PreCONNECT® PURE: Reliable planning of data center cabling
PreCONNECT® PURE is a milestone in the development of high-end IT cabling for data centers. It eliminates two uncertainty factors that are critical to overall performance in day-to-day operations:
PreCONNECT ® PURE
Uncertainty factor: contamination
§ § Integration of optical contacts in the LC-Duplex interfaces: ruling out contamination during installation
By their very nature, the optical contacts integrated in PURE interfaces make it impossible for contamination or damage to occur during installation. The LC-Duplex interface is sealed at the factory. You just snap it into the back of the front panel.
Your advantages at a glance
§ § Guaranteed parameters for unused channels until they are actually used § § Factory-sealed to prevent improper opening and handling
§ § Visual quality of ferrule end faces significantly better than IEC 61300-3-35 § § Quick, tool-free mounting with simple snap-in on the back of the panel § § Complete system consisting of trunk cables, patch cables, SMAP-G2 panels and racks
Uncertainty factor: loss budget PURE connectors have an extremely low, guaranteed insertion loss – not just in each-to-each tests, but in real-world applications. This gives you certainty in the planning of transmission paths and allows you to implement more connections per channel.
The PURE effect Twice as many connections and 15 meters more channel length *
2
* In relation to 1.0 dB Insertion loss, a channel length of 150 m and a loss budget of 1.54 dB according to original Fibre Channel 16 Gbit/s OM4 specification.
§§ Insertion loss and return loss exceeding IEC 61755-5 Ed. 1.0 CD Grade Cm (Multimode) §§ Guaranteed maximum insertion loss of 0.4 dB (application limit, LC Multimode 50μm) § § Mean insertion loss = 0.15 dB (LC Multimode 50μm)
§ § Multimode and Singlemode
PreCONNECT® PURE is the first infrastructure cabling system based on OM4 being awarded a ”6 connector channel certification” for 40/100GBE and 16 GFC by GHMT (test report no. P3568a-14-D).
PreCONNECT® PURE will help to keep your data center running smoothly over the long term. But that’s not all. Read the following pages to learn about details and additional features.
Rosenberger-OSI GmbH & Co. OHG | www.rosenberger.com/osi
3
Seal
Dust cap with nipple
Completely redesigned interface
PURE Innovation No more contamination, no more uncertainty about attenuation.
4
Shutter
Studies have shown that about 50 % of all network errors are caused by cabling problems. Of these, most involve contamination of fiber-optic cable connections, improper patching or even damage arising from patching. PreCONNECT ® PURE eliminates these causes from the start. §§ PURE trunk cables have preassembled PURE interfaces instead of conventional connectors §§ The optical contacts integrated in the interfaces are factory-tested for perfect optical quality and absolute cleanliness before the seal is applied §§ The connection does not have to be opened during installation; thanks to the new interface design, the complete unit can be snapped into the panel from behind §§ On the patch side the LC-Duplex interfaces are sealed with protective caps, preventing contamination even if the channels are not used for a long time. The warranty permits opening of seals and patching only by certified personnel (see also page 14/15, Services) In this way PURE not only ensures maximum data transmission over long distances, it saves time and costs by at least 15 %, because on-site acceptance tests and cleaning are unnecessary.
Insertion loss “Application limit” versus “Production limit” „Anwendungs-Grenzwert“ vs. „Produktions-Grenzwert“ An increase in transmission speed always means a reduction in the maximum permissible attenuation of multimode links. In high-end applications it is therefore essential to keep the insertion loss of fiber-optic connections as low as possible. To impress customers, cable manufacturers often quote the so-called production limit value, which is measured using reference couplers and connectors. But this value is of no relevance to actual practice, in which standard components with varying specifications are involved. For this reason Rosenberger OSI always quotes the so-called application limit value for PURE. This value applies to any combination of connectors, and it’s guaranteed. The value is 0.4 dB*, which is 0.2 dB better than the highest performance class specified in IEC 61755-5 Ed. 1.0 CD Grade Cm (see also page 6). The mean* insertion loss (IL) measured for PURE components is well below this, at 0.15 dB (see “Overall process capability” chart). This gives you a big safety margin from the application limit value. In actual practice even better values are achieved.
Overall process capability PURE connectors Application limit Frequency of measurement results
Clean connections: For absolute certainty
Maximum insertion loss
Rosenberger-OSI GmbH & Co. OHG | www.rosenberger.com/osi
5
Installation: tool-free and easy
Overall performance:
PURE trunk cables are preassembled with LC-Duplex interfaces at both ends and sealed. Thanks to the newly designed interface with an innovative locking mechanism, each channel can easily be snapped from behind into the part front plates of the SMAP-G2 panels.
IEC 61755-5 Ed. 1.0 CD Grade Cm versus PURE
Comparison of maximum channel lengths*
The performance parameters for fiber-optic connections are set forth in the IEC 61753 and 61755 standards, which define grades. The highest performance class for multimode fibers is IEC 61755-5 Ed. 1.0 CD Grade Cm, which specifies a maximum insertion loss (IL) of 0.6 dB for 97 % of the connections and a minimum return loss (RL) of 20 dB. PreCONNECT ® PURE significantly exceeds both of these values:
150 m for IEC 61755-5 Ed. 1.0 CD Grade Cm
165 m for PreCONNECT ® PURE
PURE versus IEC 61755-5 Ed. 1.0 CD Grade Cm PURE Quality 50μm MM
IEC 61755-5 Ed. 1.0 CD Grade Cm
IL
100 % max. 0.4 dB Mean 0.15 dB
97 % max. 0.6 dB Mean 0.35 dB
RL
min. 40 dB
min. 20 dB
Application limit
Comparison of possible connections*
(Grades Am & Bm are not covered by standards, RL Grade 2m)
With maximum IL (0.4 and 0.6 dB respectively)
Thus, for any given loss budget, PreCONNECT ® PURE permits up to twice as many connections per channel as with IEC-specified cabling. In addition, the high quality of Rosenberger OSI OM4 fibers allows elongated channel lengths (see illustration at right).
With mean IL (0.15 and 0.35 dB respectively)
Cladding Core
PURE end faces without scratches and contamination 2 connections for IEC 61755-5 Ed. 1.0 CD Grade Cm
®
6
Every connection between two optical fibers can impede the propagation of light in the channel. To minimize insertion loss it is therefore essential for the fiber ends to meet exactly and for the end faces to have as few imperfections (scratches and defects) as possible. By exercising the utmost care in manufacturing we achieve visual quality results for our PURE interfaces that are well above the requirements of IEC 61300-3-35.
1 connection for IEC 61755-5 Ed. 1.0 CD Grade Cm
2 connections for PreCONNECT ® PURE
6 connections for PreCONNECT PURE
Visual quality of the fiber surfaces: in a class of its own
*Example: Fibre Channel 16 Gbit/s OM4
Fiber end faces with scratches and moderate contamination
Visual quality of end faces Zone
Specification
Scratches
Defects
A: core 0 - 65μm
PURE MM
No scratches > 2μm
No defects permitted
IEC 61300-3-35 MM
No scratches > 3μm
Up to 4 defects < 5μm
B: cladding 65 - 115μm
PURE MM
No scratches > 3μm
Up to 5 defects < 3μm
IEC 61300-3-35 MM
No scratches > 5μm
Up to 5 defects < 5μm
Rosenberger-OSI GmbH & Co. OHG | www.rosenberger.com/osi
7
PreCONNECT ® PURE Trunk
Cable types
Technical data | PreCONNECT® Fiber Trunks
Application
Cable design
Stranded mini loose tubes
Infrastructure cabling of data centers
§ § With all standard loose tube cables up to 144 fibers available § § Cable data sheets on request
Numbers of fibers, max.
36
48
72
96
144
Leg length stepped (cm) approx.
65-90
65-98
65-90
95-110
95-125
Properties
Fiber types
Outer (mm)
8.0
8.0
8.4
9.4
11.4
§§ Both sides factory assembled § § Standard light propagation “channelwise crossed” § § Cable length up to 2,000 m, longer on request
§ § OM4 and SM § § Fiber data sheets on request
Max. tensile strength (N)
3000
3000
3000
3000
3000
Max. crush resistance (N/dm)
1000
1000
1000
1000
1000
Min. blending radius (mm) static dynamic
80 120
80 120
84 126
94 141
114 171
Length definition
Optional
Fire load (MJ/m)
0.69
0.69
0.73
0.92
1.43
§ § Order length: length between the connectors at the longest legs at both sides (not between the cable dividers) § § Length tolerances: < 10 m = +/- 50 cm 11 m to 30 m = +/- 100 cm 31 m to 100 m = +/- 150 cm > 100 m = +/- 2 % § § Leg lengths on both sides stepped acc. to table on page 9
§ § Cable with increased tensile strength and crush resistance § § Cable with special armoring
Interface LC-Duplex with shutters
Part numbers Number of fibers/Interfaces
SM APC 8° 9/125 G.657.A1
OM4 50/125 BI
Delivery form
36
LC-Duplex
024P0141 G657 A
024P0101 OM4
§ § Factory measured IL and RL, including measurement report §§ Product ID labels behind both cable dividers § § Dependent on the length as cable ring, on cardboard or wooden drum
48
LC-Duplex
024P0126 G657 A
024P0103 OM4
72
LC-Duplex
024P0142 G657 A
024P0105 OM4
96
LC-Duplex
024P0128 G657 A
024P0107 OM4
144
LC-Duplex
024P0129 G657 A
024P0109 OM4
Other interfaces, fiber types and numbers of fibers on request.
PURE products A perfect product line
8
Rosenberger-OSI GmbH & Co. OHG | www.rosenberger.com/osi
9
Applications
Cable types
Patchcords appropriate for use in data centers
§§ Different FRNC-LSZH cables §§ Cable data sheets on request
Properties
Cable type round I-V(ZN)H 2.8 mm FRNC-LSZH
§§ Optimized kink and crush resistance with regards to application requirements § § Operating temperature range -10 °C to +60 °C, patchcords for other operating temperature ranges on request §§ Standard light propagation: Full-Duplex cables: Duplex connectors at both sides acc. to ISO/IEC 11801 and EN 50173 = “crossed”
Fiber types §§ OM4 und SM, bend-insensitive §§ Fiber data sheets on request
<1m = - 50 mm 2 m to 3 m = - 100 mm 4 m to 25 m = - 200 mm > 25 m =-1%
Part numbers Connector
Length
Connectors
SM APC 8° 9/125 G.657.A1
OM4 50/125 BI
LC-Compact » LC-Compact
Variabel
087P6609 G657 A
087P6601 OM4
LC-Compact
Other plug connection, cable- and fiber data on request.
Delivery form §§ Factory measured IL and RL, measurement report on request §§ Serial number label at both cable ends for use in network documentation §§ Product ID label on the package §§ Each packed in a foil bag, cables longer than 100 m on cardboard drum
Length tolerances §§ §§ §§ §§
Duplex patchcord
Duplex patchcord Cable type double-jacket-round I-V(ZN)H(ZN) 2.8/5.0 mm FRNC-LSZH
Part numbers Connector
Length
SM APC 8° 9/125 G.657.A1
OM4 50/125 BI
LC-Compact » LC-Compact
Variabel
087P6612 G657 A
087P6613 OM4
Other plug connection, cable- and fiber data on request.
PreCONNECT® PURE Patchcords
Duplex patchcord Cable type round I-V(ZN)H 2.0 mm FRNC-LSZH Part numbers Connector
Length
SM APC 8° 9/125 G.657.A1
OM4 50/125 BI
LC-Compact » LC-Compact
Variabel
087P6622 G657 A
087P6623 OM4
Other plug connection, cable- and fiber data on request.
