Transcript
Pc Mitho Software Manual
2.0
PC Mitho2 Manuale SW-EN-24805552 02-05-13
Contents
PC Mitho 2.0
Contents of the package and system requirements Package contents
Warnings
- -
The information in this manual is covered by the rights of Bpt S.p.a. or its suppliers and may not be reproduced in any way, nor transmitted to others.
USB cable for connection between PC and OH/GW CD with Pc Mitho software
PC MITHO HOAS
IS ON SERVICE
SW1 1 2 3 4
OFF
ON 1 2 3 4
Hardware and software requirements -
-
The information in this manual is subject to change without advance notice. Bpt S.p.a. shall not be held liable for any errors which this document may contain.
PC Pentium III 700 MHz or greater, RAM 128 MB, 40 MB of space on HD, XGA video
Unless specified otherwise, any reference to companies, names, data and addresses used in the reproduction of screens and in the examples is merely a coincidence and is only for the purpose of illustrating the use of the Bpt S.p.a. product. No part of this manual may be reproduced in any mechanical or electronic form or means, for any use, without the written permission of Bpt S.p.a. The content of this programme is covered by exclusive rights of Bpt S.p.a..
Compatible operating systems Windows 98SE Windows ME Windows 2000 Windows XP (with minimum RAM 512 MB) Windows Vista (with minimum RAM 1 GB) Windows 7 Windows 8
m PAY ATTENTION !
In computers running the Microsoft Vista operating system, Pc Mitho will only run if the Administrator profile is installed.
•2•
Contents
PC Mitho 2.0
Table of Contents
Contents of the package and system requirements . . . . . . . . . . . . . . . . . . . . . . .
Pag.
Custom Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2
Package contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Hardware and software requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pag.
3
The home automation modules and their characteristics . . . . . . . . . . . . . . . .
Pag.
5
System devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modules with digital inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modules with Relay based Digital Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mixed Modules with Digital Inputs and Relay Digital Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . Modules with Analogue Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modules with Analogue Outputs and mixed modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Relay modules for motor control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modules to control thermal zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Other modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General information on programming the installation . . . . . . . . . . . . . . . . . .
Software Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Creating a new installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pag. 13
Pag. 14
Adding “Zones” to the installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Adding “Spaces” to the installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Add the "Network components" container to the structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Adding essential devices to an installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 5 6
14 14 15
15 To define a new Master terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6 6
Programming application examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
Pag. 18
Relay controlled lighting point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Lighting groups with differing properties controlled by push-button switches . . . . . . . 21 Lighting point manually controlled by a dimmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
7 8
Dimmer mode properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Wave mode properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Digital inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Relay digital outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Analogue inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Analogue outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Lighting point automatically linearly controlled by dimmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Analogue output properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . State change notification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Signal property 0-10V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Linear mode properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Threshold Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Analogue Step mode properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digital step modality properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Tracking modality properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Analogue output control logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 8 8 8 8
Digital output control logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 “CYCLIC" relay function (bistable) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . “ON” function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . “OFF” function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . “DIRECT” (monostable) functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . “ENABLE” function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . “PULSE” function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pag. 12
Building the installation structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
Definition of analogue and digital inputs and outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
“Dimmer” logic mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . “Linear” logic mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . “Step” logic mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . “Following” logic mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Principle software commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The “Installation structure” window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5
Pag.
Pag. 11
Pc Mitho Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
26 26 26 27 27 28 29 29
Locally and timer controlled lighting points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Thermal zone with radiators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
9 9 9 9 9 9
OHZ zone thermostat properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Thermal zone with fan coil units: fan speed control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Internal temperature sensor properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 OH/FAN module properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
•3•
Contents
PC Mitho 2.0
OH/FAN advanced options properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 OH/FAN PI algorithm properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 OH/FAN diff. algorithm properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Updating home automation module firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 Configuring an Ethernet communication interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Thermal zone with fan coil units: complete control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Installation programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
How to retrieve an installation file by means of the OH/ETH1 Master . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
OH/FAN-E module properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 OH/FAN (slave) module properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Create a personalised interface with graphical maps . . . . . . . . . . . . . . . . . . . . .
Manually controlled motorised sun screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Automatic activation of a contact subordinated to the data detected by measuring devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
The characteristics of the images . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
The “Map view” window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Impulse generator properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Threshold Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Generic relay controlled by either a push-button switch or a sensor . . . . . . . . . . . . . . . . . . . 42 Create an irrigation programme . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Irrigation Sector Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
The use of custom logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 OR logic function properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Load control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Remote control contact activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Group and programme activations through Scenarios . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
67 68 69 70 70
View permissions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Actions view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connections view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
72 74 74
Print . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Scenario Delay Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Remote control of the installation using the OH/GSM dialler . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 GSM properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Management of compatible anti-intrusion control units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Integration of inputs and outputs for Proxinet control panels in the BPT home automation system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Handling of audio compatible control units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Audio Control Unit Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Pag. 58
USB communications interface configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Installation programming and diagnostics
Insert a new page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Map properties page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Building a navigation scheme . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Export the map interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Add functions to the screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
75 Monitor messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
OH/MPE6KW module properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Installation commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pag. 66
Preliminary operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pag. 59
Collect the ID codes of the connected modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 ID code association to the connected modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 ID association by means of dragging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 ID association by means of the service button on the module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 ID association from the module properties window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
•4•
Contents
PC Mitho 2.0
The home automation modules and their characteristics System devices
OH/IR The OH/IR is a module that is equipped with an IR remote control receiver and 2 digital inputs. The receiver is controlled by the OH/IRTX1 IR remote control, using NEC or universal remote controls capable of storing and replicating OH/IRTX1 signals. Once the device has been connected to the BPT system bus the inputs can then manage contacts (for example switches).
OH/A.01 The OH/A.01 is a power source that provides the voltage required to operate all the system devices connected to the bus. The device is designed for connection to an external emergency power source.
Modules with Relay based Digital Outputs
OH/AS The OH/AS is a power source that provides the voltage required to operate all the system devices connected to the bus. Since it is also equipped with an input for emergency batteries (2 x 7.2 Ah to 12 V – OH/B065) it is able to continue to provide power to the devices connected on the bus even in the event of a power cut. The batteries are kept charging by the same module and guarantee the system a minimum life of 7 hours.
OH/RP The OH/RP is a module fitted with a relay output (16 A) expandable with the OH/2RP module fitted with another two relay outputs (with the same features). OH/2RP The OH/2RP is a slave module fitted with 2 relay outputs (16 A) only usable coupled with the OH/RP module.
NH-RBB The NH-RBB is a line repeater module designed to enhance the performance of a bus line in terms of extension and quantity of devices connected to it.
Mixed Modules with Digital Inputs and Relay Digital Outputs
OH/GW The OH/GW is the module which allows the interfacing of the Bus MultiMaster (MM) network with the system bus. In addition, it allows interfacing with the gateway for LAN OH/ETH1 networks or with compatible Brahms burglar-proof systems.
OH/RI The OH/RI is a module fitted with a relay (capacity 5A for resistive loads or incandescent bulbs and 2A for inductive loads, fluorescent bulbs or ferromagnetic transformers) and 3 digital inputs for the connection of control devices fitted with output contacts free of voltage.
OH/ETH1 The device is designed to control the main automation functions of the installation via Android Smartphone, PC, iPhone and iPad devices connected to a local Ethernet or WiFi network and having an HTML5-CSS3 compatible browser; it is also designed to allow the connection of several sections of the installation each to the other via an Ethernet network (LAN).
OH/3RPI The OH/3RPI is a module fitted with 3 relay outputs (capacity 16A for resistive loads or incandescent bulbs and 5A for inductive loads, fluorescent bulbs or ferromagnetic transformers) and 3 digital inputs for the connection of control devices fitted with output contacts free of voltage. OH/R.01 The OH/R.01 is fitted with 4 relay outputs, maximum current 5A with resistive loads (2A with inductive load), and 4 digital inputs for the connection of control devices fitted with output contacts free of voltage.
Modules with digital inputs OH/6I The OH/6I is fitted with 6 inputs per contact without flow of current or voltage to the heads.
OH/RI4416 The OH/RI4416 is a module fitted with 4 relay outputs (capacity 16A for resistive loads or incandescent bulbs and 5A for inductive loads, fluorescent bulbs or ferromagnetic transformers) and 4 digital inputs for the connection of control devices fitted with output contacts free of voltage. In the event of a power cut from the BUS line it is possible to change the status of the relay to the condition desired by manually moving the coincident switch assembled on the front of the module.
OH/4I is a module fitted 4 inputs per contact. The 4 outputs may be used to activate control LEDs that require loads up to 2mA.
