Transcript
PLX SERIES
PLX12-700FT (12V715W)
HIGH RATE
Specification Nominal Voltage
12V
Power (Watts)
715W
(15min,1.67V/cell,25o C)
Rated Capacity (Ah)
190Ah
(C10,1.80V/cell,25o C)
PC-ABS flame retardant jar and cover to UL94V-0
Max. Discharge Current
1500A (5s)
Internal Resistance
Approx 3.0mΩ
Operating Temp.Range
Discharge : -40o C~65o C (-40o F~149o F) Charge : 0o C~40o C (32o F~104o F ) Storage : -20o C~40o C (-4o F~104o F)
Capacity affected by Temperature
40o C 25o C 0o C
(104o F) ( 77o F ) ( 32o F )
320±2 309.5
Threaded M8 insert with M6 front terminal adaptor
Container Material
103% 100% 86%
538.1
PLX series batteries can be stored up to 24 months at 25°C(77°F), For higher temperatures the time interval will be shorter. Battery needs to be given a freshening charge when the OCV approach 2.10V/cell or when the maximum storage time is reached, whichever occurs first.
Storage
123
561.9±2 540
20
125±2
Weight Terminal
29.3±0.5
Dimension
562±2mm (22.13 inches) 125±2mm ( 4.92 inches) 320±2mm (12.60 inches) 320±2mm (12.60 inches)
2
Length Width Container Height Total Height (with Terminal) 60.5Kg (133.1 Ibs)
M8
242±1
Unit: mm
t est ed Germany
Constant Current Discharge (Amperes) at 25 0 C (77 0 F ) F.V/Time
5min
10min
15min
20min
30min
45min
1h
2h
3h
4h
5h
8h
10h
20h
1.85V/cell
399.0
338.6
296.4
254.8
192.7
142.1
112.5
64.9
46.8
36.8
30.7
21.4
18.4
9.58
1.80V/cell
458.3
378.5
330.6
281.6
207.9
151.2
118.8
67.2
48.6
38.0
31.7
22.1
19.0
9.88
1.75V/cell
499.3
408.1
351.9
300.4
220.8
158.8
124.5
68.7
49.6
39.0
32.5
22.5
19.3
10.1
1.70V/cell
547.2
437.2
370.1
313.5
231.4
165.7
128.6
70.5
50.7
39.8
33.1
22.9
19.5
10.2
1.67V/cell
655.0
462.8
382.1
326.0
239.6
171.0
133.0
71.8
51.3
40.1
33.5
23.3
19.6
10.3
1.60V/cell
670.1
487.9
398.5
334.6
246.8
175.8
136.0
73.0
51.6
40.5
33.8
23.4
19.8
10.4
0
0
Constant Power Discharge (Watts/cell) at 25 C (77 F ) F.V/Time
5min
10min
15min
20min
30min
45min
1h
2h
3h
4h
5h
8h
10h
20h
1.85V/cell
742.9
645.3
572.3
495.9
377.6
281.1
223.2
129.6
93.7
73.9
61.8
43.5
37.4
19.5
1.80V/cell
846.0
713.4
635.1
544.5
404.8
297.0
234.1
133.4
96.8
76.0
63.6
44.5
38.5
20.1
1.75V/cell
913.5
764.0
671.7
575.5
426.3
309.7
243.7
135.8
98.4
77.5
64.8
45.3
39.0
20.4
1.70V/cell
975.1
805.8
699.6
595.0
443.3
321.0
250.5
138.8
100.2
78.9
65.8
46.1
39.3
20.6
1.67V/cell
1000.0
825.2
715.0
612.4
460.0
329.5
257.5
140.7
101.0
79.3
66.5
46.6
39.4
20.7
1.60V/cell
1060.0
842.6
720.0
621.6
475.0
335.4
261.3
142.0
101.0
79.7
66.8
46.7
39.7
20.8
Specifications subject to change without notice.
