Pegler Yorkshire
SUPERIOR QUALITY HEAT INTERFACE UNITS PUTTING YOU IN CONTROL
Pegler Yorkshire
PUTTING YOU IN CONTROL Diverse industry expertise combined with cuttingedge technological innovation mean Pegler Yorkshire’s Control solutions help you overcome unique challenges and meet the highest standards in both performance and system aesthetics. PERFORMANCE WITH PRECISION Pegler Yorkshire’s Control products enable you to balance precision flow control, energy efficiency and comfort through innovative products and systems that ensure building performance criteria are met and the resulting installation is easy, efficient and economical to operate. Our comprehensive Terrier, Meibes and Ballorex product ranges offer proven energy saving solutions, exceptional accuracy and optimised system performance – so, whatever your project or challenge, you can be sure you’ll always be in control.
GLOBAL EXPERIENCE, COMBINED EXPERTISE With over 100 years of manufacturing and innovation combined with extensive industry knowledge and worldwide market experience, Pegler Yorkshire offers the most advanced and complete Connect & Control systems on a global scale. As one of Britain’s largest and most respected manufacturers and suppliers of products for the plumbing and heating industries, Pegler Yorkshire is confident we can provide you with all the controls, connections and support your project requires.
For more information visit www.pegleryorkshire.co.uk
2
CONTENTS ENERGY EFFICIENT SOLUTIONS SUITABLE FOR CENTRALISED BOILER PLANTS Introduction A comprehensive range for all applications Service Energy efficiency with improved SAP ratings Pegler Yorkshire is pleased to be associated with several influential industry organisations:
A TOTAL SUPPORT PACKAGE FOR SPECIFIERS, CONTRACTORS AND FACILITIES MANAGERS Benefits Choosing the best system for your application
Association of Plumbing and Heating Contractors
The Bathroom Manufacturers Association
The UK Copper Board
The Chartered Institution of Building Services Engineers
Brass
pec
4 4-5 6 7
8 9-11
PRODUCT DETAILS Product focus A2 RX Blu-Climate range A2 UX Blu-Climate range A1 RX Blu-Climate range A1 CX Blu-Climate range
12-13 14-17 18-21 22-25 26-29
TECHNICAL GLOSSARY
30-31
DISTRICT HEATING SYSTEMS CLIMATE CONTROL
32-33
CERTIFICATION LTD
The Brass Page for specifiers, designers, engineers and manufacturers
British Plumbing Employers Council
Thermostatic Mixing Valve Manufacturers Association
Construction Products Association
The Copper Development Association
Scottish and Northern Ireland Plumbing Employers Federation
Builders Merchants Federation
Institute of Plumbing
The UK District Energy Association
3
ENERGY EFFICIENT SOLUTIONS SUITABLE FOR CENTRALISED BOILER PLANTS
The Meibes brand and German heritage is renowned for its precision engineering quality and innovative designs that deliver unparalleled performance, efficiency and ease of installation.
Meibes Heat Interface Units (HIUs) facilitate the use of centralised systems for space heating and domestic hot water in multi-residential buildings. They are high performing units, engineered with fully tested and approved components, designed to provide optimum performance for end users, while ensuring that they are easy to install and maintain.
Pegler Yorkshire also holds a comprehensive range of spares for fast delivery throughout the UK. Meibes HIUs are pre-fabricated units linked to the central heat source(s) via a network of three pipes – heating flow and return and a separate potable water feed. A zone valve in each unit, linked to a standard timer and room thermostats, controls the space heating for each apartment. A patented Proportional Modulating (PM) valve intelligently prioritises the requirement for domestic hot water (DHW) over heating, in a similar way to a combi boiler.
A COMPREHENSIVE RANGE FOR ALL APPLICATIONS The Meibes HIUs offered by Pegler Yorkshire have been designed to meet the specific needs of the UK market. For example, Meibes HIUs for the UK are configured for top-entry pipework for ease of installation in ceiling voids
The breadth of the Meibes HIU range delivers solutions for all types of centralised heating networks serving multi-residential accommodation, ensuring effective control of heating and DHW in apartments and other spaces. The design of HIUs facilitates a balanced system that delivers consistent performance, irrespective of variation in hot water demands or how far the units are from the plant room.
TYPICAL APPLICATIONS Private apartments Local Authority accommodation Housing Associations Student accommodation Nurse accommodation Sheltered housing.
4
“Whatever the application, Meibes HIU have the authoritative solution” DESIGN
BUILD
Performance
Installation innovation
Pegler Yorkshire has various high performance Meibes HIU products that are suitable when designing apartments with multiple bathrooms. These ensure reliable performance for individual use and against the overall building requirements. Guidance on network and temperature flow rates can also be provided by the Pegler Yorkshire team.
The Meibes HIU range is part of Pegler Yorkshire Connect & Control, which fully recognises the importance of minimising installation costs whilst ensuring the building performs efficiently and optimally. Meibes HIUs were one of the first to be designed with a first fix rail which is available to aid staged installation, supporting the primary network set-up.
Allocating design space
No special commissioning required
Meibes HIU headline A2 RX Indirect Heating and Domestic Hot Water units are compact in size at only 500mm wide, enabling them to be fitted into minimal cupboard space. This also provides the option to fit them into an appliance space. Further options are also available for direct heating units at 650mm wide.
Meibes HIUs are designed to remove complications and provide clarity on installation. There is no need to have a specialist for commissioning as the standard installation process requires a competent installer to simply follow the specifier’s set-up parameters.
