Subject 9910 UPS title for IBM Power Systems
North America
Power Protection Handbook August 2013
Cover headline Cover subheadline
Table of Contents 9 power problems and their UPS solutions ....................................................................................... 2 UPS topologies: online, line-interactive and standby ........................................................................ 3 The basics of voltage, amperes and frequency ................................................................................. 4 Input plugs and receptacles .............................................................................................................. 5 Frequently asked questions .............................................................................................................. 6 Preventing UPS problems ................................................................................................................. 7 Glossary of power terms ................................................................................................................... 8 Commonly-used acronyms .............................................................................................................. 10 How much battery runtime do you need? ........................................................................................ 11 UPS software overview ................................................................................................................... 12 Attributes at a glance....................................................................................................................... 13 IBM 9910 model P13 ....................................................................................................................... 14 IBM 9910 model E15 ....................................................................................................................... 17 IBM 9910 model E35 ....................................................................................................................... 20 IBM 9910 model E50 ....................................................................................................................... 23 IBM 9910 model E66 ....................................................................................................................... 26 IBM 9910 model E82 ....................................................................................................................... 29 Power Cords ................................................................................................................................... 33 Software and connectivity ............................................................................................................... 34 Service and support ........................................................................................................................ 35
Note: Due to continuing product improvement programs, all specifications are subject to change without notice. For the latest information, go to www.eaton.com/ibm.
Eaton, Eaton, ABM, Intelligent Power, ConnectUPS, and X-Slot are trade names, trademarks and/or service marks of Eaton Corporation or its subsidiaries and affiliates. All other trademarks are property of their respective owners.
www.eaton.com/ibm 1.800.925.4426
1
9 power problems and their UPS solutions In an ideal world, your wall socket would provide an infinite stream of perfect power, at constant voltage and cycling exactly the same number of times per second. Don’t count on it.
2
Power Problem
Definition
1
Power Failure
Total loss of utility power.
2
Power Sag
Short-term low voltage.
3
Power Surge (Spike)
Short-term high voltage more than 110% of normal.
4
Under-voltage (Brownout)
Reduced line voltage for an extended period of a few minutes to a few days. Often happens during the summer months when everyone is cranking up their air conditioners.
5
Over-voltage
Increased line voltage for an extended period of a few minutes to a few days.
6
Electrical Line Noise
High power frequency power wave caused by radio frequency interference (RFI) or electromagnetic interference (EMI).
7
Frequency Variation
A loss of stability in the power supply’s normal frequency of 50 or 60 Hz.
8
Switching Transient
Instantaneous under-voltage in the range of nanoseconds.
9
Harmonic Distortion
Distortion of the normal power wave, generally transmitted by unequal loads.
Eaton Power Protection Handbook: 9910 UPS for IBM Power Systems
UPS topologies: online, line-interactive and standby There are several different UPS topologies that offer varying levels of protection. Selecting the best fit depends on several factors, including the level of reliability and availability desired, the type of equipment being protected and the application/environment. While all three of the most common UPS topologies outlined below meet the input voltage requirements for IT equipment, there are key differences in how the result is achieved, as well as the frequency and duration of demands on the battery.
Standby UPS Technology
Standby UPSs allow equipment to run off utility power until the UPS detects a problem, at which point the UPS switches to battery power to protect against sags, surges or outages. Because the band of normal operation is typically narrow, the UPS must resort to batteries frequently, which can reduce battery runtime and service life.
Line-Interactive UPS Technology
Online UPS Technology
Online UPSs provide the highest level of protection by isolating equipment from raw utility power—converting power from AC to DC and back to AC. When input voltage is within preset UPS tolerances, the output is regulated without going to battery. In this manner, the UPS uses the batteries less often and for less time than either standby or line-interactive designs. Many online UPSs allow an even wider input acceptance window when the UPS is below 100% load.
Line-interactive UPSs regulate voltage either by boosting or decreasing utility power as necessary before allowing it to pass to the protected equipment or by resorting to battery power. Line-interactive models typically switch to battery mode with a transfer time of 3-8 milliseconds, which is within acceptable limits for most power supplies. Battery usage is lower than a standby UPS, but still higher than an online model.
www.eaton.com/ibm 1.800.925.4426
3
The basics of voltage, amperes and frequency When discussing and dealing with electricity and electrical products, several terms are used to specify electrical characteristics. Three of the most common are voltage, amperes and frequency. In layman’s terms, volts (V) is a measure of the “pressure” with which electricity moves through a wire/circuit, while amperes or amps (A) is a measure of the “volume.” Volts and amps are often compared to water in a hose, with volts representing the amount of pressure and amps representing the volume. When you turn on a garden hose without a nozzle, there is a lot of water (amps) but not much pressure (volts), but by placing your thumb over the end of the hose, you reduce the quantity (amps) and increase the pressure (volts), so it squirts farther. Applying this analogy to electricity, the number of amps signifies how many electrons are flowing in the wire, while the number of volts characterizes how hard those electrons are being pushed. For an equivalent voltage, a wire carrying more amps needs to be a larger diameter, similar to a fire hose operating at the same pressure as a garden hose will obviously deliver more water. Frequency, on the other hand, is the number of times per second (Hz) that the electrical signal oscillates. Frequency in household voltages may vary based on geographic location, while industrial voltagtes can often be customized to meet specific site requirements. Ensuring that the volts, amps and frequency of connected equipment are compatible with the supply of electricity is much like filling up a car with the appropriate type of fuel. Just as diesel fuel would not power a gasoline-driven car, a 120V, 15A, 60 Hz device cannot be connected to a 240V, 15A, 50 Hz outlet.
4
Eaton Power Protection Handbook: 9910 UPS for IBM Power Systems
Input plugs and receptacleswww.eaton.com/powerquality Any UPS with a rating of 1500 VA or below (P13 and E15) can be plugged into a standard household receptacle/socket. UPS models with ratings higher than 1500 VA use input plugs that cannot be plugged directly into a standard receptacle. The E66 is hardwired directly into the electrical distribution panel at the installation location. This procedure should only be done by a license electrician. Below is a chart to help you visually confirm input and output plug/receptacle options.
9910 UPS model P13
NEMA 5-15P
IEC-320-C20
L6-30P
IEC309 2P+G, 60A
E15 E35 E50
E66
E82
Number of output connections by UPS model
9910 UPS model P13 E15 E35
NEMA 5-15R 6
NEMA L6-20R
NEMA L6-30R
IEC-320-C13
IEC-320-C19
2
2
IEC309 2P+G, 60A
6 2
E50
4
E66
2
E82
4 4
www.eaton.com/ibm 1.800.925.4426
1
5
Frequently asked questions Knowing the answers to the following questions will prepare you for a number of common scenarios involving UPSs. 1.
What happens if the UPS is overloaded? For example, if the protected equipment and/or load draws more current than the UPS can provide. The UPS transfers the load to bypass (for a few minutes) until the overload condition is reversed. If the overload condition continues, the UPS automatically shuts down.
2.
What causes a UPS to be overloaded? There are two possible answers: (1) the UPS was undersized (e.g. the load is rated at 1200 VA but a 1000 VA UPS was provided), or (2) the customer plugs more equipment into the UPS than it was designed to handle.
3.
How do you convert watts to VA? Multiply watts by the power factor 1.3. For example, 1000W x 1.3 = 1300 VA.
4.
How do you convert amps to VA? Multiply amps by voltage (120 volts in the US). 10A x 120V = 1200 VA
5.
How long does it take for the UPS batteries to recharge? On average it takes 10 times the discharge time for the UPS batteries to recover. (A 30-minute battery discharge requires about 300 minutes to recharge.) After each power outage, the recharge process begins immediately. It is important to note that the load is fully protected while the batteries are recharging. However, if the batteries are needed during the recharge time, the holdover time available will be less than it would have been if the batteries were fully charged.
6.
7.
8.
9.
Where can I get technical help? ® Contact your territory representative, call the IBM UPS Hotline at 1-800-925-4426, or visit eaton.com/ibm. What is the average lifespan of the batteries used in the UPS? ® The typical life of batteries in a Eaton UPS with ABM technology is 4 to 6 years. Overall service life depends on a number of factors, including temperature and the number of battery discharges. Does the UPS need to have a load on it to charge its batteries? The UPS should have a minimum of 10% load for UPS to charge its batteries. Once connected to a standard supply of electricity (via input plug or hardwiring), your UPS should charge its batteries regardless of how much load, if any, is attached to it. If my UPS is in storage, how often should I charge the batteries? If a UPS is in storage, we recommend that you plug it in every 6 months to prevent the batteries from becoming fully discharged and significantly shortening their service life. We recommend that you follow the same guidelines for charging external batteries.
