Transcript
s lay e e r ge fac Ran r e Int CR
Pluggable interface relays Technical data
Type
CR-P...1
Output circuit(s) Kind of output Contact material
CR-P...2
CR-M...2
CR-M...3
CR-M...4 11-12/14 21-22/24 31-32/34 41-42/44 Relay, 4 c/o AgNi AgNi/Au 5 µm
11-12/14
11-12/14 21-22/24
11-12/14 21-22/24
11-12/14 21-22/24 31-32/34
Relay, 1 c/o
Relay, 2 c/o AgNi AgNi/Au 5 µm
Relay, 2 c/o
Relay, 3 c/o
AgNi
AgNi
AgNi
Rated operational voltage Ue (VDE 0110, IEC 60947-1)
11-12/14 31-32/34
11-12/14 21-22/24 31-32/34
Relay, 2 c/o
Relay, 3 c/o
AgNi
5V
Maximum switching voltage
DC
300 V DC
AC
400 V AC
250 V DC 250 V AC
Minimum switching current
5 mA (AgNi), 2 mA (AgNi/Au)
Rated free air thermal current Ith Rated operational current (IEC 60947-5-1)
AC rating (UL 508)
CR-U...3
250 V
Minimum switching voltage
6
CR-U...2
16 A
8A
12 A
10 A
6A
10 A
AC12 (resistive) 230 V
16 A
8A
12 A
10 A
6A
10 A
AC15 (inductive) 230 V
1.5 A
1A
1.5 A
1.5 A
1A
1.5 A
DC12 (resistive) 24 V
16 A
8A
12 A
10 A
6A
10 A
DC13 (inductive) 24 V
2A
2A
8A
8A
6A
2A
Utilization category (Control Circuit Rating Code)
-
-
-
B 300
max. rated operational voltage
-
-
-
300 V AC
max. continuous thermal current at B 300
-
-
-
5A
max. making / breaking apparent power at B 300
-
-
-
3600/360 VA
Utilization category General Purpose (single phase)
-
-
10 A, 250 V AC
10 A, 250 V AC
10 A, 250 V AC
-
10 A, 250 6 A, 250 V AC 6 A, 250 V AC V AC 10 A, 150 10 A, 150 12 A, 150 V V AC V AC AC 0.3 W (AgNi), 0.1 W (AgNi/Au)
Utilization category (Resistive)
16 A, 250 V AC
8 A, 250 V AC
AC-1
4000 VA
2000 VA
Minmum switching power Maximum switching power Contact resistance Maximum switching capacity
rated load AC-1 without load
Mechanical lifetime Electrical lifetime
AC1 (resistive)
3000 VA
2500 VA
0.3 W
1500 VA
2500 VA
100 m
100 m
600 switching cycles/h
1200 switching cycles/h
72000 switching cycles/h > 3 x 107 switching cycles > 10 5 switching cycles (16 A, 250 V) (8 A, 250 V)
cos ϕ
18000 switching cycles/h
12000 switching cycles/h
> 2 x 107 switching cycles > 10 5 switching cycles > 10 5 switching cycles (12 A, 250 V) (10 A, 250 V) (6 A, 250 V) (10 A, 250 V) see reduction factor F
Response time
typ. 7 ms
typ. 13 ms (DC),10 ms (AC)
typ. 18 ms (DC), 12 ms (AC)
Release time
typ. 3 ms
typ. 3 ms (DC), 8 ms (AC)
typ. 7 ms (DC), 10 ms (AC)
Isolation data Rated insulation voltage
400 V AC
Insulation class
250 V AC
C250 / B400
Rated impulse withstand voltage Uimp
between coil and contacts between open contacts
C250 / B250
5 kV AC
C250 2.5 kV AC
1 kV AC
1.5 kV AC
between c/o contacts
2.5 kV AC
2.5 kV AC
2 kV AC
2 kV AC
Clearance
between coil and contacts
10 mm
2.5 mm
1.6 mm
3 mm
Creepage distance
between coil and contacts
10 mm
4 mm
3.2 mm
4.2 mm
Overvoltage category
III
III
II
III
Pollution degree
3
3
2
3
General data Dimensions (W x H x D) when mounted Weight
12.7 x 29 x 15.7 mm
21.2 x 27.5 x 35.6 mm
35 x 35 x 54.4 mm
14 g (0.031 lb)
35 g (0.077 lb)
83 g (0.18 lb)
Mounting
on socket (see accessories)
Mounting position Degree of protection
any IP 67
IP 40
Electrical connection Connection
by socket
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email:
[email protected]
Int
er f CR ace Ra rela ng ys e
Pluggable interface relays Technical data, load limit curves
Type
CR-P...1
CR-P...2
CR-M...2
CR-M...3
CR-M...4
CR-U...2
CR-U...3
Environmental data Ambient temperature range
operation DC
-40 ... +85 °C
-40 ... +70 °C
operation AC
-40 ... +70 °C
-40 ... +55 °C
storage Vibration resistance 10-150 Hz Shock resistance