UK solution
Pegler Yorkshire is one the leading manufacturers of commercial plumbing and heating systems. Our expertise and experience enables contractors to benefit significantly when it comes to project costs, and technical and service support, by using a connect and control system they can trust.
Pegler Yorkshire ensures that UK experience, system design and installation and practices drive the solution to the product, which is why the Meibes range of HIUs is designed to meet UK needs. As a result there is no need to compromise and adapt to HIU’s with a European configuration.
Expertise
5
ENERGY EFFICIENT SOLUTIONS SUITABLE FOR CENTRALISED BOILER PLANTS
SERVICE Guarantee Pegler Yorkshire provides ultimate engineering and performance confidence. Down time can lead to client frustration and experience is the key to a well-managed building project. Meibes HIUs combine high quality components and reliability to deliver a peace of mind proposition which prevents expensive call backs. Service Pegler Yorkshire is committed to providing an after service experience that allows peace of mind for contractors and facility managers. A network of service teams is available with dedicated telephone support lines providing technical advice.
2
year
guarantee on moving parts
6
ENERGY EFFICIENCY WITH IMPROVED SAP RATINGS Centralised heating systems are becoming increasingly popular for multi-residential properties as they offer a number of key advantages over decentralised systems with individual boilers in each apartment. These include: Improved energy efficiency 11% improvement in SAP ratings (compared to decentralised systems) No gas installation throughout the building
Energy-saving features of Meibes HIUs Meibes HIUs operate on a ‘no demand-no flow’ basis, so that when there is no demand for heating or DHW the unit effectively goes into standby. The arrangement minimises the demand on the main network, reduces energy consumption and ensures the apartment is not over-heated. The performance of the units is based on primary flow temperatures of 65°C, enabling use with low carbon heat sources such as heat pumps. The resulting low return water temperatures also help to maximise condensing when condensing boilers are used.
No flues in apartments Ease of access to heating plant for maintenance Simple integration of low carbon and renewable heat sources.
To help ensure minimum heat losses from the system, all pipework is pre-insulated to save energy and reduce onsite insulation work. For further energy savings an A-rated pump aligns water flows with heating demand to minimise pump energy consumption.
7
A TOTAL SUPPORT PACKAGE FOR SPECIFIERS, CONTRACTORS AND FACILITIES MANAGERS Meibes HIUs deliver key benefits for all parties in the supply chain, from initial system design through to everyday operation and maintenance. All backed by the expertise and support of Pegler Yorkshire. BENEFITS FOR SPECIFIERS AND DEVELOPERS Lower capital costs Reduced installation time Simpler design of heating systems Simpler pipework systems No hot water storage necessary Improved energy efficiency and SAP rating Facilitates integration of different heat sources All distribution at low pressure and temperature Easier to gain planning consent.
BENEFITS FOR CONTRACTORS Ease of installation Faster fix times Ability to separate first and second fix Ease of access to components Annual servicing requirement.
BENEFITS FOR FACILITIES/PROPERTY MANAGERS All plant in a single plant room No need to enter apartments for routine maintenance Reduced energy consumption Heat metering for billing residents Ease of renewables inclusion Reduced carbon footprint Reduced annual boiler servicing cost over individual boilers.
8
CHOOSING THE BEST SYSTEM FOR YOUR APPLICATION The Meibes HIU range includes a number of different models for different applications. Use the flow chart below to select the most appropriate model for your project. No. of bathrooms Heating to be connected to the supply (direct) or Separated via a heat exchanger (indirect)?
Heating & DHW
Direct Heating & DHW
DHW requirement for shower/ bath?
One Two
+ Accessories
No. of bathrooms DHW requirement for shower/ bath?
Indirect Heating & DHW
One Two
Radiator
Stored DHW requirement?
Meibes HIU A1 RX
Instantaneous DHW requirement?
Heat Exchanger
Meibes HIU A2 RX Meibes HIU A2 RX + Accessories
Type of Emitter?
Underfloor No. of bathrooms DHW requirement for shower/ bath?
One Two
Meibes HIU A2 UX Meibes HIU A2 UX + Accessories
No. of bathrooms
Cylinder
DHW requirement for shower/ bath?
One Two
Meibes HIU A1 CX + Accessories
9
CHOOSING THE BEST SYSTEM FOR YOUR APPLICATION
The comprehensive Meibes HIU range ensures that these units can be used with a range of different system configurations. INDIRECT SYSTEM – A2 RX/A2 UX
SYSTEM BENEFITS
The indirect system provides both indirect space heating and indirect DHW. The system uses twin heat exchange units to supply instantaneous DHW and space heating. The Proportional Modulating Valve operates in the same way as a combi diverter valves. Whenever there is a call for DHW, the PM valve diverts the primary flow through the heat exchanger to generate DHW, using all available energy to support the DHW demand. Typically, this results in the heating circuit being closed for just a few minutes, having minimal impact on occupant comfort.
Reduces heat losses Reduces pumped volume around primary circuit Removes peak load issues CENTRAL HEAT GENERATOR
HEAT INTERFACE UNIT
Protects against variation in flow and return rates between apartments
(Primary heating separate to apartment circuit)
Separate heating circuit Flexible temperature control
Mains water Primary flow Primary return
When the DHW demand has been satisfied the primary flow reverts to the space heating system.
