Transcript
RESDELUX STEAM HUMIDIFIERS
SHOP DRAWINGS Date:___________________________________________________________ Job Name:__________________________________________________________ Contractor:______________________________________________________ Contractor or Order No.:___________________________________________ Engineer:________________________________________________________ Agent:__________________________________________________________ Agent P.O. No.:__________________________________________________ Date Ordered:__________________________________________________________ FUSED DISCONNECT SIZE (AMPS):
15
UNIT RUNNING AMPS (as 100% FLA): 11.5 PRIMARY SUPPLY VOLTAGE
110V
115V
120V
208V
220V
230V
240V
POWER RATING (KW):
1.3
1.3
1.4
2.4
2.5
2.65
2.76
UNIT CAPACITY (lbs/hr):
3.7
3.9
4.0
7.0
7.4
7.8
8.1
Electronic electrode self-contained steam humidifier incorporating “Auto-Adaptive” solid state control, fill/drain solenoid valves, on/off and drain switches, disposable steam cylinder, status indicator lamp, fill valve strainer with water flow regulation orifice, fill side air gap, injection molded plastic drain reservoir, primary voltage terminal block, all housed in a metal cabinet.
NORTEC Air Conditioning Ind. Ltd. 2740 Fenton Road Ottawa, ON, K1T 3T7 Tel.: (613) 822-0335 Fax: (613) 822-7964
NORTEC Industries Inc. 826 Proctor Avenue Ogdensburg, NY 13669 Tel.: (315) 425-1255 E-mail:
[email protected] FORM # 03-60
A WMH COMPANY
Printed in Canada
11.25” (285mm) 5.6” (142.5mm) 1.8” (46.5mm)
Condensate Return
0.67” (17mm)
3.4” (87.0mm)
1.25” (32.0mm) 1.4” (35.0mm)
6.75” 2.6” (26.6mm) (65.0mm)
6.5” (165.1mm) 4” (101.6mm) 0.75” (19mm)
5.6” (142.5mm)
Steam Outlet 0.875” Ø (22.2mmØ)
12.125” (308mm) 18.75” (476.3mm)
POWER ON
Wall supports
CHANGE CYLINDER
0.75” (19mm)
0.25” (6.4mm) 5.8” (147.3mm)
Note: Drain channel may be rotated as required
1.75” (44.5mm) Feed Water Connection
Electrical Connections
3.25” (82.6mm)
2.8” (71.0mm) 0.25” (6.4mm) Drain Water Outlet
Power Circuit Output Range Minimum Output Range Maximum Rated Input Rated Current Max. Circuit Protection
Performance Data
110-120/1/60 V/(phase)/Hz 1.0 lbs/hr (0.45 kg/hr) 4.0 lbs/hr (1.8 kg/hr) 1380 W 11.5 Amps 15 Amps
1.5” (38.0mm) 2.3” (58.8mm)
208-240/1/60 V/(phase)/Hz 2 lbs/hr (0.9 kg/hr) 8 lbs/hr (3.6 kg/hr) 2760 W 11.5 Amps 15 Amps
Dimensional Data
Net Weight Full Weight Front Clearance Supply Water OD Drain Water OD Steam Outlet OD
ResDelux with Blower Pack Physical Data 1/13/03
FORM #03-60
-1-
18.9 lbs (8.57 Kg) 26.5 lbs (12 Kg) 36 in ( 914 mm) 0.25 in 0.875 in 0.875 in
11.25” (285mm)
6.5” (165mm) 1.5” (38.1mm)
8.25” (209.6mm)
1.0” (25.4mm)
6.25” (160mm) 0.5” (12.7mm) Wall Mounting Holes
Holes For Mounting to ResDelux
Steam Inlet
Condensate return
2.5” (63.5mm)
1.4” (35.0mm) 5.65” (143.5mm) 7.85” (199.4mm)
Blower Pack - ResDelux Physical Data 2/20/03 FORM #03-60
-2-
Power and Controls
1581311
1581312
Control Board Connection
PN 158-1830: Steam Blower Pack. Optional accessory for RESDELUX humidifier. Refer to RESDELUX manual (Form #58) for additional information and mounting instructions. Use enclosed 3½” long steam hose only for cabinet mounted version to connect Blower Pack steam tube with cylinder. PN 158-1311: Power Supply PN 158-1312: Blower Fan Assembly
Steam Blower Pack PN 158-1830
FORM #03-60
-3-
1581821 1535062
1585001 PN 158-1820: Steam Distributor Kit. Optional accessory for RESDELUX humidifier. Refer to RESDELUX manual (Form #58) for additional information and mounting instructions. PN 158-1821: Steam Hose 4’ long. PN 153-5062: Steam Nozzle PN 158-5001: Steam Hose Bracket
RESDELUX Steam Distributor Kit PN 158-1820
FORM #03-60
-4-
FORM #03-60
-5-
TRANSFORMER WITH BUILT-IN CIRCUIT BREAKER BY OTHERS
120/208/240 V POWER SOURCE
24VAC
WALL HUMIDISTAT (PN 1329102) OR DUCT HUMIDISTAT (PN 1329108), MAKES ON FALL IN HUMIDITY
2
AIRFLOW SWITCH, MAKES WITH AIRFLOW (PN 1329203)
SUGGESTED WIRING INTERFACE FOR FAN CONTROL USING RESDELUX HUMIDIFIER 3/11/02
RESDELUX LOW VOLTAGE TERMINAL STRIP
1
HI-LIMIT HUMIDISTAT (PN 1329108) MAKES ON FALL IN HUMIDITY
WIRED IN PARALLEL WITH NORMAL FAN RELAY
DPDT AUX FAN RELAY, 24VAC COIL WITH 2 NORMALLY OPEN CONTACTS