10. I came across a spare, unused Eaton UPS that we had in storage. Is it still operable? If the UPS has been in storage for more than 6 months, the
6
batteries inside your UPS may be bad. If your UPS has been in storage without any charge for longer than a year, it’s likely that the batteries need to be replaced. 11. How can you be sure UPS batteries are in good condition in order to insure they have maximum holdover in the event of a power failure? What preventive maintenance procedures should be done and how often should they be done? The batteries used in the UPS and associated battery modules and cabinets are sealed, lead-acid batteries often referred to as maintenance-free batteries. While this type of is sealed and you do not need to check the fluid level in the battery, they do require some attention to assure proper operation. You should inspect the UPS a minimum of once per year by initiating a self-test of the UPS. 12. I already have surge protection. Why do I need a UPS? Surge protection will not keep your business, network or phones operational during a blackout. In addition, surge protectors do nothing to improve the quality of power feeding your sensitive and expensive telecom equipment. The Eaton UPS provides perfect, clean power to your equipment at all times. Over time, poor quality power will degrade your equipment. 13. What’s the difference between a surge protector and a UPS? While surge protection is important, power surge is one of many power anomalies that occur in business every day. In addition to surge protection, a UPS continually regulates incoming voltage and provides battery backup in the event of a power failure. You’ll often see surge protectors plugged into a UPS for added surge protection and additional output receptacles. 14. How much capacity of a UPS should I use? To allow for future expansion, we recommend that you install a UPS at approximately 75% capacity. In addition, the batteries degrade overtime so by over sizing you provide room for error. In the Eaton.com/ibm sizing tool we have included a “capacity used” column. 15. How is battery runtime impacted if I reduce the load on the UPS? There can be a significant increase in runtime. Generally speaking, a UPS that provides 5 minutes at full load will provide 15 minutes at half load. 16. Why is power quality such a problem today? Today’s high-tech IT equipment and control units are much more sensitive to electrical disturbances and are more important to the critical functions of many businesses than in the past. As a result, power quality problems today are more frequent and more costly than ever. 17. Are power quality problems always noticeable? No. In many cases, disturbances can cause imperceptible damage to circuits and other components, a major cause of premature equipment failure and problems like computer lockups. Many power quality problems go unresolved resulting in lost revenue and data.
Eaton Power Protection Handbook: 9910 UPS for IBM Power Systems
Preventing UPS problems The following observations can help you avoid potential problems with the sale and installation of a UPS. Observation #1 alone will protect you from a large percentage of problems. If you have any questions about this information, please contact your IBM consultant for IBM UPS sales. 1.
2.
3.
4.
Always be sure to advise the customer which wall receptacle is required to plug in the UPS. Only UPSs with power ratings up to 1500 VA plug into a standard 15-amp wall outlet. All others require a larger receptacle, which must be installed by an electrician. Things will go more much more smoothly if your customers are not waiting for this to be done after all of their equipment has arrived. Does your customer have the correct set of interconnecting cords? For some applications, it’s as simple as plugging the UPS into the wall socket and plugging the loads into the UPS. However, IBM 9910 applications often require specific interconnecting cords in order to complete installation. We recommend that you make that determination before installation to avoid delays. Be sure that the UPS has enough output receptacles. If the UPS is not equipped with enough output receptacles, you may need to add a PowerPass Distribution Module or choose another UPS. Adding batteries to the UPS provides additional battery runtime only, not added capacity. If a customer adds equipment to the configuration, a higher rated UPS may be needed.
With larger UPS models particularly above 3 kVA and for 3-phase UPS solutions, it is extremely important to make sure that you review that site at which the UPS will be located. Here are a few general guidelines: 5.
Make sure the UPS, batteries, and options will fit in the allocated space. Is there enough room for a technician to service the UPS? Some customers have limited space.
6.
Does the UPS have adequate ventilation? Most UPS models incorporate internal fans to cool the UPS but they need to pull cooler air through the UPS to work effectively. You should not install the UPS in a sealed container or small, sealed room.
7.
Ensure that the UPS can be placed in its final position. Will the UPS components fit through any doors? Are there any stairs?
8.
Is the floor strong enough? The UPS and its battery cabinets can be heavy so make sure that the site has the proper floor loading capacity.
9.
Check to see if there is an adequate electrical supply near the UPS. Compare UPS fuse ratings (amps) and breaker types and whether any electrical work may be needed (i.e. cabling to the UPS terminal block input). The site may have its own electrical contractors.
www.eaton.com/ibm 1.800.925.4426
7
Glossary of power terms The following terms are common when discussing power and UPSs. Familiarizing yourself with these terms will enhance your overall understanding of power protection. Ampere (A or Amp) – The unit of measure for the “rate of flow” of electricity, analogous to “gallons per minute.” VA x 0.7 (power factor) = Watts Alternating Current (AC) – An electric current that reverses its direction at regularly recurring intervals. Arc – Sparking that results when undesirable current flows between two points of differing potential. This may be due to leakage through the intermediate insulation or a leakage path due to contamination. Audible Noise – A measure of the noise emanating from a device at audible frequencies. Backup Time – The amount of time the battery in a UPS is designed to support the load. Blackout – A zero-voltage condition lasting for more than two cycles.
Electromagnetic Interference (EMI) – Electrical interference that can cause equipment to work improperly. EMI can be separated into conducted EMI (interference conducted through cables out of the UPS) and radiated EMI (interference conducted through the air). Ground – A conducting connection, whether intentional or accidental, by which an electric circuit or equipment is connected to the earth, or to some conducting body of relatively large extent that serves in place of the earth. Harmonic – A sinusoidal component of an AC voltage that is multiple of the fundamental waveform frequency. Certain harmonic patterns may cause equipment problems. Harmonic Distortion – Regularly appearing distortion of the sine wave whose frequency is a multiple of the fundamental frequency. Converts the normal sine wave into a complex waveform. Hertz (Hz) – A unit of frequency equal to one cycle per second.
BTU – British Thermal Unit. Used to measure heat dissipation. Energy required to raise one pound of water one degree Fahrenheit. One pound of water at 32 degrees F requires the transfer of 144 BTUs to freeze into solid ice. Brownout – A steady state of low voltage, but not zero voltage. Common Mode Noise – An undesirable voltage that appears between the power conductors and ground. Crest Factor – Usually refers to current. It is the mathematical relationship between RMS current and peak current. A normal resistive load will have a crest factor of 1.4142, which is the normal relationship between peak and RMS current. A typical PC will have a crest factor of 3. Critical Equipment – Equipment such as computers, communications systems or electronic process controls, whose continuous availability is imperative. Direct Current (DC) – An electric current in which the flow of electrons is in one direction, such as supplied by a battery. Double-Conversion – A UPS design in which the primary power path consists of a rectifier and inverter. Double conversion isolates the output power from all input anomalies such as low voltage surges and frequency variations. Downtime – The time during which a functional unit cannot be used because of a fault within the functional unit or within the environment. Electrical Line Noise – Radio frequency interference (RFI), electromagnetic interference (EMI) and other voltage or frequency disturbances.
8
High Voltage Spike – Rapid voltage peak up to 6,000 volts. Hot-Swappable – The ability to change a module without taking the critical load off the UPS. Input Voltage Range – The voltage range within which a UPS operates in “normal” mode and does not require battery power. Inverter – UPS assembly that converts internal DC power to output AC power to run user’s equipment. When the inverter is supporting 100% of the load at all times, as with an online UPS, there is no break from utility power to battery power. System i Server – One of a family of general-purpose systems that supports IBM i5/OS and Operating System 400 and that provides application portability across all models. Kilovolt Ampere (kVA) – An approximation of available power in an AC system that does not take the power factor into account. Line-Interactive – An offline UPS topology in which the system interacts with the utility line in order to regulate the power to the load. Load – The equipment connected to and protected by a UPS. Logical Partition (LPAR) – (1) A set of key or RID pairs in a non-partitioning index that are associated with a particular partition. (2) A subset of a single system that contain resources (processors, memory, and input/output devices). A logical partition operates as an independent system. If hardware requirements are met, multiple logical partitions can exist within a system.