RADIATOR/ UNDERFLOOR HEATING
Heating flow Heating return Potable water DHW flow
DIRECT SYSTEM – A1 RX
Low maintenance requirements.
SYSTEM BENEFITS
The direct configuration delivers the primary heating direct to the apartment circuit, with indirect DHW.
Reduced cost Less space required in apartment
CENTRAL HEAT GENERATOR
Low maintenance requirements.
HEAT INTERFACE UNIT (Primary heating direct to apartment circuit)
Mains water Primary flow Primary return
HEAT EMITTER
Heating flow Heating return Potable water DHW flow
INDIRECT FOR CYLINDER SYSTEM – A1 CX When using a cylinder system the primary circuit is separate to the secondary circuit, so that hot water is supplied from the cylinder, ensuring hot water is always available. The system incorporates a zone valve which is controlled by standard controls such as a time clock and a room thermostat to switch off the unit when there is no demand, thereby reducing network load.
SYSTEM BENEFITS Simple design DHW CYLINDER
Heat usage metered Hot water reserve in apartment. CENTRAL HEAT GENERATOR
HEAT INTERFACE UNIT (Using a cylinder system)
HEAT EMITTER Mains water Primary flow Primary return
10
Differential pressure control
Heating flow Heating return Potable water DHW flow
A2 RX
A1 RX
A1 CX
A2 UX
11
PRODUCT FOCUS
Primary return
Strainer – protects from system debris and prolongs life
Differential Pressure Control Valve – improved control, performance and installation
Primary Cold water flow mains
DHW
Heating flow
Heating return
Strainer – protects from system debris and prolongs life
Pump – A-rated pump ensures efficient performance
Proportional Modulation Valve – gives priority to heating over DHW Blending valve
Heat exchanger (DHW) – provides highly efficient performance from a compact unit
A2 RX HIU
12
Heat exchanger (IH)
FIX RAILS First fix rails allow a faster installation that can be staged to align with progress on other parts of the project. For example, the first fix may be carried out in the early stages, with the HIUs themselves being installed later in the project schedule. This reduces the risk of onsite damage to the HIUs. The first fix rail is secured to the wall in the appropriate position allowing all plumbing connections to be made, pressure tested, flushed and filled. Depending on the nature of the contract, this may also support staged billing for work carried out and products installed.
HEAT METERS
FEATURES WRAS approved ball valves Factory sealed flow/ return connections Primary Bypass Module
Available with bypass for easy system flushing Fix rail supports primary pipe work testing.
First fix Rail (also available with Primary Bypass Module)
FEATURES
Meibes HIUs can be factory-fitted with optional heat meters, allowing for accurate, measurement of heat energy use in individual apartments. Use of factory-fitted heat meters reduces onsite work and enables optimum use of skilled labour for more complex tasks. Factory-fitted units are pressure tested before delivery to site.
Heat meter measures the differential between flow and return temperatures
Data from the heat meters can be collected manually or via a wired or wireless network. Pre-payment can also be incorporated.
RHI and OMS compliant
MID approved factory fitted ultrasonic heat meters Conforms to EN1434-3;1997 Common Mbus output into data extraction 10 year battery life Permanent display (shown in kWh).
DATA EXTRACTION The most popular form of data extraction from heat meters is an Mbus network connection, which can be pre-fitted to the heat meter. The data extraction unit sends a master signal to slave meters, which then report on energy consumption data. The readings can be sent via email or pulled directly from the data logger. Where required, heat meters can be fitted with radio-based data extraction systems.
FEATURES Ability to consolidate readings from up to 400 meters Allows data extraction to be directly or remotely configured Flexible programming allows meter readings to be time defined Data can be retrieved or sent automatically via email as CSV-file or xml-file
Available May 2014
SD card as back-up to prevent risk of data loss.
13
PRODUCT DETAILS
MEIBES HIU INDIRECT UNIT
A2 RX BLU-CLIMATE RANGE
14
MEIBES HIU A2 RX BLU-CLIMATE RANGE The A2 RX is a higher capacity version of the A1 RX, suitable for apartments with two bathrooms.
FEATURES & BENEFITS Designed to provide instantaneous Domestic Hot Water and Indirect Heating Compact design – 500mm wide Available in 15 and 19 litres per minute of DHW HIU enables secondary heating for radiators High specification Differential Pressure Control Valve Unique trickle bypass to enable unit primed for DHW Available with case with window for viewing heat meter Also available without case for fitting within an existing cabinet
687902/687906
First fix rails and bypass option also available Complete with WRAS approved ball valves Top connections for easy contractor access.
