OCS05E-1.qxp 08.3.31 9:52 AM Page 1 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS April 2008 TECHNICAL DATA BOOK R410A [Model names] [Model names] No. OCS05 REVISED EDITION-E INVERTER PLA-RP·BA(2) PLA-RP·AA(2) PEAD-RP·EA(2) PEAD-RP·GA PEA-RP·GA PKA-RP·GAL PKA-RP·FAL(2) PCA-RP·GA(2) PCA-RP·HA PSA-RP·GA Revision: • PLA-RP·BA2 and PUHZRP·HA3 are added in REVISED EDITION-E. • Some descriptions have been modified. • Please void OCS05 REVISED EDITION-D. PUHZ-RP35/50/60/71/100/125/140VHA2 PUHZ-RP35/50/60/71/100VHA3 PUHZ-RP100/125/140YHA2 PUHZ-RP100YHA3 PUHZ-RP200/250YHA2 CONTENTS 1. REFERENCE SERVICE MANUAL·············································2 2. SPECIFICATIONS ······································································3 3. OUTLINES AND DIMENSIONS················································30 4. WIRING DIAGRAM···································································54 5. REFRIGERANT SYSTEM DIAGRAM ······································75 6. PERFORMANCE CURVES ······················································80 7. CORRECTION FACTORS ························································82 8. APPLICABLE EXTENSION PIPE FOR EACH MODEL ··········83 9. AIR FLOW DATA ······································································92 10. NOISE CRITERION CURVES·················································111 11. OPTIONAL PARTS···································································124 kW Model OCS05E-1.qxp 1 08.3.31 9:52 AM Page 2 REFERENCE SERVICE MANUAL For information on service, please refer to the service manual as follows. 1-1. INDOOR UNIT Model name PLA-RP35/50/60/71/100/125/140BA PLA-RP71/100/125BA2 Service Ref. Service Manual No. PLA-RP35/50/60/71/100/125/140BA(1).UK PLA-RP71/100/125BA2.UK OCH412 OCB412 PLA-RP35/50/60/71/100/125/140BA OCH416 OCB416 PLA-RP35/50/60/71AA.UK PLA-RP35/50/60/71AA PLA-RP35/50/60/71AA PLA-RP100/125/140AA2 PLA-RP100/125/140AA2.UK PCA-RP50/60/71/100/125/140GA PCA-RP50GA2 PCA-RP50/60/71/100/125/140GA PCA-RP50GA2 PCA-RP71/125HA PCA-RP71/125HA PKA-RP35/50GAL PKA-RP35/50GAL PKA-RP60/71/100FAL PKA-RP50FAL2 PKA-RP60/71/100FAL PKA-RP50FAL2 PSA-RP71/100/125/140GA PSA-RP71/100/125/140GA PEAD-RP50/60/71/125/140EA PEAD-RP35/100EA2 PEAD-RP50/60/71/125/140EA.UK PEAD-RP35/100EA2.UK PEAD-RP60/71/100GA PEAD-RP60/71/100GA.UK PEA-RP200/250/400/500GA PEA-RP200/250/400/500GA.TH-AF PEA-RP200/250GA.TH-AFMF OC335 OC327 OC357 OC328 OC329 OC330 OC331 OC332 HWE05210 HWE05060 HWE0708A 1-2. OUTDOOR UNIT Model name Service Ref. Service Manual No. PUHZ-RP35/50/60/71VHA2 PUHZ-RP100/125/140VHA2 PUHZ-RP100/125/140YHA2 PUHZ-RP35/50/60/71/100VHA3 PUHZ-RP100YHA3 PUHZ-RP35/50/60/71VHA2(1) PUHZ-RP100/125/140VHA2(1) PUHZ-RP100/125/140YHA2(1) PUHZ-RP35/50/60/71/100VHA3 PUHZ-RP100YHA3 PUHZ-RP60/71/100VHA3#1 PUHZ-RP100YHA3#1 PUHZ-RP125/140VHA2#2 PUHZ-RP125/140YHA2#2 PUHZ-RP200/250YHA2 PUHZ-RP200/250YHA2 2 OC374 OCH428 OCB428 OCS05E-1.qxp 08.3.31 9:52 AM Page 3 SPECIFICATIONS 2 2-1. CEILING CASSETTE TYPE Model name Indoor unit Outdoor unit Cooling Capacity Btu/h kW kW Total input EER Energy label class SHF Capacity Heating Btu/h kW kW Total input COP Energy label class Booster heater Phase Cycle Voltage Breaker size Air flow (Low-Medium2-Medium1-High) Power supply Indoor unit kW [ Hz V A CMM CFM Pa External pressure Sound level (Low-Medium2-Medium1-High) External finish (Panel) Dimension Unit (Panel) W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch CMM CFM dB(A) dB(A) Weight Unit (Panel) Field drain pipe O.D. Outdoor unit Air flow Sound level at cooling Sound level at heating External finish Dimension W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch mm inch m m Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Height difference Length Refrigerant pipe length NOTE: 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Upper Lower Upper Heating Lower Cooling limit limit limit limit D.B. D.B. D.B. D.B. Indoor 35˚C, W.B. 22.5˚C 19˚C, W.B. 15˚C 28˚C 17˚C dB(A) D.B. D.B. D.B. D.B. PLA-RP35BA PUHZ-RP35VHA2 PUHZ-RP35VHA3 12,300 3.6(1.6-4.5) 1.07 3.36 A 0.84 14,000 4.1(1.6-5.2) 1.12 3.66 A – PLA-RP50BA PUHZ-RP50VHA2 PUHZ-RP50VHA3 17,100 5.0(2.3-5.6) 1.55 3.23 A 0.81 20,500 6.0(2.5-7.3) 1.66 3.61 A – 1 50 230 16 11-12-13-15 390-425-460-530 0 12-14-16-18 425-495-565-635 0 27-28-29-31 28-29-31-32 White Munsell 6.4Y 8.9/0.4 840 (950) 840 (950) 258 (35) 33-1/16 (37-3/8) 33-1/16 (37-3/8) 10-3/16 (1-3/8) 22(6) 49(13) 32 1-1/4 35 1,240 44 46 Ivory Munsell 3Y 7.8/1.1 800 300+23 600 31-1/2 11-13/16 + 7/8 23-5/8 45(VHA2)/42(VHA3) 99(VHA2)/92(VHA3) 12.7 1/2 6.35 1/4 Max. 30 Max. 50 Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Outdoor 46˚C -5˚C w 21˚C, W.B. 15˚C -11˚C, W.B. -12˚C 3 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit Single phase 230V 50Hz w If optional air protect guide installed. D.B.-15: OCS05E-1.qxp 08.3.31 9:52 AM Model name Page 4 Indoor unit Outdoor unit Cooling Capacity Total input 20,500 24,200 6.0(2.7-6.7) 7.1(3.3-8.1) kW 1.65 2.12 3.64 3.35 SHF Total input 23,900 27,300 8.0(3.5-10.2) kW 1.85 2.21 3.78 3.61 A A – [ Cycle Hz 50 Voltage V 230 1 A External pressure Sound level (Low-Medium2-Medium1-High) 25 CMM 12-14-16-18 14-16-18-21 CFM 425-495-565-635 495-565-635-740 Pa 0 0 dB(A) 28-29-31-32 28-30-32-34 External finish (Panel) White Munsell 6.4Y 8.9/0.4 Dimension W : mm 840 (950) Unit (Panel) D : mm 840 (950) H : mm 258 (35) W : inch 33-1/16 (37-3/8) D : inch 33-1/16 (37-3/8) H : inch 10-3/16 (1-3/8) Weight kg 23(6) Unit (Panel) lbs 51(13) Field drain pipe O.D. Air flow mm 32 inch 1-1/4 CMM 55 CFM 1,940 Sound level at cooling dB(A) 47 Sound level at heating dB(A) External finish Weight Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Upper Lower Upper Heating Lower limit limit limit limit W : mm 950 D : mm 330+30 H : mm 943 W : inch 37-3/8 D : inch 13 + 1-3/16 H : inch 37-1/8 kg 75(VHA2)/68(VHA3) lbs 165(VHA2)/150(VHA3) mm 15.88 inch 5/8 mm 9.52 inch 3/8 Height difference m Max. 30 Length m Max. 50 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Cooling 48 Ivory Munsell 3Y 7.8/1.1 Dimension Refrigerant pipe size – Phase Air flow (Low-Medium2-Medium1-High) Outdoor unit 0.73 7.0(2.8-8.2) kW Breaker size Indoor unit A 0.76 kW Energy label class Power supply A Btu/h COP Booster heater PUHZ-RP71VHA2 kW Energy label class Capacity PLA-RP71BA Btu/h EER Heating PLA-RP60BA PUHZ-RP60VHA2 PUHZ-RP60VHA3 D.B. D.B. D.B. D.B. Indoor 35˚C, W.B. 22.5˚C 19˚C, W.B. 15˚C 28˚C 17˚C D.B. D.B. D.B. D.B. Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Outdoor 46˚C -5˚C w 21˚C, W.B. 15˚C -11˚C, W.B. -12˚C 4 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit Single phase 230V 50Hz w If optional air protect guide installed. D.B.-15: OCS05E-1.qxp 08.3.31 9:52 AM Model name Page 5 Indoor unit Outdoor unit Cooling Capacity Total input PLA-RP71BA2 PLA-RP100BA2 PLA-RP125BA2 PUHZ-RP71VHA3 PUHZ-RP100VHA3 PUHZ-RP125VHA2 Btu/h 24,200 34,100 42,700 kW 7.1(3.3-8.1) 10.0(4.9-11.4) 12.5(5.5-14.0) 1.94 2.44 3.73 3.66 4.10 3.35 kW EER Energy label class SHF Heating Capacity Total input 27,300 38,200 47,800 8.0(3.5-10.2) 11.2(4.5-14.0) 14.0(5.0-16.0) kW kW 1.90 2.54 3.51 4.21 4.41 3.99 A A A – – – Phase [ Cycle Hz 50 Voltage V 230 Breaker size Indoor unit A 0.71 kW Energy label class Power supply A 0.74 Btu/h COP Booster heater A 0.73 Air flow (Low-Medium2-Medium1-High) External pressure Sound level (Low-Medium2-Medium1-High) 1 A 25 CMM 14-16-18-21 20-23-26-30 22-25-28-31 CFM 495-565-635-740 710-810-920-1060 780-880-990-1090 Pa 0 0 0 dB(A) 28-30-32-34 32-34-37-40 34-36-39-41 External finish (Panel) White Munsell 6.4Y 8.9/0.4 Dimension W : mm Unit (Panel) D : mm 840 (950) 840 (950) H : mm 258 (35) W : inch 298 (35) 33-1/16 (37-3/8) D : inch 33-1/16 (37-3/8) H : inch 10-3/16 (1-3/8) Weight kg 23(6) 27(6) Unit (Panel) lbs 51(13) 60(13) Field drain pipe O.D. Outdoor unit 32 Air flow 11-3/4 (1-3/8) mm 32 inch 1-1/4 CMM 55 100 CFM 1,940 3,530 Sound level at cooling dB(A) 47 49 50 Sound level at heating dB(A) 48 51 52 External finish Dimension Ivory Munsell 3Y 7.8/1.1 W : mm 950 D : mm 330+30 H : mm 943 1,350 W : inch 37-3/8 D : inch 37-1/8 kg 68 116 lbs 150 256 Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: 53-1/8 mm 15.88 inch 5/8 mm 9.52 inch 3/8 Height difference m Max. 30 Length m 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Upper limit Lower limit Upper limit Heating Lower limit Cooling 13 + 1-3/16 H : inch Max. 50 Max. 75 Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Indoor Outdoor D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 21˚C, W.B. 15˚C D.B. 28˚C D.B. -11˚C, W.B. -12˚C D.B. 17˚C 5 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit Single phase 230V 50Hz w If optional air protect guide installed. D.B.-15: OCS05E-1.qxp 08.3.31 Model name 9:52 AM Page 6 Indoor unit Outdoor unit Cooling Capacity Total input PLA-RP100BA PLA-RP125BA PLA-RP140BA PUHZ-RP100VHA2 PUHZ-RP125VHA2 PUHZ-RP140VHA2 Btu/h 34,100 42,700 47,800 kW 10.0(4.9-11.4) 12.5(5.5-14.0) 14.0(5.5-15.3) kW 3.02 3.87 4.65 3.31 3.23 3.01 A A B 0.74 0.71 0.71 EER Energy label class SHF Heating Capacity Total input Btu/h 38,200 47,800 54,600 kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0) kW 3.10 3.88 4.43 3.61 3.61 3.61 A A A – – – COP Energy label class Booster heater Power supply kW Phase [ Cycle Hz 50 Voltage V 230 Breaker size Indoor unit 1 A Air flow (Low-Medium2-Medium1-High) External pressure Sound level (Low-Medium2-Medium1-High) 32 20-23-26-30 22-25-28-31 24-26-29-32 CFM 710-810-920-1060 780-880-990-1090 850-920-1020-1130 Pa 0 0 0 dB(A) 32-34-37-40 34-36-39-41 36-39-42-44 External finish (Panel) White Munsell 6.4Y 8.9/0.4 Dimension W : mm 840 (950) Unit (Panel) D : mm 840 (950) H : mm 298 (35) W : inch 33-1/16 (37-3/8) D : inch 33-1/16 (37-3/8) H : inch 11-3/4 (1-3/8) Weight kg 25(6) 27(6) Unit (Panel) lbs 55(13) 60(13) Field drain pipe O.D. Outdoor unit 40 CMM Air flow mm 32 inch 1-1/4 CMM 100 CFM 3,530 Sound level at cooling dB(A) 49 Sound level at heating dB(A) 51 External finish Dimension 50 52 Ivory Munsell 3Y 7.8/1.1 W : mm 950 D : mm 330+30 H : mm 1350 W : inch 37-3/8 D : inch 13 + 1-3/16 H : inch Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: 121 116 lbs 267 256 mm 15.88 inch 5/8 mm 9.52 inch 3/8 Height difference m Max. 30 Length m Max. 75 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Upper limit Lower limit Upper limit Heating Lower limit Cooling 53-1/8 kg Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Indoor Outdoor D.B. 35˚C, W.B. 22.5˚C D.B. 46: D.B. 19˚C, W.B. 15˚C D.B. -5: w D.B. 21:, W.B. 15: D.B. 28˚C D.B. -20:, W.B. -20: D.B. 17˚C 6 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit Single phase 230V 50Hz w If optional air protect guide installed. D.B.-15: OCS05E-1.qxp 08.3.31 9:52 AM Model name Page 7 Indoor unit Outdoor unit Cooling Capacity Total input Heating PLA-RP100BA PLA-RP125BA PLA-RP140BA PUHZ-RP100YHA2 PUHZ-RP125YHA2 PUHZ-RP140YHA2 Btu/h 34,100 42,700 47,800 kW 10.0(4.9-11.4) 12.5(5.5-14.0) 14.0(5.5-15.3) kW 3.02 3.87 4.65 EER Energy label class 3.31 3.23 3.01 A A B SHF 0.74 0.71 0.71 Capacity Total input Btu/h 38,200 47,800 54,600 kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0) kW 3.10 3.88 4.43 3.61 3.61 3.61 A A A – – – COP Energy label class Booster heater Power supply kW Phase [ Cycle Hz 50 Voltage V 400 Breaker size Indoor unit A Air flow (Low-Medium2-Medium1-High) 16 CMM 20-23-26-30 22-25-28-31 24-26-29-32 CFM 710-810-920-1060 780-880-990-1090 850-920-1020-1130 Pa 0 0 0 dB(A) 32-34-37-40 34-36-39-41 36-39-42-44 External pressure Sound level (Low-Medium2-Medium1-High) 3 External finish (Panel) White Munsell 6.4Y 8.9/0.4 Dimension W : mm 840 (950) Unit (Panel) D : mm 840 (950) H : mm 298 (35) W : inch 33-1/16 (37-3/8) D : inch 33-1/16 (37-3/8) H : inch kg 25 (6) 27 (6) Unit (Panel) lbs 55 (13) 60 (13) Field drain pipe O.D. Outdoor unit 11-3/4 (1-3/8) Weight Air flow mm 32 inch 1-1/4 CMM 100 CFM 3,530 Sound level at cooling dB(A) 49 Sound level at heating dB(A) 51 50 52 External finish Dimension Ivory Munsell 3Y 7.8/1.1 W : mm 950 D : mm 330+30 H : mm 1350 W : inch 37-3/8 D : inch 13 + 1-3/16 H : inch Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: 135 130 lbs 298 287 mm 15.88 inch 5/8 mm 9.52 inch 3/8 Height difference m Max. 30 Length m Max. 75 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Upper limit Lower limit Upper limit Heating Lower limit Cooling 53-1/8 kg Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Indoor Outdoor D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 21˚C, W.B. 15˚C D.B. 28˚C D.B. -20˚C, W.B. -20˚C D.B. 17˚C 7 3. Guaranteed voltage Indoor unit 198~264V, 50Hz Outdoor unit 342~457V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit 3 phase 400V 50Hz w If optional air protect guide installed. D.B.-15: OCS05E-1.qxp 08.3.31 Model name 9:52 AM Page 8 Indoor unit Outdoor unit Cooling Capacity 34,100 42,700 kW 10.0(4.9-11.4) 12.5(5.5-14.0) kW 2.50 3.79 EER Energy label class 4.00 3.30 A A SHF 0.74 0.71 Capacity Btu/h 38,200 47,800 kW 11.2(4.5-14.0) 14.0(5.0-16.0) kW 2.60 3.57 4.31 3.92 A A Total input COP Energy label class Booster heater Power supply kW – [ Cycle Hz 50 Voltage V 400 Air flow (Low-Medium2-Medium1-High) Sound level (Low-Medium2-Medium1-High) 3 A 16 CMM 20-23-26-30 22-25-28-31 CFM 710-810-920-1060 780-880-990-1090 Pa 0 0 dB(A) 32-34-37-40 34-36-39-41 External pressure External finish (Panel) White Munsell 6.4Y 8.9/0.4 Dimension W : mm 840 (950) Unit (Panel) D : mm 840 (950) H : mm 298 (35) W : inch 33-1/16 (37-3/8) D : inch 33-1/16 (37-3/8) H : inch 11-3/4 (1-3/8) Weight kg 27 (6) Unit (Panel) lbs 60 (13) Field drain pipe O.D. Outdoor unit Air flow mm 32 inch 1-1/4 CMM 100 CFM 3,530 Sound level at cooling dB(A) 49 Sound level at heating dB(A) 51 External finish Dimension NOTE: 950 D : mm 330+30 H : mm 1350 W : inch 37-3/8 D : inch 13 + 1-3/16 H : inch 53-1/8 Gas side O.D. kg 130 lbs 287 mm 15.88 inch 5/8 mm 9.52 inch 3/8 Height difference m Max. 30 Length m Max. 75 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Upper limit Lower limit Upper limit Heating Lower limit Cooling 52 W : mm Liquid side O.D. Refrigerant pipe length 50 Ivory Munsell 3Y 7.8/1.1 Weight Refrigerant pipe size – Phase Breaker size Indoor unit PLA-RP125BA2 PUHZ-RP125YHA2 Btu/h Total input Heating PLA-RP100BA2 PUHZ-RP100YHA3 Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Indoor Outdoor D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 21˚C, W.B. 15˚C D.B. 28˚C D.B. -20˚C, W.B. -20˚C D.B. 17˚C 8 3. Guaranteed voltage Indoor unit 198~264V, 50Hz Outdoor unit 342~457V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit 3 phase 400V 50Hz w If optional air protect guide installed. D.B.-15: OCS05E-1.qxp 08.3.31 9:52 AM Page 9 Model name Indoor unit Outdoor unit Cooling Capacity Total input 12,300 17,100 kW 3.6(1.6-4.5) 5.0(2.3-5.6) kW 1.07 1.55 3.36 3.23 Energy label class SHF Capacity Total input 0.86 14,000 20,500 4.1(1.6-5.2) 6.0(2.5-7.3) kW 1.12 1.62 3.66 3.70 A A kW - - Phase [ Cycle Hz 50 Voltage V 230 Breaker size Indoor unit A 0.89 kW Energy label class Power supply A Btu/h COP Booster heater PLA-RP50AA PUHZ-RP50VHA2 Btu/h EER Heating PLA-RP35AA PUHZ-RP35VHA2 1 A 16 Air flow CMM 11-12-13-14 14-15-16-18 (Low-Medium2-Medium1-High) CFM 390-425-460-495 495-530-565-635 Pa 0 0 dB(A) 27-28-29-31 28-29-31-33 External pressure Sound level (Low-Medium2-Medium1-High) External finish (Panel) White Munsell 0.70Y 8.59/0.97 Dimension W : mm 840 (950) Unit (Panel) D : mm 840 (950) H : mm 258 (30) W : inch 33-1/16 (37-3/8) D : inch 33-1/16 (37-3/8) H : inch 10-3/16 (1-3/16) Weight kg 24 (5) Unit (Panel) lbs 53 (11) Field drain pipe O.D. Outdoor unit Air flow mm 32 inch 1-1/4 CMM 35 CFM 1,240 Sound level at cooling dB(A) 44 Sound level at heating dB(A) External finish Dimension W : mm 800 D : mm 300+23 H : mm 600 W : inch 31-1/2 D : inch 11-13/16 + 7/8 H : inch 23-5/8 kg 45 Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Upper limit Lower limit Upper limit Heating Lower limit lbs 99 mm 12.7 inch 1/2 mm 6.35 inch 1/4 Height difference m Max. 30 Length m Max. 50 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Cooling 46 Ivory Munsell 3Y 7.8/1.1 Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Indoor Outdoor D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 21˚C, W.B. 15˚C D.B. 28˚C D.B. -11˚C, W.B. -12˚C D.B. 17˚C 9 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit Single phase 230V 50Hz w If optional air protect guide installed. D.B.-15: OCS05E-1.qxp 08.3.31 9:52 AM Model name Page 10 Indoor unit Outdoor unit Cooling Capacity Total input 20,500 24,200 kW 6.0(2.7-6.7) 7.1(3.3-8.1) kW 1.65 1.97 3.64 3.60 Energy label class SHF Capacity Total input 0.74 23,900 27,300 7.0(2.8-8.2) 8.0(3.5-10.2) kW 1.85 2.34 3.78 3.42 A B kW - - Phase [ Cycle Hz 50 Voltage V 230 Breaker size Indoor unit A 0.78 kW Energy label class Power supply A Btu/h COP Booster heater PLA-RP71AA PUHZ-RP71VHA2 Btu/h EER Heating PLA-RP60AA PUHZ-RP60VHA2 1 A 25 Air flow CMM 14-15-16-18 15-16-18-20 (Low-Medium2-Medium1-High) CFM 495-530-565-635 530-565-635-705 Pa 0 0 dB(A) 28-29-31-33 28-30-32-34 External pressure Sound level (Low-Medium2-Medium1-High) External finish (Panel) W : mm 840 (950) Unit (Panel) D : mm 840 (950) H : mm 258 (30) W : inch 33-1/16 (37-3/8) D : inch 33-1/16 (37-3/8) H : inch 10-3/16 (1-3/16) Weight kg 24 (5) Unit (Panel) lbs 53 (11) Field drain pipe O.D. Outdoor unit White Munsell 0.70Y 8.59/0.97 Dimension Air flow mm 32 inch 1-1/4 CMM 55 CFM 1,940 Sound level at cooling dB(A) 47 Sound level at heating dB(A) External finish Dimension Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Upper limit Lower limit Upper limit Heating Lower limit W : mm 950 D : mm 330+30 H : mm 943 W : inch 37-3/8 D : inch 13 + 1-3/16 H : inch 37-1/8 kg 75 lbs 165 mm 15.88 inch 5/8 mm 9.52 inch 3/8 Height difference m Max. 30 Length m Max. 50 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Cooling 48 Ivory Munsell 3Y 7.8/1.1 Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Indoor Outdoor D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 21˚C, W.B. 15˚C D.B. 28˚C D.B. -11˚C, W.B. -12˚C D.B. 17˚C 10 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit Single phase 230V 50Hz w If optional air protect guide installed. D.B.