•5•
Contents
PC Mitho 2.0
Modules with Analogue Inputs
Relay modules for motor control
OH/AI4 The OH/AI4 is a device fitted with 4 analogue inputs through which it is possible to acquire signals coming from sensors with 0-10V, 0-1V, 4-20mA or 0-20mA outputs. The OH/AI4 is also fitted with 2 pulse counter inputs (max. freq. 50kHz ) for acquiring signals from pulse output based sensors.
OH/MA The OH/MA is a module to control a motorization for automatic opening (e.g. blinds, shutters, etc.). It is also fitted with 3 digital inputs for the connection of control devices fitted with output contacts free of voltage.
OH/MT2 The OH/MT2 is a device fitted with 2 inputs through which it is possible to acquire signals coming from OH/STI, OH/STE temperature probes or PT1000 thermal probes. It also has 2 inputs for the connection of hygrometers with 4-20 mA output.
Modules to control thermal zones OH/FAN The OH/FAN is a module to control the speed (3) of the fan of a fan coil unit through 3 relay outputs (16A) It is also fitted with 3 digital inputs for the connection of control devices fitted with output contacts free of voltage that control the outputs of the device with the following mode: •The closure/opening of I1-I3 inputs activates the corresponding relays that regulate the fan speed. •The closure/opening of the STOP contact forces the closure/opening of the relays of the same module (window contact).
Modules with Analogue Outputs and mixed modules OH/AO4010 The OH/AO4010 is a module fitted with 4 0-10V outputs via which it is possible to control devices such as proportional solenoid valves, devices for the control of lights etc. It is also fitted with 4 relay outputs (capacity 16A for resistive loads or incandescent bulbs and 5A for inductive loads, fluorescent bulbs or ferromagnetic transformers) and 4 digital inputs for the connection of control devices fitted with output contacts free of voltage. The relays are always associated with the corresponding 0-10V output, therefore it will not be possible to associate relay 1 of the module to a 0-10V output that is not number 1.
OH/FAN-E The OH/FAN-E is a module to completely control a fan coil unit fitted with: • 3 relay outputs (16A) to control the speeds (3) of the fan • 2 change-over relay outputs (5A) and two analogue outputs 0-10V to control the solenoid valves (ON/OFF or proportional) to control the heating or cooling circuits • 2 digital inputs for the connection of “door contacts” for the turning off command • 1 input for the connection of a OH/STI temperature sensor connected to the delivery pipe to enable outputs.
OH/AO1010 The module comes equipped with 1 relay and 1 0-10 V output; via the aforementioned, it is possible to control devices with 0-10 V inputs, for example, dimmers for neon and incandescent lamps. It is also equipped with 1 digital input for the management of contacts (for example push-button switches).
OH/Z.02 The OH/Z.02 is a module fitted with a thermal probe to detect the temperature of the environment in which it is installed. It is also fitted with a display and functional keys to read the temperature detected and the setting of the desired temperature.
OH/ DI2230 The OH/ DI2230 is a module fitted with 2 outputs for the dimming of the power supply voltage of 2 loads with a max power of 300W or a single load of 500W. It is also fitted with 2 analogue inputs for sensors with 0-10V output and 2 digital inputs for the connection of control devices fitted with output contacts free of voltage.
OH/MT2 The OH/MT2 has 2 inputs to which it is possible to connect OH/STI, OH/STE temperature probes or PT1000 thermal probes. It also has 2 inputs for the connection of 4-20 mA humidity sensors.
•6•
Contents
PC Mitho 2.0
Other modules OH/MPE6KW The OH/MPE6KW is an electrical power measuring module (up to 6KW) that provides the display of the cumulative and instantaneous consumption values as well as the implementation of algorithms for the control of the maximum absorption and prevention of overloading (“electrical load control” function). Schneider Measurement Module The Schneider module is a three-phase electrical power meter (up to 18KW) that provides the display of the cumulative and instantaneous consumption values as well as the implementation of the algorithms for the control of the maximum absorption and prevention of overloading (“electrical load control” function). OH/GSM The OH/GSM module is a GSM communicator through which it is possible to realise the remote management of a home automation system. When suitably programmed the OH/GSM can send a status and/or alarm SMS or receive an SMS command for the activation of “scenarios” or else thermal zone commands.
•7•
Contents
PC Mitho 2.0
General information on programming the installation Definition of analogue and digital inputs and outputs
Analogue output control logic
Digital inputs
“Dimmer” logic mode
Input type, available in many home automation modules that provide the connection of devices equipped with clean contacts (buttons, switches, sensors with relay output etc.)
The manual functioning logic (or “Dimmer”) commands the output and therefore the load by using a normal button. • by pressing the button for less than 1 second, the load is “cyclically” commanded (each time the button is pressed you pass from on to off or vice versa) and each time it is turned on the dimming assumes the last saved value. • by pressing the button for more than 1 second but less than 2 seconds, the load is controlled with the maximum dimming value at the set maximum value. • by pressing the button for more than 2 seconds, the degree of dimming is varied (increasing and then decreasing). In this way the desired value can be arrived at. Upon release the chosen value is maintained.
Relay digital outputs Output type, available in many home automation modules that provide the “on/off” command (turning on / off ) of electrical loads such as lights, solenoid valves, motors etc...
Analogue inputs Input type, only available in dedicated home automation modules, through which it is possible to acquire, by digitalizing it, the value of the sensors, transducers etc. able to convert the value of a physical quantity (light intensity, humidity, wind intensity etc...) in an electrical signal.
“Linear” logic mode
Analogue outputs
According to this automatic functioning logic the output value is a linear function of an analogue input value. The scale factor (k) can be programmed.
Output type, only available in dedicated home automation modules that provide the command through a voltage variable over time (0-10V), of devices such as proportional solenoid valves, devices for the control of lights etc. A “special” type of analogue output is the “dimmer” output that allows for the direct command of electrical loads powered at mains voltage via lowering the drive voltage. This type of output allows for the control of lights and resistive loads, etc.
“Step” logic mode According to this automatic functioning logic the output value assumes the values associated with “events” (max 8) given by the programmable threshold (“increasing” and/or “decreasing”) of an analogue input (local or system) being exceeded or by the activation of one or more digital inputs.
“Following” logic mode
By means of the configuration software it is possible to choose the most suitable input and output types for the requirements of the installation to automate, create the “logic” links that determine the operation of the installation and programme the functions that determine the operation of the system.
According to this automatic functioning logic the output “follows” the set-point set (from configuration software, terminal or analogue input) upon the variation of the measured value (directly or indirectly) of the variable that you want to control.
•8•
Contents
PC Mitho 2.0 Push button switch
Digital output control logic
ON
Timer or Switch
OFF
ON
Relays
ON OFF
ON
Relays
OFF
OFF
“CYCLIC" relay function (bistable) Push button switch Push button switch Push Relays button switch Relays
ON OFF ON ON OFF ON OFF ON OFF OFF
Switch
ON Push button A simple application is the switch turning OFF on and off ON Timer or ON than one Push Switch command of a light, also with more ON OFF button buttons. ON OFFON switch Relays OFF Timer or Switch Relays OFF
Relays
ON OFF
Relays
ON
Relays
Push button switch Push button switch Push Relays button switch Relays
ON
ON Push “ON” function ON Push button Each timeOFF the command button buttonis activated, the switch OFF ON Push relay changes to ON status ifswitch it is OFF, otherwise ON Push button ON the command is ignored. button OFF switch R R OFFON switch ON Push Relays OFF T Relays OFF button This function is useful should you want to imT ON OFF switch ON R R plement an unconditioned “turning on” comRelays OFF Relays OFF mand. T
ON OFF ON OFF OFF ON OFF
Relays
Push button switch Push button switch Push Relays button switch Relays
ON
Crepuscolar
OFF ON ON OFF ON OFF ON OFF OFF ON
Relays
OFF
Timer or Crepuscolar Switch
R OFF ON OFF ON ON OFF
OFF “OFF” function
R T
Push button switch Crepuscolar
T
OFF R
R
OFF
T
T
Push button switch
ON
“ENABLE” function
ON
Activation of the relay is as with direct control, but it will take place only if there is the consent of the enable command (e.g. dusk), which will in turn be connect to an input
OFF ON OFF
Timer or Relays Switch
ON ON OFFOFF
Relays
ON OFF
T
Crepuscolar
ON OFF
Timer or Switch
ON OFF
R
R T
The most typical example is the use of a dusk device on groups of outdoor lights activated by a timer or turned on with a normal button
T
OFF
ON Each the command button is activated, the ON Crepuscolar Timer or timeON ON OFF Switch OFF relay changes to the OFF status if it is ON, otherRelays OFF Relays OFF wise the command is ignored.
Timer or Switch Relays
OFFON
OFF
ON
Relays
Relays
OFF
OFF
ON OFF
Note. This function can be associated with a push-button switch if this is the only one that acts on a relay.
OFF ON
ON
Relays
ON
Push button switch Relays
As long as the input contact remains closed (ON), the relay remains energised (ON).
