VFS11 Parameter List for CPU version 108/109 Setting Date Customer End user Application Application No/Serial No
Inverter’s Type-Form Quantity Inverter’s Serial No Motor’s capacity If user’s setting value is same as shipping value, entry column is blank. -Terminal stand use state Terminal Name Main terminal block
PA/+ PB PC/PO R/L1 S/L2 T/L3 U/T1 V/T2 W/T3 E/G
Control terminal block
FLA FLB FLC RY RC CC VIA VIB PP FM F R RES S1 S2 S3 CC OUT NO P24
Setting of slide switch
VIA FM SW1
Use state
SOURCE
1
V V /
/ I / I PLC
/
SINK
E6581304②
1
User parameters
Title
Function
Unit
Operation frequency of operation panel
Hz
Minimum setting unit
Adjustment range
Panel/Communica
Default setting
User setting
Reference
tion
2
0.1/0.01
-
0.0
3.2
Basic parameters • Four automatic functions or basic parameters Minimum
Title
Communi cation No.
Function
Unit
setting unit Panel/Commu
Adjustment range
Default User setting setting
Reference
nication
-
History function
-
-
0000
Automatic acceleration/ deceleration
-
-
0001
Automatic torque boost
-
-
0040
Automatic function setting
-
-
Command mode selection Frequency setting mode selection 1
-
-
-
-
0003 0004
Displays parameters in groups of five in the reverse order to that in which their settings were changed. * (Possible to edit) 0: Disabled (manual) 1: Automatic 2: Automatic (only at acceleration) 0: Disabled 1: Automatic torque boost + auto-tuning 2: Vector control + auto-tuning 3: Energy saving + auto-tuning 0: Disabled 1: Coast stop 2: 3-wire operation 3: External input UP/DOWN setting 4: 4-20 mA current input operation 0: Terminal board 1: Operation panel 0: Built-in potentiometer 1: VIA 2: VIB 3: Operation panel 4: Serial communication 5: UP/DOWN from external contact 6: VIA + VIB (Override)
2
-
4.1.4
0
5.1.1
0
5.2
0
5.3
1
5.4
0
5.4 6.5.1
E6581304②
Title
Communic ation No.
0005
0006
0007
0008
Minimum Default User setting unit Function Unit Adjustment range Panel/Com setting setting munication 0 Meter selection 0:Output frequency 1:Output current 2:Set frequency 3:DC voltage 4:Output voltage command value 5:Input power 6:Output power 7:Torque 8:Torque current 9:Motor cumulative load factor 10:Inverter cumulative load factor 11:PBR (braking reactor) cumulative load factor 12:Frequency setting value (after PID) 13:VIA/II Input value 14:VIB Input value 15:Fixed output 1 (Output current: 100%) 16:Fixed output 2 (Output current: 50%) 17:Fixed output 3 (Other than the output current: 100%) 18:Serial communication data 19:For adjustments ( set value is displayed.) Meter adjustment 0 Default setting 0: 1: 50Hz default setting 2: 60Hz default setting 3: Default setting (Initialization) 4:Trip record clear 5:Cumulative operation time clear 6:Initialization of type information 7: Save user-defined parameters 8:Call user-defined parameters 9:Cumulative fan operation time record clears Forward/ 0: Forward run 0 reverse run 1: Reverse run selection 2: Forward run (Operation (F/R switching possible) panel) 3: Reverse run (F/R switching possible) 3
Reference
5.5
5.5 5.6
5.7
E6581304②
Title
Communic ation No.