A2 RX Blu-Climate HIU range options HIU model
With box
With heat meter
Code
Meibes A2 RX Blu-Climate HIU 15 IDH & HW HM
Yes
Yes
687900
Meibes A2 RX Blu-Climate HIU 15 IDH & HW
Yes
No
687901
Meibes A2 RX Blu-Climate HIU 15 IDH & HW HM B
No
Yes
687902
Meibes A2 RX Blu-Climate HIU 15 IDH & HW B
No
No
687903
Meibes A2 RX Blu-Climate HIU 19 IDH & HW HM
Yes
Yes
687904
Meibes A2 RX Blu-Climate HIU 19 IDH & HW
Yes
No
687905
Meibes A2 RX Blu-Climate HIU 19 IDH & HW HM B
No
Yes
687906
Meibes A2 RX Blu-Climate HIU 19 IDH & HW B
No
No
687907
A2 RX Blu-Climate HIU accessory options Accessory
Code
Meibes A2 RX Fix Rail
687550
Meibes A2 RX Fix Rail TP
687551
15
PRODUCT DETAILS
MEIBES HIU TECHNICAL & PERFORMANCE O C DATA
A2 RX BLU-CLIMATE RANGE A2 RX Blu-Climate HIU Technical data Type Description
Construction
Duty (primary) domestic hot water mode
Duty (secondary) domestic hot water
Duty (secondary) heating
Pressure
Connections
Mounting
Wall mounted
Size (WxDxH, height of the case)
500 x 350 x 750mm
Heating system
2 pipe flow
Pipework
Fully insulated flexible stainless steel with brass fittings
Plates heat exchanger
Stainless steel (heat exchanger space heating fully insulated)
Casing
White powder coated sheet steel cover
Primary fluid
Low pressure hot water
Secondary fluid – heating
Low pressure hot water
Secondary fluid – domestic hot water
Potable hot water service
Heat transfer capacity
42kW
50kW
Flow rate
0.275 l/s (990 l/h)
0.282 l/s (1,014 l/h)
Minimum flow temperature primary
65ºC
65ºC
Heat transfer capacity
42kW @ 40K ΔT
50kW @ 40K ΔT
Flow rate
15 l/min (0.250 l/s)
19 l/min (0.317 l/s)
Fluid temperature in
10ºC
10ºC
Fluid temperature out
50ºC
50ºC
Blending valve
35-65ºC
35-65ºC
Capacity
20kW max. @ 20K ΔT
20kW max. @ 20K ΔT
Fluid temperature flow
60ºC @ 65ºC primary flow
60ºC @ 65ºC primary flow
Fluid temperature return
40ºC
40ºC
Maximum primary pressure
10bar
10bar
Maximum secondary pressure
3bar
3bar
Minimum supply water pressure
2bar, maximum 4bar
2bar, maximum 4bar
All external connections
¾"
¾"
Secondary circulation pump
Fittings – primary and secondary heating
Fittings – secondary domestic hot water service
16
Heat Interface Unit for indirect heating and instantaneous domestic hot water
Wilo ‘A rated’ pump in secondary flow
Expansion vessel
8 litre fitted in secondary flow
Strainer
On primary flow and secondary return
Sensor pockets
Flow for heat meter
Heat meter
Rossweiner ‘HeatSonic’ M-Bus heat meter with permanent display
Differential Pressure Control Valve (DPCV)
Factory set at 30kPa (maximum differential pressure 250kPa)
Primary bypass/trickle bypass
Thermostatic bypass between primary flow and return
Air vents
Manual
Controls
Not pre-fitted – externally mounted single channel time switch + roomstat
Controls
Proportional modulation controlled
Dimensions and clearances
Hydraulic layout Primary side Return
Flow
Secondary side
Cold water mains
Domestic hot/cold water
DHW
Flow
Return
1 3 W
2
2 8
4 3
5
16 6 10 15
7 13 14 12
M
9
P
11
Key 1 First fix Rail with connection ball valves (not illustrated) 2 Strainer 3 Provision for test points (½" connection) 4 Heat meter 5 Differential Pressure Control Valve (DPCV) 6 Proportional Modulation Valve (PMV) 7 Plate heat exchanger, DHW 8 Thermostatic blending valve 9 Drain point 10 Thermostatic circulation valve (trickle bypass) 11 Zone valve. Primary side space heating circuit 12 Plate heat exchanger. Space heating 13 Pressure gauge, secondary side 14 Over pressure relief valve, secondary side 15 Expansion vessel 16 Circulator pump, secondary side
750mm
500mm
350mm
Flow performance 100
100
90
90
80
80
15L of DHW @
70 60ºC
Primary flow degrees ºC
Primary flow degrees ºC
70
60 15L of DHW @
15L of DHW
50
50ºC
@ 45ºC
40
30
19L of DH W
60
19L of DH W
19L of DH W
50
@ 60ºC
@ 50ºC
@ 45ºC
40
30 36.43kW/cold water 10ºC
46.15kW/cold water 10ºC
20
20 41.61kW/cold water 10ºC
52.70kW/cold water 10ºC
51.92kW/cold water 10ºC 10
64.76kW/cold water 10ºC 10
*The primary flow should not exceed 1,000 l/h
0
*The primary flow should not exceed 1,000 l/h
0 0
500
1000
1500
2000
Primary flow rate l/h*
2500
3000
3500
0
500
1000
1500
2000
2500
3000
3500
Primary flow rate l/h*
17
PRODUCT DETAILS
MEIBES HIU INDIRECT UNIT
A2 UX BLU-CLIMATE RANGE
18
MEIBES HIU A2 UX BLU-CLIMATE RANGE A2 UX models have been specifically designed for use with underfloor heating.
FEATURES & BENEFITS Designed to provide instantaneous Domestic Hot Water and Indirect Heating Compact design – 500mm wide Available in 19 litres per minute of DHW HIU enables secondary heating for underfloor heating Integrated thermix module High specification Differential Pressure Control Valve
Available May 2014
Unique trickle bypass to enable unit primed for DHW
687932
Available with case with window for viewing heat meter Also available without case for fitting within an existing cabinet Complete with fix rails Bypass option also available Complete with WRAS approved ball valves Top connections for easy contractor access.