ON
Timer or Switch
OFF
ON OFF
ON
OFF
“DIRECT” (monostable) functions
Upon each activation of the control button, the ON Timer relayorchanges status.
Push button Relays switch
ON ON OFF OFF
This function is useful should you want to implement ON an unconditioned “turning off” comRelays mand. OFF
An input pulse of any duration causes the activation of the relay for a time of delay (R) and duration (T) programmed in the OH/T terminal (the times are programmable from 1” to 59’ 59”)
ON ON OFF OFF
ON
Relè
“PULSE” function
OFF
R
R T
R T T
The duration of programmed activation is independent of the duration of the command pulse. If the input is activated again the timer is then reactivated.
•9•
An example might be turning on the stairwell lights in a block of flats
Contents
PC Mitho 2.0
Custom Logic Logic type AND The AND logic function gives a "true" output only when all inputs are "true"
OR The OR logic function gives a "true" output when at least one input is "true"
XOR The XOR logic function gives a “true” output only when the two inputs present opposite logic states.
Truth table Input A 0 0 1 1
Input B 0 1 0 1
Output OUT 0 0 0 1
Input A 0 0 1 1
Input B 0 1 0 1
Output OUT 0 1 1 1
Input A 0 0 1 1
Input B 0 1 0 1
Output OUT 0 1 1 0
Input A 0 1
NOT The NOT logic function gives a "true" output when its input condition is false and vice versa.
COMPARE The Comparator logic function allows for the comparison of either 2 analogue or temperature inputs. The Comparator gives a "true" output if and when the first input value is lower than the second. It is also possible to add hysteresis to the comparison.
Logic type
Input A 9 13 11 8 7
ADDER The Adder logic logic function allows for the summation (even of weighted values) of 2 analogue or temperature inputs: for example to find the average value of two temperatures. This function can also be used as the input to a comparator.
Input A
Multiplication Factor
Input B
Multiplication Factor
10.0 20.0 30.0 40.0
0.5 0.5 0.5 0.5
10.0 15.0 20.0 20.0
0.5 0.5 0.5 0.5
Output OUT 10.0 17.5 25.0 30.0
Example of AND function on the same push-button switch DELAY with a delay of 2 seconds. The Delay logic function allows for Push-button the delay of an output state: for Push-button Time (s) switch A Output OUT example in handling prolonged switch A (delayed) push-button switch depression. Up to 1 0 0 0 4 events can be memorised that can 2 1 0 0 be applied to an output during the delay period. 3 1 0 0 4 1 1 1 5 0 1 0 6 0 1 0 A 2sec. 7 0 0 0
Output OUT 1 0
Input B 12 10 8 11 15
Truth table
CONSTANT A constant value, used as an input to a comparator it can be a reference for an analogue input or temperature value.
Hysteresis Output OUT 2 1 2 0 2 0 2 1 2 1
A B
• 10 •
Temperature A 15.8 18.7 21.1 22.8 17.2
Constant value 20.0 20.0 20.0 20.0 20.0
Hysteresis (10ths of a °C) 10 10 10 10 10
Output OUT 1 1 0 0 1
Contents
PC Mitho 2.0
Software Installation
Pc Mitho Installation Insert the installation CD and follow the instructions that will appear during the procedure.
Choose the destination for the programme on your hard disk.
• 11 •
Once the installation procedure has completed it will be possible to launch the programme via an icon on the desktop.
Contents
PC Mitho 2.0
Principle software commands
Open installation files with the “.bptdomo” extension
Save installation files that are already open
Allow software preference configuration
Program connected automation devices
Allow the choice of interface language Refresh all system messages generated by the software that have subsequently been suppressed by the user
The insertion of a password is required every time the programme is launched
. Note: Configuration modifications only take effect after restarting the software
• 12 •
Allow monitoring of the system's USB bus for diagnostic purposes
Allow searching for device IDs connected to the system's USB bus
Allow access the the system's printer options
Contents
PC Mitho 2.0
Creating a new installation The “Installation structure” window From the main menu select “New Installation" The newly created installation in “Installation View” mode. Enter the name to be assigned to the root of the installation in the field within area C.
A
B
The programme is structured to for the allow off-line virtual creation and programming of an installation according to a hierarchy that is as similar as possible to the actual system. The programming system is extremely intuitive in that to create such a structure you only need to drag the elements that will make up the installation from area B to area A .
C
The software has been designed in such a way as to avoid programming errors caused by dragging icons from zone B to an area erroneously hierarchically organised in area A. By means of window C it is possible to programme all available parameters for the device selected in window A. With the aim of limiting the number of icons and devices shown in window B it is possible to select a filter that will allow the display of only those devices necessary to realise the section of the installation currently being programmed.
• 13 •
Contents
PC Mitho 2.0
Building the installation structure Adding “Zones” to the installation Drag the “Zone” icon to the root of the installation. A new window will appear, where a name can be assigned to the zone you have just added. You can also create, in just a single step, several zones with the same name followed by a progressive number. To do so, select the quantity in the specified menu. Proceed in the same way for all other zones into which the installation is to be divided.
Programming requires the home environment to be divided into “Zones”, “Spaces”, and “Network components” thereby facilitating easier viewing of the physical location of the devices. Zone A “Zone” can be a collection of several spaces within the home that share common features. For example, it might be the first floor. Space A “Space” is a specific place in the home. It might be a hallway, a room, or several rooms.
Adding “Spaces” to the installation Once you have inserted the desired zones into an installation, you then need to drag into the zones the “Spaces” that they include. You will also be able to name the spaces.
. Note: Use special care in assigning names to “Zones” ans "Spaces" because these names will appear within the graphical interface of the terminal. Living area Kitchen area
Shutter 1
Shutter 2
Shutter 3
Shutter 4
Shutter 5
Shutter 6
Example of the visualisation of “Zones” and “Spaces” on Mitho terminals.
• 14 •
Contents
PC Mitho 2.0 Add the "Network components" container to the structure Drag "Network components” element into the “Spaces”. The location of the “Networks components” icon is not physically binding, i.e. it is not necessary for the network components to be physically located within the space where they are located in the virtual programming space. However, it is advisable (especially in very large installations) to locate the modules near the devices to be controlled, in this way they can be easily identified if necessary. The “Network components” element can be renamed by selecting its icon and entering a new name in the appropriate field.
Network components The element referred to as “Network components” can be interpreted as a container within which IN/OUT devices that form the necessary functions of the installation may be positioned. It doesn't necessarily have to correspond to a real-world location within the building and can be positioned exclusively within a “Space”.
Adding essential devices to an installation Once the structure of the building has been realised and subsequently divided up into “Zones” and “Spaces” all that is left to do is to locate within the spaces the devices that make up the installation as per the summary tables contained within the OH/A.01 module which were filled out during the physical creation of the installation. After having located the "Network components" icon within the installation drag the OH/GW module to the centre of it. Where featured, also add the OH/ETH1 device to the installation.
• 15 •
Gateway OH/GW The OH/GW is the module which allows the interfacing of the Bus MultiMaster (MM) network with the system bus. In addition, it allows interfacing with the gateway for LAN OH/ETH1 networks or with compatible burglar-proof systems. Gateway OH/ETH1 The device is designed to control the main automation functions of the installation via PC, iPhone, iPad and Android tablet and smartphones connected to the local Ethernet or WiFi network and fitted with HTML5-CSS3 compatible browser; it is also designed to allow the connection of several sections of the installation to one another via an Ethernet network (LAN).
Contents
PC Mitho 2.0 Select the OH/GW module and in the properties window, where it says “Controlled device” select the gateway module OH/ETH1 which will then be physically connected to the OH/GW module.
m PAY ATTENTION If the installation is to feature one or more OH/ETH.01 modules then before proceeding with the complete programming of the installation, it is essential that every OH/ETH.01 be associated with an HO/GW module and that every (OH/ETH.01+OH/GW) node be programmed separately: refer to appropriate chapter: “Configuring an Ethernet communication interface” on page 63.
Device/Module without an ID or to which a specific function has not been associated Connect the OH/A.01 power supply module. Indicates that the device is not controlled by any push-button switch or input; the device is nonetheless terminal controlled. Unprogrammed module
• 16 •
Contents
PC Mitho 2.0 In the desired “Space” place the required Mitho terminal(s).
. Note:
There may be more than one Mitho terminal in the same installation.
The building automation installation is capable of functioning without a supervising terminal, in such a case all functions are controlled by physical push-button switches distributed within the building.
Factory settings assume that the first terminal added to the installation will be considered the Master terminal.
To define a new Master terminal With the left mouse button select the terminal intended as the new Master terminal and click on "Make master”.
• 17 •
Contents
PC Mitho 2.0
Programming application examples Relay controlled lighting point 1
2
Modules used in the example: OH/3RPI Drag the lighting points with their activation buttons from list A to the spaces B.