0009
0010
0011
0012
0013
0014
0409
0015
0016 0600
0017
Function Acceleration time 1 Deceleration time 1 Maximum frequency Upper limit frequency
Minimum setting unit Unit Adjustment range Panel/Com munication s 0.1/0.1 0.0-3200
Default User setting setting
Reference
10.0
5.1.2
s
0.1/0.1
0.0-3200
10.0
5.1.2
Hz
0.1/0.01
30.0-500.0
80.0
5.8
Hz
0.1/0.01
0.5-
5.9
Lower limit frequency Base frequency 1
Hz
0.1/0.01
0.0-
50.0 (WP) 60.0 (WN, AN) 0.0
Hz
0.1/0.01
25-500.0
5.10
Base frequency voltage 1 V/F control mode selection 1
V
1/0.1
50.0 (WP) 60.0 (WN, AN) *3
−
−
% % (A)
0.1/0.1 1/1
-
-
Torque boost 1 Motor electronic-ther mal protection level 1 Electronicthermal protection characteristic selection *2
50-330 (200V class) 50-660 (400/600V class) 0: V/F constant 1: Variable torque 2: Automatic torque boost control 3: Vector control 4: Automatic energy-saving 5: Dynamic automatic energy-saving (for fans and pumps) 6: PM motor control 0.0-30.0 10-100
Set 0 1 2 3 4 5 6 7
OL protect on Standard on motor off off on on VF motor off off
OL stall off on off on off on off on
*1:Default values vary depending on the capacity. See the table of the last page *2:on:valid、off:invalid *3 : 230 (200V class), 460 (400V class), 575V (600V class)
4
5.9
5.10 6.13.6
2
5.11
*1 100
5.12 5.13 6.19.1
0
5.13
E6581304②
Title
Communic ation No.
0018
0019
0020
0021
0022
0023
0024
-
-
Function Preset-speed operation frequency 1 Preset-speed operation frequency 2 Preset-speed operation frequency 3 Preset-speed operation frequency 4 Preset-speed operation frequency 5 Preset-speed operation frequency 6 Preset-speed operation frequency 7 Extended parameters Automatic edit function
Minimum setting unit Unit Adjustment range Panel/Com munication Hz 0.1/0.01 -
Default setting
User setting
Reference
5.14
0.0
Hz
0.1/0.01
-
0.0
Hz
0.1/0.01
-
0.0
Hz
0.1/0.01
-
0.0
Hz
0.1/0.01
-
0.0
Hz
0.1/0.01
-
0.0
Hz
0.1/0.01
-
0.0
-
-
-
-
-
4.1.2
-
-
-
-
-
4.1.3
5
E6581304②
3
Extended parameters • Input/output parameters
Title
Communicati on No.
0100
0101
0102
0105
0108
0109
0110
0111
0112
0113
0114
0115
0116
0117
Function Low-speed signal output frequency Speed reach setting frequency Speed reach detection band Priority selection (Both F-CC and R-CC are ON) Always-active function selection 1 Analog/contact input function selection (VIA/VIB terminal)
Always-active function selection 2 Input terminal selection 1 (F) Input terminal selection 2 (R) Input terminal selection 3 (RES) Input terminal selection 4 (S1) Input terminal selection 5 (S2) Input terminal selection 6 (S3) Input terminal selection 7 (VIB)
Minimum setting unit Unit Adjustment range Panel/Com munication Hz 0.1/0.01 0.0-
Default User setting setting
Reference
0.0
6.1.1
Hz
0.1/0.01
0.0-
0.0
6.1.3
Hz
0.1/0.01
0.0-
2.5
6.1.2
-
-
0: Reverse 1: Slowdown Stop
1
6.2.1
-
-
0-65
0
6.3.1
-
-
0
6.2.2
-
-
0: VIA - analog input VIB - analog input 1: VIA - analog input VIB - contact input (Sink) 2: VIA - analog input VIB - contact input (Source) 3: VIA - contact input (Sink) VIB - contact input (Sink) 4: VIA - contact input(Source) VIB - contact input (Source) 0-65 (ST)
1
6.3.1
-
-
0-65 (F)
2
6.3.2
-
-
0-65 (R)
3
-
-
0-65 (RES)
10
-
-
0-65 (SS1)
6
-
-
0-65 (SS2)
7
-
-
0-65 (SS3)
8
-
-
5-17 (SS4)
9
6
E6581304②
Title
Communicati on No.