-15: OCS05E-1.qxp 08.3.31 9:52 AM Model name Page 11 Indoor unit Outdoor unit Cooling Capacity Total input PLA-RP100AA2 PLA-RP125AA2 PLA-RP140AA2 PUHZ-RP100VHA2 PUHZ-RP125VHA2 PUHZ-RP140VHA2 Btu/h 34,100 42,700 47,800 kW 10.0(4.9-11.4) 12.5(5.5-14.0) 14.0(5.5-15.3) kW 3.02 3.87 4.65 3.31 3.23 3.01 A A B 0.78 0.74 0.71 EER Energy label class SHF Heating Capacity Total input Btu/h 38,200 47,800 54,600 kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0) kW 3.02 3.88 4.69 3.61 3.61 3.41 A A B - - - COP Energy label class Booster heater Power supply kW Phase [ Cycle Hz 50 Voltage V 230 Breaker size Indoor unit 1 A 32 CMM 19-21-23-27 24-25-27-30 (Low-Medium2-Medium1-High) CFM 670-740-810-950 850-880-950-1060 Pa 0 0 dB(A) 33-36-39-41 37-40-43-45 External pressure Sound level (Low-Medium2-Medium1-High) External finish (Panel) White Munsell 0.70Y 8.59/0.97 Dimension W : mm 840 (950) Unit (Panel) D : mm 840 (950) H : mm 298 (30) W : inch 33-1/16 (37-3/8) D : inch 33-1/16 (37-3/8) H : inch 11-3/4 (1-3/16) Weight kg 32 (5) Unit (Panel) lbs 71 (11) Field drain pipe O.D. Outdoor unit Air flow mm 32 inch 1-1/4 CMM 100 CFM 3,530 Sound level at cooling dB(A) 49 Sound level at heating dB(A) 51 External finish Dimension 950 D : mm 330+30 H : mm 1350 W : inch 37-3/8 D : inch 13 + 1-3/16 Gas side O.D. Liquid side O.D. NOTE: 53-1/8 kg 121 116 lbs 267 256 mm 15.88 inch 5/8 mm 9.52 inch 3/8 Height difference m Max. 30 Length m Max. 75 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Upper limit Lower limit Upper limit Heating Lower limit Cooling 52 W : mm Weight Refrigerant pipe length 50 Ivory Munsell 3Y 7.8/1.1 H : inch Refrigerant pipe size 40 Air flow Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Indoor Outdoor D.B. 35˚C, W.B. 22.5˚C D.B. 46: D.B. 19˚C, W.B. 15˚C D.B. -5: w D.B. 21:, W.B. 15: D.B. 28˚C D.B. -20:, W.B. -20: D.B. 17˚C 11 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit Single phase 230V 50Hz w If optional air protect guide installed. D.B.-15: OCS05E-1.qxp 08.3.31 Model name 9:52 AM Page 12 Indoor unit Outdoor unit Cooling Capacity Total input PLA-RP100AA2 PLA-RP125AA2 PLA-RP140AA2 PUHZ-RP100YHA2 PUHZ-RP125YHA2 PUHZ-RP140YHA2 Btu/h 34,100 42,700 47,800 kW 10.0(4.9-11.4) 12.5(5.5-14.0) 14.0(5.5-15.3) kW 3.02 3.87 4.65 3.31 3.23 3.01 A A B 0.78 0.74 0.71 EER Energy label class SHF Heating Capacity Total input Btu/h 38,200 47,800 54,600 kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0) kW 3.02 3.88 4.69 3.61 3.61 3.41 A A B - - - COP Energy label class Booster heater Power supply kW Phase [ Cycle Hz 50 Voltage V 400 Breaker size Indoor unit 3 A 16 Air flow CMM 19-21-23-27 24-25-27-30 (Low-Medium2-Medium1-High) CFM 670-740-810-950 850-880-950-1060 Pa 0 0 dB(A) 33-36-39-41 37-40-43-45 External pressure Sound level (Low-Medium2-Medium1-High) External finish (Panel) White Munsell 0.70Y 8.59/0.97 Dimension W : mm 840 (950) Unit (Panel) D : mm 840 (950) H : mm 298 (30) W : inch 33-1/16 (37-3/8) D : inch 33-1/16 (37-3/8) H : inch 11-3/4 (1-3/16) Weight kg 32 (5) Unit (Panel) lbs 71 (11) Field drain pipe O.D. Outdoor unit Air flow mm 32 inch 1-1/4 CMM 100 CFM 3,530 Sound level at cooling dB(A) 49 50 Sound level at heating dB(A) 51 52 External finish Dimension Ivory Munsell 3Y 7.8/1.1 W : mm 950 D : mm 330+30 H : mm 1350 W : inch 37-3/8 D : inch 13 + 1-3/16 H : inch Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: 135 130 lbs 298 287 mm 15.88 inch 5/8 mm 9.52 inch 3/8 Height difference m Max. 30 Length m Max. 75 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Upper limit Lower limit Upper limit Heating Lower limit Cooling 53-1/8 kg Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Indoor Outdoor D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 21˚C, W.B. 15˚C D.B. 28˚C D.B. -20˚C, W.B. -20˚C D.B. 17˚C 12 3. Guaranteed voltage Indoor unit 198~264V, 50Hz Outdoor unit 342~457V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit 3 phase 400V 50Hz w If optional air protect guide installed. D.B.-15: OCS05E-1.qxp 08.3.31 9:52 AM Page 13 2-2. CEILING-CONCEALED TYPE Model name Indoor unit Outdoor unit Cooling Capacity 16,700 3.6(1.6-4.5) 4.9(2.3-5.6) kW SHF 1.12 1.52 3.21 3.22 A A 0.89 0.82 Btu/h 14,000 20,500 kW 4.1(1.6-5.2) 6.0(2.5-7.3) Total input kW COP Energy label class Booster heater kW 1.20 1.65 3.41 3.64 B A - - Phase [ Cycle Hz 50 Voltage V 230 Breaker size Indoor unit PUHZ-RP50VHA3 kW Energy label class Power supply PUHZ-RP35VHA3 12,300 EER Capacity PEAD-RP50EA PUHZ-RP50VHA2 Btu/h Total input Heating PEAD-RP35EA2 PUHZ-RP35VHA2 1 A 16 Air flow CMM 13.5-17 (Low-High) CFM 476-600 Pa 30(70) External pressure Sound level dB(A) 36-40 (Low-High) (70Pa : 38-44) External finish Galvanized sheets Dimension W : mm 935 D : mm 700 H : mm 295 W : inch 36-13/16 D : inch 27-5/8 H : inch Weight 33 35 lbs 73 77 Unit drain pipe Outdoor unit R1(External thread) Air flow CMM 35 CFM 1,240 Sound level at cooling dB(A) 44 Sound level at heating dB(A) External finish W : mm 800 D : mm 300+23 H : mm 600 W : inch 31-1/2 D : inch 11-13/16 + 7/8 H : inch 23-5/8 kg 45(VHA2)/42(VHA3) lbs 99(VHA2)/92(VHA3) mm 12.7 Weight Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Upper Lower Upper Heating Lower limit limit limit limit inch 1/2 mm 6.35 inch 1/4 Height difference m Max. 30 Length m Max. 50 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Cooling 46 Ivory Munsell 3Y 7.8/1.1 Dimension Refrigerant pipe size 11-5/8 kg D.B. D.B. D.B. D.B. Indoor 35˚C, W.B. 22.5˚C 19˚C, W.B. 15˚C 28˚C 17˚C D.B. D.B. D.B. D.B. Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Outdoor 46˚C -5˚C w 21˚C, W.B. 15˚C -11˚C, W.B. -12˚C 13 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit Single phase 230V 50Hz w If optional air protect guide installed. D.B.-15: OCS05E-1.qxp 08.3.31 9:52 AM Model name Page 14 Indoor unit Outdoor unit Cooling Capacity Total input 24,200 6.0(2.7-6.7) 7.1(3.3-8.1) SHF A A 0.79 0.83 23,900 27,300 7.0(2.8-8.2) 8.0(3.5-10.2) kW kW 1.90 2.34 3.68 3.42 A B - - Phase [ Cycle Hz 50 Voltage V 230 Breaker size Indoor unit 2.15 3.30 kW Energy label class Power supply 1.86 3.23 Btu/h COP Booster heater PUHZ-RP71VHA3 kW Energy label class Total input PUHZ-RP60VHA3 20,500 kW Capacity PEAD-RP71EA PUHZ-RP71VHA2 Btu/h EER Heating PEAD-RP60EA PUHZ-RP60VHA2 1 A 25 Air flow CMM 17-21 20-25 (Low-High) CFM 600-741 706-883 Pa 30(70) 70(130) dB(A) 37-41 37-41 (70Pa : 39-46) (130Pa : 40-45) External pressure Sound level (Low-High) External finish Galvanized sheets Dimension W : mm 1175 D : mm 700 H : mm 295 740 325 W : inch Weight 46-1/8 D : inch 27-5/8 29-1/8 H : inch 11-5/8 12-13/16 kg 42 44 lbs 92 97 Unit drain pipe Outdoor unit R1(External thread) Air flow CMM 55 55 CFM 1,940 1,940 Sound level at cooling dB(A) 47 47 Sound level at heating dB(A) 48 External finish Dimension Weight W : mm 950 950 D : mm 330+30 330+30 H : mm 943 943 W : inch 37-3/8 37-3/8 D : inch 13 + 1-3/16 13 + 1-3/16 H : inch 37-1/8 37-1/8 kg 75(VHA2)/68(VHA3) lbs Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Upper Lower Upper Heating Lower limit limit limit limit 165(VHA2)/150(VHA3) mm 15.88 inch 5/8 15.88 5/8 mm 9.52 9.52 inch 3/8 3/8 Height difference m Max. 30 Max. 30 Length m Max. 50 Max. 50 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Cooling 48 Ivory Munsell 3Y 7.8/1.1 D.B. D.B. D.B. D.B. Indoor 35˚C, W.B. 22.5˚C 19˚C, W.B. 15˚C 28˚C 17˚C D.B. D.B. D.B. D.B. Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Outdoor 46˚C -5˚C w 21˚C, W.B. 15˚C -11˚C, W.B. -12˚C 14 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit Single phase 230V 50Hz w If optional air protect guide installed. D.B.-15: OCS05E-1.qxp 08.3.31 9:52 AM Model name Page 15 Indoor unit PEAD-RP100EA2 Outdoor unit PUHZ-RP100VHA2 PUHZ-RP100VHA3 Cooling Capacity Total input 34,100 42,700 47,800 12.5(5.5-14.0) 14.0(5.5-15.3) SHF 4.65 3.01 A A B 0.86 0.82 0.83 38,200 47,800 54,600 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0) kW kW 3.19 3.88 4.69 3.51 3.61 3.41 B A B - - - Phase [ Cycle Hz 50 Voltage V 230 Breaker size Indoor unit 3.89 3.21 kW Energy label class Power supply 3.06 3.27 Btu/h COP Booster heater PUHZ-RP140VHA2 10.0(4.9-11.4) Energy label class Total input PUHZ-RP125VHA2 kW kW Capacity PEAD-RP140EA Btu/h EER Heating PEAD-RP125EA 1 A 32 40 Air flow CMM 33.5-42 36.5-46 (Low-High) CFM 1183-1483 External pressure Sound level 70(130) dB(A) (Low-High) 44-50 46-51 (130Pa : 46-52) (130Pa : 47-53) External finish Dimension 1288-1624 Pa Galvanized sheets W : mm 1415 1715 D : mm 740 H : mm 325 W : inch 55-11/16 67-1/2 D : inch 29-1/8 H : inch Weight 12-13/16 kg 65 70 lbs 143 154 Unit drain pipe Outdoor unit R1(External thread) Air flow CMM 100 CFM 3,530 Sound level at cooling dB(A) 49 50 Sound level at heating dB(A) 51 52 External finish Dimension Ivory Munsell 3Y 7.8/1.1 W : mm 950 D : mm 330+30 H : mm 1350 W : inch 37-3/8 D : inch 13 + 1-3/16 H : inch Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: 121(VHA2)/116(VHA3) 116 lbs 267(VHA2)/256(VHA3) 256 mm 15.88 inch 5/8 mm 9.52 inch 3/8 Height difference m Max. 30 Length m Max. 75 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Upper limit Lower limit Upper limit Heating Lower limit Cooling 53-1/8 kg Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Indoor Outdoor D.B. 35˚C, W.B. 22.5˚C D.B. 46: D.B. 19˚C, W.B. 15˚C D.B. -5: w D.B. 21:, W.B. 15: D.B. 28˚C D.B. -20:, W.B. -20: D.B. 17˚C 15 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit Single phase 230V 50Hz w If optional air protect guide installed. D.B.-15: OCS05E-1.qxp 08.3.31 Model name 9:52 AM Page 16 Indoor unit PEAD-RP100EA2 PUHZ-RP100YHA2 Outdoor unit PUHZ-RP100YHA3 Cooling Capacity Total input 34,100 42,700 47,800 12.5(5.5-14.0) 14.0(5.5-15.3) SHF 4.65 3.01 A A B 0.86 0.82 0.83 38,200 47,800 54,600 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0) kW kW 3.19 3.88 4.69 3.51 3.61 3.41 B A B - - - Phase [ Cycle Hz 50 Voltage V 400 Breaker size Indoor unit 3.89 3.21 kW Energy label class Power supply 3.06 3.27 Btu/h COP Booster heater PUHZ-RP140YHA2 10.0(4.9-11.4) Energy label class Total input PUHZ-RP125YHA2 kW kW Capacity PEAD-RP140EA Btu/h EER Heating PEAD-RP125EA 3 A 16 Air flow CMM 33.5-42 36.5-46 (Low-High) CFM 1183-1483 1288-1624 External pressure Pa Sound level 70(130) dB(A) (Low-High) 44-50 46-51 (130Pa : 46-52) (130Pa : 47-53) External finish Dimension Galvanized sheets W : mm 1415 1715 D : mm 740 H : mm 325 W : inch 55-11/16 67-1/2 D : inch 29-1/8 H : inch Weight 12-13/16 kg 65 70 lbs 143 154 Unit drain pipe Outdoor unit R1(External thread) Air flow CMM 100 CFM 3,530 Sound level at cooling dB(A) 49 50 Sound level at heating dB(A) 51 52 External finish Dimension Ivory Munsell 3Y 7.8/1.1 W : mm 950 D : mm 330+30 H : mm 1350 W : inch 37-3/8 D : inch 13 + 1-3/16 H : inch Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: 135(YHA2)/130(YHA3) 130 lbs 298(YHA2)/287(YHA3) 287 mm 15.88 inch 5/8 mm 9.52 inch 3/8 Height difference m Max. 30 Length m Max. 75 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Upper limit Lower limit Upper limit Heating Lower limit Cooling 53-1/8 kg Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Indoor Outdoor D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 21˚C, W.B. 15˚C D.B. 28˚C D.B. -20˚C, W.B. -20˚C D.B. 17˚C 16 3. Guaranteed voltage Indoor unit 198~264V, 50Hz Outdoor unit 342~457V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit 3 phase 400V 50Hz w If optional air protect guide installed. D.B.-15: OCS05E-1.qxp 08.3.31 9:52 AM Model name Page 17 Indoor unit Outdoor unit Cooling Capacity Total input PEAD-RP60GA PEAD-RP71GA PEAD-RP100GA PUHZ-RP60VHA2 PUHZ-RP71VHA2 PUHZ-RP100VHA2 PUHZ-RP100VHA3 PUHZ-RP60VHA3 PUHZ-RP71VHA3 Btu/h 20,500 24,200 34,100 kW 6.0(2.7-6.7) 7.1(3.3-8.1) 10.0(4.9-11.4) kW 1.68 2.15 3.08 3.57 3.30 3.25 A A A 0.88 0.83 0.86 EER Energy label class SHF Heating Capacity Total input Btu/h 23,900 27,300 38,200 kW 7.0(2.8-8.2) 8.0(3.5-10.2) 11.0(4.5-14.0) kW 1.77 2.34 3.23 3.95 3.42 3.41 A B B - - - COP Energy label class Booster heater Power supply kW Phase [ Cycle Hz 50 Voltage V 230 Breaker size Indoor unit 1 A 25 Air flow CMM 16.5-21 (Low-High) CFM 582-741 External pressure Pa Sound level 32 26.5-33 706-883 935-1165 35-38/37-41/37-43 40-43/42-45/42-46 (10/50/70Pa) (10/50/70Pa) 10/50/70 dB(A) (Low-High) 33-37/35-40/36-42 (10/50/70Pa) External finish Dimension 20-25 10/50/70 Galvanized sheets W : mm 1171 1411 D : mm 740 H : mm W : inch 275 46-1/8 55-9/16 D : inch 29-1/8 H : inch Weight 10-13/16 kg 42 50 lbs 93 111 CMM 55 100 CFM 1,940 3,530 Unit drain pipe Outdoor unit R1(External thread) Air flow Sound level at cooling dB(A) 47 49 Sound level at heating dB(A) 48 51 External finish Dimension Ivory Munsell 3Y 7.8/1.1 W : mm 950 D : mm 330+30 H : mm 943 1350 W : inch 37-3/8 D : inch 37-1/8 53-1/8 kg 75(VHA2)/68(VHA3) 121(VHA2)/116(VHA3) lbs 165(VHA2)/150(VHA3) Weight Refrigerant pipe size 13 + 1-3/16 H : inch Gas side O.D. mm Liquid side O.D. inch 5/8 mm 9.52 inch Refrigerant pipe length NOTE: 3/8 Height difference m Max. 30 Max. 30 Length m Max. 50 Max. 75 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Upper limit Lower limit Upper limit Heating Lower limit Cooling 267(VHA2)/256(VHA3) 15.88 Indoor D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. 28˚C D.B. 17˚C Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Outdoor D.B. 46˚C D.B. -5˚C w1 D.B. 21˚C, W.B. 15˚C D.B. -11˚C, W.B. -12˚C w2 17 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit Single phase 230V 50Hz w1. If optional air protect guide installed. D.B.-15: w2. For RP100 D.B. -20:, W.B. -20: OCS05E-1.qxp 08.3.31 9:52 AM Model name Page 18 Indoor unit PEAD-RP100GA Outdoor unit PUHZ-RP100YHA2 PUHZ-RP100YHA3 Cooling Capacity Total input Btu/h 34,100 kW 10.0(4.9-11.4) kW 3.08 EER 3.25 Energy label class A SHF Heating Capacity Total input 0.86 Btu/h 38,200 kW 11.0(4.5-14.0) kW 3.23 COP 3.41 Energy label class Booster heater Power supply - Phase [ 3 Cycle Hz 50 Voltage V 400 Breaker size Indoor unit B kW A 16 Air flow CMM 26.5-33 (Low-High) CFM 935-1165 External pressure Sound level Pa 10/50/70 dB(A) 40-43/42-45/42-46 (Low-High) (10/50/70Pa) External finish Dimension Weight Galvanized sheets W : mm 1411 D : mm 740 H : mm 275 W : inch 55-9/16 D : inch 29-1/8 H : inch 10-13/16 kg 50 lbs 111 Unit drain pipe Outdoor unit Air flow R1(External thread) CMM 100 CFM 3,530 Sound level at cooling dB(A) 49 Sound level at heating dB(A) External finish Dimension Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Upper limit Lower limit Upper limit Heating Lower limit W : mm 943 D : mm 330+30 H : mm 1350 W : inch 37-3/8 D : inch 13 + 1-3/16 H : inch 53-1/8 kg 135(YHA2)/130(YHA3) lbs 298(YHA2)/287(YHA3) mm 15.88 inch 5/8 mm 9.52 inch 3/8 Height difference m Max. 30 Length m Max. 75 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Cooling 51 Ivory Munsell 3Y 7.8/1.1 Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Indoor Outdoor D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 21˚C, W.B. 15˚C D.B. 28˚C D.B. -20˚C, W.B. -20˚C D.B. 17˚C 18 3. Guaranteed voltage Indoor unit 198~264V, 50Hz Outdoor unit 342~457V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit 3 phase 400V 50Hz w If optional air protect guide installed. D.B.-15: OCS05E-1.qxp 08.3.31 9:52 AM Model name Page 19 Indoor unit Outdoor unit Cooling Capacity Total input 65,000 75,000 kW 19.0(9.0-22.4) 22.0(11.2-28.0) kW 6.70 8.34 2.84 2.64 Energy label class SHF Capacity Total input 0.86 76,000 92,000 22.4(9.5-25.0) 27.0(12.5-31.5) kW 6.50 8.20 3.45 3.29 B C kW - - Phase [ Cycle Hz 50 Voltage V 400 Breaker size Indoor unit D 0.81 kW Energy label class Power supply C Btu/h COP Booster heater PEA-RP250GA PUHZ-RP250YHA2 Btu/h EER Heating PEA-RP200GA PUHZ-RP200YHA2 3 A Indoor 15 / Outdoor 32 Air flow CMM 52-65 64-80 (Low-High) CFM 1835-2295 2260-2825 External pressure Pa Sound level 150 dB(A) 48-51 W : mm 1400 49-52 (Low-High) External finish Dimension Galvanized steel 1600 D : mm 634 H : mm W : inch 400 55-1/8 63 D : inch 25 H : inch Weight 15-3/4 kg 70 77 lbs 155 170 Unit drain pipe Outdoor unit R1 Air flow CMM 130 CFM 4590 Sound level at cooling dB(A) 58 Sound level at heating dB(A) 59 External finish Dimension Ivory Munsell 3Y 7.8/1.1 W : mm 950 D : mm 330+30 H : mm 1350 W : inch 37-3/8 D : inch 13 + 1-3/16 H : inch Weight Refrigerant pipe size Gas side O.D. 53-1/8 kg 135 lbs 298 136 300 mm 25.4 inch Liquid side O.D. Refrigerant pipe length NOTE: 9.52 inch 3/8 12.7 1/2 Height difference m Max. 30 Length m Max. 120 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Upper limit Lower limit Upper limit Heating Lower limit Cooling 1 mm Indoor D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. 28˚C D.B. 17˚C Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Outdoor D.B. 46˚C D.B. -5˚C w1 D.B. 21˚C, W.B. 15˚C D.B. -20˚C, W.B. -20˚C 19 3. Guaranteed voltage 342~457V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit 3 phase 400V 50Hz Outdoor unit 3 phase 400V 50Hz w1. If optional air protect guide is installed : D.B.-15: OCS05E-1.qxp 08.3.31 9:52 AM Page 20 2-3. WALL MOUNTED TYPE Model name Indoor unit Outdoor unit Cooling Capacity Total input 15,700 3.6(1.6-4.5) 4.6(2.3-5.4) kW 14,000 15,400 4.1(1.6-5.2) 4.5(2.5-6.2) kW kW 50 230 1 A 16 Air flow CMM 9-10-11-12 (Low-Medium2-Medium1-High) CFM 320-355-390-425 Pa 0 dB(A) 36-38-41-43 Weight Field drain pipe I.D. Air flow White Munsell 0.70Y 8.59/0.97 W : mm 990 D : mm 235 H : mm 340 W : inch 39 D : inch 9-1/4 H : inch 13-3/8 kg 16 lbs 35 mm 20 inch 13/16 CMM 35 CFM 1,240 Sound level at cooling dB(A) 44 Sound level at heating dB(A) External finish Dimension Weight Gas side O.D. Liquid side O.D. 46 Ivory Munsell 3Y 7.8/1.1 W : mm 800 D : mm 300+23 H : mm 600 W : inch 31-1/2 D : inch 11-13/16 + 7/8 H : inch 23-5/8 kg 45(VHA2)/42(VHA3) lbs 99(VHA2)/92(VHA3) mm 12.7 inch 1/2 mm 6.35 inch 1/4 Height difference m Max. 30 Length m Max. 50 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Upper limit Lower limit Upper limit Heating Lower limit C - V Dimension Cooling C Hz External finish NOTE: 1.40 3.21 Voltage (Low-Medium2-Medium1-High) Refrigerant pipe length 1.27 3.23 Cycle Sound level Refrigerant pipe size C 0.74 [ External pressure Outdoor unit A 0.84 Phase Breaker size Indoor unit 1.63 2.82 kW Energy label class Power supply 1.03 3.50 Btu/h COP Booster heater PUHZ-RP50VHA3 kW SHF Total input PUHZ-RP35VHA3 12,300 Energy label class Capacity PKA-RP50GAL PUHZ-RP50VHA2 Btu/h EER Heating PKA-RP35GAL PUHZ-RP35VHA2 Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Indoor Outdoor D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 21˚C, W.B. 15˚C D.B. 28˚C D.B. -11˚C, W.B. -12˚C D.B. 17˚C 20 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit Single phase 230V 50Hz w If optional air protect guide installed. D.B.-15: OCS05E-1.qxp 08.3.31 9:52 AM Model name Page 21 Indoor unit Outdoor unit Cooling Capacity Total input PKA-RP50FAL2 PKA-RP60FAL PKA-RP71FAL PKA-RP100FAL PUHZ-RP50VHA2 PUHZ-RP60VHA2 PUHZ-RP71VHA2 PUHZ-RP100VHA2 PUHZ-RP100VHA3 PUHZ-RP50VHA3 PUHZ-RP60VHA3 PUHZ-RP71VHA3 Btu/h 17,000 20,500 24,200 34,100 kW 5.0(2.3-5.6) 6.0(2.7-6.7) 7.1(3.3-8.1) 10.0(4.9-11.4) kW 1.66 1.55 1.98 2.93 3.01 3.87 3.59 3.41 B A A A 0.86 0.83 0.77 0.77 EER Energy label class SHF Heating Capacity Total input Btu/h 20,500 23,900 27,300 38,200 kW 6.0(2.5-7.3) 7.0(2.8-8.2) 7.6(3.5-10.2) 11.2(4.5-14.0) kW 1.76 2.01 2.23 3.25 3.41 3.48 3.41 3.45 B B B B - - - - COP Energy label class Power supply Booster heater Phase kW Cycle Hz 50 Voltage V 230 Breaker size Indoor unit Air flow (Low-High) External pressure Sound level (Low-High) 1 [ A 16 25 32 CMM 15-20 15-20 22-28 CFM 530-705 530-705 780-990 Pa 0 dB(A) 39-45 External finish Dimension 1400 13-3/8 kg 24 24 28 lbs 53 53 62 mm 20 inch 13/16 35 55 100 CFM 1,240 1,940 3,530 Sound level at cooling dB(A) 44 47 49 Sound level at heating dB(A) 46 48 51 W : mm 800 950 950 D : mm 300+23 330+30 330+30 External finish Dimension Weight Gas side O.D. Liquid side O.D. NOTE: Ivory Munsell 3Y 7.8/1.1 H : mm 600 943 1350 W : inch 31-1/2 37-3/8 37-3/8 D : inch 11 - 13/16 13 + 1-3/16 13 + 1-3/16 H : inch 23-5/8 37-1/8 53-1/8 kg 45(VHA2)/42(VHA3) 75(VHA2)/68(VHA3) 121(VHA2)/116(VHA3) lbs 99(VHA2)/92(VHA3) 165(VHA2)/150(VHA3) 267(VHA2)/256(VHA3) mm 12.7 15.88 15.88 inch 1/2 5/8 5/8 mm 6.35 9.52 9.52 inch 1/4 3/8 3/8 Height difference m Max. 30 Max. 30 Max. 30 Length m Max. 50 Max. 50 Max. 75 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Upper limit Lower limit Upper limit Heating Lower limit Cooling 66-1/8 CMM Air flow Refrigerant pipe length 55-1/8 9-1/4 H : inch Refrigerant pipe size 1680 340 55-1/8 D : inch Outdoor unit 1400 235 H : mm W : inch Field drain pipe I.D. 41-46 Munsell 3.4Y 7.7/0.8 W : mm D : mm Weight 39-45 Indoor D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. 