B A
3
4
Open the “Networks components” section C and access the list of modules therein. Select the device necessary for controlling a lighting point and associated push-button switch (in the example an OH/3RPI module with 3 inputs and 3 outputs) and drag it to the desired network components container.
C
• 18 •
Contents
5
PC Mitho 2.0 Drag every lighting point corresponding to the relay that will control it (or vice versa).
6
Drag the push-button switch corresponding to the light that it will control (or vice versa). The installation screen now displays the lights connected to their associated push-button switches.
At the same time associate a push-button switch with the available connections
Device/Module without an ID or to which a specific function has not been associated Indicates that the device is not controlled by any push-button switch or input; the device is nonetheless terminal controlled. Unprogrammed module
7
Selecting one of the push-button switches present within the structure. At the bottom-left of the push-button switch is a list of its properties. The first drop-down menu list the type of function for the switch itself.
• 19 •
. Note: For more information about the programming functions (CYCLE, ON, OFF, DIRECT, IMPULSE, ENABLE) see the chapter entitled “Digital output control logic” on page 9.
Contents
PC Mitho 2.0
8
The drop-down menu D is for setting the state of the input contact which will control the relay.
When programming is complete, if everything has been done correctly, the icons for the lighting point and the associated switches must be free of any error notification.
Device/Module without an ID or to which a specific function has not been associated Indicates that the device is not controlled by any push-button switch or input; the device is nonetheless terminal controlled Unprogrammed module
Living area
. Note: D
Use special care in assigning names to “Zones”, "Spaces" and "Lighting Points" because this name will appear in the graphic interface of the terminal.
Kitchen area
Kitchen light 1
Kitchen light 2
Kitchen light 3
Example of the visualisation of lighting points on Mitho terminals.
• 20 •
Contents
PC Mitho 2.0
Lighting groups with differing properties controlled by push-button switches 1
2
3
Modules used in the example: OH/3RPI In this example an ambient is illuminated by 3 lighting points activated by a presence sensor which maintains an ON state for a predetermined length of time. It is required that the same lighting points may be controlled by a ON/OFF push-button switch. Within the desired space place the lighting points and the push-button switches that will control them; one of the push-button switches will in reality be the presence sensor. Insert the OH/3RPI module (fig. 1) into the “Netwok components” container. Connect the contacts to the push-button switches and the lighting points to the relays (fig. 2).
4
m PAY ATTENTION
The lighting group is controlled by the last push-button pressed in chronological order.
. Note: For more information about the programming functions (CYCLE, ON, OFF, DIRECT, IMPULSE, ENABLE) see the chapter entitled “Digital output control logic” on page 9.
• 21 •
Now add the “Lighting group” icon to the Space and drag to it the lighting points that make up the group (fig. 3). The padlock that appears on the lighting points indicates that they belong to a group and can therefore no longer be controlled individually. Drag the push-button switches that correspond to the “Lighting group” and programme the properties of the single push-button switches as necessary. (fig. 4).
Contents
PC Mitho 2.0
Lighting point manually controlled by a dimmer 1
2
Modules used in the example: OH/AO4010
C B
A
Drag the lighting points with their related activating push-button switches and a network components container, from list A to within spaces B (fig. 1). In order to access the list of modules open the “Network components” section C, select a device necessary for dimming a lighting-point and a relative control push-button (in the example there is a module with 4 inputs and 4 analogue 0-10V outputs OH/AO4010). Drag the device to the desired network component container (fig. 2).
3
4 Drag each lighting-point corresponding to the analogue output that it controls (fig. 3). Lighting-points associated with analogue outputs are identified by the icon (fig.4).
• 22 •
Contents
PC Mitho 2.0
5
Drag the push-button switch corresponding to the lighting point to be controlled (or vice versa). The installation screen now displays the lighting-points connected to their associated push-button switches.
Kitchen light 1
Cooker Extractor Light
Dining room light
Kitchen light 1
Dimmer mode properties
D Field that allows a mode identifying name to be assigned.
D E
E Choose the value that must have the output at each turning on after a power cut.
F
F Min/Max dimming percentage for the lighting-point.
G
G Progressive output Turn On/ Turn OFF time.
H
6
H Select an input who's threshold value will cause the lighting-point to be automatically turned off.
By adding an appropriate analogue signal to “Dimmer mode” a light can be dimmed in wave mode.
• 23 •
Example of the visualisation of a dimmed lighting-point on Mitho terminals
. Note: Visualisation filters (see paragraph, “The “Installation structure” window” on page 13) can inhibit the presence of selected functions and modules. Selecting the filter “All” will render visible all available functions and filters
Contents
PC Mitho 2.0
7
Wave mode properties In “Wave” mode the turning on of an output occurs progressively respecting the brightness thresholds K and ramp timings L programmed to achieve the steps specified J (MAX 16). I Field that allows a modality identifying name to be assigned. J Specify the number of dimming steps to be assigned to the lighting-point (MAX 16).
I J K L
• 24 •
K indicate the brightness threshold for each step. L indicate the ramp time for each step.
Contents
PC Mitho 2.0
Lighting point automatically linearly controlled by dimmer 1
2
The example aims to programme two analogue outputs in such a way that their activation/dimming will take place according to the subordinate modality of one or more analogue signals.
A B
Modules used in the example: OH/DI2230 Drag a network components container from list A to within spaces B. Add the “Analogue output” icon to the desired space (fig. 1); in the example the analogue outputs are lighting-points (fig. 2).
3
4
Open the “Network components” section. Within the “Analogue devices” section access the list of modules, select the OH/DI2230 module and drag it to the network components container desired (fig. 3). From the “Analogue signals” section drag the icon corresponding to the signal produced by the brightness sensor which will be used in the installation (fig.4).
• 25 •
Contents
5
PC Mitho 2.0 Add the lighting-points (analogue outputs) to the appropriate outputs of the OH/DI2230 module and the icon for the signal generated by the brightness sensor to the analogue input.
6
Select the brightness sensor icon in order to see the properties of the emitted signal.
Signal property 0-10V A Specify the minimum and maximum values of the signal emitted by the device. (expressed in Volts) .
A
B Specify the signal measurement units.
B C
7
F . Note: “State change notificaG The tion” set-up is particularly imH portant because it determines
Now select the analogue output icon (lighting point).
Analogue output properties D Choose the value that the output will assume after an interruption to the electricity supply.
D
E Specify the way the output will function (specifically in the “linear” case).
C indicate the scale factor that the software should use to convert the voltage to the unit of measurement indicated.
State change notification Determine the modality and rate of transmission to the terminal of device state variation information. F Choose the way in which the status of the input/output must be sent. G Choose the message generation rate. H Choose the percentage of variation that will provoke the generation of a message on the BUS ignoring the periodicity indicated.
E
• 26 •
the rate and quantity of the messages that are transmitted on the system BUS.
Contents
PC Mitho 2.0
8
Choose the icon that represents the “Mode” chosen.
Linear mode properties This modality can be used to linearly bind an output to the selected analogue input.
Driveway Light 1
Driveway Light 2
A From the list of inputs choose the one to be controlled.
A B C D
9
If in the “Analogue output properties” (page 26) window “Analogue step modality” is selected it will be necessary to add one or more thresholds (MAX 8) to be added to the input signal (in the specific case a brightness sensor).
B Specify the Min/Max values of the control input. Example of analogue output visualisation. C Specify the Min/Max values of the output corresponding to the Min/Max values of the control input. D Proportionality constant to be applied between input and output (in the case of the example the proportionality is inverse).
10
Select the icon that represents the added “Threshold”.
Threshold Properties E Choose the percentage of the signal at which to place the threshold.
E F G H
F Specify the hysteresis (tolerance) to apply to the threshold. G Specify how the threshold should be recognised. H Reaching the threshold can activate one of the contacts (push-button switches, alarms, warnings...) in the system selectable via this drop-down menu.
• 27 •
Contents
PC Mitho 2.0
11
Select the icon that represents the “Mode” selected.
Analogue Step mode properties This mode can be used to linearly bind a programmed thresholds output to the selected analogue input. A Specify the control input Min/Max values. B Choose the analogue control input from the list. C Specify the output's initial output value.
A B C D
12
If in the “Analogue output properties” (page 26) window “Digital step modality” is selected it will be necessary to add one or more push-button switches (or enabled digital inputs) (MAX 8) which will be used to activate the output at an established value.
D Indicate at what value the output is to be activated upon reaching the threshold.
13
In the example illustrated 3 push-button switches, that are connected to an OH/6I module have been added. They have the task of turning on the driveway light at 30, 40 or 50% of luminous intensity. Now add the push-button switches to the “Digital step modality”function.
• 28 •
Contents
PC Mitho 2.0
14
Digital step modality properties Select the icon that represents the “Push-button switch properties” of the button linked to this modality. This modality can be used to bind an output to programmed thresholds that are linked to the selected digital input. Use the cursor to set the output dimmer value at the point of activation of the contact (push-button switch).