-40 ... +85 °C
n/o contact
10 g
5g
5g
n/c contact
10 g
5g
5g
5g
n/o contact
30 g
20 g
10 g
10 g
n/c contact
30 g
20 g
5g
10 g
EN 60810-1, EN 60255-23 IEC 61810-7
EN 60255-1-00
Standards Product standard
EN 61810-1, EN 60255-23 IEC 60664-1
Low Voltage Directive
73/23/EEC
CR-P with 1 c/o contact
CR-P with 2 c/o contacts
CR-U with 2 and 3 c/o contacts
DC current [A]
DC current [A]
DC current [A]
Load limit curves - Maximum switching power at resistive DC load
1 = resistive load, T = 0 ms 2 = inductive load, T = 40 ms
DC voltage [V]
DC voltage [V]
DC current [A]
DC voltage [V]
CR-M with 4 c/o contacts
1 = resistive load, T = 0 ms 2 = inductive load, T = 40 ms
DC voltage [V]
DC current [A]
CR-M with 3 c/o contacts
DC current [A]
DC voltage [V]
CR-M with 2 c/o contacts
DC voltage [V]
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email:
[email protected]
6
s lay e e r ge fac Ran r e Int CR
Pluggable interface relays Load limit curves
Load limit curves - Electrical lifetime at resistive AC load
Switching cycles
Switching cycles
CR-U with 2 and 3 c/o contacts
Switching power [kVA] Switching power [kVA]
CR-M with 2 c/o contacts
Switching power [kVA]
CR-M with 4 c/o contacts
Switching power [kVA]
Switching cycles
Switching cycles
Switching cycles
CR-M with 3 c/o contacts
Switching power [kVA]
Switching power [kVA]
Reduction factor F at inductive AC load CR-M
CR-U
Reduction factor
Reduction factor
CR-P
Reduction factor
6
CR-P with 2 c/o contacts
Switching cycles
CR-P with 1 c/o contact
Power factor
Power factor
Power factor
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email:
[email protected]
Pluggable interface relays Connection diagrams
Int
er f CR ace Ra rela ng ys e
Connection diagrams
6 CR-P with 1 c/o contact
CR-P with 2 c/o contacts
CR-M with 2 c/o contacts
CR-M with 3 c/o contacts
CR-M with 4 c/o contacts
Dimensional drawings
CR-P
CR-U with 2 c/o contacts
CR-U with 3 c/o contacts
Dimensions in mm
CR-M with 2 c/o contacts
CR-U with 2 c/o contacts
CR-M with 3 c/o contacts
CR-U with 3 c/o contacts
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email:
[email protected]
s lay e e r ge fac Ran r e Int CR
Pluggable interface relays Approximate dimensions
Dimensional drawings
Dimensions in mm
Sockets for screw connection
Marker
Marker
42,6
27,2
62
27,2
27,2
24
51,2
15,8 7,5
Relay 35,4
75,2
29
Holder
10
6 76
20
Pluggable function module
Relay
CR-M2SS - CR-M3SS - CR-M4SS Holder
60,8
27,2 Marker 27,2
42,6
27,2
24
Pluggable function module
62
75
35,4
Relay
CR-PLS
Holder
62 61 CR-M2LS
42.5
CR-M3LS
Pluggable function module
29,1
CR-M4LS
3.2
37,3
38,1
78.5
Relay
75,3
Holder 9 - M3
Pluggable function module
24
7.62
35,4
75,3
12 - M3
29.4
5.08
20.32
5.08
CR-M2LS - CR-M3LS - CR-M4LS
50 4
15.5
29,8
CR-PLSx
CR-U2S
29,8 CR-U3S
CR-U2S - CR-U3S
Marker
42.8
76
20
10
Holder
Relay
CR-U3E Pluggable function module
24 15,8
CR-PSS
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email:
[email protected]
Int
er f CR ace Ra rela ng ys e
Pluggable interface relays Approximate dimensions Dimensional drawings
Dimensions in mm 38,1
38,1
26
27,8
27,8
8 - M3
35,4
61,8
61,8
11 - M3
6 CR-U2SM
CR-U3SM
4
CR-U2SM
CR-U3SM
Sockets for spring connection 43,5
42,5
33,8 7,62
33,2 31
24
95 5,5
25,9
20,32
5,08
97,5
15
5,08
12,4
12,4
24,4
16,3
27
34,4
26 79,5
CR-PLC
CR-M2LC , CR-M4LC
Jumper
9 x 27.2 (=244,8) 27.2 ±0.2 2±0,2
6±0,2
1
R1
9,5
10
246.8
CR-PJ 9x15 (=139,5) 15,5 ±0,2
2±0,2
R1
1,5
6±0,2
10
10
141,5+1
CR-MJ
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: