Transcript
PA6/PA8 6 Zone Wired Intruder Alarm System
Zones
0 1
2
3
4
5
6
1
2
3
4
Power Attack Tamper
5
6
7
8
9
CHIME
OMIT
RESET
PROG
SET
Day
Installation & Operating Manual
FOREWORD The PA6 and PA8 Alarm Systems are designed for ease of
Note: Where a Control Panel Back-up Battery is not
installation using only conventional domestic tools. However,
readily available it is recommended that the Control
it is essential that the installer reads and fully understands the
Panel's connected to a 13 Amp, 3 pin plug (fused 3A)
advice and procedures contained in this manual and plans
via a 5A, 3 core mains cable until the installation is
the system before proceeding with the installation.
complete.
All components are designed and manufactured to provide a high standard of security protection and long, reliable service.
This will enable the Control Panel to be
readily switched ON and OFF where indicated during installation in lieu of connecting/disconnecting the Back-up Battery.
During installation, it is important that the procedures described in this manual are followed in sequence.
DANGER - 240 VOLTS. To prevent the risk of electrocution, it is essential to turn off the mains electricity supply to the
This manual should be retained in a safe place for future
Control Panel before commencing installation and work
reference.
within the Control Panel.
Note:
Do not permanently connect the mains supply until the
The PA6 system is not supplied with the Remote
Keypad. All references to planning, installation and operation
installation is complete.
of the Remote Keypad should be ignored for the PA6 system and are only applicable to the PA8 system.only.
The permanent mains supply to the control panel must come from an un-switched fused connection unit (fitted with a 3A fuse) directly connected to the mains
IMPORTANT
consumer unit. It should not be connected to circuits
All components, with the exception of the External
supplying domestic appliances, (e.g. washing machines,
Siren & Strobe, are suitable for mounting in dry interior
etc), as these types of appliances may cause the system
locations only.
to malfunction.
Internal mounted components must not be exposed
The mains supply to this product should be installed by a
to dripping or splashing water and liquid filled objects
competent person (e.g. a qualified electrician) in accordance
must not be placed on it.
with the instructions contained with the product and in accordance with the appropriate clauses of the current edition of the IEE wiring regulations (BS7671).
Tools and Equipment Required: 3mm flat bladed screwdriver
Bradawl
No.1 Philips Screwdriver
Drill
No.2 Philips Screwdriver
5 & 6mm Masonry Drill Bits
Wire Cutters & Strippers
Hammer
2. It is essential that all connections are made as instructed, that cables are not stressed and that terminals are fully tightened. 3. Always follow the manufacturers advice when using
Additional Requirements: Terminal Strip or Insulating Tape Back-up Battery:
BUB12/1.2 12V/1.2Ah Sealed Lead-Acid type
power tools; steps, ladders etc. and wear suitable protective equipment (e.g. safety goggles) when drilling holes and hammering home cable clips etc. 4. Before drilling holes in walls, check for hidden electricity
SAFETY WARNINGS
cables and water pipes. The use of a cable/pipe locater
Before proceeding with the installation, please note the
maybe advisable if in doubt.
following safety warnings: 1. For safety reasons, the complete system operates at 13V powered from the Control Panel transformer, which is
SYSTEM SECURITY This system has been designed to both detect intruders and act as a strong deterrent to would-be intruders.
connected to the mains supply. The Control Panel has facilities for a 12V, 1.2Ahr Rechargeable Back-up Battery to
Please remember that given adequate knowledge and time
power the system in the event of a mains failure. It is
it is possible to overcome any alarm system and we
strongly recommended that a Back-up Battery is purchased
therefore recommend that an Intruder Alarm is used in
and installed in the Control Panel and that the complete
conjunction with good physical protection such as security
installation and testing of the system is undertaken with the
window and door locks.
Control Panel powered from the Back-up Battery only.
Friedland
PA6/PA8 - 6 Zone Wired Intruder Alarm System
CONTENTS Page No.
Page No. KIT CONTENTS
2
INTRODUCTION & OVERVIEW
3
INSTALLING THE MAGNETIC CONTACTS
14
Wiring The Magnetic Contacts
15
Testing Magnetic Contacts At The Control Panel
16
Control Panel
3
Remote Keypad
3
Passive Infra-Red Movement Detectors
3
Mounting the External Siren & Strobe Enclosure
16
Magnetic Contact Sets
3
Wiring the Siren & Strobe Unit
16
External Siren & Strobe
4
SYSTEM FEATURES
4
INSTALLING THE EXTERNAL SIREN & STROBE
16
CONNECTING THE CONTROL PANEL MAINS SUPPLY
17
PROGRAMMING
18
Arm/Disarm
4
Quick Set
4
Event Replay
4
Chime
4
Reset
4
Alarm Duration
18
Programming
4
Main User Access Code
18
Detection Zones
4
Second User Access Code
18
Personal Attack (PA) Zone
4
Installer Access Code
19
24 Hour Tamper Circuit
4
Omit Prevent Zones
19
Siren & Strobe Anti Tamper Monitoring
4
Program And Zone Set Up
19
Keypad Security
4
To Exit From Programming Mode
19
Programmable Zone Options
5
Reset To Factory Set Default Conditions
20
Zone Entry Modes
5
Program Exit Modes
5
General System Programmable Options
5
To Enter Programming Mode
18
Exit Timer
18
Entry Timer
18
TESTING THE SYSTEM OPERATING INSTRUCTIONS
PLANNING THE INSTALLATION
6
To Arm The System
20 20 20
6
To Set A Program
20
Mains Wiring
6
Faults During Setting
21
Detector Wiring
6
To Omit A Zone
21
Quick Set
21
Control Panel And Remote Keypad
Magnetic Contact Sets
6
PIR Movement Detectors
6
External Siren & Strobe
7
Installation Example
7
INSTALLING THE CONTROL PANEL AND REMOTE KEYPAD
8
Mounting The Control Panel
8
Mounting The Remote Keypad
9
Wiring The Remote Keypad
9
Testing The Control Panel (and Remote Keypad) INSTALLING THE PIR MOVEMENT DETECTORS
10 10
Auto Reset and Re-Arm
21
Day LED
21
Power LED
21
Alarm Memory Recall
21
MAINTENANCE Control Panel, Keypad & Detectors
22 22
Rechargeable Batteries
22
Control Panel Fuses
22 22
11
TROUBLE SHOOTING
23
14
EXTENDING YOUR ALARM SYSTEM
24
11
Wiring The PIR Movement Detectors Testing The PIR Movement Detectors At The Control Panel
PA6/PA8 Alarm
21 21
ALARM RECORD
Mounting The PIR Movement Detectors
TYPICAL WIRING ARRANGEMENTS
To Disarm The System Chime
12-13
COMPONENT SPECIFICATION
Back Cover
1
KIT CONTENTS INTRODUCTION
The PA6 and PA8 Alarm kits contain the following components.
Zones
0 1
2
3
4
5
1
2
3
4
Power
6
Attack Tamper
5
6
7
8
9
CHIME
OMIT
RESET
PROG
SET
3
4
Day
Control Panel
Zone 1
0
Zone 2 Zone 3
1
2
Zone 4 Zone 5 Zone 6
5
6
7
8
9
Chime
Omit
Reset
Prog
Set
Zone 7 Zone 8 Tamper Attack
Day
Power
2 x Sets of Magnetic Contacts
External Siren & Strobe
IMPORTANT Please check all items are present BEFORE breaking the Remote Keypad 2 x PIR Movement Detectors (PA6)
packaging warranty seals. No claims for missing parts will be accepted unless pack seals are in place and intact.
(PA8 contains 4 PIRs)
1 x 6 Zone Control Panel 1 x Remote Keypad (PA8 only) 1 x External Siren & Strobe 2 x Passive Infra-Red Detectors (PA8 contains 4 PIRs) 2 x Magnetic Contact Sets
EXTENDING THE ALARM SYSTEM The following additional accessories are available to enhance your system and provide further protection and a higher level of security where required. Component
Product Code
2 x 50m coils of 6 Core Cable 1 x Fixings Pack
Accessory Pack containing: 2 x Passive Infra-Red Movement Detectors 2 x Magnetic Contact Sets
Also included:Installation & Operating Manual Siren Cover Sticker Window Warning Stickers
2
25m coil of 6 Core Cable
PU1
Passive Infra-Red Movement detectors (Twin Pack)
PU2
Full details of these accessories are given on page 24.
PA6/PA8 Alarm
INTRODUCTION & OVERVIEW necessary to install a complete system. The items included
This is because the PIR detectors require a period of
in your package are shown opposite, the main components
3-4 minutes to stabilise before they operate correctly
are as follows:-
and during this period they effectively generate an
INTRODUCTION
The PA6 and PA8 Alarm kits contain all components
alarm signal to the Control Panel.
CONTROL PANEL The Control Panel is the heart of the intruder alarm system
Note: Although optional, it is strongly recommended that backup batteries are fitted.
and contains the microprocessor and electronic circuitry
All detectors and alarm circuits are wired from the
necessary to monitor the various detection circuits (Zones)
Control Panel and operate at 12 Volts dc.
and to initiate an alarm condition in the event of an intrusion into a protected area. The complete system operates at 13 Volts powered from
REMOTE KEYPAD
the Control Panel transformer which is connected to the
The Remote Keypad has the facilities to duplicate all the
mains supply.
operation and control functions of the main Control Panel;
The Control Panel is operated via the push buttons on the
thus allowing the Control Panel to be located out of general
front of the Control Panel allowing the user to Arm/Disarm
sight or to suit cable routing.
(PA8 only)
the system, view the event record and test the system. A four digit Main User Access Code and Optional Second User Access Code ensures that only authorised users can
PASSIVE INFRA-RED MOVEMENT DETECTORS
operate the system.
