Multi Zone Heat Pump System for Buildings Large Capacity Zoned VRF System DC Inverter Controlled Compressor Long Piping System Design High Efficiency R410A Refrigerant
Fujitsu General creates high-quality and environmentally-friendly products that provide a comfortable environment by using the air conditioning technology, innovation and creativity which we developed over 35 years ago.
High Reliability High Efficiency
V series
More Comfort
Multiple condensing units on a single S series 8 Tons / Heat recovery refrigerant circuit 8 Tons / Heat recovery 6, 8 Tons / Heat pump provides greater capacity. & Heat pump 6, 8 Tons / Cooling
2001
VRF System
2003
2006 Green Initiatives Fujitsu introduces Inverter technology and the use of R410A refrigerant.
Easy Installation
Easy Service & Design Versatility
Maintenance
TABLE OF CONTENTS FEATURES
AIRSTAGE History
Design Versatility .......................................... 5 Easy Installation ........................................... 6 High Reliability ............................................. 7 Comfort & Convenience ............................... 8 Easy Service & Maintenance ....................... 9
FUJITSU GENERAL’s VRF AIRSTAGE Series has been developed based on our long-term air-conditioning technology know-how and was first provided 10 years ago. We have offered a series of products for large homes to large-scale buildings to meet the various market needs.
MODEL LINEUP Indoor and Outdoor Model Table ................. 10
OUTDOOR UNITS Energy Saving Features ............................ 12 Dimensions & Specifications ....................... 13
INDOOR UNITS 60Hz 6 to 24 Tons / Heat pump 100% Inverter driven For USA and Latin America
V-II series New 4-face heat exchanger reduces unit size and increases efficiency.
2009
2010
2012
RoHS Compliant
Green Advancement
Restriction of Hazardous Substances is an EU directive intended to protect the environment by forcing manufacturers to use environmentally friendly materials in all consumer electronics.
Use of 100% Inverter driven DC compressors.
High Quality Development and Production Environment The Headquarters-JAPAN R&D Center is equipped with a wide range of testing equipment envisioning a variety of operating conditions. This i n c l u d e s a t e s t i n g t o w e r w i t h a 1 9 8 f t . ( 6 0 m ) h e i g h t d i ff e r e n c e f o r buildings.We provide high quality & reliable products that meet the
Compact Cassette ....................................... 14 Cassette ......................................................16 Slim Compact Duct ..................................... 18 Duct ............................................................ 20 High Static Pressure Duct ........................... 22 Floor/Ceiling ................................................ 24 Ceiling ......................................................... 26 Compact Wall Mount ................................... 28 Wall Mount .................................................. 30
CONTROLLERS Comparison Table of Controllers .................. 32 Summary of Software, Controllers, Converters & Adapters, Service & Monitoring Tools ...................................... 33 Central Remote Controller ........................... 36 Touch Panel Controller ................................ 38 System Controller ........................................ 40 Control System Diagram .............................. 42
SOFTWARE Airstage Portal ............................................. 43 Service Tool ................................................ 44 Design Simulator ......................................... 46 Building Information Management ............... 48
customers' needs from all over the world through this advanced R&D center and 6 factories based in China and Thailand.
OPTIONAL PARTS Auto Louver Grille Kit .................................. 49 Connection Units, Duct Models ................... 50 Cassette, Ceiling ......................................... 51 JAPAN R&D center and 198 ft. (60m) height testing tower Central R&D center for global air conditioner development. Advanced products are developed and next generation technologies are researched.
FUJITSU GENERAL CENTRAL AIR-CONDITIONER(WUXI)CO.,LTD (China) VRF Main factory. ISO9001 and ISO14001 certified. This factory has high quality and high reliability system for manufacturing VRF system.
APPLICATIONS Medical and Healthcare Facilities ................ 52 Educational and Religious Facilities ............ 53 Multi-Tenant Dwellings ................................. 54 Office Buildings and Retail Spaces .............. 55
Variable Refrigerant Flow System For Small and Large Buildings ( \ XU& K
; @S? SS >; " UZ _*; & ; XU Z [ K
;
; ( ( + K
9
\& Q&
4
VRF VRF
9 _ ;
World’s longest total pipe length
3,280 ft. max.
Overall piping length 3,280 ft.
between outdoor and indoor units
+
164 ft. max.
492 ft. max.
M@S@
unit
196 ft. max. between indoor and indoor units
49 ft. max.
High static pressure
Wide operating range@
&
;
SX 'Q?
&
%
.32 in.WG as standard
V-II series Installation Example
K M M Z@@Z@ZKU\KU[?X?KX@K X K
K
@XX Z? 115°F (46°C ) @?U U? Q\ S?
70°F (21°C ) \Q X? Z? @? SX
?
23°F (-5°C ) @U @? U X? 5°F (-15°C )
-4°F (-20°C )
/
9K
SX 'Q?
@_* ; ):&
K ; :*K X:
\ Q
Z@ZK
5
Easy Installation Easily transported Easily craned into position using lifting belt hooks
Easy access Can be transported in a small elevator
By adopting an L-Shape front panel that can be removed, the work space for installation and service has been greatly expanded by this design. For multiple installations, work is performed easily and efficiently even in a narrow space.
Design of outdoor unit allows for lifting straps to be used Slots in base of the unit allow for easy transportation by forklift.
High capacity connection
Simple signal line connection Communication wiring can be connected continuously to any component, making installation easier.
Up to maximum
11,811 ft / 3,600 m
length
Various combinations from 6 Tons to 24 Tons with 33 indoor unit models, 9 types, can be selected. A minimum of 50% to a maximum of 130% indoor unit connectable capacity. Connectable indoor unit capacity Ratio up to
130 %
Connectable indoor unit number
up to
45
Wide variety of indoor units
9
Other wiring method
types,
33 models
Simple wiring method Note: When total indoor unit capacity is greater than 100%, individual indoor units will operate at a slightly lower capacity when maximum capacity is required.
Automatic address setting
Automatic address setting is performed at outdoor unit
The address of each indoor unit can be automatically set by the touch of a button on the outdoor unit.
Addresses are automatically distributed from outdoor unit.
Note: In a multiple refrigerant system installation there could be a case where Automatic addressing sequence cannot be initiated.
Press the pushbutton switch of outdoor unit.
6
3
7
1
0
2
4
5
6
Manual address setting from indoor unit and remote controller is also possible.
VRF
High Reliability Life-extending operation Outdoor unit operation rotation The compressor starting order is rotated so that the running time is shared. Rotation
Rotation
DC D C 2
DC 1
Rotation
DC DC 1
DC DC 3
DC 2
DC DC 1
D DC C 3
DC 3
DC DC 2
Note: The inverter compressors start in priority. Rotate operation is alternated by the start / stop timing of the compressors.
Oil return design
Refrigerant circulation control
Individual oil separator and intelligent oil feedback operation logic are adopted. Oil return pipe of oil separator is connected directly to the compressor suction line through capillary and through solenoid valve.
Innovative compressor control logic balances refrigerant mass flow rate of each outdoor unit by controlling inverter speed.
Oil separator
Strainer Load Level
Compressor Capillary tube
Oil
Solenoid valve
ON
ON
OFF
ON
ON
ON
DC 1
DC 2
DC 3
DC 1
DC 2
DC 3
Master
Slave 1
Slave 2
Master
Slave 1
Slave 2
Unbalanced operation condition
Balanced operation condition
Refrigerant
Compressor under operation
Adoption of blue fin heat exchanger
Liquid back flow protection
Blue fin treatment to the outdoor unit’s heat exchanger improves corrosion resistance.
By adopting a large sized accumulator, the refrigerant which is not completely vaporized is left inside the accumulator and only a stable supply of gas is fed from the accumulator.
Blue fin heat exchanger
Cobalt Blue protection Standard chromate protection Aluminium base material Hydrophilic coating
Compressor Accumulator
From Evaporators
Large Sized Accumulator
Compressor
Additional Accumulator
7
Comfort and Convenience Centralized Control It is possible to manage the operation and comfort of an entire building by using a Fujitsu VRF Control System. Controllers can be selected to meet the number of indoor units and control requirements of the occupants.
Touch Panel Controller
Central Remote Controller System Controller
Quiet operation Low noise mode: Two low noise modes can be selected automatically using quiet priority setting or capacity priority setting, depending on the usage environment and outside temperature load. Quiet priority setting Air conditioning load factor
Capacity priority setting
Heat load
Heat load
100%
down
Capacity
100%
0
0
Rated noise level
Rated noise level
Operating sound
0
Alternated automatically
0 time
Reset automatically
Quiet priority low noise mode
time
Capacity priority low noise mode
Remote monitoring The Web Monitoring system allows you to view system operation at all times over the internet ensuring trouble free operation. Low noise design: Compressor noise has been significantly reduced by shielding the compressor compartment.
Compressor compartment
Monitoring Side VRF Network System Side Outdoor unit Transmission line Internet or Public Telephone Line
USB adaptor (Included)
Web Monitoring Tool
Non-stop oil recovery operation A comfortable room condition is maintained during oil recovery mode because the product continues to operate without stopping the cooling or heating operation.
8
Indoor unit
The operating VRF network system in the building can be monitored in real time over the Internet.
VRF
Easy Service & Maintenance Designed for easy service and maintenance Inspection and replacement of main parts is easy due to innovative construction and an LED operational display. Easy-to-read 7-segment LED display which explains operational and trouble status
Consolidated electrical components make maintenance easy
Movable PCB panel that allows for easier maintenance work behind the PCB Split front panel allows for maintenance from top or bottom of the outdoor unit
Maintenance of electrical components, valv val va ve and compressor parts from the ves valves, fro front is possible.
Error status can be checked easily via the indoor unit wired controller
Wired Remote Controller
Simple Remote Controller
Faulty unit number (Remote controller address) Error code
An error code is displayed on a liquid crystal screen.
Remote controller address Error code
SU MO TU WE TH FR SA
Emergency stop function Emergency alarm can be received by indoor or outdoor units, Central Remote Controller or Touch Panel Controller. All units will be stopped when emergency alarm signal is received. Note: In case of received emergency alarm by indoor/outdoor unit: All units connected within same refrigerant system will be stopped. Central Remote Controller/Touch Panel Controller: all units connected within VRF network system with Central Remote Controller/Touch Panel Controller will be stopped.
Emergency stop function Touch Panel Controller
Emergency stop function
Emergency stop function
9
Outdoor units lineup 96,000 BTU (8 Tons) 28.1kW (10HP)
144,000 BTU (12 Tons) 42.2kW (16HP)
168,000 BTU (14 Tons) 49.2kW (18HP)
AOUA72RLBV
AOUA96RLBV
AOUA144RLBVG
AOUA168RLBVG
AOUA192RLBVG
UNIT : AOUA72RLBV
UNIT : AOUA96RLBV
UNIT : AOUA72RLBV UNIT : AOUA72RLBV
UNIT : AOUA72RLBV UNIT : AOUA96RLBV
UNIT : AOUA96RLBV UNIT : AOUA96RLBV
72,000 BTU (6 Tons) 21.1kW (8HP)
192,000 BTU (16 Tons) 56.2kW (20HP)
Indoor units lineup Capacity range (Btuh)
7,000
9,000
12,000
14,000
AUUA7RLAV
AUUA9RLAV
AUUA12RLAV
AUUA14RLAV
ARUL9RLAV
ARUL12RLAV
ARUL14RLAV
ABUA12RLAV
ABUA14RLAV
ASUA12RLAV
ASUA14RLAV
Compact Cassette 1
Cassette 2
Slim Compact Duct ARUL7RLAV
Duct
High Static Pressure Duct
Floor / Ceiling
Ceiling
Compact Wall Mounted ASUA7RLAV
ASUA9RLAV
Wall Mounted
10
1 Compact Cassette Grille UTG-CCGV sold separately. Must order one with each Compact Cassette. 2 Cassette Grille UTG-LCGV sold separately. Must order one with each Cassette.