A2 UX Blu-Climate HIU range options HIU model
With box
With heat meter
Code
Meibes A2 UX Blu-Climate HIU 19 IDH & HW HM
Yes
Yes
687930
Meibes A2 UX Blu-Climate HIU 19 IDH & HW
Yes
No
687931
Meibes A2 UX Blu-Climate HIU 19 IDH & HW HM B
No
Yes
687932
Meibes A2 UX Blu-Climate HIU 19 IDH & HW B
No
No
687933
A2 UX Blu-Climate HIU accessory options Accessory
Code
Meibes A2 RX Fix Rail
687550
Meibes A2 RX Fix Rail TP
687551
19
PRODUCT DETAILS
MEIBES HIU TECHNICAL & PERFORMANCE O C DATA
A2 UX BLU-CLIMATE RANGE A2 UX Blu-Climate HIU Technical data Type Description
Construction
Duty (primary) domestic hot water mode
Duty (secondary) domestic hot water
Duty (secondary) heating
Pressure
Connections
Fittings – primary and secondary heating
Fittings – secondary domestic hot water service
20
District heating station for indirect heating and instantaneous domestic hot water
Mounting
Wall mounted
Size (WxDxH, height of the case)
500 x 350 x 750mm
Heating system
2 pipe flow
Pipework
Fully insulated flexible stainless steel with brass fittings
Plates heat exchanger
Stainless steel (heat exchanger space heating fully insulated)
Casing
White powder coated sheet steel cover
Primary fluid
Low pressure hot water
Secondary fluid – heating
Low pressure hot water
Secondary fluid – domestic hot water
Potable hot water service
Heat transfer capacity
50kW
Flow rate
0.282 l/s (1,014 l/h)
Minimum flow temperature primary
65ºC
Heat transfer capacity
50kW @ 40K ΔT
Flow rate
19 l/min (0.317 l/s)
Fluid temperature in
10ºC
Fluid temperature out
50ºC @ 65ºC primary flow temperature
Blending valve
35-65ºC
Capacity
20kW max. @ 20K ΔT
Fluid temperature flow
60ºC @ 65ºC primary flow
Fluid temperature return
Max. 40ºC (depends on UFH settings)
Maximum primary pressure
10bar
Maximum secondary pressure
3bar
Minimum supply water pressure
2bar
Maximum supply water pressure
4bar
All external connections
¾"
Secondary circulation pump
‘Thermix’ underfloor heating module with Grundfos pump and automatic mixer 20-80ºC
Expansion vessel
12 litre fitted in secondary flow
Strainer
On primary flow and secondary return
Sensor pockets
Flow for heat meter
Test points
Binder style test points
Heat meter
Rossweiner ‘HeatSonic’ M-Bus heat meter with permanent display
Differential Pressure Control Valve (DPCV)
Factory set at 30kPa (maximum differential pressure 250kPa)
Primary bypass/trickle bypass
Thermostatic bypass between primary flow and return
Air vents
Manual
Zone valve
Fitted with electrical actuator head, max. differential pressure 100 kPa (kvs=1.85)
Controls
Not pre-fitted – externally mounted single channel time switch + roomstat
Controls
Proportional modulation controlled
Dimensions and clearances
Hydraulic layout Primary side Return
Domestic hot/cold water Cold water DHW mains
Flow
Secondary side Flow
Return
1 3 W
2
2
8
4 3
5
16 6 10 15
7 13 14 12
M
9
P
11
Key 1 First fix rail with isolating ball valves 2 Strainer 3 Provision for test points (½" connection) 4 Heat meter 5 Differential Pressure Control Valve (DPCV) 6 Proportional Modulation Valve (PMV) 7 Plate heat exchanger, DHW 8 Thermostatic blending valve 9 Drain point 10 Thermostatic circulation valve (trickle bypass) 11 Zone valve. Primary side space heating circuit 12 Plate heat exchanger. Space heating 13 Pressure gauge, secondary side 14 Over pressure relief valve, secondary side 15 Expansion vessel 16 Underfloor heating, module secondary side (inc. pump mixer)
750mm
500mm
350mm
Flow performance 100
100
90
90
80
80
15L of DHW @
70 60ºC
Primary flow degrees ºC
Primary flow degrees ºC
70
60 15L of DHW @
15L of DHW
50
50ºC
@ 45ºC
40
30
19L of DH W
60
19L of DH W
19L of DH W
50
@ 60ºC
@ 50ºC
@ 45ºC
40
30 36.43kW/cold water 10ºC
46.15kW/cold water 10ºC
20
20 41.61kW/cold water 10ºC
52.70kW/cold water 10ºC
51.92kW/cold water 10ºC 10
64.76kW/cold water 10ºC 10
*The primary flow should not exceed 1,000 l/h
0
*The primary flow should not exceed 1,000 l/h
0 0
500
1000
1500
2000
Primary flow rate l/h*
2500
3000
3500
0
500
1000
1500
2000
2500
3000
3500
Primary flow rate l/h*
21
PRODUCT DETAILS
MEIBES HIU DIRECT UNIT
A1 RX BLU-CLIMATE RANGE
22
MEIBES HIU A1 RX BLU-CLIMATE RANGE The A1 RX unit provides direct heating and instantaneous hot water.