Eaton Power Protection Handbook: 9910 UPS for IBM Power Systems
Glossary of power terms (continued) Maintenance bypass – An external wiring path to which the load can be transferred in order to upgrade or perform service on the UPS without powering down the load. Make-Before-Break – Operational sequence of a switch or relay where the new connection is made prior to disconnecting the existing connection, also soft-load-transfer switching Noise – (1) A disturbance that affects a signal; it can distort the information carried by the signal. (2) Random variations of one or more characteristics of any entity such as voltage, current or data. (3) Loosely, any disturbance tending to interfere with normal operation of a device. Offline – Any UPS that does not fit the definition of online. Line-interactive and standby topologies are offline. Ohm – The unit of measurement for electrical resistance or opposition to current flow. Online – (1) A UPS that provides power to the load from its inverter 100% of the time, regulating BOTH voltage and frequency, usually double conversion topology. Orderly Shutdown – The sequenced shutdown of units comprising a computer system to prevent damage to the system and subsequent corruption or loss of data. Plug-and-Play – An electrical device that does not require extensive setup to operate. Power Factor (PF) – The ratio of real power to apparent power. Watts divided by VA. Most power supplies used in communication and computer equipment have a power factor of 0.7. (PF = 0.7) VA x PF = W W/PF = VA
Redundancy – Duplication or repetition of elements in electronic equipment to provide alternative functional channels in case of failure. Relay Communication – Communication between a UPS and a computer through the opening and closing of solid-state relays which are pre-defined to indicate UPS status. RS-232 – The standard for serial interfaces (serial refers to the eight bits of each character successively sent down one wire) used by most computers, modems and printers; a 25-pin physical interface. Sine Wave – A waveform that represents periodic oscillations of a pure frequency. Single-Phase – Power system with one primary waveform. Standby – UPS technology where power is applied to the load directly from the utility under normal operation, but switched to the inverter and battery for emergency support (offline topology). System p Servers – The IBM server family that uses IBM’s POWER architecture designed for AIX and Linux operating systems. Three-Phase – A power system with three primary voltage waveforms spaced equally (in time) out of phase with each other. Total Harmonic Distortion (THD) – Describes how much the circuit voltage deviates from a perfect sine wave. A poor voltage THD is most often manifested in a “flat topped” waveform that comes from the inability of a power source to respond to the demands of highly non-linear loads. Uninterruptible Power System (UPS) – An electrical system designed to provide instant, transient-free back up power during power failure or fault. Some UPSs also filter and/or regulate utility power (line conditioning).
Power Sag – Low voltage (below nominal 120 volts). Power Server – The most current generation of the IBM System family. Built as an open platform for choice with IBM i, IBM AIX and Linux, Power servers provide solutions for organizations of all sizes that help turn massive volumes of raw data into actionable business insights on a scalable, secure, and resilient system.
Volt/voltage (V) – Electrical pressure that pushes current through a circuit. High voltage in a computer circuit is represented by 1; low (or zero) voltage is represented by 0. Volt Amps (VA) – Voltage x amps. Volts Direct Current (Vdc)
Power Surge – High voltage (above nominal 120 volts).
Volts Alternating Current (Vac)
Rectifier – UPS component that converts incoming AC power to DC power for feeding the inverter and for charging the battery.
Watts (W) – The rate of doing electrical work. W x 1.3 = VA.
Rackmount – Ability to mount an electrical assembly into a standardized rack.
xSeries® Servers – The product name of an IBM eServer product that emphasizes industry-standard server scalability and self-managing server technologies. It is the successor to the Netfinity® family of servers.
www.eaton.com/ibm 1.800.925.4426
9
Commonly-used acronyms When selling power protection solutions, you will likely encounter the following acronyms: ABM
Advanced Battery Management
SAN
Storage Area Network
AC
Alternating Current
THD
Total Harmonic Distortion
BBM
Break-Before-Make (Bypass Switch)
UL
Underwriter’s Laboratory
BDM
Bypass Distribution Module
UPS
Uninterruptible Power System
BTU
British Thermal Unit
USB
Universal Serial Bus
CSA
Canadian Standards Association
VA
Volt Amps
DC
Direct Current
VoIP
Voice Over IP
EBC
Extended Battery Cabinet
WAN
Wide Area Network
EBM
Extended Battery Module
EMEA
Europe, Middle East, Africa
HW
Hardwired
IEEE
Institute of Electrical And Electronics Engineers
IP
Internet Protocol
kVA
Kilovolt ampere
LAN
Local Area Network
MBB
Make-Before-Break (bypass switch)
MTBF
Mean Time Before Failure
MTTR
Mean Time To Repair
NEMA
National Electrical Manufacturers Association
NEC
National Electrical Code
PBX
Private Branch Exchange
PDM
Power Distribution Module
PPDM
PowerPass Distribution Module
PoE
Power Over Ethernet
PUE
Power Usage Efficiency
REPO
Remote Emergency Power-off
RFI
Radio Frequency Interference
RM
Rackmount
RoHS
Restriction of Hazardous Substances
SNMP
Simple Network Management Protocol
10
Eaton Power Protection Handbook: 9910 UPS for IBM Power Systems
How much battery runtime do you need? To meet customer needs of continued operation during power outages, IBM 9910 UPS solutions offer options that can extend battery runtimes beyond 60 minutes. In today's 24x7 business environment, continued availability along with application and safety considerations must be taken into account and estimated when calculating UPS battery runtimes. For example, a typical battery runtime is 15 minutes. The recommended formula used to calculate runtime is: Runtime (calculated in minutes) = business + system application shutdown + safety Example Business needs System (application) shutdown Safety margin Total battery runtime required
= = = =
5 6 4 15
Business needs: Approximately 80% of power outages are less than 5 minutes in duration. Using 5 minutes will ensure that if the typical power outage is less than 5 minutes, the application will not start a premature or unrecoverable shutdown. In the example, 5 minutes is used. System shutdown: The National Power Laboratory Power Quality Report indicates there may be consecutive power outages before power continuity is fully restored. By doubling the system/application time, you allow for two consecutive power outages to occur while providing an adequate reserve of battery runtime to initiate a safe system shutdown during the second power outage. In the example, it takes the application 3 minutes to shut down. Doubling the shutdown time results in 6 minutes. Safety margin: Allows for natural battery charge cycles, temperature variations and aging. Also take into account variations in business needs. In the example, 4 minutes is used. Find the correct UPS model then select the runtime required. If the power consumption of the equipment to be protected is unknown, use the maximum load (Watts) number given for the UPS. For example, if the load requires less than 3,500 Watts and the runtime is 15 minutes, a valid UPS will be the E50 with one Extended Battery Module providing 25 minutes of battery backup (autonomy) runtime at the E50 maximum capacity of 3,500 watts. Note: The runtime is total (standard internal batteries and optional EBMs), not additive.
Battery Runtime in Minutes at Maximum Watts Supported UPS Model P13 E15 E35 E50 E66 E82
Maximum Watts Supported 950 1050 2700 3500 4500 8000
Standard (Internal) Battery 5 7 5 5 8 5
+1 EBM 34 29 22 19 12
+2 EBMs 63 n/a 41 n/a 27
+3 EBMs 88 n/s 62 n/s 35
www.eaton.com/ibm 1.800.925.4426
+4 EBMs 135 n/a 83 n/a 45
EBM Feature Code None 6647 6651 6648 6652 6646
11
UPS software overview
Figure 1. Intelligent Power Manager facilitates easy and versatile monitoring and management of multiple devices, keeping you apprised of power and environmental conditions.
Operating a UPS without power management software is kind of like driving in the rain without windshield wipers—you may be protected from the downpour, but your visibility only lasts for so long. While a UPS protects the attached load during a power outage, power management software is required to ensure that all work-in-progress is saved and sensitive electronic equipment is gracefully shut down if the power outage exceeds battery runtime. Without software, the UPS simply runs until its batteries are depleted and then drops the load. In addition to facilitating automatic, orderly shutdown of all connected devices during an extended outage, power management software delivers a broad spectrum of other advantages. The perfect complement to any UPS solution, management software keeps a constant pulse on network health through its monitoring and management capabilities. Most power management software is shipped with the UPS and is usually available as a free download online as well. Power event notifications are available as audible alarms, pop-up alerts on a monitor, emails to pre-designated recipients based on the condition, text messages, phone calls from our remote monitoring center, and triggers for a multitude of network and building management systems to initiate the orderly shutdown of equipment. Some software offerings are capable of delivering a global view across the network —often from any PC with an Internet browser. Software can also provide a complete log of events and UPS utility data, which is invaluable when debugging a power anomaly. Many power management products have the ability to centralize alarms, organize data by customized views and maintain event logs for preventive maintenance of the entire installed equipment base. The more robust and versatile software offerings are compatible with devices that support a network interface, including all manufacturers’ UPSs, environmental sensors, ePDUs and other devices. Furthermore, power management software enables load segment control for UPS models supporting that feature. Because power protection and management are just as vital for virtual machines as they are for physical servers, new software technologies have been specifically designed to provide monitoring and management capabilities in virtualized environments. Shutdown software is now compatible with VMware’s ESXi and vSphere and Microsoft’s Hyper-V, enabling graceful shutdown of multiple virtual machines. To view an online demonstration of power management software capabilities, please visit www.eaton.com/ibm.