PIR detectors are designed to detect movement in a
A separate Installer Access Code allows access to the
protected area by detecting changes in infra-red radiation
programming functions at the Control Panel. The Control
levels caused for example when a person moves within or
Panel also contains a small speaker used to indicate various
across the devices field of vision. If movement is detected,
conditions by means of a variety of tones.
an alarm condition is generated at the Control Panel (if the system is armed). PIR detectors will also detect animals, so
The Control Panel incorporates a ‘Non Volatile Memory’,
ensure that pets are not permitted access to areas fitted
(NVM) which records all program and system settings
with Passive Infra-Red Movement Detectors when the
indefinitely even when all power has been removed.
system is armed.
The Control Panel will also remember which mode it was in
Additional Passive Infra-Red Movement Detectors can be
when power was disconnected and revert to this mode
purchased separately, if required.
when power is restored, e.g. if the panel was in Alarm Mode when the power was removed, the panel will continue to be in Alarm Mode when power is restored.
MAGNETIC CONTACT SETS The Magnetic Contact Set comprises two parts; a Magnetic Contact Switch and a Magnet. They are designed to be
SYSTEM OPERATION AFTER POWER FAILURE If a power failure occurs while the system is armed and backup batteries are not fitted (or flat) then when power is restored the system will be in its previously armed state. If there are any PIR detectors wired to any active zone then an alarm will initially occur. The siren will sound for the set alarm duration after the 3-4 minutes required for the PIR detectors to stabilise.
fitted to either doors or windows with the Magnet fixed to the moving/opening part and the Contact Switch fixed to the fixed door or window frame. When the protected door or window is closed the Contact Switch is held closed by the Magnetic field from the Magnet.
Opening the protected
door or window will remove the magnetic field and allow the Contact Switch to open generating an alarm signal at the Control Panel, (if the system is armed). Additional accessory packs including Magnetic Contact Sets can be purchased separately, if required.
PA6/PA8 Alarm
3
INTRODUCTION
EXTERNAL SIREN & STROBE
EVENT REPLAY
The External Siren enclosure houses the 110dB Siren &
The Control Panel incorporates a memory capable of
Strobe Unit, which when assembled, installed and wired to
storing 8 alarm events. Event replay will enable the user to
the Control Panel will activate in the event of an intrusion
establish which Zones have been activated if an alarm has
with the system armed. In the event of the cable to the
occurred.
Siren & Strobe Unit being deliberately cut or the supply to the Control Panel being interrupted, the External Siren will
CHIME
operate from its own internal battery. For this reason, it is
Chime is a low security application for use when the system
recommended that a 12V 1.2Ah Back-up Battery is fitted to
is Standby. When a Zone that is set to chime is operated,
the main Control Panel.
the internal sounder will produce a low volume two stage warning tone and the Zone LED will illuminate.
The Siren enclosure also features an anti-tamper device, which will cause an alarm to activate if either the front
A typical use of the Chime function would be in a shop to
cover is removed or the complete assembly is pulled off
warn of a customer’s presence or in a house to warn that a
the wall.
door or particular area has been accessed.
To comply with local Noise Abatement Legislation, timers are incorporated both in the Control Panel and Siren & Strobe Unit to silence the siren after a pre-determined time.
The Control Panel timer is factory pre-set to 20
RESET Pressing this button clears any previously entered information at the keypad, e.g. incorrect buttons pressed and also clears any Fault Lights, unless the fault still exists.
minutes, but can be set by the user between 01 minute and 99 minutes. The Siren & Strobe Unit timer limit is factory pre-set to 20 minutes, but can be reduced to 3 minutes by cutting an on-board link.
The Siren will reset with the
PROGRAMMING When a valid installer code has been entered, access to programming the various system options will be permitted.
Control Panel timer but will not continue beyond the set Siren timer limit (i.e. 20 or 3 minutes).
DETECTION ZONES
A strobe warning light is incorporated into the external
The Control Panel incorporates 6 detection Zones for the
siren enclosure and will flash in the event of an alarm to
connection of the system detectors. The function of each
provide a visual indication.
Zone is fully programmable in each of 3 setting programs.
Note: The strobe light will continue to flash after the siren has stopped to indicate that an alarm has occurred.
24 HOUR TAMPER CIRCUIT Many system components incorporate tamper protection facilities and the associated wiring can be monitored on a 24 hour basis to generate an alarm condition if the
SYSTEM FEATURES
equipment or wiring is interfered with. It is recommended that all system components with tamper facilities are
ARM/DISARM
monitored for tamper.
The system has an easy arming facility. To fully arm the system simply enter a valid User Access Code. The system
SIREN & STROBE ANTI TAMPER MONITORING
also has facilities to pre-program 3 Set routines or
Wiring to the external Siren housing is monitored on a
‘Programs’.
24 hour basis. In the event of the wiring to the external
The
OMIT
button enables you to omit a Zone(s) from a
housing being damaged or deliberately cut, or the housing opened or completely removed, the Control Panel will
program on a once only or temporary basis.
initiate an alarm condition and the External Siren will sound, powered from the siren’s integral Back-up Battery.
QUICK SET The final arming of the system can be quicker.
This is
useful for night setting when the Entry/Exit sounder can be silenced after just a few seconds.
KEYPAD SECURITY The Control Panel and Remote Keypad are protected from unauthorised disarming by means of initiating a Tamper Alarm if more than 20 incorrect key pushes are made.
4
PA6/PA8 Alarm
PROGRAMMABLE ZONE OPTIONS
Note:
The Control Panel uses 3 Set routines known as Programs.
the system, Program 1 will automatically Set.
In each Program the Exit Mode can be changed and the
Program 1 is usually considered as the ‘Full Set Program’
Zone may be set up to have a different function.
containing all of the Zones.
If a Program is not selected when the user Sets
The examples below show how 3 typical Programs could be used in a house.
GENERAL SYSTEM PROGRAMMABLE OPTIONS ENTRY TIME:
Program 1: To arm all of the Zones and become Set as the user leaves the property and closes the final door.
Factory Default setting: 30 seconds This is the time programmed to allow the user to reach the
Program 2: To protect the perimeter of the property in the
Control Panel or Remote Keypad to disarm the system before
evening and become Set after say 20 seconds.
a full alarm occurs. The Entry time may be set between 10 990 seconds in 10 second intervals, depending on your
Program 3: To protect the downstairs areas of the house at night and become Set instantly and silently.
requirements. If the system is not disarmed during the Entry delay period, a full alarm will occur when the Entry time expires.
ZONE ENTRY MODES
EXIT TIME:
TIMED:
Factory Default setting: 30 seconds
This function would be used to protect the main Entry/Exit
This is the time programmed to allow the user to exit the
door or the first sensor in the entry route.
premises before the system fully arms. The Exit time may be
Opening the door or operating the sensor whilst the system is
set between 10 - 990 seconds in 10 second intervals,
Set will start the Entry timer and allow time to Unset the system.
depending on your requirements. You will need to leave all protected areas and close protected doors/windows before
WALK THROUGH: This is used for detectors located between the main entry/exit door or sensor and the Control Panel or Keypad. On entry, once a Timed Zone has been operated and the Entry Timer started, the Zone will be inhibited and allow
the Exit time expires or a full alarm will occur. Note: If a Zone is open when the system is arming the Control Panel will emit a tone (different to the Entry/Exit tone) to indicate a Zone is open. It is not possible to Arm the system until the Zone is clear or omitted before arming.
access through to the Control Panel or Keypad. But when the system is Set, the Zone is fully active and will
ALARM DURATION::
cause an instant alarm activation.
Factory Default setting: 20 minutes This is the time that the alarm will sound for following an
INSTANT:
alarm activation. The Alarm Duration can be set to between
This function would be used for all Zones that are not part
01 - 99 minutes, depending on individual requirements.
of an entry route and will immediately cause a full alarm
Note: The maximum length of time that the External Siren
condition when activated.
will sound for when activated is set within the Siren & Strobe to either 3 or 20 minutes.
PROGRAM EXIT MODES TIMED: A Timed Program will become Set as the Exit timer expires.
SYSTEM RESET: System Reset (return all options to factory settings). If the User/Installer Access Codes have been lost or forgotten, or
FINAL DOOR:
the installer is unsure of the programmed options, it is
A Final Door Program will be Set 5 seconds after a timed
possible to return the Control Panel program to the factory
Zone has opened and closed.
default settings. All previously programmed options will be
If a timed Zone is not operated during the Exit period, the system will NOT Set. INSTANT:
cleared and the system will require re-programming. USER ACCESS CODE: Factory Default setting: Main User - 0 1 2 3 Second User - not programmed
An Instant Program will be Set silently 3 seconds after the Exit route has been initiated.
Two User Access Codes are available to Arm/Disarm and test the system.
PA6/PA8 Alarm
Each code is 4 digit, selectable from
5
INTRODUCTION
Therefore
0000 - 9999. However, the Main User Access Code has
from outside the property when arming the system.
the authority to add, change or delete the Second User Access Code. The User Access Codes should be changed
MAINS WIRING
from the factory default settings during programming after
Mains wiring to the Control Panel should come from an
installation is complete.
independently supplied, un-switched fused connection unit (fitted with a 3A fuse) located close to the Control Panel.
INSTALLER ACCESS CODE: Factory Default setting: 9 9 9 9
It is not advisable to connect the supply to other household circuits, as this may cause the system to malfunction. Attempt
To allow programming of the system options, a unique Installer Access Code must be entered at the Control Panel
to keep the mains cable run as short as possible between the fused connection unit and the Control Panel, (less than 3m).
Keypad. The Installer Access Code should be changed from the factory default setting during programming after installation is complete.
IMPORTANT: The mains supply to this product should be installed by a competent person (e.g. a qualified electrician) in accordance with the instructions contained with the
Note:
For security reasons, once the system has been
INSTALLATION
Armed by the User Access code, the Installer Access code
product and in accordance with the appropriate clauses of the current edition of the IEE wiring regulations (BS7671).
cannot be used to reprogram the system. It would be an advantage to have the mains supply connection Note: The User Access Codes and the Installer Access Code should all be different.
unit fitted prior to commencing the installation to avoid any unnecessary delay in fully commissioning your system. Note: The mains wiring should be kept separate from wiring
PLANNING THE INSTALLATION
to the detectors, both within the premises and on entering the Control Panel. Always route mains and detector wiring separately, preferably 300mm apart.