FEATURES & BENEFITS Designed to provide instantaneous Domestic Hot Water and Direct Heating Compact design – 600mm wide Available in 17 litres per minute of DHW HIU enables differential pressure controlled primary heating for radiators Unique trickle bypass to enable unit primed for DHW Includes heat meter (optional) Top connection
Also available without case for fitting within an existing cabinet
Bottom connection
Complete with fix rails and connectors for top connection Complete with WRAS approved ball valves.
A1 RX Blu-Climate HIU range options HIU model
With box
With heat meter
Code
Meibes A1 RX Blu-Climate HIU 17 DH & HW HM
Yes
Yes
687950
Meibes A1 RX Blu-Climate HIU 17 DH & HW
Yes
No
687951
Meibes A1 RX Blu-Climate HIU 17 DH & HW HM B
No
Yes
687952
Meibes A1 RX Blu-Climate HIU 17 DH & HW B
No
No
687953
A1 RX Blu-Climate HIU accessory options Accessory
Code
Meibes A1 RX Fix Rail (for bottom connection)
687570
Meibes A1 RX Fix Rail (for top connection)
687573
Meibes A1 RX Hose Flush
687571
Meibes A1 RX Water Meter
687572
23
PRODUCT DETAILS
MEIBES HIU TECHNICAL & PERFORMANCE O C DATA
A1 RX BLU-CLIMATE RANGE A1 RX Blu-Climate HIU Technical data
Description
Construction
Duty (primary) domestic hot water mode
Duty (sanitary)
Apartment substation for direct and instantaneous domestic hot water Wall mounted
Size (WxDxH, height of the case)
600 x 210 x 800mm
Heating system
2 pipe flow
Pipework
Fully insulated flexible stainless steel with brass fittings
Plate heat exchanger
Stainless steel heat exchanger for domestic hot water (non-insulated for fast cool down/insulated if optional sanitary circulation)
Casing
White powder coated sheet steel cover
Heating fluid
Low pressure hot water
Domestic hot water
Potable hot water service
Heat transfer capacity
46kW
Primary flow rate
910 l/h
Minimum flow temperature primary
65ºC
Flow rate
17 l/min
Flow limiter
Internal choke disk at cold water inlet
Fluid temperature in
10ºC
Fluid temperature out
50ºC @ 65ºC primary flow temperature
Blending valve
35-65ºC
Capacity
10kW max. @ 20K ΔT
Maximum primary pressure
6bar
Maximum supply water pressure
10bar
Optimal supply water pressure
2bar
Temperatures
Maximum operating temperature
110ºC
Connections
All external connections
¾"
Strainer (optional)
In primary flow inlet and/or space heating return (not LogoComfort Basis 600 plus)
Sensor pockets
Sensor pocket in primary flow for optional heat meter
Duty (space heating)
Pressure
Fittings – heating
Fittings – domestic hot water service
24
Type Mounting
Heat meter mounting
110mm spool piece in primary return flow
Heat meter (optional)
Rossweiner ‘HeatSonic’ M-Bus heat meter with permanent display
Differential Pressure Control Valve (optional)
Mounted in primary flow. Factory set = 30kPa, maximum differential pressure = 250kPa
Primary bypass/trickle bypass
Thermostatic bypass between primary flow and return (adjustable 45-65ºC)
Air vents
Manual
Zone valve
In space heating return flow for optional electric actuator head mounting kvs = 1.85
Heating control (optional)
Externally mounted electronic room heating control
Control
Proportional flow control with priority switch
Water meter mounting (optional)
110mm spool piece in cold water inlet
Water meter (optional)
Rossweiner water meter, M-Bus
Connection (optional)
Second cold water outlet after water meter
Sanitary circulation (optional)
Sanitary circulation pump Wilo Star-Z Nova (P max = 4.5W) and external time switch
Dimensions and clearances
Hydraulic layout 4
2
1
M
3
5
13 4
9 6
10
7 8
12
10
800mm 11
Potable water
600mm
Flow performance 100
90
Primary flow degrees ºC
80
17L of DHW @
60
17L of DHW @ 50 ºC 17L of DHW @ 45 ºC
50
Cold water mains
Primary flow
Primary Heating Heating flow return return
Key 1 Stainless steel plate heat exchanger 2 Proportional Modulation Valve (PMV) 3 Flow restrictor disc 17 l/min 4 Bleed point 5 Zone valve (space heating control unit – optional) 6 Balancer or Differential Pressure Control Valve (DPCV) – optional 7 Thermostatic circulation bridge 45...65ºC – optional 8 Spool piece for heat meter (L=110mm, 2 x ¾" outer thread) 9 ½" blind plug – to be replaced by temp. sensor pocket for flow sensor (heat meter) 10 Strainer 11 Isolating ball valve ¾" female connection – optional 12 Male connection/thread spool piece for cold water meter (L=110mm, 2 x ¾" outer thread) – optional 13 Blending valve (thermostatic hot water mixing valve) – optional
210mm
70
DHW
60ºC
40
30 46.6kW/cold water 10ºC 20 53.2kW/cold water 10ºC 65.6kW/cold water 10ºC 10
*The primary flow should not exceed 1,000 l/h
0 0
500
1000
1500
2000
2500
3000
3500
Primary flow rate l/h*
25
PRODUCT DETAILS
MEIBES HIU INDIRECT UNIT FOR O U UFH AND C CYLINDERS S
A1 CX BLU-CLIMATE RANGE
26
MEIBES HIU A1 CX BLU-CLIMATE RANGE A1 CX units are for use with a separate hot water cylinder and have the capacity to serve apartments with two bathrooms.