VRF
216,000 BTU (18 Tons) 63.3kW (24HP)
240,000 BTU (20 Tons) 70.3kW (26HP)
264,000 BTU (22 Tons) 77.3kW (28HP)
AOUA216RLBVG
AOUA240RLBVG
AOUA264RLBVG
AOUA288RLBVG
UNIT : AOUA72RLBV UNIT : AOUA72RLBV UNIT : AOUA72RLBV
UNIT : AOUA72RLBV UNIT : AOUA72RLBV UNIT : AOUA96RLBV
UNIT : AOUA72RLBV UNIT : AOUA96RLBV UNIT : AOUA96RLBV
UNIT : AOUA96RLBV UNIT : AOUA96RLBV UNIT : AOUA96RLBV
18,000
24,000
30,000
36,000
AUUA18RLAV
AUUA24RLAV
AUUB18RLAV
AUUB24RLAV
AUUB30RLAV
AUUB36RLAV
ARUM24RLAV
ARUM30RLAV
ARUM36RLAV
288,000 (24 Tons) 84.3kW (30HP)
48,000
60,000
ARUH48RLAV
ARUH60RLAV
ARUL18RLAV
ARUH36RLAV
ABUA18RLAV
ABUA24RLAV
ABUA30RLAV
ASUB18RLAV
ABUA36RLAV
ASUB24RLAV
11
Various Energy Saving Features Energy saving technology increases efficiency Powerful large propeller fan: High performance, low noise Computational Fluid Dynamics designed fan.
DC Fan motor: Power consumption has been reduced by using a compact and high performance DC fan motor.
4-face heat exchanger: Heat exchange efficiency is significantly improved by the use of a 4-face heat exchanger that increases effective surface area.
Sine-wave DC inverter control: High efficiency operation is achieved by using a sine wave DC inverter control.
Subcooled heat exchanger: High heat exchange efficiency is achieved by using an internal projection shape double pipe construction.
DC twin rotary compressor: High efficiency is achieved by using a large capacity DC twin rotary compressor, improving refrigerant intake and compression efficiency.
In multiple outdoor unit installations, the unique front intake design improves airflow into the Heat Exchanger.
Room temperature set point limitation
Peak cut operation
The minimum and maximum temperature range can be set providing energy savings while considering the comfort of the occupants.
To reduce peak demand charges, this function sets a maximum value (maximum average power) for the entire air conditioning system during specified peak periods. Consumption is monitored using a field-installed power meter. During a Peak Cut condition, the heating or cooling delivered to each indoor unit will be adjusted by: shifting indoor set temperature, applying a forced off function to specified units, or by stopping the entire system.
°F 86.0 82.0 79.0 75.0 72.0 68.0 64.0 61.0 57.0 54.0 50.0
°C 30.0 28.0 26.0 24.0 22.0 20.0 18.0 16.0 14.0 12.0 10.0
Peak cut
Capacity
Control device
Setting level Heating Cooling
Heating set Cooling set temp. range temp. range
Original Set temp. limitation
Set point limitation setting
W
Operation setting (System Controller)
Time
Signal input
Off timer Each remote controller is equipped with an OFF timer function that automatically stops operation when a fixed time has elapsed from the start of operation. This prevents wasting energy. (Note: Except simple remote controller)
Set Temp.
Down
Heating Set Temperature
Down
MAX. -8°F/-4°C
Down
Down
Economy operation Control Temperature Economy operation
Economy operation Economy operation can be set by remote controller. The temperature setting is offset automatically over a certain period of time.
12
Set Temp.
Economy operation Control Temperature MAX. +4°F/+2°C Cooling Set Temperature
Economy operation Up Up
VRF
A Front side knockout position
Outdoor Units
ø 1.7 (43.7)
27.2 (690) (Bolt pitch) 3.1 (80) 20.9 (530) (Bolt pitch)
6, 8 Tons (8, 10HP) AOUA72RLBV AOUA96RLBV
Power supply cable port
2.9 (73) 2.1 (53)
8-12×17 (Hole)
ø 0.9 (22.2) Transmission cable port
Dimensions Unit : in (mm) 36.6 (930)
0.4 (10) 3.0 (75) 3.9 (100)
28.8 (732) (Bolt pitch)
3.7 (95)
ø 0.9 (22.2) Transmission cable port Pipe port
4.9 (125) 7.0 (179)
B Left side knockout position
30.1 (765) ø2.4 (61.3) Power supply cable port
ø1.7 (43.7) Power supply cable port
ø0.9 (22.2)
66.5 (1690)
Transmission cable port
25.7 (652.5)
C Bottom side knockout position
A
3.1 (80)
Pipe port
Back view
C
3.2 (82)
B
Top view
1.7 (42)
7.5 (190)
Specifications Capacity Range
Tons (HP)
6 (8)
8 (10)
12 (16)
14 (18)
16 (20)
18 (24)
20 (26)
22 (28)
24 (30)
AHRI Ref. No. - Non-Ducted AHRI Ref. No. - Ducted
5198211
5198214
5198217
5198220
5198223
5198226
5198229
5198232
5198235
5198212
5198215
5198218
5198221
5198224
5198227
5198230
5198233
5198236
AHRI Ref. No. - Mixed
5198213
5198216
5198219
5198222
5198225
5198228
5198231
5198234
5198237
Model Number
AOUA72RLBV
AOUA96RLBV
AOUA144RLBV AOUA168RLBV AOUA192RLBV
AOUA216RLBV
AOUA240RLBV
AOUA264RLBV
AOUA288RLBV
Outdoor Units
AOUA72RLBV
AOUA96RLBV
AOUA72RLBV AOUA72RLBV AOUA96RLBV AOUA72RLBV AOUA96RLBV AOUA96RLBV
AOUA72RLBV AOUA72RLBV AOUA72RLBV
AOUA72RLBV AOUA72RLBV AOUA96RLBV
AOUA72RLBV AOUA96RLBV AOUA96RLBV
AOUA96RLBV AOUA96RLBV AOUA96RLBV
92
12.5 / 12.3 / 12.4 21.7 / 18.2 / 19.9
High Heating 47°F
Capacity (kBtuh) EER IEER Capacity (kBtuh)
77
103
(Non-Ducted/Ducted/Mixed)
COP
3.76 / 3.64 / 3.70
3.55 / 3.47 / 3.51
Low Heating 17°F
Capacity (kBtuh)
(Non-Ducted/Ducted/Mixed)
COP
Cooling (Non-Ducted/Ducted/Mixed)
69
138
160
56
73
2.30 / 2.30 / 2.30
2.50 / 2.40 / 2.45
154
180 118
24
Power Source
274 9.6 / 10.0 / 9.8 18.0 / 15.3 / 16.6
230
258
282
308
3.53 / 3.58 / 3.56
3.21 / 3.21 / 3.21
3.21 / 3.21 / 3.21
160
166
191
200
2.38 / 2.27 / 2.33
2.24 / 2.20 / 2.22
2.31 / 2.20 / 2.26
2.37 / 2.20 / 2.29
29
31
35
42
45
21 x 3
32
3-phase 3 wires, 208-230V, 60Hz
MCA (A) Recommended Breaker Size (A) RLA kBtuh
Cooling
kW Capacity
kBtuh
Heating
kW Height
in./ mm.
Width Depth
Pre-charge Refrigerant
Operation Range
252 10.3 / 10.9 / 10.6 19.0 / 16.4 / 17.7
50% to 130% 16
12
Connectable Indoor Units
Connection Pipe Diameter
228 11.3 / 11.9 / 11.6 19.6 / 17.2 / 18.4
3.72 / 3.60 / 3.66
128
2.36 / 2.19 / 2.28 2.47 / 2.22 / 2.35 2.53 / 2.30 / 2.42
Indoor Unit Connectable Capacity
Dimensions
12.0 / 12.0 / 12.0 20.2 / 17.2 / 18.7
196
3.68 / 3.46 / 3.57 3.60 / 3.54 / 3.57 3.55 / 3.44 / 3.50
107
206
175
11.7 / 11.6 / 11.6 12.4 / 11.0 / 11.7 11.6 / 11.2 / 11.4 11.4 / 11.1 / 11.2 20.8 / 17.8 / 19.3 19.5 / 14.6 / 17.0 19.5 / 17.1 / 18.3 19.6 / 17.3 / 18.4
41 x 2
45
45 x 2
Gas Cooling Heating
°F / °C
45 x 3
21
14 x 2
14 + 21
21 + 21
14 x 3
14 +14 + 21
14 +21 + 21
72
96
144
168
192
216
240
264
288
21.1
28.1
42.2
49.2
56.2
63.3
70.3
77.3
84.3
80
108
162
188
216
243
270
296
324
23.4
31.6
47.4
55.1
63.3
71.2
79.1
86.7
94.9
66.5 / 1,690
66.5 / 1,690
66.5 / 1,690
36.6 / 930
36.6 x 2 / 930 x 2
36.6 x 3 / 930 x 3
30.1 / 765
in./ mm.
41 x 3
14
24.69 / 11.20
lb / kg Liquid
41
30.1 / 765
1/2 / 12.70 7/8 / 22.22 5 ~ 115 / -15 ~ 46
30.1 / 765
24.69 + 24.69 / 11.20 +11.20
24.69 + 24.69 + 24.69 / 11.20 + 11.20 + 11.20
3/4 / 19.05
5/8 / 15.88 1-1/8 / 28.58
1-3/8 / 34.92 23 ~ 115 / -5 ~ 46 -4 ~ 70 / -20 ~ 21
Note: Specifications are based on the following conditions: Cooling: Indoor temperature of 80.6°F / 27°C and outdoor temperature of 95°F / 35°C. Heating: Indoor temperature of 68°F / 20°C and outdoor temperature of 45°F / 7°C. Pipe length: 24.6 ft. / 7.5 m., Height difference between outdoor unit and indoor unit: 0 ft. / 0 m. Our outdoor units shall withstand 1,000 hours of salt spray tested per procedure ASTM B117.
13
Compact Cassette Models
AUUA7RLAV AUUA9RLAV AUUA12RLAV AUUA14RLAV AUUA18RLAV AUUA24RLAV Compact size panel design that fits a standard ceiling panel 23-5/8 x 23-5/8in (600x600mm)
2-stage turbo fan
Quiet quality
High efficiency design by 2 stage structure
Optimization of wing form (laminar wing type) and wing number (7 blades each)
Evenly spread air distribution across the heat exchanger is possible due to the new 2 stage turbo fan which produces two separate airflow streams.
Designed using Computational Fluid Dynamics (CFD) simulations.
Adoption of laminar wing Quiet
+
2-stage
Airflow runs smoothly along the laminar wing
2-stage turbo fan
1-stage
Laminar wing
Heat exchange efficiency
=
Wind velocity Fast
20%UP Quiet
Slow
Spin direction
No airflow separation
Airflow direction
Specifications Model name
AUUA18RLAV
AUUA24RLAV
14,000
18,000
24,000
4.1
5.3
7.0
13,500
15,600
20,000
27,000
3.2
4.0
4.6
5.9
7.9
25
29
35
36
84
324 (550)
353 (600)
400 (680)
418 (710)
606 (1,030)
AUUA7RLAV
AUUA9RLAV
Btu/h
7,500
9,500
12,000
kW
2.2
2.8
3.5
Btu/h
9,500
10,900
kW
2.8
W
25
CFM (m³ / h)
318 (540)
Power source Cooling Heating Input power Airflow rate
High Med
Sound pressure level
265 (450)
265 (450)
312 (530)
347 (590)
341 (580)
489 (830)
Low
206 (350)
206 (350)
230 (390)
230 (390)
235 (400)
265 (450)
High
34
35
37
38
41
50
30
30
34
34
35
44
25
25
27
27
27
30
Med
dB(A)
Low in.(mm)
Dimensions (H x W x D)
lbs.(kg)
Weight Connection pipe diameter
Liquid (Flare) Gas (Flare)
in.(mm)
9-21/32 × 22-7/16 × 22-7/16 (245 × 570 × 570) 33 (15)
38 (17)
ø 1/4 (6.35)
ø 3/8 (9.52)
ø 1/2 (2.70)
ø 5/8 (15.88)
Drain
ø 3/4 (25) (I.D) ; ø 1-1/16 (32) (O.D.)