Tracking modality properties 15
If in the “Analogue output properties” (page 26) window “Tracking modality” is selected it will not be necessary to add any push-button switches.
In the example the analogue output (Driveway Light ) adapts to the signal detected by the control input.
16
A Specify the Min/Max values of the control input. B Choose the analogue control input from the list.
A B C D E F
C Choose a set-point input from the list. D Specify the control input value. E Specify the constant of proportionality between input and output. F Specify the hysteresis (tolerance) to be applied to the set-point value.
• 29 •
Contents
PC Mitho 2.0
Locally and timer controlled lighting points 1
2
3
Modules used in the example: OH/3RPI Drag the lighting points, related push-button switches and the module necessary to drive the contacts and relays to the desired space (fig. 1). Add the contacts to the push-button switches and the lighting points to the relays (fig. 2). Add the push-button switches to the lighting points that they will control (fig. 3).
. Note: One output can be timed even if it is not linked to a physical push-button switch.
4
5
From the “Save” menu drag a “Timer" to the space (fig. 4). Add the lighting points to the timer (fig. 5). Programming the timer can be carried out at the terminal.
Garden lights timer
mon tue wed thu
fri
sat
sun
Timer programming page on Mitho terminals.
• 30 •
Contents
PC Mitho 2.0
Thermal zone with radiators 1
2
Modules used in the example: OHZ -
OH/R
Place the components necessary for the management of the thermal installation within the desired space. In the case illustrated the installation calls for a boiler and an OH/Z zone thermostat. Alternatively a temperature sensor could be used in place of the OH/Z module (fig. 1).
. Note:
Insert a relay module (fig. 2).
Only one zone thermostat (OH/Z) can be inserted into each individual “Space”.
3
4
Add the eventual pump and zone valve to the “Heating” section of the OHZ module (fig. 3). Now add the devices to the relays that they will have to activate (fig. 4).
. Note: Therefore, the use of the pump and boiler icons is optional. They should be used based on the heating installation that is being constructed.
• 31 •
Contents
5
PC Mitho 2.0 6
OHZ zone thermostat properties Select the zone thermostat (fig. 5). Choose the type of heating. It is possible to choose a contact (push-button switch, alarm, warning...) which once activated will change the functionality of the thermostat.
Living area 21.2 °C Kitchen area
21.2 °C Bathroom
21.2 °C Entrance
Example of the visualisation of thermal zones on Mitho terminals.
• 32 •
Contents
PC Mitho 2.0
Thermal zone with fan coil units: fan speed control 1
2
Modules used in the example: OH/3RPI -
OH/MT2 -
OH/FAN
In the case illustrated a humidity sensor and temperature probe that may be used as an alternative to an OH/Z zone thermostat have been dragged from the list to the space. As according to the temperature sensor drag two valves, one for cooling and one for heating. Add to the installation structure the automation modules necessary to control the devices (fig. 1). Connect a hydrometer and temperature sensor to the appropriate inputs of the OH/MT2 module (fig. 2). Associate the valves with the relays that control them (fig. 3).
Internal temperature sensor properties 3
A Specify the type of heating.
4
B From the list specify the sensor manufacturer. C It is possible to choose (from the list of contacts available) a contact that once activated causes the change of state of the thermal zone.
A B C D E F
• 33 •
D Here it is possible to insert a correction value for the temperature detected by the probe, should the probe be placed in a critical position. E See (“State change notification” on page 26). F It is possible to choose (from the list of contacts available) a contact that once activated causes the change of season of the thermal zone (Heating/Cooling).
Contents
5
PC Mitho 2.0 6
Drag the OH/FAN module onto the icon for the temperature sensor by which it will be controlled (fig. 5).
OH/FAN module properties
G H I J K L M N
G Specify the number of fan speeds. H Choice of the status of the thermal zone upon activating the contact. I If under point H the “Manual” option is chosen it is possible to specify the temperature to be reached. J Choose the function mode. The module is fitted with an input (window contact) that may directly intervene with the operation of the module by ignoring the programming of the fan coil. K Choose the local contact typology. L Choose the result that the activation of the contact must produce. M If under point L forcing the turning on was chosen, here it is possible to indicate the fan speed. N Insert the time period that must elapse between the activation of the contact and the execution of the command.
• 34 •
Contents
PC Mitho 2.0
7
Drag the advanced options icon onto the OH/FAN module.
OH/FAN advanced options properties A Minimum turning on time of the fan. B Minimum temperature threshold below which the frost mode intervenes. C Maximum temperature threshold above which the overheating mode intervenes.
A B C D E F G
D Minimum temperature threshold below which a frost alarm message is sent on the bus. E Frequency of sending a module status message on the bus. F Mode of sending a frost alarm message on the bus. G If under point F the cyclical sending of the alarm message has been chosen, specify the time period that must elapse between one message and another.
H
H Select a remote contact window together with the contact topology.
8
Drag the PI (proportional integration) icon onto the OH/FAN module.
OH/FAN PI algorithm properties I Percentage difference from the set point (calculated by the algorithm) that causes the activation of speed 1, 2 and 3. J Specify the size of the environment to be air conditioned.
I J
• 35 •
PI (Proportional integration) control regulates the cycles of the turning on and off of the boiler as a function of the difference between the actual temperature and the set temperature: the smaller the difference in temperatures the fewer the power cycles.
Contents
PC Mitho 2.0
9
Alternatively, drag the diff. OH/FAN (differential integration) icon onto the OH/FAN module.
OH/FAN diff. algorithm properties K State the temperature margin, compared to the one set, in excess of which the algorithm intervenes by causing the activation of the fans at speed 1.
K L M
L State the temperature margin that added to the thermal differential causes the activation of the fans at speed 2.
The use of this thermal differential control system allows a simple and efficient on/off regulation regime for the boiler which is independent of the temperature set value. The boiler is turned on when the ambient temperature, as measured by the relative sensor, is lower than the set-point value less the configured differential; the turn-off off of the boiler is the opposite occurring as it does when the measured ambient temperature has risen above the set-point value plus the configured differential.
M State the temperature margin that added to the thermal differential causes the activation of the fans at speed 3.
Living Area 21.2 °C 45% Kitchen Area
21.2 °C Bathroom
21.2 °C Entrance
Example of the visualisation of thermal zones on Mitho terminals
• 36 •
Contents
PC Mitho 2.0
Thermal zone with fan coil units: complete control 1
2
Modules used in the example: OHZ 3x
OH/FAN-E
OH/FAN
In the case illustrated an OH/Z zone thermostat has been dragged from the list to the space. Drag the OH/FAN-E module corresponding to the thermostat (fig. 1). Now drag the desired OH/FAN modules corresponding to the OH/FAN-E module, in this way the OH/FAN-E module will automatically become the Master module (fig. 2).
3
OH/FAN-E module properties A See “OH/FAN module properties” on page 34. B Indicate the type of heating that the module will control.
A C Indicate the type of control valve that the module will have to drive.
B C
• 37 •
. Note: The OH/FAN-E module allows for the temperature regulation of a thermal zone by acting directly on the speed of the fan and the apertures of the hydraulic valves to which it is connected. Thus it is not necessary to locate within the installation other relay modules or devices such as valves or pumps since the valves are subject to the direct control of the module.
Contents
PC Mitho 2.0
4
Living area
OH/FAN (slave) module properties
Living Space
D Specify the number of fan speeds. E Choose the local contact typology.
D E F G H
AUTO
F Choose the result the activation of the contact must produce. G Insert the time period that must elapse between the activation of the contact and the execution of the command. H Choose the type of rapport that the module will have with the Master.
• 38 •
Example of the visualisation of thermal zones fitted with fans on Mitho terminals
Contents
PC Mitho 2.0
Manually controlled motorised sun screen 1
2
Modules used in the example: OH/MA -
OH/RI -
OH/AI4
In the case illustrated the “Window”, icon has been dragged from the list to the space which by convention represents a generic automated aperture; in this specific example it refers to a sun screen. Locate within the appropriate container the necessary modules, OH/MA e OH/RI (fig. 1). Now drag the OH/MA module to the aperture to be controlled, in this way the aperture is immediately controllable either by terminal or local push-button switches. Whenever remote control commands are to be added, drag the push-button switches corresponding to the OH/RI module contacts (fig. 2).
3
Once the push-button switches are connected to the contacts drag them to the commands that will activate them as a function of automation (fig. 3).
Living area Living room
Shutter 1
Shutter 2
Shutter 3
Shutter 4
Shutter 5
Shutter 6
Select the icons Open Close
Example of the visualisation of apertures on Mitho terminals
It is possible to specify the duration of the opening and closing action based on the automation device.
• 39 •
Contents
PC Mitho 2.0
Automatic activation of a contact subordinated to the data detected by measuring devices 1
Let's take for example the automation of the aperture in the preceding example (“Manually controlled motorised sun screen” on page 39). Other than by means of local commands we want the opening/closing of the screen to be controlled by measurement devices which in this case will provoke the closing of the screen in the presence of high wind and re-open it when the alarm condition passes.