12
Eaton Power Protection Handbook: 9910 UPS for IBM Power Systems
Attributes at a glance Understanding the features of specific IBM UPS models will help you to determine the best device to meet your customers’ needs. For example, some customers will want the option of extending battery runtime, so it is important o be able to identify a UPS offering this attribute.. The following chart summarizes the key information and features of each IBM UPS model.
Attribute
P13
E15
E35
E50
E66
E82
IBM Part Number
39J4809
44V6738
74Y8478
44V7912
74Y8483
44V3918
Vac Input/Output
120
120
208
208
208
220-240
Maximum Output (Watts)
950
1350
2700
3500
4500
8000
Maximum Output (VA)
1400
1500
3000
5000
5000
10000
Level of Protection (Series)
5
9
5
9
5
9
Tower Form Factor
Rackmount Form Factor
Rack Height (U)
3
3
4
6
ABM Technology
Hot-Swappable Batteries
Hot-Swappable Electronics Module Maintenance (Service) Bypass
Load Segments
Extended Battery Module
6647
6651
6648
6652
6646
44V6740
74Y8481
44V7915
74Y8486
44V3921
Communication Card Option
Relay Interface Card
Network Management Card or Relay Serial Card
ConnectUPSMS Web/SNMP
Network Management Card or Relay Serial Card
ConnectUPS Web/SNMP
Communication Card Feature Code
2941
2945 or 2944
2941
2945 or 2944
2934
EBM Feature Code EBM IBM part number
www.eaton.com/ibm 1.800.925.4426
13
IBM 9910 model P13 950 Watt/1400 VA, 120 Vac UPS The IBM 9910 Model P13 offers an ideal, low-cost tower solution to safeguard entry- to mid-level servers.
Features and Benefits Low cost power protection for entry- to mid-level desk side servers Extends battery service life and provides advanced warning of the end of
useful battery life with ABM technology Regulates power fluctuations with Buck and Boost voltage regulation Protects equipment connected by network or phone wiring from ”back door”
power surges with a network transient protector Minimizes downtime with hot-swappable batteries Serial connectivity enhances communication capability Tested and approved by IBM to assure out-of-box usability Backed by a five-year Advanced Element Exchange Warranty (including battery) with IBM as point
of contact
P13 Model Guide Model Number
IBM Number
Power Out (Watts/VA)
Input Connection
Output Connections
Dimensions (HxWxD, in/mm)
Unit Weight (lb/kg)
950/1400
NEMA 5-15P
(6) NEMA 5-15R
7.6 x 5.9 x 15.4/ 193 x 150 x 390
37/16.8
120 Vac1; 50/60 Hz auto-sensing
9910-P13
39J4809
1
120V default, also user-selectable for 110V with rear panel DIP switches.
P13 Battery Runtimes Chart (in Minutes) Load
UPS Internal Batteries
128W/200 VA
58
192W/300 VA
41
320W/500 VA
28
402W/600 VA
19
500W/750 VA
14
603W/900 VA
10
670W/1000 VA
8
804W/1200 VA
6
938W/1400 VA
5
Note: This guide provides typical application information. Battery times are approximate and may vary with equipment, configuration, disk access, battery age, temperature, etc.
14
Eaton Power Protection Handbook: 9910 UPS for IBM Power Systems
P13 Technical Specifications* General Topology
Line-interactive
Power Factor
0.68
Dimensions and Weight
See Model Guide
Network Transient Protector
In and out RJ-11 jack for telephone/modem protection or RJ-45 for 10BaseT network cable; UL497A tested
Electrical Input Nominal Voltage
120 Vac (user selectable to 110 Vac)
Online Voltage Range
±20% for nominal voltage at full load
Nominal Input Frequency
45–65 Hz, 50/60 Hz; auto-sensing
Input Protection
Reset-able circuit breaker
Connection
6-ft cord with NEMA 5-15P
Electrical Output Power Levels
950W/1400 VA
Online Regulation
-10%, +6% of nominal voltage
On Battery Voltage Regulation
±5% of nominal voltage; -10% after low battery warning
On Battery Frequency Regulation
±0.1 Hz of nominal frequency
Voltage Wave Shape
Sine wave (during normal and battery operation)
Connections
(6) NEMA 5-15R
Indicators and Controls Front Panel LEDs
Power on, on battery, overload, and battery fault
Front Panel Buttons
On/off and alarm silence/self-test
Communication Port
DB-9 female (UPS ships with communication cable); USB Interface Adapter is optional
Battery Battery Type
Sealed, maintenance-free lead-acid; starved electrolyte
Battery Description
(3) 12V, 9 Ah
Battery Recharge
<3 hours to 90% capacity
Battery Runtime
See Battery Runtimes table
Start-On-Battery
Startup with UPS batteries in absence of utility power
Environmental and Safety Operating Temperature
0°C to 40°C (32°F to 104°F) UL tested at 25°C (77°F)
Transit/Storage Temp.
-15°C to 55°C (5°F to 131°F)
Relative Humidity
05% to 95% noncondensing
Heat Dissipation
189 BTU/hr, maximum
Audible Noise
<45 dBA typical
Safety Markings
UL, cUL, and CSA
Safety Conformance
UL 1778, CAN/CSA C22.2, No. 107.1
EMC Markings
FCC Class B; 230V models also CE (EN50091-2) and C-Tick
Surge Suppression
ANSI C62.41 Category A (formerly IEEE 587)
Immunity
IEC 801-2, -3, -4
*Due to continuing product improvement programs, specifications subject to change without notice.
www.eaton.com/ibm 1.800.925.4426
15
P13 UPS Rear Panel
What’s included with the P13 UPS 950W /1400 VA, 120V UPS Serial Cable, DB-9 to DB-9 (6 ft/1.8m) AS/400 Interface Cable (6 ft/1.8m) USB Cable, DB-9 to USB (6 ft/1.8m) Eaton 5115 UPS User’s Guide Eaton (9910-P13 and P14) Communication Options for IBM Applications Manual Eaton Software Suite CD Service and Support Manual for IBM Applications
16
Eaton Power Protection Handbook: 9910 UPS for IBM Power Systems
IBM 9910 model E15 1350 Watt/1500 VA, 120 Vac UPS Offering premium performance and a high power factor design, the IBM 9910 Model E15 delivers continuous clean power for high availability and uptime.
Features and Benefits Protects against downtime, data loss and process interruption by
providing continuous, clean power Offers premium performance with a 0.9 power factor and >95 percent efficiency in high efficiency
mode Increases battery service life and system uptime with ABM battery charging technology Enables prolonged runtime of essential equipment during power outages by allowing for orderly,
remote shutdown of non-critical systems or processes Conserves valuable space with a slim tower design Ensures data and system integrity with LanSafe power management software Backed by a five-year Advanced Element Exchange Warranty (including battery) with IBM as point
of contact
E15 Model Guide Model Number
IBM Number
Power Out (Watts/VA)
Input Connection
Output Connections
NEMA 5-15P
(6) NEMA 5-15R
—
—
Dimensions (HxWxD, in/mm)
Unit Weight (lb/kg)
9.1 x 6.3 x 16.9 (230 x 160 x 430)
42/19
9.1 x 6.3 x 16.9 (230 x 160 x 430)