Dimensions (H x W x D) in.(mm)
1-31/32 × 27-9/16 × 27-9/16 (50 × 700 × 700)
UTG-CCGV
Model name Weight
14
AUUA14RLAV
Single phase, 208-230V , 60Hz
Capacity
Grille(option)
AUUA12RLAV
lbs.(kg)
6 (2.6)
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 80°F(26.7°C)DB/67°F(19.4°C)WB,and outdoor temperature of 95.0°F(35°C)DB/75°F(23.9°C)WB. Heating : Indoor temperature of 70°F(21.1°C)DB/60°F(15.6°C)WB,and outdoor temperature of 47°F(8.3°C)DB/43°F(6.1°C)WB. Pipe length : 25ft.(7.5 m), Height difference : 0ft.(0 m) (Outdoor unit - Indoor unit). Built-in protective functions may limit capacity or shut off unit if unit is operated outside of unit design operating temperature ranges.
VRF
Improvement of airflow distribution
Condensate Drain Pump (Standard) Max Lift
Ceiling panel
27-9/16in (700mm)
1
A B C D
3
High ceiling mode
2
1
Grille cover
The compact cassette can be installed up to a height of 9’ 10-1/8” (3.0m) (AUUA12/14/18/24).
Easy maintenance of fan and motor The maximum height from floor to ceiling ft.(m)
Access and maintenance of the fan and motor can be accomplished by removing the panel. The fan and motor can be easily removed. A : Fan motor C : Bell-mouth
Model code
7 9 12 14 18 24
B : 2-stage turbo fan D : Panel
2
Long life filter : standard equipment
3
Adaptation of transparent drainage parts
Standard mode
High ceiling mode
8’ 10-5/16” (2.7) 8’ 10-5/16” (2.7) 8’ 10-5/16” (2.7) 8’ 10-5/16” (2.7) 8’ 10-5/16” (2.7) 8’ 10-5/16” (2.7)
-
9’ 10-1/8” (3.0) 9’ 10-1/8” (3.0) 9’ 10-1/8” (3.0) 9’ 10-1/8” (3.0)
During installation, maintenance and operation, the drain pump and kit can be checked easily.
Optional parts
22-7/16in 570mm
Compact design
22-7/16in 570mm
Air Outlet Shutter Plate : UTR-YDZB Insulation Kit for High Humidity : UTZ-KXGC Fresh Air Intake Kit : UTZ-VXAA
Worlds first 24,000Btu model in the compact cassette category (Easy installation by taking off ceiling panel of 23-5/8 x 23-5/8in (600 x 600mm)
Dimensions
IR Receiver is standard for communicating with Optional Wireless Controller.
Unit: In (mm)
Models: AUUA7 / AUUA9 / AUUA12 / AUUA14 / AUUA18 / AUUA24
20-7/8(530)
View A 11-7/32(285)
21-1/4(540) Hanging bolt position
14-9/16(370)
22-7/16(570): Indoor unit
27-9/16(700) IR reciever
22-27/32 to 26(580 to 660) Ceiling openings
20-7/8(530) Hanging bolt position
27-9/16(700)
A View B
Drain hose 5-13/16(146)
11-7/32(285)
7-7/32(183)
1-3/16(30)
10-5/16(262)
Gas pipe Liquid pipe
4-27/32(123)
Control Box
1-3/16(30)
3/4(19)
Ceiling
4-1/2(114)
4-1/2(114)
8-15/32(215)
B
1-9/16(40)
15
Cassette Models
AUUB18RLAV AUUB24RLAV AUUB30RLAV AUUB36RLAV Powerful, wide airflow and quiet operation
High efficiency turbo fan with 3-dimensional blade
Quiet quality Optimization of wing form (laminar wing type) and wing number (7 blades each)
High efficiency airflow distribution has been achieved by the introduction of a 3 dimensional blade which increases the air passing over the heat exchanger.
Designed using Computational Fluid Dynamics (CFD) simulations
Adoption of laminar wing Quiet
19-11/16in (500mm)
Laminar wing Airflow runs smoothly along the laminar wing
3-dimensional blade
Heat exchanger < Motor side > Wind velocity Fast
Quiet
Quiet
Spin direction
No airflow separation
Slow
No airflow separation
Airflow direction : Airflow direction
: Spin direction
Specifications AUUB18RLAV
Model name
AUUB24RLAV
Power source Capacity
Cooling Heating
Input power Airflow rate
High Med
Sound pressure level
Btu/h
18,000
24,000
30,000
kW
5.3
7.0
8.8
10.6
Btu/h
20,000
27,000
34,000
40,000
kW
5.9
7.9
10.0
11.7
W
39
46
59
80
CFM (m³ / h)
677 (1,150)
753 (1,280)
942 (1,600)
1,059 (1,800)
612 (1,040)
765 (1,300)
765 (1,300)
512 (870)
512 (870)
647 (1,100)
647 (1,100)
High
36
38
40
44
30
33
38
38
29
29
33
33
Dimensions (H x W x D) Weight Connection pipe diameter
dB(A) in.(mm)
9-11/16 × 33-1/16 × 33-1/16 (246 × 840 × 840)
lbs.(kg)
51 (23)
Gas (Flare)
11-11/32 × 33-1/16 × 33-1/16 (288 × 840 × 840) 60 (27)
Liquid (Flare)
ø 3/8 (9.52) in.(mm)
ø 5/8 (15.88)
ø 3/4 (19.05)
Drain
ø 3/4 [I.D.] ; ø 1-1/16 [O.D.]
Dimensions (H x W x D) in.(mm)
1-31/32 × 37-13/32 × 37-13/32 (50 × 950 × 950)
Model name Weight
36,000
553 (940)
Low
16
AUUB36RLAV
Low Med
Grille(option)
AUUB30RLAV
Single phase, 208-230V , 60Hz
UTG-LCGV lbs.(kg)
13 (5.5)
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 80°F(26.7°C)DB/67°F(19.4°C)WB,and outdoor temperature of 95.0°F(35°C)DB/75°F(23.9°C)WB. Heating : Indoor temperature of 70°F(21.1°C)DB/60°F(15.6°C)WB,and outdoor temperature of 47°F(8.3°C)DB/43°F(6.1°C)WB. Pipe length : 25ft.(7.5 m), Height difference : 0ft.(0 m) (Outdoor unit - Indoor unit). Built-in protective functions may limit capacity or shut off unit if unit is operated outside of unit design operating temperature ranges.
VRF
Improvement of the airflow distribution
Condensate Drain Pump (Standard)
The louver design distributes air leaving a space between the chassis and the ceiling allowing far and wide air flow distribution. Front part
Max Lift
Ceiling panel
Ceiling
33-1/2in (850mm)
Bottom view
Rear part
Wide airflow discharge reduces temperature irregularity
Round louver
High ceiling mode This cassette can be installed up to a height of 13’9”. (4.2m) (AUUA36).
Hanger position can be adjusted after installation
The maximum height from floor to ceiling ft. (m) Model code
18 24 30 36
Detachable Grille corner
Standard mode
High ceiling mode
9’ 10-1/8” (3.0) 9’ 10-1/8” (3.0) 10’ 6” (3.2) 10’ 6” (3.2)
11’ 6” (3.5) 11’ 6” (3.5) 11’ 9-3/4” (3.6) 13’ 9-3/8” (4.2)
Adjustment can be done by taking off the corner part
Optional parts IR Receiver Kit : Air Outlet Shutter Plate : Panel Spacer :
UTZ-KXGA / UTZ-KXGB UTG-AGYA-W UTZ-VXGA
Insulation Kit for High Humidity : Wide Panel : Fresh Air Intake Kit :
Unit: In (mm) 37-13/32(950)
9-27/32(250)
A
14-3/32(358) 14-3/32(358)
7-9/32(185)
1-7/32(31) 1-7/32(31)
Fresh air inlet (cut out) 2-3/4(70) Drain hose
View A
33-27/32 to 35-13/16(860 to 910) Ceiling opening
23-29/32(607)
37-13/32(950)
SS@@\QU?M%
31-11-32(796) Hanging bolt position
27-17/32(699) Hanging bolt position
IR reciver (Option)
16-17/32(420)
Dimensions
UTY-LRHYB1 UTR-YDZC UTG-BGYA-W
View B 10-15/16(278)
2-3/8(60) 1-9/16(40)
C Gas pipe
Wire hole
5-1/2(140)
Liquid pipe
1-23/32(44)
13/32(10)
Ceiling
5-19/32(142)
5-19/32(142)
7-7/8(200)
B
Model AUUB18/24 AUUB30/36
C 10-3/32(256) 11-23/32(298)
17
Slim Compact Duct Models (Drain pump internal model)
ARUL7RLAV ARUL9RLAV ARUL12RLAV ARUL14RLAV ARUL18RLAV
ARUL7RLAV ARUL9RLAV
ARUL12RLAV ARUL14RLAV
ARUL18RLAV
Slim design and wide range of static pressure for flexible installation.
Slim design
Flexible installation
This model has a slim design so it can be installed in narrow ceilings.
Slim Compact Duct units can be mounted horizontally or vertically and can deliver up to 0.36” external static pressure providing the power and flexibility to meet the needs of most applications.
Drain port
Ceiling concealed Height
7-25/32in (198mm) Drain pump built-in Floor concealed
Drain pump
Specifications ARUL9RLAV
ARUL7RLAV
Model name
ARUL12RLAV
Power source Capacity
Cooling
Heating Input power Airflow rate
High Med
Static pressure range
9,500
12,000
14,000
2.2
2.8
3.5
4.1
5.3
Btu/h
9,500
10,900
13,500
15,600
20,000
kW
2.8
3.2
4.0
4.6
5.9
W
44
50
54
92
83
324 (550)
353 (600)
353 (600)
471 (800)
553 (940)
288 (490)
324 (550)
300 (510)
418 (710)
494 (840)
258 (440)
283 (480)
265 (450)
359 (610)
441 (750)
0 to 0.36 (0 to 90)
0 to 0.36 (0 to 90)
0 to 0.36 (0 to 90)
0 to 0.36 (0 to 90)
0 to 0.36 (0 to 90)
0.10 (25)
0.10 (25)
0.10 (25)
0.10 (25)
0.10 (25)
28
29
30
34
34
25
26
27
32
32
22
24
24
28
CFM m3/ h
High Med
dB(A)
Low Dimensions (H x W x D)
in.(mm)
Weight
lbs.(kg) Liquid (Flare) Gas (Flare) Drain
18
18,000
7,500
kW
in.WG (Pa)
Standard static pressure
Connection pipe diameter
ARUL18RLAV
Btu/h
Low
Sound pressure level
ARUL14RLAV
Single phase, 208-230V , 60Hz
in.(mm)
7-25/32 × 27-9/16 × 24-13/32 (198 × 700 × 620) 40 (18)
42 (19)
28 7-25/32 × 35-7/16 × 24-13/32 (198 × 900 × 620)
51 (23)
ø 1/4 (6.35)
ø 3/8 (9.52)
ø 1/2 (12.70)
ø 5/8 (15.88)
ø 3/4 [I.D.] ; ø 1-1/16 [O.D.]
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 80°F(26.7°C)DB/67°F(19.4°C)WB,and outdoor temperature of 95.0°F(35°C)DB/75°F(23.9°C)WB. Heating : Indoor temperature of 70°F(21.1°C)DB/60°F(15.6°C)WB,and outdoor temperature of 47°F(8.3°C)DB/43°F(6.1°C)WB. Pipe length : 25ft.(7.5 m), Height difference : 0ft.(0 m) (Outdoor unit - Indoor unit). Built-in protective functions may limit capacity or shut off unit if unit is operated outside of unit design operating temperature ranges.
VRF
Auto Louver Grille Kit (Option)
Condensate Drain Pump (Standard)
Simple flat Auto Louver will provide comfortable airflow and blend with any interior.