2
Now within the appropriate container, locate the OH/4I module taken from the analogue devices. Connect the anemometer to the appropriate OH/4I module input.
Add to the installation schematic a pulse generator (in this specific case an anemometer)
3
4
Impulse generator properties A Indicate the minimum/maximum value detectable by the device.
A B C D E F
B Indicate the unit of measurement with which the data detected will be displayed. C Indicate the conversion factor from Hz to the unit of measurement chosen. D Choose with which mode the status of the input must be sent. E Choose the message generation frequency. F Choose the percentage of variation that will provoke the generation of a message on the BUS ignoring the periodicity indicated.
• 40 •
Now add the icons that will represent the alarms that we intend to associate with the events generated by the anemometer.
Contents
PC Mitho 2.0
5
Add a threshold to the pulse counter (anemometer) - take it from the analogue signals container.
Threshold Properties G Give a meaningful name to threshold which reflects its associated function. H Threshold (compared to the maximum value) in excess of which a message on the bus is generated.
Example of the visualisation of alarms on Mitho terminals
I Variation tolerance compared to the threshold.
G H I J K
6
J Indicate the modality for the detection of exceeding the threshold. K Choose a contact to be activated upon exceeding the threshold.
Add a second threshold to the the pulse counter (anemometer); take it from the analogue signals container. The threshold value must be greater than the previous threshold value.
• 41 •
7
m PAY ATTENTION It is important to add thresholds to the measurement device one at a time starting from the threshold with the lowest percentage and to take care not to overlap the hysteresis values.
Complete the programming by combining the action with the alarms that will be triggered by passing through the thresholds (rising or falling).
Contents
PC Mitho 2.0
Generic relay controlled by either a push-button switch or a sensor 1
2
Modules used in the example: OH/RI To allow for the management of devices not available from the list, generic relays can be added to the installation instead. Drag the “Generic load” icon from the list of devices to the desired space, then add the eventual push-button switch that will control it (fig. 1). After having added the OH/ RI module to the structure connect the load to one of the relays and the push-button switch to one of the contacts.
3
To terminate the programming link the push-button switch to the load that it is to control.
Ventilator Ri Generic device 3
Generic device 2 Generic device 4
Example of the visualisation of generic loads on Mitho terminals
• 42 •
Contents
PC Mitho 2.0
Create an irrigation programme 1
2
Modules used in the example: OH/R.01 Within the desired “Irrigation sectors”space place a logic set that will serve to group the irrigators (fig. 1). Place the relative irrigators within the sectors (fig. 2).
3
4
Insert an OH/R.01 module within the “Network components” container. Add the relays to the irrigators that they will activate (fig.3). Add a rain sensor to the structure, this will serve to interrupt irrigation should it rain. A Specify the type of contact fitted to the installed sensor.
A
• 43 •
Contents
PC Mitho 2.0
5 Hedge
Hedge 1
Hedge 2
Hedge 3
Hedge 4
Hedge 5
Hedge 6
Example of the visualisation of irrigation sectors on Mitho terminals
Irrigation Sector Properties Select an irrigation sector.
B C
B Choose an eventual remote contact that will provoke the activation of the irrigation sector. C Choose an eventual remote contact that will provoke the dissactivation of the irrigation sector (in this case the rain sensor).
• 44 •
Contents
PC Mitho 2.0
The use of custom logic 1
2
Modules used in the example: OH/RI To the example illustrated in the previous chapter (“Create an irrigation programme” on page 43), we wish to add a pump to the irrigation installation which must be activated/ disactivated at the precise moment when any one of the irrigators receives the command to activate/disactivate. Add a “Generic load” to the installation structure, in the case in question an irrigation pump. From within the “Network components” container locate a relay module (OH/RI); this will be necessary to drive the pump (fig. 1). Take a “Warning” from the list of “Analogue signals” locate it within the desired space and link it to the load (fig. 2). In this way the alert will in all respects function by means of a (virtual) activation button.
• 45 •
Contents
3
PC Mitho 2.0 4
From the “Custom logic” container, (see “Custom Logic” on page 10) take an “OR” logic function and place it within the terminal (that is the device that will control the activation of the irrigators). Within the “OR” logic function link the irrigators that will be controlled by it (fig.3).
OR logic function properties Select the logic function icon
A B
A Choose the destination for the result of the logic comparison B Choose the actuation mode.
5
Choose the irrigators one by one C Choose the type of message that the device will generate as a funtion of its state.
C
• 46 •
Contents
PC Mitho 2.0
Load control 1
2
Modules used in the example: OH/MPE6KW -
OH/RP
Place the loads to be controlled within the desired spaces (fig. 1). Place an OH/MPE6KW electrical power measurement module within the“Network components” container. (fig. 2).
3
4
In the same way add the necessary OH/RP relay modules Link the relays to the loads to be controlled (fig.3). Once they are connected to the modules drag the loads corresponding to the OH/ MPE6KW meter which will control them.
• 47 •
Contents
PC Mitho 2.0
5
OH/MPE6KW module properties Select the module A Indicate the minimum electricity power variation that must be detected and transmitted on the bus (expressed in Watts).
Dryer
Washing machine
Oven
Dish washer
B Indicate the minimum period of time (expressed in seconds) which must elapse between one consumption variation check and the next. C Indicate the amount of time (in seconds) that must elapse between checks in variation in consumption in the case that there are no changes detected above rate indicated at point B.
Example of the visualisation of a threshold alarm on a Mitho terminal.
. Note: If the installation calls for more electrical power meters then they can be dragged to the “Power meter group” icon (after it has been added to the structure). In this way, other than the data provided by a single meter, it will be possible to see the comprehensive readings of the group of meters on the terminal.
A B C
• 48 •
Contents
PC Mitho 2.0
Remote control contact activation 1
2
Modules used in the example: OH/IR Place an OH/IR module within the“Network components” container which will allow contacts present within the installation to be controlled remotely. (fig. 1). Add a push-button switch to the structure (fig. 2).
• 49 •
Contents
3
PC Mitho 2.0 4
Drag the newly added push-button switch either to the device or to the action that it will control (fig. 3). Add the "virtual" push-button switch to the remote control button that it will command.
. Note: The "virtual" buttons added to the remote control can have all the functions of a normal push-button switch including the activation of scenarios.
• 50 •
Contents
PC Mitho 2.0
Group and programme activations through Scenarios 1
2
By means of the terminal or local or remote push-button switches, scenarios allow for progressive or instantaneous complex actions or activation sequences. The icon that represents the scenario can be located within a “Zone” or a “Space” (fig. 1). Within the icon that contains the “Actions” (if necessary) it is possible to locate a “Delay scenario” icon.
3
Drag to the “Actions” icon the “Zones”, the “Spaces” or the individual devices that are to be controlled by means of the scenario. Select the Scenario delay icon.
. Note: Other scenarios can be linked to the “Actions” icon. In this way the activation of one scenario triggers the execution of other scenarios associated with it.
Scenario Delay Properties A Indicate the delay to be applied to the execution of the Scenario.
A B
B Indicate the way in which the delay is to applied. Uniform: The execution of the scenario takes places after the length of time indicated at point A. Progressive: The execution of the scenario is immediate but the activations contained within it occur progressively as a function of the delay indicated at point A.
• 51 •
. Note: This function may be useful to avoid sudden overloads of the electrical system if several high consumption devices are activated simultaneously.
Contents
PC Mitho 2.0
4
When selecting the elements found within the “Actions” icon there appears in the properties window a list of proposed actions that can be carried out within the Scenario.
If the scenario calls for the turning on of dimmer enabled lights it is possible to specify both the brightness percentage of the lights and the transition duration.
5
6
Within the “Actions” icon can be found other delays and devices that can be used in order to obtain the desired result.
Enter
Exit
Morning
Night
Party
Cinema
Example of the visualisation of scenarios on a Mitho terminal
The “Push-button switch” icon is there to house local physical push-button switches which will be used to active the scenario.
. Note: Local push-button switches that are intended to activate scenarios will permit complex activation combinations while far from the terminal simply by pressing a button.
• 52 •
Contents
PC Mitho 2.0
Remote control of the installation using the OH/GSM dialler 1
2
The installation can be remotely controlled using the OH/GSM dialler, which lets you activate scenarios, query and modify the status and the temperature of thermal zones, receive notifications if technical alarms occur or in the event of power outage and restoration. It is also possible to receive information on the installation's status at specified days and times. Place the GSM module within the “Network components” container. The icons that are seen as appendices to the module represent the functions that can be controlled by means of SMS messages from the GSM module itself: Thermal zones, Scenarios and Alarms (fig. 1). All that is needed is to drag the elements to be controlled to the corresponding icons (fig. 2).
• 53 •
Contents
PC Mitho 2.0
1
A B
C
GSM properties
m PAY ATTENTION
A Allow the transmission of periodic installation state messages (every 12 or 24 hours).
