Transcript
OPzV 2-800
2V800Ah
OPzV Series SLA Battery Range Summary By combining the newly developed tubular positive plates with fumed gelled electrolyte, BSB created the innovative OPzV range of batteries. The range offers 20 years design life and very high deep cycling capabilities. This range is recommended for telecom outdoor applications, renewable energy systems and other harsh environment applications.
Application · Medical Equipment · UPS · Railroad Utility · Photovoltaic System · Alternative Energy System
· Telecommunications · Cable Television · Electric Utility · Control Equipment · Security System
General Features · Sealed and maintenance free operation. · Non-Spillable construction design. · ABS containers and covers(UL94 V0, optional). · Safety valve installation for explosion proof. · High quality and high reliability. · Super long service life. · Lowest self discharge characteristic. · Super reliability.
7mm (0.28inch)
20mm (0.79inch)
M8mm (0.31inch)
Construction Safety valve Terminal Separator Electrolyte
...... ...... ...... ......
EPDR Copper Polymer Thixotropic Gel
191mm(7.52inch)
Terminal Dimensions
681mm(26.8inch)
Lead dioxide Lead ABS ABS Epoxy Resin
646mm(25.4inch)
Positive ...... Negative ...... Container ...... ...... Cover Sealant ......
210mm(8.27inch)
Battery Model
OPzV 2-800
Designed Floating Life Capacity(20oC)
20 Years 20HR(43.0A,1.80V)
10HR(80.0A,1.75V)
1HR(448A,1.75V)
705Ah
448Ah
800Ah
860Ah Dimensions
5HR(141A,1.75V)
Length
Width
Height
Total Height
191mm(7.52inch)
210mm(8.27inch)
646mm(25.4inch)
681mm(26.8inch)
Approx. Weight
58.5Kg (129 lbs)
Internal Resistance
Full charged at 20oC: 0.0004 Ohm
Self Discharge
2% of capacity declined per month at (20oC)
Capacity Affected by Temp.(10HR) Charge Voltage(20oC)
40oC 109%
20oC
0oC
100%
85%
Cycle use 2.35V-2.40V(-5mV/ oC), max. Current: 160A
Page 1 of 2
-15oC 65% Float use
2.25-2.29V(-3mV/ oC)
OPzV 2-800
2V800Ah
Charge Voltage
(CA) (V/Cell)
(%) 120
2.35 100 80
0.20
Discharge Characteristic (20oC)
Charge Characteristic o
Constant Charge At 0.2CA-2.35V (20 C) Charge Capacity
Charge Voltage
2.17 100%Discharge
60
0.15
40
0.10
20
0.05
2.00
50%Discharge
1.83 Charge Current
0
0
0
2
4
6
8
10
Discharge Voltage (V/Cell)
Current
Charge
Charge Capacity
OPzV Series SLA Battery
2.17 2.00 1.83 0.05CA 0.25CA 0.1CA
1.67 1.60
0
12
2
6
30
60
3
10 Hour
20
Self Discharge Characteristics
2.25
110 105
2.17
100 95 90
Capacity (%)
Battery Voltage (V/Cell)
12 Min
Relationship of OCV and state of charge
2.00
0.6CA
1.33
Time(hour)
2.08
1CA
85 80 75 70 65 60 55 50
1.92
45
1.83
0
10
20
30
40
50
60
70
80
90
100
40 0
o
3
20oC
30oC
40 C 6
9
12
15
18
21
24
27
30
Storage time:months
Remained Capacity(%)
Constant current discharge ratings-amperes at 20oC
F.V/Time 1.70V 1.75V 1.80V 1.83V 1.87V 1.90V
15min 848 752 656 592 480 416
30min 688 624 560 504 440 392
1h 468 448 416 384 344 312
2h 286 278 266 256 236 220
3h 212 208 200 195 183 172
5h 142 141 139 136 130 124
8h 98.0 97.6 96.0 94.0 89.6 86.0
10h 82.0 81.0 80.0 78.0 74.5 71.5
20h 44.3 43.7 43.0 42.1 40.2 38.6
3h 427 417 402 396 389 353
5h 293 289 284 269 260 256
8h 195 191 189 179 174 167
10h 158 156 154 151 146 138
20h 86.5 86.0 85.0 84.0 81.0 78.5
Constant power discharge ratings-watts at 20oC
F.V/Time 1.70V 1.75V 1.80V 1.83V 1.87V 1.90V
15min 1462 1346 1192 1096 1038 890
30min 1190 1142 1074 919 870 799
1h 849 810 779 718 699 635
2h 542 528 514 490 480 472
ISO9001