Max Lift
33-1/2in (850mm)
Slim Duct
Auto Louver Grille
Opened louver
Drain hose is a standard accessory Closed louver
Selectable External Static Pressure The external static pressure can be selected for any value from 0 to 0.36 in.WG. (0 to 90 Pa). Static pressure setting can be changed using the remote controller.
Wired Remote Controller
Wireles Remote Controller
Operation with indoor unit UP and Down auto swing Auto-closing louver Static pressure range
See Page 49 for more details.
Filter (Accessory)
0.36 in.WG (0 to 90 Pa)
ARUL7 / 9 / 12 / 14 / 18
Filter (2pcs.)
Air-intake Air intake direction can be selected to match the installation site.
Optional parts Bottom side
Remote Sensor Unit : UTD-RS100 IR Receiver Unit : UTB-YWC Auto Louver Grille Kit : UTD-GXSA-W (for ARUL7/9/12/14RLAV) UTD-GXSB-W (for ARUL18RLAV)
Back side
In locations where fan noise may be a concern, do not use bottom inlet without providing an elbow to prevent line of sight to the fan.
Dimensions
Unit: In (mm)
1-3/16 (30)
M
V
2 (51)
22-19/32 (574)
2-25/32 (71)
6 (152)
6-27/32 (174)
14-27/32 (377)
Models: ARUL7 / ARUL9 / ARUL12 / ARUL14 / ARUL18
Rear view
U 25-19/32 T(650) 28-29/32 S(734)
N O P Q R S T U V
Liquid
Refrigerant pipe flare connection
Gas
Drain hose connection -
Drain Hose
ARUL7, ARUL9, ARUL12, ARUL14 ø 1/4 (6.35)
ø 3/8 (9.52)
ø 1/2 (12.70)
ø 5/8 (15.88)
ARUL18
I.D. 31/32 (25), O.D. 1-1/4 (32) 27-9/16 (700)
35-7/16 (900)
-
26-5/32 (664)
34-1/32 (864)
-
25-19/32 (650)
33-15/32 (850)
-
28-29/32 (734)
36-25/32 (934)
25-19/32 (650)
33-15/32 (850)
3-15/16 (100) x 6 = 23-5/8 (600) 22-19/32 (574)
3-15/16 (100) x 8 = 31-1/2 (800) 30-15/32 (774)
3-15/16 (100) x 6 = 23-5/8 (600) (Drain hose)
1-7/8 (48)
1-7/32 (31)
R 26-5/32 Q (664) 27-9/16 P (700)
25-19/32 (650)
Front view
1-27/32 (47)
3-1/2 (89)
2-5/32 (55) 3-1/16 (78)
6-13/32 (163)
1-11/16 (43)
4-11/16 (119)
2-5/32 (55)
3-7/32 (82)
3-1/16 (78)
5-15/16 (151)
6-5/8 (168)
7-25/32 (198)
Top view
13/32 (10)
Drain port
2-23/32 (69) 5-21/32 (144) 10-13/32 (264) 14-7/16 (367) 24-13/32 (620)
Side view
19
Duct Models
ARUM24RLAV ARUM30RLAV ARUM36RLAV Slim Compact design allows for easy installation in narrow ceiling spaces up to 10-5/8in (270mm).
Slim & Compact design
Easy maintenance
In the case of bottom return air connection, not only does the indoor unit design allow for installation in a narrow ceiling space of up to 10-5/8in (270mm), further space savings have been achieved by mounting the electrical control box internally inside the chassis.
Structural improvement is attained by making the bottom panel two pieces, front and rear. The internal fan casing is also manufactured in two pieces, namely upper and lower. The maintenance of the motor and fan can be easily carried out by removing the rear panel and the lower part of the casing while leaving the main chassis 1 installed.
44-11/16in (1,135mm)
Control box is now included as part of the main chassis
4
10-5/8in (270mm)
3
2
1.Control box 2.Fan casing 3.Fan 4.Motor
Bottom panel: 2 pieces
One touch operating and easy to install long life filter (Optional Parts)
Specifications Model name
ARUM24RLAV
Power source Capacity
Cooling
Heating Input power Airflow rate
High Med
Static pressure range
24,000
30,000
kW
7.0
8.8
10.6
Btu/h
27,000
34,000
40,000
kW
7.9
10.0
11.7
W
200
200
320
CFM (m³ / h)
706 (1,200)
706 (1,200)
1,012 (1,720)
in.WG (Pa)
Standard static pressure High Med
dB(A)
Low Dimensions (H x W x D)
in.(mm)
Weight
lbs.(kg)
Connection pipe diameter
Gas (Flare)
36,000
647 (1,100)
647 (1,100)
983 (1,670)
589 (1,000)
589 (1,000)
942 (1,600)
0.12 to 0.60 (30 to 150)
0.12 to 0.60 (30 to 150)
0.12 to 0.60 (30 to 150)
0.40 (100)
0.40 (100)
0.40 (100)
40
40
43
38
38
41
36
36
39
10-5/16 × 44-11/16 × 27-9/16 (270 × 1,135 × 700) 93 (42)
95 (43)
Liquid (Flare)
Drain
20
ARUM36RLAV
Btu/h
Low
Sound pressure level
ARUM30RLAV Single phase, 208-230V , 60Hz
ø 3/8 (9.52) in.(mm)
ø 3/4 (19.05)
ø 5/8 (15.88) ø 3/4 [I.D.] ; ø 1-1/16 [O.D.]
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 80°F(26.7°C)DB/67°F(19.4°C)WB,and outdoor temperature of 95.0°F(35°C)DB/75°F(23.9°C)WB. Heating : Indoor temperature of 70°F(21.1°C)DB/60°F(15.6°C)WB,and outdoor temperature of 47°F(8.3°C)DB/43°F(6.1°C)WB. Pipe length : 25ft.(7.5 m), Height difference : 0ft.(0 m) (Outdoor unit - Indoor unit). Built-in protective functions may limit capacity or shut off unit if unit is operated outside of unit design operating temperature ranges.
VRF
Two-direction drain piping
Installation styles Embedded in Ceiling
Hanging from Ceiling
Duct indoor unit Two-direction drain piping
Air-intake Air intake direction can be selected to match the installation site.
Optional parts Bottom side
Remote Sensor Unit : UTD-RS100 Long Life Filter* : UTD-LF25NA Flange (Square) : UTD-SF045T
Back side
In locations where fan noise may be a concern, do not use bottom inlet without providing an elbow to prevent line of sight to the fan.
Dimensions
Flange (Round) : UTD-RF204 IR Receiver Unit : UTB-YWC Drain Pump Unit : UTZ-PX1NBA
*Note, Duct models do not include a standard filter.
Unit: In (mm)
5-7/16 (138) 10-13/32 (264) 10-13/32 (264)
10-13/32 (264)
3-5/32 (80) 3-5/32 (80)
Models: ARUM24 / ARUM30 / ARUM36
1-17/32 (39)
4-Ø1/8 (3.2) (hole)
3-5/32 (80) 4-3/4 (121)
M N O P Q
Refrigerant pipe flare connection Drain hose connection -
ARUM36
Liquid
ø 3/8 (9.52)
ø 3/8 (9.52)
Gas
ø 5/8 (15.88)
ø 3/4 (19.05)
Drain Hose
4-23/32 P4-29/32 (125) x 3 = 14-3/4 (375) (120) 39-31/32 (1015)
3-5/32 (80)
Side view (L)
2-7/8 (73)
2-7/32 (107)
11-5/32 (283)
9-7/16 (240)
6-5/8 (168) 8-Ø3/16 (5) (hole) P4-29/32 (125) x 3 = 14-3/4 (375)
27/32 (21.8)
27/32 (21.8)
6-11/32 (173)
6-11/32 (161)
3-5/32 (80) 3-5/32 (80)
Bolt pitch 18-25/32 (477)
Ø7-7/8 (200) (knock out hole)
11-1/16 (281)
1-1/4 (32)
P.C.D. Ø8-27/32 (225)
ARUM24, ARUM30
2-19/32 (66)
Outlet
1-1/4 (32)
Drain port
4-1/2 (114)
Bolt pitch 46-11/32 (1177)
10-5/8 (270)
2-1/8 (54)
Rear view
2-15/16 (75)
P.C.D. Ø8-27/32 (225)
Front view
9-7/16 (240)
Drain port
Ø8-1/16 (205) (hole)
4-Ø1/8 (3.2) (hole)
1-9/16 (40)
(Drain hose)
3-5/32 (80)
5-7/16 (138) 3-5/32 (80)
3-7/32 (82)
2-Ø3/16 (5) (hole) 6-11/16 (170) 9-7/16 (240)
1-11/32 (34) 5/8 (16)
10-5/8 (270)
44-11/16 (1135)
Top view
Side view (R)
I.D. 31/32 (25) , O.D. 1-1/4 (32) 7-7/8 (200) 29/32 (23)
21
High Static Pressure Duct Models
ARUH36RLAV ARUH48RLAV ARUH60RLAV High Static Pressure Ducted Units combine efficient casing design with non metallic fan wheels and casings to reduce noise levels; units are capable of delivering hot or cold air at static pressures up to 1 in.WG. These units are perfect for conditioning hard-to-reach areas and are able to meet the needs of many different types of applications.
Easy installation (Compact size & Lightweight)
32-11/16in (500mm)
41-11/32in (1,050mm)
A compact and lightweight chassis has been developed to simplify installation and provide better flexibility for tight installation spaces.
15-3/4in (400mm)
99lb (45kg)
Specifications ARUH36RLAV
Model name Power source Capacity
Cooling
Heating Input power Airflow rate
36,000
48,000
kW
10.6
14.1
17.6
Btu/h
40,000
54,000
67,000
kW
11.7
15.8
19.6
W
530
750
810
1,324 (2,250)
1,766 (3,000)
1,972 (3,350)
1,030 (1,750)
1,589 (2,700)
1,678 (2,850)
824 (1,400)
1,354 (2,300)
CFM m 3/ h
Low Static pressure range
in.WG (PA)
Standard static pressure High Med
dB(A)
Low lbs.(kg)
Weight Liquid (Flare) Gas (Flare) Drain
22
0.40 to 0.80 (100 to 200)
60,000
1,501 (2,550) 0.40 to 1.00 (100 to 250)
0.40 (100) 43
47
48
37
43
44
32
40
41
in.(mm)
Dimensions (H x W x D)
Connection pipe diameter
ARUH60RLAV
Btu/h
High Med
Sound pressure level
ARUH48RLAV Single phase, 208-230V , 60Hz
15-3/4 × 41-11/32 × 19-11/16 (400 × 1,050 × 500) 95 (43)
99 (45) ø 3/8 (9.52)
in.(mm)
ø 3/4 (19.05) ø 3/4 [I.D.] ; ø 1-1/16 [O.D.]
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 80°F(26.7°C)DB/67°F(19.4°C)WB,and outdoor temperature of 95.0°F(35°C)DB/75°F(23.9°C)WB. Heating : Indoor temperature of 70°F(21.1°C)DB/60°F(15.6°C)WB,and outdoor temperature of 47°F(8.3°C)DB/43°F(6.1°C)WB. Pipe length : 25ft.(7.5 m), Height difference : 0ft.(0 m) (Outdoor unit - Indoor unit). Built-in protective functions may limit capacity or shut off unit if unit is operated outside of unit design operating temperature ranges.
VRF
High static pressure design
Low noise Indoor unit
Up To
Efficient chassis design has enabled less turbulent air flow. Non-metallic fan wheel and casing reduces fan noise.
1 in.WG (250Pa)
Non-metallic fan Heat 8-27/32in exchanger ø225mm
(ARUH48/60 )
Casing (Non-metallic)
Med. noise level
43dB(A) (ARUH48)
Optional parts Long-Life Filter* : UTD-LF60KA IR Receiver Unit : UTB-YWC Remote Sensor Unit: UTD-RS100 *Note, High Static Pressure Duct models do not include a standard filter.