28˚C D.B. 17˚C Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Outdoor D.B. 46˚C D.B. -5˚C w1 D.B. 21˚C, W.B. 15˚C D.B. -11˚C, W.B. -12˚C w2 21 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit Single phase 230V 50Hz w1. If optional air protect guide installed. D.B.-15: w2. For RP100 D.B. -20:, W.B. -20: OCS05E-1.qxp 08.3.31 Model name 9:52 AM Page 22 Indoor unit PKA-RP100FAL Outdoor unit PUHZ-RP100YHA2 PUHZ-RP100YHA3 Cooling Capacity Total input Btu/h 34,100 kW 10.0(4.9-11.4) kW 2.93 EER 3.41 Energy label class A SHF Heating Capacity Total input 0.77 Btu/h 38,200 kW 11.2(4.5-14.0) kW 3.25 COP 3.45 Energy label class Booster heater Power supply - Phase [ 3 Cycle Hz 50 Voltage V 400 Breaker size Indoor unit B kW A 16 Air flow CMM 22-28 (Low-High) CFM 780-990 Pa 0 dB(A) 41-46 External pressure Sound level (Low-High) External finish Dimension Weight Field drain pipe I.D. Outdoor unit Air flow Munsell 3.4Y 7.7/0.8 W : mm 1680 D : mm 235 H : mm 340 W : inch 66-1/8 D : inch 9-1/4 H : inch 13-3/8 kg 28 lbs 62 mm 20 inch 13/16 CMM 100 CFM 3,530 Sound level at cooling dB(A) 49 Sound level at heating dB(A) 51 External finish Dimension Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: W : mm 950 D : mm 330+30 H : mm 1350 W : inch 37-3/8 D : inch 13 + 1-3/16 H : inch 53-1/8 kg 135(YHA2)/130(YHA3) lbs 298(YHA2)/287(YHA3) mm 15.88 inch 5/8 mm 9.52 inch 3/8 Height difference m Max. 30 Length m Max. 75 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Upper limit Lower limit Upper limit Heating Lower limit Cooling Ivory Munsell 3Y 7.8/1.1 Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Indoor Outdoor D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 21˚C, W.B. 15˚C D.B. 28˚C D.B. -20˚C, W.B. -20˚C D.B. 17˚C 22 3. Guaranteed voltage Indoor unit 198~264V, 50Hz Outdoor unit 342~457V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit 3 phase 400V 50Hz w If optional air protect guide installed. D.B.-15: OCS05E-1.qxp 08.3.31 9:52 AM Page 23 2-4. CEILING SUSPENDED TYPE Model name Indoor unit Outdoor unit Cooling Capacity Total input PCA-RP50GA PCA-RP50GA2 PCA-RP60GA PCA-RP71GA PUHZ-RP50VHA2 PUHZ-RP50VHA2 PUHZ-RP60VHA2 PUHZ-RP71VHA2 PUHZ-RP71VHA3 PUHZ-RP50VHA3 PUHZ-RP50VHA3 PUHZ-RP60VHA3 Btu/h 16,000 17,000 20,500 24,200 kW 4.7(2.3-5.4) 5.0(2.3-5.6) 6.0(2.7-6.7) 7.1(3.3-8.1) 1.67 1.66 1.63 2.14 2.81 3.01 3.68 3.32 kW EER Energy label class SHF Heating Capacity Total input A 0.74 18,800 20,500 23,900 27,300 5.5(2.5-6.6) 6.0(2.5-7.3) 7.0(2.8-8.2) 7.6(3.5-10.2) kW kW 1.71 1.76 2.03 2.23 3.22 3.41 3.45 3.41 C B B B - - - - Phase [ Cycle Hz 50 Voltage V 230 Breaker size Indoor unit A 0.86 kW Energy label class Power supply B 0.88 Btu/h COP Booster heater C 0.76 Air flow (Low-Medium2-Medium1-High) External pressure Sound level (Low-Medium2-Medium1-High) 1 A 16 25 CMM 10-11-12-13 14-15-16-18 CFM 355-390-425-460 495-530-565-635 Pa dB(A) 37-38-40-42 W : mm 1000 37-39-41-43 210 51-9/16 39-3/8 D : inch 8-1/4 kg 27 34 34 lbs 60 75 75 mm 26 inch Outdoor unit Air flow 1 CMM 35 55 CFM 1,240 1,940 Sound level at cooling dB(A) 44 47 Sound level at heating dB(A) 46 External finish Dimension Weight Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: W : mm 800 330+23 950 330+30 H : mm 600 943 W : inch 37-3/8 D : inch 31-1/2 13 + 7/8 H : inch 23-5/8 37-1/8 kg 45(VHA2)/42(VHA3) 75(VHA2)/68(VHA3) 13 + 1-3/16 lbs 99(VHA2)/92(VHA3) 165(VHA2)/150(VHA3) mm 12.7 15.88 inch 1/2 5/8 mm 6.35 9.52 inch 1/4 3/8 Height difference m Max. 30 Max. 30 Length m Max. 50 Max. 50 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Upper limit Lower limit Upper limit Heating Lower limit Cooling 48 Ivory Munsell 3Y 7.8/1.1 D : mm Refrigerant pipe size 51-9/16 26-3/4 H : inch Field drain pipe O.D. 1310 680 H : mm Weight 37-39-41-43 White Munsell 0.70Y 8.59/0.97 1310 D : mm W : inch 495-530-565-635 0 External finish Dimension 14-15-16-18 Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Indoor Outdoor D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 21˚C, W.B. 15˚C D.B. 28˚C D.B. -11˚C, W.B. -12˚C D.B. 17˚C 23 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit Single phase 230V 50Hz w If optional air protect guide installed. D.B.-15: OCS05E-1.qxp 08.3.31 Model name 9:52 AM Page 24 Indoor unit PCA-RP100GA Outdoor unit PUHZ-RP100VHA2 PUHZ-RP100VHA3 Cooling Capacity Total input 34,100 42,700 47,800 12.5(5.5-14.0) 14.0(5.5-15.3) SHF 4.65 3.01 A A B 0.75 0.77 0.75 38,200 47,800 54,600 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0) kW kW 3.26 4.11 4.60 3.44 3.41 3.48 B B B - - - Phase [ Cycle Hz 50 Voltage V 230 Breaker size Indoor unit 3.88 3.22 kW Energy label class Power supply 2.92 3.42 Btu/h COP Booster heater PUHZ-RP140VHA2 10.0(4.9-11.4) Energy label class Total input PUHZ-RP125VHA2 kW kW Capacity PCA-RP140GA Btu/h EER Heating PCA-RP125GA 1 A 32 40 Air flow CMM 20-21-23-25 27-30-32-34 (Low-Medium2-Medium1-High) CFM 705-810-840-885 955-1060-1130-1200 Pa 0 0 dB(A) 40-41-43-45 W : mm 1310 External pressure Sound level (Low-Medium2-Medium1-High) External finish Dimension 41-43-45-46 White Munsell 0.70Y 8.59/0.97 1620 D : mm 680 H : mm 270 W : inch 51-9/16 63-3/4 D : inch 26-3/4 H : inch Weight Field drain pipe O.D. Outdoor unit 10-5/8 kg 37 43 45 lbs 82 95 99 mm 26 inch 1 Air flow CMM 100 Sound level at cooling dB(A) 49 Sound level at heating dB(A) 51 CFM 3,530 External finish Dimension 50 52 Ivory Munsell 3Y 7.8/1.1 W : mm 950 D : mm 330+30 H : mm 1350 W : inch 37-3/8 D : inch 13 + 1-3/16 H : inch Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: 53-1/8 kg 121(VHA2)/116(VHA3) 116 lbs 267(VHA2)/256(VHA3) 256 mm 15.88 inch 5/8 mm 9.52 inch 3/8 Height difference m Max. 30 Length m Max. 75 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Upper limit Lower limit Upper limit Heating Lower limit Cooling 42-44-46-48 Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Indoor Outdoor D.B. 35˚C, W.B. 22.5˚C D.B. 46: D.B. 19˚C, W.B. 15˚C D.B. -5: w D.B. 21:, W.B. 15: D.B. 28˚C D.B. -20:, W.B. -20: D.B. 17˚C 24 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit Single phase 230V 50Hz w If optional air protect guide installed. D.B.-15: OCS05E-1.qxp 08.3.31 9:52 AM Model name Page 25 Indoor unit PCA-RP100GA Outdoor unit PUHZ-RP100YHA2 PUHZ-RP100YHA3 Cooling Capacity Total input 34,100 42,700 47,800 12.5(5.5-14.0) 14.0(5.5-15.3) SHF 4.65 3.01 A A B 0.75 0.77 0.75 38,200 47,800 54,600 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0) kW kW 3.26 4.11 4.60 3.44 3.41 3.48 B B B - - - Phase [ Cycle Hz 50 Voltage V 400 Breaker size Indoor unit 3.88 3.22 kW Energy label class Power supply 2.92 3.42 Btu/h COP Booster heater PUHZ-RP140YHA2 10.0(4.9-11.4) Energy label class Total input PUHZ-RP125YHA2 kW kW Capacity PCA-RP140GA Btu/h EER Heating PCA-RP125GA 3 A 16 Air flow CMM 20-21-23-25 27-30-32-34 (Low-Medium2-Medium1-High) CFM 705-810-840-885 955-1060-1130-1200 Pa 0 0 dB(A) 40-41-43-45 W : mm 1310 External pressure Sound level (Low-Medium2-Medium1-High) External finish Dimension 41-43-45-46 White Munsell 0.70Y 8.59/0.97 1620 D : mm 680 H : mm 270 W : inch 51-9/16 D : inch Field drain pipe O.D. 63-3/4 26-3/4 H : inch Weight Outdoor unit 10-5/8 kg 37 43 45 lbs 82 95 99 mm 26 inch 1 Air flow CMM 100 Sound level at cooling dB(A) 49 Sound level at heating dB(A) 51 CFM 3,530 External finish Dimension 950 D : mm 330+30 H : mm 1350 W : inch 37-3/8 D : inch 13 + 1-3/16 Gas side O.D. Liquid side O.D. NOTE: 53-1/8 kg 135(YHA2)/130(YHA3) 130 lbs 298(YHA2)/287(YHA3) 287 mm 15.88 inch 5/8 mm 9.52 inch 3/8 Height difference m Max. 30 Length m Max. 75 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Upper limit Lower limit Upper limit Heating Lower limit Cooling 52 W : mm Weight Refrigerant pipe length 50 Ivory Munsell 3Y 7.8/1.1 H : inch Refrigerant pipe size 42-44-46-48 Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Indoor Outdoor D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 21˚C, W.B. 15˚C D.B. 28˚C D.B. -20˚C, W.B. -20˚C D.B. 17˚C 25 3. Guaranteed voltage Indoor unit 198~264V, 50Hz Outdoor unit 342~457V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit 3 phase 400V 50Hz w If optional air protect guide installed. D.B.-15: OCS05E-1.qxp 08.3.31 Model name 9:52 AM Page 26 Indoor unit PCA-RP71HA Outdoor unit PUHZ-RP71VHA2 PUHZ-RP71VHA3 Cooling Capacity Total input 24,200 42,700 42,700 12.5(5.5-14.0) 12.5(5.5-14.0) kW 2.21 3.88 3.88 3.21 3.22 3.22 A A A 0.74 0.77 0.77 Btu/h 27,300 47,800 47,800 kW 7.6(3.5-10.2) 13.8(5.0-16.0) 13.8(5.0-16.0) kW 2.23 4.05 4.05 3.41 3.41 3.41 B B B - - COP Energy label class Booster heater Power supply kW [ Cycle Hz 50 50 Voltage V 230 400 1 A 3 25 16 Air flow CMM 17-19 30-38 (Low-High) CFM 600-670 1060-1350 Pa 0 0 dB(A) 34-38 44-50 W : mm 1136 External pressure Sound level (Low-High) External finish Dimension Stainless steel 1520 D : mm 650 H : mm 280 W : inch 44-3/4 D : inch 59-7/8 25-5/8 H : inch Weight Field drain pipe O.D. 11 kg 41 56 lbs 90 124 mm 26 inch Outdoor unit Air flow 1 CMM 55 100 CFM 1,940 3,530 Sound level at cooling dB(A) 47 50 Sound level at heating dB(A) 48 52 External finish Dimension Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Ivory Munsell 3Y 7.8/1.1 W : mm 950 950 D : mm 330+30 330+30 H : mm 943 1350 W : inch 37-3/8 37-3/8 D : inch 13 + 1-3/16 13 + 1-3/16 H : inch 37-1/8 kg 75(VHA2)/68(VHA3) 116 lbs 165(VHA2)/150(VHA3) 256 mm 15.88 53-1/8 130 287 15.88 inch 5/8 5/8 mm 9.52 9.52 inch 3/8 3/8 Height difference m Max. 30 Max. 30 Length m Max. 50 Max. 75 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Upper limit Lower limit Upper limit Heating Lower limit Cooling - Phase Breaker size Indoor unit PUHZ-RP125YHA2 7.1(3.3-8.1) SHF Total input PUHZ-RP125VHA2 kW Energy label class Capacity PCA-RP125HA Btu/h EER Heating PCA-RP125HA Indoor D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C D.B. 28˚C D.B. 17˚C Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Outdoor D.B. 46˚C D.B. -5˚C w1 D.B. 21˚C, W.B. 15˚C D.B. -11˚C, W.B. -12˚C w2 26 3. Guaranteed voltage 198~264V, 50Hz (RP125Y : 342~457V, 50Hz) 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit V: Single phase 230V 50Hz, Y: 3 phase 400V 50Hz w1. If optional air protect guide installed. D.B.-15: w2. For RP125 D.B. -20:, W.B. -20: OCS05E-1.qxp 08.3.31 9:52 AM Page 27 2-5. FLOOR STANDING TYPE Model name Indoor unit PSA-RP71GA Outdoor unit PUHZ-RP71VHA2 PUHZ-RP71VHA3 Cooling Capacity Total input Btu/h 24,200 kW 7.1(3.3-8.1) kW 2.20 EER 3.23 Energy label class A SHF Heating 0.73 Capacity Total input Btu/h 27,300 kW 7.6(3.5-10.2) kW COP Energy label class B Booster heater Power supply kW - Phase [ 1 Cycle Hz 50 Voltage V 230 Breaker size Indoor unit A 25 Air flow CMM 15-18 (Low-High) CFM 530-635 Pa 0 dB(A) 40-45 External pressure Sound level (Low-High) External finish Dimension White Munsell 0.70Y 8.59/0.97 W : mm 270 H : mm 1900 W : inch 23-5/8 D : inch 10-5/8 H : inch 74-13/16 kg 43 lbs 98 Field drain pipe I.D. Air flow mm 20 inch 13/16 CMM 55 CFM 1,940 Sound level at cooling dB(A) 47 Sound level at heating dB(A) External finish Dimension W : mm 950 D : mm 330+30 H : mm 943 W : inch 37-3/8 D : inch 13 + 1-3/16 H : inch 37-1/8 kg 75(VHA2)/68(VHA3) lbs 165(VHA2)/150(VHA3) mm 15.88 Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Upper limit Lower limit Upper limit Heating Lower limit inch 5/8 mm 9.52 inch 3/8 Height difference m Max. 30 Length m Max. 50 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Cooling 48 Ivory Munsell 3Y 7.8/1.1 Weight Refrigerant pipe size 600 D : mm Weight Outdoor unit 2.23 3.41 Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Indoor Outdoor D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 21˚C, W.B. 15˚C D.B. 28˚C D.B. -11˚C, W.B. -12˚C D.B. 17˚C 27 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit Single phase 230V 50Hz w If optional air protect guide installed. D.B.-15: OCS05E-1.qxp 08.3.31 Model name 9:52 AM Page 28 Indoor unit PSA-RP100GA Outdoor unit PUHZ-RP100VHA2 PUHZ-RP100VHA3 Cooling Capacity Total input 34,100 42,700 47,800 12.4(5.5-14.0) 13.8(5.5-15.3) kW 2.99 4.12 4.91 3.34 3.01 2.81 A B C 0.81 0.75 0.74 Btu/h 38,200 47,800 54,600 kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0) kW 3.28 4.11 4.97 3.41 3.41 3.22 B B C - - - COP Energy label class Booster heater Power supply kW Phase [ Cycle Hz 50 Voltage V 230 Breaker size Indoor unit 1 A 32 40 Air flow CMM 24-31 26-33 27-35 (Low-High) CFM 850-1060 920-1165 955-1240 External pressure Pa Sound level 0 dB(A) (Low-High) 44-49 External finish Dimension 46-51 600 D : mm 350 H : mm 1900 W : inch 23-5/8 D : inch 13-3/4 H : inch 74-13/16 Field drain pipe I.D. Air flow kg 51 53 lbs 112 117 mm 20 inch 13/16 CMM 100 CFM 3,530 Sound level at cooling dB(A) 49 Sound level at heating dB(A) 51 External finish Dimension 50 52 Ivory Munsell 3Y 7.8/1.1 W : mm 950 D : mm 330+30 H : mm 1350 W : inch 37-3/8 D : inch 13 + 1-3/16 H : inch Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: 53-1/8 kg 121(VHA2)/116(VHA3) lbs 267(VHA2)/256(VHA3) 116 256 mm 15.88 inch 5/8 mm 9.52 inch 3/8 Height difference m Max. 30 Length m Max. 75 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Upper limit Lower limit Upper limit Heating Lower limit Cooling 47-52 White Munsell 0.70Y 8.59/0.97 W : mm Weight Outdoor unit PUHZ-RP140VHA2 10.0(4.9-11.4) SHF Total input PUHZ-RP125VHA2 kW Energy label class Capacity PSA-RP140GA Btu/h EER Heating PSA-RP125GA Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Indoor Outdoor D.B. 35˚C, W.B. 22.5˚C D.B. 46: D.B. 19˚C, W.B. 15˚C D.B. -5: w D.B. 21:, W.B. 15: D.B. 28˚C D.B. -20:, W.B. -20: D.B. 17˚C 28 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit Single phase 230V 50Hz w If optional air protect guide installed. D.B.-15: OCS05E-1.qxp 08.3.31 9:52 AM Model name Page 29 Indoor unit Outdoor unit PSA-RP100GA PSA-RP125GA PSA-RP140GA PUHZ-RP100YHA2 PUHZ-RP125YHA2 PUHZ-RP140YHA2 PUHZ-RP100YHA3 Cooling Capacity Total input Btu/h 34,100 42,700 47,800 kW 10.0(4.9-11.4) 12.4(5.5-14.0) 13.8(5.5-15.3) kW 2.99 4.12 4.91 3.34 3.01 2.81 A B C 0.81 0.75 0.74 EER Energy label class SHF Heating Capacity Total input Btu/h 38,200 47,800 54,600 kW 11.2(4.5-14.0) 14.0(5.0-16.0) 16.0(5.0-18.0) kW 3.28 4.11 4.97 3.41 3.41 3.22 B B C - - - COP Energy label class Booster heater Power supply kW Phase [ Cycle Hz 50 Voltage V 400 Breaker size Indoor unit 3 A 16 Air flow CMM 24-31 26-33 27-35 (Low-High) CFM 850-1060 920-1165 955-1240 External pressure Pa Sound level 0 dB(A) (Low-High) 44-49 External finish Dimension 600 D : mm 350 H : mm 1900 W : inch 23-5/8 D : inch 13-3/4 H : inch 74-13/16 Field drain pipe I.D. Air flow kg 51 51 53 lbs 112 112 117 mm 20 inch 13/16 CMM 100 CFM 3,530 Sound level at cooling dB(A) 49 Sound level at heating dB(A) 51 External finish Dimension 50 52 Ivory Munsell 3Y 7.8/1.1 W : mm 950 D : mm 330+30 H : mm 1350 W : inch 37-3/8 D : inch 13 + 1-3/16 H : inch Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: 53-1/8 kg 135(YHA2)/130(YHA3) 130 lbs 298(YHA2)/287(YHA3) 287 mm 15.88 inch 5/8 mm 9.52 inch 3/8 Height difference m Max. 30 Length m Max. 75 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Heating Indoor : D.B. 20: (68˚F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Upper limit Lower limit Upper limit Heating Lower limit Cooling 47-52 White Munsell 0.70Y 8.59/0.97 W : mm Weight Outdoor unit 46-51 Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Indoor Outdoor D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C D.B. 19˚C, W.B. 15˚C D.B. -5˚C w D.B. 21˚C, W.B. 15˚C D.B. 28˚C D.B. -20˚C, W.B. -20˚C D.B. 17˚C 29 3. Guaranteed voltage Indoor unit 198~264V, 50Hz Outdoor unit 342~457V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit 3 phase 400V 50Hz w If optional air protect guide installed. D.B.-15: OCS05E-1.qxp 08.3.31 9:52 AM Page 30 OUTLINES AND DIMENSIONS PLA-RP50BA PLA-RP125BA PLA-RP100BA2 PLA-RP60BA PLA-RP140BA PLA-RP125BA2 Ceiling hole 20~45 Suspension bolt pitch Detail connecting of branch duct(Both aspects) 100 100 90 Cut out hole 100 90 860~910 620 Ceiling hole Indoor power supply terminal block(Option part) w 605 +35 -5 Suspension bolt pitch 840 Branch duct hole 155 Remote controller terminal block Indoor unit/Outdoor connecting terminal Branch duct hole 350 [175 167 70° 160 (7.5) 160 Unit : mm 20~45 860~910 810 Fresh air intake hole PLA-RP71BA 130 INDOOR UNIT PLA-RP35BA PLA-RP100BA PLA-RP71BA2 20~45 3 w 14-[2.8 Burring hole pitch Burring hole [150 Detail drawing of fresh air intake hole (7.5) 24 160 D C 90 150 Cut out hole Burring hole 840 60 284 ( Connected the attached Drain pipe connected to VP-25 flexible pipe or socket. 377 w Control wire entry w 190 B w Cut out hole [100 Keep approximately 10 to 15mm space between unit ceiling and ceiling slab. w Ceiling w In case of standard grille : PLP-6BA / PLP-6BAMD Ceiling 35 Power supply wire, Indoor unit/Outdoor unit connecting wire entry 156 105 w w 17 +50 Suspension bolt lower edge 140 w 50~70 170 A 2 ) 158 1 Burring hole pitch [125 120° 120° 160 Suspension bolt M10 or W3/8 3-[2.8 20~45 187.5 Grille 597 Drain hole Drain pump clean hole and Drain emergency drainage hole M Emergency operation switchand Emergency Up/Down switch Emergency switchand Emergency Up/Down switch 597 Auto vane (Air outlet) Air intake hole 500 Air outlet hole 950 M In case of auto-grille : PLP-6BAJ In case of wireless remote controller : PLP-6BALM Auto grille Air intake grille up/down discharge Ceiling L.L Filter Air intake grille DEFROST/STAND BY lamp Receiver M Operation lamp Air intake grille 83 M 36 500 Vane motor 83 36 Air outlet hole 950 Indoor unit Grille 1500mm or more 1000mm or more Indoor unit Ceiling Max. 4.0m Air intake hole 3000mm or more Obstacle Floor 1800mm or more from floor For high attachment Note 1. Please choose the grille from a standard grille, auto-grille. 2. As for drain pipe, please use VP-25(O.D. [32 PVC TUBE). Drain pump is included. Max. lifting height is 850mm from the ceiling. 3. As for suspension bolt, please use M10 or W3/8. (Procured at local site) 4. Electrical box may be removed for the service purpose. Make sure to slack the electrical wire little bit for control/ power wires connection. 5. The height of the indoor unit is able to be adjusted with the grille attached. 6. For the installation of the optional high efficiency filter or optional multi-functional casement. 