54/24
120 Vac; 50/60 Hz auto-sensing 9910-E15
44V6738
1350/1500
1
Extended Battery Module (EBM) 9910-6647
44V6740
—
1. E15 includes (3) IEC-320-C13 to NEMA 5-15P interconnecting cords.
E15 Battery Runtimes Chart (in Minutes) UPS Internal +1 EBM +2 EBMs +3 EBMs +4 EBMs Batteries 34 63 1050/1500 7 88 135 44 84 788/1125 11 129 210 79 148 525/750 18 207 267 167 278 263/375 38 475 540 Note: This guide provides typical application information. Battery times are approximate and may vary with equipment, configuration, disk access, battery age, temperature, etc. Runtimes are shown at a 0.7 power factor. Load (Watts/VA)
www.eaton.com/ibm 1.800.925.4426
17
E15 Technical Specifications* General User interface
Graphical LCD with blue backlight and text in English, French, German, Russian and
LEDs
Four status-indicating LEDs
Topology
True online, double-conversion
UPS bypass
Automatic bypass
Remote Emergency Power Off (REPO)
Emergency shutdown control through the REPO port
Electrical Input Nominal voltage
120V
Voltage range
60-138 Vac (voltage low level vary according to output load level)
Power draw of UPS
12.5A
Frequency
50/60 Hz
Frequency range
40-70 Hz
Electrical Output Power factor
0.9
On utility voltage regulation
±2% of nominal
On battery voltage regulation
±3% of nominal
Efficiency
>94% in high-efficiency mode; >86% in online mode
Frequency regulation
±2% Hz online, user-configurable
Voltage waveform
Sine wave
Load segments
Two configurable, individually controlled receptacles
Battery Battery type
VRLA 12V/9 Ah (both internal and external)
Battery replacement
Hot-swappable internal and external batteries
Start-on-battery
Allows start of UPS without utility input
Communications Serial port
RS-232 standard, for interface to power management software
USB port
USB HID port/serial/optional LAN Card
Relay output
Common alarm standard
Communication slot
Optional communication slots (BD Slot)
Optional communication cards
SNMP/Web card for direct control and monitoring in SNMP-based networks, monitoring of UPS status and meters through Web browser interface. Relay card for integration to industrial environment and building management systems, remote shutdown for IBM AS/400 systems
Environmental and Safety Safety markings
UL, cUL, VCCI
EMC markings
FCC Class B, EN55022 Class B
Audible noise
<50 dB
Ambient operating temperature
0°C (32°F) to 40°C (104°F)
Storage temperature
-20°C (-4°F) to +40°C (104°F) with batteries and -25°C (-13°F) to +55°C (131°F) without batteries
Relative humidity
5-90% non-condensing
Normal mode: 670 BTU/hr On battery: 1011 BTU/hr *Due to continuing product improvement programs, specifications subject to change without notice. Heat dissipation
18
Eaton Power Protection Handbook: 9910 UPS for IBM Power Systems
E15 UPS Rear Panel
What’s included with the E15 UPS 1350W /1500 VA, 120V UPS Relay Interface Card (1014018) 9406 UPS to AS/400 Communication cable (7.6m/25 ft) (103004349-5501) Relay Interface Card Instructions (1018946) Eaton 9130 (9910-E15/E16) Installation Guide for IBM Applications (164201783) (1) Eaton 9130 UPS (1500 VA) User’s Guide (164201718) (1) Software Suite CD (619-00205-15) (1) USB Cable (1.8m/6 ft) (720-65037-01) (1) RS-232 Cable (1.8m/6 ft) (720-60258-00) (3) C13 to 5-15P Equipment Power Cords, UL and cUL rated, (1.8m/6 ft) (108-00101-01A)
E15 Options Various options are available depending on application.
Description
IBM Feature Code
IBM Part Number
Extended Battery Module (EBM) (up to 4 EBMs)
6647
44V6740
www.eaton.com/ibm 1.800.925.4426
19
IBM 9910 model E35 2700 Watt/3000 VA, 208 Vac UPS Cost-effective UPS lowers the price per watt protected and delivers a robust 2700 watts of power in a space efficient 3U form factor.
Features and Benefits Provides up to 3000 VA/2700 W in only 3U of rack space A 95 percent or greater efficiency rating helps reduce energy usage and costs Intuitive, customizable LCD display in nine languages and bundled intelligent IBM UPS Manager
software enhance control and manageability Hot-swappable batteries for maximum uptime, availability and ease of maintenance Load segments allow for individual control of receptacle groups Integrates with IBM Systems Director Active Energy Manager™
E35 Model Guide Model Number
IBM Number
Power Out (Watts/VA)
Input Connection
Output Connections
Dimensions (HxWxD, in/mm)
Unit Weight (lb/kg) 3
2700/3000
L6-30P2
(2) L6-20R, (2) IEC-320-C19 (2) IEC-320-C13
5 x 17.25 x 20.8/ 127 x 438 x 527
88/40
208 Vac; 50/60 Hz auto-sensing 9910-E351
74Y8478
Extended Battery Module (EBM) 5 x 17.25 x 20.8/ 119/59 127 x 438 x 527 1. Base configuration for the E35 consists of the E35 Accessory Kit (IBM part number 74Y8480) and internal batteries. 2. Input mains connection is an IEC-320-C19 to NEMA L6-30P (Type 11) power cord. 9910-6651
74Y8481
—
—
—
E35 Battery Runtimes Chart (in Minutes) Load in Watts
UPS Internal Batteries
+1 EBM
660 41 153 1403 14 68 2040 10 43 2660 5 29 Note: This guide provides typical application information. Battery times are approximate and may vary with equipment, configuration, disk access, battery age, temperature, etc.
20
Eaton Power Protection Handbook: 9910 UPS for IBM Power Systems
E35 Technical Specifications* General VA/Watts rating
3000 VA/2700 W
Nominal output voltage (Vac) (autosensing at first power-up)
208V
Waveform type
Sine wave
Output connections (All output receptacles are controllable via TwoLoad Groups (segments))
(2) NEMA L6-20R, (2) IEC 320 C19, (2) IEC 320 C19
Nominal output voltage (Vac)
184 - 228V (208V)
Input Nominal input voltage
208V
Input frequency (autosensing)
50/60 Hz +/- 3 Hz
Input connection type
IEC-320-C20 with IEC-320-C19 to NEMA L6-30P (Type 11) power cord
Batteries Typical backup times
14 minutes (at 50% rated W), 5 minutes (at rated W)
Battery type
Valve Regulated Lead Acid (VRLA)—maintenance free, sealed, leak proof
Optional external battery pack
Yes
Typical recharge time
4 hours to 90% charge from a UPS/battery discharge of 50% rated load.
Communications and Management Interface port
USB HID port/serial/optional LAN Card
Management software included
IBM UPS Manager software
Control panel
Intelligent three-button, dual-color, backlit graphical LCD displays vital UPS status in nine languages
Audible alarm
Alarm when on battery: Distinctive low-battery alarm
Remote Power Off (REPO)
REPO port
Surge Protection and Filtering Surge energy rating
2400J
Filtering
ANSI/IEEE C62.41; 1991 CATEGORYB3 (SURGE)
Physical Rack height
3U
Dimensions (HxWxD)
5 x 17.25 x 20.8 in./127 x 438 x 527 mm
Product weight
88 lb/40 kg
Packaging weight
110 lb/ 50 kg
Color
IBM black bezel
Environmental and Safety Audible noise, 1 meter from unit surface
Normal operation at rated load and Battery Discharge Mode <55 dbA For load <70% <50 dbA
Efficiency
95% minimum at full-rated load—normal usage, not during battery recharge
Operating temperature
0°C (32°F) to +40°C (104°F)
Maximum operating altitude
10,000 ft/3048 m
Relative humidity
0-95% noncondensing
Safety markings
UL, cUL; IEC/EN 62040-1-1, IEC/EN 60950-1, TUV CB Report ; CE Mark, TUV CB Report transfer global
EMC markings
208 V FCC Class A, EN55022 Class A; BSMI, CNS14757-2, Class A 230 V: CE (per IEC/EN62040-2:Emissions, Category C2; Immunity, Category C2); VCCI, Class A; C-Tick, AS/NZS 3548, Class A; IEC61000-3-2:2000; IEC61000-3-3: 2004; ICES Canada
* Due to continuing product improvement programs, specifications subject to change without notice.
www.eaton.com/ibm 1.800.925.4426
21
E35 UPS Rear Panel
What’s included with the E35 UPS 2700W/3000 VA, 208V UPS
- 3U cabinet, 298V - Battery - Rail Kit - Shipping bracket Accessory kit (IBM Part Number 74Y8480) consisting of - Documentation CD-ROM - UPS Management Software CD-ROM - 3000 VA UPS and EBM Installation Guide - REACH document - UPS front cover - RS-232 cable - (16) Screws, M5x16 round slotted for rack installation - (2) IEC 320 C13 to C14 jumper cords
E35 Options Various options are available depending on application. Description
22
IBM Feature Code
IBM Part Number
Extended Battery Module (EBM)
6651
74Y8481
EBM Accessory Kit (1 per FC 6652)
-
74Y8487
Network Management Card (NMC)
2945
74Y8489
Relay Serial card
2944
74Y8488
PDU to UPS Power Cord, UTG/ Burndy to IEC-320-C20, 6 ft.
2974
42R4333
IEC-320-C19 to NEMA L6-30P Power Cord
2975
C19 to L6-20P (Type 11) input power cord, 14 ft.