0118
0130
0131
0132
0137
0138
0139
0167
0170
Function Input terminal selection 8 (VIA) Output terminal selection 1A (RY-RC) Output terminal selection 2A (OUT-NO) Output terminal selection 3 (FL) Output terminal selection 1B (RY-RC) Output terminal selection 2B (OUT-NO) Output terminal logic selection (RY-RC, OUT-NO)
Frequency command agreement detection range Base frequency 2
Minimum setting unit Unit Adjustment range Panel/Com munication 5-17 (AD2)
Default User setting setting 5
6.3.2
6.3.3
-
-
0-255 (LOW)
4
-
-
0-255 (RCH)
6
-
-
0-255 (FL)
10
-
-
0-255 (always ON)
255
-
-
0-255 (always ON)
255
-
-
Hz
0.1/0.01
0: and and 1: or and 2: and or 3: or or 0.0-
Hz
0.1/0.01
25.0-500.0
0170
Base frequency Hz 1/0.1 50-330 (200V class) voltage 2 50-660 (400/600V class) 0172 Torque boost 2 % 0.1/0.1 0.0-30.0 Motor % 1/1 10-100 0173 electronic(A) thermal protection level 2 Stall prevention % 1/1 10-199 0185 level 2 (A) 200 (disabled) *1 : Default values vary depending on the capacity. See the table of last page *3 : 230 (200V class), 460 (400V class), 575 (600V class) 7
Reference
0
6.3.3
2.5
6.3.4
50.0 (WP) 60.0 (WN, AN) *3
6.4.1
*1 100
150
E6581304② • Frequency parameters Minimum
Communicati
Title
on
Function
Unit
No.
setting unit
Adjustment range
Panel/Commu
0200
Frequency priority selection
-
-
0201
%
1/1
0202
Hz
0.1/0.01
0203
%
1/1
0204
VIA input point 1 setting VIA input point 1 frequency VIA input point 2 setting VIA input point 2 frequency
Hz
0.1/0.01
0: (Switchable to by terminal input) 1: (Switchable to at less than 1.0Hz of designated frequency) 0-100
0.0-500.0
0210
VIB input point 1 setting VIB input point 1 frequency VIB input point 2 setting VIB input point 2 frequency
%
1/1
Hz
0.1/0.01
%
1/1
Hz
0.1/0.01
0.0-500.0
Hz
0.1/0.01
Hz
0241 0242
0250
0251
6.5.2
100
-
Starting frequency setting Operation starting frequency Operation starting frequency hysteresis DC braking starting frequency DC braking current
0
0-100
-
0240
6.5.1
0.0
Frequency setting mode selection 2
0213
0
0.0-500.0
0207
0212
Reference
nication
0211
Default User setting setting
0: Built-in potentiometer 1: VIA 2: VIB 3: Operation panel 4: Serial communication 5: UP/DOWN from external contact 6: VIA + VIB (Override) 0-100
50.0 (WP) 60.0 (WN, AN) 1
6.5.1
0
6.5.2
0.0-500.0
0.0
0-100
100
0.5-10.0
50.0 (WP) 60.0 (WN, AN) 0.5
6.6.1
0.1/0.01
0.0-
0.0
6.6.2
Hz
0.1/0.01
0.0-
0.0
6.6.2
Hz
0.1/0.01
0.0-
0.0
6.7.1
%(A)
1/1
0-100
50
8
E6581304② Minimum
Communicati
Title
on
Function
Unit
No.
0252 0254 0256
0260 0261 0262
0264
0265
0266
0267
0268 0269
0270 0271 0272 0273
setting unit Panel/Commu
Adjustment range
Default User setting setting
Reference
nication
DC braking time Motor shaft fixing control Time limit for lower-limit frequency operation Jog run frequency Jog run stopping pattern Panel jog run operation mode Input from external contacts – UP response time Input from external contacts – UP frequency step width Input from external contacts – DOWN response time Input from external contacts – DOWN frequency step width Initial value of UP/DOWN frequency Saving of changed value of UP/DOWN frequency Jump frequency 1 Jumping width 1 Jump frequency 2 Jumping width 2
s
0.1/0.1
-
-
s
0.1/0.1
Hz
0.1/0.01
-
-
-
-
s
0.0-20.0 0: Disabled 1: Enabled (after DC braking) 0: None 0.1-600.0
−20.0
1.0
6.7.1
0
6.7.2
0.0
6.8
5.0
6.9
0.1/0.1
0: Slowdown stop 1: Coast stop 2: DC braking 0: Disabled 1: Panel jog run operation mode enabled 0.0-10.0
0
0.1
Hz
0.1/0.01
0.0-
0.1
s
0.1/0.1
0.0-10.0
0.1
Hz
0.1/0.01
0.0-
0.1
Hz
0.1/0.01
0.0
−
−
Hz
0
0.1/0.01
0: Not changed 1: Setting of changed when power is turned off 0.0-
0.0
Hz
0.1/0.01
0.0-30.0
0.0
Hz
0.1/0.01
0.0-
0.0
Hz
0.1/0.01
0.0-30.0
0.0
9
6.5.2
1
6.10
E6581304② Minimum
Communicati
Title
on
Function
Unit
No.