1) Requires E or more space between transom and ceiling for the installation. 2) Add 135 mm to the dimensions w marked on the figure. 3) The optional high efficiency filter becomes optional multi-functional casement and concomitant use. 7. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur. (It becomes the cause of dew drops/water dew.) 8. As for necessary installation/service space, please refer to the left figure. Models PLA-RP35/50BA PLA-RP60BA PLA-RP71BA PLA-RP71BA2 PLA-RP100,125,140BA PLA-RP100,125BA2 30 1 2 Refrigerant pipe ···[6.35 Flared connection ···1/4 inch Refrigerant pipe [6.35 / [9.52 Flared connection 1/4 inch/3/8 inch (compatible) Refrigerant pipe ···[12.7 Flared connection ···1/2 inch Refrigerant pipe ···[9.52 Flared connection ···3/8 inch A B C D E 80 74 241 258 87 400 Refrigerant pipe ···[15.88 Flared connection ···5/8 inch 85 77 281 298 440 08.3.31 9:53 AM Page 31 Unit : mm PLA-RP35AA PLA-RP50AA PLA-RP60AA PLA-RP71AA PLA-RP100AA2 PLA-RP125AA2 PLA-RP140AA2 Ceiling hole 860 - 910 20 - 45 159 16 197 {125 Burring hole pitch 120 _ 20 - 45 3 - {2.8 Burring hole 120_ 159 C 89 Detail drawing of fresh air intake 98 192 {150 159 840 {100 (Cut out hole) Suspension bolt M10 or W3/8 1 Ceiling surface Feeding hole (Drain pump) 286 374 60 860 - 910 Ceiling hole Terminal block 840 14 - {2.8 Burring hole Suspension bolt pitch 605 Branch duct hole 350 {175 167 155 159 130 70_ 20 - 45 810 Suspension bolt pitch Fresh air intake 20 - 45 Branch duct hole (Cut out hole) 100 90 100 100 90 158 Drain pipe VP-25connection (O.D.{32) B +5 0 30 135 Ceiling surface 17 Control wire entry Power line entry Suspension bolt lower edge 190 105 140 50 - 70 170 A 2 +5 0 High efficiency filter & Fresh air intake casement (option) 577 Air intake hole Air intake grille 17 Grille Drain hole M A M Emergency operation switch (cooling) Emergency operation switch (heating) Auto vane 577 Air intake hole (WIRELESS PANEL) 411 Air outlet hole A 950 DEFROST/STAND BY lamp M Receiver 77 Operation lamp M 411 Air outlet hole 950 51 OCS05E-1.qxp Use the current nuts meeting the pipe size of the outdoor unit. Available pipe size 1 LIQUID SIDE 2 GAS SIDE RP35, 50 RP60 RP71 RP100, 125, 140 [6.35 [6.35 — — [9.52 [9.52 [9.52 [9.52 [12.7 — — — [15.88 [15.88 [15.88 [15.88 — — — [19.05 Models PLA-RP35,50AA A B C 241 258 80 281 298 84 PLA-RP60,71AA PLA-RP100,125,140AA2 : Initial flare nut size 31 Vane motor 77 51 Branch duct hole OCS05E-1.qxp 08.3.31 9:53 AM Page 32 Unit : mm PEAD-RP35EA2 PEAD-RP50EA PEAD-RP60EA Model A RP35,50 772 RP60 B 305 1012 280 w Initial flare nut size F G R410A Outdoor unit : 6.35 w R410A Outdoor unit : 12.7 w R407C Outdoor unit : 9.52 R407C Outdoor unit : 15.88 Outdoor unit (SUZ) : 6.35 15.88 290 1070 1044 R407C Outdoor unit : 9.52 w C D E - 830 804 Service space:500 or more 50~150 29 Refrigerant piping flare connection (liquid [ F copper tube):HP Refrigerant piping flare connection (gas [G copper tube):LP Drain R1(External thread) Electrical parts box Drain Pump (Option) Set Drain Pipe (Option) ... Flexible joint VP-25(I.D. [32) Filter 55 Access door 81 C B 81 197 450 Lifting bolt hole (14×22) C 13 13 30 277 45 80 85 282 288 256 176 Air inlet E 6 40 24 10 179 227 2 35 1 243 109 3.5 21 10 10- [3 (RP35,50) 12- [3 (RP60) D 30 61 4 In case of rear inlet 81 A 44 75 640 30 B 10 18 56 355 365~465 159 1 2 3 4 5 6 7 10- [3 (RP35,50) 12- [3 (RP60) A 10 450 5 7 3.5 Air outlet 3 Keep duct-work length 850mm or more. Be sure to apply the air filter near the air inlet grille. In case of bottom inlet 10- [3 (RP35,50) 12- [3 (RP60) Air outlet 10 7 40 15 176 256 10 3.5 81 C B 81 A Air inlet PEAD-RP71EA PEAD-RP100EA2 PEAD-RP125EA PEAD-RP140EA Service space:500 or more Air inlet 375 Lifting bolt hole (14x22) 12-[3 44 E 75 D 243 6 5 7 Air outlet 4 C A 13 307 45 122 113 1 81 80 2 20 53 B 365~465 323 308 30 10 680 C 197 450 169 210 30 12-[3 A 81 81 35 7 140 6 282 5 3.5 30 4 40 3 Refrigerant piping flare connection (liquid [9.52 copper tube):HP Refrigerant piping flare connection (gas [F copper tube):LP Drain R1 (External thread) Electrical parts box Drain Pump (Option) Set Drain Pipe (Option) ... Flexible joint VP25(I.D.[32) Filter 319 261 181 2 3.5 1 55 Access door 3 Keep duct-work length 850mm or more. Be sure to apply the air filter near the air inlet grille. 32 B 81 10 F A B C D E Model 15.88 RP71 1012 280 290 1070 1044 RP100,125 1252 360 370 1310 1284 R410A Outdoor unit : 15.88 w RP140 1552 460 470 1610 1584 R407C outdoor unit : 19.05 w Initial flare nut size 10 50~150 29 450 13 30 OCS05E-2.qxp 08.3.31 10:20 AM Page 33 Unit : mm PEAD-RP60GA PEAD-RP71GA PEAD-RP100GA Model A B C D E F G H J RP60 1125 1090 1050 1012 7 840 8 Outdoor unit(SUZ) : 6.35 Other outdoor unit : 9.52 w 15.88 RP71 1125 1090 1050 1012 7 840 8 9.52 15.88 RP100 1365 1330 1290 1252 9 1080 10 9.52 R410A Outdoor unit : 15.88 w R407C Outdoor unit : 19.05 w Initial flare nut size 33 A 39 Drain R1 565 634 530 Left side view Refrigerant pipe [9.52 (3/8 braze) Return air Return air sensor 50 Refrigerant pipe 10 [25.4 (1 braze) A Rubber bush Rubber bush Rubber bush 54 10 55 376 Supply air Pipe cover···················2pcs. (For dew condensation prevention of local piping and unit connection) Remote controller········1pc. 330 22 145 144 130 130 35 89 35 73 262 Control box 462 40 40 155 Supply air duct flange 45 20 42 124 31 Front view 1284 1400 1340 1260 1000 Top view 7x130(=910) 1300 130 22-[ 3.1 20 34 31 Return air duct flange 105 40 4- [12 45 [Field supply] 10 130 10 24-[ 3 Holes 1102 8x130(=1040) 199 200 131 100 400 70 75 129 100 100 25 25 34 95 10:20 AM 250 08.3.31 11 OCS05E-2.qxp Page 34 PEA-RP200GA Unit : mm Refrigerant pipe [25.4 (1 braze) A 39 Drain R1 565 634 530 Return air sensor A Left side view Refrigerant pipe [12.7 (1/2 braze) Return air 50 10 Rubber bush Rubber bush Rubber bush 54 10 55 376 Supply air Control box 462 40 100 40 255 Supply air duct flange 45 20 42 124 66 Front view 1484 1600 1540 1460 1000 Top view 7x130(=910) 1500 400 130 130 20 34 66 10 Return air duct flange 205 40 4- [12 45 [Field supply] 10 26- [3 Holes 22- [3.1 1302 9X130(=1170) 199 200 131 Pipe cover··················2pcs. (For dew condensation prevention of local piping and unit connection) Remote controller·······1pc. 330 22 145 144 130 130 35 89 35 73 262 70 75 129 100 100 25 25 35 95 10:20 AM 250 08.3.31 11 OCS05E-2.qxp Page 35 PEA-RP250GA Unit : mm 40 *2 *2 *1 *1 50 10 A 700 Return air sensor (2 places) 764 664 Left side view Refrigerant pipe 39 PEA-RP400GA : [9.52 (3/8 braze) PEA-RP500GA : [12.7 (1/2 braze) Drain R1 [2 places (*2 part)] Return air 120 Refrigerant pipe [25.4 (1 braze) [2 places (*1 part)] A 50 10 Rubber bush 61 Rubber bush Rubber bush 60 60 60 570 Control box 425 20 100 45 149 29 Supply air 40 Supply air duct flange 59 595 395 42.5 Front view 1824 1947 1880 1800 1125 Top view 8X130(=1040) 1840 130 130 24- [3.1 36- [3 HOLES 10 280 42.5 10 1618 12X130(=1560) 40 4- [15 [Field supply] 20 Return air duct flange 33 29 203 320 141 Pipe cover··················4pcs. (For dew condensation prevention of local piping and unit connection) Remote controller·······1pc. 22 22.5 81 525 22.5 4X120(=480) 117 156 117 102 40 130 130 40 36 188 10:20 AM 340 08.3.31 22 OCS05E-2.qxp Page 36 PEA-RP400, 500GA Unit : mm 360 405 420 495 Sleeve w1 [90 MITSUBISHI ELECTRIC 150 or more m r.SLIm Through hole [90~[100 245 70 21 R52.5 Liquid pipe Gas pipe 990 705 Air outlet 80 715 Air intake 400 12-Louvers(manual) 340 Air intake ëOñ Å@ÇeÇqÇnÇmÇs 449 581 ÅrÇoÇoÅqÅ@ 700 (Flexible hose total length800) ÅrÇoÇoÅqÅ@ 395 Auto vane 280 Air intake 225 40 86 54 70 35 MITSUBISHI ELECTRIC mr.SLIm 190 160 235 ON STAND COOL HEAT OFF BY 233 153 (Right side piping installation) Terminal block for power supply (Heater (PKH-P35, 50GALH only)) Terminal block to outdoor unit Service panel (Power supply access) [15.88 — [12.7 [15.88 — [9.52 [9.52 P35, 50 [6.35 RP35, 50 PKA-RP35GAL PKA-RP50GAL : initial flaare nut size GAS SIDE LIQUID SIDE Knockout hole for right piping Refrigerant pipe.Drain pipe. Wiring hole Less than 15 Knockout hole for under piping Refrigerant piping.Drain pipe. Wiring hole 235 60 Right side Use the current nuts meeting the pipe size of the outdoor unit. Available pipe size ëOñ Å@ÇeÇqÇnÇmÇs Front view(to open the grille) Filter grip 50 Lower side (Left side piping installation) Unit drain pipe O.D.20 35 272 310 322 230 190 130 0 35 55 80 (Necessary clearance for unit installation) Less than 130 Right side 60 340 w1 Sleeves are available on the market. w2 This size shows the lower end of through hole. Right-rear piping hole R52.5 Unit center Installation plate balance point hole Knockout hole for right-rear piping 5 Model 35, 50 2. Knockout hole for left-rear piping R5 Left-rear piping hole 49-[5hole for tapping screw 300 Details of installation plate 245 HEAT 75 32 20 0 35 0 14-[14hole for bolts 5 STAND COOL BY 95 50 or more 135 2. R5 190 230 210 ON OFF 150 Allowing clearances Front view 205 170 190 30 or more 180 or more 260 53 79 Knock out hole for left piping Refrigerant pipe.Drain pipe.Wiring hole. 320 345 Front view 80 Left side 495 37 425 198 Air intake 60 280 10:20 AM 31 245 08.3.31 70 21 OCS05E-2.qxp Page 37 Unit : mm OCS05E-2.qxp 08.3.31 10:20 AM Page 38 Unit : mm PKA-RP50FAL2 PKA-RP60FAL PKA-RP71FAL Display section 62.5 Top 45 235 235 45 235 45 Defrosting Initial heating lamp 13 235 Power lamp Front Right side 1400 Left side Emergency switch(Heat) Emergency switch(Cool) Receiving section 235 Knockout hole for right piping Refrigerant pipe. Drain pipe 340 A 197 1090 Air intake Terminal block for indoor/outdoor connecting line 15 Terminal block for heater (PKH only) Liquid pipe Knockout hole for left piping C Gas pipe 25 Drain hose for left-hand side piping 58 42 Bolt Drain hose O.D.20 Drain hose 1110 183 55 (Gas pipe) 107 120 111 (Liquid pipe) Lower side Liquid pipe [9.52(3/8F) Gas pipe [15.88(5/8F) Auto vanes 1120 240 552 Air outlet 552 Air outlet Louvers (manual) Under panel Removable at left-hand side piping Knockout hole for under-piping Sleeve w1 Through hole [ 90 [ 90~ [ 100 w1 Sleeves are available on the market. B Use the current nuts meeting the pipe size of the outdoor unit. Refrigerant pipe. Drain pipe Unit center 990 245 455 Knockout hole for wiring 91 225 240 180 12-ø6 hole for tapping screw 280 314 610 90 C 30 100 B 37 74 39 39 37 74 98 32 4 32-ø12 hole for bolt 30 60 184 30 66-ø6 hole for tapping screw A 30 37 65 on left-hand side Drainage range on right-hand side 100 4 39 18 285 19 10 30 80 29 280 Wall fixture 10 91=(910) 900 18 Drainage range Rear piping opening Range for left rear piping opening Available pipe size RP50 5LIQUID SIDE [ 6.35 [ 9.52 6GAS SIDE [ 12.7 [ 15.88 :Initial flare nut size 38 RP60,71 / P60,71 [ [ 9.52 15.88 08.3.31 10:20 AM Page 39 Unit : mm PKA-RP100FAL Top 62.5 Display section 45 235 45 235 45 235 235 45 13 235 Receiving section Emergency switch(Heat) Emergency switch(Cool) Defrosting Initial heating lamp Power lamp Front Left side Knockout hole for right piping Right side 1680 235 1370 Air intake 340 197 A Knockout hole for left piping C Terminal block for indoor/outdoor connecting line 15 Terminal block for heater (PKH only) Liquid pipe Gas pipe 25 Drain hose O.D.20 Drain hose Drain hose for left-hand side piping 58 42 Bolt 1110 Drain hose 183 Lower side 1400 55 (Gas pipe) 102 120 111 (Liquid pipe) 240 694 Air outlet Use the current nuts meeting the pipe size of the outdoor unit. Available pipe size RP100 P100 694 Air outlet LIQUID SIDE [9.52 [15.88 [19.05 : Initial flare nut size [9.52 GAS SIDE Louvers (manual) B Under panel (Removable at left-hand side piping) [19.05 Auto vane Knockout hole for under-piping Refrigerant pipe. Drain pipe Unit center 1270 Knockout hole for wiring Drainage range 91 on right-hand side 60 295 225 Range for left rear piping opening 240 180 280 750 30 41-ø12 hole for bolt A 30 314 90 Range for left rear piping opening 12-ø6 hole for tapping screw 39 Rear piping opening B C 30 100 Drainage range on left-hand side 285 19 37 74 39 98 32 39 13 91=(1183) 900 37 65 18 100 4 39 18 184 30 84-ø6 hole for tapping screw 245 595 10 30 29 Wall fixture 80 280 Unit out line 37 74 4 OCS05E-2.qxp OCS05E-2.qxp 08.3.31 10:20 AM Page 40 Unit : mm PCA-RP50GA NOTES: 1. Use M10 or W3/8 screws for anchor bolt. 2. When optional drain lift-up mechanism is installed, always provide upward piping for refrigerant piping. 140 70 320 150 80 17 6 933 (suspension bolt pitch) 85 983 15 81 76 7 226 2 157 Electrical box 180 210 70 904 182 1000 gas 241 (Drainage) 254 506 680 56 Air outlet liquid 201 Air intake 161 90 918 5 1 4 38 131 161 46 175 1 8 38 79 Ceiling 6~7 42 32 Electrical box [Front view] 179 3 2 1 2 3 4 5 6 7 8 Drainage pipe connection (26mm I.D.) Drainage pipe connection (for the left arrangement) Knockout hole for left drain-piping arrangement Refrigerant-pipe connection (gas pipe side/flared connection) Refrigerant-pipe connection (liquid pipe side/flared connection) Knockout hole for upper drain pipe arrangement Knockout hole for left drain pipe arrangement Knockout hole for wiring arrangement Use the current nuts meeting the pipe size of the outdoor unit. 86 138 171 263 352 525 Available pipe size RP50 P50 5 LIQUID SIDE [6.35 928 [9.52 4 GAS SIDE When electrical box is pulled down [15.88 : Initial flare nut size 40 [9.52 [12.7 [15.88 OCS05E-2.qxp 08.3.31 10:20 AM Page 41 Unit : mm PCA-RP50GA2 PCA-RP60GA PCA-RP71GA NOTES: 1. Use M10 or W3/8 screws for anchor bolt. 2. When optional drain lift-up mechanism is installed, always provide upward piping for refrigerant piping. 140 70 320 150 80 17 6 1240 (suspension bolt pitch) 85 1290 Electrical box 15 2 226 210 180 81 76 7 157 70 1214 182 (Liquid) 1310 201 (5/8 inch Gas) 241 (Drainage) 254 506 680 56 Air outlet Air intake 161 90 1228 38 131 161 525 1 4 46 175 1 Ceiling 5 8 3879 32 [ Front view ] 6~7 42 179 3 Electrical box 2 86 138 171 263 416 1 2 3 4 5 6 7 8 Drainage pipe connection (26mm I.D.) Drainage pipe connection (for the left arrangement) Knockout hole for left drain-piping arrangement Refrigerant-pipe connection (gas pipe side/flared connection) Refrigerant-pipe connection (liquid pipe side/flared connection) Knockout hole for upper drain pipe arrangement Knockout hole for left drain pipe arrangement Knockout hole for wiring arrangement Use the current nuts meeting the pipe size of the outdoor unit. Available pipe size RP50 5 LIQUID SIDE [6.35 [9.52 4 GAS SIDE [12.7 1235 When electrical box is pulled down [15.88 : Initial flare nut size 41 RP60 RP71,P60,P71 [6.35 [9.52 [9.52 [15.88 [15.88 OCS05E-2.qxp 08.3.31 10:20 AM Page 42 Unit : mm PCA-RP100GA NOTES: 1. Use M10 or W3/8 screws for anchor bolt. 2. When optional drain lift-up mechanism is installed, always provide upward piping for refrigerant piping. 140 70 320 150 80 18 6 1240 (suspension bolt pitch) 87 70 16 2 229 217 270 81 96 7 207 Electrical box 1214 182 1310 198 245 254 506 680 56 Air outlet (3/8 inch Liquid) (5/8 inch, 3/4 inch gas) (Drainage) Air intake 161 90 1228 Ceiling 8 5 1 4 6~7 38 192 45 42 236 38 140 1 93 [ Front view ] 160 239 3 Electrical box 2 1 2 3 4 5 6 7 8 525 687 Drainage pipe connection (26mm I.D.) Drainage pipe connection (for the left arrangement) Knockout hole for left drain-piping arrangement Refrigerant-pipe connection (gas pipe side/flared connection) Refrigerant-pipe connection (liquid pipe side/flared connection) Knockout hole for upper drain pipe arrangement Knockout hole for left drain pipe arrangement Knockout hole for wiring arrangement Use the current nuts meeting the pipe size of the outdoor unit. 86 138 171 263 Available pipe size RP100 P100 5 LIQUID SIDE 1235 [9.52 [9.52 [15.88 [19.05 [19.05 4 GAS SIDE When electrical box is pulled down :Initial flare nut size 42 OCS05E-2.qxp 08.3.31 10:20 AM Page 43 Unit : mm PCA-RP125GA PCA-RP140GA NOTES: 1. Use M10 or W3/8 screws for anchor bolt. 2. When optional drain lift-up mechanism is installed, always provide upward piping for refrigerant piping. 140 70 320 150 80 18 6 1547(suspension bolt pitch) 87 70 16 229 2 217 270 81 96 7 207 Electrical box 1524 182 1620 198 245 254 506 680 56 Air outlet (3/8 inch Liquid) (5/8 inch, 3/4 inch gas) (Drainage) Air intake 161 90 1535 [ Front view ] Ceiling 8 5 1 4 192 236 Drainage pipe connection (26mm I.D.) Drainage pipe connection (for the left arrangement) Knockout hole for left drain-piping arrangement Refrigerant-pipe connection (gas pipe side/flared connection) Refrigerant-pipe connection (liquid pipe side/flared connection) Knockout hole for upper drain pipe arrangement Knockout hole for left drain pipe arrangement Knockout hole for wiring arrangement 6~7 38 45 42 160 38 140 1 93 Electrical box 239 3 2 1 2 3 4 5 6 7 8 525 Use the current nuts meeting the pipe size of the outdoor unit. 86 138 171 263 Available pipe size RP125,140 P125,140 5 LIQUID SIDE [9.52 [9.52 4 GAS SIDE [15.88 [19.05 [19.05 687 1545 When electrical box is pulled down :Initial flare nut size 43 1224 1098 1136 986 bolt pitch> 75 21 1 175 Suspension bolt 80 70 Filter element for the exchange model:PAC-SG38KF-E (12pcs.) 360 handle 3 or more 100 650 289 320 495 Filter (3-pieces) Inspection port (pipe sensor) 75 243 1 Rear wall Adjustable part 85 45 1136 Ceiling 176 105 140 18 318 2 4 or more 100 366 6 7 0 90˚ Terminal block box [2 22 [ 20 9 130 250 Less than Allowing clearances 480 (122 ) 8 1Refrigerant-pipe connection(gas pipe side/flared connection : 5/8 inch) 2Refrigerant-pipe connection(liquid pipe side/flared connection : 3/8 inch) 3Flexible hose(accessory) Drainage pipe connection(26mm I.D.) 4Knockout hole for behind refrigerant-piping arrangement 5Knockout hole for upper refrigerant-pipe arrangement 6Knockout hole for wiring arrangement : 2- [ 27 7Terminal block(indoor/outdoor connecting line) 8Terminal block(remote controller) 9Knockout hole (duct for fresh air intake): 2- [ 200 · Optional parts:duct flange( [ 200). model: PAC-SF28OF-E(1 pc.) 43 110 1180 70~90 13 130 650 280 16 288 120 165 90 Less than 210 38 5 300 Terminal block box Less than 44 500 PCA-RP71HA or more 10:20 AM 2~3 08.3.31 (Gap to ceiling) OCS05E-2.qxp Page 44 Unit : mm Use the current nuts meeting the pipe size of the outdoor unit. NOTES. 1.Use M10 or W3/8 screw for anchor bolt. The half bottom of FAN CASING can be separated. Electrical box 1482 1520 outlet> 75 1 GAS SIDE 2 LIQUID SIDE 197 21 Suspension bolt 80 70 [ 19.05 [ 15.88 [ 9.52 RP125 or more 1 18 45 85 140 2 4 Rear wall 298 176 105 Adjustable part 3 : Initial flare nut size Filter element for the exchange model:PAC-SG38KF-E (12pcs.) 360 handle 100 650 289 320 495 Filter (4-pieces) Inspection port (pipe sensor) 75 243 110 102 110 Available pipe size 1370 70~90 13 120 90 280 16 288 165 1Refrigerant-pipe connection(gas pipe side/flared connection : 5/8 inch, 3/4 inch) 2Refrigerant-pipe connection(liquid pipe side/flared connection : 3/8 inch) 3Flexible hose(accessory) Drainage pipe connection(26mm I.D.) 4Knockout hole for behind refrigerant-piping arrangement 5Knockout hole for upper refrigerant-pipe arrangement 6Knockout hole for wiring arrangement : 2- [ 27 7Terminal block(indoor/outdoor connecting line) 8Terminal block(remote controller) 9Knockout hole (duct for fresh air intake) : 2- [ 200 · Optional parts:duct flange( [ 200). model: PAC-SF28OF-E(1 pc.) 650 210 38 2 15 300 130 Less than 5 Less than 130 Terminal block box 500 45 or more 10:20 AM 90˚ 2~3 08.3.31 (Gap to ceiling) OCS05E-2.qxp Page 45 Unit : mm 10 10 38 38 controller Front side Knockout hole for refrigerant and drainage 90 60 oval (Provided on both sides) 235 70 600 71 250 270 180 130 Metal fixture against overturning 530 520 260 240 370 340 125 Knockout hole for under-piping(120 70 oval) 95 Terminal block for heater power supply 22 (Only PSH-P·GAH) Terminal block for indoor/outdoor connection. 50 Knockout hole for wiring [27 (Provided on both sides) Front side Rear side A 105 Knockout hole for under-piping Drain pipe Gas pipe [15.88(5/8 inch) Liquid pipe [ 9.52(3/8 inch) Knockout hole for piping and wiring (140 80 oval) 47 95 Electrical parts box 277 461 20 20 160 218 VIEW "A" Knockout hole for bottom fixing 90 15 111 Knockout hole for branch duct 100 130 130 100 240 130 50 260 20 10 827 30 132 40 1900 143 55 Rear side 115 766 608 216 175 123 714 46 767 40 186 66 Front 1,000 or more 100 or more 1 2 300 or more 5 or more 1. Service access allows for insertion of screw driver. 2. Adjustable 100 or more PSA-RP71GA 110 10:20 AM 590 08.3.31 480 OCS05E-2.qxp Page 46 Unit : mm controller 315 Knockout hole for refrigerant and drainage 90 60 oval (Provided on both sides) 70 600 71 330 350 260 130 Metal fixture against overturning 530 520 260 240 370 340 125 130 130 10 10 38 38 Front side 100 15 111 Knockout hole for branch duct 130 50 260 20 132 40 1900 Knockout hole for 95 under-piping(120 70 oval) Terminal block for indoor/outdoor connection. Terminal block for heater power supply (Only PSH-P·GAH) 22 Knockout hole for bottom fixing Knockout hole for wiring [27 (Provided on both sides) A 20 461 Front side Rear side 105 Gas pipe Drain pipe 66 40 261 Front 1,000 or more 100 or more 1. Service access allows for insertion of screw driver. 2. Adjustable 100 or more [ 19.05 [15.88(5/8 inch) [19.05(3/4 inch) Liquid pipe [9.52(3/8 inch) Knockout hole for piping and wiring (140 80 oval) 47 95 — [ 19.05 [ 9.52 [ 15.88 [ 9.52 RP100,125,140 P100,125,140 : Initial flare nut size GAS SIDE LIQUID SIDE Available pipe size Use the current nuts meeting the pipe size of the outdoor unit. Knockout hole for under-piping Electrical parts box 277 120 20 218 VIEW "A" 120 240 50 201 77 Rear side 115 10 827 30 255 123 714 766 608 216 140 767 47 110 PSA-RP100GA PSA-RP125GA PSA-RP140GA 590 10:20 AM 480 08.3.31 1 2 300 or more 5 or more OCS05E-2.qxp Page 47 Unit : mm OCS05E-2.qxp 08.3.31 10:20 AM Page 48 Unit : mm OUTDOOR UNIT PUHZ-RP35VHA2 PUHZ-RP50VHA2 PUHZ-RP35VHA3 PUHZ-RP50VHA3 400 [33 drain hole 347.5 365 Air intake 330 300 152 155 43.6 Air intake [33 drain hole 45.4 40 18 Service panel 23 32.5 4-10 o 21 oval hole (M10 foundation bolt) Service panel for charge plug Air discharge Handle for moving 43 Connection for gas pipe 90 10 155 300 35 600 Connection for liquid pipe 150 183 69 287.5 Service port Installation bolt pitch: 500 800 1. FOUNDATION BOLTS 2. PIPING-WIRING DIRECTION Please secure the unit firmly with 4 foundation (M10) bolts. (Bolts, washer and nut must be purchased locally.) Free space around the outdoor unit (basic example) Piping and wiring connection can be made from the rear direction only. 100 mm or more as long as no obstacle is placed on the rear and light-and-left sides of the unit. 100 mm w1 18 or below Basically open 3. ATTACHING THE CONDUIT ore m 00 m or m 1 In order to attach the conduit, it is necessary to fix the metal plate with 2 screws to the back panel. Procure the metal plate and make screw holes locally. It is recommended to use the metal plate shown below. Align the metal plate to the marks on the unit and attach it. FOUNDATION or m w The position and the size of conduit hole depend on the conduit to be used. ore 40 w1 w2 ore m 0m 50 or m 350 mm 20 or m ore 2 sides should be open in the right, left and rear side. 60 Minimum installation space for outdoor unit 80 w Conduit hole w 1. In the place where short cycle tends to occur, cooling and heating capacity and power consumption might get lowered by 10%. Air outlet guide (optional PAC-SG58SG) will help them improve. w 2. If air discharges to the wall, the surface might get stained. Holes for metal plate fixing screw w The size of hole depends on the screw to be used. 48 Over10 Service space Front piping hole (Knockout) Front trunking hole (Knockout) 92 {92 40 65 45 Power supply wiring hole (2-{27Knockout) 19 92 75 55 40 {92 Right piping hole (Knockout) Piping Knockout Hole Details Air Intake Handle for moving w1 ···Indication of STOP VALVE connection location Over 65 45 92 {92 40 Rear piping hole (Knockout) Side Air Intake Handle for moving Handle for moving Rear Air Intake Piping and wiring connections can be made from 4 directions: front, right, rear and below. 4 PIPING-WIRING DIRECTIONS Power supply wiring hole (2-{27Knockout) Rear trunking hole (Knockout) FOUNDATION Please secure the unit firmly with 4 foundation (M10) bolts. (Bolts and washers must be purchased locally.) 30 Power supply wiring hole (2-{27Knockout) Right trunking hole (Knockout) 500 Over 1···Refrigerant GAS pipe connction (FLARE) {15.88(5/8 inch) 2···Refrigerant LIQUID pipe connection (FLARE) { 9.52(3/8 inch) Example of Notes m 0m er 1 Ov m 00m er 5 Ov m 00m er 1 Ov m 0m er 1 Ov Dimensions of space needed for service access are shown in the below diagram. 500 3 FOUNDATION BOLTS Less than 2 SERVICE SPACE Handle for moving Side Air Intake 943 FREE 55 27 330 30 30 23 The diagram below shows a basic example. Explantion of particular details are given in the installation manuals etc. 73 63 23 55 27 63 23 27 92 73 Over100 73 63 23 473 219 1 FREE SPACE (Around the unit) 322 220 175 145 145 145 Earth terminal 950 Air Discharge Installation Feet 600 Rear Air Intake 42 Drain hole (5-{33) 71 2 1 Handle for moving Service panel Terminal Connections Left···Power supply wiring Reight···Indoor/Outdoor wiring 2-12o36 oval holes (Foundation Bolt M10) 65 175 2-U Shaped notched holes (Foundfation Bolt M10) 71 49 81 45 56 53 (19) 370 417 28 Bottom piping hole (Knockout) Rear piping cover Front piping cover PUHZ-RP60VHA2 PUHZ-RP71VHA2 w1 443 10:20 AM 673 08.3.31 w1 447 OCS05E-2.qxp Page 49 PUHZ-RP60VHA3 PUHZ-RP71VHA3 Unit : mm m 00m FREE mm r 10 Ove m 0m r 15 Ove 10 Service space Over 500 Over Front piping hole (Knockout) 92 {92 65 Power supply wiring hole (2-{27Knockout) Front trunking hole 40 45 (Knockout) 19 92 75 Right piping hole (Knockout) Piping Knockout Hole Details 55 {92 Air intake Handle for moving 150 500 40 65 45 Right trunking hole (Knockout) 92 {92 40 Handle for moving Handle for moving Rear piping hole (Knockout) Rear trunking hole (Knockout) Side Air Intake Rear Air Intake Piping and wiring connections can be made from 4 directions: front, right, rear and below. 4 PIPING-WIRING DIRECTIONS Power supply wiring hole (2-{27Knockout) FOUNDATION Please secure the unit firmly with 4 foundation (M10) bolts. (Bolts and washers must be purchased locally.) Power supply wiring hole (2-{27Knockout) 1···Refrigerant GAS pipe connction (FLARE){15.88(5/8 inch) 2···Refrigerant LIQUID pipe connection (FLARE){ 9.52(3/8 inch) w 1···Indication of STOP VALVE connection location. Example of Notes Ove mm r 10 r 10 Ove Over Over 3 FOUNDATION BOLTS Less than Dimensions of space needed for service access are shown in the diagram below. 30 2 SERVICE SPACE 175 322 145 Air Discharge Installation Feet 600 Rear Air Intake 66 175 2-U Shaped notched holes (Foundation Bolt M10) 30 220 145 145 Earth terminal 950 42 Handle for moving Side Air Intake 1350 The diagram below shows a basic example. Explantion of particular details is given in the installation manuals etc. 55 27 63 23 27 92 73 635 371 Drain hole (5-{33) 71 2 1 Handle for moving Service panel Terminal connection Left···Power supply wiring Right···Indoor/Outdoor wiring 2-12 x 36 Oval holes (Foundation Bolt M10) 417 1 FREE SPACE (Around the unit) 73 63 23 73 63 23 55 27 330 30 23 219 (19) 45 56 370 53 28 71 50 81 Front piping cover 1,079 930 RP·V RP·Y Bottom piping hole (Knockout) Rear piping cover A PUHZ-RP100VHA2 PUHZ-RP100VHA3 PUHZ-RP125VHA2 PUHZ-RP140VHA2 PUHZ-RP100YHA2 PUHZ-RP100YHA3 PUHZ-RP125YHA2 PUHZ-RP140YHA2 w 1 443 10:21 AM A 08.3.31 w 1 447 OCS05E-2.qxp Page 50 Unit : mm r1 m 0m FREE 10m m 5 1 er Ov er Ov m 0m 10 500 Over Handle for moving Service space Over [12.7 (1/2 inch) PUHZ-RP250YHA2 421 447 A Front piping hole (Knockout) 92 [92 Front trunking hole 40 (Knockout) 65 45 Power supply wiring hole (2-[27Knockout) Piping Knockout Hole Details [9.52 (3/8 inch) PUHZ-RP200YHA2 2 19 92 75 Right piping hole (Knockout) Air Intake 1· · · ·Refrigerant GAS pipe connction (FLARE)[19.05(3/4 inch) 2· · · ·Refrigerant LIQUID pipe connection (FLARE) *1· · · ·Indication of STOP VALVE connection location. *2· · · ·Refrigerant GAS PIPE connention(BRAZING) O.D[25.4 Example of Notes e Ov m 10m 00 er Ov 150 500 Over 55 [92 Less than 40 65 45 Right trunking hole (Knockout) 92 Handle for moving Handle for moving Rear piping hole (Knockout) Rear trunking hole (Knockout) Power supply wiring hole (2-[27Knockout) Rear Air Intake [92 40 FOUNDATION Side Air Intake Side Air Intake Piping and wiring connections can be made from 4 directions: front, right, rear and below. Please secure the unit firmly with 4 foundation (M10) bolts. (Bolts and washers must be purchased locally.) 4 PIPING-WIRING DIRECTIONS 3 FOUNDATION BOLTS Power supply wiring hole (2-[27Knockout) Dimensions of space needed for service access are shown in the below diagram. 55 27 Over The diagram below shows a basic example. Explantion of particular details is given in the installation manuals etc. 63 73 30 2 SERVICE SPACE 23 27 92 30 220 322 Air Discharge 175 Rear Air Intake 330 Handle for moving Side Air Intake 1350 635 371 145 145 950 145 Drain hole (5-[33) 71 60 175 Earth terminal 2-12o36 oval holes (Foundation Bolt M10) 70 Installation Feet 600 2-U Shaped notched holes (foundation Bolt M10) 19 370 ( Terminal Connections Left···Power supply wiring Right···Indoor/Outdoor wiring 56 40 0 53 Brazing 1 2 Handle for moving Service Panel 37 28 Front piping cover Rear piping cover Bottom piping hole (Knockout) 71 1 FREE SPACE (Around the unit) 73 63 23 73 63 23 55 27 *1 A 30 23 219 81 417 *2 339 51 *1 439 ) 10:21 AM 999 08.3.31 995 OCS05E-2.qxp Page 51 PUHZ-RP200YHA2 PUHZ-RP250YHA2 Unit : mm OCS05E-2.qxp 08.3.31 10:21 AM Page 52 Unit : mm WIRED REMOTE CONTROLLER 43.5 120 130 19 52 08.3.31 10:21 AM Page 53 Unit : mm WIRELESS REMOTE CONTROLLER 58 159.3 55 19 OCS05E-2.qxp 53 OCS05E-2.qxp 08.3.31 4 10:21 AM Page 54 WIRING DIAGRAM 4-1. INDOOR UNIT PLA-RP35BA PLA-RP50BA PLA-RP100BA PLA-RP125BA PLA-RP60BA PLA-RP140BA PLA-RP71BA [LEGEND] SYMBOL I.B CN2L CN32 CN41 CN51 DSA FUSE LED1 LED2 LED3 SW1 SW2 SWE X1 ZNR01,02 DCL DP FS NAME INDOOR CONTROLLER BOARD CONNECTOR (LOSSNAY) CONNECTOR (REMOTE SWITCH) CONNECTOR (HA TERMINAL-A) CONNECTOR (CENTRALLY CONTROL) SURGE ABSORBER FUSE (T6.3AL250V) POWER SUPPLY (I.B) POWER SUPPLY (R.B) TRANSMISSION (INDOOR-OUTDOOR) SWITCH (MODEL SELECTION) wSee table 1 SWITCH (CAPACITY CORD) wSee table 2 CONNECTOR (EMERGENCY OPERATION) RELAY (DRAIN PUMP) VARISTOR REACTOR DRAIN-UP MACHINE DRAIN FLOAT SWITCH SYMBOL MF MV TB2 TB4 TB5,TB6 NAME FAN MOTOR VANE MOTOR TERMINAL BLOCK (Indoor unit Power (option)) TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) TERMINAL BLOCK (REMOTE CONTROLLER TRANSMISSION LINE) ROOM TEMP. THERMISTOR (0: / 15k", 25: / 5. 4k" DETECT) PIPE TEMP. THERMISTOR/LIQUID (0: / 15k", 25: / 5. 4k" DETECT) COND. / EVA. TEMP. THERMISTOR (0: / 15k", 25: / 5. 4k" DETECT) TH1 TH2 TH5 OPTIONAL PART W.B BZ LED1 LED2 RU SW1 SW2 PCB FOR WIRELESS REMOTE CONTROLLER BUZZER LED (OPERATION INDICATION : GREEN) LED (PREPARATION FOR HEATING : ORANGE) RECEIVING UNIT EMERGENCY OPERATION (HEAT / DOWN) EMERGENCY OPERATION (COOL / UP) Refer to tables 1 and 2. DCL TB5 2 1 TRANSMISSION WIRES DC12V 2 1 TB6 YLW R.B I.B VANE CNV(WHT) SW1 20 18 16 14 12 10 8 6 4 2 J41 J42 SW2 19 17 15 13 11 9 7 5 3 1 CN32 (WHT) 1 CN51(WHT) Pair No. 5 2 1 LED1 3 AUTO GRILLE CN3G 1 (BLK) WIRELESS CN90 (WHT) 9 I-SEE I-SEE SENSOR SENSOR MOTOR CN4Y CN6Y (WHT) (RED) 1 4 9 5 5 5 5 M M M M MV MV MV MV 4 CNB 6 1 2 LED2 SW2 LED1 GRILLE 1 2 3 4 5 ON OFF 4 FS 3 I-SEE SENSOR CORNER PANEL (OPTIONAL PART) 1 CN3G PLA-RP50BA PLA-RP60BA PLA-RP71BA t° t° TH2 TH5 t° TH1 CN3A SW2(CAPACITY CODE) MODELS 1 2 5 3 1 W.B SW2 Manufacture/Service MODELS 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 ON PLA-RP100BA OFF ON PLA-RP125BA OFF ON PLA-RP140BA OFF ZNR01 YLW ORN X1 FAN CNMF (WHT) 7 4 1 1 D.U.M 3 CNP (BLU) TB4 YLW S1 ORN S2 S3 TO OUTDOOR UNIT ORN BRN M 3~ 1~ MF DP w Be sure to turn off the power source and then disconnect fan motor connector. (Failure to do so will cause trouble in Fan motor.) AUTOMATIC FILTER ELEVATION PANEL (OPTIONAL PART) PLA-RP35BA 4 1 U.B RU
SW1(MODEL SELECTION) SW1 Manufacture/Service (BLU) 1 U DC325V MS M MT SW1 3 1 FUSE ZNR02 U RECTIFICATION ON OFF AUTO GRILLE FLOAT SW LIQUID/PIPE INTAKE POWER CN4F CN44 CN20 CNAC (WHT) (WHT) (RED) (WHT) 3 5 I-SEE SENSOR BZ 1 (BLU) REMOCON CN22 1 SWE 3 1 4 DSA INDOOR/OUTDOOR COMMUNICATION CN3C 1 CN2L LED2 (BLK) 1 3 CN41(WHT) LED3 Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual. OUTDOOR 1 3 5 CN01 3 w1(Fig. 1) CN01 I.B (BLK) YLW 5 ORN 3 1 RED BLU GRN/YLW TB2 L N POWER SUPPLY ~(1PHASE) 230V 50Hz Manufacture/Service 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 YLW TB4 ORN S1 ORN S2 BRN S3 ON OFF ON OFF I.B TO OUTDOOR UNIT 1 3 INDOOR/OUTDOOR CN3C COMMUNICATION (BLU) ON OFF ON OFF Notes: 1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block). 2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings. 3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing. 4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of power and signal. w1: When supplying power separately to indoor and outdoor units, refer to Fig 1. w2: For power supply system of this unit, refer to the caution label located near this diagram. 54 OCS05E-2.qxp 08.3.31 10:21 AM Page 55 PLA-RP71BA2 PLA-RP100BA2 PLA-RP125BA2 [LEGEND] SYMBOL I.B CN2L CN32 CN41 CN51 DSA FUSE LED1 LED2 LED3 SW1 SW2 SWE X1 ZNR01,02 DCL DP FS NAME INDOOR CONTROLLER BOARD CONNECTOR (LOSSNAY) CONNECTOR (REMOTE SWITCH) CONNECTOR (HA TERMINAL-A) CONNECTOR (CENTRALLY CONTROL) SURGE ABSORBER FUSE (T6.3AL250V) POWER SUPPLY (I.B) POWER SUPPLY (R.B) TRANSMISSION (INDOOR-OUTDOOR) SWITCH (MODEL SELECTION) wSee table 1 SWITCH (CAPACITY CODE) wSee table 2 CONNECTOR (EMERGENCY OPERATION) RELAY (DRAIN PUMP) VARISTOR REACTOR DRAIN-UP MACHINE DRAIN FLOAT SWITCH
SW2(CAPACITY CODE) SW2 MODELS Manufacture/Service PLA-RP71BA2 PLA-RP100BA2 PLA-RP125BA2 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 SYMBOL MF MV TB2 TB4 TB5,TB6 NAME FAN MOTOR VANE MOTOR TERMINAL BLOCK (Indoor unit Power (option)) TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) TERMINAL BLOCK (REMOTE CONTROLLER TRANSMISSION LINE) ROOM TEMP. THERMISTOR (0: / 15kΩ, 25: / 5. 4kΩ DETECT) PIPE TEMP. THERMISTOR/LIQUID (0: / 15kΩ, 25: / 5. 4kΩ DETECT) COND. / EVA. TEMP. THERMISTOR (0: / 15kΩ, 25: / 5. 4kΩ DETECT) TH1 TH2 TH5 OPTION PART W.B BZ LED1 LED2 RU SW1 SW2 PCB FOR WIRELESS REMOTE CONTROLLER BUZZER LED (OPERATION INDICATION : GREEN) LED (PREPARATION FOR HEATING : ORANGE) RECEIVING UNIT EMERGENCY OPERATION (HEAT / DOWN) EMERGENCY OPERATION (COOL / UP)
SW1(MODEL SELECTION) SW1 Manufacture/Service Refer to tables 1 and 2. ON OFF ON OFF 2 1 TB6 ON OFF 1 2 3 4 5 TB5 2 1 TRANSMISSION WIRES DC12V DCL ON OFF YLW R.B I.B VANE CNV(WHT) SW1 20 18 16 14 12 10 8 6 4 2 SW2 J41 J42 CN32 (WHT) 1 CN51(WHT) Pair No. 19 17 15 13 11 9 7 5 3 1 5 2 1 LED2 4 LED1 3 AUTO GRILLE CN3G 1 (BLK) WIRELESS CN90 (WHT) 9 5 5 5 I-SEE SENSOR MOTOR CN6Y (RED) 6 1 4 CNB BZ I-SEE SENSOR 5 MV M MV M MV M SW1 LED2 MV SW2 LED1 1 4 1 U DC325V ZNR01 RECTIFICATION (BLU) W.B 3 4 t° FS I-SEE SENSOR CORNER PANEL (OPTION PART) RU GRILLE 3 1 FUSE ZNR02 U 1 2 7 t° t° M MT M 1 2 REMOCON CN22 1 3 5 DSA FAN CNMF (WHT) 4 YLW ORN X1 TO OUTDOOR UNIT ORN BRN 1 D.U.M CNP 1 3 TB4 YLW S1 ORN S2 S3 (BLU) 9 5 I-SEE SENSOR CN4Y 1 (WHT) 4 (BLK) (BLU) SWE ON OFF AUTO GRILLE POWER FLOAT SW LIQUID/PIPE INTAKE CNAC CN20 CN4F CN44 (WHT) (RED) (WHT) (WHT) 3 1 1 OUTDOOR CN01 1 3 INDOOR/OUTDOOR COMMUNICATION CN3C 1 CN41(WHT) CN2L LED3 3 U.B 3 1 CN3G 5 3 1 CN3A TH2 TH5 TH1 MS 3~ M 1~ MF DP wBe sure to turn off the power source and then disconnect fan motor connector. (Failure to do so will cause trouble in fan motor) AUTOMATIC FILTER ELEVATION PANEL (OPTION PART) w1(Fig. 1) CN01 I.B (BLK) YLW 5 ORN 3 1 Notes: 1.SymboIs used in wiring diagram above are, :Connector, : : Terminal (block). 2.Indoor and outdoor connecting wires have poIarities, make sure to match the terminal numbers (S1, S2, S3) for correct wirings. 3.Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring for servicing. 4.This diagram shows the wiring of indoor and outdoor connecting wires.(specification of 230V), adopting superimposed system of power and signal. w1:When work to supply power separately to indoor and outdoor units was applied, refer to Fig 1. w2:For power supply system of this unit, refer to the caution label located near this diagram. I.B RED BLU GRN/YLW YLW ORN ORN BRN TB2 L N TB4 S1 S2 S3 INDOOR/OUTDOOR COMMUNICATION 1 3 CN3C(BLU) Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual. 55 POWER SUPPLY ~(1PHASE) 230V 50Hz TO OUTDOOR UNIT OCS05E-2.qxp 08.3.31 10:21 AM PLA-RP35AA Page 56 PLA-RP50AA PLA-RP60AA PLA-RP71AA [LEGEND] SYMBOL P.B I.B FUSE ZNR BCR CN2L CN32 CN41 CN51 LED1 LED2 LED3 X1 X4 SW1 SW2 SWE C NAME INDOOR POWER BOARD INDOOR CONTROLLER BOARD FUSE(T6.3AL250V) VARISTOR FAN CONTROL ELEMENT CONNECTOR(LOSSNAY) CONNECTOR(REMOTE SWITCH) CONNECTOR(HA TERMINAL-A) CONNECTOR(CENTRALLY CONTROL) POWER SUPPLY(I.B) POWER SUPPLY(I.B) TRANSMISSION(INDOOR-OUTDOOR) RELAY(DRAIN PUMP) RELAY(FAN MOTOR) SWITCH(MODEL SELECTION)wSee table 1 SWITCH(CAPACITY CORD)wSee table 2 CONNECTOR(EMERGENCY OPERATION) CAPACITOR(FAN MOTOR) SYMBOL MF MV H2 DP DS TB2 TB4 TB5, TB6 TH1 TH2 TH5 R.B NAME SYMBOL FAN MOTOR W.B VANE MOTOR RU DEW PREVENTION HEATER BZ DRAIN-UP MACHINE LED1 DRAIN SENSOR LED2 TERMINAL BLOCK (HEATER)wPLH-P.AAH SW1 models only or option for PLA-RP.AA models. SW2 TERMINAL BLOCK (INDOOR/ HEATER OUTDOOR CONNECTING LINE) FS1 FS2 TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE) H1 26H ROOM TEMP.THERMISTOR (0:/15k", 25:/5.4k" DETECT) 88H PIPE TEMP.THERMISTOR/LIQUID (0:/15k", 25:/5.4k" DETECT) COND./EVA. TEMP. THERMISTOR (0:/15k", 25:/5.4k" DETECT) WIRED REMOTE CONTROLLER BOARD NAME WIRELESS REMOTE CONTROLLER BOARD RECEIVING UNIT BUZZER LED(RUN INDICATOR) LED(HOT ADJUST) SWITCH(HEATING ON/OFF) SWITCH(COOLING ON/OFF) THERMAL FUSE(72:, 16A) THERMAL FUSE(104:, 16A) HEATER HEATER THERMAL SWITCH HEATER CONTACTOR GRILLE MV MV MV MV 5 5 5 5 H2 5 MF 3 2 1 DC 13.1V 2 1 1 2 3 6 7 4 8 9 5 10 1 2 3 CNSK P.B (RED) CN2S (WHT) TB4 YLW S1 ORN S2 ORN S3 BRN TO OUTDOOR UNIT 5 1 2 3 DP BCR X4 X1 BRN ORN BLK WHT 1 3 VANE CND POWER INDOOR/OUTDOOR CN6V (ORN) CN2D COMMUNICATION (GRN) (WHT) CN3C (BLU) CN51 CN41 CN2L 1 3 POWER 1 2 FUSE D.U.M 1 3 D.HEATER 1 3 1 3 CNC(RED) CNP POWER (BLU) CNDK (RED) X4 FAN 1 3 5 (WHT) YLW ORN RED WHT YLW YLW I.B YLW YLW RED WHT BLK C X1 ZNR CN32 SWE SW2 LED3 LED2 HEATER D.SENSOR CN24 CN31 (YLW) (WHT) SW1 ON OFF DS Refer to tables 1 and 2. BLU BLU 1 2 3 LED1 INTAKE LIQUID PIPE REMOCON CN20 CN21 CN29 CN22 WIRELESS (RED) (WHT) (BLK) (BLU) CN90 1 2 1 2 1 2 1 2 (WHT) TH1 2 1 W.B BZ 9 LED1 SW1 SW2 RU R.B TB5 TRANSMISSION WIRES DC12V TH2 LED2 CNB 1 2 TB6 TB2 RED BLU GRN/YLW W1 (Fig.1) TH3 [PLH-P.AAH models only] I.B FS2 1 3 WHT 26H 88H GRY 1 3 POWER INDOOR/OUTDOOR CND COMMUNICATION (ORN) CN3C (BLU) 1 2 YLW YLW I.B YLW TB4S1 ORN S2 ORN S3 BRN H1 YLW ORN POWER SUPPLY ~(1PHASE) 230V 50Hz TB2 88H FS1 L RED RED RED 1 N BLU 2 WHT GRN/YLW HEATER CN24 (YLW) 6 5 WHT TO OUTDOOR UNIT Table 2 SW1 MODELS Manufacture/Service 56 POWER SUPPLY ~(1PHASE) 230V 50Hz Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual. Table 1 Notes: 1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block). PLA-RP. AA 2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings. 3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit PLH-P. AAH electric wiring diagram for servicing. 