9860
Eaton Power Protection Handbook: 9910 UPS for IBM Power Systems
IBM 9910 model E50 3500 Watt/5000 VA, 208 Vac UPS The IBM 9910 Model E50 not only delivers continuous clean power to protect critical equipment, it does so in a space-saving 3U design.
Features and Benefits Provides clean continuous power to protect critical equipment and applications from power-related
downtime, data loss and corruption, and process interruption Saves valuable rack space by delivering 5000 VA/3500W in only 3U. Rail kits and pedestal included. Offers extended battery runtime options to power essential systems for more than an hour during outage Simplifies UPS monitoring and management with a bright LCD user interface, intuitive LanSafe software Backed by a five-year Advanced Element Exchange Warranty (including battery) with IBM as point of contact
E50 Model Guide Model Number
IBM Number
Power Out (Watts/VA)
Input Connection
Output Connections
Dimensions (HxWxD, in/mm)
Unit Weight (lb/kg)
44V7912
3500/5000
L6-30P
(4) L6-30R
5.14 x 17.5 x 29.2 (130 x 444 x 741)
125.7 (57.0)
5.25 x 17.5 x 29.2 (133 x 444 x 741)
155.4 (77.5)
UPS E50
Extended Battery Module 6648
44V7915
E50 Battery Runtimes Chart (in Minutes) Load UPS Internal +1 EBM +2 EBMs +3 EBMs +4 EBMs (Watts/Load) Batteries 132 232 700/1000 36 332 433 52 95 1400/2000 13 140 184 40 74 2100/3000 10 110 146 29 53 2800/4000 7 80 107 22 41 3500/5000 5 62 83 Note: This guide provides typical application information. Battery times are approximate and may vary with equipment, configuration, disk access, battery age, temperature, etc. Runtimes are shown at a 0.7 power factor.
What’s included with the E50 UPS 3500W /5000 VA, 208V UPS Rail Kit (IBM9136RCKIT) Battery Tray (IBM PN 44V7914) E50 Accessory Kit which includes the following:
-
Software Suite CD (619-00205-151) Eaton 9135 (5000 VA) UPS User’s Guide (164201726) Eaton 9135 (9910-E50) Installation Guide for IBM Applications (164201784) (4) Pedestals (3312123900) RS-232 Cable (6 ft/1.8m) (3080432001) ConnectUPS-MS Web/SNMP Card Communication Cable 673807 AS/400 (8 ft/2.4m) (3081324500)
www.eaton.com/ibm 1.800.925.4426
23
E50 UPS Rear Panel
E50 Options Various options are available depending on application.
IBM Feature Code 2941 2972 2973 6648 1420 1421
24
IBM Part Number 44V7917 25R2555 42R4331 44V7915
Description ConnectUPS-MS Web/SNMP Card PDU to UPS Power Cord (14 ft/4.3m) PDU to UPS Power (4 ft/1.2m) Extended Battery Module (EBM) L6-30R to L6-30P (Type 12) input power cord, 14 ft. L6-30R to L6-30P (Type 12) input power cord, 6 ft.
1422
L6-30R to Russell Stoll RS3750 (Type 40) input power cord, 6 ft.
1423
L6-30R to Russell Stoll RS3750 (Type 40) input power cord, 14 ft. For Europe and Latin America.
Eaton Power Protection Handbook: 9910 UPS for IBM Power Systems
Quantity Min: 0, Max: 1 Min: 0, Max: 4 Min: 0, Max: 4 Min: 0, Max: 4
E50 Technical Specifications* General User interface
Graphical LCD with blue backlight and text in English, French, German, Portuguese, Italian and Spanish
LEDs
Four status-indicating LEDs
Topology
True online, double-conversion
Diagnostics
Full system self-test
UPS bypass
Automatic bypass
Electrical Input Nominal voltage
208V; 200V, 208V, 220V, 230V, 240V and 250V user-selectable
Voltage range
156-280 Vac (output PF 0.7)
Power draw of UPS
24.0A
Recommended input breaker rating
NA: 30A ; EMEA: 32A
Frequency
50/60 Hz
Frequency range
40-70 Hz
Electrical Output Power factor
0.7
On utility voltage regulation
±2% of nominal
On battery voltage regulation
±2% of nominal
Efficiency
>97% in high-efficiency mode; 91% in online mode
Frequency regulation
±3% Hz online
Load crest factor
3 to 1
Voltage waveform
Sine wave
Battery Internal Battery Type
5.5 Ah, sealed, lead-acid; maintenance free
External Battery Modules
Up to four per E50, rail kits included for rackmounting
EBM battery type
5.5 Ah, sealed, lead-acid; maintenance free
Battery runtime
Four minutes with internal batteries @ 100% load (0.7 PF)
Battery recharge time
Six hours to recover 90% of nominal backup time after 100% RCD load discharge
Battery replacement
Hot-swappable internal and external batteries
Start-on-battery
Allows start of UPS without utility input
Communications Serial port
RS-232 standard, RS-232 cable provided
USB port
HID standard
Relay output
DB-9 dry contact – common alarm standard
Communications slot
Optional communication slots (Mini X- Slot)
Software
LanSafe UPS monitoring and management software
Environmental Safety markings
CE, C-Tick, UL, GS
EMC markings
FCC-A, VCCI-A, BSMI-A, C-Tick, CE Compliance
Audible noise
Max 46 dB
Ambient operating temperature
0°C (32°F) to 40°C (104°F)
Storage temperature
-20°C (-4°F) to +40°C (104°F) with batteries and -25°C (-13°F) to +55°C (131°F) without batteries
Relative humidity
5-90% non-condensing
Heat dissipation
Normal mode: 1150 BTU/hr at 91% efficiency; Battery: 1650 BTU/hr at 86% efficiency; High efficiency: 370 BTU/hr at 97% efficiency
*Due to continuing program improvements, specifications are subject to change without notice.
www.eaton.com/ibm 1.800.925.4426
25
IBM 9910 model E66 4500 Watt/5000 VA, 208 Vac UPS High-efficiency protection delivers more real power in space-saving design.
Features and Benefits Provides up to 5000 VA/4500 W in only 4U of rack space A 95 percent or greater efficiency rating helps reduce energy usage and costs Intuitive, customizable LCD display in nine languages and bundled intelligent IBM UPS Manager
software enhance control and manageability Hot-swappable batteries for maximum uptime, availability and ease of maintenance Load segments allow for individual control of receptacle groups Integrates with IBM Systems Director Active Energy Manager™
E66 Model Guide Model Number
IBM Number
Power Out (Watts/VA)
Input Connection
Output Connections
Dimensions (HxWxD, in/mm)
Unit Weight (lb/kg) 3
4500/5000
L6-30P
(2) L6-30R, (4) IEC-320-C19
7 x 17.25 x 31/ 178.5 x 438 x 790
159/72
208 Vac; 50/60 Hz auto-sensing 9910-E661
74Y8483
Extended Battery Module (EBM) 5.25 x 17.25 x 28/ 127 x 438 x 706 1. Base configuration for the E66 consists of the E66 Accessory Kit (IBM p/n 74Y8485) and internal batteries. 9910-6652
74Y8486
—
—
—
119/59
E66 Battery Runtimes Chart (in Minutes) Load in Watts
UPS Internal Batteries
+1 EBM
1125 51 112 2250 21 51 3375 12 31 4500 8 19 Note: This guide provides typical application information. Battery times are approximate and may vary with equipment, configuration, disk access, battery age, temperature, etc.
26
Eaton Power Protection Handbook: 9910 UPS for IBM Power Systems
E66 Technical Specifications* General VA/Watts rating
5000 VA/4500 W
Nominal output voltage (Vac) (autosensing at first power-up)
208V
Waveform type
Sine wave
Output connections (All output receptacles are controllable via TwoLoad Groups (segments))
(2) NEMA L6-30R (4) IEC 320 C19
Nominal output voltage (Vac)
184 - 228V (208V)
Input Nominal input voltage
208V
Input frequency (autosensing)
50/60 Hz +/- 3 Hz
Input connection type
L6-30P power cord
Batteries Typical backup times
21 minutes (at 50% rated W), 8 minutes (at rated W)
Battery type
Valve Regulated Lead Acid (VRLA)—maintenance free, sealed, leak proof
Optional external battery pack
Yes
Typical recharge time
4 hours to 90% charge from a UPS/battery discharge of 50% rated load.
Communications and Management Interface port
USB HID port/serial/optional LAN Card
Management software included
IBM UPS Manager software
Control panel
Intelligent three-button, dual-color, backlit graphical LCD displays vital UPS status in nine languages
Audible alarm
Alarm when on battery: Distinctive low-battery alarm
Remote Power Off (REPO)
REPO port
Surge Protection and Filtering Surge energy rating
1300J
Filtering
ANSI/IEEE C62.41; 1991 CATEGORYB3 (SURGE)
Physical Rack height
4U
Dimensions (HxWxD)
7 x 17.25 x 31 in./178.5 x 438 x 790 mm
Product weight
159 lb/72 kg
Packaging weight
183 lb/ 83 kg
Color
IBM black bezel
Environmental and Safety Audible noise, 1 meter from unit surface
Normal operation at rated load and Battery Discharge Mode <55 dbA For load <70% <50 dbA
Efficiency
95% minimum at full-rated load—normal usage, not during battery recharge
Operating temperature
0°C (32°F) to +40°C (104°F)
Maximum operating altitude
10,000 ft/3048 m
Relative humidity
0-95% noncondensing
Safety markings
UL, cUL; IEC/EN 62040-1-1, IEC/EN 60950-1, TUV CB Report ; CE Mark, TUV CB Report transfer global
EMC markings
208 V FCC Class A, EN55022 Class A; BSMI, CNS14757-2, Class A 230 V: CE (per IEC/EN62040-2:Emissions, Category C2; Immunity, Category C2); VCCI, Class A; C-Tick, AS/NZS 3548, Class A; IEC61000-3-2:2000; IEC61000-3-3: 2004; ICES Canada
* Due to continuing product improvement programs, specifications subject to change without notice.
www.eaton.com/ibm 1.800.925.4426
27
E66 UPS Rear Panel
What’s included with the E66 UPS 4500W/5000 VA, 208V UPS
- 4U cabinet, 298V - Battery - Rail Kit - Shipping bracket Accessory kit (IBM Part Number 74Y8485) consisting of - Documentation CD0-ROM - UPS Management Software CD-ROM - 6000 VA UPS and EBM Installation Guide - REACH document - UPS upper front cover (with LCD opening) - UPS lower front cover - RS-232 cable - (16) Screws, M5x16 round slotted for rack installation - (2) IEC 320 C13 to C14 jumper cords
E66 Options Various options are available depending on application. Description
28
IBM Feature Code
IBM Part Number
Extended Battery Module (EBM)
6652
74Y8486
EBM Accessory Kit (1 per FC 6652)
-
74Y8487
Network Management Card (NMC)
2945
74Y8489
Relay Serial card
2944
74Y8488
PDU to UPS Power Cord, UTG/ Burndy to IEC-320-C20, 6 ft.
2974
42R4333
Eaton Power Protection Handbook: 9910 UPS for IBM Power Systems
IBM 9910 model E82 8000 Watt/10000 VA, 208-240 Vac UPS The IBM 9910 Model E82 provides ideal protection for dense and blade environments, offering a high-power, low-profile design.
Features and Benefits High power, low profile design ideal for dense Power Servers or Blades Supports multiple PDUs (1–5 PDUs in a non-redundant power configuration and 2-10 PDUs in a
dual-redundant power configuration) Maximizes 60A input (mains) power connection capacity by providing 8000
watts of output power Optional interface/communication cards expand control of application Tested and approved by IBM to assure out-of-box usability Backed by a five-year Advanced Element Exchange Warranty (including battery) with IBM as point
of contact
E82 Model Guide Model Number
IBM Number
Power Out (Watts/VA)
Input Connec-tion2
Output Connections
Dimensions (HxWxD, in/mm)
Unit Weight (lb/kg) 3
IEC309 2P+G 60A
(1) IEC309 2P+G 60A, (4) IEC-320-C19
10.5 x 17.2 x 30/ 266 x 437 x 762
254/115
200-240 Vac; 50/60 Hz auto-sensing 9910-E821
44V3918
8000/10000
Extended Battery Module (EBM) 5.25 x 17.2 x 23.9/ 179/81 133.5 x 437 x 607 1. Base configuration for the E82 consists of the E82/E83 Accessory Kit (IBM p/n 44V3919) and four UPS Internal Battery Trays (IBM p/n 44V3920). 2. Input power cord is 9.9ft/3m. 3. Weight includes batteries. 9910-6646
44V3921
—
—
—
E82 Battery Runtimes Chart (in Minutes) UPS Internal +1 EBM +2 EBMs +3 EBMs +4 EBMs Batteries 1000 80 137 189 275 365 2000 31 61 99 138 181 3000 18 38 68 92 121 4000 12 27 52 69 90 5000 9 21 42 55 72 6000 7 17 35 46 60 7000 6 14 31 40 51 8000 5 12 27 35 45 Note: This guide provides typical application information. Battery times are approximate and may vary with equipment, configuration, disk access, battery age, temperature, etc. Load in Watts
www.eaton.com/ibm 1.800.925.4426
29
E82 Rear Panel
What’s included with the E82 UPS 8000W/10000 VA, 208V nominal, optional 200–240V UPS (4) Battery Trays (IBM Part Number 44V3920) (Internal) Accessory Kit (no IBM PN)
- Mounting Brackets front and rear - Rails (left, right) and hardware (External) Accessory kit (IBM Part Number 44V3919) consisting of: - Eaton 9140 (9910 E82 & E83) Installation Guide for IBM Applications - User’s Guide CD (in Nine languages) - Eaton Software Suite CD - Serial Cable, RJ-45 to DB-9 (6 ft/1.8m) - Serial Cable, DB-9 to DB-9 (12 ft/3.6m) - REPO Connector Plug 10A, 2-pin
E82 Options Various options are available depending on application.
IBM Part Number
POWER (AIX, Linux), System p Rack Worldwide
POWER (IBM i), System i Rack Worldwide
Description
IBM Feature Code
ConnectUPS-X Web/SNMP Card
2934
1
39J4824
Yes
No
X-Slot Relay/Serial Card Kit
2939
1
42R4332
No
Yes
Extended Battery Module (EBM) (up to 4 EBMs)
6646
44V3921
Yes
Yes
EBM Accessory Kit (1 per FC 6646)
-
44V3922
Yes
Yes
PDU to UPS Power Cord, UTG/ Burndy to IEC-320-C20, 6 ft.
2974
42R4333
Yes
Yes
RS/6000 Rack
7015
Yes
No
AS/400 iSeries Expansion Unit
7117
No
Yes
2
1. Maximum one FC 2934 or 2939 per E82 UPS. ConnectUPS-X Web/SNMP Card required if implementing Logical Partitions (LPARs) on POWER Systems (AIX or Linux), p5 or System p. 2. Used to connect a 7188/9188/5889/7109 PDU to the C19 outlet.
30
Eaton Power Protection Handbook: 9910 UPS for IBM Power Systems
E82 Technical Specifications* General Battery Module Replacement
Yes, hot-swap
Diagnostics
Full system self-test on power up
UPS Bypass
Internal bypass
Dimensions and Weight
See Model Guide
Electrical Input Nominal Voltage
208 default, optional; 200, 220, 230, and 240 Vac
Input Voltage Ranges
200/208; 160–253V, 220/230/240; 174-288V
Frequency
50/60 Hz, auto-sensing
Frequency Range
45-65Hz
Default Frequency
60Hz
Maximum Input Current at Nominal Utility Voltage
48A
Noise Filtering
MOVs and line filter for normal and common mode noise
Connections
9.9ft/3-meter IEC309 2P+G 60A (360P6W) power cord
Input Power Factor
>0.99
Input Mode
Single-phase with input power cord. Three-phase input available when input power cord removed.
