Preview only show first 10 pages with watermark. For full document please download

Ordering Guide Foms-fps-hd

   EMBED


Share

Transcript

Ordering Guide for FOMS-FPS-HD product range FOMS-FPS-HD Ordering guide Page 1 of 11 Issue 0.2 07-2012 O r d e r in g G u id e fo r th e 1 9 ” H ig h D e n s ity F r o n t P a t c h in g /S p lic in g S h e lf ( F O M S FPS-HD) This document provides assistance with the selection of the High Density Front Patching/Splicing shelf. It includes the following sections: 1 Product description 2 2 Ordering information 3 2.1 FOMS front patching/splicing shelf 3 3 Product guide 5 3.1 Shelf description 5 3.2 Shelf dimensions 7 3.3 Shelf capacity 8 3.4 Accessories 9 3.5 Tools 11 FOMS-FPS-HD Ordering guide Page 2 of 11 Issue 0.2 07-2012 1 Product description The High Density Front Patching/Splicing Shelf, FOMS-FPS-HD is a shelf assembly that provides cable splicing and patch cord patching in a rack environment. The 1HU FOMS-FPS-HD shelf has a capacity of 48 patching points with SC and LC connectors. The 2HU FOMS-FPS-HD shelf has a capacity of 96 patching points with SC and LC connectors. This shelf can be used with TE Connectivity racks as well as with other 19” (including standard brackets) or metric (ETSI) racks (optional mounting brackets see section 3.4 "Accessories"). Multiple configurations are possible: −Patching only −Splicing and patching of either loose tube, intra-facility (IFC) The shelf consists of a metal chassis with pivoting bottom tray for easy access to the front patch panel and splicing area. The connectors on the front panel are left- or right-angled to reduce the risk of eye damage when working with active fiber. These positions also allows easy jumper routing to the sides in (for example) an equipment rack. Connector adapters and pigtails are pre-mounted for easy installation and handling. The patch panel is positioned backwards so that the connector boots are not protruding from the shelf. Field installable mounting brackets are provided and allow for different mounting positions (for details see installation instructions). The ‘splicing and patching’ shelf includes a tray tower with splicing trays behind the patch panel and prefibered pigtails routed from the splicing tray to the back of the patch panel. The FOSC-400A splicing trays are equipped with splice holders, a plastic transparent cover and a cable management spider to store overlength of 900µ pigtails. Connector adapters and 900µ pigtails are included in the standard kit content. Positive fiber management is guaranteed by bend controls on the bottom plate and in the splicing trays. FOMS-FPS-HD Ordering guide 2 Orde ri ng informa ti on 2.1 FOMS front patching/splicing shelf Refer to Section 3 for full product descriptions. Patch Standard kit 1HU content (right) Installed on the shelf • Id label • 48 pre-mounted adapters Included in a separate kit • 19” 1HU mounting bracket (+screws/cage nuts) • 45° angled bracket with 1HU wraparound trumpet • 1m Hook and loop fastener Patch Standard kit 2HU content (right) Installed on the shelf • Id label • 96 pre-mounted adapters Included in a separate kit • 19” 2HU mounting brackets (+screws/cage nuts) • 45° angled bracket with 2 times 1HU wraparound trumpet • 1m Hook and loop fastener Page 3 of 11 Issue 0.2 07-2012 FOMS-FPS-HD Ordering guide Page 4 of 11 Issue 0.2 07-2012 Splice Standard kit 1HU content (right) Installed on the shelf • Id label • 48 pre-mounted adapters + pigtails (12 colors) with 1.2m overlength installed in the tray, allowing 10 repair splices • 2 times 24 splice tray + covers + wedge + Hook and loop fastener Included in a separate kit • 19” 1HU mounting brackets (+screws/cage nuts) • Flex tube (inner Ø 6.2 mm; outer Ø 10.0 mm; length 650 mm ± 5 mm) • 45° angled bracket with 