FEATURES & BENEFITS Designed to suit projects where stored water is preferred Compatible with pre-plumbed unvented cylinders Complete with heat meter Available with case with window for viewing heat meter Also available without case for fitting within an existing cabinet Includes high specification Differential Pressure Control Valve Top connections for easy contractor access Flow and primary return test points included
687972
687974
Built-in strainer for unit.
A1 CX Blu-Climate HIU range options HIU model
With box
With heat meter
Code
Meibes A1 CX Blu-Climate HIU 20K DH & HW HM
Yes
Yes
687970
Meibes A1 CX Blu-Climate HIU 20K DH & HW
Yes
No
687971
Meibes A1 CX Blu-Climate HIU 20K DH & HW HM B
No
Yes
687972
Meibes A1 CX Blu-Climate HIU 20K DH & HW B
No
No
687974
A1 CX Blu-Climate HIU accessory options Accessory
Code
Meibes A1 CX Fix Rail
687424
Meibes A1 CX Fix Rail and Bypass
687485
27
PRODUCT DETAILS
MEIBES HIU TECHNICAL & PERFORMANCE O C DATA
A1 CX BLU-CLIMATE RANGE A1 CX Blu-Climate HIU Technical data
Description
Construction
Duty (primary)
Pressure Connections
Fittings – primary side
28
Type
District heating station to be installed in conjunction with a pre-plumbed unvented cylinder
Mounting
Wall mounted with top or bottom connections
Size (WxDxH, height of the case)
400 x 180 x 500mm
Heating system
2 pipe flow
Pipework
Fully insulated flexible stainless steel with brass fittings
Plate heat exchanger
Fully insulated stainless steel
Casing
White powder coated sheet steel cover with viewing window for the heat meter
Primary fluid
Low pressure hot water
Secondary fluid
Low pressure hot water
Heat transfer capacity
20kW max. @ 30K ΔT (500 l/h)
Fluid temperature flow
65ºC @ 70ºC primary flow
Fluid temperature return
40ºC
Maximum primary pressure
10bar
Maximum secondary pressure
3bar
All external connections
¾" female ball valves 4x: optional ‘First fix rail’
Strainer
On primary flow
Test points
Binder style test points
Sensor pocket
Primary flow temperature sensor for heat meter
Heat meter
Rossweiner ‘HeatSonic’ M-Bus heat meter with permanent display
Solenoid valve (optional)
Not pre-fitted – fitted via removable spool piece
Differential Pressure Control Valve (DPCV)
Factory set at 30kPa (maximum differential pressure 250kPa)
Air vents
Manual
Zone valve
Fitted with electrical actuator head maximum differential pressure 100kPa (kvs=1.85)
Dimensions and clearances
Hydraulic layout
Secondary side Return
8
Primary side
Flow
Flow
8
Return
8
8
1
1
W
2 5 M
500mm
3 6
7 4
400mm
9 M
180mm
Key 1 Test points 2 Strainer 3 Spool piece for heat meter (L=110mm, 2 x ¾" outer thread) 4 Differential Pressure Control Valve (DPCV) 5 Zone valve 6 Plate heat exchanger 7 Bleed points 8 ¾" ball valves (not illustrated) 9 Solenoid valve (optional)
29
MEIBES HEAT INTERFACE UNIT TECHNICAL GLOSSARY
Meibes heat interface unit Features Designed specifically for UK
30
Benefits Designed to meet UK requirements to avoid installation and performance issues. Comprehensive spare stocks available in UK.
Top entry connections
Top entry pipework facilitates pipework runs in ceiling voids for quicker, simpler and more cost effective connection.
First fix rail
Enables faster installation and facilitates staged installation to suit the project timetable and contractor’s schedule. Also allows earlier primary testing of the main heat network. The first fix rail allows all plumbing connections to be made, pressure tested, flushed and filled before installation of the main unit, thereby reducing risk of damage and supporting staged applications for payment where appropriate.
All pipework is pre-insulated
Minimises heat loss for higher energy efficiency, while also improving end user comfort by preventing heat transfer to property during summer.
Integrated Differential Pressure Control Valve (DPCV)
Integrated DPCV make the system ‘self balancing’ and ensures each unit only draws as much energy/flow as it requires in conjunction with a Proportional Modulating Valve. Results in a simpler design with improved control and less noise.
Vertically mounted, un-insulated Domestic Hot Water heat exchanger (DHW)
Uninsulated vertical heat exchanger accelerates cooling of DHW heat exchanger through convection and thermal radiation, minimising limescale formation, maintaining high performance and extending life of units.
Proportional Modulating Valve (PMV)
Gives priority to DHW generation over space heating to ensure full DHW performance. Primary flow rates are matched to cold water input.
Carbon coated operating rod in PM valve, with ceramic disk
Carbon coating provides self lubricating operation, with ceramic disc removing limescale each time the valve operates to deliver a longer, trouble free, service life.
Indirect energy supply
Separates main primary circuit from secondary circuits, ensuring issues in either do not impact on the other. Also provides clear demarcation where different contractors are used for primary and secondary circuit installation.
No demand – no flow
With no demand for hot water or heating the unit is effectively on standby with no flow (see trickle bypass). Minimises demand on main network, reduces energy costs and avoids ‘overheating’ of space where unit is fitted.
‘A-rated’ pump
The electronic pump is an ‘A-rated’ Wilo pump which delivers energy-savings due to only using the minimum amount of electricity.