GENERAL
DETECTOR WIRING
Before attempting to install any wiring or system
Where only one detector per Zone is to be connected, the
components, it is recommended that a plan of the proposed
cable should be run directly to the detector. However, if
installation is prepared. This should help the installation to
more than one detector is to be connected to a Zone, either
be completed using the most unobtrusive and effective
(a) run all cables back to the Control Panel or (b) run one
methods. The following guidelines should be followed and
cable to the Control Panel and link the detector contacts in
used in conjunction with the example provided when
‘Series’ and power supplies in ‘Parallel’. (Refer to example
preparing your own system plan.
installation wiring diagrams on pages 12-13.
CONTROL PANEL AND REMOTE KEYPAD
MAGNETIC CONTACTS
(Remote Keypad PA8 only)
The Magnetic Contact is suitable for mounting in dry interior
The Control Panel & Remote Keypad should be located in a
locations only.
position out of sight of potential intruders and in a safe location,
Decide which doors and windows are to be protected by fitting
but accessible for system operation. Typically, the Control Panel
Magnetic Contact switches. Usually the front and back doors
may be located in a small cupboard under the stairs (or other)
will have Magnetic Contact Switches fitted. Additional contacts
close to the mains supply and for ease of cable installation, with
may be fitted where required to other more vulnerable doors or
the Keypad located adjacent to the main Entry/Exit door. An
windows, e.g. garage, patio and conservatory doors etc.
ideal mounting height would be the same as a household light switch or similar. If small children are in the household, a further consideration should be given to keeping the units out of reach. However, the final positions of the Control Panel and Keypad will
Note: It is not recommended to connect more than ten Magnetic Contacts to any one Zone, as this may cause difficulty in wiring and hinder any attempt to remedy wiring faults efficiently.
depend on the individual user’s requirements.
PIR MOVEMENT DETECTORS
Note: Also consider the user’s ability to hear the Exit/Entry
When considering and deciding upon the mounting position
tone (emitted by the Control Panel) effectively when setting
for the detector the following points should be considered to
the system. It is preferable that the Exit tone can be heard
ensure trouble free operation:
6
PA6/PA8 Alarm
1. Ideally the detector should be positioned in a corner of the room to be protected where the logical path of an intruder would cut across the fan detection pattern of the device. PIR detectors respond more effectively to movement across the device than to movement directly towards it. 2. Do not position the detector facing a window or where it is exposed to direct sunlight.
Surface cabling should be clipped at 1m (max) intervals using the cable clips supplied. In order to keep wiring consistent and aid installation/ connections, it is recommended that the following wiring code is adhered to throughout the installation:Red
+ve power supply to each PIR Movement Detector
Black
0V power supply to each PIR Movement Detector
Yellow/Blue
Normally closed detector contact Alarm zone circuit
Green/White
24 Hr normally closed Tamper circuit
PIR detectors are not
suitable for use in conservatories. 3. Do not position the detector where it is exposed to draughts. 4. Do not position the detector directly above a heat
5. Do not position the detector in a position where it is subject to excessive vibration.
The power supply to each PIR Movement Detector should ideally be taken direct from the Control Panel to each detector, so that a break in the cable only results in one
Note: When the system is armed, household pets should not be allowed into an area protected by a PIR as their movement would trigger the PIR and activate the alarm. Alternatively a PIR protected Zone may be 'Omitted' to allow
detector being out of service. However, the power supply can be taken from one detector to the next if required. A maximum of four detectors and 50m of cable may be connected per Zone.
for pet movement. All Zone and Tamper circuit wiring must be wired in a
EXTERNAL SIREN & STROBE The external housing should be located as high as possible in a prominent position so that it can be easily seen and heard.
The Siren should be mounted on a solid even
‘SERIES’ loop from the appropriate terminals in the Control Panel.
Where ‘SERIES’ connections are made terminal
blocks or insulating tape must be used to prevent bare wires touching each other.
surface so that the rear tamper switch is not activated
Please refer to the appropriate circuit wiring diagrams for
when mounted. Ensure that the tamper switch does not
typical wiring arrangements for the detectors supplied.
fall into the recess between brick courses as this would prevent the switch from closing. When running the cable
INSTALLATION EXAMPLE
to the Siren, the cable should pass through a hole in the
The following example overpage shows typical floor plans
external wall and enter through the rear of the casing.
for a two story domestic property incorporating the
Surface wiring to the External Siren & Strobe is not
suggested positions for the Control Panel, External Siren &
recommended unless it is mechanically protected, e.g. in
Strobe and Detectors, for optimum security. Use this as a
steel tubing or equivalent. However, if surface wiring is
guide for your installation in conjunction with the
unavoidable, the 24 hour monitoring will activate the alarm
recommendations for planning your intruder alarm system.
if damage to the wiring occurs. In this example, the front door is the Entry/Exit route to the
FURTHER CONSIDERATIONS
property and is connected to Zone 1.
If the system is to be armed at night (i.e. Zones Omitted)
The back/side door is also fitted with a Magnetic Contact
while the occupants remain in the household, make sure that
and is connected to Zone 2.
any detectors which are to be omitted are wired exclusively to those Zone(s). Pay particular attention to the most vulnerable points of entry to your property, which are the doors and windows to the side and rear of the property.
The Living Room and Dining Room are fitted with PIR Movement Detectors detecting entry into the rooms and are connected to Zone 3. A PIR has been fitted on the upstairs landing. The upstairs PIR Movement Detector will detect entry into the first floor
Plan your cable runs for ease of installation and neatness of final
and is connected to Zone 4 (This is the Zone which will be
appearance, allowing for concealing cables where necessary.
intentionally omitted when the system is armed at night).
PA6/PA8 Alarm
7
INSTALLATION
source, (e.g. fire, radiator, boiler, etc).
PIR Movement Detector (Zone 4) (omitted during night setting)
TYPICAL GROUND FLOOR PLAN
PIR Movement Detector (Zone 3)
PIR Movement Detector (Zone 3)
Bedroom 2 Dining Room Living Room
Magnetic Contact Detector
Bedroom 1
Hallway Kitchen
Back Door (Zone 2)
Landing
Bedroom 3
Control Panel
Front Door (Entry/Exit Zone 1)
TYPICAL FIRST FLOOR PLAN
Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8
Each property will have its own layout - the diagrams shown are intended only as a guide.
Tamper
INSTALLATION
Attack
Magnetic Contact Detector
Day
Power
Remote Keypad
Control Panel (under stairs)
External Siren & Strobe
Zones 5 and 6 are not used in this example
INSTALLING THE CONTROL PANEL AND REMOTE KEYPAD Choose a suitable position to locate the Control Panel and
holes. A small spirit level placed on the casing will
Remote Keypad as described in ‘Planning The Installation’.
ensure a perfect level. Remove the Control Panel, drill
Note:
The Control Panel & Remote Keypad should be
two 6mm holes and insert the 30mm Wall Plugs.
mounted on an even flat surface to prevent the possibility
Important: Do not drill the fixing holes with the Control
of distortion to the casings.
Panel in position; as the resulting dust and vibration may damage the Control Panel’s internal components
MOUNTING THE CONTROL PANEL
and invalidate the guarantee. Cable entry holes are provided in the rear of the base
WARNING
and around the outside edges through the thinned out
To prevent injury, this Control Panel must be securely
plastic sections, which may be cut away as required. It
attached to the wall in accordance with the following
is recommended that the round hole adjacent to the
instructions.
fused terminal block is used for the mains cable. 3. Loosely fix the lower mounting screws to allow for
1. Remove both screws located on the front of the Control Panel. Hinge down and remove the lower half of the
cables to be fitted through the entry holes at the rear of the casing.
casing. Locate the centre keyhole fixing on the back of the Control Panel and mark its position on the wall. Remove the Panel and drill a 6mm hole and fit the 30mm Wall Plug, fit a 30mm No.8 screw almost fully home. 2. Place the Control Panel onto the screw on the top keyhole fixing, (adjust the screw as required so that it is a snug fit to the keyhole slot). Hold the Control Panel casing in position and mark the two bottom mounting
8
4. If required connect the battery charging leads to the BATT +/- terminals (Red to ‘+’ and Black to ‘-’). Using the cable tie provided tie both battery leads to transformer leads conecting to the main printed circuit board close to the terminal blocks. 5. Ensure the Control Panel speaker wires are connected to terminals marked with a speaker symbol.
PA6/PA8 Alarm
Speaker Leads
Cover Tamper Switch
Casing Keyhole Fixing
Control Panel Speaker Volume Adjustment
Speaker Fuse
Bell/Strobe/Fuse
Remote Keypad Fuse Cover Fixing Screws
Back-up Battery Fuse
1
2
3
4
5
0
1
2
3
4
5
6
7
8
9
CHIME
OMIT
RESET
PROG
SET
Power
6
Attack
RKP FUSE
Tamper Day
SOUND
13V
TAMP
PA
1
2
3
4
5
6
7
8
+
TAMP
-
+13V
0V
+
-
STROBE
T A SCB
D B BELL SET
1A
1A
+ BATT
AC
Back-up Battery Leads Secured to Transformer Leads
1.6A
Mains Connection Terminal Block and Fuse
Bottom Cover
Mains Cable Entry Hole
Casing Fixing Holes
Mains Transformer
WP12.1-6
Optional Back-up Battery
Control Panel Internal Physical Layout
MOUNTING THE REMOTE KEYPAD 1. Having chosen a suitable position to locate the Keypad,
then fold over and wire into the appropriate terminals on the Keypad as follows:
run the required length of 6 core cable back to the Control
Red
13V
Panel. Do not make any connections at this stage.
Black
0V
Yellow
COMMS
Blue
SOUND
Green/White
TAMP
2. Loosen the bottom fixing screw until the lower edge of the Keypad releases and remove the front from the mounting panel. 3. Hold the mounting panel in position and mark the mounting holes.