Dimensions
Unit: In (mm)
3-15/32 (88)
Models: ARUH34 / ARUH48 / ARUH54
9/16 (14)
23-1/32 (585) 19-11/16 (500)
Drain port
(Drain hose)
5-15/32 (139)
Front view
14-19/32 (371) 14-1/32 (356) 8-3/16 (208) 4-1/4 (108)
42-17/32 (1080) 39-3/8 (1000) 33-15/16 (862)
1-5/8 (41)
15-3/4 (400) 12-3/4 (324) 6-3/32 (155)
4-27/32 (123)
2-25/32 (71)
Rear view
12-Ø1/8 (3)
P4-23/32 (120) x 2 = 9-7/16 (240) 11-5/8 (295)
1-3/32 (28) 1-1/32 (26)
4-31/32 (126)
P4-23/32 (120) x 5 = 23-5/8 (600) 33-1/2 (851)
ARUH36, ARUH48, ARUH60
M N O
Refrigerant pipe flare connection
Liquid
Drain hose connection
Drain Hose
Gas
ø 3/8 (9.52)
Side view (L)
41-11/32 (1050)
Side view (R)
4-29/32 (125) 3-11/32 (85)
Top view
ø 3/4 (19.05) I.D. 31/32 (25) , O.D. 1-1/4 (32)
23
Floor / Ceiling Models
ABUA12RLAV ABUA14RLAV ABUA18RLAV ABUA24RLAV The slim and lightweight design allows the unit to be suspended from the ceiling or installed on the floor. This type suits many room designs.
Flexible installation Example of floor installation
Example of ceiling installation
Floor console
Under ceiling
Specifications ABUA12RLAV
Model name
ABUA14RLAV
Power source Capacity
Cooling
Heating Input power Airflow rate
12,000
14,000
18,000
kW
3.5
4.1
5.3
7.0
Btu/h
13,500
15,600
20,000
27,000
kW
4.0
4.6
5.9
7.9
W
30
42
74
99
388 (660)
459 (780)
589 (1,000)
589 (1,000)
CFM (m³ / h)
336 (570)
377 (640)
424 (720)
483 (820)
288 (490)
324 (550)
341 (580)
400 (680)
High
36
40
46
47
32
36
39
42
28
34
35
37
dB(A)
Low Dimensions (H x W x D)
7-27/32 × 38-31/32 × 25-25/32 (199 × 990 × 655)
in.(mm) lbs.(kg)
Weight Liquid (Flare) Gas (Flare) Drain
24
24,000
Low
Med
Connection pipe diameter
ABUA24RLAV
Btu/h
High Med
Sound pressure level
ABUA18RLAV
Single phase, 208-230V , 60Hz
in.(mm)
60 (27)
56 (25) ø 1/4 (6.35)
ø 3/8 (9.52)
ø 1/2 (12.70)
ø 5/8 (15.88) ø 3/4 [I.D.] ; ø 1-1/16 [O.D.]
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 80°F(26.7°C)DB/67°F(19.4°C)WB,and outdoor temperature of 95.0°F(35°C)DB/75°F(23.9°C)WB. Heating : Indoor temperature of 70°F(21.1°C)DB/60°F(15.6°C)WB,and outdoor temperature of 47°F(8.3°C)DB/43°F(6.1°C)WB. Pipe length : 25ft.(7.5 m), Height difference : 0ft.(0 m) (Outdoor unit - Indoor unit). Built-in protective functions may limit capacity or shut off unit if unit is operated outside of unit design operating temperature ranges.
VRF
Double auto swing
Super vane
A combination of up/down and right/left directional swing allows three-dimensional air direction control.
Double Louver Super vane with newly developed special configuration boosts airflow, quickly sending cool air to every corner of the room.
RIGHT and LEFT SWING
UP and DOWN SWING
Auto-closing louver 3
2
1
4
1
5
When operation is stopped, the louvers will automatically close. (This function is available on all non-ducted models.)
2 3 4
Compact design
5 steps selectable
Symmetrical, slim and compact design. 4 steps selectable
Unit : in (mm)
High power DC fan motor
25-25/32 (655)
;
39 (990)
7-27/32 (199)
Note: IR Receiver is standard for communicating with Optional Wireless Controller.
Unit: In (mm) 35-7/16 (900) 19-11/16 (500)
(Drain hose)
7-7/8 (200) 20-7/8 (530)
7
1
3-15/32 (100)
1-3/32 (28)
6-7/8 (175) 3-15/32 5 (100) 1-27/32 (47)
4
7-27/32 (199)
1-1/16 (27)
ø 5/8 (15.88)
I.D. 31/32 (25), O.D. 1-1/4 (32)
Drain Outlet
ø 1-25/32 (45)
-
Use M10 screw bolt
2
2-5/8 (67)
2-15/32 (63)
ø 1/2 (12.70)
Drain Hose
1-13/16 (46)
2-27/32 (72)
3-27/32 (98)
Knock out hole Hole for lifting bolt
Gas
3-5/32 (80)
Drain hose connection
Liquid
ø 3/8 (9.52)
6-3/8 (162)
Refrigerant pipe flare connection
ABUA18, ABUA24
ø 1/4 (6.35)
3-15/32 (100)
2-9/32 (58)
1
5
3-15/32 (100)
M N O P QR S
ABUA12, ABUA14
1-21/32 (42)
1-27/32 (72)
4-7/8 (124)
1-11/16 (43)
2
25/32 (20)
3-15/32 (100)
7-15/32 (190) 5-23/32 (145) 1/2 (13) 3-15/32 (100)
5
25-25/32 (655)
Dimensions
Models: ABUA12 / ABUA14 / ABUA18 / ABUA24
6 4-7/8 (124)
29-7/32 (742)
25
Ceiling Models
ABUA30RLAV ABUA36RLAV Powerful ceiling-hung indoor units are easy to install and can provide plenty of warm or cold air to a large space. Ceiling-hung units are the perfect solution for large spaces such as classrooms, restaurants, and kitchens.
Installation Open
Concealed
Wall mounted (Field Supplied)
General installation pattern which suspends the indoor unit from the ceiling.
Installation pattern where part of the indoor unit is embedded into the ceiling.
Installation which fixes the indoor unit to the wall by the use of wall brackets (Field supplied). This type of installation can be used when the ceiling space is insufficient.
Specifications Power source Capacity
Single phase, 208-230V , 60Hz Cooling
Heating Input power Airflow rate
High Med
Sound pressure level
Btu/h
30,000
kW
8.8
10.6
Btu/h
34,000
40,000
kW
10.0
11.7
W
66
85
859 (1,630)
995 (1,690)
CFM (m3/ h)
806 (1,370)
824 (1,400)
671 (1,140)
689 (1,170)
High
42
45
38
38
dB(A)
Low in.(mm)
Weight
lbs.(kg) Liquid (Flare) Gas (Flare)
34
33
Dimensions (H x W x D)
Drain
26
36,000
Low
Med
Connection pipe diameter
ABUA36RLAV
ABUA30RLAV
Model name
in.(mm)
9-7/16 × 5ft. 5-11/32 × 27 -9/16 (240 × 1,660 × 700) 104 (47)
106 (48)
ø 3/8 (9.52)
ø 3/8 (9.52) ø 3/4 (19.05)
ø 5/8 (15.88) ø 3/4 [I.D.] ; ø 1-1/16 [O.D.]
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 80°F(26.7°C)DB/67°F(19.4°C)WB,and outdoor temperature of 95.0°F(35°C)DB/75°F(23.9°C)WB. Heating : Indoor temperature of 70°F(21.1°C)DB/60°F(15.6°C)WB,and outdoor temperature of 47°F(8.3°C)DB/43°F(6.1°C)WB. Pipe length : 25ft.(7.5 m), Height difference : 0ft.(0 m) (Outdoor unit - Indoor unit). Built-in protective functions may limit capacity or shut off unit if unit is operated outside of unit design operating temperature ranges.
VRF
Double auto swing and wide airflow
Condensate drain pump (Optional)
Auto airflow direction and auto swing
Optional drain lift-up mechanism allows flexible installation.
Right and left
Max Lift
19-11/16in (500mm)
Fresh air intake 5 steps selectable Up and down Fresh air 1 Indoor
2
Outdoor
3 4
High power DC fan motor
4 steps selectable
;
Quiet, powerful airflow Powerful airflow ensures comfort to every corner of a large room.
Long-life filter High Efficiency long-life filter doubles the life of the filter compared to standard filters.
-flow
e air
nc ista
gd
Lon
Optional parts
Slim & compact design
Dimensions
Drain Pump Unit : UTR-DPB24T Flange: UTD-RF204
Height
9-7/16in (240mm)
Note: IR Receiver is standard for communicating with Optional Wireless Controller.
Unit: In (mm)
Models: ABUA30 / ABUA36
65-11/32 (1660) 63 (1600)
3
Drain hose connection Knock out hole
Liquid Gas
ø 3/4 (19.05)
Drain Hose
I.D. 31/32 (25), O.D. 1-1/4 (32)
Drain Outlet Fresh Air
ø 1-31/32 (50)
Refrigerant Pipe
Hole for lifting bolt
ø 3/8 (9.52) ø 5/8 (15.88)
-
ø 7-7/8 (200) Use M10 screw bolt
5-1/8 (130) 6-1/2 (165)
6
3-7/32 5-5/16 (82) (135) 6-5/16 (160) 4-21/32 (118)
5 6-5/16 (160) 3-25/32 (96)
7-9/16 (192)
Refrigerant pipe flare connection
6-5/16 (160)
N O P Q R S
3-15/32 (88)
5-29/32 (150)
M
ABUA36
7-7/8 (200) 6-5/16 (160) 1-5/16 (33) 3-3/4 (95)
5-29/32 (150) ABUA30
1-3/16 (30)
9-7/16 (240)
2-9/16 (65) 5-13/32 (137)
4-17/32 3-15/16 (115) (100)
11-11/16 (300) 27-9/16 (700)
7
(Drain hose)
7-15/16 (202)
2
1
Drain port
4
Drain port
27
Compact Wall Mounted Models
ASUA7RLAV ASUA9RLAV ASUA12RLAV ASUA14RLAV Compact and stylish design
Filter features High performance filters provide high quality air conditioning
Deodorizing effect
(Odor reduction rate) Trimethylamine
Ammonia
Long-life*1 Ion Deodorization Filter
(ppm)
(ppm)
160
160 With no filter
120
The filter deodorizes by poerfully decomposing absorbed odors using the oxidizing and reducing effects of ions generated by the ultra-fine-particle ceramic.
With no filter
120
New filter
80
80
New filter
40
40 0
0 0
30
60
120 (min)
0
30
60
120 (min)
Apple-catechin Filter* 2 Hydrogen sulfate
Fine dust invisible mold spores and harmful microorganisms
; ;
; ; extracted from apples. @&
S; ; *2 Both filters can be mounted on the same unit.
(ppm)
160 With no filter
120 80
New filter
40 0 0
30
60
120 (min)
High performance filters have been thoroughly tested by the Environmental Sanitary Inspection Center using an advanced Deodorization Test.
Specifications ASUA7RLAV
Model name
Capacity
Cooling
Heating % +
High
[Z??
>Z??
@X???
kW
2.2
2.8
SZ
4.1
Btu/h
>Z??
@?>??
@SZ??
@Z\??
kW
2.8
3.2
4.0
4.6
W
16
16
19
30
288 (490)
X>UZ??
SS?Z\?
394 (670)
CFM (m³ / h)
X\ZUZ?
X\ZUZ?
283 (480)
288 (490)
218 (370)
218 (370)
247 (420)
247 (420)
High
SZ
36
39
44
Med
33
33
SZ
37
27
27
31
32
dB(A)
Dimensions (H x W x D)
in.(mm)
Weight
lbs.(kg) Liquid (Flare) Gas (Flare) Drain
28
@U???
Btu/h
/
Connection pipe diameter
ASUA14RLAV
/
Med
Sound pressure level
ASUA12RLAV
ASUA9RLAV
X?QXS?_\?