Blending valve
Controls maximum temperature of DHW from the heat exchanger at 60ºC. The blend valve allows the temperature to adjust from 60ºC down to 35ºC depending on the application requirement.
Trickle bypass (included)
Ensures that the prime flow is hot when the unit is switched off, ensuring quicker response times for DHW demand and eliminating ‘cold legs’ in network where HIUs are some distance from the main network. Avoids need for bypasses on risers, thereby simplifying network design.
Performance based on lower primary flow temperatures – 65ºC
Ensures maximum performance with condensing boilers and supports use of low carbon heat sources (e.g. heat pumps) with lower primary flow temperatures.
Return temperature limited (RTL) valve
An optional RTL is available if required to allow the return temperature to be limited. This protects the boiler from excessive temperatures.
Optional factory fitted, heat meter
Allows accurate measurement of individual energy use. Pressure tested and fitted at factory, reducing on site labour and risk. Range of options to suit project requirements – ultrasonic or mechanical. M-Bus, radio, manual reading, prepayment.
Potable water circuit
WRAS approved to meet UK requirements and compliant with European Drinking Water directive, in line with Pegler Yorkshire’s commitment to highest quality and safety.
Warranties
2 year warranty on the unit and moving parts such as pump (on selected units).
Designed for ease of servicing
Ease of access to all components ensures annual servicing can be completed quickly and efficiently.
Reduced lifecycle costs
Product quality and ease of servicing ensure minimal cost of ownership with sustained high efficiency and performance.
Flexible stainless steel pipework
Reduces thermal expansion stresses for quieter operation during warm up and cool down. Easier future servicing due to flat face connections. In the unlikely event of a need for component replacement, flexible pipework makes re-connection easier.
Test points
Allows confirmation of flow pressure and temperature.
Strainers on primary and secondary circuits
Help to capture debris from either circuit, thereby protecting heat exchangers and/or other components, as well as extending service life. Strainer cleaning is included in annual servicing.
Vertically mounted insulated heat exchanger for heating circuit
Ensures heating circuit heat exchanger remains at temperature without introducing ‘heat’ to the unit. Lack of cycling and appropriate water treatments ensure that limescaling is not an issue.
Simple, straightforward control wiring
External control wiring is similar to a conventional combi boiler and therefore familiar to installers.
Indirect system A2 RX/A2 UX
Direct system A1 RX
Indirect for cylinder system A1 CX
D D
D D
D D
D
³
D
D D
D D
D D
D
D
³
D D D D D D
D D
³
³
D
D
³
³
³
D
³
D
D
³
D D D D D D D D D D D D
D
D
³
³
D D D D D D
D
³ ³ ³
D
³
³
D D D D D ³
D D 31
DISTRICT HEATING SYSTEMS CLIMATE CONTROL
Connect with confidence 1
2
Market-leading Cost effective Highly versatile metal push-fit
Exceptional performance press-fit for the widest variety of applications.
3 Strong, reliable press-fit with simple, heat-free installation
2
MEIBES BLU-CLIMATE A2 RX HIU Indirect DHW Indirect SH
HEAT INTERFACE UNIT
MEIBES BLU-CLIMATE A2 UX HIU
1
MEIBES BLU-CLIMATE A1 CX HIU
1
32
DATA EXTRACTION UNIT
DHW CYLINDER
HEAT INTERFACE UNIT
Indirect DHW Indirect SH
GAS
5
5
5
HEAT INTERFACE UNIT
Indirect DHW Direct SH
BIOMASS
5
1
1
MEIBES BLU-CLIMATE A1 RX HIU
MICRO CHP
5
HEAT INTERFACE UNIT
Indirect DHW Indirect SH
4
5
Mains water Primary flow Primary return
Heating flow Heating return Potable water DHW flow
6 6
HEAT EMITTER
5
5
6
DHW flow 6 6
3
6 UNDERFLOOR HEATING CIRCUIT
DHW flow 6
HEAT EMITTER
5
6 5
6
DHW flow 6 6
HEAT EMITTER
5
5
6
DHW flow
Putting you in control 4 Commission and system balancing that optimises building system performance
5 Energy-saving radiator valves that maximise comfort
6 Elegantly designed, exceptional quality taps and showers
33
NOTES
34
35
Pegler Yorkshire
Follow us on
UK ENQUIRIES UK SALES
Free Phone: 0800 156 0010 Free Fax: 0808 156 1011 Email:
[email protected] TECHNICAL HELP
Free Phone: 0800 156 0050 Free Fax: 0808 156 1012 Email:
[email protected] BROCHURE HOTLINE
Free Phone: 0800 156 0020 Free Fax: 0808 156 1011 Email:
[email protected]
INTERNATIONAL ENQUIRIES EXPORT
Tel: +44 (0) 1302 855 656 Fax: +44 (0) 1302 730 513 Email:
[email protected]
HEAD OFFICE
Registered in England Company No. 00401507
Pegler Yorkshire Group Limited St. Catherine’s Avenue, Doncaster, South Yorkshire DN4 8DF, England
All brand names and logo styles are registered trademarks. Maintaining a policy of continual product development, Pegler Yorkshire reserves the right to change specifications, design and materials of products listed in this publication without prior notice
Tel: +44 (0) 844 243 4400 Fax: +44 (0) 844 243 9870 Email:
[email protected] LIT.REF: 880153.03.14
www.pegleryorkshire.co.uk