Always enter the appropriate international dialling code before the numbers that are being added to the address book.
B Indicate the SMS language to be used so as to be able to correctly read the messages. C These 10 spaces are used to type in the telephone numbers that make up the phone book of the dialler. All of the numbers inserted in this phone book can remotely control the installation via SMS or conversely be informed of the installation's status. D Indicate the "Service Centre" number that can easily be found on service provider's website. The messages received by the dialler from this number (which normally only provides information on expiration of credit) will automatically be sent to the first number of the phone book.
D
• 54 •
. Note: For further information on the programming of the GSM module, consult the instructions for the module itself.
Contents
PC Mitho 2.0
Management of compatible anti-intrusion control units 1
2
Modules used in the example: OH/GW Place an OH/GW module within a “Network components” container which will allow communication between the anti-intrusion control unit and the building automation installation (fig. 1). Select the OH/GW module and from the dropdown menu select the device to be connected to it (fig. 2).
Example of the visualisation of an anti-intrusion control unit on a Mitho terminal.
. Note: On the Mitho terminal the subdivision into areas or scenarios is displayed according to the programming of the connected anti-intrusion control unit.
• 55 •
Contents
PC Mitho 2.0
Integration of inputs and outputs for Proxinet control panels in the BPT home automation system. 1
Modules used in the example:
2
OH/GW Place an OH/GW module within a “Network components” container which will allow communication between the anti-intrusion control unit and the building automation installation (fig. 1). Insert the Proxinet control panel in the desired Space and then position the Security I/O module inside the control panel; 10 virtual buttons and 10 relays will immediately be displayed. Select the OH/GW module and from the dropdown menu select the Proxinet control panel to be connected to it (fig. 2).
. Note: The buttons and relays can be used for home automation functions if they are programmed for this purpose using the PX manager software. 3
The outputs can be associated with lights or generic loads such as any other relay in the system (for instance, to turn on a light point or control a generic activation).
The Virtual buttons (in the case of fig. 4 a volumetric sensor) can be used to operate a light point or other home automation activations such as a scenario, for instance.
4
m ATTENTION
PCMitho cannot be used to configure the inputs of the Proxinet control panel to operate the outputs of the control panel itself. To do this, the control panel must be configured using PXManager. The control panel inputs, when used as sensors, in the event of an alarm will not signal their status to the home automation system, but an alarm will be generated by the control panel.
• 56 •
Contents
PC Mitho 2.0
Handling of audio compatible control units 1
2
Audio Control Unit Properties Place within the installation structure the icon that represents the audio control unit.
A Select the OH/ETH1 to which the control unit is physically connected. B Indicate the IP address of the audio control unit. C Select the type of control unit installed.
Bedroom 01 Audio
A B C
m PAY ATTENTION
If the installation calls for one or more OH/ ETH.01 modules then before commencing with the complete programming of the installation, it is essential that every OH/ETH.01 should be linked to the OH/ GW module and that every node (OH/ ETH.01+OH/GW) be individually programmed; see chapter: “Configuring an Ethernet communication interface” on page 63.
Example of the visualisation of an audio control unit on a Mitho terminal.
. Note: On the Mitho terminal the subdivision into areas or scenarios is displayed according to the programming of the connected anti-intrusion control unit.
• 57 •
Contents
PC Mitho 2.0
Installation commissioning Once virtual programming of the installation has been done (which can be performed completely off-line), in order to recognise the devices that are physically connected, followed by the actual programming of the installation, you will need to connect the PC to the installation (as shown in the diagram) .
USB communications interface configuration 1
2
Insert the USB cable into the USB port of the PC so as to start the guided installation of the new hardware (fig. 1). Press “Next” to proceed with installation (fig. 2).
3
4
A
RESET
Select the path of the driver based on the installed operating system B.
MM
CN1
B
LA
R+R–T+T– –
Select the option: “search for the best driver available on these paths” A.
The drivers are available in a subdirectory of the installation directory of Pc Mitho: C:\...\bpt\PcMitho-2.00\ Usb-Driver\Mitho
OH/GW
. Note: At the end of the procedure, the green LED located on the OH/GW device must be on. If it is not, then repeat the installation procedures.
You will now need to repeat the previous operations to install the second part of the hardware.
Wait for installation to be completed and press “Stop”.
• 58 •
Contents
PC Mitho 2.0
Installation programming and diagnostics 1
Collect the ID codes of the connected modules
A
At the end of the installation construction phase, carried out by means of PC Mitho, the devices will have the icon indicating the lack of an identification code binding the "virtual" module to the real module actually connected within the installation.
Press button A to open the “Device search” window. Press button B to start the automatic search for the ID codes of all the modules actually physically connected within the installation.
Device/module without an ID or to which a specified function has not been associated Indicates that the device is not controlled by any push-button switches or input; the device is nonetheless controlled by the terminal. Unprogrammed module
Alternatively press button C to read a specific ID by pressing the appropriate button (service) to be found on all modules.
I3 I2 I1 C LA
B
C
D
1
C NA
2
C NA
3
C NA
Made in Italy
67600700
OH/3RPI SERVICE
E By pressing button D it is possible to manually indicate the type of module and its ID code.
. Note: • To send the ID of the Mitho terminal, proceed as follows: From the main screen of the Mitho terminal, select the icon “setup”, “service”, and press the button “send sn”. • To send the ID of the zone thermostat OH/Z.02, press the button located on the front of the module. • The ID code can be found on the adhesive sticker present on all modules.
Button E removes all found IDs from the list
• 59 •
Contents
PC Mitho 2.0
ID code association to the connected modules 2
3
ID association by means of dragging Once the identification codes of the modules have been collected, it is then possible to proceed to the association of the "virtual" module with the corresponding "real" ones by means of dragging. The module that is associated with the identification code is now accompanied by the icon which indicates that the device has not yet been programmed.
m PAY ATTENTION If and when the system envisages the presence of more OH/GWs, it will be necessary to proceed as follows. Once the structure of the installation has been built, assign the IDs to the OH/GWs and programme them individually before proceeding to the identification and programming of the other devices within the installation.
• 60 •
Contents
4
PC Mitho 2.0 5
ID association by means of the service button on the module It is also possible to directly click on the module with the right mouse button and then select “Read ID”. A message will appear inviting you to press the “service” button on the module to be identified.
I3 I2 I1 C
1
C NA
2
C NA
3
C NA
Made in Italy
67600700
OH/3RPI
LA
SERVICE
ID association from the module properties window Another option is to select the module with which to associate the ID and in the Properties window, under "Identifier", choose the desired ID code for the module. Once the ID code has been assigned then within the properties of the module, the firmware version will also appear. This can be useful in the case of servicing.
m PAY ATTENTION During the updating of the home automation modules in already functioning systems (buildings already lived in), it is necessary to ascertain that no command/activation occurs that could cause the malfunction of the module (service light fixed on). If the updating of the module is not successful (Programming failed) carry out a new update of the module without leaving the programming window to avoid damaging the module.
. Note: • This ID acquisition system requires the presence of two persons at the installation.
• 61 •
Contents
PC Mitho 2.0
Updating home automation module firmware 1
Before programming the modules verify whether or not a new version of the firmware is available.
Select the module using the right mouse button and then select “Update firmware”.
m PAY ATTENTION • When updating the devices, disable the energy saving functions or other functions which may cause your PC to go into standby mode. This will prevent damage to the devices. • The necessary update files should be located in the directory C:\Programmi\bpt\PcMitho\ modules • To update a device, it is necessary to connect the PC to the gateway (OH/GW) located up the line from the device itself. • Once you have updated the OH/GW module, you must disconnect the USB cable from the device, press the “RESET” button on the device, reconnect the cable and re-programme the module (OH/GW).
• 62 •
2
Choose the firmware update desired and press “Start”.
Contents
PC Mitho 2.0 bus MM
MithoXL
Configuring an Ethernet communication interface
AL
– +
M1
B
MM
VAS/101 –
18V +
®
M2
230V
OH/RS422
OH/GW
Connect the PC to the USB socket of the OH/GW module connected to the Master OH/ETH1.
MM
M2
M4 M3
CN1
Assign the identifying code to the OH/GW module using one of the aforementioned methods.
M1
LA
M1
LA
M3
CN2
OH/ETH1 J9
CN1
CN3
M2
VAS/100MH
M1
bus BPT
SEC
– +
18V
+ 18V –
LAN ETHERNET
230V
R+ R– T+ T– – MM
230V
230V
PRI
M2
S TX+ TX– RX+ RX– – SW
M4
Made in Italy 24140770
OH/RS422 CN1
CN2
M3 CN1 LA
M1
OH/ETH1 CN2
J1
J9
LA
M3
LA M2
BK
bus BPT bus MM
LAN ETHERNET
J2
OH/A.01
M1
50Hz 18V 10VA
OH/RS422
OH/GW
A
CN2
J1
CN1 + –
LA
BK
A select the OH/ETH1 device physically connected to the OH/GW module.