@?@S@\£S@SSX£Q@ZSXX[Z£[>?£X@Z 20 (9) ¤@U\SZ
in.(mm)
ø 1/2 (12.70) ¤@[SX@SQ¥%9¦¤ZQ@ZQ¤X@SX@\[¥:9¦
) M K M% Q?X\[K9§\[@>UK§
>Z?SZK9§[ZXS>K§ M% [?X@@K9§\?@Z\K§
U[QSK9§US\@K§ MXZ [Z M? ?: % Built-in protective functions may limit capacity or shut off unit if unit is operated outside of unit design operating temperature ranges.
VRF
Low noise
Auto swing louver
Electronic Expansion valves are ;
&+ / ensures that the air direction corresponds to the mode selected.
27dB(A) (ASUA7/9)
Indoor unit
1 2
3
Compact size
Width
Powerful output in a compact design
Step
31-1/8 in. (790mm)
S@X >? Lambda type heat exchanger.
4
Easy maintenance The front panel can be removed for easy access during maintenance.
Symmetrical design ;
Open panel
High power DC fan motor
; K
Dimensions
) M%**
: Wireless Controller.
Unit: In (mm)
Models: ASUA7 / ASUA9 / ASUA12 / ASUA14 Q@ZSXX@Z
@?@S@\X[Z
31-3/32 (790)
21/32 (16.7)
18-1/2 (470) X?[QZS? @Z@\X4)
XZS@SX\\?
18-1/2 (470) X?[QZS?
+"+[+"+> +"+@X+"+@U
M N
Refrigerant pipe flare connection
O
Drain hose connection
Liquid
¤@U\SZ
Gas
ø 1/2 (12.70)
Drain Hose
%9@[SX@SQ :9ZQ X@SX@ZQ@\[ 9 M/¨XSZQ\??
29
Wall Mounted Models
ASUB18RLAV ASUB24RLAV Stylish, slim and elegant, these popular wall mounted units are perfect for smaller rooms where a clean, aesthetic design is preferred. Variable speed DC fan motors deliver heating or cooling quietly and comfortably.
Compact & Slim design Stylish, slim and elegant, these popular wall mounted units are perfect for smaller rooms where a clean, aesthetic design is preferred. Variable speed DC fan motors deliver heating or cooling quietly and comfortably.
39-9/32in. (998mm)
DC fan motor
Specifications ASUB18RLAV
Model name Power source Capacity
Cooling
Heating Input power Airflow rate
High
18,000
kW
5.3
7.0
Btu/h
20,000
24,000
kW
5.9
7.9
W
35
64
494 (840)
647 (1,100)
CFM (m³ / h)
453 (770)
536 (910)
406 (690)
430 (730)
High
41
48
39
43
Med
dB(A)
in.(mm)
Dimensions (H x W x D)
lbs.(kg)
Weight Liquid (Flare) Gas (Flare) Drain
30
35
35
Low
Connection pipe diameter
24,000
Btu/h
Low
Med
Sound pressure level
ASUB24RLAV Single phase, 208-230V , 60Hz
12-19/32 × 39-9/32 × 8-31/32 (320 × 998 × 228) 31 (14) ø 3/8 (9.52)
in.(mm)
ø 5/8 (15.88) ø 15/32 (12) [I.D.] ; ø 5/8 (16) [O.D.]
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 80°F(26.7°C)DB/67°F(19.4°C)WB,and outdoor temperature of 95.0°F(35°C)DB/75°F(23.9°C)WB. Heating : Indoor temperature of 70°F(21.1°C)DB/60°F(15.6°C)WB,and outdoor temperature of 47°F(8.3°C)DB/43°F(6.1°C)WB. Pipe length : 25ft.(7.5 m), Height difference : 0ft.(0 m) (Outdoor unit - Indoor unit). Built-in protective functions may limit capacity or shut off unit if unit is operated outside of unit design operating temperature ranges.
VRF
“Vertical airflow” provides powerful floor level heating
Air conditioner filter features
ft.(m) 7 (2.1) 16
Ion Deodorization Filter
(24/30)
Organic coating fin used heat exchanger
3 (1)
0 10 (3)
46
20 (6)
Outside air conditions: 35.6oF (2o C) 60% Operation contents: Heating Set temperature (Max set temp) 86oF (30oC), Air flow Hi Vertical flap : Downward Horizontal flap : Center
o
40 (12) ft.(m)
30 (9)
92
90
88
86
33
32
31
30
Apple-catechin Filter
84 (oF) 29 (oC)
Pre Filter
Power diffuser (full open)
Antibacterial deodorizing pre-filter with special ceramic powder
Long-life* Ion Deodorization Filter
“Horizontal airflow” does not blow cool air directly atft.(m)the occupants in the room
The filter deodorizes by powerfully decomposing absorbed odors using the oxidizing and reducing effects of ions generated by the ultra-fine-particle ceramic.
7 (2.1)
3 (1)
Apple-catechin Filter* 0 10 (3) Power diffuser
20 (6)
Outside air conditions: 95oF (35oC) 40% Operation contents: Cooling Set temperature (Min set temp) 64oF (18oC), Air flow Hi Vertical flap : Upward Horizontal flap : Center
30 (9)
40 (12) ft.(m)
58
60
62
64 (oF)
15
16
17
18 (oC)
Fine dust, invisible mold spores, and harmful microorganisms are absorbed onto the filter by static electricity, and further growth is inhibited and deactivated by the polyphenol extracted from apples. *The filter can be used for approx. 3 years if it is washed under water to restore its surface action when it is dirty. *Using different filters at both sides.
Easy maintenance Note: IR Receiver is standard for communicating with Optional Wireless Controller.
Simplification of drain pan cleaning improves maintenance-ability.
Dimensions
Unit: In (mm)
Models: ASUB18 / ASUB24
12-19/32 (320)
39-9/32 (998)
ø1-1/4 (32) ø5/8 (16) ø15/32 (12)
1 (25)
20-15/32 (520) 23-7/32 (590) 28-3/8 (721)
8-31/32 (228)
ASUB18, ASUB24
20-15/32 (520)
M N
Refrigerant pipe Liquid flare connection Gas
O
Drain hose connection
Drain Hose
ø 3/8 (9.52) ø 5/8 (15.88) I.D. 15/32 (12), O.D. 5/8 (16) Drain house: L=26-3/8 (670)
31
Comparison Table of Controllers Controller Individual control Wired Remote Controller
Type
Simple Simple *1 Remote Remote Controller Controller
Centralized control Wireless Remote Controller
Central Remote Controller
Touch Panel Controller
System Controller (Software)
UTY-RNKU UTY-RSKU UTY-RHKU UTY-LNHU UTY-DCGY UTY-DTGY
UTY-APGX
SU MO TU WE TH FR SA
7 3 6 9 12 15 18 21
Model name
Max. controllable remote controller groups Max. controllable indoor units Max. controllable groups
1
1
1
1
100
400
1600
16
16
16
16
100
400
1600
-
-
-
-
16
400
1600
On / Off
Air conditioning control function
Operating mode setting
-
Fan speed setting Room temp. setting
-
Room temp. set point limitation
-
-
Test operation
-
Up/down air direction flap setting
-
-
Right/left air direction flap setting
-
-
Group setting
-
-
-
-
RC prohibition
-
-
-
-
Anti freeze setting
-
-
-
-
-
-
Failure
-
Display
Defrosting
-
Current time
-
-
Day of week
-
-
-
-
-
R.C. prohibition Cooling/heating priority
-
Address display
-
Schedule timer
Period On/off per day On/off per week
Timer
-
-
Economy mode setting
-
Week
-
-
-
Week
Year
4
-
-
-
20
20
72
28
-
-
-
140
140
504
On/off timer
Year
-
-
-
-
-
Sleep timer
-
-
-
-
-
-
Program timer
-
-
-
-
-
-
10
10
10
-
-
Day off
Control
-
-
-
-
Min. unit of timer setting(Minutes)
30
-
-
5
Status monitoring system
-
-
-
-
Electricity charge calculation
-
-
-
-
Error history
*2
*2
Emergency stop
-
-
-
-
Control via internet
-
-
-
-
-
-
E-mail notification for malfunction
-
-
-
-
-
-
-
*1 "Operation" setting is not available for this model. *2 This function is available only through external input.
Controller
Type
IR Receiver Unit
IR Receiver Kit
UTB-YWC
UTY-LRHYB1
Converter & Adapter
Network Converter
BACnet® Network Converter Gateway for LonWorks®
Signal Amplifier
Service & Monitoring
External Switch Controller
Service Tool
Web Monitoring Tool
Model name
32
UTY-VGGX UTY-VLGX UTY-ABGX UTY-VSGX
UTY-TEKX UTY-ASGX UTY-AMGX
VRF
Design Simulator Software which quickly performs model selection and creates material for model estimation in the VRF initial design stage. +
ª +
+
+ K+99 9«*89 *+ + ( 8
;
Controller Wired Remote Controller
Max. controllable
16
indoor units F
UTY-RNKU The room temperature can be controlled by detecting the temperature from the built-in sensor § ;9 ;& K @\ " X
Max. controllable
Simple Remote Controller
16
indoor units F
F
UTY-RSKU UTY-RHKU (Without ability to change operation mode) Compact remote controller provides access to basic functions UTY-RSKU
" @\
;
UTY-RHKU Without ability to change operation mode
Wireless Remote Controller
Max. controllable
16
UTY-LNHU
F
indoor units
Simple and sophisticated operations with a choice of 4 daily timers
e
+ @\
daily timers
4
Built-in timers Select from 4 different timer programs: : : Program timer: The program timer operates the ON and OFF timer once XU
Central Remote Controller UTY-DCGY Central control of small- and medium-sized buildings and tenants. %
@?? Z && " ;
; ( 9 ; K [
M( K '
*
UTY-LNHU
Max. controllable
100
Indoor units Max. controllable
16
groups
Easy Installation &
;
separately. ; K
33
K Touch Panel Controller
8
400
UTY-DTGY / [Z && /K9( ;
;
) ¬ " U??
X ;;% / K [
M( K '
*
System Controller
8
4
_* ;
UTY-APGX
8
The System Controller’s advanced integrated monitoring & control of VRF network system provides monitoring & control of small to large scale buildings.
400
8
1,600
" U_* ;@\??
U??
; K [
M( K '
*
( ;
:
"§+
IR Receiver Unit
IR Receiver Kit 9;
* K
IR Receiver Unit
IR Receiver Kit
* K
UTB-YWC
UTY-LRHYB1
Necessary to control all duct type models by Wireless Remote Controller
Cassette type indoor unit can be controlled with Wireless Remote Controller
K ª+ 8
Network Converter
16
) K
UTY-VGGXZ1 &
; _* ; ;
34
"&_''«@
_*
Network Converter for LONWORKS®
8
8
4
" §8
UTY-VLGX
128
_* ;
/:)W:*¯ ®
§8 &"&_/'«
_* ; §8 /:)W:*¯ ® " @XQ%
) K /:)W:*¯ ®
BACnet±Gateway
8
8
4
400
_* ;
UTY-ABGX
"&_/'«
8
1,600
&_* ;
§ 8
; ( @\?? §+K ®
K +)%+*+(
®@SZX??U§+K ®+ K §+K §+K ®% ( K
U_* ;@\?? U?? ; K ;§&/
CD-ROM (Software) Software Protection Key
"§+
External Switch Controller UTY-TEKX Air conditioner switching can be controlled by connecting other sensor switches % K ¯; ( K :):*
8 & K ;
ª8 Service Tool
8 8
8 8
400
UTY-ASGX
100
Extensive monitoring and analysis functions for installation and maintenance :
; ; K " U?? _* ;
&
;
"§ Computer not included. "§+
Web Monitoring Tool UTY-AMGX
8
4
_* ;
"§+ 8
Product features & ; ; ; ; (
;
@ *¬
9
¬ &
; +
; 8 ¬ ¬ ;% (
1,600
@M" ;¬
35
Central Remote Controller
Max. controllable
100
Indoor units
UTY-DCGY
Max. controllable
Central control of small and medium-sized buildings. The operation status of all indoor units can be viewed at a glance on a large LCD monitor.