0274 0275
0287
0288
0289
0290
0291
0292
0293
0294
setting unit
Adjustment range
Panel/Commu
Default User setting setting
Reference
nication
Jump frequency 3 Jumping width 3 Preset-speed operation frequency 8
Hz
0.1/0.01
0.0-
0.0
Hz
0.1/0.01
0.0-30.0
0.0
Hz
0.1
-
0.0
Preset-speed operation frequency 9 Preset-speed operation frequency 10 Preset-speed operation frequency 11 Preset-speed operation frequency 12 Preset-speed operation frequency 13 Preset-speed operation frequency 14 Preset-speed operation frequency 15 (Fire-speed)
Hz
0.1
-
0.0
Hz
0.1
-
0.0
Hz
0.1
-
0.0
Hz
0.1
-
0.0
Hz
0.1
-
0.0
Hz
0.1
-
0.0
Hz
0.1
-
0.0
6.10
5.14
6.11.2
• Operation mode parameters Minimum
Communicati
Title
on
Function
Unit
No.
0300
0301
0302
setting unit
Adjustment range
Panel/Commu
Default User setting setting
Reference
nication
PWM carrier frequency Auto-restart control selection
kHz
0.1/0.01
-
-
Regenerative power ride-through control (Deceleration stop)
-
-
2.0 - 16.0 0: Disabled 1: At auto-restart after momentary stop 2: ST terminal on or off 3: At auto-restart or when turning ST-CC on or off 4: At start-up 0: Disabled 1: Automatic setting 2: Slowdown stop
10
12.0
6.12
0
6.13.1
0
6.13.2
E6581304② Minimum
Communicati
Title
on
Function
Unit
No.
setting unit
Adjustment range
Panel/Commu
Default User setting setting
Reference
nication
0303
Retry selection Times (number of times) Dynamic braking selection Over-voltage limit operation (Slowdown stop mode selection)
0304
0305
0307
Supply voltage correction (limitation of output voltage)
0308
0309
0311
Dynamic braking resistance Dynamic braking resistor capacity Reverse-run prohibition
0312
1/1
-
-
-
-
Ohm
0.1/0.1
kW
0: Disabled 1-10
0
6.13.3
0: Dynamic braking disabled 1: Dynamic braking enabled, overload protection enabled 0: Automatic setting 1: Disabled 2: Enabled (Quick deceleration) 3: Enabled (Dynamic quick deceleration) 0: Supply voltage uncorrected, output voltage limited 1: Supply voltage corrected, output voltage limited 2: Supply voltage uncorrected, output voltage unlimited 3: Supply voltage corrected, output voltage unlimited 1.0-1000
0
6.13.4
2
6.13.5
2 (WP, WN) 3 (AN)
6.13.6
*1
6.13.4
*1
6.13.4
0
6.13.7
0
6.12
1
6.12
0 10
6.14 6.14
0.01/0.01 0.01-30.00
-
-
Random mode
-
-
0316
Carrier frequency control mode selection
-
-
0320 0323
Drooping gain Drooping insensitive torque band
% %
1/1 1/1
0:Forward/reverse run permitted 1:Reverse run prohibited 2:Forward run prohibited 0:Disabled 1:Automatic setting 0:Carrier frequency not reduced automatically 1:Carrier frequency reduced automatically 2:Carrier frequency not reduced automatically Support for 400V models 3:Carrier frequency reduced automatically Support for 400V models 0-100 0-100
*1 : Default values vary depending on the capacity. See the table of last page.