10
Rosenberger-OSI GmbH & Co. OHG | www.rosenberger.com/osi
11
19“ SMAP-G2 PURE distribution panel with 1/4 part front plates
Applications §§ For installation in 19“ racks §§ To interconnect e.g. PreCONNECT® PURE Trunks with patchcords in data centers
Properties §§ Maximum modularity and flexibility due to application-specific combinable 1/2 and 1/4 part front plates §§ Very robust panel at low weight §§ Suitable to accept all cables assembled by Rosenberger OSI §§ 1 to 5 HU assembled with 1 HU 1/2 or 1/4 part front plates (PFP) depending on the number of fibers and coupler type
§§ Matrix numbering of the PFPs: channels within PFPs are labeled 1 to n, PFPs within the panel are labeled 1 to n with clips
Material and color: §§ Front: steel, powder coated RAL 9005 (black) §§ Body: aluminum §§ Back planes: steel, powder coated RAL 9005 (black)
§ § High density data center infrastructures §§ To build passive data center patch locations with highest density
Delivery form
Properties
§§ Completely factory assembled without couplers §§ Coupler interfaces on trunk
§ § Innovative barrier-free cable management system § § No rack pillars that interfere with cable routing due to cable managers being integrated into the pillars §§ Covers of the cable managers are hinged in both directions and completely removable § § Several perforated feedthroughs in the side and rear walls of the cable managers for easy cable routing in the vertical and horizontal direction §§ Professional routing of large cable volumes from patchfields and storage of cable overlength inside the vertical cable managers §§ Particularly suitable for FO cables due to cable retainers (L-Fingers) and Finger-Slots § § The rounded L-Fingers ensure high bending and kinking protection for the cables even under tensile load § § L-Fingers do not have sharp edges and are very robust and break resistant
Part numbers | Single components 19“ SMAP-G2 PURE distribution panel to accept SMAP part front plates, RAL 9005 (black) 1 HU
171P0001
2 HU
172P0001
3 HU
173P0001
5 HU
175P0001
SMAP-G2 PURE 1/4 part front plate, RAL 9005 (black)
19” SMAP-G2 PURE distribution panel
PURE Patch Location Rack
Blind-part front plate
170P0001
12 Channels/24 Fibers for interface-type LC-Duplex
170P0130
SMAP-G2 PURE 1/2 part front plate, RAL 9005 (black) Blind-part front plate
170P0002
24 Channels/48 Fibers for interface-type LC-Duplex
170P0170
Applications
§ § Cables can neither be squeezed nor kinked for there is enough space within the finger-slots § § During work with open or removed covers the L-Fingers hold the cables back in the finger-slots §§ Dimensions (h x d x w): 213 (46 HU) x 90 x 90 cm
Material and color Steel, powder coated, RAL 9005 (black)
Optional 19“ intermediate rack to build rack rows with an uneven number of racks on request
Delivery form § § Factory mounted on a pallet (total height with pallet and packaging = 230 cm) § § Incl. adjustable pedestals for on-site mounting
Part numbers RAL 9005 (black)
142P3000
Other interfaces and numbers of fibers on request.
12
Rosenberger-OSI GmbH & Co. OHG | www.rosenberger.com/osi
13
PURE interfaces are guaranteed to be absolutely clean all the way to completion of trunk cable installation. But what happens when they are to be connected? The moment the seal is removed and the protective caps are taken off for connecting a patch cable, the end faces of the fibers can be soiled or damaged if the connector is improperly handled. For this reason our warranty for insertion loss in PURE connectors is valid only if patching is carried out by Rosenberger OSI Services or certified service providers.
We ensure that your project stays on track in each phase of implementation: Cabling Design § § Advisory services § § Conception and planning § § Training and workshops
Cabling Installation §§ Installation and mounting §§ Project management and site supervision §§ Quality assurance
The advantages for you § § You ensure consistent PURE transmission quality over the long term § § You minimize technical downtimes by relying on experienced specialists § § You relieve your technical staff of work unrelated to your core business §§ You obtain quick, expert help in an emergency § § You can plan with confidence on the basis of fixed, foreseeable costs
Maintaining PURE quality With Rosenberger OSI Services
14
Status April 2017 – Technical modifications and errors excepted. Similar images.
Three levels to ensure maximum performance
Each data center is different. The requirements relating to performance, security and availability of expert knowledge can vary widely. For this reason Rosenberger OSI gives you three different service levels to choose from. We have developed them for you based on more than 25 years of experience in the operation of data centers.
Managed Cabling § § Basic services for data center operation § § Guaranteeing of resources § § Additional services as needed
Basic §§ For midsize companies with small server rooms §§ The most important standard services for basic operation §§ Provision of a technical hotline §§ Implementation via individual contracts
The Premium Plus level gives you a choice of eleven service modules in four service areas. From channel qualification to considerably extended warranty periods, this is the ultimate in professional cabling management for data centers. With PreCONNECT® PURE and Rosenberger OSI Services you can be sure of getting maximum cabling performance over the long term – and finally you can ensure a reliable planning of data center cabling.
Premium §§ For high-performance data centers §§ Including on-site availability of experts and technicians §§ Extended warranty for installed Rosenberger OSI products §§ Implementation via fixed monthly payments
Premium PLUS §§ For high-performance data centers with maximum availability §§ Custom warranty and service §§ Customer-specific activities §§ Implementation via fixed monthly payments