A small spirit level placed on the
casing will ensure a perfect level.
2. Tighten the mounting plate fixing screws. Hook the Keypad over the top edge of the mounting plate, swing the Keypad down into position and tighten the bottom
4. Cable entry holes are provided around the outside
fixing screw to secure the Keypad.
edges through the thinned out plastic sections, which may be cut out as required.
3. Bring the Keypads cable through the cable entry slot in the rear of the Control Panel and strip back 5mm of
5. Mount the unit using two 25mm No.4 screws and
each core and twist the strand ends.
25mm wall plugs as required, (a 5mm hole will be required for the wall plugs).
4. Ensure that the mains power is switched off and the Back-up Battery is disconnected at the Control Panel. Connect the wires to the Keypad Terminals on the left
WIRING THE REMOTE KEYPAD
side of the Control Panel PCB following the colour
1. Thread the cable through the entry on the base, then
coding indicated above. Removing the TAMP wire link
strip back 5mm of each core, twist the strand ends
PA6/PA8 Alarm
as the wires are connected.
9
INSTALLATION
Volume + -
BATT
0V
SPEAKER
Detection and Alarm Wiring Terminal Blocks
COMMS
BELL/STROBE
Remote Keypad Terminal Block
Control Panel Schematic Wiring Diagram Showing Factory Links Fitted
RKP FUSE
TAMP
SOUND
COMMS
0V
13V
Remote Keypad
SOUND COMMS 13V 0V
TAMP
6
7
+
8
TAMP
-
+13V
+
0V
-
STROBE
T A SCB
D B BELL
1A
SET
BATT
5
4
SPEAKER
3
BELL/STROBE
PA
2
1
230 Volts AC
1A
+ BATT
AC
1.6A
Factory Links Note: Remove factory wire links before connecting circuit wiring. Transformer
INSTALLATION
Leave the factory wire links in place where a zone/circuit is unused.
Zones
PA Tamper Button Circuit
Detector Power Supply
Strobe
External Siren
Optional Control Panel Rechargeable Battery
TESTING THE CONTROL PANEL (AND REMOTE KEYPAD)
Once all Zones are tested, press
Before continuing with the installation, the Control Panel (and
Note: If the system is activated at any time during the
Keypad) should now be tested before any detectors are
testing and installation, enter the Factory Access Code
RESET
3 times to return
to Standby Mode.
connected and powered from a 12 Volt Battery only.
The
0
1
2
3
to silence the alarm.
Control Panel is factory fitted with small wire links inserted across the Zone and TAMPer connections.
These can be
removed, and then replaced when testing the Control Panel to simulate a detector opening and closing.
4. To test the Remote Keypad follow steps 1 to 4 above using the Keypad. 5. Disconnect the Back-up Battery and mains supply
If the front cover Tamper Switch is not defeated, the Control
before continuing with the installation.
Panel would indicate a Tamper fault, indicated by the appropriate panel LED and internal sounder activating. Connect a short piece of the alarm cable between terminals 15 (TAMP) and A. This will defeat the front cover tamper spring while you test
INSTALLING THE PIR MOVEMENT DETECTORS
the Zones. Leave this wire connected throughout the installation while you connect the detectors to the Control Panel.
The Passive Infra-Red Movement Detectors (PIRs) supplied with this kit are suitable for mounting in dry interior locations only.
1. Connect the 12 Volt Battery to the red and black battery leads. Observe the correct polarity, red wire to
It is recommended that the PIR Detector is mounted in the
the red battery terminal (+) and black wire to the black
corner of a room, approximately 2.2m above floor level. At this
battery terminal (-).
height the detector will have a 12m range with a 90º spread. If required the detector may be mounted at an 8° angle to tilt
2. The alarm will sound. Code
0
1
2
Enter the User Access
3
Before fitting the detector, observe the environmental considerations as described in ‘Planning The Installation’.
3. Set the panel into ‘Walk Test’ by entering:PROG
,
0
1
2
downwards and reduce the detection pattern range.
to silence the alarm.
3 ,
0 ,
5
All Zone LEDs will extinguish, the Attack, Tamper and
90° angle
Day LED’s will be illuminated. 4. Remove the wire links from each Zone in turn. As you do so the panel will beep and the appropriate Zone LED will illuminate. Replace the link to silence the alarm. The Zone LED will remain illuminated.
10
PIR Detection Pattern (90°Spread)
PA6/PA8 Alarm
PIR Sensor (Do Not Touch)
2.2 metres 2
4
6
8
10
AntiTamper Switch
12
Distance (metres)
Alarm LED PIR LED
2.2 metres N/C
24HR
123
8° Tilt 2
4
6
8
10
12
Distance (metres)
Retaining Clip
Connection Terminals
Cover Retaining Screw
Pulse Count Jumper Link
PIR Detection Patterns (Range)
Note: A maximum of ten PIR Movement Detectors can be connected to the system in total.
4. Carefully cut (or drill) out the required mounting holes and cable entry.
Only remove the minimum required
number of screw or cable entry holes, to avoid insects
MOUNTING THE PIR MOVEMENT DETECTORS Top Mount
entering the detector and causing false triggering. Mount the unit using two 18mm No.4 screws and 25mm wall plugs as required, (a 5mm hole will be required for the wall plugs). Note: Do not over tighten or use larger headed screws
Vertical Mount
when mounting the unit, as this may distort the casing.
WIRING THE PIR MOVEMENT DETECTORS Angled Mount
1. Thread the cable through the entry on the base, then strip back 5mm of each core, twist the strand ends 8°
then fold over and wire into the appropriate terminals on the PIR Detector.
1. Having chosen a suitable position to locate the PIR Detector, run the required length of 6 core cable back to the Control
The terminals on the PIR and the wires in the cable are
Panel. Do not make any connections at this stage.
colour coded.
The correct colour coding should be
followed throughout the entire system. 2. Slightly loosen the cover retaining screw on the PIR and remove the cover. Carefully remove the PCB by unclipping
Red
+ve power supply to each PIR Movement Detector
Black
0V power supply to each PIR Movement Detector
Yellow/Blue
Normally closed detector contact Alarm zone circuit
Green/White
24 Hr normally closed Tamper circuit
the PCB retaining clip at the bottom left of the PCB. Important: Do not touch the PIR sensor in the middle of the PCB as any marking may impair the unit’s performance. If accidentally touched, clean with a dry lint free cloth. 3. The unit can be mounted for the standard 12m range by using the top two side holes, or tilted down by 8° using the bottom two side holes. Alternatively, the unit can be ceiling mounted using the two holes at the extreme top of
2. Carefully refit the PCB into the casing taking care not to touch the PIR detector lens.
the casing. Cable entry cut outs are provided top and bottom, as required.
PA6/PA8 Alarm
Continued on Page 14 11
INSTALLATION
PIR Movement Detector PCB Layout
TYPICAL WIRING ARRANGEMENTS PIR MOVEMENT DETECTOR +
N/C
-
CONTROL PANEL PA
24 Hr
5
4
3
2
1
7
6
TAMP
-
+
8
+13V
+
0V
-
STROBE
T A SCB
D B BELL SET
CONNECT TO REQUIRED ZONE GREEN WHITE BLACK RED YELLOW BLUE
INSTALLATION
Wiring diagram for Single PIR Detector on a single zone
PIR MOVEMENT DETECTOR N/C
+
-
CONTROL PANEL PA
24 Hr
1
2
3
4
5
6
7
8
+
TAMP
-
+13V
0V
+
-
STROBE
T A SCB
D B BELL SET
CONNECT TO REQUIRED ZONE GREEN WHITE BLACK
N/C
YELLOW
BLUE
BLUE
+
RED
-
Twist (or Solder) cable cores together and insulate
BLACK
24 Hr
GREEN WHITE
PIR MOVEMENT DETECTOR
RED YELLOW
Wiring diagram for two PIR Detectors to a single zone with all cables returning to the Control Panel
PIR MOVEMENT DETECTOR N/C
+
-
CONTROL PANEL PA
24 Hr
1
2
3
4
5
6
7
8
+
TAMP
-
+13V
0V
+
-
STROBE
T A SCB
D B BELL SET
CONNECT TO REQUIRED ZONE GREEN WHITE BLACK RED BLUE
YELLOW
YELLOW
BLUE Twist (or Solder) cable cores together and insulate
GREEN WHITE
MAGNETIC CONTACT
Wiring diagram for PIR and Magnetic Contact Detector on different zones with all cables returning to the Control Panel
12
PA6/PA8 Alarm
CONTROL PANEL PA
5
4
3
2
1
MAGNETIC CONTACT
7
6
TAMP
-
+
8
+13V
+
0V
-
STROBE
T A SCB
D B BELL SET
MAGNETIC CONTACT
Twist (or Solder) cable cores together and insulate
YELLOW
BLUE
BLUE
YELLOW
GREEN
WHITE
WHITE
GREEN
PIR MOVEMENT DETECTOR N/C
+
-
PIR MOVEMENT DETECTOR
CONTROL PANEL PA
24 Hr
1
2
5
4
3
6
7
8
TAMP
-
+
+13V
+
0V
-
STROBE
T A SCB
D B BELL
N/C
+
-
24 Hr
SET
GREEN
WHITE
WHITE
GREEN
BLACK
BLACK
RED
RED
YELLOW
BLUE
BLUE
YELLOW
Twist (or Solder) cable cores together and insulate
GREEN
WHITE
WHITE
GREEN
YELLOW
BLUE
BLUE
YELLOW
Wiring diagram with Zones 1 - 4 used with all cables returning to the Control Panel
MAGNETIC CONTACT
MAGNETIC CONTACT
CONTROL PANEL Note: For clarity not all terminals are shown.