Electrical Output Regulation
Nominal Outputs
Output Overload
Voltage Waveform Output Receptacles
Nominal output voltage +/- 2% Static, +/- 10% Dynamic 200/208/220/230/240 (voltage configurable or auto-sensing) 45/48/45/43/41A 9/10/10/10/10 kVA 7.2/8/8/8/8 kW 100-110%: Activates Overload alarm 110-130%: load transfers to Bypass mode after 1 minute 130-150%: load transfers to Bypass mode after 1 second >150%: load transfers to Bypass mode after 100 ms Normal mode: Sine wave; <3% THD with linear load; <5% with nonlinear load (4) IEC-320-C19, 16A (1) IEC309 2P+G 60A (360C6W)
Battery Battery Type
Sealed, maintenance-free, valve-regulated, lead-acid
Monitoring
Advanced monitoring for earlier failure detection and warning
Configuration
(32) 12V, 5 Ah
Battery Runtime
See Battery Runtime Chart
Battery Replacement
Hot-swappable UPS internal batteries and external batteries modules
Charging (in minutes) to 80% usable capacity at nominal line voltage after full load discharge
UPS Internal Batts 266
Start-On-Battery
Allows start of UPS without utility input
+1 EBM 336
+2 EBMs 368
+3 EBMs 398
+4 EBM 419
Communications User Interface
Front control panel, with two-line graphical LCD with backlight
Languages
User selectable
Audible Alarms
For various UPS alarm conditions, including: On Battery, Low Battery, Overload, and UPS Fault
REPO Port
Meets NEC code 645-11 intent and UL requirements
Communication Ports
Native USB and serial port (DB-9)
X-Slot Interface
Empty; other X-Slot options available
Cable
Two (2) 6-ft communication cables (DB-9 to DB-9 and RJ-45 to DB-9) included
Power Management Software
Eaton Software Suite CD-ROM (bundled with UPS)
www.eaton.com/ibm 1.800.925.4426
31
Environmental and Safety Operating Temperature
0 to 40°C (32 to 104°F)
Storage Temperature
-20 to 50°C (-4 to 122°F)
Relative Humidity
0% to 95% noncondensing
Heat Dissipation
2066 BTU/hr (605.5W) maximum
Lightning & Surge Protection
ANSI/IEEE C62.41 (IEEE 587), IEC61000-4-5
Surge Energy Rating
High-energy 6500A peak
Audible Noise
<55 dBA at 5 feet with battery fully charged, without horn
Altitude
3000m (10,000 ft) without derating
Leakage Current
<3.5 mA
Surge Suppression
ANSI C62.41 Category B3
Safety Certifications
UL 1778; CSA C22.2, No. 107.3; EN and IEC 62040-2; NOM-019-SCFI-1993;
Agency Markings
cULus, cUL, NOM, CE
EMC Compliance
FCC Part 15, EN 50091-2, ICES-003
Seismic
Uniform Building Code (UBC) and Bellcore for Zone 4 Earthquake
*Due to continuing product improvement programs, specifications subject to change without notice.
32
Eaton Power Protection Handbook: 9910 UPS for IBM Power Systems
Power Cords Consult the table below for country-specific and region-specific input power cords.
Power Cord Feature Code
Description
For use with UPS Model
Order Through
9910-2975
C19 to L6-30P (Type 12) input power cord, 6 ft.
E35 with Power Server
Factory or MES
9910-2976
C19 to IEC 309 (P+N+G) 32A (Type 46) input power cord, 4.3m.
E35 with Power Server
Factory or MES
9910-9860
C19 to L6-20P (Type 11) input power cord, 14 ft.
E35 with Power Server
Factory or MES
9910-9866
C19 to CEE 7 VII 16A (Type 18) input power cord, 4.3 m.
E35 with Power Server
Factory or MES
9910-9867
C19 to SABS 16416A (Type 22) input power cord, 4.3 m.
E35 with Power Server
Factory or MES
9910-9868
C19 to CEI 23-16 16A (Type 25) input power cord, 4.3 m.
E35 with Power Server
Factory or MES
9910-9871
C19 to IEC 309 (P+N+G) 16A (Type 46) input power cord, 4.3m.
E35 with Power Server
Factory or MES
9910-9872
C19 to SII 32-1971 16A (Type 32) input power cord, 4.3m.
E35 with Power Server
Factory or MES
9910-9874
C19 to SAA-AS 3112 16A (Type 54) input power cord, 4.3m.
E35 with Power Server
Factory or MES
9910-9875
C19 to IEC 60083-A5 16A (Type 64) input power cord, 4.3m.
E35 with Power Server
Factory or MES
9910-1420
L6-30R to L6-30P (Type 12) input power cord, 14 ft.
E50 with Power Server
Factory or MES
9910-1421
L6-30R to L6-30P (Type 12) input power cord, 6 ft.
E50 with Power Server
Factory or MES
E50 with Power Server
Factory or MES
E50 with Power Server
Factory or MES
E50 with Power Server
Factory or MES
9910-1422 9910-1423 9910-1424
L6-30R to Russell Stoll RS3750 (Type 40) input power cord, 6 ft. L6-30R to Russell Stoll RS3750 (Type 40) input power cord, 14 ft. For Europe and Latin America. L6-30R to IEC 309 (P+N+G) 32A (Type 46) input power cord, 4.3m.
9910-1426
L6-30R to PDL Australia 30A (Type PDL) input power cord, 4.3m.
E50 with Power Server
Factory or MES
9910-1427
L6-30R to PDL New Zealand 30A (Type PDL) input power cord, 4.3m.
E50 with Power Server
Factory or MES
www.eaton.com/ibm 1.800.925.4426
33
Software and connectivity Power management software unifies and centralizes UPS management Bundled with every IBM 9910 UPS, UPS power management software gives you all the tools you need to manage power devices in your physical or virtual environment. This innovative software solutions ensures system uptime and data integrity by allowing you to monitor, manage and control the devices on your network remotely. IBM offers two levels of software. Use each software independently or as a powerful combination. Together with your IBM UPS, they provide end-to-end power management for maximum uptime and data integrity: Intelligent Power Manager: software for extensive monitoring and management Supervisory software lets you monitor and manage multiple power and environmental devices across the network from a single interface, giving you up-to-the-minute information on the status of power in your network. It also works seamlessly with VMware’s vCenter Server™ and vMotion™ as well as other platforms and migration applications. Intelligent Power Protector: shutdown software for extended power outages Protection software provides graceful, automatic shutdown of network devices during a prolonged power disruption, preventing data loss and saving work-in-progress. As part of Eaton’s power network management system, these two applications work together to deliver comprehensive power management and protection. Seamlessly integrate UPSs into the IBM Management Console with Eaton Extensions for IBM Active Energy Manager Eaton Extensions allow administrators to monitor UPSs in the network, in real-time and obtain advance notice on critical elements of server power management, such as UPS battery status, load level, temperature and alarms for battery replacement. Monitor, diagnose, configure, set alarms, schedule selftests, check battery, gather inventory information, and control Eaton UPSs network wide from a single console within IBM AEM. Connectivity options offer maximum flexibility Connectivity options are available to suit nearly any communication requirement. Eaton UPSs are equipped with an RS-232 serial communication port, some with built-in USB port to interface with power management software. You can customize your UPS by adding any of the following X-Slot interface options for other types of communication: Network Management Card (FC2945) allows the E35 or E66 UPS to directly connect to the Ethernet network and the Internet, supporting real-time monitoring and control of UPSs across the network via a standard Web browser, SNMPcompliant network management system or power management software.
Relay Serial Card (FC2944) for use with E35 or E66 UPS, provides a simple way to remotely deliver UPS information to an alarm system, PLC or computer system via dry contacts, or it can be an RS-232 interface for connection to a PC or a UPS control display unit. ConnectUPS Web/SNMP Interface Card (FC 2934) enables direct control and monitoring in SNMP-based networks, plus the ability to monitor UPS status and meters through a Web browser (includes built-in switch hub). Use with IBM POWER Systems (AIX, Linux), p5/System p server, OpenPower, or xSeries server with virtualization LPARs and/or Network (Web server) connection (UPS as a node).
Relay-Serial Card and Cable Kit (FC 2939) provides DB-9 and DB-25 serial interface between the UPS and IBM POWER Systems (IBM i (i5/OS)), System i (AS/400) server and Serial Server (Microsoft Windows, Linux, AIX, or other operating systems).
ConnectUPS-MS Web/SNMP Card (2941) is designed for the rigorous task of managing the 9910-E50 UPS that protects equipment and the critical data residing throughout the network
34
Eaton Power Protection Handbook: 9910 UPS for IBM Power Systems
Service and support In the United States and Canada, call 1-800-IBMSERV (1-800-426-7378). In Europe, the Middle East, and Africa (EMEA); Latin America; or Asia-Pacific, call the IBM office that services your account. Please have your serial, model, and part number ready when you call (see Figure 1).
Figure 1. Example of IBM front and rear panel labels
www.eaton.com/ibm 1.800.925.4426
35
For more information, please visit
www.eaton.com/IBM
Eaton Electrical Sector 1000 Eaton Boulevard Cleveland, OH 44122 USA Eaton.com ©2013 Eaton Corporation All RightsReserved 9910HBNA / TN August 2013
Eaton, Intelligent Power, Powerware, ABM, LanSafe, ConnectUPS, and X-Slot are trade names, trademarks and/or service marks of Eaton Corporation or its subsidiaries and affiliates. All other trademarks are property of their respective owners.