15
40
0.10
20
0.05
2.00
50%Discharge
1.83 Charge Current
0
0
0
2
4
6
8
10
Discharge Voltage (V/Cell)
Current
Charge
Charge Capacity
Opzv Series SLA Battery
2.17 2.00 1.83 0.05CA 0.25CA 0.1CA
1.67 1.60
0
2
6
Relationship of OCV and state of charge
30
60
3
10 Hour
20
Self Discharge Characteristics
2.25
110 105
2.17
100 95 90
Capacity (%)
Battery Voltage (V/Cell)
12 Min
Time(hour)
2.00
0.6CA
1.33
12
2.08
1CA
85 80 75 70 65 60 55 50
1.92
45
1.83
0
10
20
30
40
50
60
70
80
90
100
40 0
o
3
20oC
30oC
40 C
9
6
12
15
18
21
24
27
30
Storage time:months
Remained Capacity(%)
Constant current discharge ratings-amperes at 20oC
F.V/Time 1.70V 1.75V 1.80V 1.83V 1.87V 1.90V
15min 572 515 448 406 350 292
30min 437 406 371 342 303 273
1h 283 274 259 245 237 203
2h 175 171 164 159 149 137
3h 129 127 123 119 114 106
5h 90.0 88.2 86.5 85.0 84.0 74.5
8h 62.0 61.6 60.0 59.5 58.0 55.0
10h 52.0 51.0 50.0 49.7 48.0 46.0
20h 28.0 27.5 27.0 26.8 25.9 24.8
3h 235 230 225 221 210 180
5h 158 156 153 149 145 127
8h 114 112 109 105 100 95.0
10h 95.3 95.0 94.0 93.5 88.8 85.8
20h 57.0 56.0 55.0 54.0 52.0 51.0
Constant power discharge ratings-watts at 20oC
F.V/Time 1.70V 1.75V 1.80V 1.83V 1.87V 1.90V
15min 936 825 685 600 538 520
30min 762 711 634 555 468 500
1h 511 477 467 442 429 388
2h 343 333 301 290 275 247
ISO9001
COPYRIGHT BSB POWER COMPANY LIMITED Page 2 of 2
(Updated: 1-Nov-2010)