16
groups
%
@?? Z && " ;
; ( 9 ; [
M( K '
*
User friendly operation : ; % ;
Function Menu ;
Registration indoor unit
Function button @ @ ;
76°F Operation guidance
System overview % 8 @\ % Group : Hallway Group : 3F Group : Division A
Group : Division B
Group : Division C
Group : Tenant B
Group : Tenant C
Group : 2F Group : Tenant A
( ;
36
_*
Functions Diverse control of indoor units % : : 8 &
( ; +
Weekly timer :;
; combinations. QXXQK QXXQK
76°F
Weekday
[>X\K
[>X\K
[>X\K
[>X\K
QXXQK
QXXQK
Weekend
Holiday QM??
@XM?? @M??
\M??
>M?? Time
Remote controller prohibition (All, On / Off, Automatic clock adjustment : The time setting for all controllers on the ;
;
Mode, Temp, Timer, Filter) :
R.C prohibition setting prohibits individual remote control operation from this controller
* upper and lower limitation
Error history 64°F 64°F 50°F
X?? +
;
troubleshooting.
86°F 86°F 86°F
Easy Installation &
;
; ; K
wall or installed on the wall. Setting pattern 1
+
Indoor unit registration
Setting pattern 2 Ceiling ;
% start
§:«
Wall Control panel + Power supply unit
Control panel
Wall
% finish
Specifications UTY-DCGY
8 K
; 9 9
;"
9KZ_
@??XU?_Z?\?
UXSSX\SQ@@X?@\XX\
SX>SXZZ@\@@[SX>>@SZS>X
@?>S?Q
@XZSZZ
/
K
;" K
37
&
K
Max. controllable
400
Indoor units
UTY-DTGY ;
; [Z &&/K9
/ [Z && ; ( ;
;
; ) ¬ " U??
K X ;; [
M( K '
*
Functions 2012
[?
[?
[Q
[\
[\
*
[? [Q
[?
[?
[X
+
Easy operation
Easy maintenance
( ;
' "% '"%
;
)
( ;
:
; ; " ; § §
38
_*
Up to 400 indoor units can be controlled Group A
Group B
%
( ; +
( ;
Function
Versatility
" U??
8
X? ; ( ; &
K_ K
&
K
9
;"§
%
Easy installation &
K ¬
; ) ¬
%
Automatic clock adjustment &
;
Specifications 8 ; 9 9 %
UTY-DTGY @??XU?_Z?\? @?@UX\?>@@@\XU\X@QZU U@@Q X@Z? "§X?
39
;K
Max. controllable
Software
4
VRF network systems
UTY-APGX
Max. controllable
400
;K
ª _* ;
Outdoor units
+
K " U_* ;@\??
U??
;K + ( ;
Max. controllable
1,600
Indoor units
User friendly views and operation Kª: M& ; ; ( ; K ;
Click & Operate the whole building!
View options: Site View, Building View, Floor View, List View
Click & Operate any specified unit(s)!
Alternate between views at the press of a button.
Site view
List view
Batched control of defined groups
Building view Batched control of selected units
The floor layout drawing can be imported to show the actual building layout. Click & Operate the whole floor!
Floor view
40
Click & Operate the unit !
VRF VRF
Schedule control
Remote centralized control
+
@US ; + ; ; ;
;K ; ; /+) K ¬ _*K
_*( VRF Controller
: 8 U_* ;
Internet or Telephone Line or LAN VRF Explorer
K 8
Error display & E-mail notification ( ; ;
;9 8
Operating & control record
Electricity charge apportionment
9 ; ;
+ _*;
;
K ; S ; ;
Prohibition Setting ;K
Multiple language display
Energy used by each unit is calculated
Energy apportioned by the outdoor unit to each indoor unit is calculated
&
+
&
+
[
M( K '
*
&
§
&
§
Security Support ( ;/( ; & ;
Energy saving management
Option
Optional features for additional energy savings: K: : " K ; % " * :
&
K
&
K
Electricity charges by tenant are calculated & ;;
; ; ; ;
The energy used by each indoor unit and the energy apportioned by the outdoor unit are added together to calculate the total amount of energy used. % ;
Operation Requirements ;K
( ; ¬ SX \U K
«S + _*9
&
&
+
&
§
&
K
Electric Bill
Electric Bill
Electric Bill
+ ;
Indoor unit total energy used
41
Control System Diagram Building Management
Air Conditioning Central Control System Controller (Software) UTY-APGX
Air Conditioning Individual Control Wired Remote Controller UTY-RNKU
System
Outdoor unit
USB Adaptor *2 Indoor unit
(Field supplied)
Internet or Public Telephone Line Simple Remote Controller UTY-RSKU
Remote/Monitoring side Touch Panel Controller UTY-DTGY
Signal Amplifier UTY-VSGX Simple Remote Controller UTY-RHKU Without master control
IR Receiver Unit UTB-YWC Central Remote Controller UTY-DCGY Wireless Remote Controller UTY-LNHU
General-purpose Building Control Computer
IR Receiver Kit UTY-LRHYB1 Connectable to various sized BMS/BAS*1 BACnet ® Gateway (Software) UTY-ABGX
USB Adaptor *2
(Field supplied) or
Network Convertor (BMS / LONWORKS® ) UTY-VLGX Card-key
External Switch Controller UTY-TEKX For single split
(Field supplied) Web Monitoring Tool (Software) UTY-AMGX
Service Tool (Software) UTY-ASGX USB Adaptor*2
Internet or Public Telephone Line
(VRF system side)
(Field supplied)
(Monitoring side) *1. BMS/BAS: Building Management System / Building Automation System *2. USB Adaptor is U10 USB Network Interface of Echelon® Corporation.
42
Network Convertor UTY-VGGX
USB Adaptor*2 (Field supplied)
Transmission line (VRF Network)
LONWORKS ® Network
Module link
Ethernet
Remote controller line
Signal line(Single split system)
USB cable
Group Remote Controller line
VRF
Airstage Portal portal.fujitsugeneral.com
What’s on the Portal? Tools for Engineers and Contractors
The Airstage Portal provides a single source for all information for Fujitsu Airstage VRF systems. From the Airstage Portal, all registered users have access to: Manuals, Literature, Design Simulator Software, Commissioning Forms, Troubleshooting Guides, Design & Technical Manuals and Online Training.
´+ / : ´+ 8
´9 9
Additional features, such as the Airstage Project Manager, are available to Fujitsu Reps, Fujitsu Distributors and Fujitsu Sales Engineers. The Airstage Project Manager supports projects from the design stage through completion and ensures clear and effective communication between all Fujitsu team members.
´& ' ´% _ ´¬ ;+^
The Airstage Project Manager applies technology to simplify project management and ensure a successful VRF installation.
A central place for project members to coordinate. Who Has Access to the Portal? ´% + * ´Engineers ´* 8
*8 ´K ´9 ´ ( (
Information & Downloads
Technical Information
Training ´9 + ; ´* on-site training classes ´/
Airstage features
Warranty & Commissioning ´K * ´ (
;K ´ % 9
Tools for Fujitsu Sales Team Maintain Projects ´" 9 ´&
Submittals & Closeout Documentation ´+ ; submittals & closeout documents ´K *
closeout documents are archived for future reference
Warranty ´
;
43
&
Software
Control and Monitor Up To
100
UTY-ASGX
Outdoor units
(
;
Control and Monitor Up To
:
; 9
; : _* ; U??
:
& ;
;
& _* ; K
K_ ; create commissioning report. K
;
"§ *1 (included) K
_* ; "@?"§
400
Indoor units
Wiring connection Refrigerant piping
Indoor unit USB adapter (included) Transmission line Indoor unit *USB Adapter is U10 USB Network interface of Echelon Corporation. ®
Functions @;/ 9 ; ; in a list form.
X(¬ 9 9 9 ; &
;
S(¬ 9 / 9 ;
; &
;
error occurs.
U: ; & ;
& ; ;
K_
44
(Field supplied)
Easy connection using USB adapter
VRF
Z( ;
m
9 ; &
¬ ; ; Z? ;
\* 9 :
;
"
; ; ;
[K & 9
+
K_
Q) & ;+ ; +
_*; ;
9) Remote Setting
;
@?;& & ; ;
;
11) Software Version
@U( 8 ;*
& ¬
;
;
K_
12) Central Release
) M& ( 8 ;* !&
; * : 8
&
/
temperature limit).
@Z&' %
@S8 ) +
9
K_
PERSONAL COMPUTER SPECIFICATIONS +& 8 ® ® : ;
8 ® ®« ( S 8 ® ® Vista ® § ( ( X 8 ® ®[ ( @
CPU
Intel ® Pentium ®K ®+89+ &89 &8@'
99
10 GB or more of free space
8 ;
@'§_ [Z@X8§«
Interface
"§ "@?"§) %
;
Required Software
% ( \? [? Q?+ ® Reader® 9.0 or later
*¬
K9*:8
/
K9*:8¯;"@?"§+
45
Design Simulator Easy Equipment Selection, Complete Selection Output, Reliable Project Management Design Simulator makes it easy to select equipment for complex building air conditioning systems. The software output contains all important design data including: Equipment Schedule, Piping Layout, etc. (all of the documentation needed to estimate a project.) Design Simulator simplifies the design process. To design a system, just select the indoor unit types, designate the groups, and the software will automatically select the outdoor unit and create the piping and wiring diagram. Design Simulator also checks all of the equipment information to ensure proper installation.
Step
1
Select the model
Choose the model for each system.
Step
4
Piping Length / Piping Diagram
Piping diagram is created automatically. As piping lengths are entered, system automatically calculates refrigerant charge.
Step
2
Select the Indoor Unit
Choose the unit types and the conditions and the software will select the correct indoor unit. Indoor unit can also be selected manually.
Step
5
Wiring / Controller Diagram
Automatically creates the wiring diagram. Simple grouping functions create a custom wiring diagram for the project.
Step
3
Select the Outdoor Unit
Using the Drag & Drop function, connect the indoor unit to the appropriate outdoor unit.
Step
6
Select Converters and Central Control
Choose additional devices to meet the needs of the project.
Setting Software can be customized for any geographic location.
Step
7
Report Output
Design Simulator creates a project output with all of the project schedules and schematic drawings.
46
Units (US conventional / Metric) Custom Database Function Output Settings
Language Setting
VRF
Software Requirements Sof tw a re
Design Simulator
Operating System
Microsoft Windows XP / Vista / 7 Hardware
System Requirements
Display Software
CPU: 500 MHz or more Memory: 1 GB (Vista), 512 MB (XP) or more HDD: 1 GB or more 1024 x 768 dots or more Internet Explorer 6.0 or more Acrobat Reader 4.0 or more Microsoft Word 2003/2007
Specifications Item Subject model
Preferences
Model selection
Drawing
Output data
Report format
Update
Function VRF V-II Multiple language setting (Choose from 25 different languages) Multiple unit setting Project detail information setting Brand/User name setting User option setting Auto mode selection (Indoor unit/Outdoor unit/Piping/Wiring) Manual mode selection Optional parts selection Controller/Adapter/Convertor selection Auto drawing (Piping diagram/Wiring diagram) Auto product information display Material list display Product detail display (Photo, Specifications, Options) Diagrams display (Piping/Wiring) Additional refrigerant volume (Input piping length) CAD data (2D-DXF, 3D-RFA) Word (rtf) CSV DXF Auto update via internet Download the latest data from the Airstage Portal (portal.fujitsugeneral.com)
Note: 1. Specifications are subject to change without notice 2. New models will be added as they are introduced.
Output Equipment selections and schedules can be output in standard industry file formats.
Auto Update Software updates automatically with the latest product data.
Request for update
Latest information is transmitted
Word format Excel format Auto CAD format 2D Data 3D Data (RevitMep data) Wiring and piping schematic drawings
user side(PC)
Maintains software integrity Maintains software history
FTPserver side (PC)
Updates product information
47
Building Information Modeling (BIM) FUJITSU provides the Building Information Modeling (BIM) object models and contents for our VRF system and some products to the architect, designer and contractor using Autodesk® Revit® technology from our Website and Autodesk® Seek Website, etc.