11
E6581304② Minimum
Communicati
Title
on
Function
Unit
No.
setting unit
Adjustment range
Panel/Commu
Default User setting setting
nication
0342
Braking mode selection
-
-
0343
Release frequency Release time Creeping frequency Creeping time PID control waiting time PID control Proportional gain
Hz
0.1/0.01
s Hz
0.01/0.01 0.00-2.50 0.1/0.01 -20.0
0.05 3.0
s s
0.01/0.01 0.00-2.50 1/1 0-2400
0.10 0
-
0: Disabled, 1: Enabled 0.01/0.01 0.01-100.0
0 0.30
-
0.01/0.01 0.01-100.0 0.01/0.01 0.00-2.55
0.20 0.00
0344 0345 0346 0359 0360 0362 0363 0366
Reference
Integral gain Differential gain
0: Disabled 1: Enabled (forward run) 2: Enabled (reverse run) 3: Enabled (operating direction) -20.0
0
6.15
3.0 6.15
6.16
•Torque boost parameters Minimum
Title
Communicati on No.
Function
Unit
setting unit
Adjustment range
Panel/Commu
Default User setting setting
Reference
nication
0: Auto-tuning disabled 1: Initialization of (reset to 0) 2: Auto-tuning enabled (after execution: 0) 0-150
50
0.1/0.1
0.0-30.0
*1
0.1/0.1
0.1-100.0
*1
1/1
10-90
*1
1/1
100-32000
-
1/1
1-150
1410 (WP) 1710 (WN, AN) 40
-
1/1
1-100
20
0400
Auto-tuning
0401
0402
0415
0416
0417
Slip frequency % gain Motor constant % #1 (primary resistance) Motor rated A current Motor no-load % current min-1 Motor rated speed
0418 0419
Speed control response coefficient Speed control stability coefficient
-
-
1/1
12
0
6.17
E6581304② • Input/output parameters2 Minimum
Title
Communicati on No.
Function
Unit
VIA input bias VIA input gain VIB input bias VIB input gain
-
setting unit
Adjustment range
Panel/Commu
Default User setting setting
Reference
nication
0470 0471 0472 0473
1/1 1/1 1/1 1/1
0-255 0-255 0-255 0-255
128 148 128 148
6.5.4
• Torque boost parameters2 Minimum
Title
Communicati on No.
Function
Unit
setting unit Panel/Commu
Adjustment range
Default User setting setting
Reference
nication
0480
Exciting % 1/1 100-130 strengthening coefficient 0485 Stall 1/1 10-250 cooperation gain at field weakening zone 1 0492 Stall 1/1 50-150 cooperation gain at field weakening zone 2 Motor 1/1 0-200 0494 adjustment factor Maximum % 1/1 90-110 0495 voltage Adjustment coefficient Waveform kHz 0.1/0.1 0.1-14.0 0496 switching Adjustment coefficient *1 : Default values vary depending on the capacity. See the table of last page.
13
100
6.17
100
100
*1
104
-
0.2
-
E6581304② • Acceleration/deceleration time parameters Minimum
Title
Communicati on No.
Function
Unit
setting unit
Adjustment range
Panel/Commu
Default User setting setting
Reference
nication
0500
0501
0502
0503
0504
0505
0506
0507
0510 0511
0512
0513
Acceleration time 2 Deceleration time 2 Acceleration/ deceleration 1 pattern Acceleration/ deceleration 2 pattern Acceleration/ deceleration selection (1, 2, 3)
s
0.1/0.1
0.0-3200
10.0
s
0.1/0.1
0.0-3200
10.0
-
-
-
-
-
-
Acceleration/ deceleration 1 and 2 switching frequency S-pattern lower-limit adjustment amount S-pattern upper-limit adjustment amount Acceleration time 3 Deceleration time 3 Acceleration/ deceleration 3 pattern Acceleration/ deceleration 2 and 3 switching frequency
Hz
0.1/0.01
%
0: Linear 1: S-pattern 1 2: S-pattern 2
6.18
0
0
1: Acceleration/deceleration 1 2: Acceleration/deceleration 2 3: Acceleration/deceleration 3 0.0-
0.0
1/1
0-50
10
%
1/1
0-50
10
s
0.1/0.1
0.0-3200
10.0
s
0.1/0.1
0.0-3200
10.0
-
-
Hz
0.1/0.01
0: Linear 1: S-pattern 1 2: S-pattern 2 0.0-
14
1
0
0.0
6.18
E6581304② • Protection parameters Minimum
Title
Communicati on No.
Function
Unit
setting unit
Adjustment range
Panel/Commu
Default User setting setting
Reference
nication
0601
0602
0603
0604
0605
0607
0608
0609
0610
0611
0612
0613
Stall prevention level 1 Inverter trip retention selection
% (A)
1/1
-
-
Emergency stop selection
-
-
Emergency DC braking time Output phase failure detection mode selection
s
0.1/0.1
-
-
Motor 150%overload time limit Input phase failure detection mode selection Low current detection hysteresis Low current trip/alarm Small current detection current Small current detection time Detection of output short-circuit during start-up
s
1/1
-
-
%
1/1
-
-
%
10-199, 200 (disabled)
150
6.19.2
0
6.19.3
0
6.19.4
1.0
6.19.4
0
6.19.5
300
6.19.1
0: Disabled, 1: Enabled
1
6.19.6
1-20
10
6.19.7
0
1/1
0: Alarm only 1: Tripping 0-100
0
s
1/1
0-255
0
-
-
0: Each time(standard pulse) 1: At start-up (only one time after power is turned on) (standard pulse) 2: Each time (short-time pulse) 3: At start-up (only one time after power is turned on) (short-time pulse)
0
0:Canceled with the power off 1:Still retained with the power off 0:Coast stop 1:Slowdown stop 2:Emergency DC braking 0.0-20.0
0:Disabled 1:At start-up (only one time after power is turned on) 2:At start-up (each time) 3:During operation 4:At start-up + during operation 5:Detection of cutoff on output side 10-2400
15
6.19.8
E6581304② Minimum
Title
Communicati on No.
Function
Unit
setting unit
Adjustment range
Panel/Commu
Default User setting setting
Reference
nication
0615
0616
0618
0619
0621
0626
0627
0633
0634
Over-torque trip/alarm selection Over-torque % detection level Over-torque s detection time Over-torque % detection level hysteresis Cumulative 100 operation time Time alarm setting Over-voltage % stall protection level Under-voltage trip/alarm selection
Trip at VIA low level input mode Annual average ambient temperature (calculation for life alarms)
-
1/1 0.1/0.1 1/1
0.1/0.1 (=10 hours) 1/1
-
%
1/1
-
-
0: Alarm only 1: Tripping
0
6.19.9
0-250
150
0.0-10.0
0.5
0-100
10
6.19.9
0.0-999.9
610
6.19 .10
100-150
*1
6.13.5
0: Alarm only (detection level below 60%) 1: Tripping (detection level below 60%) 2: Alarm only (detection level below 50%, DC reactor necessary) 0: Disabled, 1-100
0
6.19 .12
0
6.19 .13
3
6.19 .14
1: -10 to +10 degree C 2: 11-20 degree C 3: 21-30 degree C 4: 31-40 degree C 5: 41-50 degree C 6: 51-60 degree C
*1 : Default values vary depending on the capacity. See the table of last page.
16
E6581304② • Output parameters Minimum
Title
Communicati on No.
Function
Unit
setting unit
Adjustment range
Panel/Commu
Default User setting setting
Reference
nication
0669
0676
0677
0691
0692
Logic output/pulse train output selection (OUT-NO) Pulse train output function selection (OUT-NO)
Maximum numbers of pulse train Inclination characteristic of analog output Meter bias
-
-
0: Logic output 1: Pulse train output
0
6.20.1
-
-
0
6.20.1
pps
1/1
0:Output frequency 1:Output current 2:Set frequency 3:DC voltage 4:Output voltage command value 5:Input power 6:Output power 7:Torque 8:Torque current 9:Motor cumulative load factor 10:Inverter cumulative load factor 11:PBR (braking reactor) cumulative load factor 12:Frequency setting value (after PID) 13:VIA/II Input value 14:VIB Input value 15:Fixed output 1 (Output current: 100%) 16:Fixed output 2 (Output current: 50%) 17: Fixed output 3 (Other than the output current: 100%) 500-1600
800
6.20.1
-
-
1
6.20.2
%
1/1
0
6.20.2
0: Negative inclination (downward slope) 1: Positive inclination (upward slope) 0−100
17
E6581304② • Operation panel parameters Minimum
Title
Communicati on No.