4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of power and signal. w1: When supplying power separately to indoor and outdoor units, refer to Fig 1. w2: For power supply system of this unit, refer to the caution label located near this diagram. L N 1 2 3 4 5 1 2 3 4 5 MODELS SW2 Manufacture/Service ON OFF PLA-RP35AA PLH-P35AAH 1 2 3 4 5 ON OFF PLA-RP50AA PLH-P50AAH 1 2 3 4 5 PLA-RP60AA PLH-P60AAH 1 2 3 4 5 PLA-RP71AA PLH-P71AAH 1 2 3 4 5 ON OFF ON OFF ON OFF ON OFF OCS05E-2.qxp 08.3.31 10:21 AM PLA-RP100AA2 Page 57 PLA-RP125AA2 PLA-RP140AA2 [LEGEND] SYMBOL P.B FUSE ZNR IPM I.B CN2L CN32 CN41 CN51 LED1 LED2 LED3 X1 SW1 SW2 SWE MF NAME INDOOR POWER BOARD FUSE(T5AL250V) VARISTOR POWER MODULE INDOOR CONTROLLER BOARD CONNECTOR(LOSSNAY) CONNECTOR(REMOTE SWITCH) CONNECTOR(HA TERMINAL-A) CONNECTOR(CENTRALLY CONTROL) POWER SUPPLY(I.B) POWER SUPPLY(I.B) TRANSMISSION(INDOOR-OUTDOOR) RELAY(DRAIN PUMP) SWITCH(MODEL SELECTION)wSee table 1 SWITCH(CAPACITY CORD)wSee table 2 CONNECTOR(EMERGENCY OPERATION) FAN MOTOR SYMBOL MV H2 DP DS TB2 TB4 NAME SYMBOL VANE MOTOR W.B DEW PREVENTION HEATER RU DRAIN-UP MACHINE BZ DRAIN SENSOR LED1 TERMINAL BLOCK (Indoor unit Power (option)) LED2 TERMINAL BLOCK SW1 (INDOOR/OUTDOOR CONNECTING LINE) SW2 TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE) REACTOR ROOM TEMP.THERMISTOR (0:/15k", 25:/5.4k" DETECT) PIPE TEMP.THERMISTOR/LIQUID (0:/15k", 25:/5.4k" DETECT) COND./EVA. TEMP. THERMISTOR (0:/15k", 25:/5.4k" DETECT) WIRED REMOTE CONTROLLER BOARD TB5, TB6 DCL TH1 TH2 TH5 R.B NAME WIRELESS REMOTE CONTROLLER BOARD RECEIVING UNIT BUZZER LED(RUN INDICATOR) LED(HOT ADJUST) SWITCH(HEATING ON/OFF) SWITCH(COOLING ON/OFF) 5 MF BLK WHT RED 3 2 1 5 3 1 IPM CN2S (WHT) 2 1 P.B POSITION DETECTION SENSOR INPUT CN3 (WHT) CN4 (WHT) FUSE TRANS ZNR RECTIFIER 3 FAN 2 CN2 1 (GRN) CN01 (BLK) 5 3 1 CN03 (BLU) DCL YLW TB4 YLW S1 ORN S2 ORN S3 BRN YLW ORN CN02 2 1 (GRN) 1 3 5 FAN 1 2 3 CN33 (GRN) D.U.M 1 3 CNP (BLU) X1 D.HEATER 1 3 CNC (RED) X1 1 3 POWER 1 3 J42 J41 Refer to tables 1 and 2. 1 2 3 DS 5 W.B BZ LED2 LED1 SW1 SW2 CNB R.B 1 2 TB6 Notes: 1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block). w1 (Fig.1) 2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal CN01 numbers (S1, S2, S3) for correct wirings. (BLK) 3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit 5 electric wiring diagram for servicing. 4. This diagram shows the wiring of indoor and outdoor connecting wires (specification 3 of 230V), adopting superimposed system of power and signal. 1 w1: When supplying power separately to indoor and outdoor units, refer to Fig 1. w2: For power supply system of this unit, refer to the caution label located near this diagram. Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual. P.B TB2 YLW ORN 1 2 3 4 5 ON OFF (Table 2) SW2 (CAPACITY CORD) SW2 MODELS Manufacture/Service MODELS PLA-RP100AA2 PLA-RP125AA2 1 2 3 4 5 1 2 3 4 5 ON OFF PLA-RP140AA2 ON OFF 57 1 3 Manufacture/Service 1 2 3 4 5 ON OFF RED BLU GRN/YLW L N YLW TB4S1 ORN S2 ORN BRN S3 I.B (Table 1) SW1 (MODEL SELECTION) SW1 Manufacture/Service RU TB5 TRANSMISSION WIRES DC12V wBe sure to turn off the power source TH2 and then disconnect fan motor connector. (Failure to do so will cause trouble in fan motor.) TH5 H2 GRILLE INTAKE LIQUID PIPE REMOCON CN20 CN21 CN29 CN22 WIRELESS (RED) (WHT) (BLK) (BLU) CN90 1 2 1 2 1 2 1 2 (WHT) 2 1 5 1 2 3 6 7 4 8 9 5 10 9 TH1 5 5 CN41 CN2L BLU BLU SWE SW2 ON OFF 5 1 2 VANE CND INDOOR/OUTDOOR POWER CN6V (ORN) COMMUNICATION CN2D (GRN) CN3C (WHT) 5 (BLU) CN32 CN51 LED3 LED2 LED1 SW1 Pair No. D.SENSOR CN31 (WHT) MV MV MV MV BLK WHT BRN ORN ORN YLW YLW YLW I.B GRILLE YLW YLW PNK WHT BLK DP TO OUTDOOR UNIT INDOOR/OUTDOOR COMMUNICATION CN3C (BLU) POWER SUPPLY ~(1PHASE) 230V 50Hz TO OUTDOOR UNIT OCS05E-2.qxp 08.3.31 10:21 AM Page 58 PEAD-RP35EA2 PEAD-RP50EA PEAD-RP60EA PEAD-RP71EA PEAD-RP100EA2 PEAD-RP125EA PEAD-RP140EA [LEGEND] NAME SYMBOL SYMBOL I.B. INDOOR CONTROLLER BOARD SW2 FUSE FUSE(T6.3AL250V) SWE ZNR VARISTOR X1 CN2L CONNECTOR(LOSSNAY) X4 X5 CN24 CONNECTOR(HEATER) CN32 CONNECTOR(REMOTE SWITCH) X6 CN41 CONNECTOR(HA TERMINAL-A) P.B. CN51 CONNECTOR(CENTRALLY CONTROL) DRAIN PUMP DP CN90 CONNECTOR(WIRELESS) LED1 POWER SUPPLY(I.B.) DS LED2 POWER SUPPLY(REMOTE CONTROLLER) C LED3 TRANSMISSION(INDOOR·OUTDOOR) MF SW1 SWITCH(MODEL SELECTION) NAME SYMBOL SWITCH(CAPACITY CORD) TB4 SWITCH(EMERGENCY OPERATION) RELAY(DRAIN PUMP) TB5 RELAY(FAN MOTOR) TH1 RELAY(FAN MOTOR) RELAY(FAN MOTOR) TH2 INDOOR POWER BOARD (OPTIONAL PARTS) TH5 DRAIN PUMP DRAIN SENSOR CAPACITOR(FAN MOTOR) FAN MOTOR NAME TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) TERMINAL BLOCK(REMOTE CONTROLLER) INTAKE AIR TEMP. THERMISTOR (0: /15t, 25:/5.4t DETECT) PIPE TEMP. THERMISTOR/LIQUID (0: /15t, 25:/5.4t DETECT) COND./EVA. TEMP. THERMISTOR (0: /15t, 25:/5.4t DETECT) INSIDE SECTION OF CONTROL BOX DS TH1 TH2 TH5 1 B B L L U U 3 CN31 1 2 1 2 CN22 (BLU) CN20 (RED) I.B. 1 2 1 2 3 1 2 3 4 5 6 7 8 9 1 2 3 4 1 2 1 2 3 45 1 2 3 CN21 CN29 (WHT) (BLK) CN31 (WHT) CN90 (WHT) CN41 (WHT) CN24 (YLW) CN51 (WHT) CN32 (WHT) 1 2 1 2 SW1 CN2L (RED) SW2 SWE ON OFF LED1 LED2 LED3 2 1 WHT BLK X1 (BLU) CN3C X4 X5 X6 X5 CN2D (WHT) ZNR FUSE (ORN) CND O3B 1 R R N N X4 X1 W3B1 H L T K O3Y 1 R L N W (RED) CNDK 3 1 X6 7 5 3 1 (BLU) CNP (WHT) FAN W P P B H N N L T K K K External static pressure 30Pa W B H L T K TB5 BL TO MA-REMOTE CONTROLLER DC8.7-13V U B L U 2 1 W H T 3 2 1 wA 2 1 B L K CN2S (WHT) External static pressure 70Pa DP P.B. External static pressure 70Pa 1 CNSK (RED) Optional parts 1 2 3 4 5 6 (RED) Optional parts 1 2 3 4 5 6 1 2 3 4 5 6 (RED) (WHT) TB4 S3 S2 S1 TO OUTDOOR UNIT BRN ORN YLW MF C MF C MODELS SW1 SW2 Model selection Capacity cord switch switch 12345 ON 35EA(2) OFF 12345 ON 50EA OFF 12345 ON 60EA OFF 12345 12345 ON ON 71EA OFF OFF 12345 ON 100EA(2) OFF 12345 ON 125EA OFF 12345 ON 140EA OFF External static pressure 130Pa (IN CASE OF CONNECTING THE REPLACEMENT WIRING) L N 1 2 1 2 TO CND S1 S2 S3 1 2 POWER SUPPLY ~(1PHASE) 230V 50Hz TO OUTDOOR UNIT TO CN3C Notes: 1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block). 2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings. 3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing. 4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of power and signal. w1: When supplying power separately to indoor and outdoor units, refer to wA. w2: For power supply system of this unit, refer to the caution label located near this diagram. 58 OCS05E-2.qxp 08.3.31 10:21 AM PEAD-RP60GA Page 59 PEAD-RP71GA PEAD-RP100GA [LEGEND] NAME NAME SYMBOL SYMBOL I.B. INDOOR CONTROLLER BOARD SW1 SWITCH(MODEL SELECTION) FUSE FUSE(T6.3AL250V) SW2 SWITCH(CAPACITY CORD) ZNR VARISTOR SWE SWITCH(EMERGENCY OPERATION) CN2L CONNECTOR(LOSSNAY) X1 RELAY(DRAIN PUMP) X4 RELAY(FAN MOTOR) CN24 CONNECTOR(HEATER) CN32 CONNECTOR(REMOTE SWITCH) X5 RELAY(FAN MOTOR) CN41 CONNECTOR(HA TERMINAL-A) X6 RELAY(FAN MOTOR) CN51 CONNECTOR(CENTRALLY CONTROL) P.B. INDOOR POWER BOARD C CAPACITOR(FAN MOTOR) CN90 CONNECTOR(WIRELESS) MF LED1 POWER SUPPLY(I.B.) FAN MOTOR LED2 POWER SUPPLY(REMOTE CONTROLLER) TB4 TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) LED3 TRANSMISSION(INDOOR·OUTDOOR) NAME SYMBOL TERMINAL BLOCK(REMOTE CONTROLLER) TB5 TH1 INTAKE AIR TEMP.THERMISTOR (0: /15t, 25:/5.4t DETECT) TH2 PIPE TEMP. THERMISTOR/LIQUID (0: /15t, 25:/5.4t DETECT) TH5 COND./EVA. TEMP. THERMISTOR (0: /15t, 25:/5.4t DETECT) INSIDE SECTION OF CONTROL BOX TH1 TH2 TH5 B B L L U U I.B. 1 2 1 2 1 2 1 2 CN22 (BLU) CN20 (RED) CN21 (WHT) CN29 (BLK) 1 2 3 1 2 3 4 5 6 7 8 9 1 2 3 4 CN90 (WHT) CN41 (WHT) CN31 (WHT) 1 2 CN24 (YLW) 1 2 3 4 5 1 2 3 CN51 (WHT) CN32 (WHT) 1 2 SW1 CN2L (RED) SW2 SWE ON LED1 LED2 LED3 OFF X1 2 1 WHT BLK (BLU) CN3C O3B1 R R N N ZNR TO MA-REMOTE CONTROLLER DC8.7-13V (ORN) CND W3B1 H L T K O3Y1 R L N W W H T 2 1 B L K 3 2 1 wA X1 FUSE W B H L T K TB5 BL U B 2 L 1 U X4 X5 X6 X5 CN2D (WHT) CN2S (WHT) (RED) CNDK 3 1 (BLU) CNP X4 X6 7 5 3 1 B B O L L R U K G CNSK (RED) 1 2 3 4 5 6 1 TO OUTDOOR UNIT (WHT) 240V 5Pa 10Pa 20Pa WHT 35Pa 50Pa 60Pa RED 50Pa 70Pa 75Pa MF C THE REPLACEMENT WIRING) L N 1 2 TO CND 230V BLU (Initial setting) BRN ORN YLW (IN CASE OF CONNECT 1 2 *External static pressure CONNECTOR COLOR 220V * P.B. TB4 S3 S2 S1 (WHT) FAN G Y Y B R L L L Y W W K S1 S2 S3 1 2 TO CN3C POWER SUPPLY ~(1PHASE) 230V 50Hz MODELS SW1 12345 ON OFF 60GA 12345 12345 TO OUTDOOR UNIT SW2 Model selection Capacity cord switch switch 71GA ON OFF ON OFF 12345 ON OFF 100GA Notes: 1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block). 2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings. 3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing. 4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of power and signal. w1: When supplying power separately to indoor and outdoor units, refer to wA. w2: For power supply system of this unit, refer to the caution label located near this diagram. 59 PE 1 2 TB5 60 REMOTE CONTROLLER BOARD TB6 LCD 2 1 CN3C 3 1 LED3 LED2 LED1 TAB1 CN2S CNSK 1 1 DC 3 2 13.1V 3 1 CN32 2 3 1 2 CN31 3 CN51 1 CND 3 2 1 3 2 1 C02 (3P) (Hi) TH5 TH2 TH1 CNDK 1 CN20 2 1 CN21 2 7 52F Lo 5 X1 3 FAN CR2 52F Hi 1 X4 X5 X6 X4 X5 X6 X1 5 4 C01 51F TB4 S1 S2 S3 49F CR1 X1 SWE ON OFF SW2 1 1 2 3 4 5 ON 2 CN41 OFF 3 INDOOR 4 CONTROLLER SW1 1 2 3 4 5 BOARD 1 ON CN29 OFF 2 MF1 3 1 C01 (6P) (Lo) FUSE 52F Hi ZNR 52F Lo 5 4 3 2 1 INDOOR POWER BOARD FB CN2D DC13.1V 1 2 3 4 5 CN90 6 7 8 9 1 CN22 2 1 CN2L 2 DSR DSA ZNR5~7 SNB BOARD 1 51F TERMINAL BLOCK NAME NAME FAN MOTOR (INDOOR) OVER CURRENT RELAY (INDOOR FAN MOTOR) MAGNETIC CONTACTOR (INDOOR FAN MOTOR) MAGNETIC CONTACTOR (INDOOR FAN MOTOR) INTERNAL THERMOSTAT (INDOOR FAN MOTOR) TERMINAL BLOCK ROOM TEMP. LIQUID PIPE TEMP. THERMISTOR COND./EVA. TEMP. AUXILIARY RELAY SURGE KILLER FERRITE CORE FUSE (T6.3AL250V) VARISTOR AUXILIARY RELAY SWITCH (MODEL SELECTION) SWITCH (CAPACITY CODE) CONNECTOR (EMERGENCY OPERATION) LED (POWER SUPPLY) LED (POWER SUPPLY) LED (TRANSMISSION) CONNECTOR (LOSSNAY) CONNECTOR (DRAIN SENSOR) CONNECTOR (REMOTE SWITCH) CONNECTOR (HA TERMINAL-A) CONNECTOR (CENTRALLY CONTROL) CONNECTOR (WIRELESS REMOTE CONTROLLER) VARISTOR ARRESTER TO OUTDOOR UNIT CONNECTING WIRES (POLAR) OUTDOOR UNIT Caution, 1. To protect fan motor from abnormal current, overcurrent relays are installed. Therefore, do not change factory set value of overcurrent relays. Note:1. The dotted lines show field wiring. 2. Color of earth wire is yellow and green twisting. 3. Specification subject to change without notice. 4. Indoor and outdoor connecting wires have polarities, make sure to match wiring and terminal. 5. Emergency operation If a trouble occurs with either the remote controller or the indoor microcomputer and no other trouble exists, emergency operation for cooling or heating can be performed by changing the setting of connector (SWE) "ON" on the indoor controller board. SWE :ON / Indoor fan is running at high speed. 6. mark is connector. mark is terminal. SYMBOL TB6 REMOTE CONTROLLER SYMBOL MF1 51F 52FLo 52FHi 49F TB2,4,5 TH1 TH2 TH5 X1 CR1,2 FB FUSE ZNR X4-6 SW1 SW2 SWE INDOOR LED1 CONTROLLER LED2 BOARD LED3 CN2L CN31 CN32 CN41 CN51 CN90 SNB ZNR5~7 BOARD 1 DSA,DSR 10:21 AM REMOTE CONTROLLER N TB2 RED L1 WHITE L2 BLACK L3 RED INDOOR UNIT 08.3.31 POWER SUPPLY 3N~PE 380/400/415V 50Hz CIRCUIT BREAKER (FIELD SUPPLY) PEA-RP200,250GA:15A BLACK INDOOR UNIT WHITE OCS05E-2.qxp Page 60 PEA-RP200, 250GA POWER SUPPLY 3N~PE 380/400/415V 50Hz L1 L2 L3 N 1 2 TB5 CR GREEN/YELLOW RED WHITE BLACK BLUE TB2 REMOTE CONTROLLER BOARD LCD TB6 1 CN2L 2 61 2 1 FUSE FB12 TAB1 CN2S CNSK 1 1 DC 3 2 13.1V (No.2) CND CNDK X1 5 3 1 CN3C 3 1 3 LED3 ZNR 1 CND SW2 TH1-2 TH2-2 TH5-2 FAN CNDK 7 X2 5 3 1 ON OFF ON OFF S1 S2 S3 TB4-1 S1 S2 S3 TB4-2 SWE ON OFF FAN X4 X5 X6 LED1 LED2 1 CN20 X4 X5 X6 2 3 1 7 ON OFF SWE ON OFF 1 1 2 3 4 5 2 CN41 3 INDOOR 4 CONTROLLER 1 2SW1 3 4 5 1 CN29 BOARD (No.2) 2 FB22 3 1 X4 X5 X6 1 CN20 X4 X5 X6 2 1 CN21 2 1 CN21 2 FUSE 1 SW2 3 2 ON OFF C02 1 1 1 2 3 4 5 2 CN41 3 INDOOR SW1 4 CONTROLLER 1 2 3 4 5 1 CN29 BOARD (No.1) 2 1 2 CN32 3 1 2 CN31 3 CN51 5 4 3 2 1 INDOOR FB21 POWER BOARD CN2D DC13.1V 1 2 3 4 5 CN90 6 7 8 9 1 CN22 2 TAB1 CN2S CNSK 1 DC 1 3 2 13.1V (No.1) 3 LED3 ZNR LED2 LED1 1 2 CN32 3 1 2 CN31 3 CN3C 3 1 FB11 INDOOR POWER BOARD CN2D DC13.1V 1 CN2L 2 2 1 1 2 3 4 5 CN90 6 7 8 9 1 CN22 2 CN51 5 4 3 2 1 TH5-1 TH2-1 MF1 TH1-1 DSR DSA 3 2 1 C01 49F 51F X01 X02 51F 5 52F ZNR5~7 SNB BOARD 1 52F TO OUTDOOR UNIT CONNECTING WIRES (POLAR) (No.2) TERMINAL BLOCK NAME REMOTE CONTROLLER SYMBOL NAME TB6 TERMINAL BLOCK OUTDOOR UNIT SYMBOL TB3,TB8 Caution, 1.To protect fan motor from abnormal current, overcurrent relays are installed. Therefore, do not change factory set value of overcurrent relays. Note:1. The dotted lines show field wiring. 2. Color of earth wire is yellow and green twisting. 3. Specification subject to change without notice. 4. Indoor and outdoor connecting wires have polarities, make sure to match wiring and terminal. 5. Emergency operation If a trouble occurs with either the remote controller or the indoor microcomputer and no other trouble exists, emergency operation for cooling or heating can be performed by changing the setting of connector (SWE) "ON" on the indoor controller board. SWE :ON / Indoor fan is running at high speed. 6. mark is connector. mark is terminal. OUTDOOR UNIT (No.1) OUTDOOR UNIT TO OUTDOOR UNIT CONNECTING WIRES (POLAR) FUSE (T6.3AL250V) VARISTOR AUXILIARY RELAY SWITCH (MODEL SELECTION) SWITCH (CAPACITY CORD) CONNECTOR (EMERGENCY OPERATION) LED (POWER SUPPLY) LED (POWER SUPPLY) LED (TRANSMISSION) CONNECTOR (LOSSNAY) CONNECTOR (DRAIN SENSOR) CONNECTOR (REMOTE SWITCH) CONNECTOR (HA TERMINAL-A) CONNECTOR (CENTRALLY CONTROL) CONNECTOR (WIRELESS REMOTE CONTROLLER) VARISTOR ARRESTER NAME FAN MOTOR (INDOOR) OVER CURRENT RELAY (INDOOR FAN MOTOR) MAGNETIC CONTACTOR (INDOOR FAN MOTOR) INTERNAL THERMOSTAT (INDOOR FAN MOTOR) TERMINAL BLOCK ROOM TEMP. THERMISTOR LIQUID PIPE TEMP. COND./EVA. TEMP. AUXILIARY RELAY SURGE KILLER FERRITE CORE 10:21 AM C01 4 INDOOR UNIT INDOOR UNIT SYMBOL MF1 51F 52F 49F TB2,4-1,4-2,5 TH1-1,1-2 TH2-1,2-2 TH5-1,5-2 X1,2 CR FB11,FB12 FB21,FB22 FUSE ZNR X4-6 SW1 SW2 SWE LED1 INDOOR CONTROLLER LED2 LED3 BOARD CN2L CN31 CN32 CN41 CN51 CN90 SNB ZNR5~7 BOARD 1 DSA,DSR 08.3.31 REMOTE CONTROLLER PE CIRCUIT BREAKER (FIELD SUPPLY) PEA-RP400,500GA:15A BLACK WHITE RED OCS05E-2.qxp Page 61 PEA-RP400, 500GA 08.3.31 10:21 AM PKA-RP35GAL [LEGEND] SYMBOL P.B I.B FUSE ZNR CN2L CN32 CN41 CN51 SW1 SW2 SWE X4 BCR LED1 LED2 LED3 Page 62 PKA-RP50GAL SYMBOL C MF MV TB2 NAME INDOOR POWER BOARD INDOOR CONTROLLER BOARD FUSE (T6.3AL250V) VARISTOR CONNECTOR CONNECTOR CONNECTOR CONNECTOR SWITCH wSee Table 1. SWITCH wSee Table 2. SWITCH RELAY FAN CONTROL ELEMENT POWER SUPPLY POWER SUPPLY TRANSMISSION P.B CNDK (RED) TB4 TB5,TB6 TH1 TH2 TH5 TB4 YLW S1 S2 ORN S3 ORN BRN BLK WHT YLW ORN RED WHT RED WHT BLK POWER POWER 1 2 1 3 VANE CNDK 1 3 CND 1 3 CN6V INDOOR/OUTDOOR (GRN) (RED) (ORN) POWER CN2D(WHT) COMMUNICATION CN3C(BLU) ZNR X4 CN41 CN2L CN51 CN32 RED BLU GRN/YLW TO OUTDOOR UNIT I.B 6 FUSE X4 BCR THERMAL FUSE <104:10A> THERMAL FUSE <84:10A> HEATER HEATER THERMAL SWITCH HEATER CONTACTOR TB2 C FAN 1 3 5 (WHT) NAME WIRELESS REMOTE CONTROLLER BOARD RECEIVING UNIT BUZZER LED LED SWITCH (HEATING ON/ OFF> SWITCH (COOLING ON/ OFF> WIRED REMOTE CONTROLLER BOARD w1 (Fig.1) 1 2 1 2 3 I.B SYMBOL W.B RU BZ LED1 LED2 SW1 SW2 R.B HEATER FS1 FS2 H1 26H 88H CN2S (WHT) 1 2 DC13.1V 3 MF NAME CAPACITOR FAN MOTOR VANE MOTOR TERMINAL BLOCK (HEATER) wPKH-P.GALH models only or option for PKA-RP.GAL models. TERMINAL BLOCK TERMINAL BLOCK
Maximum pipe length Liquid pipe (mm) Gas pipe (mm) OD Thickness OD Thickness RP35•50 [6.35 t0.8 [9.52 [12.7 t0.8 t0.8 Standard size 30m w1 50m [30m] [30m] 10m [10m] RP60•71 [15.88 t1.0 w2 30m [30m] [12.7 t0.8 10m [10m] 30m [30m] [9.52 t0.8 [15.88 t1.0 w2 30m [20m] Standard size 50m [30m] Standard size 50m w3 [30m] 30m [20m] RP100~140 [19.05 t1.0 [12.7 t0.8 [19.05 [15.88 t1.0 t1.0 : It can be used. : Cooling capacity is lowered. : Additional refrigerant charge is required when the pipe length exceeds 10m. 50m [30m] 50m [20m] The maximum pipe length Charge-less pipe length 50m [30m] 30m [20m] 50m [20m] w1. RP50 : maximum pipe length is 10m. w2. Change the SW8-1 on the outdoor controller circuit board from OFF to ON. w3. The maximum length is 75m in case of new pipes. (2) TWIN AND TRIPLE SYSTEM (a) TWIN SYSTEM (b) TRIPLE SYSTEM
Maximum pipe length
Maximum pipe length RP71(RP35o2) Main pipe (mm) [A] Liquid pipe Gas pipe Liquid pipe [6.35 Gas pipe [12.7 [6.35 [12.7 Branch pipe Liquid pipe [9.52 (mm) Gas pipe [15.88 [B, C] Liquid pipe [12.7 Gas pipe RP100(RP50o2) [9.52 [9.52 [15.88 [15.88 Standard size Standard size 50m 50m w [30m] [30m] 50m [30m] [9.52 [19.05 [12.7 [19.05 50m [30m] 50m [20m] 50m [30m] 50m [30m] 50m [20m] RP125(RP60o2) • RP140(RP71o2) [9.52 [15.88 Standard size 50m w [30m] [9.52 [19.05 50m [30m] RP140(RP50o3) [12.7 [19.05 Main pipe (mm) [A] 50m [20m] Branch pipe Liquid pipe ø9.52 (mm) Gas pipe ø15.88 [B, C, D] Liquid pipe ø12.7 ø9.52 ø9.52 ø15.88 ø19.05 Gas pipe Liquid pipe ø6.35 Standard size 50m w 50m Gas pipe ø12.7 [30m] [30m] Liquid pipe 50m [30m] 50m [20m] 50m [20m] Gas pipe ø19.05 [19.05 w The maximum length is 75m in case of new pipes. w The maximum length is 75m in case of new pipes. Indoor unit side Indoor unit side Indoor unit Indoor unit Indoor unit Indoor unit B h B h 50m [30m] ø12.7 ø19.05 C C D Indoor unit Distribution pipe Outdoor unit H H Outdoor unit Distribution pipe Outdoor unit side Outdoor unit side A A Total length A + B + C + D RP140: 75 m Total length A + B + C RP71 : 50 m RP100-140: 75 m 83 OCS05E-3.qxp 08.3.31 9:58 AM Page 84 8-1-2. ADJUSTING THE AMOUNT OF REFRIGERANT • Check additional refrigerant charging amount referring to table 5, 6 when liquid pipe is 1 size larger than standard diameter.