BIM Object Models Ensure Proper Design Many products available We provide BIM data for indoor units, outdoor units, and accessories. We will continue to create and provide products to support the global market. Object models: VRF “AIRSTAGETM V-II” /8 Rooms Multi “HFI” / Energy Recovery Ventilator Files : Indoor units 75 files / Outdoor units 22 files / Options 15 files
3D and 2D product data We provide 3D data that is similar to the product appearance. 2D CAD design operations are supported and 2D display is also provided. The data can also be output in other formats, such as DXF and DWG, which are used by other design CAD.
Installation limitation The equipment installation limitation range is shown. The distance range from the wall, etc., is automatically displayed to make it easy to provide highly reliable layout designs.
Installation information Other information, such as symbols showing the airflow direction that are required for installation drawings, is built in and can be automatically reflected in 2D drawings. Installation drawings can be created easily.
Product specifications & Link information Contains the basic information required for air conditioner design, including unit size, capacity, input power, noise, and airflow rate.
Data volume Fujitsu Revit® files are small, requiring very little system resources.
Required software Autodesk® Revit® series software • Autodesk® Revit® Architecture • Autodesk® Revit® MEP • Autodesk® Revit® Structure
48
Data format • RFA
Product parameter Power source Input power Capacity Airflow rate Sound pressure level Dimensions Weight Connection pipe diameter Refrigerant Material/Color
VRF
Auto Louver Grille Kit UTD-GXSA-W, UTD-GXSB-W
Operation with indoor unit
Opened louver
Auto Louver can be controlled by remote controller of indoor unit.
Up and Down auto swing Fixed airflow or auto swing 4 angle settings
Closed louver
Auto-closing louver When operation of indoor unit is stopped, the louver will automatically close.
Dimensions
Flexible Control
W2 Fitting Flange
Auto Louver Grille
Grille
Duct type H2
H1
W1
D1
D2 Unit: in.
Model Name
W1
W2
UTD-GXSA-W 26-7/8 25-13/32
H1
H2
D1
D2
Wired Remote Controller
Wireles Remote Controller
7-3/32 5-13/16 11/32 3-5/16
UTD-GXSB-W 34-3/4 33-1/4
Specifications UTD-GXSA-W
Model name
ARUL7/9/12/14RLAV
Applicable Indoor Unit Power Supply Fixing of Auto Louver Grille Extension Square Duct Limit Net Dimension inch (H x W x D) (mm) Weight
Net Gross
lb. (kg)
Color Louver Motor Accessories Operation range
Cooling Heating
UTD-GXSB-W
°F (°C) % RH °F (°C)
ARUL18RLAV
Connecting with Control box of indoor unit Screw ¸xing to Flange or Rectangluar Duct 39-3/8” (Max. duct length between indoor unit and grille) 7-3/32x26-7/8x(3-5/16+11/32) 7-3/32x34-3/4x(3-5/16+11/32) [180x683x(84+9)] [180x883x(84+9)] 4.4 (2.0)
5.6 (2.5)
6.7 (3.0)
7.8 (3.5) White Stepping Motor Fitting Flange, etc. 64 to 90 (18 to 32) 80% or less 50 to 86 (10 to 30)
49
Optional Parts Connection Units Outdoor Unit Branch Kit Liquid Pipe
Gas Pipe
Separation Tube
Header Gas Pipe
Gas Pipe
Liquid Pipe
UTR-CP567X
Type Outdoor Unit Branch Kit Separation Tube
Header (6 Branch) Header (8 Branch)
Liquid Pipe
UTR-BP567X / UTR-BP180X / UTR-BP090X
Compatibility Multiple Outdoor Units Greater than 193,000 (BTU/h) 96,500 to 193,000 (BTU/h) 96,500 (BTU/h) or less 96,500 to 193,000 (BTU/h) 96,500 (BTU/h) or less 96,500 to 193,000 (BTU/h) 96,500 (BTU/h) or less
6-Branch: UTR-H0906L / UTR-H1806L 8-Branch: UTR-HD908L / UTR-H1808L
Model Name UTR-CP567X UTR-BP567X UTR-BP180X UTR-BP090X UTR-H1806L UTR-H0906L UTR-H1808L UTR-H0908L
For Duct Models Flange
IR Receiver Unit
Round
Rectangular
UTD-RF204
UTD-SF045T
Auto Louver Grille Kit
Remote Sensor Unit
For Slim duct type
Accurate temperature is possible sensing room temperature using a remote sensor unit.
UTD-GXSA-W (For 7/9/12/14 type) UTD-GXSB-W (For 18 type)
Type Flange (Round) Flange (Rectangular) IR Receiver Unit Long-Life Filter Auto Louver Grille Kit Remote Sensor Unit Drain Pump Unit
50
UTB-YWC
UTD-RS100
Compatibility Duct Type (ARUM24-36) Duct Type (ARUM24-36) All Duct Type High Static Duct Type (ARUH36-60) Duct Type (ARUM24-36) Slim Compact Duct (ARUL7-14) Slim Compact Duct (ARUL18) All Duct Type Duct Type (ARUM24-36)
Long-Life Filter
UTD-LF25NA
UTD-LF60KA
Drain Pump Unit
UTZ-PX1NBA
Model Name UTD-RF204 UTD-SF045T UTB-YWC UTD-LF60KA UTD-LF25NA UTD-GXSA-W UTD-GXSB-W UTD-RS100 UTZ-PX1NBA
VRF
For Cassette Models Air Outlet Shutter Plate
Wide Panel
Closes the air outlet when 2 or 3 directional airflow is required.
Fresh Air Intake Kit For Compact Cassette type
For Cassette type
Indoor unit 37.5” (950 mm) Panel 23.5” (600 mm) 23.5” (600 mm)
UTG-AGYA-W
UTR-YDZC
Panel Spacer
UTR-YDZB
UTZ-VXAA
UTZ-VXGA
IR Receiver Kit
Insulation Kit For High Humidity
Wireless Remote Controller sold separately. Insulation Kit
9.5” (242 mm) Panel spacer
UTG-BGYA-W
Type Wide Panel Air Outlet Shutter Plate Fresh Air Intake Kit Panel Spacer Insulation Kit for High Humidity IR Receiver Unit
UTZ-KXGA / UTZ-KXGB / UTZ-KXGC
UTY-LRHYB1
Compatibility Cassette Type (AUUB18-36) Cassette Type (AUUB18-36) Compact Cassette Type (AUUA7-24) Cassette Type (AUUB18-36) Compact Cassette Type (AUUA7-24) Cassette Type (AUUB18-36) Cassette Type (AUUB30-36) Cassette Type (AUUB18-24) Compact Cassette Type (AUUA7-24)
Model Name UTG-AGYA-W UTR-YDZC UTR-YDZB UTZ-VXGA UTZ-VXAA UTG-BGYA UTZ-KXGA UTZ-KXGB UTZ-KXGC
Cassette Type (AUUB18-36)
UTY-LRHYB1
For Ceiling Models Drain Pump Unit
Type Drain Pump Unit
Compatibility Ceiling Type (ABUA30-36)
Model Name UTR-DPB24T
UTR-DPB24T
51
Applications There are many applications for Airstage VRF systems including such markets as education, healthcare, hospitality, utilities, office buildings, apartment buildings, condominiums, and restaurants. Note: VRF Heat Pump System does NOT provide simultaneous Heating and Cooling. System operates in either Heating mode OR Cooling mode.
Medical and Healthcare Facilities VRF gives each patient individual control of their room temperature. Central control ensures that air conditioning is only delivered to rooms that are occupied.
INDIVIDUAL CONTROL VRF gives each patient or each room individual control of their room temperature.
CLEAN AIR VRF systems can use ductless indoor units reducing the time and expense of maintaining a HVAC system and eliminating the risk of duct-borne molds and bacteria. CENTRAL CONTROL Powerful central control ensures that heating or cooling is only delivered to rooms that are occupied. This provides enormous savings for facilities with revolving occupancy.
RELIABLE PERFORMANCE Since each refrigerant circuit has the ability to operate independently, a properly designed VRF system can add a layer of security to a HVAC system. If an individual unit needs to be shut down for repairs, the rest of the system can operate normally. HEALTHIER FACILITY VRF systems can be integrated with fresh air systems to ensure that air quality meets the needs of the occupants. VRF provides the most comfortable environment for all occupants.
INDIVIDUAL COMFORT With VRF, each patient can have their own controller to set the room temperature for their maximum comfort. 52
VRF
Educational and Religious Facilities In a school, an investment in VRF is an investment in your community. VRF is more efficient than conventional systems, providing financial savings to the school for many years. Also, a quiet VRF HVAC system (as quiet as19 dB) creates a much better learning environment for students.
HEALTHIER FACILITY VRF systems can be integrated with fresh air systems to ensure that air quality meets the needs of the teachers and students. CENTRAL CONTROL Powerful central control can monitor and control individual schools, or an entire college campus, from a single location. ZONING Save energy by only heating or cooling the classrooms that are occupied. Set temperature can be pre-programmed to meet the energy budget for the school district. COMFORT VRF helps achieve a healthier, quieter, more comfortable and productive learning environment.
53
Multi-Tenant Dwellings VRF improves the quality of multi-tenant buildings while reducing tenant complaints. High quality VRF systems let owners save on energy costs and reduced maintenance costs. With VRF, each tenant has individual control over the temperature setting for the comfort of their home.
QUALITY By delivering quiet, efficient heating and cooling, VRF improves the quality of multitenant buildings and reduces tenant complaints.
ENERGY SAVINGS Efficient VRF systems reduce the total energy costs for buildings over most other options. High quality systems reduce maintenance and service costs. INDIVIDUAL BILLING Using the Energy Charge Apportionment feature, landlords can easily bill each tenant for the percentage of total energy the individual tenant consumes. INDIVIDUAL COMFORT With VRF, each tenant can have their own controller to set their room temperature for their maximum comfort. CONVENIENT CENTRAL CONTROL Landlord can monitor and control all indoor units from a central location. Landlord can even troubleshoot or solve tenant complaints remotely. QUIET Indoor units as quiet as 19dB ensures a quiet, comfortable living environment for all tenants. 54
VRF
Office Buildings and Retail Spaces VRF provides a comfortable work environment for all employees. Zoning ensures that energy is only used to cool/heat occupied offices. Quiet indoor units and precise temperature control creates the most comfortable and productive work environment.
QUIET Indoor units (as quiet as 19dB) and outdoor units (less than 64dB) creates a pleasant work environment and reduces noise complaints. ZONING Save energy by only heating or cooling occupied offices. No more hot/cold calls since each zone or tenant has individual control of the set temperature.
CONTROL Powerful controls options can manage and monitor entire building from a single location.
EASE OF INSTALLATION Can be installed in occupied office spaces with minimal disruption to occupants. Can even be installed without disrupting the existing HVAC system. FLEXIBLE As tenants and office configurations change, VRF system configurations can also be modified (within original design constraints) to meet the needs of new tenants. COMFORT VRF provides a comfortable work environment for all employees. Quiet indoor units and precise temperature control creates the most comfortable and productive work environment. 55
FUJITSU GENERAL AMERICA, INC. 353 Route 46 West, Fairfield, NJ 07004 airstage.fujitsugeneral.com
Variable Refrigerant Flow (VRF) Multi-Split AC and HP AHRI Standard 1230
%:>??@ %:@U??@ K M?@@??Q>S>U K M?@@?U>XUZ@?@
Fujitsu General (Thailand) Co., Ltd.
%:>??@ K M?@@??[>X\>
%:@U??@ Certified number : 272043
Fujitsu General (
) Co., Ltd.
%:>??@ Certified numberM??\?Q^@@?\@*X8
%:@U??@ K M??\?>(X?UZU*X8
Fujitsu General Central Air-conditioner (Wuxi) Co., Ltd.
! "$%&"'()(*+//%8%&(9
$
:
;
; Actual products’ colors may be different from the colors shown in this printed material. Internet sales are strictly prohibited and unauthorized. Any HVAC systems purchased on the Internet, from an online retailer or any similar e-tailing website, OR where the original factory serial numbers of the display have been removed, defaced, or replaced in any way WILL NOT BE COVERED BY WARRANTY.