Twist (or Solder) cable cores together and insulate
PA
YELLOW
YELLOW BLUE
Zone Wiring from Detector 1
YELLOW BLUE
Zone Wiring from Detector 2
4
3
2
1
BLUE
-
+
+13V
WHITE
Zone Wiring from Detector 3
WHITE GREEN
Zone Wiring from Detector 4
Twist (or Solder) cable cores together and insulate
0V
GREEN
YELLOW BLUE
Series wiring of zone connections from multiple detectors on a single zone
PA6/PA8 Alarm
TAMP
"24-Hour" Wiring from Detector 1
WHITE GREEN
"24-Hour" Wiring from Detector 2
WHITE GREEN
"24-Hour" Wiring from Detector 3
WHITE GREEN
"24-Hour" Wiring from Detector 4
"24-Hour" Wiring from Siren Tamper Connections
Series wiring 24-hour connections from multiple detectors
13
INSTALLATION
Wiring diagram with multiple detectors on a different zones with all cables returning to the Control Panel
3. The PIR detector incorporates an anti false alarm feature
Slowly walk across the PIR Movement Detector’s field of
designed to compensate for situations where the detector
view. As you are detected, the LED on the PIR Movement
may be affected by environmental changes, (e.g. insects,
Detector will illuminate, the Control Panel will bleep and
air temperature, etc). This feature is called "Pulse Count"
the relevant Zone LED will illuminate.
and may be selected for 1, 2 or 3 pulse detection.
3. When clear of the detector, the bleep will cease and the
The factory default and recommended setting is for
PIR Movement Detector LEDs will extinguish. The Zone
2 Pulse detection. However, in cases of extreme
LED will remain illuminated.
environmental problems, or if unattributable false alarms are experienced, it may be necessary to set "Pulse Count" 3.
again to confirm that the PIR Movement Detector gives the desired protection within the area required.
Note: The higher the Pulse Count the more movement will be necessary before the PIR detector will trigger the alarm. 3 Pulses
2 Pulses
1 Pulse
4. Allow ten seconds for the detector to settle, then move
5. Repeat the above test sequence for each PIR Movement Detector fitted. 6. When all the PIR Movement Detectors have been
INSTALLATION
1 2 3
1 2 3
tested successfully, press
1 2 3
RESET
3 times to return to
the Standby Mode.
Pulse Count Jumper Link Positions 4. Select the required ‘Pulse Count’, . Refit the cover and tighten the retaining screw. The PIR Movement Detector
7. Disconnect the Back-up Battery and mains supply before continuing with the installation.
is now ready to be connected at the Control Panel. 5. Bring the detector cable(s) through the cable entry slot in
SIMPLE TROUBLE SHOOTING
the rear of the Control Panel and strip back 5mm of each core and twist the strand ends. 6. Ensure that the mains power is switched off and the Backup Battery is disconnected at the Control Panel. Remove
If the PIR Movement Detector is not operating, i.e. LED not illuminating, the following simple checks should be carried out; 1. Allow 4 minutes for the detector to stabilise then retest.
the appropriate wire links and then connect the wires to the terminals as shown in the diagrams on pages 12-13. 7. When the wiring has been completed, re-connect the system power and Enter
0
1
2
3
to
reset the Control Panel. 8. Wait 4 minutes for the PIR detectors to stabilise. The
2. If the PIR Movement Detector LED does not illuminate, check the power supply to the PIR Movement Detector. Check for a damaged cable or poor termination. 3. If the PIR Movement Detector false alarms, the unit may be positioned incorrectly. Re-position the unit and adjust the ‘Pulse Count’ if necessary.
‘Day’ LED should be illuminated on the Control Panel. No Zone or Tamper LEDs should be illuminated at this stage. If any Zone or Tamper LEDs are ON, refer to
4. If the PIR Movement Detector LED is operating, but not activating an alarm, check that the relevant Zone wire link has been removed at the Control Panel.
Trouble Shooting.
TESTING THE PIR MOVEMENT DETECTORS AT THE CONTROL PANEL 1. Test the PIR Movement Detectors one at a time. Important:
When testing a PIR Movement Detector,
The Magnetic Contact comprises two parts; a Magnetic
ensure that no movement occurs in any other area
Contact Switch and a Magnet. They are designed to be
protected by PIR Movement Detectors.
fitted to either doors or windows with the Magnet screwed to
2. Set the Control Panel into ‘Walk Test’ by entering PROG
14
INSTALLING THE MAGNETIC CONTACTS
,
0
1
2
3 ,
0 ,
5
the moving/opening part and the Contact Switch screwed to the fixed frame.
When the protected door or window is
closed the Contact Switch is held closed by the magnetic
All Zone LEDs will extinguish, the Attack, Tamper and
field from the Magnet.
Day LED’s will be illuminated.
window will remove the magnetic field and allow the Contact
Opening the protected door or
PA6/PA8 Alarm
Switch to open generating an alarm signal at the Control Panel, (if the system is armed).
WIRING THE MAGNETIC CONTACTS 1. Remove one of the cable entry cut-outs on the Contact Switch and thread the cable through the entry into the
Cable Entry Knockouts
Contact Switch housing.
Spare Terminals Reed Switch
Magnetic Contact Terminals
2. Carefully remove the outer sheath of the cable and then strip 5mm of insulation from the Yellow and Blue wires.
Magnet Spare Terminal
Connect the Yellow and Blue wires to the Contact Switch terminals as shown.
Cable Entry Knockouts CONTACT SWITCH
MAGNET
YELLOW
The Magnetic Contact Sets supplied with this kit are suitable for mounting in dry interior locations only.
BLUE
SINGLE CONTACT
WHITE
Decide which doors and windows are to be protected by
GREEN
will have Magnetic Contact Switches fitted. Additional contacts
3. Strip off 5 mm of the insulation from the Green and White
may be fitted where required to other more vulnerable doors or
wires and connect together using a spare terminal in the
windows, e.g. garage, patio and conservatory doors etc.
contact housing.
Note: It is not recommended to connect more than 10
Note: If the spare contact terminals are not presant in
Magnetic Contacts in any one zone, as this may cause
the contact then the ends of the wires should be securely
difficulty in wiring and hinder any attempt to efficiently remedy
twisted (or soldered) together and insulated.
any wiring faults and locate the device that initiated the alarm. 1. Having chosen a suitable position to locate the Magnetic Contact, run the required length of 6 core cable back to
If connecting multiple contacts the Tamper circuit wiring should be continued in a series loop in a similar way to the zone wiring.
the Control Panel. 4. The remaining wires should be trimmed back and Alternatively, Magnetic Contact(s) may be wired in series with each other and terminated appropriately.
insulated to prevent short circuits and then tucked away in the Contact Switch housing.
Do not make any connections at this stage. 2. Fit the Magnet to the moving part of the window or door
MULTIPLE CONTACTS Wired in series
(on the opening edge opposite the hinge) and make sure that the parallel gap to where the Reed Switch on the frame will be fitted is no more than 9 mm. Magnet
Contact Switch
Magnet
Contact Switch
Note: If spare terminals are not present in the Contact Switch, ends of wires should be twisted (or soldered) together and insulated.
GREEN WHITE
BLUE
YELLOW
Door Mounting
Window Mounting
5. Fix the Contact Switch to the fixed part of the door/ Max Gap 9mm
window frame immediately beside and parallel to the
(door/window closed)
Magnet using two 25mm Counter-sunk fixing screws. Ensure that the parallel gap between the Magnet and
Typical position of contact fitted to door
PA6/PA8 Alarm
Contact Switch positions is no greater than 9mm.
15
INSTALLATION
Magnetic Contact switches; usually the front and back doors
6. Bring the contact cable(s) through the cable entry slot in the rear of the Control Panel and strip back 5mm of each core and twist the strand ends.
visible and at a height that is relatively inaccessible to an intruder. Consideration should also be given to the cable route to
7. Ensure that the mains power is switched off and the Backup Battery is disconnected at the Control Panel. Remove the appropriate wire links and then connect the wires to the terminals as shown in the diagrams on pages 12-13.
0
1
2
3
external wall directly into the back of the siren housing. The external weatherproof housing contains the Siren Tamper Unit and Strobe and is protected against deliberate
8. When the wiring has been completed, re-connect the system power and Enter
the Siren, with the cable preferably passing through the
to
reset the Control Panel.
interference by means of an anti-tamper switch. In the event of the cover being removed, or if the unit is removed from the wall, the Control Panel sounder will activate. However, if the
9. Wait 4 minutes for any PIR detectors to stabilise. The ‘Day’ LED should be ON at the Control Panel.
system is armed at the time, a full alarm will occur. If the cable is cut or the power to the Siren interrupted, the Siren &
INSTALLATION
Strobe’s integral battery will immediately sound the Siren. No Zone or Tamper LEDs should be illuminated at the
The integral battery is automatically trickle charged to full
Control Panel at this stage.
capacity when connected to the Control Panel.
TESTING MAGNETIC CONTACTS AT THE CONTROL PANEL 1. First, ensure that all doors and windows fitted with Magnetic Contacts are closed.
Note: To comply with local Noise Abatement Legislation, the Siren Unit incorporates a cut off timer, to ensure that the Siren will only operate for a maximum of 20 minutes. However, this time may be reduced to 3 minutes by cutting a small link on the Siren Unit.
2. Set the Control Panel into ‘Walk Test’ by entering PROG
,
0
1
2
3
,
0 ,
5
All Zone LEDs will extinguish, the Attack, Tamper and Day LED’s will be illuminated. Note: At this stage, if contacts are open or PIR Movement Detectors are activated, the relevant Zone LED(s) will be ON and the panel will bleep. You should ensure that no movement occurs in areas fitted with PIR Movement Detectors, as this may cause confusion during the test sequence. If walking past a PIR is unavoidable, allow 10 seconds at the Control Panel for the PIR to settle.
MOUNTING THE EXTERNAL SIREN & STROBE ENCLOSURE IMPORTANT:
If ladders are required to reach the
mounting position of the Siren they should be positioned on a firm stable surface at the correct angle and suitably secured before use. 1. Undo the two front cover retaining screws and remove the front cover by sliding up and away from the backplate. 2. Run the required length of cable from the Control Panel to the External Siren & Strobe position. Drill a
Open the first contact, the Control Panel will bleep and the
hole directly through the wall so that the cable enters
relevant Zone LED will illuminate. Close the contact to
through the rear of the housing without showing on
silence the alarm. The Zone LED will remain illuminated.
the outside of the property.