Required additional charge when the pipe size is 1 size larger than the standard diameter (1:1 SYSTEM) Liquid pipe O.D. Refrigerant amount to be added PUHZ-RP35,50 [9.52 60 g per 1 m PUHZ-RP60,71 [12.7 100 g per 1 m PUHZ-RP100~140 [12.7 100 g per 1 m Outdoor unit
Required additional charge when the pipe size is 1 size larger than the standard diameter (TWIN/TRIPLE SYSTEM) Outdoor unit When the extension pipe length (main piping + branch piping) exceeds 20 m PUHZ-RP71~140 Additional refrigerant amount W(g) = (100 o L1) + (60 o L2) + (30 o L3) - 2000 If the calculation produces a negative number ( W [ 0), additional charging is not necessary. L1: [12.7 liquid pipe length (m) L2: [9.52 liquid pipe length (m) L3: [6.35 liquid pipe length (m)
Additional refrigerant charging amount for pipe of standard diameter Additional refrigerant charging amount Permitted Amount of unit for pipe length exceeding 30 m (kg) Type Outdoor unit pipe length filling refrigerant (kg) 31 – 40m 41 – 50m 51 – 60m 61 – 70m 71 – 75m 1:1 PUHZ-RP35,50 system PUHZ-RP71 PUHZ-RP100~140 Type Outdoor unit Twin Triple PUHZ-RP71 system PUHZ-RP100~140 50m or less 2.5kg 0.2kg 0.4kg 3.5kg 0.6kg 1.2kg 75m or less 5.0kg 0.6kg 1.2kg Permitted pipe length Amount of unit filling refrigerant (kg) 31 – 40m 41 – 50m 50m or less 3.5kg 0.6kg 1.2kg 75m or less 5.0kg 0.6kg 1.2kg 1.8kg 2.4kg Additional refrigerant charging amount for pipe length exceeding 30 m (kg) 84 51 – 60m 1.8kg 61– 70m 71 – 75m 2.4kg OCS05E-3.qxp 08.3.31 9:58 AM Page 85 8-1-3. CAPACITY CORRECTION CURVES Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity curves below. When the diameter of gas pipe is 1 size smaller than standard diameter, cooling capacity is lowered comparing to the standard diameter. The lowered capacity can be obtained by referring to capacity curves for gas pipe which is 1 size smaller than standard size. Corrected pipe length (m) = actual pipe length (m) + number of bends x 0.3 (m) [Sample calculation] Indoor unit RP60 o 2 units (Twin system) Outdoor unit RP125 o 1 ■ Condition Using existing pipes. • Outdoor unit side Liquid pipe [12.7 / Gas pipe [19.05 pipe length (A) 20m • Indoor unit side Liquid pipe [9.52 / Gas pipe [15.88 pipe length (B) 20m + (C) 15m 1) Farthest piping length 20m + 15m = 35m Number of bends : 10 2) Corrected piping length 35m + 0.3 o 10 = 38m 3) Capacity correction Outdoor unit side’s gas pipe [19.05 Standard [15.88 → 1 size up Refer to 1Capacity curves 4) Capacity Cooling capacity = Standard cooling capacity o 0.89 Heating capacity = Standard heating capacity o 0.98 1 Capacity curves for PUHZ-RP · HA2 model Cooling Heating 100 Heating RP35, 50, 60, 71, 100, 125 and 140 models (Up to 55m for RP35, 50, 60, 71 models) 95 Capacity ratio [%] Cooling RP35, 60 models Cooling RP71 model 90 85 Cooling RP50, 100 models 80 Cooling RP125 model Cooling RP140 model 75 Note: The permitted pipe length is up to 55m for RP35, 50, 60, 71 model. The permitted pipe length is up to 80m for RP100 ~ 140 model. 70 5 10 15 20 25 30 35 40 45 50 55 Corrected pipe length [m] 85 60 65 70 75 80 OCS05E-3.qxp 08.3.31 9:58 AM Page 86 2 Capacity curve for PUHZ-RP35, 50 models Cooling Heating 100 Heating RP35, RP50 ([9.52) Capacity ratio [%] 95 90 Cooling RP50 ([9.52) 85 Cooling RP35 ([9.52) 80 5 10 15 20 25 30 35 Corrected pipe length [m] 3 Capacity curve for PUHZ-RP60, 71 models 100 Heating RP60, RP71 ([12.7) Capacity ratio [%] 95 90 85 80 Cooling RP60,RP71 ([12.7) 5 10 15 20 25 30 35 Corrected pipe length [m] 4 When gas pipe is one size larger than standard size for PUHZ-RP100, 125 and 140. 1 Capacity can be obtained by referring to capacity curves of standard size. 86 OCS05E-3.qxp 08.3.31 9:58 AM Page 87 8-2. PUHZ-RP200·250YHA2 8-2-1. 1:1 SYSTEM (1) Pipe length
Maximum pipe length (RP200·RP250) Liquid pipe (mm) OD [9.52 [12.7 [15.88 Thickness t0.8 t0.8 t1.0 gas pipe (mm) OD [19.05 [22.2 [25.4 [28.58 [19.05 [22.2 [25.4 [28.58 [22.2 [25.4 [28.58 [31.75 Thickness t1.0 t1.0 t1.0 t1.0 t1.0 t1.0 t1.0 t1.0 t1.0 t1.0 t1.0 t1.0 50m [20m] 50m [20m] 50m [20m] 50m [20m] 50m [20m] 50m [20m] Standard size RP200 20m [20m] SW 50m [30m] 70mw1 [30m] 70m [30m] 50m [30m] 70m [30m] 70m [30m] SW 20m [20m] 50m [30m] 20m [20m] 50m [30m] 20m [20m] 70m [30m] 70mw1 [30m] SW SW Standard size SW RP250 70m [30m] 70m [30m] SW w2 SW 50m [20m] w2 SW 50m [20m] Note : w1 The maximum pipe length is 120m in case of new piping. w2 When using [31.75 pipe, the outdoor temperature range (dry-bulb temperature) for heating operation is -11 to +21:. • Be sure to use hard (tempered) one for pipe over [22.2(RP200)/ [19.05(RP250).(Do not use soft (annealed) one.) SW : When the outdoor unit is located lower than the indoor unit, set DIP SW8-1 on the outdoor unit controller board to ON. : It can be used. : Cooling capacity is lowered. Refer to . : Additional refrigerant charge is required when the pipe length exceeds 20m. Refer to . SW The maximum pipe length Charge-less pipe length 70m [30m] (2) Adjusting the amount of refrigerant Check additional refrigerant charging amount referring to table 7 when the liquid pipe diameter is 1 size larger than the standard size, and table 2 when the pipe of the standard diameter is used.
permitted pipe length Outdoor unit RP200 Initial charge (kg) 120m or less Amount of additional refrigerant charge (kg) 30 m and less 6.5 No additional charge necessary 7.1 RP250 31-40 m and less 41-50 m and less 51-60 m and less 61-70 m and less 71-120 m and less The additional charge 0.9 kg 1.8 kg 2.7 kg 3.6 kg 1.2 kg 2.4 kg 3.6 kg 4.8 kg amount is obtained by the following formula. Calculate the additional charge amount based on the following procedure. If the calculation results in an amount that is smaller than the "Additional charge amount for 70m," perform the additional charge using the amount shown in "Additional charge amount for 70m." Amount of additional charge [kg] = Main piping: Liquid line size [12.7 over all length [m] o 0.12 [kg/m] + Main piping: Liquid line size [9.52 overall length [m] o 0.09 [kg/m] + Branch piping: Liquid line size [9.52 overall length [m] o 0.06 [kg/m] + Branch piping: Liquid line size [6.35 overall length [m] o 0.02 [kg/m] – 3.6 (kg) Additional charge amount RP200 3.6 kg for 70 m RP250 4.8 kg •If the wiring connecting the indoor and outdoor units is longer than 80m, use separate indoor /outdoor unit power supplies. 87 OCS05E-3.qxp 08.3.31 9:58 AM Page 88 (3) Capacity correction Cooling and heating capacity is lowered according to the piping length. Capacity can be obtained by referring to the following capacity curves. When the diameter of the gas pipe is smaller than the standard size, cooling capacity is lowered comparing to the operation using the standard diameter pipe. The lowered capacity can be obtained by referring to the capacity curves for gas pipe which is 1 or 2 size smaller than standard size. Corrected pipe length (m) = actual pipe length (m) + number of bends o 0.3 (m) 1. Capacity curves 1 Cooling Heating 100 Capacity ratio [%] 95 RP200,250 90 85 80 RP200 75 RP250 70 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 Corrected pipe length [m] 2. Capacity curves 2 100 Heating RP200([22.2), RP250([25.4) Capacity ratio [%] 95 Cooling RP250([25.4) 90 85 80 Cooling RP200([22.2) 75 70 5 10 15 20 25 30 35 40 45 50 55 Corrected pipe length [m] 3. Capacity curves 3 100 Cpacity ratio [%] 95 Heating RP200([19.05), RP250([22.2) 90 85 Cooling RP250([22.2) 80 Cooling RP200([19.05) 75 70 5 10 15 20 25 Corrected pipe length [m] 88 OCS05E-3.qxp 08.3.31 9:58 AM Page 89 8-2-2. TWIN, TRIPLE AND QUADRUPLE SYSTEM (1) Twin Maximum pipe length (Main pipe[A]+Branch pipe diameter [ B and C ]) RP200 twin (RP100O2) RP250 twin (RP125O2) [9.52 [12.7 [15.88 [9.52 [12.7 [15.88 [19.05 [22.2 [25.4 [28.58 [19.05 [22.2 [25.4 [28.58 [22.2 [25.4 [28.58 [31.75 [19.05 [22.2 [25.4 [28.58 [19.05 [22.2 [25.4 [28.58 [22.2 [25.4 [28.58 [31.75 Liquid pipe Gas pipe Main pipe (mm)[A] Liquid pipe [6.35 Gas pipe [12.7 Liquid pipe Branch pipe Gas pipe [mm] Liquid pipe [B, C] Gas pipe Liquid pipe Gas pipe Standard SW Standard SW SW w2 SW sw w2 sw sw sw size size 20m 50m 70mw1 70m 20m 50m 70m 70m 50m 50m 50m 50m 20m 50m 70m 70m 20m 50m 70mw1 70m 50m 50m 50m 50m [15.88 [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] [9.52 w2 SW [9.52 sw sw sw w2 sw 20m 50m 70m 70m 20m 50m 70m 70m 50m 50m 50m 50m 20m 50m 70m 70m 20m 50m 70m 70m 50m 50m 50m 50m [19.05 [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] SW SW SW w2 SW [12.7 sw sw sw w2 sw 20m 50m 70m 70m 20m 50m 70m 70m 50m 50m 50m 50m 20m 50m 70m 70m 20m 50m 70m 70m 50m 50m 50m 50m [19.05 [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] SW SW SW w1 The maximum pipe length is 120m in case of new pipping. w2 When using [31.75 pipe, the outdoor temperature range (dry-bulb temperature) for heating operation is -11 to +21:. • Be sure to use hard (tempered) one for pipe over [22.2(RP200)/ [19.05(RP250).(Do not use soft (annealed) one.) (2) Triple Maximum pipe length (Main pipe [A] + Branch pipe [ B, C and D ]) Main pipe (mm)[A] RP200 triple (RP60O3) RP250 triple (RP71O3) [9.52 [12.7 [15.88 [9.52 [12.7 [15.88 [19.05 [22.2 [25.4 [28.58 [19.05 [22.2 [25.4 [28.58 [22.2 [25.4 [28.58 [31.75 [19.05 [22.2 [25.4 [28.58 [19.05 [22.2 [25.4 [28.58 [22.2 [25.4 [28.58 [31.75 Liquid pipe Gas pipe Liquid pipe [6.35 Gas pipe [12.7 Liquid pipe Branch pipe Gas pipe [mm] Liquid pipe [B, C, D] Gas pipe Liquid pipe Gas pipe Standard SW Standard SW SW w2 SW SW SW w2 SW sw w2 sw size sw sw size 20m 50m 70mw1 70m 20m 50m 70m 70m 50m 50m 50m 50m 20m 50m 70m 70m 20m 50m 70mw1 70m 50m 50m 50m 50m [15.88 [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] [9.52 SW sw sw sw w2 sw 20m 50m 70m 70m 20m 50m 70m 70m 50m 50m 50m 50m 20m 50m 70m 70m 20m 50m 70m 70m 50m 50m 50m 50m [19.05 [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] [9.52 w2 SW [12.7 sw sw sw w2 sw 20m 50m 70m 70m 20m 50m 70m 70m 50m 50m 50m 50m 20m 50m 70m 70m 20m 50m 70m 70m 50m 50m 50m 50m [19.05 [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] SW SW SW w1 The maximum pipe length is 120m in case of new pipping. w2 When using [31.75 pipe, the outdoor temperature range (dry-bulb temperature) for heating operation is -11 to +21:. • Be sure to use hard (tempered) one for pipe over [22.2(RP200)/ [19.05(RP250).(Do not use soft (annealed) one.) (3) Quadruple Maximum pipe length (Main pipe[A]+Branch pipe [ B, C, D and E ]) Main pipe (mm)[A] RP200 quadruple (RP50O4) RP250 quadruple (RP60O4) [9.52 [12.7 [15.88 [9.52 [12.7 [15.88 [19.05 [22.2 [25.4 [28.58 [19.05 [22.2 [25.4 [28.58 [22.2 [25.4 [28.58 [31.75 [19.05 [22.2 [25.4 [28.58 [19.05 [22.2 [25.4 [28.58 [22.2 [25.4 [28.58 [31.75 Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Branch pipe Gas pipe [mm] Liquid pipe [B, C, D, E] Gas pipe Liquid pipe Gas pipe Standard sw w2 sw sw sw size 20m 50m 70mw1 70m 20m 50m 70m 70m 50m 50m 50m 50m [12.7 [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] [6.35 SW SW Standard SW w2 SW [9.52 sw sw sw w2 sw size 20m 50m 70m 70m 20m 50m 70m 70m 50m 50m 50m 50m 20m 50m 70m 70m 20m 50m 70mw1 70m 50m 50m 50m 50m [15.88 [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] SW w2 SW sw sw sw w2 sw 20m 50m 70m 70m 20m 50m 70m 70m 50m 50m 50m 50m 20m 50m 70m 70m 20m 50m 70m 70m 50m 50m 50m 50m [19.05 [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] [9.52 [12.7 SW SW SW SW w1 The maximum pipe length is 120m in case of new pipping. w2 When using [31.75 pipe, the outdoor temperature range (dry-bulb temperature) for heating operation is -11 to +21:. • Be sure to use hard (tempered) one for pipe over [22.2(RP200)/ [19.05(RP250).(Do not use soft (annealed) one.) SW : When the outdoor unit is located lower than the indoor unit, set DIP SW8-1 on the outdoor unit controller board to ON. SW 70m [30m] SW w2 SW 20m 50m 70m 70m 20m 50m 70m 70m 50m 50m 50m 50m [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] [19.05 : It can be used. : Cooling capacity is lowered. Refer to . : Additional refrigerant charge is required when the pipe length exceeds 20m. Refer to . The maximum pipe length Charge-less pipe length 89 OCS05E-3.qxp 08.3.31 9:58 AM Page 90 Pipe diameter and thickness OD (mm) [6.35 Thickness 0.8 (mm) [9.52 [12.7 0.8 0.8 [15.88 [19.05 1.0 [22.2 1.0 1.0 [25.4 [28.58 1.0 [31.75 1.0 1.1 Be sure to use hard (tempered) one for pipe over [19.05(RP250)/[22.2(RP200).(Do not use soft (annealed) one.) 4 B 4 E 1 Indoor unit Outdoor unit Main piping Branch piping Multi distribution pipe (option) 1 Height difference (Indoor unitOutdoor unit) Max. 30 m 2 Height difference (Indoor unitIndoor unit) Max. 1 m 3 Distance between indoor and indoor units pipe length. Max. 8m 1 1 4 D 1 2 3 4 5 1 2 1 4 C B—C B—D B—E C—D C—E D—E 5 3 A 4 Number of pipe bends Within 15 points 8 points between main pipe A and each branch pipe (B, C, D, E). 2
Lowered cooling capacity by the smaller gas pipe diameter Cooling capacity ratio gas pipe [22.2 gas pipe [19.05 100% 100% 100~95% 100~88% 95~88% 88~77% 88~83% 83~79% 79~75% Pipe length 5m and less 6~10m 11~20m 21~30m 31~40m 41~50m
Additional refrigerant amount when the liquid pipe of the larger diameter is used. (Single /Simultaneous Twin / Simultaneous Triple / Simultaneous Quadruple) Capacity When the extension pipe length (main piping + branch piping) exceeds 20m RP200, RP250 Additional refrigerant amount W(g)=(180oL1)+(120oL2) (90oL3)+(30oL4)-3000 L1 : [15.88 liquid pipe (m) L3 : [9.52 liquid pipe (m) L2 : [12.7 liquid pipe (m) L4 : [6.35 liquid pipe (m) If the calculation produces a negative number (i.e. a "minus" charge), additional charging is not necessary. ( W [ 0)
Outdoor unit Permissible total piping length A+B+C+D+E A+B or A+C or A+D or A+E Charge-less piping length A+B+C+D+E RP200 PR250 120 m and less 100 m and less 30 m and less
Outdoor unit B-C or B-D or B-E or C-D or C-E or D-E RP200 RP250 8 m and less Number of pipe bends Within 15 90 OCS05E-3.qxp 08.3.31 9:58 AM Page 91
Outdoor unit RP200 RP250 permitted pipe length 120m or less At time of shipping (kg) 6.5 A+B+C+D 30 m and less No additional charge necessary 7.1 Amount of additional refrigerant charge (kg) 31-40 m and less 41-50 m and less 51-60 m and less 61-70 m and less 71-120 m and less The additional charge 0.9 kg 1.8 kg 2.7 kg 3.6 kg 1.2 kg 2.4 kg 3.6 kg 4.8 kg amount is obtained by the following formula. When length exceeds 70 m When the total length of the piping exceeds 70 m, calculate the amount of additional charge based on the following requirements. Note: If the calculation produces a negative number (i.e. a “minus” charge), or if calculation results in an amount that is less than the “Additional charge amount for 70 m,”perform the additional charge using the amount shown in “Additional charge amount for 70 m.” Amount of additional charge Main piping: = Liquid line size [12.7 overall length 0.12 + Main piping: Liquid line size [9.52 overall length 0.09 (Gas line:[28.58) Branch piping: Liquid Branch piping: Liquid + line size + line size [9.52 overall length [6.35 overall length 0.06 (Gas line: [15.88) 0.02 (Gas line: [15.88) – 3.6 (kg) Additional charge amount RP200 3.6 kg for 70 m RP250 4.8 kg 1. Perform refrigerant piping connections for the indoor / outdoor unit while the outdoor unit's stop valve is completely closed (Initial setting), and then vacuumize the refrigerant lines through the service port of the outdoor unit. 2. Open the stop valves of the outdoor unit completely. This will completely connects the refrigerant circuits of the indoor and outdoor units. Stop valve opening method is shown on the outdoor unit’s installation manual. Note : · Apply refrigerating machine oil over the flare seat surface. Do not apply to the threaded portion. (It will cause the flare nut to loosen.) · Use 2 wrenches to tighten piping connection. · Use leak detector or soapy water to check for gas leaks after connections are completed. · For the insulation of the connection at the indoor side, make sure to use the attached insulation materials and thoroughly follow the instruction shown in the manual. · Always use a non-oxidizing brazing material when brazing the pipes. Adjusting the amount of refrigerant Check additional refrigerant charging amount referring to the procedure 2 below when the liquid pipe diameter of the main piping A is larger than the standard size. 1 When the standard diameter pipe is used for the main piping A, calculate the additional refrigerant amount by referring to
as well as the 1:1 system. 2 When the liquid pipe diameter of the main piping A is one size larger than the standard size: · When the extension pipe length (main piping + branch piping) does not exceed 20m, adjustment of the refrigerant is not necessary (charge-less). · When the extension pipe length (main piping + branch piping) exceeds 20m, charge the amount of refrigerant that is obtained by the formula shown in
. If the calculation produces a negative number (i.e. a "minus" charge), additional charging is not necessary. Note: Apply 0 to L1, L2, L3 and L4 which correspond to the liquid pipe size that are not used. Correcting the capacity value When calculating the lowered capacity by the extension pipe length, use the longest length between the indoor and the outdoor units. 91 OCS05E-3.qxp 9 08.3.31 9:58 AM Page 92 AIR FLOW DATA 9-1. OUTLET AIR SPEED AND COVERAGE RANGE PLA-RP71BA PLA-RP100BA PLA-RP125BA PLA-RP140BA PLA-RP35BA PLA-RP50BA PLA-RP60BA PLA-RP71BA2 PLA-RP100BA2 PLA-RP125BA2 Airflow m3/min. Air speed m/sec. Coverage range m 15 2.6 4.1 18 3.2 4.8 18 3.2 4.8 30 5.3 8.0 21 3.7 5.6 31 5.4 8.2 32 5.6 8.5 PLA-RP35AA PLA-RP50AA PLA-RP60AA PLA-RP71AA PLA-RP100AA2 PLA-RP125AA2 PLA-RP140AA2 28 30 30 14 18 18 20 Airflow m /min. 4.9 6.6 6.6 2.8 3.6 3.6 4.0 Air speed m/sec. 7.4 8.9 8.9 4.0 5.2 5.2 5.7 Coverage range m 3 PCA-RP50GA PCA-RP50GA2 PCA-RP60GA 13 3.7 8.8 18 3.8 10.4 PCA-RP71GA PCA-RP100GA PCA-RP125GA PCA-RP140GA Airflow Air speed Coverage range m3/min m/sec m Airflow Air speed Coverage range m3/min m/sec m PCA-RP71HA 19 2.9 7.9 PCA-RP125HA 38 4.2 13.2 Airflow Air speed Coverage range m3/min m/sec m(ft) PKA-RP35GAL 12 5.3 10(32.8) PKA-RP50GAL 12 5.3 10(32.8) PKA-RP50FAL2 PKA-RP60FAL PKA-RP71FAL PKA-RP100FAL 20 4.9 12.4(40.7) 20 4.9 12.4(40.7) 28 5.4 15.3(50.2) PSA-RP100GA 31 4.5 14.3 PSA-RP125GA 33 4.8 15.2 Airflow Air speed Coverage range m3/min m/sec m(ft) Airflow Air speed Coverage range m3/min m/sec m PSA-RP71GA 18 2.6 8.3 18 3.8 10.4 25 4.1 12.6 34 4.4 15.2 34 4.4 15.2 PSA-RP140GA 35 4.9 16.1 w The air coverage range is the distance to which the 0.25m/sec air can reach, when air is blown out horizontally from the unit at the High notch position. The coverage range should be used only as a general guideline since it varies according to the size of the room and the furniture inside the room. 92 OCS05E-3.qxp 08.3.31 9:58 AM Page 93 9-2. PLA-RP·BA(2) 9-2-1 FRESH AIR INTAKE AND BRANCH DUCT 1. Branch duct hole and fresh air intake hole (Fig. 1) At the time of i nstallation, use the duct holes ( cut out) located at the positions shown in Fig.1, as and when required. • A fresh air intake hole for the optional multi function casement can also be made. Note: The figure marked with * in the drawing represent the dimensions of the main unit excluding those of the optional multi function casement. When installing the optional multi function casement, add 135 mm to the dimensions marked on the figure. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur. Unit:mm Fresh air intake hole Fresh air intake hole diagram A Branch duct hole 3-[2.8 burring hole [125 burring hole pitch 120 A 120 Indoor unit *158 [100 cut out hole Ceiling Drain pipe Refrigerant pipe 100 100 90 130 90 Branch duct hole diagram (view from either side) 100 350 [175 burring hole pitch Fig. 1 93 *167 70° *155 A 14-[2.8 burring hole [150 cut out hole OCS05E-3.qxp 08.3.31 9:58 AM Page 94 3. Fresh air intake volume & static pressure characteristics PLA-RP35~71BA(2) 1 At using multi-function casement, standard filter 50 Static pressure[Pa] 0 -50 2 - inlet -100 -150 1 - inlet -200 0 1 2 3 4 5 6 2 Direct intake to unit 3 At using multi-function casement, high efficiency filter 50 50 0 0 Static pressure[Pa] Static pressure[Pa] Airflow rate [m3/min] -50 -100 -150 -50 2 - inlet -100 -150 1 - inlet -200 0 1 2 3 4 5 -200 6 0 1 2 3 Airflow rate [m3/min] 3 Airflow rate [m /min] 4 5 6 PLA-RP100~140BA(2) 1 At using multi-function casement, standard filter 50 Static pressure[Pa] 0 -50 2 - inlet -100 -150 1 - inlet -200 2 4 Airflow rate [m3/min] 6 8 2 Direct intake to unit 3 At using multi-function casement, high efficiency filter 50 50 0 0 Static pressure[Pa] Static pressure[Pa] 0 -50 -100 -50 -100 2 - inlet -150 -150 -200 -200 1 - inlet 0 2 4 Airflow rate [m3/min] 6 8 0 94 2 4 Airflow rate [m3/min] 6 8 OCS05E-3.qxp 08.3.31 9:58 AM Page 95 4. Change of outlet numbers The optional air outlet is necessary. To change the air outlet number to 3-, or 2-way outlet, the outlet number should be closed with the operational air outlet shutter. Indoor unit When the air outlets are closed, close the vane by removing the vane connector. Outlet concave portion Button Vane motor Up/down vanes Connector Air outlet shutter plate (Option) Vane motor Connector Button 5. Branch duct and change of outlet numbers w Branch duct should be connected to one of the branch duct holes on the main unit. <4- way air flow and branch duct> Branch duct Air intake Air outlet w Close the outlet on the side of branch duct and air flows in 3 directions. <3- way air flow and branch duct> Branch duct Air intake Air outlet Air outlet closed position w The outlet on the side of branch duct and one of the other outlets are closed. Air flows in 2 directions. <2- way air flow and branch duct> Branch duct Air Air outlet outlet closed closed position position Air intake Air outlet closed position 95 OCS05E-3.qxp 08.3.31 9:58 AM Page 96 PLA-RP71BA PLA-RP71BA2 4-way airflow (horizontal vane) Round duct 4-way airflow (horizontal vane) Rectangular duct 30 Duct Static pressure [Pa] Static pressure [Pa] 30 20 10 High Duct 20 10 High Low Low 0 0 0 2 4 6 Airflow rate [m3/min] 0 8 3-way airflow (horizontal vane) Round duct 2 80 70 70 Duct Duct 60 Close Static pressure [Pa] Static pressure [Pa] 60 50 40 30 Close 50 40 30 High 20 20 High Low 10 Low 10 0 0 2 4 6 8 Airflow rate [m3/min] 10 2-way airflow (horizontal vane) Round duct 0 100 90 90 Duct 2 Duct 80 Close Close 10 Close Close Static pressure [Pa] 70 60 50 40 30 High 20 4 6 8 Airflow rate [m3/min] 2-way airflow (horizontal vane) Rectangular duct 100 80 Static pressure [Pa] 8 3-way airflow (horizontal vane) Rectangular duct 80 0 4 6 Airflow rate [m3/min] 70 60 50 40 30 20 Low Low High 10 10 0 0 0 2 4 6 8 10 Airflow rate [m3/min] 0 12 2 4 6 8 10 Airflow rate [m3/min] • Use 1 of the 2 duct holes on the indoor unit. • Airflow rate of PLA-RP35~60BA can be calculated from the airflow rate based on the characteristic of the duct for PLA-RP71BA(2). • Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way airflow. 