1HU wraparound trumpet • 1 piece Hook and loop fastener (~120 mm ± 5 mm) • Cable termination kit (strength member + inbus + screw + washer, axial pull device, 2 tie-wraps, foam strip 15x1x40 mm) • Tie-wraps: 20 pcs • Foam strip: 15x1x200 mm Splice Standard kit 2HU content (right) Installed on the shelf • Id label • 96 pre-mounted adapters + pigtails (12 colors) with 1.2m overlength installed in the tray, allowing 10 repair splices • 4 times 24 splice tray + covers + wedge + Hook and loop fastener • Flex tube (inner Ø 9.6 mm; outer Ø 13.0mm; length 530 mm ± 5 mm) Included in a separate kit • 19” 2HU mounting brackets (+screws/cage nuts) • 45° angled bracket with 2 times 1HU wraparound trumpet • 2 pieces Hook and loop fastener (~120 mm ± 5 mm) • Cable termination kit (strength member + inbus + screw + washer, axial pull device, 2 tie-wraps, foam strip 15x1x40 mm) • Tie-wraps: 20 pcs • Foam strip: 15x1x200 mm • Edge protection: 140 mm FOMS-FPS-HD Ordering guide Page 5 of 11 Issue 0.2 07-2012 3 Product guide 3.1 Shelf description Chassis and pivoting bottom plate The FOMS-FPS-HD chassis are ready to be fitted inside an optical rack using mounting brackets, screws and cage nuts. The chassis width is designed according to the 19” standard. Adaptation brackets to ETSI are available as an option. All chassis are painted (color RAL 7035). Cable termination kit A strength member fixation and cable entrance kit are included in the standard shelf to terminate loose tube single fiber or intra-facility cable. Shelf roof The roof of the shelf can easily be removed to facilitate internal access before the shelf is installed in a rack. Mounting brackets The shelf has field-mountable brackets to accommodate for: − back-mounting specifically for TE Connectivity’s FIST racks − 2 other different back mounting positions − 3 different front mounting positions (see installation instructions) A small tool (Allen key 2.5mm) is included to fix the brackets on the shelf. Front patch panel The patching module plane is right or left angle oriented to reduce the risk of eye damage when working with active fiber. This also prevents the outgoing patch cords from making strong bends when leaving the shelf. Patching-only configuration* 1HU Patch cords enter the shelf on the side and are guided towards the back of the patch panel via overlength storage basket which controls the bend radius. Patch cords connected at the front of the patch panel leave the shelf in a controlled way via the integrated bend control and the wrap-around trumpet. Adaptors are typically pre-mounted. C a u t i o n : The 1HU patch/patch shelf doesn’t support front pigtail entrance (not enough space to install a pigtail bridge) 2HU Patch cords enter the shelf via the front, the side or the back and are guided towards the back of the patch panel via overlength storage basket that controls the bend radius. Patch cords connected at the front of the patch panel leave the shelf in a controlled way via the integrated bend control and the wrap-around trumpet. Adaptors are typically pre-mounted. FOMS-FPS-HD Ordering guide Page 6 of 11 Issue 0.2 07-2012 Splicing and patching configuration* Loose tube or intra-facility cables (IFC) enter via the side or back of the shelf and are guided towards the splicing trays. In case of a loose tube cable and a non pre-connectorized IFC, fibers have to be spliced to secondary coated pigtails in the splicing trays and then guided towards the back of the patch panel. In case of a pre-connectorized IFC, overlength is stored in a basket. Patch cords connected at the front of the patch panel leave the shelf in a controlled way via the integrated bend control and the wrap-around trumpet. Secondary coated pigtails are typically pre-installed in the shelf. The tray tower can be