Power Support System Installation Instructions I.
Model Numbers
III. Mechanical Drawings
Maximum Maximum System System Battery AC Input Voltage Current Capacity Current
XFMR Voltage
Battery Storage in Cabinet
Item Number
Model Number
01644
PLS-12050-B04-CE
12VDC
5.0A
50Ah
1.25A
17.5VAC
34Ah Max
01647
PLS-24050-B04-CE
24VDC
5.0A
50Ah
2.5A
28.2VAC
17Ah Max
II.
45.7
All dimensions are in centimeters 7.62 2 PLCS
KEY LOCK
30.5 2 PLCS
4.93 TYP
Installation Instructions 38.6
1. Mount cabinet per mechanical dimensions and knockout locations given in Section III. 2. Connect 240VAC, 50Hz., single phase to the black and white leads of the transformer in accordance with local codes. 3. Low Volt AC Input - Connected to secondary winding of the transformer. v Fused at 15 Amps (Fuse Type AGC-15) 4. Verify output voltage at "DC Output" and "Battery" terminals. 12V system measures approximately 13.8VDC. 24V system measures approximately 27.6VDC. 5. Connect battery set to "Battery" terminals. CAUTION: Observe polarity; incorrect polarity will destroy battery fuse. Fused at 15 Amps (Fuse Type AGC-15). Recommended battery type - Power Sonic (PS Series) or YUASA (NP Series) lead acid/gel cell. WARNING: For continued protection against fire hazard, replace only with the same type and rating of fuse.
0
0
3.81 46.2
11.0
30.5 2 PLCS 35.4
6. Connect "System DC" to input of user system. System DC Outputs are Class 2 Power Limited CAUTION: Observe polarity; incorrect polarity may damage user system. Refer to Section I for Maximum Allowable System Curent. Individual outputs PTC protected: Rated at 2.5 Amps each Output 7. Visual Indicators: AC Presence LED1: Green LED System OK LED2: Green LED Tripped PTC LED3, 4: Yellow LED 8. Connect "Fault Output" to system fault annunciation. Form "C" Relay Contacts rated at 1 Amp @ 24VDC Resistive. Relay Contacts labeled in the non-operational (fault) condition. Fail-safe; active until an actual fault condition. 9. Fault Conditions: Low AC / No AC / Blown AC Fuse / High or Low Battery / Blown Battery Fuse CAUTION: Fault condition reporting may be delayed dependent on power supply loading. The battery set is NOT supervised for presence. 10. Power Supply System Draw (No AC, No load) is 50mA.
0 2.54
IV.
22.9
43.2
Typical Hook-up Diagrams AC FUSE AGC-15
FAULT LED
STEP-DOWN TRANSFORMER
NO
TROUBLE CONTACTS
AC ON LED
NC C
FAULT LED
+ -
SYSTEM DC OUTPUT POWER LIMITED VERSION SHOWN
+ -
SYSTEM DC OUTPUT POWER LIMITED VERSION SHOWN
PRIMARY LEADS BLACK
WHITE
BATTERY CONNECTION
+ -
SYS OK LED
BATT FUSE AGC-15
PRIMARY AC CONNECT
AlarmSaf
65A Industrial Way Wilmington, MA USA 01887-3499 (978) 658-6717 FAX: (978) 658-8638 Web Site: www.alarmsaf.com
52-009I 032697
Power Support System Installation Instructions V.
Battery Standby Charts:
VI.
Battery Capacity
24 Hr. Standby*
60 Hr. Standby*
4 Hr. Standby
4 Ah
.109A
.043A
7 Ah
.215A
.086A
.549A
8 Ah
.250A
.100A
.814A
12 Ah
.401A
.160A
1.71A
14 Ah
.471A
.188A
2.03A
15 Ah
.507A
.203A
2.19A
16 Ah
.543A
.216A
2.35A
20 Ah
.684A
.273A
2.99A
26 Ah
.896A
.358A
3.96A
30 Ah
1.03A
.415A
4.50A
33 Ah
1.14A
.458A
5.00A
40 Ah
1.39A
.557A
5.00A
50 Ah
1.74A
.698A
5.00A
Troubleshooting Guide
Fault Output { Form "C" Relay Contacts rated 1 Amp @ 24VDC { Relay Contacts labeled in the non-operational (fault) condition { Fail-safe; active until an actual fault condition. Visual Indicators 1. AC Presence LED1: Green LED 2. System OK LED2: Green LED 3. Blown PD Fuse LED3, 4: Yellow LED
VII
Troubleshooting Chart Symptoms
1) Green "SYS OK" LED is off. Relay Contacts transfer to NC.
2) Green "AC ON" LED is not illuminated.
* 5 Minute 5.0A Ringoff Included
3) Incorrect output voltage
BATTERY CONFIGURATIONS 12 Volt Configuration
24 Volt Configuration
-
+
+
-
12 Volt Battery
-
+
12 Volt Battery
-
+
12 Volt Battery
-
+
12 Volt Battery
Possible Cause
Correction Procedure
Low AC / No AC / Blown AC fuse.
See Symptom 2.
Low or High output.
See Symptom 3.
Blown battery fuse.
See Symptom 4.
Loss of AC power.
Check AC primary supply.
Blown AC fuse.
Remove primary power and batteries, then replace fuse. CAUTION.
Loss of transformer (xfmr) power.
Check xfmr secondary voltage at PC board "Low Voltage AC Connection". If voltage is not present, replace xfmr.
Defective battery.
Check battery condition and replace if needed.
The system load is greater than the supply capability.
Remove system load and batteries; check system output voltage. If OK recheck system requirements, and/or measure output current draw with an ammeter.
Incorrect battery hook-up.
Rewire battery set.
Incorrect or defective Measure xfmr secondary voltage. If not within xfmr. proper range, replace transformer. 4) No battery back-up
+
Fault Conditions { "SYS OK" Green LED extinguishes on: 1. Low AC / No AC / Blown AC Fuse 2. Low / High Battery or Output 3. Blown Battery Fuse 4. Blown Output PD Fuse
5) No relay transfer on fault
Blown battery fuse.
Remove primary power and batteries, then replace fuse. CAUTION. Observe polarity.
Incorrect battery hook-up.
Rewire battery set.
Defective board
Replace PC Board.
For further assistance, please contact the AlarmSaf Technical Service Department.