96 12 OCS05E-4.qxp 08.3.31 10:28 AM Page 97 PLA-RP125BA PLA-RP125BA2 4-way airflow (horizontal vane) Round duct 4-way airflow (horizontal vane) Rectangular duct 30 30 Duct 20 Static pressure [Pa] Static pressure [Pa] Duct 10 20 10 High Low High Low 0 0 0 2 4 Airflow rate [m3/min] 6 0 8 3-way airflow (horizontal vane) Round duct 4 Airflow rate [m3/min] 8 80 70 70 Duct Duct Close Close 60 Static pressure [Pa] 60 50 40 High 50 40 High 30 30 20 20 Low Low 10 10 0 0 0 2 4 6 Airflow rate [m3/min] 8 0 10 2-way airflow (horizontal vane) Round duct 2 4 6 Airflow rate [m3/min] 8 10 2-way airflow (horizontal vane) Rectangular duct 100 100 90 90 Duct 80 Duct 80 Close Close 70 70 60 60 Static pressure [Pa] Static pressure [Pa] 6 3-way airflow (horizontal vane) Rectangular duct 80 Static pressure [Pa] 2 50 40 High 30 Close Close 50 High 40 Low 30 Low 20 20 10 10 0 0 0 2 4 6 8 Airflow rate [m3/min] 10 0 12 2 4 6 8 10 12 Airflow rate [m3/min] • Use 1 of the 2 duct holes on the indoor unit. • Airflow rate of PLA-RP100BA(2), PLA-RP140BA can be calculated from the airflow rate based on the characteristic of the duct for PLA-RP125BA(2). • Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way airflow. 97 OCS05E-4.qxp 08.3.31 10:28 AM Page 98 9-3. PLA-RP·AA, PLA-RP·AA2 9-3-1. Fresh air intake amount 98 OCS05E-4.qxp 08.3.31 10:28 AM Page 99 9-3-2. BRANCH DUCT (Installation at site) 99 OCS05E-4.qxp 08.3.31 10:28 AM Page 100 Branch duct airflow rate/static pressure characteristics PLA-RP35AA 4-way airflow (horizontal vane) Rectangular duct 4-way airflow (horizontal vane) Round duct 3-way airflow (horizontal vane) Rectangular duct 3-way airflow (horizontal vane) Round duct 2-way airflow (horizontal vane) Rectangular duct 2-way airflow (horizontal vane) Round duct 100 OCS05E-4.qxp 08.3.31 10:29 AM Page 101 PLA-RP50AA PLA-RP60AA 4-way airflow (horizontal vane) Rectangular duct 4-way airflow (horizontal vane) Round duct 3-way airflow (horizontal vane) Rectangular duct 3-way airflow (horizontal vane) Round duct 2-way airflow (horizontal vane) Rectangular duct 2-way airflow (horizontal vane) Round duct 101 OCS05E-4.qxp 08.3.31 10:29 AM Page 102 PLA-RP71AA 4-way airflow (horizontal vane) Round duct Static pressure [Pa] 30 20 High 10 Low 0 1 2 3 4 5 6 Static pressure [Pa] 4-way airflow (horizontal vane) Rectangular duct 30 20 High 10 Low 0 1 2 3 Airflow rate [m3/min] 3-way airflow (horizontal vane) Rectangular duct 6 60 50 Static pressure [Pa] Static pressure [Pa] 5 3-way airflow (horizontal vane) Round duct 60 40 High 30 20 Low 10 50 40 1 2 3 4 5 6 7 8 9 High 30 20 Low 10 0 0 1 2 3 4 Airflow rate [m /min] 2-way airflow (horizontal vane) Rectangular duct 5 6 7 2-way airflow (horizontal vane) Round duct 100 100 90 90 80 Static pressure [Pa] 80 70 60 High 50 40 Low 30 20 10 70 60 50 High 40 Low 30 20 10 0 1 2 3 4 5 6 7 8 9 10 8 Airflow rate [m3/min] 3 Static pressure [Pa] 4 Airflow rate [m3/min] 11 0 Airflow rate [m3/min] 1 2 3 4 5 6 Airflow rate [m3/min] 102 7 9 OCS05E-4.qxp 08.3.31 10:29 AM Page 103 PLA-RP100AA2 4-way airflow (horizontal vane) Round duct 50 Static pressure [Pa] Static pressure [Pa] 4-way airflow (horizontal vane) Rectangular duct 40 30 High 20 Low 10 0 1 2 3 4 5 6 7 8 9 50 40 30 High 20 Low 10 0 10 1 2 3 4 5 Airflow rate [m /min] 3 8 9 10 Airflow rate [m /min] 3-way airflow (horizontal vane) Round duct 100 100 90 90 Static pressure [Pa] Static pressure [Pa] 7 3 3-way airflow (horizontal vane) Rectangular duct 80 70 60 High 50 40 30 Low 20 10 80 70 60 50 High 40 30 Low 20 10 0 1 2 3 4 5 6 7 8 9 10 11 12 13 0 14 1 Airflow rate [m3/min] 110 100 100 90 90 Static pressure 120 110 80 High 60 50 Low 40 30 50 4 5 6 7 8 9 10 11 12 13 14 15 7 8 9 10 11 12 13 14 16 Airflow rate [m /min] 3 High 40 Low 30 10 3 6 60 10 2 5 70 20 1 4 80 20 0 3 2-way airflow (horizontal vane) Round duct 120 70 2 Airflow rate [m3/min] 2-way airflow (horizontal vane) Rectangular duct Static pressure [Pa] 6 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Airflow rate [m3/min] 103 16 OCS05E-4.qxp 08.3.31 10:29 AM Page 104 PLA-RP125AA2 PLA-RP140AA2 4-way airflow (horizontal vane) Round duct 50 50 40 30 High 20 Low 10 0 1 2 3 4 5 6 7 8 9 10 Static pressure [Pa] Static pressure [Pa] 4-way airflow (horizontal vane) Rectangular duct 40 30 High 20 10 Low 0 1 2 3 4 5 Airflow rate [m /min] 90 80 Static pressure [Pa] Static pressure [Pa] 100 90 70 60 High 40 Low 20 10 0 9 10 80 70 60 50 High 40 30 Low 20 10 1 2 3 4 5 6 7 8 9 10 11 12 13 0 14 1 2 3 4 5 6 Airflow rate [m /min] 3 110 100 100 Static pressure[Pa] 120 110 90 80 70 High 50 40 Low 30 8 9 10 11 12 13 14 2-way airflow (horizontal vane) Round duct 120 60 7 Airflow rate [m3/min] 2-way airflow (horizontal vane) Rectangular duct Static pressure [Pa] 8 3-way airflow (horizontal vane) Round duct 100 30 7 3 3-way airflow (horizontal vane) Rectangular duct 50 6 Airflow rate [m /min] 3 20 10 90 80 70 60 50 High 40 Low 30 20 10 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 16 1 Airflow rate [m /min] 3 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Airflow rate [m3/min] 104 16 OCS05E-4.qxp 08.3.31 10:29 AM Page 105 9-4. PEAD-RP·EA,EA2,GA Corrected Airflow 120 100 Correction factor External static pressure (Pa) (1Pa 0.1mmAq) 9-4-1. Fan Performance and Corrected Airflow PEAD-RP35EA2 Fan Performance <30Pa> 140 PEAD-RP50EA 80 60 40 20 Cooling 1.0 0.9 0.8 8 6 8 10 10 12 14 16 18 20 Airflow (CMM) Fan Performance <70Pa> 160 12 14 16 18 Airflow (CMM) 20 22 12 14 16 18 Airflow (CMM) 20 22 Heating 1.3 140 Correction factor External static pressure (Pa) (1Pa 0.1mmAq) 1.1 Capacity input 120 100 80 60 40 1.2 1.1 1.0 0.9 0.8 8 20 8 10 10 12 14 16 18 20 22 Airflow (CMM) Fan Performance <30Pa> 120 Correction factor 100 80 60 40 20 8 140 External static pressure (Pa) (1Pa 0.1mmAq) Corrected Airflow 1.1 Capacity input Cooling 1.0 0.9 0.8 12 14 16 18 20 22 Airflow (CMM) 24 26 10 12 14 16 18 20 22 24 Airflow (CMM) Heating Fan Performance <70Pa> 1.3 120 Correction factor External static pressure (Pa) (1Pa 0.1mmAq) PEAD-RP60EA 100 80 60 40 1.2 1.1 1.0 0.9 0.8 12 14 16 18 20 22 24 Airflow (CMM) 20 10 12 14 16 18 20 22 24 26 Airflow (CMM) 105 26 OCS05E-4.qxp 08.3.31 10:29 AM Page 106 PEAD-RP71EA Fan performance <70Pa> Fan performance <130Pa> Recommended range External static pressure (Pa) (1Pa = 0.1mmAq) Recommended range External static pressure (Pa) (1Pa = 0.1mmAq) 200 180 160 140 Hi Lo 120 100 80 60 40 20 180 160 140 120 Hi Lo 100 80 60 40 20 12 16 20 24 28 32 12 16 20 24 28 32 Ai r f l ow ( C M M ) Airflow (CMM) Corrected Airflow Capacity Input Cooling Heating 1.3 1.1 Correction factor Correction factor 1.2 1.0 0.9 0.8 12 16 20 24 28 1.1 1.0 0.9 32 Airflow (CMM) 0.8 12 16 PEAD-RP100EA2 PEAD-RP125EA External static pressure (Pa) (1Pa = 0.1mmAq) External static pressure (Pa) (1Pa = 0.1mmAq) 220 200 180 160 140 120 100 Hi 80 Lo 20 200 180 160 140 120 100 60 40 Lo 20 32 34 36 38 40 42 44 46 Ai r f l ow ( C M M ) Heating Corrected Airflow 1.2 Cooling Correction factor Capacity Input 1.1 1.0 0.9 34 Hi 80 Airflow (CMM) Correction factor 32 220 32 34 36 38 40 42 44 46 48 0.8 32 28 Recommended range Recommended range 40 24 Fan performance <70Pa> Fan performance <130Pa> 60 20 Airflow (CMM) 36 38 40 42 44 46 1.1 1.0 0.9 0.8 48 32 Airflow (CMM) 34 36 38 40 42 44 Airflow (CMM) 106 46 48 OCS05E-4.qxp 08.3.31 10:29 AM Page 107 PEAD-RP140EA Fan performance <70Pa> Recommended range External static pressure (Pa) 220 (1Pa = 0.1mmAq) External static pressure (Pa) Recommended range 200 180 160 140 120 100 80 60 40 Hi Lo 200 (1Pa = 0.1mmAq) Fan performance <130Pa> 180 160 140 120 100 80 Hi 60 Lo 40 20 20 36 38 40 42 44 46 48 50 52 36 38 40 42 44 46 48 50 A i rfl o w (C M M ) A i rfl ow (C MM ) Heating Corrected Airflow Capacity Input 1.1 Correction factor Correction factor Cooling 1.0 0.9 0.8 36 1.2 38 40 42 44 46 48 50 52 1.1 1.0 0.9 0.8 36 38 40 42 44 46 Airflow (CMM) Airflow (CMM) 107 48 50 52 OCS05E-4.qxp 08.3.31 10:29 AM Page 108 PEAD-RP60GA PEAD-RP71GA 108 OCS05E-4.qxp 08.3.31 10:29 AM Page 109 PEAD-RP100GA 109 OCS05E-4.qxp 08.3.31 10:29 AM Page 110 9-5. PEA-RP·GA Fan Performance Curve PEA-RP250GA Fan Performance Curve 50Hz PEA-RP200GA Fan Performance Curve 50Hz (Pa) (Pa) 250 300 External static pressure External static pressure 250 200 Hi 150 100 Lo 150 Hi 100 Lo 50 50 0 45.0 200 50.0 55.0 60.0 65.0 0 60.0 70.0 (CMM) 65.0 70.0 75.0 Airflow 85.0 90.0 (CMM) PEA-RP500GA Fan Performance Curve 50Hz (Pa) 300 (Pa) 350 250 300 External static pressure External static pressure PEA-RP400GA Fan Performance Curve 50Hz 200 150 100 50 0 70.0 80.0 Airflow 250 200 150 100 50 80.0 90.0 100.0 110.0 120.0 130.0 (CMM) 0 100.0 Airflow 110.0 120.0 130.0 140.0 Airflow 110 150.0 160.0 170.0 (CMM) OCS05E-4.qxp 08.3.31 10:29 AM 10 Page 111 NOISE CRITERION CURVES 10-1. INDOOR UNIT PLA-RP35BA NOTCH SPL(dB) High 31 Medium1 29 Medium2 28 Low 27 PLA-RP50BA LINE 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 NC-20 10 250 500 1000 2000 4000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE PLA-RP60BA 63 125 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz NOTCH SPL(dB) High 32 Medium1 31 Medium2 29 Low 28 PLA-RP71BA PLA-RP71BA2 LINE 90 NOTCH SPL(dB) High 34 Medium1 32 Medium2 30 Low 28 LINE 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 125 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 NC-20 10 63 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) NC-20 10 8000 BAND CENTER FREQUENCIES, Hz 20 LINE 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) 90 NOTCH SPL(dB) High 32 Medium1 31 Medium2 29 Low 28 250 500 1000 2000 4000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 10 8000 63 BAND CENTER FREQUENCIES, Hz 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz 111 4000 8000 OCS05E-4.qxp 08.3.31 10:29 AM PLA-RP100BA PLA-RP100BA2 Page 112 NOTCH SPL(dB) High 40 Medium1 37 Medium2 34 Low 32 LINE PLA-RP125BA PLA-RP125BA2 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 10 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 10 63 125 250 500 1000 2000 4000 8000 63 BAND CENTER FREQUENCIES, Hz PLA-RP140BA 125 250 500 1000 2000 4000 BAND CENTER FREQUENCIES, Hz NOTCH SPL(dB) High 44 Medium1 42 Medium2 39 Low 36 LINE OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) 90 UNIT 80 CEILING 70 NC-70 60 NC-60 1.5m 50 NC-50 40 NC-40 MICROPHONE 30 NC-30 20 LINE 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) 90 NOTCH SPL(dB) High 41 Medium1 39 Medium2 36 Low 34 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 10 63 125 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz 112 8000 OCS05E-4.qxp 08.3.31 10:29 AM Page 113 NOTCH SPL(dB) High 31 Medium1 29 Medium2 28 Low 27 PLA-RP35AA LINE 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 NC-20 10 250 500 1000 2000 4000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 10 8000 63 125 250 BAND CENTER FREQUENCIES, Hz LINE 1000 2000 4000 NOTCH SPL(dB) High 41 Medium1 39 Medium2 36 Low 33 PLA-RP100AA2 90 8000 LINE 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 125 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 NC-20 10 63 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) 500 BAND CENTER FREQUENCIES, Hz NOTCH SPL(dB) High 34 Medium1 32 Medium2 30 Low 28 PLA-RP71AA 20 LINE 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) 90 20 NOTCH SPL(dB) High 33 Medium1 31 Medium2 29 Low 28 PLA-RP50AA PLA-RP60AA 250 500 1000 2000 4000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 10 8000 63 BAND CENTER FREQUENCIES, Hz 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz 113 4000 8000 OCS05E-4.qxp 08.3.31 10:29 AM Page 114 NOTCH SPL(dB) 45 High 43 Medium1 40 Medium2 37 Low PLA-RP125AA2 LINE LINE 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 10 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) 90 20 NOTCH SPL(dB) 45 High 43 Medium1 40 Medium2 37 Low PLA-RP140AA2 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 10 63 125 250 500 1000 2000 4000 8000 63 BAND CENTER FREQUENCIES, Hz 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz UNIT CEILING 1.5m MICROPHONE 114 4000 8000 08.3.31 10:29 AM Page 115 (External static pressure 30Pa) PEAD-RP35EA2 PEAD-RP50EA 70 OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa PEAD-RP35EA2 PEAD-RP50EA High Low 60 NC60 50 NC50 40 NC40 30 NC30 20 NC20 10 Approximate minimum audible limit on continuous noise 0 63 125 250 500 1000 2000 4000 High Low 60 NC60 50 NC50 40 NC40 30 NC30 20 NC20 10 Approximate minimum audible limit on continuous noise 0 8000 63 OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa High Low 60 NC60 50 NC50 40 NC40 30 NC30 20 NC20 10 Approximate minimum audible limit on continuous noise 63 125 250 500 1000 2000 4000 250 500 1000 2000 4000 8000 (External static pressure 70Pa) PEAD-RP60EA 70 0 125 OCTAVE BAND CENTER FREQUENCIES (Hz) (External static pressure 30Pa) PEAD-RP60EA (External static pressure 70Pa) 70 OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa OCS05E-4.qxp 8000 70 High Low 60 NC60 50 NC50 40 NC40 30 NC30 20 NC20 10 Approximate minimum audible limit on continuous noise 0 63 OCTAVE BAND CENTER FREQUENCIES (Hz) 125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCIES (Hz) 115 8000 OCS05E-4.qxp 08.3.31 10:29 AM Page 116 116 OCS05E-4.qxp 08.3.31 10:29 AM Page 117 Sound Data PEA-RP200, 250 : Upper High/Lower Low OCTAVE BAND FREQ.Hz SPL dB(A) 63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz 51 55 54 51 49 47 43 33 27 48 50 50 47 46 44 40 29 21 52 56 55 52 50 48 44 34 28 49 51 51 48 47 45 41 30 22 PEA-RP400GA 52 53 51 52 50 46 44 39 30 PEA-RP500GA 53 55 54 51 50 48 44 40 31 Model PEA-RP200GA PEA-RP250GA Position measurement Indoor unit 1m 2m Inlet 1.5m Outlet Measurement point 117 OCS05E-4.qxp 08.3.31 10:29 AM PKA-RP35GAL PKA-RP50GAL Page 118 NOTCH SPL(dB) High 43 Medium1 41 38 Medium2 Low 36 LINE PKA-RP50FAL2 PKA-RP60FAL PKA-RP71FAL 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar) 80 20 LINE 90 10 63 125 250 500 1000 2000 4000 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 20 NC-20 10 8000 63 125 250 500 PKA-RP100FAL WALL 1m MICROPHONE 2000 4000 8000 NOTCH SPL(dB) High 46 Low 41 LINE 90 UNIT 1m 1000 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar) 90 NOTCH SPL(dB) High 45 Low 39 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 10 63 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz 118 4000 8000 OCS05E-4.qxp 08.3.31 10:29 AM Page 119 PCA-RP50GA NOTCH SPL(dB) 42 High 40 Medium1 38 Medium2 37 Low PCA-RP50GA2 PCA-RP60GA PCA-RP71GA LINE 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) 80 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 NC-20 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 250 500 1000 2000 4000 63 8000 125 PCA-RP100GA 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz NOTCH SPL(dB) High 45 Medium1 43 Medium2 41 Low 40 PCA-RP125GA LINE 90 NOTCH SPL(dB) High 46 Medium1 45 Medium2 43 Low 41 LINE 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 10 63 125 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) NC-20 10 10 20 LINE 90 90 20 NOTCH SPL(dB) High 43 Medium1 41 Medium2 39 Low 37 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 10 8000 63 BAND CENTER FREQUENCIES, Hz 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz 119 4000 8000 OCS05E-4.qxp 08.3.31 10:29 AM PCA-RP140GA Page 120 NOTCH SPL(dB) High 48 Medium1 46 Medium2 44 Low 42 LINE OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) 90 80 70 1m NC-70 1m ceiling unit about 1.4m 60 NC-60 MICROPHONE 50 NC-50 40 NC-40 30 NC-30 20 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 10 63 125 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz PCA-RP71HA NOTCH SPL(dB) High 38 Low 34 LINE PCA-RP125HA 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) LINE 90 90 20 NOTCH SPL(dB) High 50 Low 44 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 NC-20 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 10 10 63 125 250 500 1000 2000 4000 63 8000 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz 120 4000 8000 OCS05E-4.qxp 08.3.31 10:29 AM Page 121 PSA-RP71GA NOTCH SPL(dB) 45 High 40 Low PSA-RP100GA LINE 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 APPROXIMATE THRESHOLD OF REARING FOR CONTINUOUS NOISE 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 NC-20 10 APPROXIMATE THRESHOLD OF REARING FOR CONTINUOUS NOISE 125 250 500 1000 2000 4000 8000 63 125 PSA-RP125GA 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz NOTCH SPL(dB) High 51 Low 46 PSA-RP140GA LINE 90 NOTCH SPL(dB) High 52 Low 47 LINE 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF REARING FOR CONTINUOUS NOISE OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) NC-20 10 63 20 LINE 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) 90 NOTCH SPL(dB) High 49 Low 44 80 70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 NC-20 10 NC-70 APPROXIMATE THRESHOLD OF REARING FOR CONTINUOUS NOISE NC-20 10 63 125 250 500 1000 2000 4000 8000 63 125 BAND CENTER FREQUENCIES, Hz 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz unit MICROPHONE 1m 1m floor 121 4000 8000 OCS05E-4.qxp 08.3.31 10:29 AM Page 122 10-2. OUTDOOR UNIT MICROPHONE 1m UNIT 1.5m GROUND PUHZ-RP35VHA2 PUHZ-RP35VHA3 PUHZ-RP50VHA2 PUHZ-RP50VHA3 MODE SPL(dB) COOLING 44 HEATING 46 LINE 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 PUHZ-RP100VHA2 PUHZ-RP100VHA3 PUHZ-RP100YHA2 PUHZ-RP100YHA3 1000 2000 4000 8000 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 MODE SPL(dB) COOLING 49 HEATING 51 LINE 250 500 PUHZ-RP125VHA2 PUHZ-RP140VHA2 PUHZ-RP125YHA2 PUHZ-RP140YHA2 1000 2000 4000 8000 MODE SPL(dB) COOLING 50 HEATING 52 LINE 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) 125 NC-20 BAND CENTER FREQUENCIES, Hz 90 10 LINE 80 BAND CENTER FREQUENCIES, Hz 20 MODE SPL(dB) COOLING 47 HEATING 48 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) 90 PUHZ-RP60VHA2 PUHZ-RP60VHA3 PUHZ-RP71VHA2 PUHZ-RP71VHA3 8000 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz 122 8000 OCS05E-4.qxp 08.3.31 10:29 AM Page 123 PUHZ-RP200YHA2 PUHZ-RP250YHA2 MODE COOLING HEATING SPL(dB) 58 59 LINE OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 90 MICROPHONE 1m 80 UNIT 70 NC-70 1.5m 60 NC-60 50 NC-50 GROUND 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz 123 OCS05E-4.qxp 11 08.3.31 10:29 AM Page 124 OPTIONAL PARTS 11-1. INDOOR UNIT Part Name Model Name Remote sensor Remote operation adapter Multiple remote controller adapter PAC-SE41TS-E PAC-SF40RM-E Remote on/off adapter Power supply terminal kit PAC-SA88HA-E (1pc.) All models PAC-725AD (10pcs.) PAC-SE55RA-E PLA-RP·AA(2), PEAD-RP·EA(2) PAC-SG96HR-E PCA-RP·GA(2), PKA-RP·GAL/FAL(2) PSA-RP·GA L/N/Earth L/N Decoration panel Decoration panel with Wireless remote controller Decoration panel with Wired remote controller Decoration panel with i-see sensor Decoration panel with i-see sensor, Wireless remote controller Decoration panel with i-see sensor, Wired remote controller Automatic filter elevation panel i-see sensor corner panel Wireless signal receiver Space panel PAC-SH52HR-E PLA-RP·BA(2) PAC-SG97HR-E PCA-RP·HA PEAD-RP·GA PLP-6BA PLP-6BALM PLP-6BAMD PLP-6BAE PLP-6BALME PLP-6BAMDE PLP-6BAJ PAC-SA1ME-E PAC-SH48AS-E PAC-SH51SP-E PAC-SH53TM-E Multi-functional casement High-efficiency filter element (PAC-SG03TM-E is needed.) Grille + Wireless remote controller Grille + Wired remote controller Space panel Air outlet shutter plate PAC-SG03TM-E PAC-SG01KF High-efficiency filter Duct flange for fresh air Oil mist filter element (12pcs) Decoration cover (Front + Suspending bracket cover) Wired remote controller (with terminal bed) Drain lift up mechanism Motor (for high external static pressure) Drain lift up mechanism Insulation kit PLA-RP·BA(2) PAR-SA9FA-E Air outlet shutter plate Multi-function casement Flange for fresh air intake High-efficiency filter element (PAC-SH53TM-E is needed.) Wireless remote controller kit Drain lift up mechanism Applicable model PAC-SH65OF-E PAC-SH59KF-E PLP-6AALM PLP-6AAMD PAC-SG04AS-E PAC-SG06SP-E PAR-SL99B-E PAC-SH20DM-E PAC-SH21DM-E PAC-SH22DM-E PAC-SE80KF-E PAC-SE81KF-E PAC-SE82KF-E PAC-SF28OF-E PAC-SG38KF-E PAC-SF81KC-E PAC-SF82KC-E PAR-21MAAT-E PAC-SE90DM-E PAC-SK003MT-F PAC-KE03DM-F PAC-SK010DK 124 PLA-RP·AA PLA-RP·AA2 PCA-RP·GA(2) PCA-RP50,60GA(2) PCA-RP71GA PCA-RP100,125,140GA PCA-RP50GA PCA-RP50GA2, PCA-RP60,71,100GA PCA-RP125,140GA PCA-RP·HA PCA-RP71HA PCA-RP125HA PKA-RP·GAL PKA-RP·FAL(2) PKA-RP·FAL(2) PEAD-RP125,140EA PEAD-RP100EA2 PEAD-RP·EA,EA2 PEAD-RP·GA OCS05E-4.qxp 08.3.31 10:29 AM Page 125 11-2. OUTDOOR UNIT Part Name Model Name Applicable model M-NET adapter PAC-SF80MA-E PUHZ-RP71-250 A-control service tool PAC-SK52ST PUHZ-RP71-250 Drain socket PAC-SG61DS-E PUHZ-RP71-250 Air outlet guide (RP100-250 need 2 pieces.) PAC-SG59SG-E PUHZ-RP71-250 Air protect guide (RP100-250 need 2 pieces.) PAC-SG57AG-E PUHZ-RP71-250 Drain pan PAC-SG64DP-E PUHZ-RP71-250 Filter dryer ( [9.52) ([12.7) PAC-SG82DR-E PAC-SG85DR-E PUHZ-RP71-200 PUHZ-RP250 Distribution pipe (Twin) MSDD-50SR-E PUHZ-RP71-140 MSDD-50WR-E PUHZ-RP200, 250 (Triple) MSDT-111R-E PUHZ-RP140-250 (Quadruple) MSDF-1111R-E PUHZ-RP200, 250 Joint pipe (Unit Extension pipe) ( [15.88 [19.05) PAC-SG75RJ-E 125 PUHZ-RP71-140 OCS05E-4.qxp 08.3.31 10:29 AM Page 126 TM HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN CCopyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Distributed in Apr. 2008 No.OCS05 REVISED EDITION-E PDF 7 Distributed in Nov. 2007 No.OCS05 REVISED EDITION-D PDF 7 Distributed in Jun. 2007 No.OCS05 REVISED EDITION-C PDF 7 Distributed in Jul. 2006 No.OCS05 REVISED EDITION-B PDF 7 Distributed in May 2006 No.OCS05 REVISED EDITION-A PDF 8 Distributed in Feb. 2006 No.OCS05 PDF 8 Made in Japan New publication, effective Apr. 2008 Specifications subject to change without notice.