Power adapter design for seamless interface of low voltage DC equipment to 400V DC distribution Maurizio Salato, VICOR BJ Sonnenberg, Dustin J Becker, EMERSON Network Power David E. Geary, UNIVERSAL Electric Corporation / StarLine DC Solutions
Table of content • • • • •
Power Adapter Characteristics of Interest Telco site evolution options Existing sites transition to 400V DC Implications of power conversion location Power Components for 380V Adapter and the Equalizer concept • Architectural Matrixes • System safety and Harmonics considerations • Conclusions
Power Adapter Characteristics of Interest • Location in the power stream: – – – –
The power drop box (busway or cable) The rack power strip 1U space “power shelf” within the rack Plug‐in unit at “blade” level
• Electrical function and power conversion topologies • Battery backup “equalization” • Safety and protections • Harmonics
Telco site evolution options Today
Next Step Facility AC Loads
Utility Gen
Critical AC Loads
AC UPS Batt
-48V DC Power System
AC
-48VDC Batt
Facility AC Loads
.
DC
Critical 48V DC Loads
Facility DC Loads
AC DC
Many Transition Paths Possible
Utility Gen
●
380V DC 400V DC Power System
Batt
Paths forward with 400V DC for larger core sites: 1. 2. 3.
Greenfield with 400V loads (bulk or distributed 400V) Retrofit/expand -48V loads with 400V main plant (bulk) Greenfield with bulk 400V to distributed 400V/-48V
Local Generation Source
DC DC
Critical AC Loads Critical 400V DC Loads Critical -48V DC Loads
Existing sites transition to 400V DC 48V DC bulk equipment 380VDC cabling or bus way 48VDC cabling
380VDC System
380/48VDC Conversion + Secondary Distribution
48VDC Equipment Rack
380VDC Equipment Rack
The main power distribution from a 400V DC system is built with 400V DC bus way or cabling, directly to 400V DC enabled loads. For loads requiring 48V DC inputs, a bulk 400V‐48V DC conversion replaces the “secondary distribution bay” and is located close to the loads to eliminate long 48V DC cable runs.
Existing sites transition to 400V DC 48V DC rack mounted equipment The 400V DC distribution is extended close to the powered rack . The options for location of the 400V‐48V DC conversion depend on the type of feeder used (bus‐way or cabling) and distribution inside the rack. Due to the relatively low power density of 48V DC powered racks, the conversion section is compact and can be located in a bus way plug‐in box, a junction box on top of rack, inside the power strip itself or in a rack mounted shelf
Implications of power conversion location 380V busway
Adapter output supplies
Rack units management
System availability / redundancy
Busway or wire drop‐box Entire rack
Un‐qualified operator (SELV)
Fair (rack to rack)
Location
Rack
Rack power shelf
Groups of units
Un‐qualified operator (SELV)
Medium (group to group)
Individual unit adapter
Single unit
Qualified operator (AC, 400V DC)
Maximum (unit to unit)
Power Components for 380V Adapter I
SAC
V
32·I
I
V/32
SAC
V
8·I V/8
K=1/32
K=1/8
BC K=1/32: high voltage bus converter, 260‐400V input, 32:1 ratio, 8‐12.5V output
BC K=1/8: high voltage bus converter, 260‐400V input, 8:1 ratio, 32‐50V output
ZVS BO
ZVS BU
ZVS BB
ZVS BO: Zero Voltage Switching Boost regulator, 8V min. input, 55V max. output
ZVS BU: Zero Voltage Switching Buck regulator, 55V max. input, 8V min. output
ZVS BB: Zero Voltage Switching Buck‐Boost regulator, 32‐55V input, 20‐55V output
The Equalizer Concept
•
Compliance to ETSI EN 300 132‐3‐1
•
Regulate ONLY if voltage falls below normal operating range (365 V ± 15 V)
•
96%98% efficiency under normal operating conditions
•
SELV Output
380V to 12V power components matrix Power distribution
12V Loads
Source
Load Range VIN
VOUT [V]
Regulated
384V ± 1%
380‐388
Semi‐regulated
ETSI EN 300 132‐3‐1 EMERGE >3ms
380V ‐8% +3% 350‐390
380V nom
260‐400
12V Backplane 12V ± 2% 11.75‐12.25
HDD 12V ± 4% 11.5‐12.5 BC K=1/32
BC K=1/8 & BU regulator
BC K=1/32 & BO equalizer
VRMs 12V ± 35% 8‐16
380V to 48V power components matrix Power distribution
48V Loads
Source
Load Range VIN
VOUT [V]
Regulated
384V ± 1%
380‐388
48V Backplane 48V ± 2% 47‐49
ETSI 48V 48V nom 36‐60 BC K=1/8
BC K=1/8 & BO equalizer Semi‐regulated
380V ‐8% +3% 350‐390
BC K=1/8 & BB regulator ETSI EN 300 132‐3‐1 EMERGE >3ms
380V nom
260‐400
BC K=1/8 & BO equalizer
FPA 45V nom 32‐60
Adapter power architecture, peak efficiency and density vs. Distribution Ratio (DR) Power component density (components only) [W/inch3 – (W/cm3)]
Power conversion peak efficiency
2000 (122)
98% Non‐equalized output 97%
1200 (73)
96% Equalized output 95%
Regulated output
94%
400 (25) Equalizer
Bus Conv.
Bus Conv.
Bus Conv.
Equalizer
+
Power components
Regulator
Bus Conv.
+
+
OR Regulator
0.8
3
5
ܸಾಲ െ ܸಾಿ ܸಿೀಾ ܴܦൌ ܸௗಾಲ െ ܸௗಾಿ ܸௗಿೀಾ
Safety and Operators protections The SAC converter galvanically isolates the 400V DC and the low voltage distribution systems
Isolated, floating supply, 200V max with respect to hearth. Mid‐point resistive grounding early‐detection system for isolation faults.
Safely sustains up to 500V operating input to output voltage differential. Low voltage secondary in UL/CSA 60950 qualified SELV range.
Harmonics • AC distribution systems are affected by higher order harmonics generated by the interaction of AC‐DC converters. – the impact of high THD on AC distribution systems can affect up to 59% of the installed wiring capacity, leading to significant higher operating costs or even hazards.
• Bulk power systems and DC‐DC converters generate harmonics that typically start at the switching frequency of the considered converter, therefore a much higher frequency than AC‐DC converters. – Passive filtering for this type of spectrum is usually effective, small and avoids low frequency beats that may result from the interaction of asynchronous DC‐DC converters. Moreover, filter size allows effective integration within the adapter enclosure.
Conclusions • • • •
400V DC distribution systems offer quantifiable advantages not only for new telecom and/or datacenter facilities, but also for upgrades of existing ones. Power component‐based architectures for power adapters have been discussed and analyzed. The proposed locations leverage the space available within equipment racks or within racks’ rows, making maximum use of available space and enabling maximum racks density as far as equipment loads. Best location of power adapter for use with legacy loads depends on user preference based on the following criteria : – – – – –
•
Safety Availability Efficiency Ease of harmonics content elimination Cabling size
For high density loads, the best system architecture from efficiency , reliability and space savings standpoint is a direct 380VDC connection to the motherboard with on‐ board 380VDC‐48VDC bus converter and direct 48V to processor/memory factorized power system.