3. Repeat the above test sequence for each Magnetic Contact Fitted fitted. 4. When the contacts have been tested successfully, press RESET
3 times to return to the Standby Mode.
5. Disconnect the Back-up Battery and mains supply before continuing with the installation.
3. Hold the backplate in position so that the hole drilled for the cable is aligned with the cable entry aperture. Mark the positions of the four mounting holes. A spirit level placed on the casing will ensure a perfect level. 4. Mount the backplate using four 35mm No.8 screws and 30mm wall plugs as required, (a 6mm hole will be required for the wall plugs).
INSTALLING THE EXTERNAL SIREN & STROBE The External Siren & Strobe should be fitted to the outside of the building in a prominent position that is clearly
16
WIRING THE SIREN & STROBE UNIT 1. Ensure that the mains power is switched off and the Back-up Battery is disconnected at the Control Panel. 2. Strip back 5mm off all cable strands.
PA6/PA8 Alarm
3. Remove the temporary wire link from terminals 15
If the Siren still cannot be silenced the Control Panel
(TAMP) and "A" and the factory wire link from SCB
Back-up Battery may be discharged. Connect the Control
Terminals T and A.
Panel to the mains power, this will silence the Siren and
4. Twist and double over the end of each cable, then connect to the terminal blocks in the Siren & Strobe and
recharge the Control Panel Back-up Battery. If the Siren continues to sound the wiring should be re-checked. If the Siren will not silence after performing these checks,
Control Panel as shown.
contact the Helpline for advice. + STROBE
T A SCB
7. Replace the external siren cover
D B BELL SET
Cut Link for 3 minute Alarm Time
BLACK
RED GREEN WHITE
A D +
B SW T RETURN
Tamper Switch
CONNECTING THE CONTROL PANEL MAINS SUPPLY WARNING - ELECTRICITY CAN KILL! The mains supply to this product should be installed by a competent person (e.g. a qualified electrician) in accordance with the instructions contained with the product and in
Fit BATT Link once unit is connected
accordance with the appropriate clauses of the current edition of the IEE wiring regulations (BS7671).
BLUE YELLOW
The mains supply to the alarm Control Panel should be taken from a dedicated circuit from the mains consumer unit
Siren PCB
and should be protected by a 3A Fuse or MCB, (the circuit Siren
must not be protected by an earth leakage circuit breaker,
Siren & Strobe Wiring
RCD or RCBO). The mains supply should be fed via an unswitched, fused connection unit (fitted with a 3A fuse)
5. Connect the Control Panel Back-up Battery - the Control
located close to the Control Panel.
Panel and Siren will sound on ‘Tamper’ and the strobe The alarm should not be connected to other domestic
will operate.
electrical ring main circuits, as electrical interference from Enter
0
1
2
3
to silence the alarm.
After a few seconds the Control Panel alarm will sound on Tamper and the strobe will operate, (as the cover is off and the tamper switch override has been removed). Enter
0
1
2
3
to silence the alarm.
6. At the siren housing, connect the battery link to both ‘BATT’ terminals.
other appliances (e.g. fridge/washing machine) may cause the Control Panel microprocessor to malfunction. 1. Connect the connection unit to the Control Panel using 5A rated 3 core flex and connect to the mains terminal block as follows: Live (L)
Brown
Neutral (N)
Blue
Earth (E)
Green/Yellow
Note: Ear protection is recommended to be worn during this operation as the Siren could activate in close
Alternatively if the supply to the Control Panel from the
proximity to the user.
connection unit is provided by permanent wiring through conduit, 1mm Twin & Earth cable should be used. Connect
IMPORTANT: When the ‘BATT’ link is fitted, the Siren
the cables to the mains terminal block as follows:
should not activate. If the Siren does activate, it is possible that the Siren & Strobe fuse is blown or the
UK installations prior to Apr2004.
wiring is incorrect. Remove the ‘BATT’ link and check
Live (L)
Red
fuse ‘Bell/Strobe/13V’ at the Control Panel. Correct the
Neutral (N)
Black
wiring fault and/or replace the fuse if blown, then return
Earth (E)
Green/Yellow sleeved bare central copper conductor
to the siren, replace the ‘BATT’ link.
PA6/PA8 Alarm
17
INSTALLATION
Control Panel Terminals
In all other areas of the EU and in new build installation
e.g. 10 seconds ÷ 10 = 1, so enter 01
in the UK after April 2004 the following colour code for
10 seconds = 01,
twin & Earth cable may also be used.
20 seconds = 02,
Live (L)
Brown
Neutral (N)
Blue
Earth (E)
Green/Yellow sleeved bare central copper conductor
30 seconds = 03 etc. On entering the 2 digits, the Control Panel will emit a series of short beeps and the system will return to Programming Mode.
2. The Control Panel fixing screws may now be fully tightened. 3. Fit the Control Panel Back-up Battery to the charging leads. Enter
0
1
2
3 to silence the alarm.
ENTRY TIMER Default 30 seconds Maximum setting = 990 seconds
Remember to remove the wire over-riding the Control Press
Panel’s anti tamper switch if it is still fitted.
2
The ‘Attack’, Zone 1 and Zone 2 LEDs illuminate. 4. Refit the Control Panel front casing and secure with the two cover fixing screws.
Enter the required time as for Exit Timer above. On entering the 2 digits, the Control Panel will emit
5. Switch on the mains supply. The red ‘Power’ LED will illuminate.
a series of short beeps and the system will return to Programming Mode.
The Control Panel Back-up Battery will be recharged to
ALARM DURATION
full capacity after approximately 14 hours.
Factory default 20 minutes
Note: Although optional, it is strongly recommended that a backup battery is fitted.
Maximum setting = 99 minutes Press
3
PROGRAMMING
The Attack, Zone 1 and Zone 2 LEDs illuminate.
PROGRAMMING
Enter the required time in minutes.
GENERAL
00 = continuous internal sounder operation.
Follow the instructions below to change any of the Programmable
On entering the 2 digits, the Control Panel will emit
Options.
a series of short beeps and the system will return to
01 = 1 minute, 20 = 20 minutes, 99 = 99 minutes
Before you begin, check that the system is in
Standby Mode with the green ‘Day’ LED showing. Once you
Programming Mode.
are in Programming Mode, any section may be changed in
Note: Following activation into alarm condition the External
any order. Once you have finished exit from the Programming
Siren will continue to sound until either the Control Panel is
Mode and check that the system is back in Standby Mode.
Reset; or the Control Panel Alarm Duration Time expires; or
TO ENTER PROGRAMMING MODE FROM STANDBY MODE ‘Day’ LED is ON Press
expires; whichever occurs first.
MAIN USER ACCESS CODE
PROG
Factory default 0123
All Zone LEDs illuminate. Enter the Installer Access Code
until the External Siren Alarm Duration Time (3 or 20 minutes)
9
9
9
The ‘Tamper’ LED only is illuminated. The system is now in Programming Mode
9
Press
8
The ‘Attack’ and Zone 1 - 4 LEDs will illuminate. Enter new code 4 digit code. On entering the 4 digits, the Control Panel will emit
EXIT TIMER Factory default 30 seconds
a series of short beeps and the system will return to Programming Mode.
Maximum setting = 990 seconds. Press
18
1
SECOND USER ACCESS CODE
The ‘Attack’, Zone 1 and Zone 2 LEDs illuminate.
Factory default - not programmed
Enter the required time in 10 second increments, divided by 10.
Press
7
The ‘Attack’ and Zone 1 - 4 LEDs will illuminate.
PA6/PA8 Alarm
Zone number as required to select (Zone LED ON) or de-
Enter new code 4 digit code. To remove the code from the system press
OMIT
.
On entering the 4 digits, the Control Panel will emit a series of short beeps and the system returns to Programming Mode.
INSTALLER ACCESS CODE Factory default 9999 Press
select (LED OFF) the Zones. Press
0
Press
RESET
to de-select all Zones. to complete the set up of used Zones.
TIMED ENTRY/EXIT ZONES Press
2
to display the Timed Entry/Exit Zones - key
in each Zone number as required to select (Zone LED
9
ON) or de-select (LED OFF) the Zones.
The ‘Attack’ and Zone 1 - 4 LEDs will illuminate. Enter new code 4 digit code.
Press
0
to de-select all Zones.
Note: Only zones already setup as Active may be
On entering the 4 digits, the Control Panel will emit a series of short beeps and the system will return to Programming Mode.
configured as Timed Entry/Exit zones. Press
RESET
to complete the set up of Timed Entry/Exit
Zones.
OMIT PREVENT ZONES Factory default - none
WALK THROUGH ZONES
Press
Press
OMIT
After a few seconds the illuminated Zone LEDs will show the Zones currently set up as OMIT PREVENTED. Key in each Zone number to select or de-select the Zone
3
to display the Walk Through Zones - key
in each Zone number as required to select (Zone LED ON) or de-select (LED OFF) the zones as Walk Through. Press
0
to de-select all Zones.
as OMIT PREVENT. Enter the number of the zone to be
Note: Only zones already setup as Active may be
configured as OMIT PREVENTED. To re-enable a zone
configured as Walk Through zones.
so that it can be omitted during arming re-enter its
Press
number and the zone LED will turn OFF.
Zones.
0
Press
RESET
to de-select all Zones. to return to Programming Mode.
EXIT MODE Press
PROGRAM AND ZONE SET UP Factory defaults:Program 1
to complete the set up of Walk Through
Zone 1 Zone 2 Zone 3 - 6 Exit Mode
Program 2
Disabled
Program 3
Disabled
-
Timed Entry/Exit Walk Through Instant Timed
Important Notes:
6
to display the Exit Mode.
Select the Exit Mode by pressing the appropriate key. Press
0
program disabled
No LEDs illuminated
Press
1
Timed Exit
Zone 1 LED illuminated
Press
2
Final Door Set
Zone 2 LED illuminated
Press
3
Immediate Set
Zone 3 LED illuminated
Press
RESET
to complete the Exit Mode set up. As the
set up of the Zone types or Exit Mode is completed, the program number will be displayed by a flashing
1. Instant Zones are set up by making the Zone used
Zone LED.
but not Entry/Exit Timed or Walk Through. 2. The Exit Mode cannot be set up if there are no used Zones in the program.
Press
RESET
once to return to the 3 flashing Zone LEDs
and select a different program, or twice to return to the Programming Mode.
3. Programs which are not given an EXIT type are disabled. Press
TO EXIT FROM PROGRAMMING MODE
PROG
The ‘Attack’ LED will illuminate and Zone LEDs 1, 2
The ‘Tamper’ LED should be ON.
and 3 flash.
Press
Press
1 ,
2
or
3
RESET
, the system will return to Standby Mode
with the ‘Day’ LED ON.
The Day LED will illuminate and the program number selected will be displayed by a flashing Zone LED.
RESET TO FACTORY SET DEFAULT CONDITIONS.
ACTIVE ZONES
Should you need to reset the Control Panel to the factory
Press
default program settings, proceed as follows:-
1
to display the active Zones - key in each
PA6/PA8 Alarm
19
PROGRAMMING
Press
RESET
From Programming Mode with the ‘Tamper’ LED ON. Press
SET
twice. The system will return to Standby
Mode with all factory set conditions re-installed.
The Day and all Zone LEDs only are illuminated Enter User Access Code
0
2
1
3
Tamper LED only is illuminated
The Control Panel will emit a series of short beeps
Press
and the system will remain in Programming Mode
0
‘Tamper’ and ‘Attack’ LEDs only are illuminated.
with all factory set conditions re-installed.
The system is now in the Test routine
NON-VOLATILE MEMORY (NVM) RESET If the Installer Access Code has been lost or forgotten or in
Press
2
to test the Strobe
Press
0
to stop
return to factory set conditions. Before beginning check that the
Press
3
to test the External Siren
system is in Standby Mode with the green ‘Day’ LED showing.
Press
0
to stop
1. Switch OFF the mains supply and then remove the lower
Press
4
to test low volume internal sounder
Press
0
to stop
Note: The External Siren will sound on it’s Back-up
Press
2 ,
Battery until power is restored.
The strobe will also be operated during this test.
extreme circumstances where a software crash has occurred, it will be necessary to clear the Non-Volatile Memory (NVM) and
front cover of the Control Panel. If fitted disconnect the backup battery.
2. Remove all wires from terminals 13 (PA) and 27 (SET+) and fit a temporary wire link between these two terminals. 3. Temporarily restore power to the Control Panel by either reconnecting the backup battery or switching ON the mains supply.
1
to test high volume internal sounder
Press
0
to stop
Press
5
to enter Walk Test
During Walk Test the internal sounder will bleep and the respective Zone LED will illuminate as each circuit is tested. The Zone LED will remain illuminated after the zone has
The system will now power-up in an alarm condition. Press
0
4
2
3
been triggered until reset by leaving Walk Test mode.
(or the current User Access Code)
to silence the alarm.
Press
0
The Memory will now be cleared and all program settings
Press
RESET
reset to their factory default setting.
Standby Mode with only the ‘Day’ LED illuminated.
to stop RESET
to exit Test routine and return to
4. Switch OFF the mains supply and disconnect the backup battery. 5. Remove the temporary wire link between terminals 13 (PA) and 27 (SET+) and reconnect the wires originally
For clarity, the information below on Setting the System,
connected to these terminals in position.
assumes that all programs use a Timed or Final Door
6. Reconnect
0
1
the
2
silence the alarm.
backup
battery
and
press
3 (the default User Access Code) to Refit the lower front cover of the
Control Panel and switch ON the mains supply. 7. The system may now be reprogrammed and tested using
OPERATION
OPERATING INSTRUCTIONS
the Factory Default User and Installer Access Codes.
Setting routine.
TO ARM THE SYSTEM (on Program 1) The green ‘Day’ LED should be ON. Enter the User Access Code and check that the system is clear (ALL of the Zone LEDs are OFF). The sounder will now produce an exit bleep tone and you should leave by the Entry/Exit route.
The
system will set as the tone stops.
TESTING THE SYSTEM The Control Panel has a programmed test routine. You may test the system at any time, however it is recommended that the system is tested at regular intervals not exceeding 3 months. With the Control Panel in Standby Mode (‘Day’ LED ON). Press
20
PROG
TO SET A PROGRAM The green ‘Day’ LED should be ON. Enter your User Access Code and the Exit tone will start. Press
PROG
and the exit
tone will stop. Press
1 ,
2
or
3
for the required program, the
sounder will bleep to acknowledge the program number.
PA6/PA8 Alarm
The Exit tone will start and you should leave by the
Press
Entry/Exit route. The system will set as the tone stops.
imately 10 seconds the system will automatically return the
It is important that you follow the correct procedure when
0
to cancel all Zones from chime. After approx-
system to Standby Mode.
setting the system. After leaving the protected area it is
Note: Pressing RESET will immediately return the system
absolutely essential that you wait until the exit tone stops,
to Standby mode.
before assuming the system has set.
AUTO RESET AND RE-ARM FAULTS DURING SETTING
In alarm condition the sounders will operate for the
If the system is not clear when you try to set it, the Control
programmed alarm duration. The sounders will then shut
Panel will produce an open Zone tone and the zone LEDs of
down but the Strobe will continue to operate.
the responsible zones will be illuminated. Either re-enter your User Access Code to turn off and investigate or omit the faulty Zones(s) from the system.
Each Zone is then checked and if clear will be re-armed. Any circuit in fault condition will be automatically omitted.
DAY LED
TO OMIT A ZONE During the exit period (after entering your User Access Code and/or selecting a program) press
OMIT
, the Exit tone will
stop and the zone LEDs will be illuminated to indicate which zones are about to be armed and which are to be omitted.
In Standby Mode the ‘Day’ LED on the Control Panel and Remote Keypad should be illuminated.
POWER LED The red ‘Power’ LED on the Control Panel and Remote Control
Constant LED
Zone to be armed
Keypad should be illuminated at all times. If the LED goes off,
Flashing LED
Zone to be omitted
the mains supply has failed or has been disconnected.
Enter the number of the zone to be omitted and the
In the event of a power failure, the Back-up Battery (if fitted)
corresponding zone LED will flash to confirm the entry. To
will maintain system operation for a period of up to 7 hours in
re-admit a zone enter its number and the zone LED will stop
Standby, assuming the battery is fully charged and in good
flashing. When the selection is complete press
condition. However if the system is armed or extra PIRs are
SET
and
the Exit tone will start
connected, the battery life will be significantly reduced.
If a Zone refuses to be omitted, it may be because it has been programmed so it cannot be omitted (Refer to Programming
FAULTS/PROBLEMS If any faults occur, or if any fault LEDs remain on, refer to
‘Omit Prevent’ for details).
Trouble Shooting.
QUICK SET During the Exit period (after entering your User Access Code) the system may be set quickly by pressing
SET
. This
removes the time period usually allowed for exit and would be used if you are not leaving the premises. If you omit Zones and require Quick Set, you will need to press
SET
twice.
ALARM MEMORY RECALL The Control Panel will memorise the last 8 alarm conditions. To view these:Press
PROG
All Zone LEDs will illuminate. Enter your User Access Code
0
1
2
3 .
Tamper LED only is illuminated Enter your User Access Code. If the system has not been triggered, the green ‘Day’ LED only will illuminate. If the system has been triggered, then entering the code will turn the alarm OFF and the LED of the zone which triggered the alarm to be illuminated. Make a note of the Zone indicated
Press
CHIME
.
The Panel will scroll through the last 8 alarm conditions, (starting with the most recent) illuminating the Zone LED responsible for triggering that alarm condition. As each new condition is displayed the panel sounder will bleep.
to assist in tracing the cause of the alarm, before pressing
Press
1
to view the most recent (newest) event
to clear the indication and return the system to standby.
Press
2
to view the previous event
Press
8
to view the oldest event
Press
RESET
RESET
CHIME Any Zone may set to be on or off chime by pressing the CHIME
key and then keying in the required Zone number(s).
PA6/PA8 Alarm
to stop the memory recall or wait for the
scrolling to stop automatically
21
OPERATION
TO DISARM (UNSET) THE SYSTEM
Press
RESET
again to return the system to Standby Mode
with the ‘Day’ LED illuminated.
will be damaged if stored in a discharged state. At the end of its useful life the Rechargeable Battery should be
Note 1: If the ‘Day’ LED shows in any of the alarm events,
disposed of via a suitable Recycling Centre. Do not dispose
that alarm condition occurred in the Standby Mode.
of with your normal household waste. DO NOT BURN.
Note 2: If the alarm event shows as a blank display then
The Rechargeable Battery contains Sulphuric Acid - DO NOT
that event is ‘Empty’.
attempt to open the casing. The External Siren/Tamper Unit incorporates an integral Rechargeable Battery which has a typical life of 7-10 years and
MAINTENANCE
requires no maintenance.
Your Alarm System requires very little maintenance. However, a few simple tasks will ensure its continued
CONTROL PANEL FUSES The Control Panel contains 4 fuses to protect the circuit wiring.
reliability and operation.
Should a fuse blow, the cause must be established, and the
CONTROL PANEL, KEYPAD & DETECTORS
fault rectified before it is replaced.
The Control Panel, Remote Keypad and Detectors require
replaced with a fuse of the correct type and rating as follows:
Fuses should only be
no maintenance. If cleaning is required, wipe the outside FUSE REF.
REF NO.