Features & Benefits 15 years design life(25°C)
Automated COS & TTP
Excellent high rate discharge capability
Low internal resistance
M6 & M8 Terminal adapter options
for emergency backup power supply
Fast Charging Acceptance
Flame Retardant to UL94V-0
particularly UPS. High quality AGM separators minimize
Premium ABS+ jar & covers
Long Shelf Life up to 2 years @77°F(25°C)
IATA Approved for Air Freight
High-rate performance, high energy density
Heat sealed plastic container
Virgin pure lead plates / copper alloy
UL Recognized, IEC Certified
terminal inserts
with Thin Plate Pure Lead technology
Charging Charging Voltage Current
Charging Volume
Temperature 25 o C
(V)
Terminal Voltage(V)
Outstanding high rate charge capability
Charging Characteristics
Discharging Characteristics 12V Battery
electrical resistance to allow high current discharging properties.
(%)
(XCA)
140
13 12
120
0.10
100
0.08
13.5V Temperature 25oC
(V)
Charged Volume
15 14
11
80
0.263C
10
13
60
1.064C 0.615C
9
Charge Voltage
0.06
0.1C 0.053C
0.04 40
After 50% Discharge
12
After 100% Discharge
0.02
8
3.5C
1
2
4
2.4C
6 8 10 0.1
20
20
11 Charging Current
40 60 100 200
0.2 0.3 0.4 0.5
1
400 600 1000 2000
2 3 45
10
20
(Min)
0
0
0
0
4
8
Discharging Time
1h Rate
20
24
28
32
36
40
Self Discharge Characteristics
5h Rate
Temperature 25oC
10
100
Remaining Capacity C10(%)
Discharging Time (h)
16
Charging Time(hours)
Effect of Temperature on Discharging Time 15min Rate
12
(Hours)
1
0.1
0.01 -40
-30
-20
-10
0
10
20
30
25 o C
90
o
80 70 60 50 40 30
40
o
45 C 55 C
0
o
Temperature( C)
10
20
30
40
50
60
70
Storage Time (Weeks) Pure Lead Battery
General AGM Battery
China sales office
HongKong sales office
Singapore sales office
Australia Sales Office
5th Floor,Xinbaohui Bldg.,Nanhai Blvd., Nanshan,Shenzhen, China. 518052 Tel: +86-755-86036060 (100 lines) Fax: +86-755-26067269 E-mail:
[email protected]
Workshop C, 33/F, TML Tower,No. 3 Hoi Shing Road, Tsuen Wan, New Territories, Hong Kong Tel: +852 35786666 Fax:+44 1452 690125
[email protected]
No. 1 Tech Park Crescent, Singapore 638131 Tel: +65 68636078
2 /29 Tarlington Place, Smithfield. NSW 2164 Australia Tel: 02 9756 0950 E-mail:
[email protected]
Email
[email protected]
North America sales office
UK sales office
Europe/MEA Sales Office
India Sales Office
19751 Descartes, Unit A, Foothill Ranch, CA 92610, USA Tel: 949-588-5853
9B Wheatstone Court. Waterwells, Business Park, Gloucester, GL2-2AQ, UK United Kingdom Tel: +44(0) 1452 729428 / 1452 729696
1 Deligiorgi St., 121 31 Athens Greece Tel: +30 210 5760318 (2 lines)
Fax: 949-588-5966
Fax:+44 1452 690125
E-mail:
[email protected]
E-mail:
[email protected]
E-mail:
[email protected]
Shed no.A-53(b), 2nd Stage of Peenya Industrial Area, Bangalore North Taluk, Bangalore-560058, India Tel: +91-80-23440018/23440019 Fax: +91-80-23440017 E-mail:
[email protected]
Http://www.leoch.com
Fax: +65 6863 6079
© 2017 LEOCH. All rights reserved. Trademarks and logos are the property of LEOCH and its affiliates unless otherwise noted.
Http://www.leoch.us
Subject to revisions without prior notice.
Publication No.:LB-PLX12-700FT-PD-EN-V1.0-201708
Sales Offices Worldwide