Preview only show first 10 pages with watermark. For full document please download

Photometric Report

   EMBED


Share

Transcript

Photometric Report Tuesday, December 04, 2012 CATALOG NUMBER: AS607-4-X-OP/LP-X-X-T8 FILENAME: AS607-4-OP-LP-T8 LTL#100627.IES IESNA:LM-63-2002 [TEST] LTL100627 [MANUFAC] PRECISION ARCHITECTURAL LIGHTING [LUMCAT] AS607-4-X-OP/LP-X-X-T8 [LUMINAIRE] EXTRUDED ALUMINUM HOUSING WITH CAST ALUMINUM [MORE] END CAPS AND HIGH REFLECTANCE WHITE ENAMEL ALUMINUM [MORE] REFLECTORS WITH WHITE ALUMINUM PARABOLIC BAFFLE AND OPEN [MORE] TOP [LAMP] THREE PHILIPS F32T8/TL830/XLL/ALTO RATED 2950 LUMENS EACH SUMMARY DATA EFFICIENCY (Total): EFFICIENCY (Downlight): EFFICIENCY (Uplight): CIE CLASSIFICATION: SPACING CRITERION (0-Deg.): SPACING CRITERION (90-Deg.): LUMENS/LAMP: NO. OF LAMPS: LUMINOUS OPENING: RECTANGULAR Width: Length: Height: INPUT WATTS: CANDELA PLOT 170 2000 65.9 % 17.4 % 48.5 % SEMI-INDIRECT 1.14 1.42 2950 3 160 150 140 130 120 1500 110 1000 0.50 (Feet) 4.00 0.00 90 100 500 ZONAL LUMEN SUMMARY Zone 0 - 30 0 - 40 0 - 60 60 - 90 0 - 90 90 - 180 0 - 180 90 Lumens % Lamp % Luminaire 434.3 4.9 7.4 718.3 8.1 12.3 1257.1 14.2 21.6 285.2 3.2 4.9 1542.2 17.4 26.4 4289.9 48.5 73.5 5832.2 65.9 100.0 500 80 10 20 30 40 50 60 Quadralaterally Symmetric Dashed: 0 Degrees Solid: 90 Degrees AVERAGE LUMINANCE (Candelas / Square Meter) Angle 0 45 55 65 75 85 0 2913 2445 2346 1884 1168 463 22.5 2913 2587 2487 2063 1500 1041 45 2913 3108 2750 2099 1850 1561 67.5 2913 3165 2636 2171 2201 1793 90 2913 3115 2584 2242 2317 1735 COEFFICIENT OF UTILIZATION TABLE Effective Floor Cavity Reflectance = 20% Pcc ... Pw ... RCR 0 1 2 3 4 5 6 7 8 9 10 70 .67 .61 .56 .51 .46 .42 .39 .36 .33 .31 .29 80 50 30 .67 .58 .51 .45 .39 .35 .31 .28 .25 .23 .21 .67 .56 .47 .40 .34 .30 .26 .23 .21 .18 .17 10 70 .67 .54 .44 .36 .31 .26 .22 .20 .17 .15 .13 .60 .54 .49 .45 .41 .38 .35 .32 .30 .27 .26 70 50 30 .60 .52 .45 .40 .35 .31 .28 .25 .23 .21 .19 .60 .50 .42 .36 .31 .27 .24 .21 .19 .17 .15 10 50 50 30 10 50 30 30 10 50 10 30 10 0 0 .60 .48 .40 .33 .28 .24 .20 .18 .16 .14 .12 .46 .40 .35 .31 .28 .25 .22 .20 .18 .17 .15 .46 .39 .33 .29 .25 .22 .19 .17 .15 .13 .12 .46 .38 .31 .26 .22 .19 .17 .14 .13 .11 .10 .34 .30 .26 .23 .21 .18 .17 .15 .14 .12 .11 .34 .29 .25 .21 .19 .16 .14 .13 .11 .10 .09 .34 .28 .24 .20 .17 .15 .13 .11 .10 .09 .08 .23 .20 .18 .16 .14 .13 .11 .10 .09 .09 .08 .23 .20 .17 .15 .13 .11 .10 .09 .08 .07 .07 .23 .19 .16 .14 .12 .10 .09 .08 .07 .06 .06 .17 .15 .12 .10 .09 .08 .07 .06 .05 .05 .04 Reported data calculated from manufacturer's data file, based on IESNA recommended methods. 70 Photometric Report Tuesday, December 04, 2012 CATALOG NUMBER: AS607-4-X-OP/LP-X-X-T8 FILENAME: AS607-4-OP-LP-T8 LTL#100627.IES CANDELA TABLE Vertical Angle 0 2.5 5 7.5 10 12.5 15 17.5 20 22.5 25 27.5 30 32.5 35 37.5 40 42.5 45 47.5 50 52.5 55 57.5 60 62.5 65 67.5 70 72.5 75 77.5 80 82.5 85 87.5 90 92.5 95 97.5 100 102.5 105 107.5 110 112.5 115 117.5 120 122.5 125 127.5 130 132.5 135 137.5 140 142.5 145 147.5 150 152.5 155 157.5 160 162.5 165 Horizontal Angles 0 22.5 45 541 541 541 539 540 539 536 537 536 530 531 532 523 524 531 513 517 532 502 510 535 489 504 537 476 497 534 460 493 525 445 486 512 429 477 500 411 464 490 394 446 479 377 428 460 361 406 441 347 385 431 334 364 420 321 340 408 308 316 389 292 298 361 273 282 329 250 265 293 226 243 258 199 218 222 174 191 191 148 162 165 123 134 143 99 111 124 77 90 106 56 72 89 38 56 74 25 42 59 15 29 42 7 17 25 3 7 10 2 6 8 12 22 19 48 60 51 95 107 109 145 161 167 200 226 222 258 293 280 318 361 349 376 424 425 437 501 503 496 573 579 554 640 649 610 700 711 667 757 768 719 809 831 770 863 904 820 910 966 867 957 1022 913 1001 1069 957 1040 1110 998 1075 1145 1039 1109 1178 1075 1139 1211 1111 1164 1237 1143 1190 1263 1173 1217 1282 1201 1244 1295 1228 1261 1307 1250 1276 1315 1272 1289 1321 1290 1301 1334 67.5 541 539 537 537 540 549 553 553 545 538 532 526 513 497 490 479 468 447 416 381 347 315 281 245 216 190 170 152 136 121 106 90 71 51 29 11 9 18 41 96 159 222 283 339 403 480 560 637 714 785 849 904 955 1015 1083 1141 1187 1224 1254 1279 1301 1322 1338 1350 1354 1356 1354 90 541 540 538 539 546 555 558 557 550 545 540 534 518 509 500 489 473 444 409 376 345 311 275 243 216 194 176 158 142 126 111 95 73 52 28 11 10 18 40 84 155 220 283 342 400 468 552 631 709 780 852 915 968 1017 1076 1144 1197 1240 1274 1301 1320 1340 1353 1370 1376 1375 1374 Reported data calculated from manufacturer's data file, based on IESNA recommended methods. Photometric Report Tuesday, December 04, 2012 CATALOG NUMBER: AS607-4-X-OP/LP-X-X-T8 FILENAME: AS607-4-OP-LP-T8 LTL#100627.IES 167.5 170 172.5 175 177.5 180 1305 1317 1327 1335 1338 1339 1310 1320 1328 1335 1337 1339 1335 1334 1334 1335 1336 1339 1356 1353 1347 1340 1340 1339 1374 1369 1354 1348 1346 1339 Reported data calculated from manufacturer's data file, based on IESNA recommended methods.