TYPE
Bell/Strobe/13V
1.0A
20mm Quick Blow (type F)
Battery
1.6A
20mm Quick Blow (type F)
RECHARGEABLE BATTERIES
Remote Keypad
1.0A
20mm Quick Blow (type F)
The Control Panel Rechargeable Back-up Battery has a
Mains Input Fuse 125mA, 250V
of the casings with a soft damp cloth. Do not use abrasive, solvent based or aerosol cleaners. Do not attempt to clean inside the units or allow water to enter the units.
typical life of 3-4 years and needs no maintenance during this period provided the battery is kept charged. The battery
20mm Anti-Surge (type T) approved to IEC60127, part 2 sheet III.
ALARM RECORD Complete the following information during installation for future reference when adding to your system and to assist Trouble Shooting.
Zone
Detector Type(s)
Location(s)
Settings per Program Instant/Timed/Walk Through/Omitted
Prog 1
Prog 2
Prog 3
1 2 3 4 5
OPERATION
6 PA
PA Button(s)
N/A
You may make a note of your User Access Codes and Installer Access Code below. User Access Codes
Installer Access Code
Purchase Date/Installation Date
This information is highly confidential and should be kept in a very safe location.
22
PA6/PA8 Alarm
TROUBLE SHOOTING Important Note: For safety reasons, switch off the mains supply to the Control Panel before carrying out fault finding. Fault finding should be carried out with the system powered by the Back-up Battery only.
Symptom
/ Recommendation
Symptom
/ Recommendation
Tamper fault (Internal Sounder and External Strobe operating or full alarm if system is armed).
Magnetic Contacts not operating.
1. Control Panel or Keypad Anti-Tamper Switch not closed fully - check/refit panel covers.
2. Check that gap between Magnet and Switch Contact blocks with the door/window is open is greater than 9mm.
2. PIR Detector Anti-Tamper Switch not closed fully check/refit detector cover. 3. External Siren Anti-Tamper Switch not closed fully adjust Siren Anti-Tamper Switch and check/refit Siren cover. 4. Tamper Zone wiring open circuit, damaged, incorrectly wired or poorly terminated.
Passive Infra-Red Movement Detector not detecting a person’s movement. 1. Allow 4 minutes for the detector to settle down and retest. 2. ‘Pulse Count’ set too high - reset to one or two ‘Pulse Count’ detection. 3. Ensure that detector is mounted the correct way up (i.e. with the cover fixing screw at the bottom). 4. Ensure that the detector is mounted at the correct height (2.2 m from floor). 5. Check that the detector is correctly wired. 6. Check/replace fuse ‘Bell/Strobe/13V’ in Control Panel
Passive Infra-Red Movement Detector false alarming. 1. Ensure that the detector is not pointing at a source of heat or a moving object. 2. Ensure that the detector is not mounted above a radiator or heater. 3. Ensure that the detector is not facing a window or in direct sunlight. 4. Check Zone wiring to detector alarm contacts. 5. ‘Pulse Count’ set too low - reset to two or three ‘Pulse Count’ detection.
1. Check that gap between Magnet and Switch Contact blocks is less than 9mm.
3. Check Zone wiring to contacts. (All contacts on a Zone must be wired in ‘Series’).
External Siren Sounding continuously (Tamper LED NOT illuminated). 1. Check for incorrect wiring to External Siren. 2. Check for short-circuits in cable to Siren, causing Siren to be permanently energised. 3. Check/replace fuse ‘Bell/Strobe/13V’. 4. Check mains supply is healthy and that Back-up Battery has not run low due to mains failure. 5. Check power supply to External Siren - check Siren cable for cuts and terminations for security.
False Alarms when the system is Armed. 1. Carefully note the Zone which activated the alarm before resetting the system. Only the detector(s) and wiring on that Zone will need to be checked. 2. Check all Zone wiring and connections for security. 3. For PIR false alarms, consider increasing ‘Pulse Count’ setting on suspect detector.
Mains LED is not illuminated. 1. Check mains input fuse in Connection Unit. 2. Check mains input fuse in Control Panel. 3. Check fuse/MCB in Consumer Unit on the circuit serving the Control Panel. Note: Before replacing any fuses or resetting the MCB, the cause of the failure should be investigated and rectified. 4. Mains power failure - check if other electrical circuits are operable.
Magnetic Contacts false alarming. 1. Check that door/window closes firmly and that movement cannot trigger the contacts. 2. Check that gap between Magnet and Switch Contact blocks with the door/window closed is less than 9mm.
PA6/PA8 Alarm
IMPORTANT: To prevent the risk of electrocution, it is essential to turn OFF the mains electricity supply before commencing work within the Control Panel or on the the mains supply wiring. If in doubt, consult a qualified electrician. continued overpage
23
TROUBLE SHOOTING Symptom
/ Recommendation
External Strobe operating continuously. 1. Strobe will continue to operate after an alarm activation until system is RESET at the Control Panel. CHECK THE SECURITY OF THE PROPERTY BEFORE ENTERING. 2. Tamper fault. Alarm panel will also emit a warning tone. The Strobe will continue to flash until the Tamper fault is located and corrected.
HELPLINE If you have a problem with your alarm, please call the helpline on:
Symptom
Continued
/ Recommendation
Detection Zone has been triggered but no alarm is sounding. 1. Entry Delay Zone(s) triggered - alarm will sound when the Entry Delay Time expires. 2. Zone omitted on a ‘PROGRAM’ setting. 3. Zone temporarily omitted before arming.
01268 563273 (Lines open 9.00am to 5.00pm, Monday to Friday)
EXTENDING YOUR PA6/PA8 WIRED INTRUDER ALARM SYSTEM Your system may be expanded to give additional protection by adding additional PIR Movement Detectors and Magnetic Contact Sets.
ACCESSORY PACK - PU1 The PU1 Accessory Pack comprises 2 PIR Movement Detectors, 2 Magnetic Contact Sets and approximately 25m of 6 Core Cable.
PU1
PASSIVE INFRA-RED MOVEMENT DETECTORS (TWIN PACK) - PU2 2 additional PIR Movement Detectors. PU2
12V 1.2 Ahr RECHARGEABLE BACK-UP BATTERY - BUB 12/1.2 (or BUB) WP12.1-6
DUMMY SIREN - PU3
BUB 12/1.2 (or BUB)
Siren box for added visual deterant. PU3
24
PA6/PA8 Alarm
If you have a problem with your Alarm, please call the Helpline on:
01268 563273 (Lines open 9.00am to 5.00pm, Monday to Friday).
GUARANTEE Novar ED&S undertakes to replace or repair at its discretion goods (excluding non rechargeable batteries) should they become defective within 1 year solely as a result of faulty materials and workmanship. Understandably if the product has not been installed, operated or maintained in accordance with the instructions, has not been used appropriately or if any attempt has been made to rectify, dismantle or alter the product in any way the guarantee will be invalidated. The guarantee states Novar ED&S entire liability. It does not extend to cover consequential loss or damage or installation costs arising from the defective product. This guarantee does not in any way affect the statutory or other rights of a consumer and applies to products installed within the UK and Eire only If If an item develops a fault, the product must be returned to the point of sale with: 1. Proof of purchase. 2. A full description of the fault. 3. All relevant batteries (disconnected). Friedland is a trade mark of Novar ED&S.
Friedland, Novar Electrical Devices and Systems The Arnold Centre, Paycocke Road Basildon, Essex SS14 3EA
PA6/PA8 - 6 Zone Wired Intruder Alarm System
Friedland
COMPONENT SPECIFICATION Control Panel Novar Electrical Devices and Systems are Quality Assurance Registered to BS EN ISO9001:2000, by Asta
External Siren & Strobe
Zones
0 1
2
3
4
5
1
2
3
4
Power
6
Attack Tamper
5
6
7
8
9
CHIME
OMIT
RESET
PROG
SET
Day
200 mm 350 mm 55
255 mm
mm
● 6 Detection Zones ● Tamper Zone
75
200 mm
● Personal Attack Zone ● Personal Attack facility
mm
● Case material yellow plastic
● Front Cover Anti-Tamper
● Dual front & rear Anti-Tamper
● 3 programs available
● 110dB Piezo Sounder
● Zone(s) programmable for
- Timed Entry Delay - Walk Through - Zone Omit ● Temporary Zone Omit facility ● Entry Delay variable 10 - 99 seconds ● Exit Delay variable 10 - 99 seconds ● Alarm duration variable 01 - 99 minutes
● Integral Back-up Battery ● Blue Lens ● Integral Strobe ● 3 or 20 minute alarm cutout limit
Magnetic Contacts
● Non-Volatile Memory ● Quick arm facility ● Chime facility ● Backlit Keypad
67
● Individual Zone alarm activation LEDs
mm
● Back-up Battery facilities (12V/1.2Ah) ● Hard-wired Siren output ● Separate strobe output (latching)
RESEARCH & DEVELOPMENT Our R & D Department is constantly developing new products. We practice a policy of continued improvement and reserve the right to change specifications without prior notice.
● 4-Digit Main User Access Code ● 4-Digit Second User Access Code
14
12
mm
● 4-Digit Installer Access Code
mm
● Magnetic Reed Switch operation
● Integral Mains Transformer
● Operating gap up to 9mm ● Door or window mounted
PIR Movement Detectors
● Surface mounting, white plastic finish
Remote Keypad 58
Zone 1
mm
Zone 2 Zone 3
0
1
2
3
4
5
6
7
8
9
Chime
Omit
Reset
Prog
Set
PA
Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Tamper
If you have a problem with your Alarm, please call the Helpline on:
82
mm
Attack
Day
68 mm
160 mm
Power
44
mm
● Detection range up to 12m at 90° field
of vision ● Integral LED ● 1, 2, 3 ‘Pulse Count’ facility
122 mm
25
mm
● Anti-Tamper
01268 563273 (Lines open 9.00am to 5.00pm, Monday to Friday).
● Corner or surface mount, with tilt facility ● 12 Vdc operated, powered from the
Control Panel
● Duplicates all operating and programming
functions of Control Panel Keypad ● Backlit Keypad ● Tamper protected ● Personal Attack facility
Friedland, Novar Electrical Devices and Systems. The Arnold Centre, Paycocke Road, Basildon, Essex SS14 3EA. UK. © Novar ED&S, 2004
45166PL Ed.4