Function
Unit
setting unit
Adjustment range
Panel/Commu
Default User setting setting
Reference
nication
0700
0701
0702
Free unit selection
0705
0706
0707
0708
0710
Inclination characteristic of free unit display Free unit display bias Free step 1 (pressing a panel key once) Free step 2 (panel display) Standard monitor display selection
0719
0721
0730
0733
Prohibition of change of parameter settings Unit selection
Canceling of operation command when standby terminal (ST) is turned off Panel stop pattern Prohibition of frequency setting on the operation panel () Panel operation prohibition (RUN/STOP keys)
-
-
-
-
0: Permitted 1: Prohibited
0:% 1:A (ampere)/V (volt) Times 0.01/0.01 0.00: Free unit display disabled (display of frequency) 0.01-200.0 0: Negative inclination (downward slope) 1: Positive inclination (upward slope) Hz 0.01/0.01 0.00- Hz
0.01/0.01 0.00: Disabled 0.01-
-
1/1
-
-
-
-
-
-
-
-
-
-
0: Disabled 1-255 0:Operation frequency (Hz/free unit) 1:Frequency command (Hz/free unit) 2:Output current (%/A) 3:Inverter rated current (A) 4:Inverter load factor (%) 5:Output power (%) 6:Frequency command after PID control (Hz/free unit) 7:Optional item specified from an external control unit 0:Operation command canceled (cleared) 1:Operation command retained
0: Slowdown stop 1: Coast stop 0: Permitted 1: Prohibited
0: Permitted 1: Prohibited
18
0
6.21.1
0
6.21.2
0.00
6.21.3
1
0.00 0.00
6.21.4
0
6.21.4
0
6.21.5
1
6.21.6
0
6.21.7
0
6.21.1
0
E6581304② Minimum Communicati
Title
on No.
setting unit
Adjustment range
Default User setting setting
Function
Unit
Prohibition of panel emergency stop operation Prohibition of panel reset operation Prohibition of change of / during operation
-
-
0: Permitted 1: Prohibited
0
-
-
0: Permitted 1: Prohibited
0
-
-
0: Permitted 1: Prohibited
1
Panel/Commu
Reference
nication
0734
0735
0736
•
6.21.1
Communication parameters Minimum
Title
Communicati
Function
Unit
0800
Communication band speed
-
0801
Parity
-
0802 0803
s
0805
0806
Inverter number Communication error trip time Communication waiting time Setting of master and slave inverters for communication between inverters (setting of master and slave)
on No.
setting unit
Adjustment range
Panel/Commu
Default User setting setting
Reference
nication
s -
-
0: 1200bps 1: 2400bps 2: 4800bps 3: 9600bps 4: 19200bps 0: NON (No parity) 1: EVEN (Even parity) 2: ODD (Odd parity) 1/1 0-255 1/1 0: (disabled) 1-100 0.01/0.01 0.00-2.00 -
0: Slave inverter (0 Hz command issued in case the master inverter fails) 1: Slave inverter (Operation continued in case the master inverter fails) 2: Slave inverter (Emergency stop tripping in case the master inverter fails) 3: Master inverter (transmission of frequency commands) 4: Master inverter (transmission of output frequency signals)
19
3
1
0 0 0.00 0
6.22
E6581304② Minimum
Title
Communicati on No.