pivoted to improve accessibility for splicing. Page 7 of 11 FOMS-FPS-HD Issue 0.2 Ordering guide 07-2012 3.2 Shelf dimensions 19” chassis standard 1HU version 2HU version Width (with/without mounting brackets) 481 / 444 mm 481 / 444 mm Height 44 mm 88 mm HU-Height Units (requires 1 19” HU) (requires 2 19" HU) Depth 280 mm 280 mm Note: A HU is a “height unit”. Refer to rack documentation for more details. Page 8 of 11 FOMS-FPS-HD Issue 0.2 Ordering guide 07-2012 3.3 Shelf capacity FOMS-FPS-HD Number of FOSC A splicing trays Splice & patch Patch only 2 or 4 for 1HU NA(b) 4 or 8 for 2HU FOSC A splicing tray capacity 12 or 24 NA Incoming cable 2 NA Patch panel capacity (1HU / 2HU) 48/96 48/96 Patch cord length inside the shelf – from the trumpet till the NA 0.50-0.90 m 0.06-0.40 m 0.06-0.40 m back side of the patch panel (a) Patch cord length inside the shelf – from the trumpet till the front side of the patch panel (a) (a) This patch cord length is measured for the open shelf to allow access after installation. (b) 1 optional tray possible for repair splices Page 9 of 11 FOMS-FPS-HD Issue 0.2 Ordering guide 07-2012 3.4 Accessories Name Qty/Pk Description FOMS-FPS-O-MB2-M 1 kit ETSI mounting brackets (for 1HU) FIST-MB2-2HU-M 1 kit ETSI mounting brackets (for 2HU) FIST-GS-FLEX-7-50 50 m Flexible tubing (internal ∅ 6.2 mm) FIST-GS-FLEX-10-50 50 m Flexible tubing (internal ∅ 10.0 mm) FOMS-FPS-HD-CT-B-1 1pc Extra axial pull kit 2 SMOUV-1120-02-PK 100 pc 45 mm long heat-shrinkable splice protection sleeves nd cable * For additional trumpet brackets, contact your local sales engineer Adaptation brackets FOMS-FPS-O-MB2-M - FIST-MB2-2HU-M These brackets allow the installation of this 19” shelf in an ETSI rack. FIST-GS-FLEX-7-50 - FIST-GS-FLEX-10-50 50 meter flexible tubing with inside diameter of 6.2 mm/10 mm, needed when terminating a loose tube cable in a TE Connectivity rack. Flexible tubing FIST-GS-FLEX-10-50 Flexible tubing with inside diameter of 10 mm, needed when terminating a loose tube cable in a TE Connectivity rack. Page 10 of 11 FOMS-FPS-HD Issue 0.2 Ordering guide 07-2012 FOMS-FPS-HD-CT-B-1 Additional axial pull kit. Van be used to terminate a 2 nd SMOUV-1120-02-PK 45 mm long heat-shrinkable splice protection sleeves cable FOMS-FPS-HD Ordering guide Page 11 of 11 Issue 0.2 07-2012 3.5 Tools Cage nut tool FACC-CAGE-NUT-TOOL Tool to install cage nuts in the rack. Long Allen key FACC-ALLEN-KEY-5-350 Allen key, diameter 5 mm, length 350 mm for back mounting of shelves in rack. TE Connectivity products deliver a competitive advantage by meeting stringent demands for performance and reliability. Innovative TE Connectivity components and systems are used in telecommunications, electronics, transportation, infrastructure and energy networks markets throughout the world. Tyco Electronics Raychem bvba TE (logo) and TE Connectivity are trademarks of the TE Connectivity group of companies and its licensors. Diestsesteenweg 692 While TE Connectivity and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalog, TE Connectivity cannot assure that this information is error free. For this reason, TE Connectivity does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. TE Connectivity reserves the right to make any adjustments to the information at any time. TE Connectivity expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. TE Connectivity’ only obligations are those stated in TE Connectivity’ Standard Terms and Conditions of Sale. TE Connectivity will in no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgment to evaluate the suitability of a product for a certain purpose and test each product for its intended application. B-3010 Kessel-Lo, Belgium Tel.: 32-16-351 011 Fax: 32-16-351 697 www.te.com www.telecomnetworks.com OG/FOMS-FPS-HD/2/07/12