Made in Italy 24140770
OH/RS422 CN1
J2
OH/A.01
Select the OH/GW gateway icon.
S TX+ TX– RX+ RX– – SW
S RX+ RX– TX+ TX– – SW
M1
R+ R– T+ T– –
1
M2
S RX+ RX– TX+ TX– – SW
The assignment of IP addresses to the OH/ETH1 must be performed using the configuration pages of the device (see the OH/ETH1 instructions).
ROUTER WI-FI
M2
LAN ETHERNET
If the installation requires the presence of one or more OH/ETH1 modules, communication between them must take place via the Ethernet network. To allow the various OH/ETH1 to recognise one another on the network, each one must be assigned an IP address and communication must take place via a single port for all the various devices.
SW4
CN1 + –
CN1
CN3
VAS/100MH SEC
– +
18V
+ 18V –
230V
50Hz 18V 10VA
230V
230V
• 63 •
PRI
Contents
PC Mitho 2.0
2
3
Select the OH/ETH1 and OH/ GW modules with the right mouse button and proceed to the individual programming of the devices Select the OH/ETH1 module icon. B type the IP address assigned to the module.
B 4
Substitute the USB connection protocol with the IP address of the OH/ETH1 Master. From now on, communication between the PC and installation will take place over the LAN network.
5
Proceed identically for all the OH/GW modules connected within the installation to the OH/ETH1 module; this will result in all of the OH/ETH1 modules being able to communicate via the Ethernet network.
How to retrieve an installation file by means of the OH/ETH1 Master If the installation foresees the connection of an OH/ETH1 (Master) then when the installation is programmed a copy of the installation file itself is automatically saved within the gateway memory. By means of the "Retrieve" button the PC Mitho application allows for the retrieval of the file stored in the gateway memory. Type into the appropriate field the IP address of the OH/ETH1 gateway from which it is intended to retrieve the installation file and press "OK".
• 64 •
Contents
PC Mitho 2.0
Installation programming 1
2
Press the “Programme” button to completely programme the installation (fig. 1). Alternatively it is also possible to programme a single module. Select the module with the right mouse button and then select “Programme device” (fig. 2).
m PAY ATTENTION During the programming phase, do not disconnect the power supply or the USB cable from the OH/GW module.
• 65 •
Contents
PC Mitho 2.0
Create a personalised interface with graphical maps Preliminary operations On compatible terminals it is possible to create supplementary interfaces that allow for the visualisation of the installation by means of maps, that is to say images that represent all or part of the installation. Within the map interface the following functions can be seen and controlled: Lights, temperature controls, apertures and scenarios. The first thing to do is to decide the way in which the installation is to be represented visually. In the example, as regards the initial view, we want to visualise the plan from the ground floor of a house and from there access the various rooms of the building.
The characteristics of the images The images can have a maximum size of 800x480 pxl (pixels). Compress the images such that they have a file size of 30-40 KB; larger sizes are also acceptable but may cause the slowing down of the programming of the installation and will not give rise to any appreciable difference in quality as seen on the terminal.
• 66 •
Contents
PC Mitho 2.0
The “Map view” window 1
Select the “Map view” tab. A Image interface viewing area. B Page interface viewing area. C Installation view.
C A
D Selected element properties area.
Insert a new page. Click the right mouse button within area B, select “Insert page”.
D
B
• 67 •
Contents
PC Mitho 2.0
2
Map properties page E Name the page. F Choose “New image” and select the desired image.
E F
• 68 •
m PAY ATTENTION The images are stored in alphabetical/numerical order, for this reason it is important that the image that is to take pole position should be correctly named.
Contents
PC Mitho 2.0
3
Proceed in the same way with all the pages that will constitute the interface.
Building a navigation scheme The first page on the list (01_Plan) is the one that will be initially viewed on the terminal whenever the "Map" section is accessed, for this reason it will also need to contain buttons to allow for navigation within the building. Drag the pages onto the plan in accordance with the area that they represent.
The result on the Mitho terminal.
• 69 •
Contents
PC Mitho 2.0
4
Select the successive pages and locate one or more navigation icons to be placed among the available pages G.
H
Add functions to the screens From window H drag the desired functions onto the page. Within the map interface the following functions can be seen and controlled: Lights, temperature controls, apertures and scenarios.
G
The result on the Mitho terminal.
5
Export the map interface Once the maps have been configured and the navigation system established, it is necessary to export the map interface. From the main menu select “Modify” and then “Export”. There are 3 different export options, that is to say 3 different export destinations.
• 70 •
Contents
PC Mitho 2.0
bus MM
MithoXL
Choosing the Mitho XL terminal as the export destination, the map interface is saved to the selected terminal or to all terminals upon which the interface is to be displayed.
AL
– +
ROUTER WI-FI
M1
B
M2
SW4
®
MM
M1
Choosing “File System” as the export destination a file is created which must be saved on the MicroSIMs of the terminals upon which the interface is to be displayed.
M2
230V
OH/GW R+ R– T+ T– – MM
M2 M1
M2
RX+ RX– – SW
OH/RS422 S TX+ TX– RX+ RX– – SW
M4
S RX+ RX– TX+ TX– – SW
–
18V +
S TX+ TX– LAN ETHERNET
VAS/101
Made in Italy 24140770
OH/RS422 CN1
CN2
M3
. Note: • This export system is particularly useful in the case of an interface being composed of numerous or particularly large images that can give rise to long periods of time being required for exporting.
CN1 LA
M1
Choosing the OHETH module as the export destination will require the specifying of the IP address. The map interface is saved within the module and visible via a PC or other compatible device.
OH/ETH1 CN2
J1
J9
J2
OH/A.01 LA
M3
CN1 + –
LA
CN1
CN3
M2
BK
VAS/100MH
M1
SEC
– + 18V
+ 18V –
230V
50Hz 18V 10VA
230V
bus BPT
230V
• 71 •
PRI
Contents
PC Mitho 2.0 View permissions
1
2
The “View permissions” window allows the blocking of the viewing and therefore of the control of selected “Zones”, “Spaces” and “Scenarios” of an installation by one or more terminals.
A
B
Within area A are visible all of the “Zones”, “Spaces”and “Scenarios” that constitute the installation. Within area B are visible all of the terminals present within the installation.
3
At the end of the permissions configuration step, when selecting one of the terminals available in area B, the “Zones”, “Spaces” and “Scenarios” in area A that are hidden from the view/control of the terminal will be greyed out.
• 72 •
Assuming that it is required to block the viewing of the 1st and 3rd floors by the terminal on the 2nd floor then proceed as follows.
C
Select the C terminal; then with the right mouse button select the “Zone”, the “Space” or the“Scenario” of the installation to be hidden or not controlled by the terminal and choose the option “Hide”.
Contents
4
PC Mitho 2.0 By means of facilitating the creation of permission categories in particularly complex installations within which numerous terminals must interact, it is possible to create groups of terminals all sharing the same permissions.
5
Drag the terminals that will form the group to the “Group” logo.
Select the root of the installation with the right mouse button and create a new “Group”.
• 73 •
6
From this moment on the components that form the group all share the same permissions.
Contents
PC Mitho 2.0 Actions view
Connections view
The “Actions view” window allows for a clear and simple verification of the correspondence of the installation cabling to that stipulated by software.
The “Connections view” window allows the verification of the number of devices connected to any branch of the installation, in this way it is always possible to have the limits of the installation firmly under control.
Pressing a push-button switch within the structure causes the corresponding light to turn on, both physically and on the nominated "Actions view" screen. These functions allow for an immediate visualisation of eventual cabling errors and the tracing of the origins of any such errors.
• 74 •
Contents
PC Mitho 2.0 Diagnostics Monitor messages Pressing the “Diagnostics” button brings up the “Monitor messages” window.
A
Pressing button A activates the registration of all messages being transmitted on the system BUS. The tabs within area B identify the origins of the messages.
B
. Note: • Monitoring the messages transmitted on the BUS can be useful in identifying problems or connection errors between modules and also in identifying their origin.
• 75 •
Contents
PC Mitho 2.0 Print The “Print” window, other than the classic printer options, contains the A window, by means of which it is possible to choose the part of the installation to be printed. The printed report lists the devices that appear within the part of the installation selected in area A together with the relative network components, ID codes and all other useful printable information pertaining to the structure of the installation.
A
m PAY ATTENTION Once the installation has been commissioned the installer must consign all documentation necessary for eventual future technical interventions (device IN/OUT interconnection tables, system files and passwords).
• 76 •
Updates to this manual are available on our website www.bpt.it.
BPT S.p.A. Via Cornia, 1 33079 Sesto al Reghena (PN)-Italy http: www.bpt.it e-mail:
[email protected] The manufacturer reserves the right to make changes to the product in order to improve its functionality.