Function
Unit
setting unit
Adjustment range
Panel/Commu
Default User setting setting
Reference
nication
0811 0812
0813 0814
0829
0870
0871
0875
0876
0877
0878
0879
0880 0890 0891 0892 0893 0894
Point 1 setting Point 1 frequency Point 2 setting Point 2 frequency
% Hz
1/1 0.1/0.01
0-100 0.0-500.0
0 0.0
% Hz
1/1 0.1/0.01
0-100 0.0-500.0
Selection of communication protocol Block write data 1 Block write data 2
-
-
0: Toshiba inverter protocol 1: Modbus RTU protocol
100 50.0 (WP) 60.0 (WN, AN) 0
-
-
-
-
Block read data 1 Block read data 2 Block read data 3 Block read data 4 Block read data 5
-
-
-
-
-
-
-
-
-
-
Free notes Parameter for option 1 Parameter for option 2 Parameter for option 3 Parameter for option 4 Parameter for option 5
-
1/1 1/1
0: No selection 1: Command information 1 2: Command information 2 3: Frequency command 4: Output data on the terminal board 5: Analog output for communications 0: No selection 1: Status information 2: Output frequency 3: Output current 4: Output voltage 5: Alarm information 6: PID feedback value 7: Input terminal board monitor 8: Output terminal board monitor 9: VIA terminal board monitor 10: VIB terminal board monitor 0-65535 0-65535
-
1/1
0-65535
0
-
1/1
0-65535
0
-
1/1
0-65535
0
-
1/1
0-65535
0
20
6.5.2
6.22
0 0
0 0 0 0 0
0 0
6.23
E6581304② • Reservation area parameters Minimum setting
Title
Communication No.
Function
Unit
unit Panel/Communi
Adjustment range
Default setting
User setting
Reference
cation
0910
0911
0912
Step-out detection current level (for PM motors) Step-out detection time (for PM motors) Q axis inductance (for PM motors)
% (A)
1/1
10-150
100
6.24
s
1/1
0.0: No detection 0.1-25.0
0.0
6.24
mH
0.01/0.01
0.00-650.00
0.00
-
21
E6581304② -Default settings by inverter rating Inverter type
VFS11S-2002PL VFS11S-2004PL VFS11S-2007PL VFS11S-2015PL VFS11S-2022PL VFS11-2002PM VFS11-2004PM VFS11-2007PM VFS11-2015PM VFS11-2022PM VFS11-2037PM VFS11-2055PM VFS11-2075PM VFS11-2110PM VFS11-2150PM VFS11-4004PL VFS11-4007PL VFS11-4015PL VFS11-4022PL VFS11-4037PL VFS11-4055PL VFS11-4075PL VFS11-4110PL VFS11-4150PL
Torque boost / (%) 6.0 6.0 6.0 6.0 5.0 6.0 6.0 6.0 6.0 5.0 5.0 4.0 3.0 2.0 2.0 6.0 6.0 6.0 5.0 5.0 4.0 3.0 2.0 2.0
(Ohm)
Dynamic braking resistor capacity (kW)
200.0 200.0 200.0 75.0 75.0 200.0 200.0 200.0 75.0 75.0 40.0 20.0 15.0 10.0 7.5 200.0 200.0 200.0 200.0 160.0 80.0 60.0 40.0 30.0
0.12 0.12 0.12 0.12 0.12 0.12 0.12 0.12 0.12 0.12 0.12 0.24 0.44 0.66 0.88 0.12 0.12 0.12 0.12 0.12 0.24 0.44 0.66 0.88
Dynamic braking resistance
Motor constant #1 Motor rated (primary current resistance) (%) (A) 8.3 6.2 5.8 4.3 4.1 8.3 6.2 5.8 4.3 4.1 3.4 3.0 2.5 2.3 2.0 6.2 5.8 4.3 4.1 3.4 2.6 2.3 2.2 1.9
22
1.2 2.0 3.4 6.2 8.9 1.2 2.0 3.4 6.2 8.9 14.8 21.0 28.2 40.6 54.6 1.0 1.7 3.1 4.5 7.4 10.5 14.1 20.3 27.3
Motor no-load current (%) 70 65 60 55 52 70 65 60 55 52 48 46 43 41 38 65 60 55 52 48 46 43 41 38
Over Motor voltage stall adjustment protection factor level (%) 90 90 80 70 70 90 90 80 70 70 70 70 70 60 50 90 80 70 70 70 70 70 60 50
134 134 134 134 134 134 134 134 134 134 134 134 134 134 134 140 140 140 140 140 140 140 140 140